PRECISION DIGITAL Loop Leader Series, Loop Leader PD6622/4 Instruction Manual

Page 1
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer
Instruction Manual
PRECISION DIGITAL CORPORATION
233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
Loop-Powered Totalizer
Loop-Powered Rate/Totalizer Loop-Powered Backlight with Red Backlight for Alarm Conditions Display rate & total simultaneously Total display includes commas for more intuitive readings 1.5 Volt Drop (4.5 Volt Drop w/ Backlight) NEMA 4X, IP65 Front -40 to 167°F (-40 to 75°C) Operating Temperature Range Five Digit Top Line Alphanumeric tag names Total, Grand Total, or Non-Resettable Grand Total Up to 13-digit total & grand total Dual Line Display 1/8 DIN Shallow Depth Case Optional Loop-Powered Solid State Relays Optional 4-20 mA Analog Output
Page 2
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
2
Disclaimer
The information contained in this document is subject to change without notice. Pre­cision Digital makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
CAUTION: Read complete
instructions prior to installa-
tion and operation of the
meter.
WARNING: Risk of elec-
tric shock or personal
injury.
Warning!
This product is not recommended for life support applica­tions or applications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. Precision Digital Corporation shall not be held liable for damages re­sulting from such improper use.
Limited Warranty
Precision Digital Corporation warrants this product against defects in material or
workmanship for the specified period under “Specifications” from the date of ship­ment from the factory. Precision Digital’s liability under this limited warranty shall not
exceed the purchase value, repair, or replacement of the defective unit.
Registered Trademarks
NORYL® and LEXAN® are registered trademarks of SABIC Innovative Plastics. All other trademarks mentioned in this document are the property of their respective owners.
© 2016 Precision Digital Corporation. All rights reserved.
www.predig.com
!
Page 3
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
3

Table of Contents

Table of Contents ----------------------------------------- 3 Table of Figures ------------------------------------------- 3 Introduction ------------------------------------------------- 4 Ordering Information ------------------------------------ 4 Specifications ---------------------------------------------- 5
General --------------------------------------------------------------- 5 Process Input ------------------------------------------------------- 5 Rate/Totalizer ------------------------------------------------------- 5 Open Collector Output ------------------------------------------ 6 Solid State Relays ------------------------------------------------ 6 4-20 mA Transmitter Output ----------------------------------- 6
Safety Information ---------------------------------------- 7 Installation -------------------------------------------------- 7
Unpacking ----------------------------------------------------------- 7 Panel Mounting Instructions ---------------------------------- 7
Mounting Dimensions ------------------------------------------- 8
Connections -------------------------------------------------------- 8
Connectors Labeling -------------------------------------------- 8 Current Loop (4-20 mA) Connections ---------------------- 9 Digital Input Connection ---------------------------------------- 9 4-20 mA Output Connections ------------------------------- 10 Solid State Relay Connections ----------------------------- 10 Open Collector Outputs -------------------------------------- 11
Setup and Programming ------------------------------ 12
Overview ----------------------------------------------------------- 12 Front Panel Buttons and Status LED Indicators ------ 12 Display Functions & Messages----------------------------- 13 Main Menu --------------------------------------------------------- 16
Setting Numeric Values -------------------------------------- 16
Setting Up the Input Signal (INPUT) ---------------------- 17
Available Unit Classes and Units -------------------------- 18 Setting Custom Units (CUSTM) ----------------------------- 18
Scaling the 4-20 mA Input ----------------------------------- 18
Setting the Display Features (DISPLAY) ---------------- 19
Changing the Units (UNITS) -------------------------------- 19 Changing the Decimal Point Location (DEC.PT) -------- 19 Enabling or Disabling the Comma on the Bottom Display (COMMA) ----------------------------------------------- 19 Programming the Bargraph (PD6624 Only) ------------ 19 Changing What is Displayed (TOP and BOTTOM) ----- 20
Programming the Outputs (OUTPUT) --------------------- 21
Open Collector Outputs (OPEN COLLECTR) ----------- 22 Solid State Relay Outputs (RELAY) ----------------------- 26 4-20 mA Output (4-20 mA) -------------------------------- 30 Output Control (CONTROL) ---------------------------------- 30
Advanced Features Menu (ADVANCED) ------------------ 31
Advanced Rate, Total, and Grand Total Setup (ADV RATE, TOTAL, GTOTAL) ------------------------------------- 31
Low-Flow Cutoff (CUTOFF) ---------------------------------- 34 Noise Filter (FILTER) ---------------------------------------- 34 Enabling Password Protection (PASSWRD) ------------- 34 Programmable Function Keys User Menu (USER) ---- 35 Changing System Settings (SYSTEM) -------------------- 36
Meter Operation ------------------------------------------ 38
Front Panel Buttons Operation ----------------------------- 38 Function Keys Operation ------------------------------------- 38 Digital Input Operation ---------------------------------------- 38 Maximum/Minimum Readings ------------------------------ 38 Changing Engineering Units -------------------------------- 38
Troubleshooting ----------------------------------------- 39
Reset Meter to Factory Defaults --------------------------- 39 Determining Software Version ----------------------------- 39
Factory Default Settings ------------------------------------- 40
Troubleshooting Tips ------------------------------------------ 41

