PRECISION DIGITAL PD683, PD688 Instruction Manual

Page 1
PRECISION DIGITAL CORPORATION
233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
PD683 & PD688
LOOP-POWERED METERS
• 2 V drop (5.7 V with backlight)
• 5-Digit LCD, 0.6" (15.2 mm) High
• Custom Engineering Units
• 20-Segment Bargraph Display
• Type 4X, NEMA 4X, IP65 Front
• Maximum & Minimum Display
• Linear, Square Root, or Programmable Exponent
• Non-Volatile Memory – No Battery Needed
Loop-
Powered
Backlight
Standard!
PD688 only
Page 2
PD683 & PD688 Loop-Powered Meters Instruction Manual
2
Disclaimer
The information contained in this document is subject to change without notice. Precision Digital makes no representations or war­ranties with respect to the contents hereof, and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
Registered Trademarks
NORYL® and LEXAN® are registered trademarks of SABIC Innova­tive Plastics. All other trademarks mentioned in this document are the property of their respective owners.
© 2016 Precision Digital Corporation. All rights reserved.
Page 3
PD683 & PD688 Loop-Powered Meters Instruction Manual
3
INTRODUCTION
The PD688 is an intrinsically safe and non-incendive loop-powered meter approved for hazardous area locations. The PD683 is a general-purpose loop-powered meter for safe area applications. The four front panel but­tons make the setup and programming an easy task. Five digits, bar­graph, engineering units, and trend arrows provide a clear and attractive presentation of the process.
The square root and programmable exponent functions allow for condi­tioning of signals from non-linear transmitters without adding external components to the system and the convenience of scaling without a cali­brated signal source make the PD683 & PD688 the ideal choice for pro­cess display applications.
ORDERING INFORMATION
Model Description
PD683-0K0* Loop-Powered Panel Meter for Safe Area
PD684-0K1 Loop-Powered Rate/Totalizer for Safe Area
PD688-0K0* ATEX/FM/CSA Approved Loop-Powered Panel Meter
PD689-0K1 ATEX/FM/CSA Approved Loop-Powered Rate/Totalizer
Enclosures and Accessories
Model Meters Description Mounting
PDA2407 1 Plastic NEMA 4X Enclosure
Inside Cover
PDA2410 3 Plastic NEMA 4X Enclosure
Inside Cover
PDA2411 2 Plastic NEMA 4X Enclosure
Inside Cover
PDA23XX 1-10 Economical Plastic NEMA 4X Enclosure Through Door
PDA25XX 1-10 Plastic NEMA 4X Enclosure
Through Door
PDA26XX 1-6 Stainless Steel NEMA 4X Enclosure
Through Door
PDA27XX 1-6 Steel NEMA 4 Enclosure
Through Door
PDA2801* 1 Low-Cost Plastic NEMA 4X Enclosure
Through Cover
PDA2812 2 Low-Cost Plastic NEMA 4X Enclosure
Through Cover
Note: XX = the last two digits of the model number.
Go to www.predig.com to find individual part numbers.
* Quick Shipment Program product, typically shipped within 2 working days
Page 4
PD683 & PD688 Loop-Powered Meters Instruction Manual
4
Table of Contents
INTRODUCTION ------------------------------------------------------------ 3 ORDERING INFORMATION --------------------------------------------- 3 SPECIFICATIONS ---------------------------------------------------------- 6
General ------------------------------------------------------------------------------- 6 Input ----------------------------------------------------------------------------------- 7
PD688 COMPLIANCE INFORMATION ------------------------------- 8
Ratings and Approvals --------------------------------------------------------- 8
SAFETY INFORMATION ------------------------------------------------- 8 INSTALLATION ------------------------------------------------------------- 9
Unpacking --------------------------------------------------------------------------- 9 Panel Mounting -------------------------------------------------------------------- 9 Wiring Connections ------------------------------------------------------------ 10
4-20 mA Input Connections ------------------------------------------------ 11
SETUP AND PROGRAMMING ---------------------------------------- 12
Front Panel Buttons & Status Indicators ------------------------------- 13 Main Menu Display Functions & Messages ---------------------------- 14 Main Menu ------------------------------------------------------------------------ 15 Setting Numeric Values ------------------------------------------------------ 15 Setting Up the Meter (setup) ------------------------------------------------ 16
Setting the Decimal Point (deC.pt) --------------------------------------- 16 Setting the Units Display (units) ----------------------------------------- 17
Programming the Meter (prog) --------------------------------------------- 18
Scaling the Meter (sCalE) -------------------------------------------------- 19 Calibrating the Meter (Cal) ------------------------------------------------- 20 Recalibrating the Internal Calibration Reference (ICal) ------------ 20 Setting Up the Bargraph (GrapH) ----------------------------------------- 21
Setting Up the Password (pass) ------------------------------------------- 22
