The information contained in this document is
subject to change without notice. Precision Digital
makes no representations or warranties with
respect to the contents hereof and specifically
disclaims any implied warranties of
merchantability or fitness for a particular purpose.
•Read complete instructions prior to installation and
operation of the controller.
•Risk of electric shock or personal injury.
•This product is not recommended for life support
applications or applications where malfunctioning
could result in personal injury or property loss.
Anyone using this product for such applications
does so at his/her own risk. Precision Digital
Corporation shall not be held liable for damages
resulting from such improper use.
WARNING
Limited Warranty
Precision Digital Corporation warrants this product
against defects in material or workmanship for the
specified period under “Specifications” from the
date of shipment from the factory. Precision
Digital’s liability under this limited warranty shall not
exceed the purchase value, repair, or replacement
of the defective unit.
FREE ConsoliDator+
Configuration Software
The easiest and quickest way to program your
ConsoliDator+ multivariable controller is to use the
FREE ConsoliDator+ configuration software.
The ConsoliDator+ configuration software is intuitive, and
most customers can get their controller programmed as
they like without even looking in the manual.
Once your controller is programmed the way you want it,
you can wire it up for your application per the instructions
in this manual and install it. If you find that you need to
adjust the programming after the controller is installed,
you can use the front panel soft keys and the instructions
in this manual to do so.
Registered Trademarks
All trademarks mentioned in this document are
the property of their respective owners.
Figure 1. Front Panel Mount Dimensions ................................................................................................................ 16
Figure 18. AC and DC Internal Inductive Loads Protection
Figure 19. Low Voltage DC Loads Protection .......................................................................................................... 24
Figure 20. Serial Connections ................................................................................................................................... 24
The ConsoliDator+ is a multi-channel controller that is both
easy to use and satisfies a wide variety of process display,
alarm, and control applications. It accepts 4-20 mA inputs,
flow meter pulse inputs, digital inputs, and Modbus RTU
inputs and displays them both in numeric and bargraph
format on a large, 5.7" color display. It can be equipped with
multiple relays with user-definable actions, 4-20 mA outputs,
digital outputs, Modbus RTU, and Ethernet Modbus TCP/IP
protocol communication capabilities. Additionally, the
controller is equipped with up to 32 timers that can be used
to control many processes or events.
The ConsoliDator+ takes full advantage of its color display
by allowing the user to customize screen colors for
bargraphs, alarm conditions, and input channels.
All this functionality is easily programmed using free
software or via the front panel pushbuttons. Choose the
model that best suits your application, from monitoring
only to fully loaded controllers with an extensive
combination of inputs, outputs and communication
protocols. The standard product offering is listed in the
ordering guide and other models are available for special
order.
Ordering Information
General Purpose Panel-Mount Models
Instruction Manual
G = General Purpose
P = Panel-Mount
AI = Analog Input
PI = Pulse Input
PDA2909 NEMA 4 Steel Enclosure
for One ConsoliDator+
The PDA2909 steel NEMA 4 enclosure provides a
convenient way to mount the PD9000 ConsoliDator+
to walls and other vertical structures. This enclosure
comes pre-cut with one cutout to mount the PD9000
in. The ConsoliDator+ is mounted in the door of the
enclosure thus allowing for programming and
operation of the device. No additional mounting
hardware other than screws to mount to the wall is
needed. The door is hinged and secured with latches.
Note: The enclosure and ConsoliDator+ are ordered
and packaged separately
.
Instruction Manual
Features
● House One ConsoliDator+ Multi-Variable Controller
● 14-Gauge Steel
● Comes Pre-Cut with One Cutout
● NEMA 4, 12 and 13
● Cover Secured with Screwed Latches
● Hinged Door
● ConsoliDator+ Mounted in Cover
● Mounting Holes Integral to Enclosure
● UL Listed, CSA Certified
Wall Mounting Dimensions:
The PDA2909 enclosure includes integral mounting
flanges at the top and bottom of the enclosure that can
be used to mount the enclosures to a wall.
Multi-Source: Two or more inputs
Interval: Enter time interval and On Time
Day & Time: Select day of the week & time
Alarm OR: Any active input alarm triggers
Alarm AND: All alarms must be active to
Automatic and manual
Manual only (Latching)
Manual with Ack only after alarm is cleared
2. Enable internal buzzer
Enable/disable in System – General menu.
activate an external horn when alarm
the OR alarm
up to change color on alarm
www.GlobalTestSupply.com
User Selectable
Based on
Wiring
Power Supply
10
or from a function key.
Manual control mode is not saved on
outputs in manual control.
Note: If it
maintain the condition through power cycl
10 years.
AC: 80-264 VAC, 47 to 63 Hz, 60 W max
DC: 113-370 VDC, 60 W max (L, N)
Two-terminal connector (G, 24V)
24 VDC can be used as backup power in
case of AC power failure.
Note: DC supply must be 24 V or less;
resettable fuse
AC: 1.25 A max
DC: 3.7 A max
Page 11
PD9000 ConsoliDator+ Multivariable Controller
External
Recommended external fuse slow-blow
24 VDC: 4 A
Isolation &
1500 V
output, analog
Environmental
Operating temperature range: -40 to 60°C
increase display refresh setting.
Internal Fan
Automatic temperature-controlled fan turns
temperature rises to 60°C.
Internal Heater
Automatic temperature-controlled heater
delivers its maximum power.
Connections
Removable screw terminal blocks
cable included.
Tightening
Screw terminal connectors:
Digital I/O terminals: 2.5 lb-in (0.28 Nm)
Enclosure
Enclosure Body: Thermoplastic Polyester,
Front Panel Keys: Silicone rubber
Mounting
Panel-mounting frame and twelve screws
Overall
10.85" x 10.85" x 4.87"
(H x W x D)
Weight
Ex: PD9000-XY-4PI-8AI-10AO-10RY
7.4 lb (3.4 kg) approx.
Warranty
Number of
Up to 32 totalizers
15 digits with comma separator
Totalizer Inputs
Calculates total based on selected rate
power is lost.
Maximum Total
18 digits
999,999,999,999,999,999
Rate Channel
Input
4-20 mA input, Pulse input, Modbus input
Rate & Total
Decimal Point
Independent and user selectable from 0 to
15 places
Totalizer Reset
Via front panel keys or digital inputs
Non-Resettable
Total may be setup to be non-resettable to
changed in the Setup Totals menu.
Total Units
Input: Rate channel
(e.g. Gallons to MGal: Factor = 0.000001)
Pulse Input
K-Factor = pulses/units of measure
Decimals: 0 to 15
Count
Down
Total may be setup to count down from a
predetermined value entered by the user
Preset
Enter the preset value to count up or down
; to
reset to zero uncheck the Preset box.
Roll-Over
Enter the value for total to roll-over to 0
Total goes to 0 after 1 million
Negative Total
Allow total value to count below 0 for
bi-directional flow based on rate channel
Total Bargraph
Bargraph may be scaled to represent the
expected maximum total
Function Keys
Screen Setup: Assign F1-F4 to Reset
Remove From total
Date
Format
Month, day, year (e.g. July 16, 2020)
Time
Format
24 hour; 00: Midnight
hh:mm:ss
Battery
3 V, P/N: CR2032 included
Display
Date & Time
Displayed on the top line of Setup and
View menus, including day of the week.
Screens
Date & Time can be added to any screen.
Channels
Date & Time can be the input to a channel.
Display Format: yyyy/mm/dd hh:mm:ss
Instruction Manual
Fuse
Grounding
120 VAC: 2.0 A
240 VAC: 1.0 A
Analog inputs/outputs-to-power line
500 V
Analog input-to-input, input-tooutput-to-output
All analog inputs and analog outputs are
isolated from each other.
Note: DC Power is not isolated. DC- is
connected to Earth Ground. Digital I/O,
USB, and Ethernet are grounded.
