Precision Digital PD6363-6R3, PD6363-6R0, PD6363-6H0, PD6363-6R5, PD6363-6H5 User manual

...
Page 1
PROVU PD6363 Dual Pulse Input Rate/Totalizer
Instruction Manual
R
P
V
S
USB Install
Rate/Totalizer
U
ERIES
®
Two (2) Pulse, Open Collector, NPN, PNP, TTL,
Switch Contact, Sine Wave (Coil), Square Wave Inputs
Displays Two Flow Inputs SimultaneouslyDisplays Rate and Total SimultaneouslyMath Functions Capabilities5, 10, or 24 V Flowmeter Power SupplyCount Up or Down, Total & Grand TotalGate Function for Rate Display of Slow Pulse RatesK-Factor, Internal Scaling, or External CalibrationNon-Resettable Grand TotalDual-Line DisplayNEMA 4X and IP65 Rated Front PanelUL Listed & CE MarkedDisplay Features 0.6" & 0.46" DigitsSix Full Digits on Each LineOptional Superluminous Sunlight Readable DisplayFree USB Programming Software & Cable2 or 4 Relays + Isolated 4-20 mA Output OptionsModbus® RTU Communication Protocol Standard
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 2
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
g
Disclaimer
The information contained in this document is subject to change without notice. Precision Digital makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
!
CAUTION: Read complete
instructions prior to installation and operation of the meter.
Warnin
This product is not recommended for life support applications or applications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. Precision Digital Corporation shall not be held liable for damages resulting from such improper use.
WARNING: Risk of electric shock or personal injury.
!
Limited Warranty
Precision Digital Corporation warrants this product against defects in material or workmanship for the specified period under “Specifications” from the date of shipment from the factory. Precision Digital’s liability under this limited warranty shall not exceed the purchase value, repair, or replacement of the defective unit.
Registered Trademarks
PROVU® and MeterView® Pro are registered trademarks of Precision Digital Corporation. Modbus® is a Registered Trademark of Schneider Automation Inc. All other trademarks mentioned in this document are the property of their respective owners.
© 2017 Precision Digital Corporation. All rights reserved.
2
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 3
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Table of Contents
Table of Contents ----------------------------------------- 3 Table of Figures ------------------------------------------- 4 Introduction ------------------------------------------------- 4 Ordering Information ------------------------------------ 5 Specifications ---------------------------------------------- 6
General ------------------------------------------------------------ 6 Dual Pulse Inputs ---------------------------------------------- 6 Dual Rate/Totalizer -------------------------------------------- 7 Relays ------------------------------------------------------------- 8 Isolated 4-20 mA Transmitter Output ------------------- 8 Modbus® RTU Serial Communications ---------------- 8 MeterView Pro -------------------------------------------------- 8
Compliance Information -------------------------------- 9
Safety -------------------------------------------------------------- 9 Electromagnetic Compatibility ---------------------------- 9
Safety Information -------------------------------------- 10 Installation ------------------------------------------------ 10
Unpacking ------------------------------------------------------ 10 Panel Mounting Instructions ----------------------------- 10
Mounting Dimensions ------------------------------------ 11
Transmitter Supply Voltage Selection (P+, P-) ---- 11 Connections --------------------------------------------------- 1 2
Connectors Labeling -------------------------------------- 12 Power Connections --------------------------------------- 12 Signal Connections --------------------------------------- 13
Configure Input Type and Level Switches ---------- 13
Modbus RTU Serial Communications ---------------- 14 Relay Connections ---------------------------------------- 14 Switching Inductive Loads ------------------------------- 14 F4 Digital Input Connections ---------------------------- 15 4-20 mA Output Connections --------------------------- 15 Analog Output Transmitter Power Supply ----------- 15 External Relay, Analog Output, & Digital I/O Connections ------------------------------------------------- 16 Interlock Relay Feature ---------------------------------- 16
Setup and Programming ------------------------------ 17
Front Panel Buttons and Status LED Indicators -- 17 MeterView® Pro Software --------------------------------- 18
MeterView Pro Installation ------------------------------ 18
Display Functions & Messages ------------------------- 19 Main Menu ----------------------------------------------------- 2 2 Setting Numeric Values ----------------------------------- 23 Setting Up the Meter (setup) ----------------------------- 23
Setting the Input Signal (Input) ----------------------- 24
Setting the Totalizer Features (total) ----------- 24 Setting the Dual-Input Mode (nmode) ------------- 24
Setting the Rate, Total, & Grand Total Units/Tags (units) ------------------------------------------------------- 26 Setting the Decimal Point (dEc pt) ------------------- 26 Programming the Rate/Totalizer (prog) ------------- 27
Input Calibration Method (InCAL) ------------------ 27 K-Factor Calibration (Fact-A, Fact-b) ----------- 27 Scaling the Meter without a Signal Source (SCAL-
A, SCAL-B) ----------------------------------------- 28
Scaling the Meter for Channel A (SCal-A) ------ 28 Error Message (Error) ------------------------------- 28
Calibrating the Meter with External Source (CAL-
A, CAL-B) ------------------------------------------- 29
Totalizer Setup (tsetup) ----------------------------- 30 Total & Grand Total Reset (treset) -------------- 30
Setting the Display Parameters & Intensity (dsplay)
----------------------------------------------------------------- 31 Setting the Relay Operation (relay) ----------------- 32
Setting the Relay Assignment (asSign) --------- 32 Setting the Relay Action (Act) ---------------------- 33 Programming Set and Reset Points -------------- 33 Setting Fail-Safe Operation ------------------------- 33 Programming Time Delay---------------------------- 33
Relay and Alarm Operation Diagrams ---------------- 34
High Alarm Operation (Set > Reset) ------------------ 34 Low Alarm Operation (Set < Reset) ------------------ 34 High Alarm with Fail-Safe Operation (Set > Reset)
----------------------------------------------------------------- 34 Low Alarm with Fail-Safe Operation (Set < Reset) 34 Pump Alternation Control Operation ------------------ 35 Relay Sampling Operation ------------------------------ 35 Total Relay Sampling Operation ----------------------- 36 Time Delay Operation ------------------------------------ 36
Relay Operation Details ----------------------------------- 37
Overview ----------------------------------------------------- 37 Relays Auto Initialization -------------------------------- 37 Fail-Safe Operation --------------------------------------- 37 Front Panel LEDs ----------------------------------------- 37 Latching and Non-Latching Relay Operation ------- 38 Non-Latching Relay (Auto) ----------------------------- 38 Non-Latching Relay (A-man) ------------------------- 38 Latching Relay (LatcH) ---------------------------------- 38 Latching Relay (Lt-Clr) --------------------------------- 38 Acknowledging Relays ----------------------------------- 39 Setting Up the Interlock Relay (Force On) Feature 39
Scaling the 4-20 mA Analog Output (Aout) --------- 39 Reset Menu (reset) ----------------------------------------- 40
Control Menu (Contrl) ------------------------------------- 40 Setting Up the Password (pass) ------------------------ 40
Protecting or Locking the Meter Functions ---------- 40 Total Reset Password & Non-Resettable Total ---- 41 Making Changes to a Password Protected Meter - 41 Disabling Password Protection ------------------------ 41
Advanced Features Menu -------------------------------- 42
Advanced Features Menu & Display Messages --- 42 Gate Function (Gate) ------------------------------------- 44 Contact De-Bounce Filter (FiLter) ------------------- 45 Rounding Feature (round) ------------------------------ 45 Modbus RTU Serial Communications (serial) --- 45 Select Menu (SElect) ------------------------------------ 46 Signal Input Conditioning (Functn) ------------------- 46
Multi-Point Linearization (Linear) ----------------- 46 Math Function (nmath) ----------------------------------- 47 Math Constants (Const) --------------------------------- 47 Low-Flow Cutoff (CutofF) ------------------------------- 48 Totalizer Count Up/Down (Count)--------------------- 48 Analog Output Programming (AoutPr) -------------- 48 Programmable Function Keys User Menu (user) - 49
Meter Operation ------------------------------------------ 51
Function Keys Operation --------------------------------- 51
3
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 4
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
F4 Operation -------------------------------------------------- 5 1 Front Panel Buttons Operation ------------------------- 51 Maximum/Minimum Readings --------------------------- 52
Troubleshooting ----------------------------------------- 52
Diagnostics Menu (diag) ---------------------------------- 52
Determining Software Version ------------------------- 52
Reset Meter to Factory Defaults ------------------------ 52
Factory Defaults & User Settings ---------------------- 53
Troubleshooting Tips -------------------------------------- 55
EU Declaration of Conformity ----------------------- 57
Table of Figures
Figure 1. 1/8 DIN Panel Cutout Dimensions .............. 10
Figure 2. Panel Mounting Details ............................... 10
Figure 3. Meter Dimensions - Side View ................... 11
Figure 4. Meter Dimensions - Top View .................... 11
Figure 5. Transmitter Supply Voltage Selection ....... 11
Figure 6. Connector Labeling for Fully Loaded
PD6363 ................................................................. 12
Figure 7. Power Connections ..................................... 12
Figure 8: Flowmeter Powered by Internal Power
Supply .................................................................. 13
Figure 9: Flowmeter Powered by External Supply ... 13 Figure 10: Self-Powered Magnetic Pickup Coil
Flowmeter ............................................................ 13
Figure 11: NPN open Collector Input ......................... 13
Figure 12: PNP Sensor Powered by Internal Supply 13
Figure 13: Switch Input Connections ......................... 13
Figure 14. Relay Connections ..................................... 14
Figure 15. AC and DC Loads Protection .................... 14
Figure 16. Low Voltage DC Loads Protection ........... 14
Figure 17. F4 Digital Input Connections .................... 15
Figure 18. 4-20 mA Output Connections .................... 15
Figure 19. Interlock Connections ............................... 16
Figure 20. Dual Input Mode (ud AB) ............................ 24
Figure 21. Dual Input Mode (ud AI) ............................ 24
Figure 22. Dual Input Mode (ud BI) ............................ 25
Figure 23. Dual Input Mode (quad 1) .......................... 25
Figure 24. Dual Input Mode (quad 2) .......................... 25
Figure 25. Dual Input Mode (quad 4) .......................... 25
Figure 26. Acknowledge Relays w/Function Key or
Digital Input .......................................................... 39
Introduction
The PROVU® PD6363 is a multipurpose, easy to use digital dual pulse input rate/totalizer ideal for flow rate, total, and flow control applications. Its superluminous LED digits make it easily readable in smoke, dust, fog, and, with the optional SunBright® display, even direct sunlight.
It accepts two pulse (e.g. 40 mVp-p to 8 Vp-p), square wave (0-5 V, 0-12 V, or 0-24 V), open collector, NPN, PNP, TTL or switch contact signals. Various math functions may be applied to the rate, total, or grand totals of the two channels; including addition, difference, average, minimum, maximum, draw, ratio and more.
The displays, relays, and the analog output may be assigned to the rate, total, or grand total of input channels A or B; or math result channel C. Three of the front panel buttons can be custom­programmed for a specific operation.
The basic model includes an isolated 24 VDC transmitter power supply that can be used to power the input transmitters or other devices. An additional isolated 24 VDC power supply is included with the 4-20 mA output option. A digital input is standard.
Meter capabilities may be enhanced with external expansion modules. External serial communication adapters are also available for use with MeterView Pro or Modbus RTU.
4
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 5
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Ordering Information
Standard Models
85-265 VAC Model 12-24 VDC Model Options Installed
PD6363-6R0 PD6363-7R0 No options PD6363-6R2 PD6363-7R2 2 relays (PD1102*) PD6363-6R3 PD6363-7R3 4-20 mA output (PD1103*) PD6363-6R4 PD6363-7R4 4 relays (PD1104*) PD6363-6R5 PD6363-7R5 2 relays & 4-20 mA output (PD1105*) PD6363-6R7 PD6363-7R7 4 relays & 4-20 mA output (PD1107*) *Model number for replacement option card.