Table of Figures

Figure 1. 1/8 DIN Panel Cutout Dimensions and Panel
Mounting Details ..................................................... 7
Figure 2. Meter Dimensions - Side View ......................... 8
Figure 3. Meter Dimensions - Front View ........................ 8
Figure 4. Connector Labeling for Fully Loaded PD6620 . 8
Figure 5. 4-20 mA Input Connection without Backlight .... 9
Figure 6. 4-20 mA Input Connection with Backlight ......... 9
Figure 7. Digital Input Connections .................................. 9
Figure 8. 4-20 mA Output Connections .......................... 10
Figure 9. Solid State Relay Connections ....................... 10
Figure 10. Open Collector Output Connections ............. 11
Page 4
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
4

Introduction

The Loop Leader PD6622 and PD6624 are loop-powered, 1/8 DIN flow rate/totalizers designed for de­manding process control applications. The four front panel buttons make setup and programming of the meter simple and intuitive. A dual-line display featuring five digits on the top line and eight digits on the bottom line, preprogrammed engineering units, and optional bargraph display (PD6624) provide a clear and attractive presentation of the process. The units of measure can be changed as needed (e.g. gal­lons/second to liters/second) without the need to re-scale the meter.
The dual-line display can be customized by the user to operate in such a way as to satisfy a specific ap­plication. Typically, the top line is used for the rate while the bottom line is used for the total, grand total, or engineering units. Three programmable function keys and a digital input come standard and allow the meter to be customized for use in specialized applications.
All models come equipped with two open collector outputs and are available with two solid state relays and a 4-20 mA analog output. These outputs can be programmed for alarm indication, signal retransmis­sion via pulse or analog signal, pump control, and a number of other useful features.
The fact that this meter is loop-powered means that there is no need to run additional, costly power lines; the meter gets all of the power it needs from the 4-20 mA loop. The Loop Leader loop-powered rate/total­izer is built in a shallow-depth case with a NEMA 4X/IP65 front and features loop-powered backlighting and a wide -40 to 167°F (-40 to 75°C) operating temperature range. It doesn't matter if it's indoors or out­doors, in bright sunlight or a dimly lit plant, or in an area that is wet, dirty, hot, or cold, the Loop Leader can go just about anywhere.