(-40 to 140°F)
Storage temperature range:
-40 to 60°C (-40 to 140°F)
Relative humidity: 0 to 90% noncondensing
*All functions operate down to
-40°C (-40°F.) LCD response is slower,
on if the inside temperature reaches 50°C
and increases the speed as the
located behind the LCD turns on at 0°C,
delivering the minimum power. If the
temperature drops below -10°C, the heater
Totalizer
Totalizers
Total
Conversion
K-Factor
channel, pulse input, digital input, or
triggered event for non-rate channels.
Total is stored in non-volatile memory if
prevent unintentional reset. This can be
Total units may be different than rate units.
Use the custom units to convert to any unit
Calculates total directly from pulse input,
digital input, or Modbus input.
Create rate channel by entering K-Fac
units and time base in sec, min, hr, or day.
tor,
Inputs/Outputs: 12 to 24 AWG wire
Digital I/O: 16 to 30 AWG
RS-485: 12 to 24 AWG wire
RJ45 Ethernet connection.
USB ports: Micro-USB (Device),
auto-resettable fuse, 30 VDC max.
The fuse resets automatically after the
125 Ω typical, including auto-resettable
existing HART communications; it
displays the 4-20 mA primary variable
and it allows the HART communications
to pass through without interruption. The
controller is not affected if a HART
communicator is connected to the loop.
The controller does not display
500 V: Input-to-input, input-to-output
All analog inputs and analog outputs are
100 dB at 50/60 Hz
www.GlobalTestSupply.com
Modbus Inputs
Number of
Timeout
Action
13
199 Modbus RTU
Modbus input may be used as the input
for creating channels and totals, the same
Signed/Unsigned: 16 (Short), 32 (Long),
64 (Long-Long)
Float 32
Float 64 (Double)
break and how long to wait for new data
data is written to the input register (e.g.
Page 14
PD9000 ConsoliDator+ Multivariable Controller
Digital
inputs
Digital Input
Normally open switch: External excitation not
Logic level: 0 to 30 V
Assignment &
Active Low or Active High
channels, totals, and alarms.
Digital
4 Outputs
Max frequency: 5 Hz
Digital Output
channel, alarm, horn, always on, or always off
Protection
Number of Relays
(4) pulse inputs, no other I/O
SPDT (Form C)
Minimum load: 100 mA @ 5 VDC
1500 VAC, 50/60 Hz for 1 min between
coil and contacts
TVS diodes & snubbers on all contacts.
(Order: PDX6901)
Any relay may be assigned to any
programmed independently.
High & Low Alarm: Defined by set and
reset points in the Alarm menu
High or Low Alarm: Assign relay to any
Note: Automatic reset only for channel
Multi-Source High or Low Alarm:
indicate common high or low condition.
Pulse Action: Set any relay for pulsing
Programmable pulse width (on/off time)
and on/off delay.
channel setup for Sampler function with
sampling time.
Pump Alternation: Any relay may be
be setup.
Front panel Ack key or digital input
Acknowledge all or any alarm.
off the relay (non-fail-safe mode).
Programmable on/off delays,
Independent for each relay.
When power is applied to the
the input to the controller.
The relay coil is energized when the
the alarm condition exists.
Instruction Manual
Digital Inputs & Outputs
Inputs
Types
Operation
Outputs
5 Inputs, non-isolated, 30 VDC max
Standard feature on all ConsoliDator+ models
Low: 0 to 1.2 V
High: 2.8 to 30.0 V
Internal pull-up: 5 kΩ to 5 V
Max pulse frequency: 1 kHz @ 5 Vp-p
+5 V terminal: Internal pull-up 100 Ω
Note: Pulse inputs may be used as digital
required (Current: 1 mA)
Open collector: 4.1 V open circuit voltage
Functions: Remote front panel button, total
functions, timer control, alarm functions,
screen navigation, horn functions, reset relay
information.
Digital inputs can be used as input source for
Standard feature on all ConsoliDator+ models
Low: 0 V (no load), 1.5 V max @ 10 mA sink
(External pull-up)
High: 5.0 V (no load), 3.5 V @ 10 mA load
Maximum current: 30 mA
Output impedance: 100 Ω
Output protection: 150 mA auto-resettable
fuse
Relays
Rating
Isolation
Deadband
Electrical Noise
Suppression
Assignment &
Operation
(5) Relays/card
(30) Relays max with (4) analog or
Resistive load: Rated 10 A @
120/240 VAC or 8 A @ 30 VDC
Inductive load: NO contacts: 1/3 HP,
120 VAC; 30,000 cycles
NC contacts: 1/8 HP, 120 VAC;
50,000 cycles
alarm, channel, total, timer, digital
input, Modbus input, pump alternation,
horn, always on, or always off.
Multiple relays may be assigned to the
same alarm or channel. All relays are
alarm or channel for on/off relay control
Assignment
Input / Output
Digital outputs require logic units as the input
Input sources: Digital input, Modbus input,
±36 V, non-isolated
Acknowledge
Alarm
Relay
Time Delay
Auto
Initialization
Fail-Safe
Operation
Assign relay to multi-source alarm to
on/off timed relay control.
Sampling: Relay must be assigned to
user-defined total increment and
setup to alternate with any relay in the
group. Multiple alternation groups may
acknowledges alarms; relays
associated with acknowledged alarm
are turned off.
Assign any relay to be driven by any
alarm; acknowledging the alarm turns
0.0 to 999.9 sec
controller, relays will reflect the state of
process variable is within safe limits
and the relay coil is de-energized when
•Read complete instructions prior to installation
and operation of the controller.
• Risk of electric shock.
• Hazardous voltages exist within enclosure.
• Installation and service should be performed only
by trained service personnel.
Installation
Unpacking
Remove the instrument from its box. Inspect the
packaging and contents for damage. Report any
damages to the carrier. If any part is missing or
the controller malfunctions, please contact your
supplier or the factory for assistance.
Panel Mounting
•Prepare panel cutout per the dimensions
provided
• Locate the panel mounting bracket and screws
• Inspect the controller to assure the gasket is
securely in place
•Insert controller in the panel cutout, the latches
on the top and bottom should hold it in place
•Insert the panel mounting bracket from the back
of the panel, observe the orientation of the piece
marked TOP
10. After the installation is complete, the following
message is displayed. Click Close to finish. A
ConsoliDator+ icon will be placed on your
desktop.
ConsoliDator+ Software
Instruction Manual
1. Connect one end of the provided USB cable to
the controller and the other end to the
computer.
2. Double-click on the ConsoliDator icon
3. The application will start displaying the System
menu
You are now ready to start using the software to
configure your ConsoliDator+ controller.
The easiest and quickest way to program your
ConsoliDator+ is to use the FREE ConsoliDator+
configuration software available on the included CD
The ConsoliDator+ configuration software is intuitive,
and most customers can get their controller
programmed as they like without even looking in the
manual.
•Only one controller may be connected at a time.
Attaching multiple controllers will cause a conflict
with the controller software.
.
4. Click on Read, at the bottom of the screen, to
read the configuration of the connected
controller. After a read the channels settings
overview is displayed.
5. You can now begin to configure the
ConsoliDator+ for your application, either by
editing the existing settings or by starting fresh
creating a new configuration.
6. Click on Configuration to save files, open
existing files, or to create a new configuration
even without a controller connected.
mA- mA+ 24V m A- m A+ 24VmA- mA+ 24V m A- m A+ 24V
mA- mA+ 24V mA- m A+ 24Vm A- m A+ 24V mA- mA+ 24V
S- S+ S- S+
-
+
Gnd
N
L
G
+
1
2
3
4
5
1
2
3
4
G
D+
D-
G
PULSE INPUTS
4-20 mA INPUTS
4-20 mA INPUTS
Instruction Manual
Connections
The back panel is labeled with the I/O boards that were installed at the factory. The removable connectors are
labeled with the connection signal for each terminal. The following diagram shows what the back of the model
PD9000-GP-4PI-8AI-10AO-10RY looks like. This model accepts (4) pulse and (8) analog inputs and has
(10) 4-20 mA outputs and (10) relays. (5) digital inputs, (4) digital outputs, RS-485 serial capability and USB
connections are standard on all ConsoliDator+ models. Ethernet is an option.