SunBright Display Models
85-265 VAC Model 12-24 VDC Model Options Installed
PD6363-6H0 PD6363-7H0 No options PD6363-6H2 PD6363-7H2 2 relays (PD1102*) PD6363-6H3 PD6363-7H3 4-20 mA output (PD1103*) PD6363-6H4 PD6363-7H4 4 relays (PD1104*) PD6363-6H5 PD6363-7H5 2 relays & 4-20 mA output (PD1105*) PD6363-6H7 PD6363-7H7 4 relays & 4-20 mA output (PD1107*) *Model number for replacement option card.
Accessories
Model Description
PDA1002 DIN rail mounting kit for two expansion modules PDA1004 4 SPST (Form A) relays PDA1011 Dual isolated 4-20 mA output expansion module PDA1044 4 digital inputs & 4 digital outputs (2 may be connected) PDA1232 RS-232 serial adapter PDA1485 RS-485 serial adapter PDA7485-I RS-232 to RS-422/485 isolated converter PDA7485-N RS-232 to RS-422/485 non-isolated converter PDA8232-N USB to RS-232 non-isolated converter PDA8485-I USB to RS-422/485 isolated converter PDA8485-N USB to RS-422/485 non-isolated converter PDX6901
Suppressor (snubber): 0.01 µF/470 , 250 VAC
5
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 6
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Specifications
Except where noted all specifications apply to operation at +25°C.
General
Display Line 1: 0.60" (15 mm) high, red LEDs
Display Intensity
Display Update Rate
Overrange
Display Assignment
Programming Methods
Max/Min Display
Password Three programmable passwords restrict
Recalibration All ranges are calibrated at the factory.
Non-Volatile Memory
Power Options
Line 2: 0.46" (12 mm) high, red LEDs 6 digits each (-99999 to 999999), with lead zero blanking
Eight user selectable intensity levels
Rate: 10 per second; up to 1 per 100 seconds (and is a function of Low Gate setting); Total: 10 per second (fixed)
Display flashes Display lines 1 & 2 may be assigned to
show:
One or more rate/math channels: Channel A (Ch-A), B (Ch-B), or C (Ch­C)
Toggle rate/math channels: Ch-A & Ch­B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch­A, Ch-B, & Ch-C
Total or grand total: Ch-A or Ch-B Rate and total or grand total: Ch-A or
Ch-B Relay set points Max and/or min values: Ch-A, Ch-B, or Ch-C Toggle between any rate/math channel
& units Total and units: Ch-A or Ch-B Toggle between totals: Ch-A & Ch-B;
Ch-A, Ch-B, and sum of Ch-A and Ch-B
Modbus input The lower display may also be set to show engineering units or be off, with no display.
Four front panel buttons, digital inputs, PC and MeterView Pro software, or Modbus registers.
Max/min readings reached by the process are stored until reset by the user or until power to the meter is cycled.
modification of programmed settings and two prevent resetting the totals.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs. Total: Prevents resetting the total manually Gtotal: Prevents resetting the grand total manually
Recalibration is recommended at least every 12 months.
All programmed settings are stored in non­volatile memory for a minimum of ten years if power is lost.
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC 10%, 15 W max
Powered over USB for configuration only
999999
Fuse Required external fuse: UL Recognized, 5 A
Isolated Transmitter Power Supply
Isolation 4 kV input/output-to-power line
Overvoltage Category
Environmental Operating temperature range: -40 to 65°C
Connections Removable screw terminal blocks accept 12
Enclosure 1/8 DIN, high impact plastic, UL 94V-0,
Mounting 1/8 DIN panel cutout required:
Tightening Torque
Overall Dimensions
Weight 9.5 oz (269 g) Warranty 3 years parts & labor
max, slow blow; up to 6 meters may share one 5 A fuse
Terminals P+ & P-: 24 VDC 10%. Selectable for 24, 10, or 5 VDC supply (internal jumper J4). 85-265 VAC models rated @ 200 mA max, 12­24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
500 V input-to-output or output-to-P+ supply
Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non-condensing
to 22 AWG wire, RJ45 for external modules and adapters.
color: black
3.622" x 1.772" (92 mm x 45 mm) Two panel mounting bracket assemblies are provided.
Screw terminal connectors: 5 lb-in (0.56 Nm)
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Dual Pulse Inputs
Two Inputs Field selectable: Pulse or square wave 0-5
Channels Channel A, Channel B, Channel C (Math
Programmabl e Constants
Low Voltage Mag Pickup
Minimum Input Frequency
Maximum Input Frequency
Input Impedance
V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 k pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7 k pull-up to 5 V @ 40 Hz; Modbus PV (Slave)
channel) Constant P (Adder): -99.999 to 999.999,
default: 0.000 Constant F (Factor): 0.001 to 999.999, default: 1.000
Sensitivity: 40 mVp-p to 8Vp-p
0.001 Hz Minimum frequency is dependent on high gate setting.
30,000 Hz (10,000 for low voltage mag pickup)
Pulse input: Greater than 300 k @ 1 kHz. Open collector/switch input: 4.7 k pull-up to 5 V.
6
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 7
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Math Functions Name Function Setting Addition (A+B+P)*F Sunm
Difference (A-B+P)*F diF Absolute diff. ((Abs(A-B))+P)*F diFAbS Average (((A+B)/2)+P)*F AvG Multiplication ((A*B)+P)*F nmulti Division ((A/B)+P)*F divide Max of A or B ((AB-Hi)+P)*F Hi-Ab Min of A or B ((AB-Lo)+P)*F Lo-Ab Draw ((A/B)-1)*F drAuw Weighted avg. ((B-A)*F)+A uw avg Ratio (A/B)*F ratio
Ratio 2 ((B-A)/A)+P)*F ratio2 Concentration (A/(A+B))*F Concen Total Addition (tA+tB+P)*F Sunm t G. Tot. Addition (GtA+GtB+P)*F SunmGT Total Difference (tA-tB+P)*F Dif t G. Tot. Difference (GtA-GtB+P)*F Dif GT Total Ratio (tA/tB)*F Tratio Total Ratio 2 ((tB-tA)/tA)*F t-rat2 Total Percent (tA/(tA+tB))*100 T PCT Note: The F constant can be any value from 0.001 to 999.999. If the value is less than 1, it will have the same effect as a
divider. For example, the average could also be derived by using (A+B)*F, where F = 0.500.
Sequence of Operations for Input Programming
Accuracy ±0.03% of calibrated span ±1 count
Temperature Drift
Multi-Point Linearization
Low-Flow Cutoff
Decimal Point Up to five decimal places or none:
1. Select Input for A and B
2. Set up the rate, total, and grand total
engineering units for channels A & B, and units for math channel C
3. Set up rate, total, and grand total
decimal points for channels A & B, and decimal point for math channel C
4. Program channel A & B rate
parameters
5. Program channel A & B total and reset
parameters
6. Set up display lines 1 & 2 and display
intensity
7. Select the transfer function for A & B
(e.g. Linear)
8. Select Math function for Channel C
9. Program constants for Factor (F) and
Adder (P).
10. Program cutoff values for A and B
Rate display is not affected by changes in temperature.
2 to 32 points for channel A and B
0-999999 (0 disables cutoff function)
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Calibration May be calibrated using K-factor, internal
calibration, or by applying an external calibration signal.
K-Factor Field programmable K-factor converts input
pulses to rate in engineering units. May be programmed from 0.00001 to 999,999 pulses/unit.
Calibration Range
Filter
Time Base Second, minute, hour, or day
Gate Low gate: 0.1-99.9 seconds
F4 Digital Input Contacts
F4 Digital Input Logic Levels
Input 1 signal may be set anywhere in the range of the meter; input 2 signal may be set anywhere above or below input 1 setting.
Minimum input span between any two inputs is 10 Hz. An error message will appear if the input span is too small.
Programmable contact de-bounce filter: 40 to 999 Hz maximum input frequency allowed with low speed filter.
High gate: 2.0-999.9 seconds
3.3 VDC on contact. Connect normally open contacts across F4 to COM.
Logic High: 3 to 5 VDC Logic Low: 0 to 1.25 VDC
Dual Rate/Totalizer
Rate Display Indication
Total Display & Total Overflow
Total Decimal Points
Dual Totalizer Calculates total for channels A and B based
Totalizer Rollover
Total Overflow
Override
Totalizer Alarm Presets
Total & Grand Total Reset
Total Reset Password
-99999 to 999999, lead zero blanking.
0 to 999,999; automatic lead zero blanking. Up to 999,999,999 with total-overflow feature.
oF” is displayed to the left of total overflow
“ and ▲ LED is illuminated.
Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Total decimal point is independent of rate decimal point. Channel A and B decimal points programmed independently.
on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed. Channel A and B totalizer parameters programmed independently.
Totalizer rolls over when display exceeds 999,999,999. Relay status reflects display.
Program total A or B total reset for automatic with 0.1 second delay and set point 1 for 999,999
Up to eight, user selectable under setup menu. Any set point can be assigned to channel A or B total or grand total (or C) and may be programmed anywhere in the range of the meter for total alarm indication.
Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications. Channel A and B total and grand total reset parameters programmed independently.
Total and grand total passwords may be entered to prevent resetting the totals or grand totals from the front panel.
7
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 8
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Programmabl e Delay On Release
Non­Resettable Total
0.1 and 999.9 seconds; applied to the first relay assigned to total or grand total.
If the meter is programmed to reset total to zero automatically when the preset is reached, then a delay will occur before the total is reset.
The grand totals can be programmed as non-resettable totals by entering the password “050873”. Both channels are set to non-resettable when this password is entered.
Once the Grand Totals have been programmed as “non-
!
resettable” the feature cannot be
on!
disabled.
Cauti
Relays
Rating 2 or 4 SPDT (Form C) internal and/or 4
Noise Suppression
Relay Assignment
Deadband 0-100% of span, user programmable
High Or Low Alarm
Relay Operation
Relay Reset
Time Delay
Fail-Safe Operation
SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads
Noise suppression is recommended for each relay contact switching inductive loads; see page 14 for details.
Relays may be assigned to channel A or B rate, total, or grand total; channel C; or Modbus control.
User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turn off).
Automatic (non-latching) Latching (requires manual acknowledge) Sampling (based on time) Pump alternation control (2 to 8 relays) Off (disable unused relays and enable Interlock feature) Manual on/off control mode
User selectable via front panel buttons, digital inputs, or PC
Automatic reset only (non
1.
hen the input p
w
2.
Automatic + manual reset at any time (non-latching) Manual reset only, at any
3.
(latching)
4.
Manual reset only after alarm condition has cleared (L)
Note: Front panel button or digital input may
be assigned to acknowledge relays programmed for manual reset.
0 to 999.9 seconds, on & off relay time delays Programmable and independent for each relay
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will go to alarm state.
asses the reset point.
-latching),
time
Auto Initialization
When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output
Output Source
Scaling Range
Calibration Factory calibrated: 4.000 to 20.000 = 4-20
Analog Out Programming
Accuracy ± 0.1% of span ± 0.004 mA
Temperature Drift
Isolated Transmitter Power Supply
External Loop Power Supply
Output Loop Resistance
Input channels A or B, rate, total, or grand total; channel C; max or min for channel A or B; highest or lowest max or min of A and B; set points 1-8; Modbus input; or manual control mode
1.000 to 23.000 mA for any display range
mA output
23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
0.4 µA/C max from 0 to 65C ambient,
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
Terminals I+ & R: 24 VDC 10%. May be used to power the 4-20 mA output or other devices. Refer to Figure 6 on page 12 and Figure 18 on page 15.
All models rated @ 40 mA max.