Ordering Information

Standard Decimal Display Models
PD6622–LNN
Loop-Powered, No Options
PD6622–L2N
Loop-Powered, Two Solid State Relays
PD6622–L3N
Loop-Powered, 4-20 mA Analog Output
PD6622–L5N
Loop-Powered, Two Solid State Relays and 4-20 mA Analog Output
Note: all models come with two open collector outputs standard.
Decimal Display with Bargraph Models
PD6624–LNN
Loop-Powered, No Options
PD6624–L2N
Loop-Powered, Two Solid State Relays
PD6624–L3N
Loop-Powered, 4-20 mA Analog Output
PD6624–L5N
Loop-Powered, Two Solid State Relays and 4-20 mA Analog Output
Note: all models come with two open collector outputs standard.
Enclosures
Model
Meters
Description
Mounting
PDA2407
1
Plastic NEMA 4X Enclosure
Inside Cover
PDA2410
3
Plastic NEMA 4X Enclosure
Inside Cover
PDA2411
2
Plastic NEMA 4X Enclosure
Inside Cover
PDA23XX
1-10
Economical Plastic NEMA 4X Enclosure
Through Door
PDA25XX
1-10
Plastic NEMA 4X Enclosure
Through Door
PDA26XX
1-6
Stainless Steel NEMA 4X Enclosure
Through Door
PDA27XX
1-6
Steel NEMA 4 Enclosure
Through Door
PDA2801*
1
Low-Cost Plastic NEMA 4X Enclosure
Through Cover
PDA2812
2
Low-Cost Plastic NEMA 4X Enclosure
Through Cover
Note: XX = the last two digits of the model number.
Go to www.predig.com to find individual part numbers.
Page 5
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
5

Specifications

Except where noted all specifications apply to operation at +25°C.

General

Display
Top: 0.7” (17.8 mm), Bottom: 0.4” (10.2 mm) Top: 5 digits -9999 to 99999 Bottom: 8 digits -9,999,999 to 99,999,999
Bottom line separated by commas
Display Update Rate
Ambient > -10°C: 1 Update/Second Ambient < -20°C: 1 Update/2 Seconds Ambient -40°C: 1 Update/10 Seconds
Overrange
Top: 99999; Bottom: 99,999,999 (flashing)
Underrange
Top: -9999; Bottom: -9,999,999 (flashing)
Programming Method
Front panel Noise Filter
1, 2, 4, 8, 16 sec.
Noise Filter Bypass
0.1 to 99.9% FS
Recalibration
Recalibration is recommended at least every 12 months.
Max/Min Display
Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
Password
Programmable password restricts modification of programmed settings.
Non-Volatile Memory
All programmed settings are stored in non-vol­atile memory for a minimum of ten years if power is lost.
Normal Mode Rejection
64 dB at 50/60 Hz
Environmental
Operating temperature range: -40 to 75°C Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non-condensing
Connections
Removable screw terminals accept 12 to 22 AWG wire
Enclosure & Materials
1/8 DIN, high impact plastic, NORYL® Poly­phenylene Ether & Polystyrene blend (PPE PS) Resin, UL 94V-0, color: gray
Gasket: Silicone Rubber
Faceplate: LEXAN® Polycarbonate (PC) Film Buttons: Silicone rubber; Color: black
Mounting
1/8 DIN panel cutout required. Two panel mounting bracket assemblies provided
Tightening Torque
Screw terminal connectors: 4.5 lb-in (0.5 Nm) Mounting screws: 8.0 lb-in max. (0.9 Nm)
Overall Dimensions
4.68" x 2.45" x 3.79" (119 mm x 62 mm x 96 mm) (W x H x D)
Weight
8.7 oz (247g) w/ option board
Warranty
3 years parts and labor