If all Input / Output slots are used exclusively for one function, the ConsoliDator+ can accept up to (28) isolated
4-20 mA inputs, (28) pulse inputs, (25) isolated 4-20 mA outputs, and (25) relays. If used as a Modbus slave only:
(35) 4-20 mA outputs, (30) relays.
All units can be powered from AC or DC; both power connections can be used at the same time. The DC power
supply can serve as backup power if the voltage is 24 V or less, otherwise the controller will run on DC power.
1. Each 4-20 mA input has its own isolated 24 VDC power supply to
2. Each 4-20 mA output has its own isolated 24 VDC power supply to
3. Each relay is Form C and rated at 10 A.
4. Input / output connections are made to removable screw connectors.
5. Every ConsoliDator+ has five digital inputs (additional digital inputs can
6. Every ConsoliDator+ has four digital outputs.
7. Every ConsoliDator+ has RS-485 with Modbus.
8. All ConsoliDator+ models can be powered from either AC or DC
9. Ethernet with Modbus TCP is an option.
10. Micro USB is used for programming the ConsoliDator+.
power the transmitter.
power the output loop.
be obtained by using the Pulse Inputs).
Power.
Figure 5. Connection Terminals for a PD9000-GP-4PI-8AI-10AO-10RY
www.GlobalTestSupply.com
•Use copper wire with 60°C or 60/75°C insulation for
all line voltage connections. Observe all safety
regulations. Electrical wiring should be performed in
accordance with all applicable national, state, and
local codes to prevent damage to the controller and
ensure personnel safety.
20
Page 21
PD9000 ConsoliDator+ Multivariable Controller
mA- mA+ 24V
-
Pwr+
3-Wire 4-20 mA
Transmitter
Analog Input
mA- mA+ 24V
-
2-Wire 4-20 mA
Transmitter
Analog Input
Signal
Pwr+
mA- mA+ 24V
-+-+
External
Power
Supply
2-Wire
4-20 mA
Transmitter
Analog Input
mA- mA+ 24V
-+
2-Wire 4-20 mA
Self-Powered
Transmitter
Analog Input
mA- mA+ 24V
3-Wire 4-20 mA
Transmitter
Analog Input
+
External
Power Supply
Signal +
Power +
Signal -
-
Power Connections
Power connections are made to one of the power
terminal connectors. All units are capable of being
powered either by AC or by DC for the ranges
specified.
90-264 VAC Power
•Use three-terminal power connector as
shown in Figure 6.
•Unit is protected internally with 1.25 A auto-
resettable fuse. 2 A max, slow blow,
250 V min, UL Recognized external fuse
recommended.
24 VDC Power ± 10%
•Use two-terminal power connector as shown
in Figure 6.
•Unit is protected internally with 3.7 A auto-
resettable fuse. 4 A max, slow blow,
50 V min, UL Recognized external fuse
recommended.
Instruction Manual
Isolated Input Signal Connections
Isolated input signal connections are made to
removable screw terminal connectors, which are
labeled individually on the back panel of the
controller. The back panel shows the type of input
card installed in each slot (The top slot is #1 and the
bottom is #7). Individual inputs are referenced as PI-1
to PI-4 for pulse inputs and AI-1 to AI-4, AI-5 to AI-8,
etc for analog inputs.
4-20 mA Analog Input Connections
Analog 4-20 Input connections are made to screw
terminal connectors (two inputs per connector). The
following figures show examples for typical
applications. Each of the 4-20 mA inputs may be
connected in any of the modes shown below.
Figure 6. Power Connections
Note:
The controller may be powered by AC voltage with
the DC power connection used as backup power. The
DC power supply must be 24 V or less to work as
backup; otherwise the controller runs on DC power.
Flow Meter Pulse Inputs are wired to four-terminal
connectors (two inputs per connector). A square
waveform is used in the illustration, but the input is
capable of reading many other types of signals within
the voltage and frequency ranges specified.
Figure 10. Flow Meter Pulse Input Connections
Digital Input Connections
Inputs are wired between terminals 1-5 of the digital
input connector and the G terminal of the 2-position
connector above the digital inputs. Normally open
switch contacts may be used as shown in
The diagram also shows a Digital Input using an NPN
open collector transistor output from a live signal.
Logic LO or switch closure appearing across the
terminals is interpreted as ON. When using an open
collector transistor, a logic HI at the base (marked “B”
Figure 11) will be interpreted as ON. The 2-position
in
connector has a +5 V terminal that may be used to
provide excitation to some sensors requiring more
than the pull-up provided on each digital input
terminal.
Figure 11.
Instruction Manual
Analog Output Connections
The following figures show examples for isolated
4-20 mA transmitter output connections. Terminal
connectors are labeled individually. The analog
outputs are isolated from each other and from the
inputs. They are powered internally to provide an
active 4-20 mA output loop. The outputs may be
powered externally by connecting the positive voltage
to the Ex+ terminal.
Figure 12. Active 4-20 mA Output Powered by
Controller
Figure 13. Passive 4-20 mA Output Powered
by External Supply
Note: Analog inputs and outputs are isolated from each other
Digital Output Connections
The digital outputs may be used to drive digital inputs,
alarm annunciators, or other devices such as solidstate relays that can be driven with low voltage signals.
Figure 14. Digital Outputs Driving 5 V Solid State
Relay
22
Page 23
PD9000 ConsoliDator+ Multivariable Controller
Connections to Power Gas Detector
Some sensors requiring more than 200 mA of
excitation current can be powered by the
ConsoliDator+ by connecting two or more power
supplies in parallel as shown in the following
diagrams.
Relay connections are made to three-terminal connectors
labeled individually. There are five relays per card.
Figure 17. Relay Connections
Switching Inductive Loads
The ConsoliDator+ has internal circuitry to protect the relays
from inductive loads, however, the use of external
suppressors (snubbers) is strongly recommended when
switching inductive loads to prevent disrupting the
microprocessor’s operation. The suppressors also prolong
the life of the relay contacts. Suppression can be obtained
with resistor-capacitor (RC) networks assembled by the user
or purchased as complete assemblies. Refer to the following
circuits for RC network assembly and installation.
Figure 18. AC and DC Internal Inductive Loads
Protection
For addi
follows:
R: 0.5 to 1 Ω for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1.Use capacitors rated for 250 VAC.
2.RC networks may affect load release time of
3.Install the RC network at the instrument's relay
tional external protection choose R and C as
solenoid loads. Check to confirm proper operation.
screw terminals. An RC network may also be
installed across the load. Experiment for best
results.
RC Networks Available from Precision Digital
RC networks are available from Precision Digital and should
be applied to each relay contact switching an inductive load.
Part number: PDX6901.
Serial Communication Connections
The RS-485 port for serial communication (using Modbus
protocol) has three terminals labeled D+, D-, and G. It is
strongly recommended to use three-wire shielded cable and
to always connect the ground terminal to the other
equipment’s ground to avoid differential voltage between the
systems. Distances up to 4000 feet can be reached with
RS-485. Up to 32 Modbus devices may be connected to a
single RS-485 bus.
Figure 20. Serial Connections
Ethernet Option
The Ethernet port is available on the RJ45 connector. This
allows the ConsoliDator+ to connect to a local area network.
The Ethernet port option is fully configured using the
Lantronix DeviceInstaller software, available for download
from the Lantronix’s Website
specifications, page 53 for setup using the ConsoliDator+
software, and page 54 for complete Ethernet Port Setup.
.
See page 15 fo
r
External Keypad Connections
Normally open pushbuttons may be wired to the digital
inputs connector for use when the front panel of the
controller is not accessible. The external keys may be
assigned to replicate the Menu and F1-F4 function keys.