35 VDC maximum
Power supply Minimum Maximum
24 VDC
VDC
35 (external)
10 700
100 1200
Modbus® RTU Serial Communications
Slave Id 1 – 247 (Meter address)
Baud Rate 300 – 19,200 bps
Transmit Time Delay
Data 8 bit (1 start bit, 1 or 2 stop bits)
Parity Even, Odd, or None with 1 or 2 stop bits
Byte-To-Byte Timeout
Turn Around Delay
Programmable between 0 and 199 ms
0.01 – 2.54 second
Less than 2 ms (fixed)
MeterView Pro
System Requirements
CommunicationsUSB 2.0 (Standard USB A to Micro USB
Configuration Configure meters one at a time
Microsoft® Windows® XP/Vista/7/8/10
B)
8
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 9
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Compliance Information
Safety
UL & c-UL Listed USA & Canada
UL 508 Industrial Control Equipment
UL File Number E160849 Front Panel UL Type 4X, NEMA 4X, IP65; panel gasket provided Low Voltage
Directive
Electromagnetic Compatibility
Emissions EN 55022:2010
Radiated Emissions
AC Mains Conducted Emissions
Immunity EN 61326-1:2013
RFI - Amplitude Modulated
Electrical Fast Transients
Electrostatic Discharge
RFI - Conducted 10V, 0.15-80 MHz, 1kHz 80% AM AC Surge ±2kV Common, ±1kV Differential Surge 1KV (CM) Power-
Frequency Magnetic Field
Voltage Dips 40%V for 5 & 50 periods
Voltage Interruptions
EN 61010-1:2010 Safety requirements for measurement, control, and laboratory use
Class A ITE emissions requirements Class A
Class A
Measurement, control, and laboratory equipment EN 61000-6-2:2005
EMC heavy industrial generic immunity standard 80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz) ±2kV AC mains, ±1kV other
±4kV contact, ±8kV air
30 A/m 70%V for 0.5 period
70%V for 25 periods <5%V for 250 periods
Note:
Testing was conducted on PD6300 Series meters installed through the covers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.
9
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 10
(
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Safety Information
!
CAUTION: Read complete
instructions prior to installation
WARNING: Risk of electric shock or personal injury.
and operation of the meter.
WARNING!
Hazardous voltages exist within enclosure. Installation and service should be performed only by trained service personnel.
Installation
There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applications.
Instructions are provided for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 11.
Unpacking
Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm). Refer to Figure 1
below, for more details.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.  Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼"
(6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Insert meter into the panel cutout.  Install mounting brackets and tighten the screws against the panel. To achieve a proper seal, tighten
the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
A
3.622" (92 mm)
Square Corners to 0.060"
B
1.772"
(45mm)
Figure 1. 1/8 DIN Panel Cutout Dimensions
1.5mm) Max Radius
Panel Cutout to DIN 43700
Tolerances: A: +0.032 (+0.8mm)
-0.000 (-0.0mm) B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Figure 2. Panel Mounting Details
10
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 11
Mounting Dimensions
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
O
-
N
+
R
N
C
N
C
N
C
C
O
O
C
N
C
O
N
N
C
N
C
Figure 3. Meter Dimensions - Side View
Figure 4. Meter Dimensions - Top View
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12-24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the wiring connectors.
2. Unscrew the back cover.
3. Slide out the back cover by about 1 inch.
4. Configure the J4 jumper, located behind the input signal connector, for the desired excitation voltage as shown.
Figure 5. Transmitter Supply Voltage Selection
11
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 12
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Connections
All connections are made to removable screw terminal connectors located at the rear of the meter.
Use copper wire with 60°C or 60/75°C insulation for all line voltage connections. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent
Caution!
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all connectors available with requested configuration.
Warning!
damage to the meter and ensure personnel safety.
Do not connect any equipment other than Precision Digital’s expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
Figure 6. Connector Labeling for Fully Loaded PD6363
Power Connections
Power connections are made to a two-terminal connector labeled POWER on Figure 6. The meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring convention.
POWER
-
+
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
Figure 7. Power Connections
12
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 13
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Signal Connections
Signal connections are made to a nine-terminal connector labeled SIGNAL on Figure 6. The COM (common) terminals are the return for certain input signals. The two COM terminals connect to the same common return, and are not isolated.
The following figures show examples of signal connections.
Figure 8: Flowmeter Powered by Internal
Power Supply
Figure 9: Flowmeter Powered by External
Supply
Figure 10: Self-Powered Magnetic
Pickup Coil Flowmeter Figure 11: NPN open Collector Input
Figure 12: PNP Sensor Powered by
Internal Supply
Figure 13: Switch Input Connections
Configure Input Type and Level Switches
Channel A and B each have an internal input type configuration switch. These switches must be set to the correct input type and level. Each switch can be set for mV, PNP, or NPN. For details on what input type to select, see Signal Connections
starting on page 13. To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Remove the back cover.
4. Configure the input selection switches for channel A and B, located behind the input connector on the far left, as needed.
5. Slide rear cover back onto the meter.
6. Screw the back cover on. Do not over tighten.
7. Replace all connectors.
13
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 14
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Modbus RTU Serial Communications
Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 6. For interfacing to the P used for interfacing with all expansion modules (e.g. external relays, additional 4-20 mA outputs, digital I/O).
®
ROVU
, use the PDA1232 for RS-232 or the PDA1485 for RS-485. The same port is
Relay Connections
Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 on Figure 6. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) contacts of the corresponding relay. The relays’ C terminals should not be confused with the COM (common) terminal of the INPUT SIGNAL connector.
RELAY4 RELAY3
4365 21
CNONO NC NC C
RELAY2 RELAY1
4365 21
CNONO NC NC C
Figure 14. Relay Connections
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as complete assemblies. Refer to the following circuits for RC network assembly and installation:
C
C
R
R
Figure 15. AC and DC Loads Protection
Choose R and C as follows: R: 0.5 to 1 Ω for each volt across the contacts C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC network may also be installed across the load. Experiment for best results.
Use a diode with a reverse breakdown voltage two to three times the circuit voltage and forward current at least as large as the load current.
Figure 16. Low Voltage DC Loads Protection
14
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 15
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
RC Networks Available from Precision Digital
RC networks are available from Precision Digital and should be applied to each relay contact switching an inductive load. Part number: PDX6901.
Note: Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input connected with a normally open closure across F4 and COM, or with an active low signal applied to F4.
Figure 17. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT. The 4-20 mA output may be powered internally or from an external power supply.
24 V
24 V
RELAY1
321
MA OUT
+
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
RI- I+
132
-
RELAY1
321
+
4-20 mA
Input Meter
-
MA OUT
-
+
12-35 VDC
Power Supply
RI- I+
132
Figure 18. 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
15
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 16
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
External Relay, Analog Output, & Digital I/O Connections
The relay, analog out, and digital I/O expansion modules PDA1004, PDA1011, and PDA1044 are connected to the meter using a CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are identical and interchangeable; they are used to connect additional modules to the system.
Note: The jumper located between the RJ45 connectors of the PDA1044 must be removed on the second
digital I/O module in order for the system to recognize it as module #2.
Do not connect or disconnect the expansion modules with the power on! More detailed instructions are provided with each
Warning!
optional expansion module.
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock relay. This feature is enabled by configuring the relay, and relative digital input(s) (see page 39). In one example, dry interlock contacts are connected in series to one digital input which will be used to force on (energize) the assigned interlock power relay when all interlock contacts are closed (safe). The interlock relay front panel LED flashes when locked out. The interlock relay would be wired in-series with the load (N/O contact). See below.
Figure 19. Interlock Connections
16
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 17
y
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Setup and Programming
The meter has been factory calibrated to read input frequency in Hz (pulses/sec). The calibration
equipment is certified to NIST standards.
Use the K-Factor menu to match the rate/totalizer with a flowmeter’s k-factor (pulse/unit of measure).  Or use the Scale menu to scale the pulse input (pulse/sec) without a signal source.  Or use Cal menu to calibrate the rate/totalizer using a signal source.
Overview
There are no jumpers to set for the meter input selection. Setup and programming is done through the front panel buttons. After power and input signal connections have been completed and verified, apply power to the meter.
Front Panel Buttons and Status LED Indicators
Button S
mbol
Notes: F4 is a digital input. Alarms
5-8 are enabled when relay expansion module installed.
Press the Menu button to enter or exit the Programming Mode at any time.  Press the Right arrow button to move to the next digit during digit or decimal point programming.  Press or hold the Up arrow button to scroll through the menus, decimal point, or to increment the
value of a digit.
Press the Enter button to access a menu or to accept a setting.  Press and hold the Menu button for three seconds to access the advanced features of the meter.
Description LED Status
Menu 1-8 Alarm 1-8 indicator
Right arrow/F1
Up arrow/F2
Enter/F3 1-4
1-8
Note: LEDs for relays in manual
mode flash with the “M” LED every 10 seconds.
Flashing: Relay in manual control
M
mode
A
Channel displayed
B
C
Flashing: Relay interlock switch open
17
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 18
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
MeterView® Pro Software
The meter can also be programmed using the PC-based MeterView Pro software included with the meter. This software can be installed on any Microsoft® Windows® (XP/Vista/7/8/10) computer by connecting the meter’s onboard USB. The meter is powered by the USB connection, so there is no need to wire anything prior to programming the meter, though USB is intended only for meter configuration.
MeterView Pro Installation
1.
Connect one end of the provided USB cable to the meter and the other end to the computer. The computer will automatically install the driver
Only one meter may be connected a A
ttaching multiple meters wi
conflict
2.
Once the driver is installed, an AutoPlay dialog should appear for the drive “MAINSTAL.” Click “O If the c drive “MAINS click on the drive labeled “MAINSTAL.”
3.
Double-click on the file named “MAStart.” The program will open a fe comp one of the dialogs below. If you receive a “User Ac Control”
4.
If there is an update available, click the “Update” button to install the ne prog
with the meter softw
omputer does not display
TAL,” you should open My Computer and double-
w windows and install two programs
uter. Simply follow the onscreen instructions until you see
warning, click “Yes.”
w version. Otherwise, click “Config
ramming your meter.
ll cause a
are.
t a time.
pen folder to view
an AutoPlay dialog for the
software it needs to talk to the meter.
files.”
on your
count
ure” to begin
Note: If you decide to update your MeterView Pro software, once the installatio will be asked if you want to update the setup files located on the meter itself. This way, you will always have the most current version on the meter for future installs.
Do not unplug the meter while the new installation files are being written to it. The meter will display notification once the process is complete.
ng!
Warni
Data logging for one meter at a time is available with MeterView Pro software. More advanced data acquisition may be accomplished by using any Modbus RTU compliant software. Additional information regarding configuration and monitoring of the meter using MeterView Pro software is available online.
18
Find Quality Products Online at: [email protected]
uwrite
www.GlobalTestSupply.com
during the process and you will receive an onscreen
n has completed, you
Page 19
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Display Functions & Messages
The following table shows the main menu functions and messages in the order they appear in the menu.