Process Input

Accuracy
±0.02% of span ±1 count, Square root and programmable exponent: 10-100% FS
Function
Linear, square root, or programmable expo­nent
Low-Flow Cutoff
0.0 to 999,999.9
Temperature Drift
25 PPM/C from -40 to 75C ambient
Decimal Point
Up to four decimal places: On top Up to seven decimal places: On bottom
Calibration Range
An Error message will appear if input 1 and input 2 signals are too close together.
Input Range Min Span input 1 & 2 4-20 mA 0.010 mA
Voltage Drop
With backlight off: 1.5 V max With backlight on: 4.5 V max
Equivalent Resistance
75 Ω @ 20 mA with backlight off 225 Ω @ 20 mA with backlight on
Input Overload
Over current protection to 1 A maximum

Rate/Totalizer

Rate Display Indication
-9999 to 99999, top display
-9,999,999 to 99,999,999, bottom display
Total Display & Total Overflow
-9999 to 99999, top display
-9,999,999 to 99,999,999, bottom display
“T” LCD segment shows while displaying total “G T” LCD segments show for grand total.
(non-bargraph display version only) Up to 9,999,999,999,999 with 13-digit feature. Total or grand total flashes and a truncated value is shown. Press function key assigned to display (default: F1) to view full number.
Total Decimal Point
Up to four decimal places: On top Up to seven decimal places: On bottom Total decimal point is independent of rate decimal point.
Totalizer
Calculates total based on rate and rate units to display total in engineering units. A custom factor must be programmed if using custom defined units.
Totalizer Rollover
Totalizer rolls over when display exceeds 99,999,999 (9,999,999,999,999 if 13-digit limit enabled). Relay status reflects display.
Total Reset
Via front panel button or external contact clo­sure on digital input
Total Reset Password
Total and grand total passwords may be en­tered to prevent resetting the total or grand total from the front panel.
Non-Resettable Total
Total and grand total reset may be disabled through the meter interface. Grand total reset may be permanently disabled by selecting YES at the PERMLOCK menu. Once the grand total reset has been permanently disabled, it cannot be enabled.
Page 6
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
6

Open Collector Output

Rating
Two NPN, Isolated open collector, 30 VDC @ 90 mA maximum
Output Assignment
Pulse, Alarm, Timer, Total Reset, or Disable
Pulse Output Source
Rate, Total, Grand Total, or Test Frequency
Pulse Output Factor
0.000001 to 999,999.9
Pulse Width
2 ms; 50% duty cycle
Pulse Output Frequency
250 Hz maximum
Quadrature Pulse Output
Available for Output 2 (90° behind Output 1)
Alarm Output Source
Assign to Rate, Total, Grand Total or Digital Input
High or Low Alarm
User programmable for high or low alarm
Alarm Deadband
0-100% FS, user programmable
On & Off Time Delay
0 to 9,999 seconds
Fail-Safe Operation
Independent for each output
Alarm Operation
Auto, Auto-man, Latch, Latch w/clear
Alarm Indication
Red backlight, Flashing display, Alarm Mes­sage, Alarm symbol (!)
Alarm Message
On or Off; User programmable, 8 characters maximum
Displayed every 10 sec for 1 sec on bottom
Alarm Acknowledge
Front panel ACK button or external digital in­put resets output and screen indication
Auto Initialization
When power is applied to the meter, relays will reflect the state of the input to the meter
Timer Output
One-shot or Continuous Off Time Delay: 1 sec to 99:59:59
(hrs:min:sec) On Time: 1 sec to 99:59:59 (hrs:min:sec)
Timer Start/Stop
Front panel or digital input, user selectable