Use diode with a reverse
breakdown voltage two to three
times the circuit voltage and
forward current at least as large
The device displays various screens throughout
programming and operation. Functions are
programmed within their respective menu screens
and in many cases are accompanied by user
prompts.
Soft-Keys and Buttons
The unit is equipped with five buttons located below
the display. The function of each button corresponds
to its soft-key, which appears at the bottom of the
screen. Buttons assume different functions, which
change according to the screen in view.
Screen Navigation
Menu Navigation
Instruction Manual
Key Action
Menu Enter menu
Step into menu/setting
Exit/go back
Next screen/channel/setting
Previous screen/channel/setting
Stop Stop automatic scan
Scan Scan screens automatically
Ack Acknowledge alarms/relays
Reset Reset total/max/min
Setup Enter the Setup menu
Edit Modify selection
Selections are highlighted with green background for
illustration purposes. The keys below are used to
navigate through menus and edit settings. Other
special keys appear throughout the programming
process.
Note:
This is not a touch-screen display; the
pushbuttons must be used to activate the soft-key
There is no need to recalibrate the instrument when first received from the factory.
The device is factory calibrated prior to shipment, for all input types and 4-20 mA outputs. The calibration
equipment is certified to NIST standards.
Overview
Setup and programming are done through the front panel buttons or with the ConsoliDator+
Software. After power and signal connections have been completed and verified, apply power to
the instrument.
Inputs, outputs, channels, and relays are configured individually. It is recommended that all inputs
be configured before channels, outputs, and relays are programmed.
Shown below are typical screens for tank level applications. Actual screens will vary according to
the selected configuration. Screens may be edited, deleted, or added to fit the application.
For information on soft-keys and button functions, see
Soft-Keys and Buttons on page 25.
Instruction Manual
Typical screen view displaying 4 channels and 4
bargraphs representing the values of each channel.
Press the Menu key to begin setup and programming
The View screen allows a user to view all the settings and values for Channels, Totals, Timers, etc.
To program the instrument, press the
key.
Typical screen view displaying 8 channels and 8
bargraphs representing the values of each channel.
The Setup menu is the starting point during the programming process for setting up Channels, Totals, Timers, Alarms, Inputs, Outputs, Screens, and System settings. The number of channels shown on this screen is determined
by the number of channels previously configured. More channels may be added to the list, by selecting New in the
Setup Channels menu.
Press Right Arrow key to step into channels. Press New key to create a new channel.
The system provides a soft keypad for entering values and tags; it contains numbers, alpha characters, and symbols.
Instruction Manual
Press Edit key to start editing the channel configuration.
The green background indicates the field to be edited.
Press Edit key again to change the channel’s tag, this
opens the data entry keypad.
To change the character set, navigate to the three dots
and press the key indicating the next set of characters.
Use the Down Arrow key to navigate to the keypad. Use
and | keys to move the cursor and use the X
the |
key to delete characters. To enter characters in the
selected text field, use the arrow keys to navigate
through the popup keypad.
To enter symbols, press the three dots and select the
desired symbol.
When done typing the characters in the selected field,
press the Enter key.
To enter numbers, select the numeric keypad, move the
cursor to the insertion point and enter the number using
the soft keys.
29
Page 30
PD9000 ConsoliDator+ Multivariable Controller
the input scaling.
Instruction Manual
Press Enter to accept the changes.
Press the Save key to save the changes. The bargraph
is automatically adjusted to reflect the scale entered.
The bargraph scaling may be changed without affecting
Setup Channels
The Setup Channels menu is used to configure each channel, enter a tag, select the input source,
scale the input, and program other settings that will determine the channel’s processing capabilities.
Linear mode refers to basic 2-point
scaling of a 4-20 mA signal in
engineering units. The graph in
Figure 22 shows the display
response based on example
scaling parameters. For this mode
select [Scale Linear 2-Pt] from
Function options, then enter your
scaling parameters.
Input
(mA)
10.00 37.50
11.00 43.75
12.00 50.00
13.00 56.25
14.00 62.50
15.00 68.75
16.00
17.00 81.25
18.00 87.50
19.00 93.75
20.00 100.00
Output
(%)
4.00 0.00
5.00 6.25
6.00 12.50
7.00 18.75
8.00 25.00
9.00 31.25
75.00
Output (%)
Figure 22. Linear Response Graph
Instruction Manual
4.000
20.000
Linear Response
100.00
80.00
60.00
40.00
20.00
0.00
4.008.0012.0016.0020.00
mA Input
0.00
100.00
Square Root Scaling
Square root mode refers to 2-point
scaling with square root extraction
typically used to linearize the signal
from a differential pressure
transmitter and display the flow rate
in engineering units. The graph in
Figure 23 shows the display
response based on example
scaling parameters. For this mode
select [Scale Square Root] from
Function options.
The square root mode supports
low-flow cutoff which can be used
to suppress readings below a
programmed value. Below the
cutoff value, the controller will
display “0”.
Exponent mode refers to 2-point
scaling with programmable
exponent, typically used in openchannel flow applications using
weirs and flumes to linearize the
signal from a level transmitter and
display the flow rate in engineering
units. The graph in
Figure 24 shows
the display response based on
example parameters and exponent
of “1.5”. For this mode select [Scale
Exponent] from Function options.
The exponent mode supports lowflow cutoff which can be used to
suppress readings below a
programmed value. Below the
cutoff value, the controller will
display “0”.
Input
(mA)
10.00 22.96
11.00 28.94
12.00 35.36
13.00 42.19
14.00
15.00 57.00
16.00 64.95
17.00 73.24
18.00 81.85
19.00 90.77
20.00 100.00
Output
(%)
4.00 0.00
5.00 1.56
6.00 4.42
7.00 8.12
8.00 12.50
9.00 17.47
49.41
Output (%)
Instruction Manual
4.000
Exponent Response
100.00
80.00
60.00
40.00
20.00
0.00
4.008.0012.0016.0020.00
0.00
mA Input
1.500
Round Horizontal Tank
The Round Horizontal Tank (RHT)
function calculates the volume of
round tank with flat ends, based on
the diameter and length dimensions
of the tank.
The input source for the channel
calculating the volume must be a
level channel with units of distance
(height). The RHT function
linearizes the signal from a level
transmitter and displays the volume
in engineering units. The graph in
Figure 25 shows the display
response based on tank example:
Diameter = 48.00 inches
Length = 120.00 inches
For this mode select [Round Horz
The PD9000, in combination with
an ultrasonic level transmitter,
makes for a practical way to
measure and display open channel
flow rate and total in most weirs
and flumes and take periodic
samples. All the user needs to do is
enter the exponent for the weir or
flume into the PD9000 and the
PD9000 automatically raises the
input signal to that power. Sampling
can be based on the total flow or
the flow rate. For instance, to
display open channel flow rate and
total from a 3-inch Parshall flume
and take a one pint sample every
100,000 gallons, the user would
program the PD9000 as shown in
the table above right.
Function Desire Programming
Open Channel Flow 3" Parshall flume Set Programmable Exponent to 1.547
Flow Rate 1
Total 1 Millions of Gallons
Sampling
Channel 2
Sampling
Relay 1
Total 2
Non-Resettable
Screen
Millions of Gallons per
Day (MGD)
Take a 1 pint sample
every 100,000 gallons
Turn valve on to take a
sample
Program controller so
total 2 can never be reset
Display flow rate, totals,
and relay status
Instruction Manual
Set 4 mA: 0
Set 20 mA: 3.508
Create custom unit: MG
Time base: day
integrated over the specified time unit to generate an
tions are
Setup Total with Rate Source
The totalizers are setup the same way as the channels.
The rate from an analog or pulse input
accumulated total that can be configured to count up or
count down. Each total may be configured as “nonresettable”*, which means the total reset func
not available for it.
The pulse inputs can be either integrated from a rate
channel or they can be directly totalized based on the
pulse count and K-Factor value; this is the most accurate
method because every pulse is counted.