Locking the Meter ------------------------------------------------------------ 22 Unlocking the Meter ---------------------------------------------------------- 23
Advanced Features Menu ---------------------------------------------------- 24
Advanced Features Menu & Display Messages ---------------------- 25 Math Functions (lnear, Squar, Prog.E, Cutof) ----------------------- 26 Contrast (contr) -------------------------------------------------------------- 27 Noise Filter (fltEr) ---------------------------------------------------------- 27 Noise Filter Bypass (bypAs) ----------------------------------------------- 27 Internal Calibration (ICal) -------------------------------------------------- 28 Information Menu (info) ---------------------------------------------------- 29
Page 5
PD683 & PD688 Loop-Powered Meters Instruction Manual
5
OPERATION ---------------------------------------------------------------- 30
Front Panel Buttons Operation -------------------------------------------- 30 Maximum & Minimum Readings (Max& MiN) --------------------------- 31
MOUNTING DIMENSIONS ---------------------------------------------- 32
Reset Meter to Factory Defaults ------------------------------------------- 33
Factory Defaults & User Settings ----------------------------------------- 34
TROUBLESHOOTING ---------------------------------------------------- 35
Troubleshooting Tips --------------------------------------------------------- 35
QUICK USER INTERFACE REFERENCE GUIDE ---------------- 36 EU DECLARATION OF CONFORMITY FOR PD688 ------------ 38 EU DECLARATION OF CONFORMITY FOR PD683 ------------ 39
Table of Figures
Figure 1. Panel Cutout and Mounting ................................................. 9
Figure 2. PD683 & PD688 Rear View ................................................. 10
Figure 3. PD683 Input Connections with Backlight ......................... 11
Figure 4. PD683 Input Connections without Backlight ................... 11
Figure 5. Meter Dimensions – Side View .......................................... 32
Figure 6. Case Dimensions – Top View ............................................ 32
Page 6
PD683 & PD688 Loop-Powered Meters Instruction Manual
6
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY Five digits
(-99999 to 99999)
0.60" (15.2 mm) high, 7-segment, au­tomatic lead zero blanking.
Four characters (Engineering Units)
0.25" (6.4 mm) high, 14 segment.
Bargraph 20-segment, 0% to 100% indication.
Trend arrows Up and down trend indication.
Backlight Orange (intensity varies with signal)
DISPLAY UPDATE RATE
1 update/second
OVERRANGE
Display flashes
99999
UNDERRANGE
Display flashes
-99999
PROGRAMMING METHOD
Four front panel buttons
NOISE FILTER Programmable from 1 to 199
RECALIBRATION Recalibration is recommended at least every 12 months.
MAX/MIN DISPLAY
Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
PASSWORD Programmable password restricts modification of
programmed settings.
NON-VOLATILE MEMORY
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
NORMAL MODE REJECTION
64 dB at 50/60 Hz
ENVIRONMENTAL Operating temperature range: -30 to 65°C (-40°C allowed)*
Storage temperature range: -40 to 65°C Relative humidity: 0 to 90% non-condensing
*Below -30°C, the LCD becomes less readable.
CONNECTIONS Removable screw terminals accept 12 to 22 AWG wire
ENCLOSURE & MATERIALS
1/8 DIN, high impact plastic, UL 94V-0, color: gray NORYL® Polyphenylene Ether & Polystyrene blend (PPE PS) Resin LEXAN® Polycarbonate (PC) Film
Page 7
PD683 & PD688 Loop-Powered Meters Instruction Manual
7
MOUNTING 1/8 DIN panel cutout required. Two panel mounting
bracket assemblies provided
TIGHTENING TORQUE
Screw terminal connectors: 4.5 lb-in (0.5 Nm) Mounting screws: 8.0 lb-in max. (0.9 Nm)
OVERALL DIMENSIONS
4.68" x 2.45" x 3.79" (119 mm x 62 mm x 96 mm) (W x H x D)
WEIGHT 5.7 oz (162 g)
WARRANTY 3 years parts and labor
EXTENDED WARRANTY
1 or 2 years, refer to Price List for details
Input
ACCURACY
±0.03% of span ±1 count, square root and programmable exponent: 10-100% FS
FUNCTION
Linear, square root, or programmable exponent
LOW-FLOW CUTOFF
-99999 to 99999 (-99999 disables cutoff function)
TEMPERATURE DRIFT
50 PPM/°C from -40 to 65°C ambient
DECIMAL POINT
Up to four decimal places:
d.dddd, dd.ddd, ddd.dd, dddd.d,or ddddd
CALIBRATION RANGE
An Error message will appear if input 1 and input 2 signals are too close together.
Input Range
Minimum Span Input 1 & Input 2
4-20 mA 0.40 mA
VOLTAGE DROP Without Backlight With Backlight
2.0 V maximum 5.7 V maximum
EQUIVALENT RE­SISTANCE
100 Ω @ 20 mA 285 Ω @ 20 mA
INPUT OVERLOAD
Over current protection to 2 A max.
Page 8
PD683 & PD688 Loop-Powered Meters Instruction Manual
8
PD688 COMPLIANCE INFORMATION
Ratings and Approvals
FM & CSA Certified as intrinsically safe with entity for use in:
Class I, Div 1, 2, Groups ABCD Class II, Div 1, Groups EFG Class II, Div 2, Groups FG Class III, Div 1, 2 Class 1, Zone 0, Group IIC
Non-incendive: Suitable for use in Class I, Div 2, Groups ABCD; Class II, Div 2, Groups FG; Class III, Div 2.