Display Parameter
setup
Input
Ch-A* Input
total
YES
No
mode
Dual
ud AB
ud A1
ud b1
ud b1
Quad 1
Quad 2
Quad 4
units
Ch-A* Rate unit
Ch-C
Tot-A* Total unit
Gtot-A*
Dec pt
Setup
Input
Total
Yes
No
Mode
Dual
Up/Down AB
Up/Down AI
Up/Down BI
Up/Down ABI
Quadrature 1
Quadrature 2
Quadrature 4
Unit
Math unit
Grand total unit
Decimal point
Action/Setting Description
Enter Setup menu
Enter Input selection menu
Set input operation for channel A (*or B)
Enable/disable totalizer functions
Enable totalizer functions
Disable totalizer functions
Select dual-input operation mode
Set independent dual input mode
Set channel A total add/subtract based on the state of channel B
Set channel A total add/subtract based on the state of a digital input
Set channel B total add/subtract based on the state of a digital input
Set channel A & B total add/subtract based on the state of a digital input for each
Set type 1 quadrature operation
Set type 2 quadrature operation
Set type 4 quadrature operation
Select the display units/tags
Set rate unit or tag for channel A (*or B)
Set unit or tag for math channel C
Set total unit or tag for channel A (*or B)
Set grand total unit or tag for channel A (*or B)
Set decimal point
Display Parameter
Ch-A*
Rate* Rate
Total* Total
Gtotal* Grand total
prog
InCAL
Ch-A
Fact-a
SCal-a
Cal-A
Inp 1
Dis 1
Inp 2
Dis 2
Error
Ch-b
Fact-b
SCal-b
Cal-b
tsetup
Ch-A* Channel A
tbase
Decimal point
Program
Input calibration
Channel A
K-factor A
Scale A
Calibrate A
Input 1
Display 1
Input 2
Display 2
Error
Channel B
K-factor B
Scale B
Calibrate B
Total setup
Time base
Action/Setting Description
Set decimal point for channel A (*or B or C)
Set rate decimal point (*channel A and B only)
Set total decimal point (*channel A and B only)
Set grand total decimal point (*channel A and B only)
Enter the Program menu
Enter the Input
Calibration menu
Enter channel A input setup
Enter channel A k-factor
Enter the Scale menu for channel A
Enter the Calibration menu for channel A
Calibrate input 1 signal or program input 1 value
Program display 1 value
Calibrate input 2 signal or program input 2 value (up to 32 points)
Program display 2 value (up to 32 points)
Error, calibration or scaling not successful, check signal or programmed value
Enter channel B input setup
Enter channel B k-factor
Enter the Scale menu for channel B
Enter the Calibration menu for channel B
Enter the Total Setup menu
Setup the total for channel A (*or B)
Program total time base
19
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 20
t
w
w
w
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Display Parameter
T Cf
Gt CF
treset
Ch-A* Channel A
T rst
Gt rst
T dly
dsplay
Line 1
Line 2
D Ch-A
D Ch-B
D Ch-C
D Ab
D AC
D BC
D AbC
D t-a
D t-b
D gt-a
D gt-b
D rt-a
Total conversion factor
Grand total conversion factor
Total reset
Total reset
Grand total reset
Time delay
Display
Display Line 2
Display Line 2
Display Ch-A
Display Ch-B
Display Ch-C
Display AB
Display AC
Display BC
Display ABC
Display total A
Display total B
Display grand total A
Display grand total B
Display rate and total A
Action/Setting Description
Program total conversion factor
Program grand total conversion factor
Program total reset mode: auto or manual
Set total reset modes for channel A (*or B)
Program total reset mode: auto or manual
Program grand total reset mode: auto or manual
Program automatic reset time delay
Enter the Display menu
Assign the upper display parameter
Assign the lower display parameter
Assign display to channel A
Assign display to channel B
Assign display to channel C (math)
Alternate display of channels A & B
Alternate display of channels A & C
Alternate display of channels B & C
Alternate display of channels A, B, & C
Assign display to channel A total
Assign display to channel B total
Assign display to channel A grand total
Assign display to channel B grand total
Alternate display of channel A rate and total
Display Parameter
D rt-b
Drgt-a
Drgt-b
Dset 1*
D Hi-A
D Lo-A
D HL-A
D Hi-B
D Lo-B
D HL-B
D Hi-C
D Lo-C
D HL-C
D a-u
D B-u
D C-u
D ta-u
Display rate and total B
Display rate and grand total A
Display rate and grand total B
Display Se 1*
Display high A
Display lo A
Display high/low A
Display high B
Display lo B
Display high/low B
Display high C
Display lo C
Display high/low C
Display A and units/tags
Display B and units/tags
Display C and units/tags
Display total A and total A units
Action/Setting Description
Alternate display of channel B rate and total
Alternate display of channel A rate and grand total
Alternate display of channel B rate and grand total
Displays relay 1(*through
8) set point.
Display high value of channel A
Display low value of channel A
Alternate between high/low value of channel A
Display high value of channel B
Display low value of channel B
Alternate between high/low value of channel B
Display high value of channel C
Display low value of channel C
Alternate between high/low value of channel C
Alternate display of channel A and the unit/tag
Alternate display of channel B and the unit/tag
Alternate display of channel C and the unit/tag
Alternate display of channel A total and total units
20
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 21
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Display Parameter
D tb-u
D tab
D TAbC
m bus
D off
D unit
d-Inty
RELaY
Assign
Asign1* Assign 1
Ch-A* Channel A*
Rate* Rate
Total* Total
Gtotal* Grand total
m bus
RLY 1* Relay 1
Act 1
Auto
Set 1
RST 1
A-nman
LatCH
Display total B and total B units
Display total A and B
Display total A, B, and sum of A and B
Display Modbus
Display off
Display unit
Display intensity
Relay
Assignmen t
Modbus
Action 1
Automatic
Set 1
Reset 1
Auto­manual
Latching
Action/Setting Description
Alternate display of channel B total and total units
Alternate display of channel A total and channel B total
Alternate display of channel A total, channel B total, and sum of totals as channel C
Display Modbus input register
Display blank line 2
Display line 1 channel units
Set display intensity level from 1 to 8
Enter the Relay menu
Assign relays to channels or Modbus
Relay 1 (*through 8) assignment
Assign relay to channel A (*or B or C)
Assign relay to rate (*channel A and B only)
Assign relay to total (*channel A and B only)
Assign relay to grand total (*channel A and B only)
Assign relay to Modbus register
Relay 1 (*through 8) setup
Set relay 1 action
Set relay for automatic reset
Enter relay 1 set point
Enter relay 1 reset point
Set relay for auto or manual reset any time
Set relay for latching operation
Display Parameter
Lt-CLr
Altern
SAmpl
Off
FaiLSF
FLS 1* Fail-safe 1
on
off
DeLAY
DLY 1* Delay 1
On 1
OFF 1
Aout
Aout 1* Aout
Dis 1
Out 1
Dis 2
Out 2
reset
Rst Hi
Rst Lo
Rst HL
Tot a
Tot b
Gtot a
Latching­cleared
Alternate
Sample
Off
Fail-safe
On
Off
Delay
On 1
Off 1
Analog output
Channel
Display 1
Output 1
Display 2
Output 2
Reset
Reset high
Reset low
Reset high & low
Reset total A
Reset total B
Reset grand total A
Action/Setting Description
Set relay for latching operation with manual reset only after alarm condition has cleared
Set relay for pump alternation control
Set relay for sample time trigger control
Turn relay off
Enter Fail-safe menu
Set relay 1 (*through 8) fail-safe operation
Enable fail-safe operation
Disable fail-safe operation
Enter relay Time Delay menu
Enter relay 1 (*through 8) time delay setup
Set relay 1 On time delay
Set relay 1 Off time delay
Enter the Analog output scaling menu
Analog Output source channel (*1-3)
Program display 1 value
Program output 1 value (e.g. 4.000 mA)
Program display 2 value
Program output 2 value (e.g. 20.000 mA)
Press Enter to access the
Reset menu
Press Enter to reset max display
Press Enter to reset min display
Press Enter to reset max & min displays
Press Enter to reset channel A total
Press Enter to reset channel B total
Press Enter to reset channel A grand total
21
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 22
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Display Parameter
Gtot b
Tot ab
Gt ab
Contrl
Auto
mAn
pass
Reset grand total B
Reset totals A and B
Reset grand totals A and B
Control
Automatic
Manual
Password
Action/Setting Description
Press Enter to reset channel B grand total
Press Enter to reset channels A and B totals
Press Enter to reset channels A and B grand totals
Enter Control menu
Press Enter to set meter for automatic operation
Press Enter to manually control relays or analog output operation
Enter the Password menu
Display Parameter
Pass 1
unloc
Locd
Pass 2
Pass 3
Total
Gtotal
999999
Password 1
Unlocked
Locked
Password 2
Password 3
Total reset password
Grand total password
Flashing
Action/Setting Description
Set or enter Password 1
Program password to lock meter
Enter password to unlock meter
Set or enter Password 2
Set or enter Password 3
Set or enter a total reset password
Set or enter a grand total reset password
Overrange condition
Main Menu
The main menu consists of the most commonly used functions: Reset, Control, Setup, and Password. Press Menu button to enter
Programming Mode then press the Up arrow button to scroll main menu.
Press Menu, at any time, to exit and
return to Run Mode. Changes made to settings prior to pressing Enter are not saved.
Changes to the settings are saved to
memory only after pressing Enter.
The display moves to the next menu
every time a setting is accepted by pressing Enter.
22
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 23
V
A
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select next digit and Up arrow to increment digit value. The digit being changed is displayed brighter than the rest. Press and hold Up to auto-increment the display value. If negative numbers are allowed, the first digit position will include a negative symbol (-) after the 9.
Press the Enter button, at any time, to accept a setting or Menu button to exit without saving changes.
Select
Next Digit
004.000
Increment
004.000
dis 1 dis 1 dis 1
Digital
alue
005.000
ccept
Setting
Next
Setting
Setting Up the Meter (setup)
The Setup menu is used to select:
1. Total enable/disable and channel A and B input modes
2. Units for A & B rate, total & grand total, and C
3. Decimal positions for A & B rate, total, and grand total, and C
4. Program the K-factor (or scale or calibrate) & total functions
5. Display parameters and intensity
6. Relay assignments and operation
7. 4-20 mA analog output scaling
Press the Menu button to exit at any time.
23
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 24
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Setting the Input Signal (Input)
There are two internal slide switches, located inside the rear meter housing to the left of the input connector, which must be configured according to the input levels and types. See Configure Input Type and Level Switches on page 13 for details.
Enter the Input menu to enable or disable the totalizer features.
Setting the Totalizer Features (total)
To simply not display the total, select alternative display parameters in the display (dsplay) menu. Enable or disable the totalizer features by selecting “Yes” or “no” after the input type has been set up. If
the totalizer features are disabled, most totalizer features and functions are hidden from the menus.
Note: The totalizer continues working in the background.
Setting the Dual-Input Mode (nmode)
The Mode menu is used to set the functions of the dual input and total. The inputs may be configured for independent one-directional total operation, bi-directional total count with the use of another input or a digital input, or for quadrature input modes.
Independent Dual Totalizers (DUAL)
Total A and B are one-directional and independent, only counting up or down depending on Count settings.
Ch-A Totalizer Add/Subtract by Ch-B Input (ud AB)
Total of channel A will add or subtract as determined by the state of input channel B. Channel A total will add at each falling edge if input B is high, and subtract at each rising edge if input B is low.
Figure 20. Dual Input Mode (ud AB)
Ch-A Totalizer Add/Subtract by Digital Input (ud AI)
Total of channel A will add or subtract as determined by the state of a digital input. Channel A total will add at each falling edge if an assigned digital input is high, and subtract at each rising edge if an assigned digital input is low.
Figure 21. Dual Input Mode (ud AI)
24
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 25
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Ch-B Totalizer Add/Subtract by Digital Input (ud BI)
Total of channel B will add or subtract as determined by the state of a digital input. Channel B total will add at each falling edge if an assigned digital input is high, and subtract at each rising edge if an assigned digital input is low.
Ch-A & Ch-B Totalizer Add/Subtract by Digital Input (ud aB)
Totals of channel A and B will add or subtract as determined by the state of a digital input assigned to each channel. This mode combines the features of ud AI and ud BI.
This setting requires the use of a digital input expansion module (see Accessories on page 5). The F4 digital input will only support one channel.
Quadrature Input Type 1 (quad 1)
Quadrature modes are used to accept inputs that are ±90 degrees out of phase, from quadrature output devices. Total of channel A will add or subtract as determined by the state of input channel B. Channel A total will add at each rising edge if channel B is high, and subtract at each rising edge if channel B is low.
Figure 22. Dual Input Mode (ud BI)
Figure 23. Dual Input Mode (quad 1)
Quadrature Input Type 2 (quad 2)
Quadrature modes are used to accept inputs that are ±90 degrees out of phase, from quadrature output devices. Total of channel A will add or subtract as determined by the state of input channel B. Channel A total will add at each rising edge if channel B is high, and at each falling edge if channel B is low. Channel A total will subtract at each rising edge if channel B is low, and at each falling edge if channel B is high.
Quadrature Input Type 4 (quad 4)
Quadrature modes are used to accept inputs that are ±90 degrees out of phase, from quadrature output devices. Totals of channel A and B will add at each rising and falling edge of that channel.