*Note:
The non-resettable function can be disabled by the user
at any time, after unlocking a password-protected
controller.
Instruction Manual
Select the rate input channel for the total and press Ok.
Setup Total with Pulse Input Source
Pulse inputs can be totalized directly without the need to
create a rate channel.
Select total units, count up or down, enter preset and
roll-over values, and select non-resettable if required.
After pressing Save, press Yes to reset the total to the
preset value.
Select the units and enter the K-Factor provided by the
flow meter manufacturer.
Up to 32 timers may be setup to control and monitor various processes. The timers may be triggered by any input or
output, such as an analog input rising above a certain threshold or a digital input going from low to high.
Timer Automatic Actions
The automatic timer actions are:
Power Up: Timer action on power up
Error: Timer action when an error is detected
Reset: Event that causes the timer to reset
Start: Event that triggers the timer to start
Stop: Event that causes the timer to stop
Timer Function Keys & Digital Inputs
The function keys and digital inputs may be used to start,
stop, and reset the timers, regardless of the automatic
actions selected.
Time Format
The time format is hh:mm:ss with 0 decimals selected.
If decimal is other than 0, the time is displayed in
seconds with the number of decimals selected.
Count Down Timer
Select count down and enter the starting time count.
Timer Bargraph
The bargraph scaling follows the time format selected
based on decimal point.
Timer Colors
Select the colors for normal and alarm conditions.
Timer Alarms
Alarms may be setup to trigger on timer values,
counting up or down. Go to the Alarms menu and select
a timer as the source for the alarm.
can be driven by a single channel, multiple channels,
digital inputs, time interval, or a combination of other
Reset (Ack)
Ack Anytime
Automatic
The system is capable of handling up to 64 alarms; they
alarms into logic AND & logic OR alarms. Set and reset
point values determine if it is a high or low alarm and the
dead band. Alarms may be setup as latching or nonlatching (automatic) with on and off time delays.
1. Tag: 15-character user-defined
2. Type: Select alarm type
• Single Source
• Multi-Source
• Time Interval
• Alarms OR
• Alarm AND
3. Input: This will depend on type selected
Type: Single and Multi-Source
• Digital
• Modbus
• Channel
• Total
• Timer
Type: Alarms AND & OR
Inputs: Other alarms
4. Automatic: Resets when PV crosses the reset point
5. Ack Anytime (Latching): Ack alarm anytime
6. Break: Alarm status when sensor/comm. break is
detected (e.g. Input < 0.01 mA)
• Alarm On
• Alarm Off
• Stay (Maintain the state before the break)
7. On/Off Delays
Multi-Source Alarm
This alarm type behaves as a logic OR; if
any of the sources crosses the set point,
the alarm goes on.
If the first source is digital (logic), only
sources with digital value (on = 1, off = 0)
are available for selection.
If the first source is a PV channel or timer,
digital inputs may be added as source.
Instruction Manual
Automatic reset and Ack anytime
Relay assigned to Horn activates on alarm condition
The Setup Inputs screen is used to configure the
hardware inputs, assigning a user-defined tag, and
setting filter values.
The top line, for each input, shows the slot # and input
location (2b = slot #2, second input from the left). It also
shows the actual current input.
The next line shows the input type and # (AI-2) with the
default tag, which can be changed at any time.
• Filter*: Select filter time
• Bypass: If the signal change is greater than the
bypass value, the reading jumps to the actual value
± Bypass % of full scale.
• Glitch Filter: Eliminates short duration noise spikes
• Break Below: Set the mA value at which a break is
reported to the system.
•Disable Input Channel: This turns off the power to
the input, but the settings are saved for future use.
This should only be used to save power on unused
inputs.
*Need more filtering?
If you need a more stable reading,
select IIR 16 sec or IIR32 sec setting.
The top line, for each input, shows the slot # and input
location (1a = slot #1, first input from the left). It also
shows the actual frequency, state of the input, and the
number of pulses received since power up, to a
maximum of 65,535.
The next line shows the input type and # (PI-1) with the
default tag, which can be changed at any time.
• Type: Select the pulse input type.
• Low Gate: this is the time window used to calculate
and update the rate.
•High Gate: This is the time window used to calculate
slow rates before the rate goes to zero.
•Low Speed: This setting is used as a de-bounce
filter for contact closure or switch inputs.
Threshold:
Is the voltage level at which a transition
from high to low is detected. For
example, the “Active 1.2V Thrshld”
setting will detect a square wave signal
when it falls below 1.2 V.
Instruction Manual
The digital inputs may be assigned to perform various
user functions, such as trigger alarm, acknowledge
alarms, reset total, etc.
Pulse inputs may be used as digital inputs by setting
them up according the type of input they are intended to
accept. For example, to accept a contact closure the
pulse input must be setup for Reed Switch type input.
A digital input can be used to execute one of the listed
functions and at the same time, it can be used to trigger
an alarm or to totalize (count) how many times the
function has been executed (e.g. Reset Total).
• None: Use digital input (DI) to trigger an alarm or timer
• Button: Digital input behaves as a front panel button
• Channel: Tare, Reset Tare, Reset Max, Reset Min
• Total: Access total functions
• Timer: Access timer functions
• Alarm: Access functions (Ack, Reset, Set Points)
• Screen: Next, Previous, Stop/Scan
• Horn: Silence, Snooze, Test
• Relay: Reset relay information
Note: The elements to be acted upon must be created
before trying to setup the digital input; otherwise it is
not available in the list of functions to execute. For
example, to assign the digital input to tare a
channel, a Tare Channel must be created first.
The controller can accept up to 199 Modbus inputs that
may be used as the source for channels, math functions,
alarms, relay control, etc. Once the data type is selected,
the register number is display to the right.
The Setup Outputs screen is used to configure the
hardware outputs, assigning a user-defined tag, scaling
the mA outputs, associating relays with alarms, and
configuring the digital outputs.
• mA Output: Configure analog outputs
• Relay Output: Configure relay outputs
• Digital Output: Configure digital outputs
• Modbus Output: Configure Modbus outputs
The mA output may be assigned to any analog input,
channel, alarm, or digital input. It may be scaled to any
input and output value.
The top line indicates the slot # and position of the
analog output (4a = slot #4, first position from the left). It
also displays the actual mA output.
The relays can be driven by alarms, digital inputs,
Modbus inputs, channels, totals, and timers. If the input
source is a channel, set and reset points must be
entered. These are the available settings depending on
the source selected.
• Input: Select the source to drive the relay
• Set & Reset: Enter values to turn on & off the relay
for Channel, Total, or Timer Input
• Pulse Output: Pulse relay on/off when set is active
• Break*: The relay state when break is detected
• Fail-Safe: Relay energized under normal conditions
• Relay Status & Runtime: hh:mm:ss
Function: Select Other to set relay to always
on, always off, drive a relay-horn, or
to alternate with another relay.
Select the input source to drive the relay and enter the
required parameters according to the input.
The F4 key may be used to momentarily turn on/off the
relays. To manually control the relays, go to the View
Menu to set the relay to be permanently on or off.
Instruction Manual
The relay runtime & cycle count can be reset (cleared)
from the relay setup screen.
*Note: Break needs to be set in the analog input menu.
Relays not assigned to alarms are used for automatic
on/off control based on set & reset point; they cannot be
acknowledged.
To setup a group of relays for pump alternation control,
follow these steps.
1. Select the primary alternating relay
2. Select the input for alternation (e.g. Ch 1)
3. Enable alternation
4. Enable alternate on time and enter time
5. Enter the On & Off alternation points according
to the number of relays to alternate
6. Select relay condition when input break is
detected*
7. Select fail-safe, if desired (Reverses the relay
contacts state: NO closes and NC opens)
8. Enter the On & Off time delays
9. After saving the primary relay configuration,
navigate to the next relay and configure it to
alternate with the primary relay
Alternation Input Sources
Most level control applications use channels as the input.
The channel is setup to read the signal from a level
transmitter and display the level either in height or
volume units. The continuous level monitoring allows for
selecting multiple alternation points.