Entity Parameters: Ui: 30 V; Ii: 175 mA; Ci: 0; Li: 0; Pi: 1.0 W
ATEX
II 1G Ex ia IIC T4 IP65 Ta = -40°C to 65°C
CE EMC Emissions and Immunity:
EN 61326:2013 EMC requirements for Electrical equipment for measurement and laboratory use – Industrial
IEC 61010-1:2010 & EN 61010-1:2010, including Group and National Differences as they apply for AU, CA, US and KR
Special Conditions for Safe Use:
The permitted ambient temperature range for the PD688 is -40°C to 65°C.
Year of Construction
This information is contained within the serial number with the first four digits representing the year and month in the YYMM format. For FM/CSA applications: The PD688 installation must be performed in accordance with Control Drawing LIM688-2 For European Community: The PD688 must be installed in accord­ance with the ATEX directive 94/9/EC, the product certificate FM08ATEX0058X, and LIM688-2
SAFETY INFORMATION
Installation and service should be per­formed only by trained service personnel. Service requiring replacement of internal components must be performed at the factory.
CAUTION: Read complete instructions prior to installation and operation of the meter.
!
Page 9
PD683 & PD688 Loop-Powered Meters Instruction Manual
9
INSTALLATION
There is no need to remove the meter from its case to com­plete the installation, wiring, and setup of the meter.
Unpacking
Remove the meter from box. Inspect the packaging and con­tents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
Panel Mounting
• Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm). Refer to Mounting Dimensions, page 32 for more details.
• Clearance: allow at least 4" (102 mm) behind the panel for wiring.
• Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Minimum steel/stainless steel panel thickness to maintain watertight rating: 0.06" (1.5 mm).
Note: A steel or stainless steel panel rather than plastic is recommended in cases where a watertight or dust-tight seal is required between the meter and the panel.
• Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
• Insert meter into the panel cutout.
• Install mounting brackets and tighten the screws against the panel.
To achieve a proper seal, tighten the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
Figure 1. Panel Cutout and Mounting
Panel
Gasket
Mounting
Bracket
Mounting
Screw
Removable
Connector
3.622" (92mm)
1.772"
(45mm)
Panel Cutout to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances: A: +0.032 (+0.8mm)
-0.000 (-0.0mm) B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
See page 32 for Mount­ing Dimensions
Page 10
PD683 & PD688 Loop-Powered Meters Instruction Manual
10
Wiring Connections
Signal connections are made to a four-terminal removable connector. This section is only intended for the PD683.
PD688 installation must be performed in accordance with Control Drawing LIM688-2 in order to meet agency approval ratings.
Observe all safety regulations. Electrical wiring should be performed in accordance with all agency requirements and applicable national, state, and lo­cal codes to prevent damage to the meter and en­sure personnel safety.
Figure 2. PD683 & PD688 Rear View
S+ S- B+ B-
Page 11
PD683 & PD688 Loop-Powered Meters Instruction Manual
11
4-20 mA Input Connections
Input connections are made to a four-terminal connector labeled S+|S-|B+|B-. The loop-powered backlight is an optional configuration and requires a total maximum voltage drop of 5.7 V. The backlight is recom­mended for dim lighting conditions and is enabled when wired as shown in Figure 3. It may be bypassed if installed in bright lighting conditions to reduce the maximum voltage drop to 2.0 V as shown in Figure 4.
Figure 3. PD683 Input Connections with Backlight
Figure 4. PD683 Input Connections without Backlight
S+ S
- B+ B-
4-20 mA
Transmitter
Power
Supply
S+ S
- B+ B-
4-20 mA
Transmitter
Power
Supply
Page 12
PD683 & PD688 Loop-Powered Meters Instruction Manual
12
SETUP AND PROGRAMMING
• There is no need to recalibrate the meter for milliamps when first received from the factory.
• The meter is factory calibrated for milliamps prior to shipment. The calibration equipment is certified to NIST standards.
Overview
There are no jumpers involved in the setup process of the meter. Setup and programming is done through the front panel buttons.
After all connections have been completed and verified, apply power to the loop.
For
Quick User Interface Reference Guide
go to page 36
Page 13
PD683 & PD688 Loop-Powered Meters Instruction Manual
13
Front Panel Buttons & Status Indicators
Button Symbol
Description Symbol Status
Menu
0%
Bargraph minimum
Right arrow/Reset
100%
Bargraph maximum
Up arrow/Max
Increasing trend
Enter/Ack
Decreasing trend
•
Press the
Menu
button to enter or exit the Programming Mode at
any time.
•
Press the
Right
arrow button to move to the next digit or decimal
position during programming.
•
Press the Up arrow button to scroll through the menus, decimal
point, or to increment the value of a digit.
•
Press the
Enter/Ack
button to access a menu or to accept a setting.
•
Press and hold the
Menu
button for five seconds to access the
Ad-
vanced Features
of the meter.