Figure 24. Dual Input Mode (quad 2)
Figure 25. Dual Input Mode (quad 4)
25
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 26
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Setting the Rate, Total, & Grand Total Units/Tags (units)
Enter the channel A and B rate, total, grand total, and math channel C units (or custom tags) that will be displayed if alternating units is selected in the units menu, or d unit is selected as the lower display parameter.
See the flow chart on page 23 for details on accessing the Units menu and parameters. Ch-A and Ch-B set the rate units, tot-A and tot-B the total units, and Gtot-A and Gtot-B the grand total units. Ch-C sets the units for the math channel C.
See the flow chart on page 31 to access the display menu to show the unit or tag on the lower display. The engineering units or custom legends can be set using the following 7-segment character set:
Display Character Display Character Display Character Display Character
0 1 2 3 4 5 6 7 8 9
A b
Notes: Degree symbol represented by (<) if programming with MeterView two 7-segment LEDs each; when selected the characters to the right are shifted one position.
Press and hold up arrow to auto-scroll the characters in the display.
0
1
2
3
4
5
6
7
8
9
A
b
C c d e f g 9 H h I
I j
C
c
d
E
F
G
g
H
h
J
k l nm n O o p q r
I
i
s
t
u
K
L
m
n
O
o
P
q
r
S
t
u
®
Pro. The letters “m” and “w” use
v
uw
x y z
­/ [ ] = !
V
w
X
Y
Z
-
/ ]
[
=
Degree(<)
Space
Setting the Decimal Point (dEc pt)
The decimal point for any channel, rate, total, or grand total, may be set with up to five decimal places or with no decimal point at all.
Pressing the Right arrow moves the decimal point one place to the right until no decimal point is displayed, and then it moves to the leftmost position. Pressing the Up arrow moves the decimal point one place to the left.
There are seven decimal points to set up for three channels: Ch-A rate, total, and grand total; Ch-B rate, total, and grand total; and Ch-C.
After the decimal points are set up, the meter moves to the Program menu.
26
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 27
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Programming the Rate/Totalizer (prog)
It is very important that one reads the following information before programming the meter:
The meter has been factory calibrated to read input frequency in Hz (pulses/sec). The calibration
equipment is certified to NIST standards.
Use the K-Factor menu to match the rate/totalizer with a flowmeter’s k-factor (pulse/unit of measure).  Or use the Scale menu to scale the pulse input (pulse/sec) without a signal source.  Or use Cal menu to calibrate the rate/totalizer using a signal source.
The Program menu contains the following menus for each channel A and B:
1. K-Factor calibration
2. Scale without a signal source
3. Calibrate with a calibrated signal source
4. Total time base & conversion factor
5. Grand total time base & conversion factor
6. Reset modes for total & grand total
The pulse inputs may be calibrated or scaled to any display value within the range of the meter. Additional parameters, not needed for most applications, are found in the Advanced Features menu; see
Advanced Features Menu, page 42.
Input Calibration Method (InCAL)
There are three methods of calibrating (or scaling) the display for each input channel to show the correct engineering units.
Use the Factor menu to enter the k-factor of a flowmeter in units/pulse Use the Scale menu to enter the scaling without a signal source.  Use the Calibrate menu to apply a signal from a signal source.
Note: The Scale, Calibrate, and K-Factor functions are exclusive of each other. The meter uses the last function programmed. Only one of these methods can be employed at a time.
Multi-Point Calibration & Scaling
The Scale and Calibrate functions can use up to 32 points (default is 2). The number of points should be set in the Advanced menu under the Multi-Point Linearization (Linear) menu selection prior to scaling and calibration of the meter, see page 46 for details.
K-Factor Calibration (Fact-A, Fact-b)
The meter may be calibrated using the K-Factor function. Most flowmeter manufacturers provide this information with the device. Enter the K-Factor (Fact-A, Fact-b) menu and select the decimal point with highest resolution possible and program the k-factor value (i.e. pulses/gal). The meter will automatically calculate the flow rate using the k-factor and the time base selected.
27
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 28
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Scaling the Meter without a Signal Source (SCAL-A, SCAL-B)
The inputs can be scaled to display the process variables in engineering units. A signal source is not needed to scale the meter; simply program the inputs and corresponding display
values. From the INCAL menu, select channel A or B, followed by SCal-A or SCal-B, and then set the signal input
value and display value for each of the scaling points (default is two). Enter the signal input values in pulses/second (Hz), and the corresponding display values in appropriate engineering units. Channel B is scaled similarly to Channel A, shown below.
Scaling the Meter for Channel A (SCal-A)
“Saved” displays
for one second
prior to
Channel B
For instructions on how to program numeric values see
Setting Numeric
Values, page 23.
Note: The display values (DiS 1 and DiS 2) need to be in units of measure per second.
For example: If the rate at 1000 Hz is 13.2 gal/min, this must be converted to gal/sec. In this scenario,
the numbers input into the SCALE menu would be as follows:
InP 1: 0.0 DiS 1: 0.000 InP 2: 1000.0 DiS 2: 0.220
Set the time base set to minutes (see page 30) and the meter will display 13.2 gal/min at 1000 Hz
Error Message (Error)
An error message indicates that the calibration or scaling process was not successful. After the error message is displayed, the meter reverts to input 2 during calibration or scaling and to input
1 during internal calibration, allowing the appropriate input signal to be applied or programmed. The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals or it is connected backwards.
2. Minimum input span requirements not maintained.
3. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum allowed input span is 1.0 Hz, which is the minimum difference between input 1 and input 2 signals required to complete the calibration or scaling of the meter.
28
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 29
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Calibrating the Meter with External Source (CAL-A, CAL-B)
To scale the meter without a signal source, refer to Scaling the
Meter without a Signal Source (SCAL-A, SCAL-B), page 28.
Warm up the meter for at least 15 minutes before performing
calibration to ensure specified accuracy.
The meter can be calibrated to display the process variables in engineering units by applying the appropriate input signal and following the calibration procedure.
The use of a calibrated signal source is strongly recommended to calibrate the meter. Channel B is calibrated similarly to Channel A, shown below.
Calibrating the Meter for Channel A (CAL-A)
Note: The display values (DiS 1 and DiS 2) need to be in units of measure per second.
29
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 30
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Totalizer Setup (tsetup)
The time base and total and grand total conversion factors for input channels A and B are located in the Totalizer Setup menu.
The time base is determined by the rate programming. Enter the time unit of the programmed rate scale.
For example: A rate display scaled in engineering units of gallons per minute would use a time base of minutes.
Total & grand total conversion factors for channel A and B are programmed independently. This means that one total or grand total can be displaying the value in gallons while another displays in million gallons, liters, m
3
, etc.
Total & Grand Total Reset (treset)
Total reset menus are located in the Program menu. The totals can be programmed for manual or automatic reset. In the automatic reset mode, a programmable time delay (t dly) in seconds is available to reset the total or grand total after the assigned preset is reached.
30
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 31
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Setting the Display Parameters & Intensity (dsplay)
Display line 1 (line 1) can be programmed to display:
1. Ch-A rate (D Ch-A)
2. Ch-B rate (D Ch-B)
3. Ch-C math channel (D Ch-C)
4. Toggle Ch-A & Ch-B rate (D
AB)
5. Toggle Ch-A rate and Ch-C (D AC)
6. Toggle Ch-B rate and Ch-C (D BC)
7. Toggle Ch-A & Ch-B rate, and Ch-C (D ABC)
8. Ch-A total (D T-A)
9. Ch-B total (D T-B)
10. Ch-A grand total (D GT-A)
11. Ch-B grand total (D GT-B)
12. Toggle Ch-A rate and total (D RT-A)
13. Toggle Ch-B rate and total (D RT-B)
14. Toggle Ch-A rate and grand total (DRGT-A)
15. Toggle Ch-B rate and grand total (DRGT-B)
16. Relay set points (1-8) (DSET 1 to DSET 8)
17. Max, min, and max & min values for
Ch-A, Ch-B, or Ch-C (D Hi-A to d HL-C)
18. Toggle Ch-A rate & units (d A-u)
19. Toggle Ch-B rate & units (d B-u)
20. Toggle Ch-C & units (d C-u)
21. Toggle Ch-A total & units (d TA-u)
22. Toggle Ch-B total & units (d TB-u)
23. Toggle Ch-A total and Ch-B total (d tAb)
24. Toggle Ch-A total, Ch-B total, and the sum of total A and
total B (d tABC).
Notes: The sum of total A and B for t ABC is independent of channel C programming. Channel C may be used normally by a different display selection even when D tABC is selected for one of the two displays.
25. Modbus input (nm bus)
Display line 2 (Line 2) can be programmed to display:
1. All options for display line 1
2. Off, with no display (d ofF)
3. Engineering units for any single channel, total, or grand to
Display Intensity: The meter has eight display intensity levels to give the best performance under various lighting conditions. Select intensity 8 for outdoor applications. The default intensity setting is 8.
After setting up the input and display, press the Menu button to exit programming and skip the rest of the setup menu.
tal
31
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 32
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Setting the Relay Operation (relay)
This menu is used to set up the assignment and operation of the relays.
During setup, the relays do not follow the input
!
Caution!
1. Relay assignment
a. Channel A rate, total, or grand total b. Channel B rate, total, or grand total c. Channel C (Math channel) d. Modbus
2. Relay action
a. Automatic reset only (non-latching) b. Automatic + manual reset at
any time (non-latching)
c. Latching (manual reset
only)
d. Latching with Clear (manual
reset only after alarm condition has cleared)
e. Pump alternation control
(automatic reset only)
f. Sampling (the relay is
activated for a user­specified time)
g. Off (relay state controlled by
Interlock feature)
3. Set point
4. Reset point
5. Fail-safe operation
a. On (enabled) b. Off (disabled)
6. Time delay
a. On delay (0-999.9 seconds) b. Off delay (0-999.9 seconds)
and they will remain in the state found prior to entering the Relay menu.
Setting the Relay Assignment (asSign)
Relays may be assigned to Channel A (rate, total, or grand total), Channel B (rate, total, or grand total), Channel C (Math channel), or Modbus input.
32
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 33
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Setting the Relay Action (Act)
Operation of the relays is programmed in the Action menu. The relays may be set up for any of the following modes of operation:
1. Automatic reset (non-latching)
2. Automatic + manual reset at any time (non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after alarm condition has cleared)
5. Pump alternation control (automatic reset only)
6. Sampling (the relay is activated for a user-specified time)
7. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup; relay 2-8 are set up in a similar fashion.
Programming Set and Reset Points
High alarm indication: program set point above reset point. Low alarm indication: program set point below reset point. The deadband is determined by the difference between set and reset points. Minimum deadband is one display count. If the set and reset points are programmed with the same value, the relay will reset one count below the set point.
Note: Changes are not saved until the reset point has been accepted.
Setting Fail-Safe Operation
In fail-safe mode of operation, the relay coil is energized when the process variable is within safe limits and the relay coil is de-energized when the alarm condition exists. The fail-safe operation is set independently for each relay. Select on to enable or select off to disable fail-safe operation.
Programming Time Delay
The On and Off time delays may be programmed for each relay between 0 and 999.9 seconds. The relays will transfer only after the condition has been maintained for the corresponding time delay.
The On time delay is associated with the set point. The Off time delay is associated with the reset point.
33
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 34
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Relay and Alarm Operation Diagrams
The following graphs illustrate the operation of the relays, status LEDs, and ACK button.
High Alarm Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. To detect a new alarm condition, the signal must go below the set point, and then go above it.
Low Alarm Operation (Set < Reset)
For Manual reset mode, ACK can be pressed anytime to turn "off" relay. For relay to turn back “on”, signal must go above set point and then go below it.
High Alarm with Fail-Safe Operation (Set > Reset)
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will go to alarm state.
Low Alarm with Fail-Safe Operation (Set < Reset)
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will go to alarm state.
34
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 35
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Pump Alternation Control Operation
Relay Sampling Operation
Input
Set
Reset
Relay
LED
Sample
Tim e
Sample
Tim e
Sample
Tim e
When the signal crosses the set point, the relay trips and the sample time starts. After the sample time has elapsed, the relay resets. The cycle repeats every time the set point is crossed, going up for high alarms and going down for low alarms.