If the input is other than a channel, the alternation is
limited to only one pump on at one time. A level switch
could be connected to a digital input and the digital input
will alternate the pumps for each on/off cycle.
Set (On) & Reset (Off) Points
Up to eight alternation points may be entered to alternate
eight relays per group. The On & Off points determine if
pumps are on when the level rises or when it falls.
On & Off Time Delays
To prevent turning pumps off and on at the same time,
it’s recommended to use On delays. The On & Off delays
are common to all the relays in the alternation group.
Alternation Groups
An alternation group is made up of a primary relay and
any number of relays selected to alternate with it.
Multiple alternation groups may be setup using different
sources for each group. A relay should NOT be assigned
to more than one group.
Alternate on Time
This is the maximum time any relay in the group will be
continuously on. After the alternation time has elapsed,
the relay will turn off and another relay will turn on. This
feature is useful for applications where the level is
maintained with one pump for a long time. Depending of
the setup and conditions, it will help distribute the load
among the pumps in the group.
Break
If Relay On is selected, only one of the alternation relays
will be on when a break is detected*.
*Note: Break needs to be set in the analog input menu.
Setup the primary alternation relay.
Setup the additional alternation relays.
Select the primary relay to alternate with.
Alternation Sequence
Instruction Manual
The first relay on is the first relay off, when more than one
relay are activated. The lowest reset point (Off) is used for
the alternation cycle.
The Digital Output menu allows assigning the 4 outputs
Setup Modbus Output
to various events generated by digital inputs, On/Off
channels, alarms, and horn on state.
• Edit the digital output tag
• Select the input
• Select the Break condition
• Invert Output logic
The Modbus Output menu allows assigning up to 64
Modbus register sets (1 to 4) to output any of the values
available in the system (e.g. PV channels, Totals, Relay
Runtime, etc.) and selecting the desired data type from
bit-logic to float 64.
The function code is 0x03 and the registers are base-1
(e.g. Reg. Address 4400 = Reg. Number 44401).
• Edit the Modbus Output tag
• Select the source for the output
• Select the data type
• The register number is assigned by the system
Instruction Manual
Select the data type.
Select the input for Modbus Output.
The register number is provided for each data type.
Up to eight PVs and/or alarms may be displayed per
Instruction Manual
Setup Screens
The Setup Screens menu is used to setup the screens
that will be displayed during operation and to setup the
actions assigned to the function keys F1-F4.
Screens Settings
screen. The screens can be setup to scan automatically,
display bargraphs, and program the function keys to be
used while the screen is visible.
These are the available settings:
• Title: User-defined title or tag
• Channels and alarms: Up to eight/screen
• Show Title: Select to display the title
• Show Channel #: Select to display the channel #
• Show Bargraphs: Select to display the bargraphs
• Bargraph Only: Select to display only the bargraphs
• Auto Scan: Select to scan the screens automatically
• Dwell Time: Number of seconds the screen is
displayed before moving to the next screen
•F1 – F4: Assign functions to be executed by the
function keys
Note:
The function keys F1 – F4 can be customized
according to the screen in view.
The function keys are setup independently for each
screen; this allows the customization of the function keys
according to the process values being displayed. For
example, if totals are being displayed, one function key
can be setup to reset one or all totals.
Note:
Functions are available for selection only if the
appropriate parameter has been set up. Example: If
there are no channels with Tare, Max, or Min, Channel
will not appear in the list for selection of a function.
•Channel
Tare (If applicable)
Minimum
Maximum
•Total
Reset Total
Reset (Confirm)
Enter Total
Add To
Remove From
Previous Screen
Next Screen
Scan / Stop
Go to Screen
View Channel
View Total
View Timer
View Alarm
View Date & Time
View mA Input
View Pulse Input
View Digital Input
View Modbus Input
View mA Output
View Relay Output
View Digital Output
View Modbus Output
Note:
The View function can be used to go to any of the
F4 Assigned to Acknowledge All Alarms
____________________________________________
• Simulate
• Horn
• mA Output
• Relay
Instruction Manual
mA Input
Pulse Input
Digital Input
Modbus Input
Channel
Total
Timer
Alarm
Silence
Snooze
Test
Manual
Hold (Manual)
Automatic
Manual / Auto
Hold / Auto
Reset Info
Reset Info (Confirm)
Force ON
Force OFF
Manual ON
Manual OFF
Hold (Manual)
Automatic
Manual ON / Auto
Manual OFF / Auto
Hold / Auto
parameters of the same type (e.g. View - all the
channels).
The Setup System menu is used to configure settings
that are used throughout the system.
Instruction Manual
Setup Display
The System Display menu is used to adjust the display
settings, setup colors for parameters, bargraphs, and
alarms.
Setup Colors
The Colors menu is used to select the colors for text,
values, and bargraphs associated with the parameter
being displayed.
The Alarm Colors menu is used to select the colors and
behavior of the alarms’ text, alarm panel background,
and the bargraph indicator for set and reset points.
The Display Settings menu is used to adjust the backlight
brightness, refresh rate and to enable or disable the
display of commas for all numeric values.
51
Page 52
PD9000 ConsoliDator+ Multivariable Controller
password protected.
Instruction Manual
General Settings
The General Settings menu contains the settings listed
below.
Set Password
The user may enter a 4-digit password to protect the
system from unintentional changes.
• Device Tag: Edit the device tag (saved on Enter)
Note: The internal buzzer is associated with the alarm's
Horn setting, which is available to drive any relay.
Password Protected Controller
The correct 4-digit password is required to make
changes to the system.
If the password is not correct after 3 attempts, the system
will not allow new tries until a timeout elapses. The
timeout will continue increasing for every 3 new
unsuccessful tries.
If an I/O card is removed permanently, pressing the
The settings provided in
menu are sufficient to
Instruction Manual
System Date & Time
The date & time of the system can be easily adjusted in
the System menu.
System Build
The Build menu provides the model number and it shows
the I/O cards installed with their location in the seven
available slots.
Modbus Settings & Passcode Protection
The Modbus settings must be configured to match the
settings of other devices on the bus. The Modbus Id
must be unique to each device on the bus.
Select Passcode and enter a Modbus passcode
between 0 and 9999 to prevent unauthorized writes to
the controller.
This is different than the main password used to protect
access to the Setup and View menus.
Ethernet Settings
The Ethernet menu provides basic information about the
Ethernet port and allows the user to program a static IP
Address, the port number, and the protocol to be used.
System
Rebuild key clears the information from the slot. This
should also be done if a different card is installed.
Replacing I/O Cards
In case that an I/O card fails, follow these steps:
3) Install the new card in the same slot where the
4) It is not necessary to click Rebuild
defective card was
www.GlobalTestSupply.com
establish Ethernet communications using TCP or UDP
protocols.
For more advanced setup, refer to the instructions
provided under Ethernet Port Setup on page 54.
Note:
If DHCP is selected, the device obtains a new IP
address automatically most of the time when the
power is cycled. This is not displayed on the
controller.
53
Page 54
PD9000 ConsoliDator+ Multivariable Controller
Ethernet Port Setup - Full
If more than one controller is connected to the
The Ethernet port option is fully configured using the
Lantronix DeviceInstaller software, available for download
from the Lantronix’s Website.
Follow these steps, after installation of the DeviceInstaller
software.
1. Connect an Ethernet cable to the Local Area Network
2. Launch the Lantronix DeviceInstaller; it will search for
XPort devices on the Local Area Network (LAN) and
display their status.
3. If no controller is found, click on Options, and select
the type of connection being used (e.g. Wi-Fi).
4.
network, determine which is the new controller by the
assigned IP address. If necessary, disconnect the new
controller and click Device – Search, take note of the
IP addresses listed. Next, connect the new controller
to the LAN and repeat the search; check the list to see
which the new IP address is.
Instruction Manual
•Consult with your IT department to configure
the Ethernet port and maintain network
security.