Page 14
PD683 & PD688 Loop-Powered Meters Instruction Manual
14
Main Menu Display Functions & Messages
The meter displays various functions and messages during setup, pro­gramming, and operation. The following table shows the main menu functions and messages in the order they appear in the menu.
Display Parameter Action/Setting
setuP
Setup
Enter Setup menu
DeC..pt
Decimal point
Set decimal point
units
Units
Enter the Units menu
prog
Program
Enter the Program menu
sCalE
Scale
Enter the Scale menu
Cal
Calibrate
Enter the Calibrate menu
inpt1
Input 1
Calibrate input 1 signal or program input 1 value
DspL1
Display 1
Program display 1 value
inpt2
Input 2
Calibrate input 2 signal or program input 2 value
DsPl2
Display 2
Program display 2 value
Error
Error
Error, calibration not successful, check signal
graph
Graph
Enter the Graph menu
Pass
Password
Enter the Password menu
unloc
Unlocked
Program password to lock meter
Locd
Locked
Enter password to unlock meter
99999
-99999
Flashing dis­play
Overrange condition Underrange condition
Page 15
PD683 & PD688 Loop-Powered Meters Instruction Manual
15
Main Menu
The main menu consists of the most commonly used functions: Setup, Program, and Password.
• Press Menu button to enter Programming Mode then press Up ar- row button to scroll main menu.
• Press Menu, at any time, to exit and return to Run Mode. Changes made to settings prior to pressing Enter/Ack are not saved.
• Changes to the settings are saved to memory only after pressing Enter/Ack.
• The display moves to the next menu every time a setting is accepted by pressing Enter/Ack.
Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select next digit and Up arrow to increment digit.
The digit being changed blinks. Press the Enter/Ack button, at any time, to accept a setting or Menu
button to exit without saving changes.
The decimal point is set using the Right or Up arrow button in the Setup-decimal point menu.
9.2846GPS setup prog pass
Run
Mode
04.000
04.000 05.000
Increment Digit
Value
Next
Setting
Select Next Digit Accept Setting
Page 16
PD683 & PD688 Loop-Powered Meters Instruction Manual
16
Setting Up the Meter (setup)
The Setup menu is used to select:
1. Decimal point position
2. Engineering units display
Press the Enter/Ack button to access any menu or press Up arrow but­ton to scroll through choices. Press the Menu button to exit at any time.
Setting the Decimal Point (deC.pt)
Decimal point may be set with up to four decimal places or with no deci­mal point at all.
Pressing the Right or Up arrow moves the decimal point one place to the right until no decimal point is displayed, then it moves to the left most position.
setuP deC.Pt
units
deC.pt
ddddd
Next
Select Decimal
Point
Previous
or
Page 17
PD683 & PD688 Loop-Powered Meters Instruction Manual
17
Setting the Units Display (units)
The meter can be set to display a combination of three alphanumeric characters for engineering units or for identification (e.g. PSI, G/S, LpM, TK3, ,L7). There is also a fourth alphanumeric character located above this row, which supports a degrees symbol and “x10” symbol (e.g. °C,
°F,
x103, x106, x109).
Press Right arrow to select next unit and Up arrow to increment unit. The unit being changed blinks. Press the Enter/Ack button, at any time, to accept a setting or Menu
button to exit without saving changes.
D aBC
Increment Character
Next
Setting
Select Next
Character
Accept Setting
D
aBC
D
aCC
Page 18
PD683 & PD688 Loop-Powered Meters Instruction Manual
18
Programming the Meter (prog)
It is very important to read the following information, before proceeding to program the meter:
• There is no need to recalibrate the meter for milliamps when first received from the factory.
• The meter is factory calibrated for milliamps prior to shipment. The calibration equipment is certified to NIST standards.
• Use the Scale menu to enter scale parameters without applying a live signal.
• Alternatively, use the Calibrate menu to apply a signal from a cali- brator or a 4-20 mA transmitter to calibrate the meter.
The Program menu contains the Calibrate and the Scale menus. Inputs may be calibrated or scaled to any display within the range of the
meter.
Additional parameters, not needed for most applications, are pro­grammed with the Advanced Features menu, see Advanced Features Menu, page 24.
Error Message (Error)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed, the meter reverts to input 1, allow­ing the appropriate input signals to be applied.
The error message might be caused by one of the following conditions:
1. Minimum input span requirements not maintained.
2. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and input 2 signals required to complete the calibration or scaling of the me­ter. The minimum span is 0.40 mA.
prog SCAle
CAL GrapH
Page 19
PD683 & PD688 Loop-Powered Meters Instruction Manual
19
Scaling the Meter (sCalE)
The 4-20 mA input can be scaled to display the process in engineering units.
A signal source is not needed to scale the meter; simply program the in­puts and corresponding display values.
For instructions on how to program
numeric values see Setting Numeric
Values, page 15.
dsPL1
Press Enter to Accept Setting
inpt2
Scale
Input 2
inpt1
Set Input 1
Value
sCalE
04.000
Set Display 1
Value
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
0.0000
Page 20
PD683 & PD688 Loop-Powered Meters Instruction Manual
20
Calibrating the Meter (Cal)
To scale the meter without a signal
source, refer to Scaling the Meter
(sCalE), page 19.