Solid State Relays

Rating
Resistive Load: 250 VAC/DC @ 1 Amp Inductive Load: 1/10 HP @ 125/250 VAC/DC
Noise Suppression
Metal oxide varistors across outputs
Relay Assignment
Alarm, Timer, Batch Control, Sample, or Disa­ble
Alarm Output Source
Assign to Rate, Total, Grand Total, or Digital Input
High or Low Alarm
User programmable for high or low alarm
Alarm Deadband
0-100% FS, user programmable
On & Off Time Delay
0 to 9,999 seconds
Fail-Safe Operation
Independent for each relay
Alarm Operation
Auto, Auto-man, Latch, Latch w/clear
Alarm Indication
Red backlight, Flashing display, Alarm Message, Alarm symbol (!)
Alarm Message
On or Off; User programmable, 8 characters maximum. Displayed every 10 sec for 1 sec on bottom
Alarm Acknowledge
Front panel ACK button or external digital in­put resets output and screen indication
Auto Initialization
When power is applied to the meter, relays will reflect the state of the input to the meter
Timer Output
One-shot or Continuous Off Time Delay: 1 sec to 99:59:59
(hrs:min:sec) On Time: 1 sec to 99:59:59 (hrs:min:sec)
Timer Start/Stop
Front panel or digital input, user selectable

4-20 mA Transmitter Output

Output Source
Rate, total, re-transmit; reverse scaling allowed
Scaling Range
1.00 to 23.0 mA
Disable
High impedance state, less than 1 mA
Calibration
Factory calibrated 4.00 to 20.00 mA
Underrange
1.0 mA, 3.5 mA, or 3.8 mA (If input < 3.5 mA); or Off; user selectable
Overrange
20.5 mA, 20.8 mA, or 23.0 mA (If input > 20.5 mA); or Off; user selectable
Isolation
500 V
Accuracy
±0.05% FS ±0.001mA
Temperature Drift
0.5 µA/°C max from -40 to 75°C ambient
External Loop Power Supply
7.0 VDC to 30.0 VDC maximum
Output Loop Resistance
10-750 Ω @ 24 VDC; 100-1100 Ω @ 30 VDC
Page 7
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
7

Safety Information

CAUTION: Read complete in-
structions prior to installation
and operation of the meter.
WARNING: Risk of electric
shock or personal injury.
Warning!
Hazardous voltages exist within enclosure. Installation and service should be performed only by trained service personnel.

Installation

There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applications.

Unpacking

Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier. If any part is missing or the meter malfunctions, please contact your supplier or the factory for assis­tance.

Panel Mounting Instructions

Prepare a standard 1/8 DIN panel cutout 3.622" x 1.772" (92 mm x 45 mm). Refer to Figure 1 be-
low, for more details.
Clearance: allow at least 4.0" (102 mm) behind the panel for wiring.  Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel,
0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼"
(6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Insert meter into the panel cutout.  Install mounting brackets and tighten the screws against the panel. To achieve a proper seal, tighten
the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
Figure 1. 1/8 DIN Panel Cutout Dimensions and Panel Mounting Details
!
Page 8
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
8

Mounting Dimensions

Figure 2. Meter Dimensions - Side View
Figure 3. Meter Dimensions - Front View

Connections

All connections are made to removable screw terminal connectors located at the rear of the meter.
Use copper wire with 60°C or 60/75°C insulation for all line voltage connections. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent damage to the me­ter and ensure personnel safety.

Connectors Labeling

The connectors’ label, affixed to the meter, shows the location of all connectors available with requested
configuration.
Figure 4. Connector Labeling for Fully Loaded PD6620
1.76"
(45mm)
0.59"
(15mm)
3.2"
(81mm)
2.45"
(62mm)
3.6"
(91mm)
Page 9
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
9

Current Loop (4-20 mA) Connections

Signal connections are made to a six-terminal connector labeled SIGNAL on Figure 4. The following fig­ures show a 4-20 mA current loop connected to the meter. The first figure shows the connection without the backlight and the second shows the connection with the backlight (the backlight may also be disa­bled/enabled in the SYSTEM menu). The meter is powered by the 4-20 mA current loop. There are no switches or jumpers to set up for the input. Setup and programming is performed through the front panel buttons.
Figure 5. 4-20 mA Input Connection without Backlight
Figure 6. 4-20 mA Input Connection with Backlight
The current input is protected against current overload up to 1 amp. The display may or may not show a fault condition depending on the nature of the overload.