The sample time can be programmed between 0.1 and 5999.9 seconds.
35
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 36
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Total Relay Sampling Operation
Total
300
200
100
Preset = 100
Relay
LED
Sample
Time
Sample
Time
Sample
Time
When the total reaches the preset, the relay trips and the sample time starts. After the sample time has elapsed, the relay resets. The cycle repeats every time the preset value is added to the total.
Time Delay Operation
The following graphs show the operation of the time delay function.
When the signal crosses the set point, the On time delay timer starts and the relay trips when the time delay has elapsed. If the signal drops below the set point (high alarm) before the time delay has elapsed, the On time delay timer resets and the relay does not change state. The same principle applies to the Off time delay.
Note: If “Automatic or Manual (A-mAn)” reset mode is selected, the LED follows the reset point and not
the relay state when the relay is acknowledged.
36
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 37
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Relay Operation Details
Overview
The relay capabilities of the meter expand its usefulness beyond simple indication to provide users with alarm and control functions. These capabilities include front panel alarm status LEDs as well as either 2 or 4 optional internal relays and/or 4 external relays expansion module. Typical applications include high or low temperature, level, pressure or flow alarms, control applications such as simple on/off pump control, and pump alternation control for up to 8 pumps. There are four basic ways the relays can be used:
1. High or Low Alarms with Latching or Non-Latching Relays
2. Simple On/Off Control with 100% Adjustable Deadband
3. Sampling (Based on Time)
4. Pump Alternation Control for up to 8 Pumps
Relays Auto Initialization
When power is applied to the meter, the front panel LEDs and alarm relays will reflect the state of the input to the meter. The following table indicates how the alarm LEDs and relays will react on power-up based on the set and reset points.
Alarm #
1 HI 1000 500 499 Off 2 LO 700 900 499 On 3 LO 250 400 499 Off 4 HI 450 200 499 On
Fail-Safe Operation
The following table indicates how the relays behave based on the fail-safe selection for each relay:
Note: NO = Normally Open,
NC = Normally Closed. This refers to the condition of the relay contacts when the power to the meter is off.
Fail-Safe Selection
Off Open Closed Closed Open Relays go to
On Closed Open Open Closed Relays go to
Non-Alarm State Alarm State Power Failure
NO NC NO NC
Front Panel LEDs
The LEDs on the front panel provide status indication for the following:
The meter is supplied with four alarm points that include front panel LEDs to indicate alarm conditions. This standard feature is particularly useful for alarm applications that require visual­only indication. The LEDs are controlled by the set and reset points programmed by the user. When the display reaches a set point for a high or low alarm, the corresponding alarm LED will turn on. When the display returns to the reset point the LED will go off. The front panel LEDs responds differently for latching and non-latching relays.
For non-latching relays, the LED is always off during normal condition and always on during alarm condition, regardless of the state of the relay (e.g. Relay acknowledged after alarm condition).
For latching relays, the alarm LEDs reflects the status of the relays, regardless of the alarm condition. The following tables illustrate how the alarm LEDs function in relation to the relays and the acknowledge button (Default: F3 key assigned to ACK).
HI or LO
Alarm
Set
Point
LED Status LED Status
Reset Point
1 Alarm 1 5 Alarm 5 2 Alarm 2 6 Alarm 6 3 Alarm 3 7 Alarm 7 4 Alarm 4 8 Alarm 8
Power-Up
Reading
non-alarm state
alarm state
Relay
& LED
37
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 38
y
A
A
y
A
A
)
A
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Latching and Non-Latching Relay Operation
The relays can be set up for latching (manual reset) or non-latching (automatic reset) operation.
The On and Off terminology does not refer to the status of the relay’s coil, which depends on the fail-safe mode selected.
In latching relay mode, latched
Warning!
relays will reset (unlatch) when power is cycled.
Relay terminology for following tables
Terminology Relay Condition
On Alarm (Tripped) Off Normal (Reset)
Ack Acknowledged
Non-Latching Relay (Auto)
In this application, the meter is set up for automatic reset (non-latching relay). Acknowledging the alarm while it is still present has no effect on either the LED or the relay. When the alarm finally goes away, the relay automatically resets and the LED also goes off.
Condition LED Relay
Normal Off Off Alarm On On Ack (No effect) On On Normal Off Off
Automatic reset only
Non-Latching Relay (A-man)
In this application, the meter is set up for automatic and manual reset at any time (non-latching relay). The LED and the relay automatically reset when the meter returns to the normal condition. The next time an alarm occurs, the operator acknowledges the alarm manually while the alarm condition still exists. This causes the relay to reset, but the LED stays on until the meter returns to the normal condition.
Automatic + manual reset at any time
Condition LED Relay
Normal Off Off Alarm On On Normal Off Off Next Alarm On On Ack On Off Normal Off Off
Latching Relay (LatcH)
In this application, the meter is set up for manual reset at any time. Acknowledging the alarm even if the alarm condition is still present resets the relay and turns off the LED.
Condition LED Rela
Normal Off Off
Manual reset any time
larm On On ck Off Off
Latching Relay (Lt-Clr)
In this application, the meter is set up for manual reset only after the signal passes the reset point (alarm condition has cleared). Acknowledging the alarm while it is still present has no effect on either the LED or the relay. When the alarm is acknowledged after it returns to the normal state, the LED and the relay go off. Notice that the LED remains on, even after the meter returns to the normal condition. This is because, for latching relays, the alarm LED reflects the status of the relay, regardless of the alarm condition.
Manual reset only after alarm
condition has cleared
Condition LED Rela
Normal Off Off
larm On On ck (No effect
Normal On On
ck Off Off
On On
38
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 39
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Acknowledging Relays
There are two ways to acknowledge relays programmed for manual reset:
1. Via the programmable front panel function keys F1-F3 (Default:
F3 assigned to ACK).
2. Remotely via a normally open pushbutton wired across one of the digital inputs and the +5 V
terminals on the digital I/O modules, or using the F4 digital input, which is triggered with a contact closure to COM, or with an active low signal (see page 15).
When the ACK button or the assigned digital input is closed, all relays programmed for manual reset are acknowledged.
PDA1044 Digital I/O Module
12345678910
+5 I1 I2 I3 I4 O1 O2 O3 O4 G
DI 1-4
ACK
DO 1-4
GND
Figure 26. Acknowledge Relays w/Function Key or Digital Input
Setting Up the Interlock Relay (Force On) Feature
Relays 1-4 can be set up as interlock relays. To set up the relays for the interlock feature:
1. Access the Setup – Relay – Action menu and set the action to off.
2. In the Advanced features – User menu program any of the digital inputs to Force On any of the
internal relays (1-4).
3. Connect a switch or dry contact between the +5V terminal and the corresponding digital input (dI-1 to
dI-4) terminal.
Note: If multiple digital inputs are assigned to the same relay, then the corresponding logic is (AND) – i.e. both switches must be closed to trip the relay.
Scaling the 4-20 mA Analog Output (Aout)
The 4-20 mA analog outputs can be scaled to provide a 4-20 mA signal for any display range selected. To select the channel and source assignments the analog outputs are assigned to, see Analog Output Source on page 49.
No equipment is needed to scale the analog outputs; simply program the display values to the corresponding mA output signal.
The Analog Output menu is used to program the 4-20 mA outputs based on display values.
* *
* IfInstalled
For instructions on
how to program
numeric values see
Setting Numeric
Values
, page 23.
39
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 40
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Reset Menu (reset)
The Reset menu is used to reset the maximum (peak) value of Ch-A and Ch-B rate (rst Hi), minimum (valley) reading of Ch-A and Ch-B rate (rst Lo), both high and low value of Ch-A and Ch-B rate (rst HL), Ch-A total (tot A) or Ch-B total (tot B), Ch-A grand total (Gtot A) or Ch-B grand total (Gtot B), both Ch-A and Ch-B totals (tot AB), or both Ch-A and Ch-B grand totals (Gt AB).
Control Menu (Contrl)
The Control menu is used to control the 4-20 mA analog output (Aout 1 only) and the relays manually, ignoring the input. Each relay and analog output can be programmed independently for manual control. Selecting automatic control sets all relays and analog output for automatic operation.
Once Manual mode is initiated on any relay or
analog output, an LED labeled “M” is turned
on. Every few seconds, all LEDs representing
outputs that are in Manual mode, as well as
the “M” LED flash. Thi s proce ss w il l co ntin ue
as long as any output is in manual mode.
Setting Up the Password (pass)
The Password menu is used for programming three levels of security to prevent unauthorized changes to the programmed parameter settings, to restrict the ability to reset the totals and grand totals, and to program the non-resettable totalizer.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs. Total: Prevents resetting the total manually Gtotal: Prevents resetting the grand total manually
Protecting or Locking the Meter Functions
Enter the Password menu and program a six-digit password. For instructions on how to program numeric values see
Setting Numeric
Values, page 23.
40
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 41
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Total Reset Password & Non-Resettable Total
The total and the grand total can be password-protected to prevent unauthorized total resets. The grand total can be programmed as a non-resettable total by entering the password “050873”.
!
Caution!
Once the Grand Total has been programmed as “non-resettable” the feature cannot be disabled.
Making Changes to a Password Protected Meter
If the meter is password protected, the meter will display the message Locd (Locked) when the Menu button is pressed. Press the Enter button while the message is being displayed and enter the correct password to gain access the menu. After exiting the programming mode, the meter returns to its password protected condition.
Disabling Password Protection
To disable the password protection, access the Password menu and enter the correct password twice, as shown below. The meter is now unprotected until a new password is entered.
If the correct six-digit password is entered, the meter displays the message unLoc (unlocked) and the protection is disabled until a new password is programmed.
If the password entered is incorrect, the meter displays the message Locd (Locked) for about two seconds, and then it returns to Run Mode. To try again, press Enter while the Locked message is displayed.
Did you forget the password?
The password may be disabled by entering a master password once. If you are authorized to make changes, enter the master password 508655 to unlock the meter.
41
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 42
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Advanced Features Menu
To simplify the setup process, functions not needed for most applications are located in the Advanced Features menu.
Press and hold the Menu button for three seconds to access the advanced features of the meter.
Advanced Features Menu & Display Messages
The following table shows the functions and messages of the Advanced Features menu in the order they appear in the menu.