The meter can be calibrated to display the process in engineering units by applying the appropriate input signal and following the calibration procedure.
The use of a calibrated signal source is strongly recommended.
1. Press the Up arrow button to scroll to the Calibration menu (CAL) and press Enter/Ack.
2. The meter displays inpt1. Apply a known signal and press En- ter/Ack. Trend arrows are displayed while accepting the signal.
3. After the signal is accepted, the meter displays dspl1. Press En- ter/Ack, enter a corresponding display value for the signal input, and press Enter/Ack to accept.
4. The meter displays inpt1. Apply a known signal and press En- ter/Ack. Trend arrows are displayed while accepting the signal.
5. After the signal is accepted, the meter displays dspl2. Press En- ter/Ack, enter a corresponding display value for the signal input, and press Enter/Ack to accept.
Recalibrating the Internal Calibration Reference (ICal)
The Internal Calibration (ICAL) menu, located in the Advanced features menu, is used to recalibrate the internal calibration reference. Recalibra­tion is recommended at least every twelve months. Refer to Internal Calibration (ICal), page 28 for instructions.
inpt1 dspl1 04.000
Set Display 1
Value
inpt2
Calibrate
Input 2
Cal
Display
Flashes
Accepting
Input
Press Enter to Accept Setting
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
Page 21
PD683 & PD688 Loop-Powered Meters Instruction Manual
21
Setting Up the Bargraph (GrapH)
The meter can be set to display a bargraph proportional to the percent­age process reading within a user-defined span.
The span is determined by values entered for 0% and 100%. If the 0% and 100% values are the same as the values that were en­tered for display 1 and display 2, respectively, from the scale or cali­brate steps, then it is not necessary to modify them.
The bargraph may be disabled by selecting OFF from the bargraph menu.
100PCT
0PCT
Set 0%
Value
-ON-
00.000
Set 100%
Value
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
50.000
GrapH
-OFF-
Run Mode
Page 22
PD683 & PD688 Loop-Powered Meters Instruction Manual
22
Setting Up the Password (pass)
The Password menu is used to program a five-digit password to prevent unauthorized changes to the programmed parameter settings.
Locking the Meter
Enter the Password menu and program a five-digit password.
For instructions on how to program numeric values see Setting Numeric Values, page 15.
Record the password for future reference. If appropriate, it may be recorded in the space provided.
Model: Serial Number: Password: __ __ __ __ __
pass unloc 00000
Program
Password
locd
Run Mode
Page 23
PD683 & PD688 Loop-Powered Meters Instruction Manual
23
Unlocking the Meter
If the meter is password protected, the correct password must be entered in order to make changes to the parameter settings.
Entering the correct five-digit number sets the password to 00000, disa­bling the protection. The meter remains unlocked until a new password is programmed or the former password is re-programmed using the Password menu.
Changes to the programmed parameter settings are allowed only with the password set to 00000.
If the password entered is incorrect, the meter displays Locd (Locked) for about three seconds, then it returns to Run Mode. To try again, press Enter/Ack while the Locked message is displayed.
Forgot the Password?
The password may be disabled by the following procedure:
1. Note display reading prior to pressing the Menu button. Ignore decimal point and sign.
2. Access the
Password menu, add 2 to the noted
reading and enter that number as the password (e.g. display reading = -1.23, password = 00125).
pass locd 00000
Enter
Password
unloc
Run Mode
Page 24
PD683 & PD688 Loop-Powered Meters Instruction Manual
24
Advanced Features Menu
To simplify the setup process, functions not needed for most applica­tions are located in the Advanced Features menu.
Press and hold the Menu button for five seconds to access the Ad- vanced Features of the meter.
bypas
Press Enter/Ack to Access Menu or to Accept Setting
contr
funct
flter
Press Up to Scroll Menu and to Increment Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
out
Press and hold for five seconds
trend
9.2846GPS
Run Mode
I CAL info
Page 25
PD683 & PD688 Loop-Powered Meters Instruction Manual
25
Advanced Features Menu & Display Messages
The following table shows the Advanced features menu functions and messages in the order they appear in the menu.
Display Parameter Action/Setting
Funct
Function
Enter Function menu
Lnear
Linear
Set linear scaling
Squar
Square Root
Set square root extraction
Prog.E
Programmable Exponent
Set programmable exponent
cutof
Low-Flow Cutoff
Set low-flow cutoff
contr
Contrast
Enter contrast adjustment menu
flter
Filter
Set noise filter value
bypas
Bypass
Set filter bypass value
Trend
Trend Arrows
Enable or disable trend arrows
-ON-
On
Enable trend arrow display
-Off-
Off
Disable trend arrow display
ICal
Initial calibration
Enter initial calibration for process inputs
Info
Meter information
Show software number and version, or reset to defaults
reset
Reset Defaults
Restore factory default parameter settings
For instructions on how to program
numeric values see Setting Numeric
Values, page 15.
Page 26
PD683 & PD688 Loop-Powered Meters Instruction Manual
26
Math Functions (lnear, Squar, Prog.E, Cutof)
The PD683 & PD688 provide a number of math functions to condition outputs from linear and non-linear transmitters.