5. Double-click on the new device IP Address to be configured.
To communicate with a device connected over a LAN, you need the IP Address and the
Local TCP Port.
9. Click on Channel 1 – Connection to select the protocol: TCP or UDP.
Note: For UDP protocol, select Datagram Type: 01
10. Under Endpoint Configuration, enter the Local Port to be used to access the controller
locally or from a remote location. This should be provided by your company’s IT department.
11. Click OK and then click Apply Settings for settings to be sent to the Ethernet device.
Test Ethernet Communication
Modbus Poll is an app that makes it easy to test your
Ethernet connection. Below are some screenshot
examples for Modbus TCP/IP connection.
The View menu is used to view individual channels, totals, timers, alarms, inputs, outputs,
and screens. For example, it provides the details for the current PV, what inputs are the
sources for the channel and what outputs are associated with the channel.
Accessing the individual parameters through the View menu also allows the simulation of
the various parameters for testing purposes as well as the manual control of the relays
and analog outputs.
Press the Right Arrow key to step into viewing
any channel.
Select any channel using the Up or Down Arrow keys
and Press the Right Arrow key again to step into
viewing the channel details.
Stepping into a channel allows the viewing of additional details for the inputs
and outputs associated with that channel. It is also possible to simulate the
selected parameter.
• Channel number and tag
• PV and units
• View the channel input source
• View alarms associated with channel
•
View analog outputs assigned to channel
•
Simulate the channel or analog input
•
Step into any associated parameter
Press the Down Arrow key to navigate to the
channel input source and then down again to view
alarms and analog outputs.
Press the 3-Bar key to enter a new total, reset the total,
or simulate a value for the total.
Totals not associated with a rate channel have additional
features: Add to or remove from the total.
Using the numbers keypad, enter a new total and then
press the Enter key to save.
60
Page 61
PD9000 ConsoliDator+ Multivariable Controller
Totals Generated by Non-Rate Inputs
For totals generated using non-rate inputs; it is possible
to add or remove from the total using the 3-Bar key on
the View Total screen.
This type of total requires the use of an external trigger
such as a digital input, function key, or a Modbus signal.
For example, if the input to T1 is Ch 1, which is
displaying the volume in a container, as provided by the
weight being measured by a load cell with a 4-20 mA
output, which is the input to channel 1.
• Total 1 = 200,500 gallons
• Channel 1 = 100.0 gallons
• Press function key Add To (+ T1)
• 100 gallons is added to Total 1
The total in Tank 1 has been incremented by 100
gallons.
The Remove From feature can be used to decrement
the volume inside a storage tank.
Normally these operations are done automatically by
using a proximity switch or a limit switch to trigger the
Add To or Remove From features.
The View Timers menu displays the value of the existing timers.
Press the Right Arrow key to step into the details of the selected timer and view the associated inputs and outputs.
Press the Right Arrow key to step into viewing timer.
Press the Right Arrow key to select timer.
Press the Right Arrow key to view timer details.
Press the 3-Bar key to choose Timer Control, Reset,
Start, Stop, or Simulate.
Press the Reset key to reset the timer, select Timer Control for additional functions. Use the Simulate
function to simulate the timer rising, falling, or jump to a
specific value using the keypad.
Press the Timer Control key (shown in the timer details
screen) to access all timer control buttons.
62
Page 63
PD9000 ConsoliDator+ Multivariable Controller
View Alarms
Simulate Alarm Condition
Real
The View Alarms menu displays the status of all the alarms and the details for each alarm.
Under the alarm details view, it is possible to reset an acknowledged alarm,
change the set/reset points, or simulate an alarm condition.
• Alarm # and tag
• Set/Reset points
• Source for the alarm
• Outputs associated with the alarm
• Acknowledge the alarm
• Reset the alarm
• Simulate alarm condition
Press the Right Arrow key to view the alarm details.
Instruction Manual
Press the 3-Bar key to select Ack Alarm, Reset Alarm,
change Set Points, or Simulate Alarm condition.
Press the Simulate key to simulate an alarm condition.
Press the Set Point key to change the Set Points. This
re-initializes the alarm to reflect the new set point.
Press the + key to turn on the alarm; note that alarm 13
and relay 1 also turned on. Press Ok key to maintain
simulation or press
63
to cancel simulation.
Page 64
PD9000 ConsoliDator+ Multivariable Controller
View Inputs
or use the
Ok
The View Inputs menu displays the values and status of all the inputs and
the details of the associated channels. Input simulation is also available in the input details.
• Input # and tag
• mA input value
• Pulse input frequency
• Digital input status
• Modbus input value
• Associated channel(s)
• Input simulation
Manual control and simulation states are not saved on
power cycle. On power up the controller initializes to the
actual process conditions.
Press the Right Arrow key to select the mA Input.
Instruction Manual
Press the Right Arrow key to view the mA Input details.
The above screen shows the Analog Input 2 details and
the associated channels.
Simulate mA Input
Use the + / - keys to ramp up and down
keypad to jump to any value within the range. Press the
All the parameters associated with the simulated input
follow the simulated value. Press the Real key to cancel
simulation and return to the actual sensor signal.
64
Page 65
PD9000 ConsoliDator+ Multivariable Controller
View Outputs
Manual Control of 4-20 mA Output
to control the analog output manually;
The View Outputs menu displays the values and status of all the outputs and
the details of the associated channels.
• Output # and tag
• mA output value
• Relay output status
• Digital output status
• Number of cycles & runtime
• Associated input
• Manual control of relays
• Manual control of 4-20 mA outputs
Manual control and simulation states are not saved on
power cycle. On power up the controller initializes to the
actual process conditions.
Press the Right Arrow key to select the mA Output.
Instruction Manual
Press the Right Arrow key to view the mA Output
details.
Select Manual
select Automatic to exit manual control.
Press the 3-Bar key to access Analog Output controls.
Manual control, hold current value, return to automatic.
Use the keypad to enter a value for the analog output or
use the + / - keys to ramp up and down is small steps.
65
Page 66
PD9000 ConsoliDator+ Multivariable Controller
View Alert Messages
View Relays
The View Relays menu allows the user to view the
details for all the relays. The F4 key can be used to turn
on and off the selected relay (momentarily).
Press the Right Arrow key to view the relay details.
• Relay # and tag
• Status
• Runtime
• Number of Cycles
• Reset relay runtime & cycles count
• Parameters associated with the relay
• Other relays used in pump alternation
• Manual control of relays
Manual control and simulation states are not saved
on power cycle.
Instruction Manual
If Alerts are enabled for alarms, the Menu key displays a
flashing Alert! message on red background.
Simulated parameters and manual control outputs,
automatically generate alert messages displayed on a
yellow background.
Press the Manual OFF to turn off relay 1; Pump #1 will
go off and remain off until the relay 1 is put back in
automatic mode.
An Alert! message is displayed in place of the Menu key
anytime an item is in manual control or simulation mode.
The Alerts! Screen allows the user to acknowledge
alarms, return outputs to automatic mode, and navigate
to any of the listed items to view the details.
The View Digital Outputs screen displays the status of
the digital outputs and shows the association with the
parameters used to drive the outputs.
The View Modbus Outputs screen displays the Modbus
outputs set up by the user; it shows the register number
and the parameter used to generate each output.
Instruction Manual
Manual control and simulation states are not saved on
power cycle. On power up the controller initializes to the
actual process conditions.
With the View Screens menu, the user can go to any
available screen and view the details. The screens can
be scanned continuously or can be stopped to stay on a
selected screen at anytime.
Press the Right Arrow key to view details of the
the selected view screen.
Instruction Manual
Press the Scan key to have all available screens
continue to scan.
Press the Stop key to have all available screens stop
scanning and stay on the current screen.
68
Page 69
PD9000 ConsoliDator+ Multivariable Controller
Individual Channel View
To view the details of any channel, press the Menu key and
bargraph.