Display Parameter Action/Setting
Gate
Lo G Hi G
filter
Ch-A
Ch-b
Lo Spd
Hi Spd
Round
seriAl
SlaveId
Baud Tr dLY
Parity
t-byt
SelEct
Gate Low gate High gate Filter Channel A
Channel B
Low speed
High speed Round
Serial
Slave ID
Baud rate Transmit
delay Parity
Time byte Select
Enter Gate function menu Program Low gate value Program High gate value Enter the Filter menu Set filter speed for
channel A Set filter speed for
channel B Set the contact de-
bounce filter value Select high speed filter Set the rounding value for
the display Set serial communication
parameters Set slave ID or meter
address Select baud rate Set serial communication
transmit delay Select parity
Even, Odd, or None with 1 or 2 stop bits
Set byte-to-byte timeout Enter the Select menu
(function, math, constant, cutoff, count, Aout programming)
Display Parameter Action/Setting
Functn
Ch-A
Ch-b
Linear
No pts
nmath
Sunm Dif difabs
Avg nmulti
Divide Hi-ab
Lo-ab
Signal input conditionin g
Channel A
Channel B
Linear
Number of points
Math
Sum Difference Abs
difference Average Multiplicatio
n Divide Max of A or
B Min of A or
B
Select linear function parameters
Select menu for channel A
Select menu for channel B
Set meter for linear function and select number of linearization points
Set the number of linearization points (default: 2)
Select the channel C math function
C = (A+B+P)*F C = (A-B+P)*F C = ((Absolute value of
(A-B))+P)*F C = (((A+B)/2)+P)*F C = ((A*B)+P)*F
C = ((A/B)+P)*F C = ((High value of
channel A or B)+P)*F C = ((Low value of
channel A or B)+P)*F
42
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 43
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Display Parameter Action/Setting
Drauw uw Avg
ratio Ratio2 Concen
Sunm t Sunmgt
Dif t Dif gt
Tratio t-rat2 T pct
Const
adder
factor
CutofF
Ch-A
Ch-b
Count
Ch-A
Ch-b
Tot C
Gtot C
up Douwn
C strt
Draw Weighted
avg. Ratio Ratio 2 Concentrati
on Sum total Sum grand
total Diff. of total Difference
of grand total
Total ratio Total ratio 2 Total
percent Constant
Adder
Factor
Cutoff Channel A
Channel B
Count Channel A
Channel B
Total count
G. total count
Count up Count
down Count start
C = ((A/B)-1)*F C = ((B-A)*F)+A
C = (A/B)*F C = ((B-A)/A)+P)*F C = (A/(A+B))*F
C = (tA+tB+P)*F C = (GtA+GtB+P)*F
C = (tA-tB+P)*F C = (GtA-GtB+P)*F
C = (tA/tB)*F C = ((tB-tA)/tA)*F C = (tA/(tA+tB))*100
Enter math equation constants
Addition constant used in channel C math calculations (P)
Multiplication constant used in channel C math calculations (F)
Set low-flow cutoff Set low-flow cutoff for
Channel A Set low-flow cutoff for
Channel B Set total count direction Set total count direction
for Channel A Set total count direction
for Channel B Set direction of total
count Set direction of grand
total count Count up Count down
Enter count down start value
Display Parameter Action/Setting
AoutPr
Aout 1* Analog
Source
Calib 4 nmA
20 nmA
O-rang
u-rang
nmAx
nmin
User
F1* F1*
F4
dI I
dO 1
Diag
LED t Info
Erase
Analog output programmi ng
output 1 Source
Calibrate 4 mA
output
20 mA output
Overrange
Underrange
Maximum
Minimum
User I/O
function key
F4 digital input
Digital input 1
Digital output 1
Diagnostics
LED test Information
Erase
Program analog output parameters
Program analog output 1 (*1-3) parameters
Select source for the 4-20 mA output
Calibrate 4-20 mA output Enter mA output value
read by milliamp meter with at least 0.001 mA resolution
Enter mA output value read by milliamp meter with at least 0.001 mA resolution
Program mA output for display overrange
Program mA output for display underrange
Program maximum mA output allowed
Program minimum mA output allowed
Assign function keys and digital I/O
Assign F1 function key (*F1/F2/F3)
Assign F4 function (digital input)
Assign digital input 1 – 8, if expansion modules are connected
Assign digital output 1 – 8, if expansion modules are connected
Display parameter settings
Test all LEDs Display software and S/N
information Erase MeterView Pro
software stored in meter’s memory
43
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 44
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Gate Function (Gate)
The gate function (Gate) is the first option in the Advanced Features menu. There are two settings for the Gate, low gate (Lo G) and high gate (Hi G). Channel A and B use the same gate settings.
The gate function is used for displaying slow pulse rates. Using the programmable gate, the meter is able to display pulse rates as slow as 1 pulse every 999.9 seconds (0.001 Hz). The gate function can also be used to obtain a steady display reading with a fluctuating input signal.
Low Gate (Lo G)
For most applications, low gate setting should be left at 1.0 second. Increase low gate setting to obtain a steadier rate display. The rate display will update in accordance with the low gate setting, for example if low gate is set at 10.0, the display will update every 10 seconds; changes in rate between updates will not be reflected until next display update.
High Gate (Hi G)
Set the high gate value to correspond to the highest expected pulse period (lowest pulse rate). For instance if the meter must display a rate when there is 1 pulse coming into the meter every 10 seconds, set the high gate to 11.0 seconds. When the signal is removed from the meter, the display will show the last reading for 11 seconds; then it will read zero.
Gate Settings
Slow Pulse Rate
Low Gate* (sec) High Gate (sec) Min Freq** (Hz)
1.0 2.0 0.5000
1.0 10.0 0.1000
1.0 20.0 0.0500
1.0 100.0 0.0100
1.0 200.0 0.0050
1.0 400.0 0.0025
1.0 800.0 0.0012
1.0 999.9 0.0010
*The low gate setting corresponds to the display update rate and is used to stabilize the display reading with a fluctuating signal.
**The minimum frequency is dependent on high gate setting.
44
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 45
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Contact De-Bounce Filter (FiLter)
The filter function (Filter) is the second option in the Advanced Features menu. The filter function (FiLter) can be used for applications where the meter is set up to count pulses generated by switch contacts. The filter value can be set anywhere between 2 and 50, the higher the value, the greater the filtering. Channel A and B have independent settings.
There are two settings, Hi SPd (high speed) and Lo SPd (low speed). After pressing ENTER to select Lo SPd, enter the desired filter setting based on the table below so that there are no extra counts when a contact closure is completed. Selecting Hi SPd does not require a programmable filter value.
Filter Settings
Contact De-Bounce Filter
Filter Setting Speed Setting Max Freq (Hz)
2 Lo SPd 999 4 Lo SPd 499
8 Lo SPd 249 16 Lo SPd 124 32 Lo SPd 62 40 Lo SPd 50 50 Lo SPd 40
N/A Hi SPd 30,000
Rounding Feature (round)
The rounding feature is used to give the user a steadier display with fluctuating signals. Rounding is used in addition to the filter function.
Rounding causes the display to round to the nearest value according to the rounding selected. This setting affects the last two digits, regardless of decimal point position.
Modbus RTU Serial Communications (serial)
The meter is equipped with serial communications capability as a standard feature using Modbus RTU Serial Communication Protocol.
The meter may be connected to a PC for initial configuration via the onboard micro USB connection. For ongoing digital communications with a computer or other data terminal equipment, an RS-232, or RS-485 option is required; see Ordering Information on page 5 for details.
Do not connect any equipment other than Precision Digital’s expansion modules, cables, or meters to the
Warning!
Note: More detailed instructions are provided with each optional serial communications adapter.
When using more than one meter in a multi-drop mode, each meter must be prov unique address. The meter address (Slave ID) may be programmed between 1 and 247. The transmit delay may be set between 0 and 199 ms. The parity can be set to even, odd, or none with 1 or 2 stop bits.
RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
ided with its own
Changes made to the Serial menu are initialized after the MENU key is pressed or after navigating through the t-byte parameter.
45
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 46
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Select Menu (SElect)
The Select menu is used to select the signal input conditioning function applied to the inputs, math function for A & B, constants, low-flow cutoff, total count direction (up or down from a preset amount), and analog output programming. Multi-point linearization is part of the linear function selection.
Signal Input Conditioning (Functn)
The Function menu is used to condition the linear input signal. Multi-point linearization is part of the linear function selection. Each input channel signal input conditioning function is programmed independently.
Multi-Point Linearization (Linear)
Meters are set up at the factory for linear function with 2-point linearization. Up to 32 linearization points can be selected for each channel under the linear function. The multi-point linearization can be used to linearize the display for non-linear signals such as those from level transmitters used to measure volume in odd-shaped tanks or to convert level to flow using weirs and flumes with complex exponent.
Note: After Scale is displayed continue pressing the Enter button until the meter completes the
scaling of the input and display values.
46
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 47
(A
((
(((
((
((
A
2
l
l
(
2
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Math Function (nmath)
The Math menu is used to select the math function that will determine the channel C value. These math functions are a combination of input channels A and B, and will display when channel C is selected in the Display menu.
A and B refer to the rate of channel A and B. tA and tB refer to the totals of channel A and B. GtA and GtB refer to the grand totals of channel A and B. The following math functions are available.
Function Display Description
Sunm Sum C = (A+B+P)*F Dif difabs Avg Average C = nmulti Multiplication C = ((A*B)+P)*F Divide Hi-ab Max of A or B C = ((High value of channel A or B)+P)*F Lo-ab Min of A or B C = ((Low value of channel A or B)+P)*F Drauw uw Avg Weighted avg. C = ((B-A)*F)+ ratio Ratio C = (A/B)*F Ratio2 Concen Concentration C = (A/(A+B))*F Sunm t Sum total C = (tA+tB+P)*F Sunmgt Dif t Dif gt Difference of grand totalC = (GtA-GtB+P)*F Tratio t-rat2 T pct Total percent C = (tA/(tA+tB))*100
Difference C = Abs difference C =
Divide C =
Draw C =
Ratio
Sum grand tota Diff. of tota
Total ratio C = Total ratio
C = ((B-A)/A)+P*F
C = (tA-tB+P)*F
C = ((tB-tA)/tA)*F
-B+P)*F
Absolute value of (A-B))+P)*F
A+B)/2)+P)*F
A/B)+P)*F
A/B)-1)*F
C = (GtA+GtB+P)*F
tA/tB)*F
Math Constants (Const)
The Math Constants menu is used to set the constants used in channel C math. The math functions include adder constant P, and factor constant F.
The Adder constant (P) may be set from -99.999 to 999.999. The Factor constant (F) may be set from 0.001 to 999.999. The chart on page 47 details the math functions that may be selected in the Math Function menu.
47
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 48
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Low-Flow Cutoff (CutofF)
The low-flow cutoff feature allows the meter to be programmed so that the often-unsteady output from a differential pressure transmitter, at low flow rates, always displays zero on the meter. The low-flow cutoff for each channel is programmed independently.
The cutoff value may be programmed from 0 to 999999. The meter will display zero below the cutoff value. Programming the cutoff value to zero disables the cutoff feature.
Totalizer Count Up/Down (Count)
The totalizer count up/down menu may be used to program the total and grand total to either count up from 0 when reset or count down from a programmed value when reset. Total and grand total may have their countdown numbers programmed individually from 0 to 999999.
Analog Output Programming (AoutPr)
The Analog Output Programming menu is used to program the behavior of the 4-20 mA outputs. The following parameters and functions are programmed in this menu for each analog output:
1. Source: Source for generating the 4-20 mA output
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Max: Maximum analog output value allowed regardless of input
5. Min: Minimum analog output value allowed regardless of input
48
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 49
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Analog Output Source
The analog output source can be based on either of the input channel rate, total, or grand totals (Ch-A, Ch-B), the math channel (Ch-C), maximum stored value of either input channel (Hi-A, Hi-B), minimum stored value of either input channel (Lo-A, Lo-B), maximum or minimum of A and B (Hi-AB, Lo-AB), relay set points, or the Modbus input.
To base an analog output on the rate, total, or grand total of channels A or B, select the channel in the Analog Output Source menu. Then select the rate, total, or grand total as the source reference for the output, and program the output scale.
Programmable Function Keys User Menu (user)
The User menu allows the user to assign the front panel function keys F1, F2, and F3, the digital input F4 (a digital input located on the signal input connector), and up to eight additional digital inputs to access most of the menus or to activate certain functions immediately (e.g. reset max & min, hold relay states, etc.). This allows the meter to be greatly customized for use in specialized applications.
Up to eight digital outputs can be assigned to a number of actions and functions executed by the meter (i.e. alarms, relay acknowledgement, reset max, min, or max & min, tare, and reset tare). The digital outputs can be used to trigger external alarms or lights to indicate these specific events.
f installed
*I
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
49
Page 50
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Function Keys & Digital I/O Available Settings
Refer to the following table for descriptions of each available function key or digital I/O setting.
Display Description
Rst Hi
Rst Lo
Rst HL
relay Set 1
Rly d
Rly E
O Hold
d Hold
D AbC
d tot
D gtot
Ln1 Hi
Ln1 Lo
Ln1 HL
Ln2 Hi
Reset the stored maximum display values for all channels
Reset the stored minimum display values for all channels
Reset the stored maximum & minimum display values for all channels
Directly access the relay menu Directly access the set point menu
for relay 1 (*through 8) Disable all relays until a button
assigned to enable relays (Rly E) is pressed
Enable all relays to function as they have been programmed
Hold current relay states and analog output as they are until a button assigned to enable relays (Rly E) is pressed
Hold the current display value, relay states, and analog output momentarily while the function key or digital input is active. The process value will continue to be calculated in the background.