Linear (lnear)
Meters are set up at the factory for linear function. The linear function provides a display that is linear with respect to the input signal.
Square Root (Squar)
The square root function is used to linearize the signal from a differential pressure transmitter and display flow rate in engineering units.
Programmable Exponent (Prog.E)
The programmable exponent function is used to linearize the level sig­nal in applications using weirs and flumes and display flow rate in engi­neering units. Upon selecting programmable exponent (Prog.E), the me­ter prompts entry of a 5-digit value between 0.5000 and 3.0000 as the exponent.
Low-Flow Cutoff (CutoF)
The low-flow cutoff feature allows the meter to be programmed so that the often-unsteady output from a differential pressure transmitter, at low flow rates, always displays zero on the meter. The cutoff value may be programmed from -99999 to 99999. Below the cutoff value, the meter will display zero. Selecting either square root or programmable expo­nent will set the cutoff value to 0. Program the cutoff value to -99999 to disable.
LnearFunct Squar
Advanced
Features
Press Enter to Accept Setting
prog.e Cutof
Page 27
PD683 & PD688 Loop-Powered Meters Instruction Manual
27
Contrast (contr)
LCD contrast is adjustable through the front panel buttons. Select contr and increase level using Up Arrow/Max button. Settings 1 through 9 will be displayed on the screen as 11111 to 99999. Settings 1 through 4 are usually best when viewing from below the angle perpendicular to the display. Settings 5 through 9 are usually best when viewing straight on (meter is at eye level) or when viewing from above.
Noise Filter (fltEr)
Most applications do not require changing this parameter. It is intended to help attain a steady display with an unsteady (noisy) input signal.
The field selectable noise filter averages any minor or quick changes in the input signal and displays the reading with greater stability.
Increasing the filter value will help stabilize the display, however this will reduce the display response to changes on the input signal.
The filter level may be set anywhere from 1 to 199.
Noise Filter Bypass (bypAs)
The meter can be programmed to filter small input changes, but allow larger input changes to be displayed immediately, by setting the bypass value accordingly.
If the input signal goes beyond the bypass value, it will be displayed im­mediately with no averaging done on it.
The noise filter bypass value may be set anywhere from 0.2 to 99.9. It corresponds to percentage of full scale.
Increasing the bypass value may slow down the display response to changes on the input signal.
Pressing the Right Arrow/Reset button will also bypass the filter and provide an instant update.
Page 28
PD683 & PD688 Loop-Powered Meters Instruction Manual
28
Internal Calibration (ICal)
• There is no need to recalibrate the meter for milliamps when first received from the factory.
• The meter is factory calibrated for milliamps prior to shipment. The calibration equipment is certified to NIST standards.
The internal calibration allows the user to scale the meter without apply­ing a signal. The use of a calibrated signal source is necessary to per­form the internal calibration of the meter. Check calibration of the meter at least every 12 months.
Notes:
• The signal source must have a full-scale accuracy of 0.01% or better between 4 and 20 mA in order to maintain the specified accuracy of the PD688.
• Allow the meter to warm up for at least 15 minutes before performing the internal calibra­tion procedure.
The Internal calibration menu is part of the Advanced features menu.
1. Press and hold the Menu button for five seconds to access the Ad­vanced Features of the meter.
2. Press the Up arrow button to scroll to the Internal calibration menu (ICAL) and press Enter/Ack.
3. The meter displays 4.000 mA. Apply a 4.000 mA signal and press Enter/Ack. The display shows both trend arrows for a moment while the meter is accepting the signal.
4. After the signal is accepted, the meter displays 8.000 mA. Apply an
8.000 mA signal and press Enter/Ack. The display shows both trend arrows for a moment while the meter is accepting the signal.
5. Continue, as in the previous step, for the remaining signals:
12.000 mA, 16.000 mA, and 20.000 mA.
Error Message (Error)
An error message indicates that the calibration or scaling process was not successful. After the error message is displayed, the meter reverts to the previous signal prompt, allowing the appropriate input signal to be applied. The error message might be caused by inadvertently leaving the signal at the previous level.
Page 29
PD683 & PD688 Loop-Powered Meters Instruction Manual
29
Information Menu (info)
The Information menu is located in the Advanced features menu, to ac­cess Information menu see Advanced Features Menu, page 24.
It shows software and version number. To determine the software ver­sion of a meter:
1. Go to the Information menu (info) and press Enter/Ack but-
ton. The number shown is the software number.
2. Press Enter/Ack again to display the release version.
Page 30
PD683 & PD688 Loop-Powered Meters Instruction Manual
30
OPERATION
Front Panel Buttons Operation
Button Symbol
Description
Press to enter or exit Programming Mode, view settings, or exit Max/Min readings
Press to reset Max/Min readings Press to manually bypass filtering
Press to display Max/Min readings alternately
Press to display Max/Min reading indefinitely while displaying Max/Min
Press ACK to acknowledge trend arrows
Page 31
PD683 & PD688 Loop-Powered Meters Instruction Manual
31
Maximum & Minimum Readings (Max& MiN)
The maximum and minimum (peak & valley) readings reached by the pro­cess are stored in the meter since the last reset or power-up. The meter shows MIN or MAX to differentiate between run mode and max/min display.