Operation
Viewing Screens
The controller displays various screens with bargraphs,
numerical values, and relay status throughout
operation, according to the user-selected setup. There
are two basic modes of operation: Automatic scan or
manual scan. The controller initializes in automatic
scan mode. Press Stop key to stop the automatic scan
and use the Left or Right Arrow keys (Previous or
Next) to navigate through the various screens. Press
the Scan key to resume automatic scanning.
The bargraphs are optional, they are enabled or
disabled during Screens setup. The scaling of the
bargraph is done during the setup of each channel and
it can be different than the channel scaling values.
then press Right Arrow key to view the channels. Select the
channel of interest. Navigate through the different items
using the navigation keys. A green bar indicates the selected
item, press the Right Arrow key to step into and see more
details about the inputs and outputs related to the channel in
view.
If applicable, alarms may be acknowledged, and totals may
be reset from these screens. Simulation and manual control
are also available on the View screens.
Low & High Alarm Indication
The alarm set points are indicated by a line at the
corresponding value on the bargraph. Color selection is
done in the Setup – Alarm menu or in the System – Display
menu.
Active High Alarm:Indicated by horizontal and vertical
lines. The bottom of the vertical line is the reset point of the
high alarm. The high alarm is indicated on the left side of the
bargraph.
Active Low Alarm:Indicated by horizontal and vertical
lines. The top of the vertical line is the reset point of the low
alarm. The low alarm is indicated on the right side of the
Instruction Manual
Alarm set points are indicated by horizontal lines.
The controller is equipped with serial communication capability as a standard feature. Baud Rate, Parity, Slave ID
(Address) and Transmit Delay are entered in the System menu, which appears in the main Setup menu. The baud
rate and parity selected must match the settings for all other devices on the network. The Slave ID must be unique,
so it will not interfere with other devices. The controller supports the following Modbus functions:
05 Write Single Coil (Bit) Set single coil value control
15 Write Multiple Coils (Bits) Set multiple coil value control
06 Write Single Register Set single value into specified holding register.
16 Write Multiple Registers Set multiple values into specified holding registers.
The multi-channel controller can also work as a “Modbus Display/Controller” by writing the desired value to the selected Modbus
input (MB-1 to MB-199). The Modbus input can be used the same way a 4-20 mA input is used; it can be brought into a channel to
be displayed and generate alarms to control relays, generate 4-20 mA outputs, and Modbus outputs (MO-1 to MO-64).
Modbus Register Tables
Table 1. Default Register Numbers / Addresses
40001 0 Channel (1) Value Float 03, 04 R
40003 2 Channel (2) Value Float 03, 04 R
40005 4 Channel (3) Value Float 03, 04 R
40007 6 Channel (4) Value Float 03, 04 R
40009 8 Channel (5) Value Float 03, 04 R
40013 12 Channel (7) Value Float 03, 04 R
40015 14 Channel (8) Value Float 03, 04 R
40017 16 Total (1) Value Float 03, 04 R
40019 18 Total (2) Value Float 03, 04 R
40021 20 Total (3) Value Float 03, 04 R
40023 22 Total (4) Value Float 03, 04 R
40025 24 Timer (1) Value Float 03, 04 R
40027 26 Timer (2) Value Float 03, 04 R
40029 28 Timer (3) Value Float 03, 04 R
40031 30 Timer (4) Value Float 03, 04 R
40033 32 Alarm (1) Status* Short 03, 04 R
40034 33 Alarm (2) Status* Short 03, 04 R
40035 34 Alarm (3) Status* Short 03, 04 R
40036 35 Alarm (4) Status* Short 03, 04 R
40037 36 Alarm (5) Status* Short 03, 04 R
40038 37 Alarm (6) Status* Short 03, 04 R
40039 38 Alarm (7) Status* Short 03, 04 R
40040 39 Alarm (8) Status* Short 03, 04 R
*Alarm Status: 0: Off, 1: On, 2: On & Acknowledged
The table above contains some predefined registers and data types used.
The following table contains the definitions of all accessible registers with their corresponding data type.
The PV’s register numbers and register addresses are calculated based on the formulas provided below. The values
are available in various data types. Examples of register addresses (base 0) are provided on the right column.
Register numbers refer to PLC Addresses (base 1). Function Code 03 Read Holding Registers (4x) are shown on this
table and used throughout the system; other functions are also supported as indicated in the Function column.
The Modbus input registers can be configured under the Setup – Inputs – Modbus menu and the Modbus output
registers can be mapped under the Setup – Outputs – Modbus menu; this allows assigning any parameter to the
Modbus output registers and selecting the data type for input and output registers.
Cleared upon execution. Must be
re-written with each Unlock.
40081
80
Set RTC
Date & Time
Short
06, 16
W 6
40082
81
Year
Short
06, 16
W 0..99
40083
82
Month
Short
06, 16
W 1..12
40084
83
Day
Short
06, 16
W 1..31
40085
84
Hour
Short
06, 16
W
0..23
Second to zero.
40086
85
Minute
Short
06, 16
W
0..59
zero
40087
86
Second
Short
06, 16
W 0..59
40081
80
Channel - Get
Tag
Short
06, 16
W
11 40082
81
Channel (N)
Short
06, 16
W
40083 40090
82 - 89
Tag
String
(16 char)
03, 04
R Null terminated string.
40081
80
Reset Channel
Short
06, 16
W
12 40082
81
Channel (N)
Short
06, 16
W
Program Code with only single
parameters.
40083
82
Thru Channel (N)
Short
06, 16
W 0 to ignore
40081
80
Set Channel
Short
06, 16
W
13
Tare, Capture, Switch
40082
81
Channel (N)
Short
06, 16
W
Program Code with only single
parameters.
40083
82
Thru Channel (N)
Short
06, 16
W 0 to ignore
40081
80
Total - Get Tag
Short
06, 16
W
27 40082
81
Total (N)
Short
06, 16
W
40083 40090
82 - 89
Tag
String
(16 char)
03, 04
R Null terminated string.
Instruction Manual
Modbus Write Protection
The Modbus write passcode protection can be enabled in the System – Modbus menu. This protection prevents
writing to the registers, unless the unlock code 1 is sent to register 81 followed by the passcode sent to register 82.
The protection is automatically restored after 30 seconds of Modbus – write inactivity. See page 53 for details.
Table 4. Program Parameters for Special Functions
40082 -
Description
Program
Function R/W
Comments
written either before or with the
Program Code plus parameters
ending at Hour will set Minute and
Program Code plus parameters
ending at Minute will set Second to
To control the relays via Modbus, use the Write Single Coil command [command code 05] or Write Multiple Coils
[command code 15] and send either the “ON” or “OFF” to the Modbus input associated with the target relay.
Setup Example #1
Follow this example to set up Modbus Input to control a relay and configure the system to display messages related
to the status of the device being controlled, in this case a pump.
Setup – MB-1.
1. Tag: Modbus Input 1
2. Type: Bit – Logic (Reg. No. 06101 or Reg. Address 06100)
3. Units: Logic = PUMP ON / PUMP OFF
4. Break: Default = OFF
Setup – RY-1.
1. Tag: Relay 1
2. Input: MB-1. Modbus Input 1
Setup – Create Screen
1. Title: Pumps
2. MB-1. Modbus Input 1
3. RY-1. Relay 1
4. F3: Assign to Force On RY-1
5. F4: Assign to Force Off RY-1
Operation: Write “1” to Reg. 06101 to turn relay 1 On; write “0” to turn relay 1 Off.
Setup Example #2
Follow this example to control the relays directly from Modbus using special program functions. You can control one
or all relays with one command.
parameter will ignore remaining
parameter will ignore remaining
parameter will ignore remaining
a. Reg. 40081: 85
b. Reg. 40082: 1
c. Reg. 40083: 0 (last relay, if more than one)
2) To manually turn off relay 1 write:
a. Reg. 40081: 86
b. Reg. 40082: 1
c. Reg. 40083: 0 (last relay, if more than one)
3) To return relays to normal operation write commands