Scrolls values for A, B & C when activated. Keeps the last value for 10 seconds and then it returns to its assignment. Values are displayed on display line 1 and the corresponding channel and units on display line 2. Scrolls through totals for channels A, B, and C (which is the sum of A and B). Values are displayed on display line 1. Scrolls through grand totals for channels A, B, and C (which is the sum of A and B). Values are displayed on display line 1.
Display maximum channel A display value on line 1
Display minimum channel A display value on line 1
Display maximum & minimum channel A display values on line 1
Display maximum channel B display value on line 2
Display Description
Ln2 Lo
Ln2 HL
Ln2 HC
Ln2 HC
LitHLC
F On 1
Contrl disabl
up-d a
up-d b
AcH
Reset Rst t Rst gt Rst ta Rst ga Rst tb Rst gb nmenu
rigHt
up
Enter
Alnm 1
Display minimum Channel B display value on line 2
Display maximum & minimum channel B display values on line 2
Display minimum channel C display value on line 2
Display maximum & minimum channel C display values on line 2
Display maximum channel C display value on line 2
Force relay 1 (*through 4) into the on state. This function is used in conjunction with a digital input expansion module to achieve interlock functionality. See page 39 for details about interlock relays.
Directly access the control menu Disable the selected function key or
digital I/O Total count mode direction control
for channel A Total count mode direction control for channel B Acknowledge all active relays that are in a manual operation mode
such as auto-manual or latching Directly access the reset menu Reset totals for all channels Reset grand totals for all channels Reset total for channel A Reset grand total for channel A Reset total for channel B Reset grand total for channel B Mimic the menu button functionality
(digital inputs only) Mimic the right arrow/F1 button
functionality (digital inputs only) Mimic the up arrow/F2 button
functionality (digital inputs only) Mimic the enter/F3 button
functionality (digital inputs only) Provide indication when alarm 1
(*through 8) has been triggered (digital outputs only)
50
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 51
y
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Meter Operation
The meter accepts two input channels (A and B) of either pulses (e.g. ±40 mV to ± 8V), square wave (0-5 V, 0-12 V, or 0-24 V), open collector NPN, PNP, TTL, or switch contact signals and displays these signals in engineering units from -99999 to 999999. (e.g. a 0-1000 Hz signal could be displayed as -50.000 to
50.000). Digital inputs and quadrature inputs can be accepted for bi-directional flow on channel A and B. Quadrature
inputs can also be accepted, using channels A and B to calculate a single bi-directional flow. A totalizer can be programmed to count the scaled engineering units, interpreting it as count per second,
minute, hour, or day. The scaled rate and total for each channel can be displayed on the top or bottom displays.
A math function channel (C) is available to perform operations on channel A and B rates or totals, with adder and factor constants, and display the results. Engineering units or tags may be displayed with these three channels.
The dual-line display can be customized by the user. Typically, display line 1 is used to display the math channel C, while line 2 is used to alternate between displaying input channels A and B rate or total.
Additionally, the meter can be set up to display any input or math channel on display line 1 and a unit or tag on line 2. The relays and analog output can be programmed to operate based on any input rate or total, or the math function channel.
Function Keys Operation
During operation, the programmable function keys operate according to the way they have been programmed in the Advanced Features – User menu.
F4 Operation
A digital input, F4, is standard on the meter. This digital input is programmed identically to function keys F1, F2, and F3. The input is triggered with a contact closure to COM, or with an active low signal. During operation, F4 operates according to the way it has been programmed in the Advanced Features – User menu.
Front Panel Buttons Operation
Button S
mbol
Description
Press to enter or exit Programming Mode, view settings, or exit max/min readings
Press to reset max/min readings or other parameter/function assigned through the User menu
Press to display max/min readings for channel A or other parameter/function assigned through the User menu
Press to acknowledge relays or other parameters/function assigned through the User menu
51
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 52
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Maximum/Minimum Readings
The max & min readings (peak & valley) reached by the process can be displayed either continuously or momentary:
1. Display briefly by assigning to the F1-F3 function keys or to the digital inputs in the User menu.
2. Display continuously by assigning either display to max/min through the Display menu.
Any of the F1-F3 function keys (buttons) and the digital inputs can be programmed to reset the max & min readings. The meters are set at the factory to display the max/min reading by pressing the Up arrow/F2 button and to use the Right arrow/F1 button to reset the max/min.
To display max and min channel A reading using function key with factory defaults:
1. Press Up arrow/F2 button to display the maximum and minimum reading of channel A since the last reset/power-up.
2. To reset max/min press Right arrow/F1 button. The max & min displays are reset to actual values.
3. Press Menu to exit max/min display reading.
Troubleshooting
The rugged design and the user-friendly interface of the meter should make it unusual for the installer or operator to refer to this section of the manual. However, due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with what an operator expects to see.
If the meter is not working as expected, refer to the Diagnostics menu and recommendations below.
Diagnostics Menu (diag)
The Diagnostics menu is located in the Advanced Features menu. To access the Diagnostics menu see Advanced Features Menu, page 42.
For a description of the diagnostic messages, see Advanced Features Menu & Display Messages, page
42.
Determining Software Version
To determine the software version of a meter:
1. Go to the Diagnostics menu (diAG) and press Enter button.
2. Press Up arrow button and scroll to Information menu (Info).
3. Press Enter to access the software number (SFT) and version (UER) information. Write down the
information as it is displayed. Continue pressing Enter until all the information is displayed.
4. The meter returns to Run Mode after displaying all the settings.
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults.
Instructions to load factory defaults:
1. Enter the Advanced Features menu. See Advanced Features Menu, page 42.
2. Press Up arrow to go to Diagnostics menu
3. Press and hold Right arrow for three seconds, press Enter when display flashes reset. Note: If Enter is not pressed within three seconds, the display returns to Run Mode.
4. The meter goes through an initialization sequence (similar as on power-up), and loads the factory default settings.
52
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 53
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Factory Defaults & User Settings
The following table shows the factory setting for most of the programmable parameters on the meter.
Parameter Display Default Setting
Input type
Total, channel A
Total, channel B
Units
Rate unit, channel A
Rate unit, channel B
Unit, channel C
Total unit, channel A
Grand total unit, ch­A
Total unit, channel B
Grand total unit, ch­B
Decimal Point
Rate, channel A
Total, channel A
Grand total, channel A
Rate, channel B
Total, channel B
Grand total, channel B
Channel C
Input Calibration
Number of points
Number of points, ch-A
Number of points, ch-B
K-Factor, channel A
K-Factor, channel B
Total setup
Time base, channel A
Total conversion factor, Ch-A
Grand total conversion factor, Ch-A
Time base, channel B
Input
Ch-A
Ch-B
units
Ch-A
Ch-B
Ch-C
Tot-A
Gtot-A
Tot-b
Gtot-b
Dec pt
rate
Total
gtotal
rate
Total
gtotal
Ch-C
InCAL
No pts
Ch-A
Ch-B
Fact-A
Fact-B
Tsetup
Tbase
T CF
Gt CF
Tbase
Yes
Yes
HZ-A
HZ-b
HZ-C
tot-A
Gtot-A
tot-b
Gtot-B
1
1
0
1
1
0
1
2
2
1.000
1.000
Sec
1.000
1.000
Sec
Parameter Display Default Setting
Total conversion factor, Ch-B
Grand total conversion factor, Ch-B
Total reset
Total reset, channel A
Grand total reset, Ch-A
Total reset, channel B
Grand total reset, Ch-B
Display assignment
Display line 1 D Ch-A Channel A
Display line 2 d Ch-B Channel B
Display intensity
Relay
Relay 1 assignment
Relay 1 action
Relay 1 set point
Relay 2 assignment Ch-A Channel A total
Relay 2 action Act 2 Automatic
Relay 2 set point
Relay 3 assignment
Relay 3 action
Relay 3 set point
Relay 3 reset point RSt 3 250.0
Relay 4 assignment Ch-A Channel A rate
Relay 4 action
Relay 4 set point
Relay 4 reset point
Fail-safe relay 1 to 4
On delay relay 1 to 4
Off delay relay 1 to 4 Off 1 0.0 sec
Analog output Aout
Display 1 analog out
Output 1 value
Display 2 analog out
T CF
Gt CF
Treset
T rst
Gt rst
T rst
Gt rst
Dsplay
d-Inty
Relay
Ch-A
Act 1
Set 1
Set 2
Ch-A
Act 3
Set 3
Act 4
Set 4
RSt 4
Fls 1
On 1
Dis 1
Out 1
Dis 2
1.000
1.000
Manual
Manual
Manual
Manual
8
Channel A total
Automatic
100.0
200.0
Channel A rate
Automatic
300.0
Automatic
400.0
350.0
Off
0.0 sec
0.0
4.000 mA
1000.0
53
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 54
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Parameter Display Default Setting
Output 2 value Out 2 20.000 mA
Source analog output
Overrange output
Underrange output
Maximum output
Minimum output
Filter
Filter, channel A
Filter, channel B Ch-B High speed
Round Round 1
Cutoff Cutoff
Cutoff value, channel A
Cutoff value, channel B
Serial
Slave ID (Address)
Baud rate baud 9600
Transmit delay Tr dly 50 ms
Parity
Byte-to-byte timeout
Math
Math, channel C
Adder (constant P)
Factor (constant F)
Source
O-rang
u-rang
mAx
min
Filter
Ch-A
Ch-a
Ch-b
Serial
SlavId
Parity
t-byt
math
Sum
Adder
Factor
Channel A
21.000 mA
3.000 mA
23.000 mA
3.000 mA
High speed
0.0 (disabled)
0.0 (disabled)
247
Even
010 (0.1 sec)
Sum
0.000
1
Parameter Display Default Setting
User
F1 function key
F2 function key
F3 function key
F4 function
(digital input)
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital output 1
Digital output 2
Digital output 3
Digital output 4
Password
Password 1
Password 2
Password 3
Total
Grand total
user
F1
F2
F3
F4
DI 1
DI 2
DI 3
DI 4
DO 1
DO 2
DO 3
DO 4
pass
Pass 1
Pass 2
Pass 3
Total
gtotal
Reset max & min
Line 1 Max & Min
Acknowledge relays
Acknowledge relays
Menu
Right arrow
Up arrow
Enter
Alarm 1
Alarm 2
Alarm 3
Alarm 4
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
000000 (unlocked)
54
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Page 55
y
)
g
PROVU PD6363 Dual Pulse Input Rate/Totalizer Instruction Manual
Troubleshooting Tips
Symptom Check/Action
No display at all Not able to change setup or
programming, Locd is displayed Meter displays error message during
calibration (Error)
Meter displays
1. 999999
2. -99999 Display is unstable
Display response is too slow Display reading is not accurate
Display does not respond to input changes, reading a fixed number
Display alternates between
1. Hi and a number
2. Lo and a number
Relay operation is reversed
Relay and status LED do not respond to signal
Flashing relay status LEDs
Meter not communicating with application programs
If the display locks up or the meter does not respond at all
Other symptoms not described above
Check power at power connector Meter is password-protected, enter correct six-digit
password to unlock Check:
1. Signal connections
2. Input selected in Setup menu
3. Minimum input span requirements Check:
1. Input selected in Setup menu
2. Corresponding signal at Signal connector Check:
1. Input signal stability and value
2. Display scaling vs. input signal
3. Filter and b Check filter and gate values
Check:
1. Proper input programming used (k-factor, scaling, calibration
Check:
1. Display assignment, it might be displaying max, min, or set point.
Press Menu to exit max/min display readings.
Check:
1. Fail-safe in Setup menu
2. Wirin
Check:
1. Relay action in Setup menu
2. Set and reset points
Relays in manual control mode or relay interlock switches opened. Check:
1. Serial adapter and cable
2. Serial settings
3. Meter address and baud rate
Cycle the power to reboot the microprocessor.
Call Technical Support for assistance.
pass values (increase)
of relay contacts
55
Find Quality Products Online at: [email protected]
www.GlobalTestSupply.com
Loading...