1. Press Up arrow/Max button to display maximum reading since the last reset/power-up.
2. Press Up arrow/Max again to display the minimum reading since the last reset/power-up.
3. Press Enter/Ack to hold Max/Min display reading, the meter will continue to track new Max/Min readings.
4. If Enter/Ack is not pressed, the Max/Min display reading will time out after ten seconds and the meter will return to display the actual reading.
5. Press Right arrow/Reset button to reset Max/Min while reading is being displayed. Max/Min display readings are reset to actual reading.
Press Up to Display and to Toggle Between Max & Min
10 Sec Time Out
9.2846GPS
Run Mode
9.5320MAX
6.1391MIN
Press Enter to hold Max/Min
Press Right to Reset Max/Min
Press Menu to Exit Max/Min
Page 32
PD683 & PD688 Loop-Powered Meters Instruction Manual
32
MOUNTING DIMENSIONS
Figure 5. Meter Dimensions – Side View
Figure 6. Case Dimensions – Top View
1.76"
(45mm)
0.59"
(15mm)
3.2"
(81mm)
2.45"
(62mm)
3.61"
(92mm)
2.50"
(64mm)
4.68"
(119mm)
Page 33
PD683 & PD688 Loop-Powered Meters Instruction Manual
33
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to de­termine what’s happening, it might be better to start the setup process from the factory defaults.
Instructions to load factory defaults:
1. Enter the Advanced features menu. See Advanced Features Menu, page 24.
2. Press Up arrow until info is shown.
3. Press and hold Right arrow/Reset for five seconds, press Enter/Ack when display flashes reset. Note: If Enter/Ack is not pressed within three seconds, display re­turns to Information menu.
4. The meter goes through an initialization sequence (same as on power-up), and loads the factory default settings.
reset
info
Press and Hold for 5 Sec
Meter Re-
Initializes
Press and Hold for 3 Sec
Flashing Display
Page 34
PD683 & PD688 Loop-Powered Meters Instruction Manual
34
Factory Defaults & User Settings
The following table shows the factory setting for most of the program­mable parameters on the meter. Next to the factory setting, the user may record the new setting for the particular application.
Model: ______________ S/N: _______________ Date: _________
Parameter Display Default Setting User Setting
Programming
prog
Scale
Input 1
inPt1
4.000 mA
Display 1
Dspl1
4.000
Input 2
inPt2
20.00 mA
Display 2
Dspl2
20.000
Decimal point
Dd.ddd
3 places
Bargraph
GrapH
On (enabled)
Bargraph 0%
0 PCT
4.000
Bargraph 100%
100 PCT
20.000
Password
pass
00000 (unlocked)
Advanced Features
Function
Funct
Linear
Contrast
contr
5 (55555)
Cutoff
Cutof
-99999 (disabled)
Filter
Flter
1
Bypass
Bypas
0.2
Trend Arrows
Trend
On (enabled)
Page 35
PD683 & PD688 Loop-Powered Meters Instruction Manual
35
TROUBLESHOOTING
The rugged design and the user-friendly interface of the meter should make it unusual for the installer or operator to refer to this section of the manual.
If the meter is not working as expected, refer to the recommendations below.
Troubleshooting Tips
Symptom Check/Action
No display or faint display
1. Check connections.
2. Increase contrast setting in
Advanced menu.
3. Perform hard reset by temporarily shorting S+ and S- terminals for a few seconds.
Rate display unsteady
Increase filter setting in
Advanced
menu.
Not able to change setup or pro­gramming,
Locd is displayed
Meter is locked, enter correct five-digit password to unlock.
Meter displays error message dur­ing calibration (
error)
Check:
1. Signal connections
2. Minimum input span requirements
Meter displays
• 99999
• -99999
Check:
1. Input signal within range.
2. When using square root or pro­grammable exponent, cutoff must be zero or greater.
Display stuck showing a number and
MAX or MIN
Press
Menu to exit Max/Min
display readings.
Display response is too slow
Check filter and bypass values to see if they can be lowered.
If the display locks up or the meter does not respond at all
Perform hard reset by temporarily short­ing S+ and S- terminals for a few sec­onds and then removing short.
Display shows blurry, hard-to-read digits in below freezing tempera­tures (less than -18°C or 0°F).
Increase the filter setting to 10 or greater and the bypass setting to 50 or greater. This will slow the display re­sponse rate, but digits will be steady and appear more clearly.
Other symptoms not described above
Call Technical Support for assistance.
Page 36
PD683 & PD688 Loop-Powered Meters Instruction Manual
36
QUICK USER INTERFACE REFERENCE GUIDE
Run Mode
Setup
Program
Password
Display
Max/Min
Decimal
ddddd
d . dddd
dd . ddd
ddd . dd
Locked Unlocked
Bargraph
Calibrate
To Password
dddd . d
Scale
Units
On
Off
Page 37
PD683 & PD688 Loop-Powered Meters Instruction Manual
37
*Access by holding Right/Reset for 3 seconds
Pushbutton Function Menu Go to Programming Mode or leave Programming, Advanced
Features, and Max/Min Modes.
Right Arrow Move to next digit or decimal point position. Reset Total. Up Arrow Move to next selection or increment digit. Go to Max/Min Mode. Enter/Ack Accept selection/value and move to next selection. Toggle Rate/
Total.
Hold to Acknowledge Alarm.
Menu held for 5 seconds enters Advanced Features
Max/Min Mode
While in Run Mode, pressing Up Arrow will initiate Max/Min Mode. Up Arrow toggles between Max & Min displays, and Right Arrow resets the Max/Min to the current value. Press Menu or wait 10 seconds to return to Run Mode. Pressing Enter/Ack will disable the 10 second timeout and continuously display Max or Min.
Press & hold Menu for 5 seconds to access Advanced Features Menu
When a password is enabled, parameter settings are locked, but scale settings can be displayed by selecting the program menu.
Program
Run
Max &
Min
Advanced
Features
Up Arrow
Menu
Menu
Menu
Menu
Operational Modes
Function
Filter
Bypass
Trend
Arrows
Initial
Calibrate
Information
Menu for 5
seconds
Linear
Square Root
Programmable
Exponent
Cutoff
On
Off
Software
Version
*Factory Defaults
Contrast
Page 38
EU DECLARATION OF CONFORMITY FOR PD688
Issued in accordance with ISO/IEC 17050-1:2004 and ATEX Directive 2014/34/EU.
We,
Precision Digital Corporation 233 South Street Hopkinton, MA 01748 USA
as the manufacturer, declare under our sole responsibility that the product(s),
Model PD688 Loop Powered Panel Meter
to which this declaration relates, is in conformity with the European Union Directives shown below:
2014/35/EU Low Voltage Directive 2014/34/EU ATEX Directive 2014/30/EU EMC Directive 2011/65/EU RoHS Directive
This conformity is based on compliance with the application of harmonized or applicable technical standards and, when applicable or required, a European Union notified body certification.
Standards:
EN 60079-0:2006 EN 60079-11:2007 EN 60079-26:2007 EN 61010-1:1995 EN 61326:2006
The standards EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007, EN 61010­1:1995, and EN 61326:2006 are no longer harmonized. The requirements of these standards have been checked against the harmonized standard EN 60079­0:2012+A11:2013, EN 60079-11:2012, EN 60079-26:2015, EN 61010-11:2010, and EN 61326:2013 and there were no major technical changes affecting the latest technical knowledge for the products listed above.
EC Type Examination Certificate: FM08ATEX0058X
Product Markings: II 1 G
Ex ia IIC T4 Tamb = -40°C to +65°C
ATEX Notified Body for EC Type Examination Certificate:
FM Approvals Ltd., NB 1725 1 Windsor Dials Windsor, Berkshire, SL4 1RS, UK
ATEX Quality Assurance Notification No.:
SIRA 10 ATEX M462 ATEX Notified Body for Quality Assurance: Sira Certification Service, NB 0518 Rake Lane Eccleston, Chester, CH4 9JN, UK
Signed for and on behalf of Precision Digital Corporation:
Name: Jeffrey Peters Company: Precision Digital Corporation Title: President Date: 04/20/2016
Document No: DoC PD688 {042016}
Page 39
EU DECLARATION OF CONFORMITY FOR PD683
Issued in accordance with ISO/IEC 17050-1:2004.
We,
Precision Digital Corporation 233 South Street Hopkinton, MA 01748 USA
as the manufacturer, declare under our sole responsibility that the product(s),
Model PD683 Loop Powered Panel Meter
to which this declaration relates, is in conformity with the European Union Directives shown below:
2014/35/EU Low Voltage Directive 2014/30/EU EMC Directive 2011/65/EU RoHS Directive
This conformity is based on compliance with the application of harmonized or applicable technical standards and, when applicable or required, a European Union notified body certification.
Standards:
EN 60079-0:2006 EN 60079-11:2007 EN 60079-26:2007 EN 61010-1:1995 EN 61326:2006
The standards EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007, EN 61010­1:1995, and EN 61326:2006 are no longer harmonized. The requirements of these standards have been checked against the harmonized standard EN 60079­0:2012+A11:2013, EN 60079-11:2012, EN 60079-26:2015, EN 61010-11:2010, and EN 61326:2013 and there were no major technical changes affecting the latest technical knowledge for the products listed above.
Product Markings:
Signed for and on behalf of Precision Digital Corporation:
Name: Jeffrey Peters Company: Precision Digital Corporation Title: President Date: 04/20/2016
Document No: DoC PD683 {042016}
Page 40
PD683 & PD688 Loop-Powered Meters Instruction Manual
LIM688_K
SFT037 Ver 1.210 & up
04/16
How to Contact Precision Digital
• For Technical Support:
Call: (800) 610-5239 or (508) 655-7300
Fax: (508) 655-8990
• For Sales Support:
Call: (800) 343-1001 or (508) 655-7300
Fax: (508) 655-8990
• For the latest version of this manual please visit:
www.predig.com