Digital Input Connection

A digital input is standard on the meter. This digital input is connected with a normally open contact across DI+ and DI-, or with an active low signal applied to DI+ and DI-.
Figure 7. Digital Input Connections
DI+ DI- mA- mA+ BL-X
DI+ DI- mA- mA+ BL-X
DI+ DI- mA- mA+ BL-X
Page 10
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
10

4-20 mA Output Connections

Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT. The 4-20 mA output must be powered from an external power supply.
Figure 8. 4-20 mA Output Connections

Solid State Relay Connections

Relay connections are made to two-terminal connectors labeled SSR1 and SSR2 in Figure 4. Each re­lay’s C terminal is common only to the normally open (NO) contact of the corresponding relay.
Figure 9. Solid State Relay Connections
I+ I-
C NO C NO
Internal
Load Load
Page 11
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
11

Open Collector Outputs

Open collector output 1 and 2 connections are made to terminals labeled O1+ and O1-, and O2+ and O2-. Connect the alarm or pulse input device as shown below.
Figure 10. Open Collector Output Connections
O1+ O1- O2+ O2-
Page 12
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
12

Setup and Programming

The meter is factory calibrated prior to shipment to read in
milliamps. The calibration equipment is certified to NIST standards.

Overview

There are no jumpers to set; setup and programming is done through the front panel buttons. The meter may be powered via the micro-USB connection located on the right side of the meter for the
purposes of programming only. The backlight will not work while the meter is powered via the USB con­nection.

Front Panel Buttons and Status LED Indicators

PD6622 PD6624
Button
Symbol
Description
LCD
Status
Menu
!
Alarm Indicator (PD6622 Only)
Right-Arrow/F1
Password Protection Indicator (PD6622 Only)
Up-Arrow/F2
G
Grand Total Indicator (PD6622 Only)
Enter/F3
T
Total Indicator (PD6622 Only)
Press the Menu button to enter or exit the Programming Mode at any time.  Press or hold the Right-Arrow button to scroll forward through the menus, select digits during nu-
meric programing, select characters during text programming, or decrement the value of a digit or character selected with the Up-Arrow button.
Press and hold the Right-Arrow button to zero or clear digits/characters while in data-entry mode.  Press or hold the Up-Arrow button to scroll backwards through the menus or to increment the value
of a digit or character.
Press the Enter button to access a menu or to accept a setting or programmed digit/character value.
Page 13
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
13

Display Functions & Messages

The meter displays various functions and messages during setup, programming, and operation. The following table shows the main menu functions and messages in the order they appear in the menu.
Parameter
Action/Setting Description
INPUT
Program the meter 4-20 mA input
SCALE RATE
Scale the rate input
UNITS
Select the display units
/SECOND
Units per second
/MINUTE
Units per minute
/HOUR
Units per hour
/DAY
Units per day
GAL/(T)
Gallons per time unit (T)
L/(T)
Liters per time unit (T)
IGAL/(T)
Imperial gallons per time unit (T)
M3/(T)
Cubic meters per time unit (T)
BBL/(T)
Barrels per time unit (T)
BUSH/(T)
Bushels per time unit (T)
cuYD/(T)
Cubic Yards per time unit (T)
cuFt/(T)
Cubic Feet per time unit (T)
cuIn/(T)
Cubic Inches per time unit (T)
LiBBL/(T)
Liquid barrels per time unit (T)
BBBL/(T)
Beer barrels per time unit (T)
HECtL/(T)
Hectoliter per time unit (T)
AF/(T)
Acre-Foot per time unit (T)
CUSTM/(T)
Custom unit per time unit (T)
INPUT 1
Program input 1 value
INP 1
Enter the input 1 value
DISP 1
Program display 1 value
DSP 1
Enter the display 1 value
INPUT 2
Program input 2 value (up to 32 points)
INP 2
Enter the input 2 value
DISP 2
Program display 2 value (up to 32 points)
DSP 2
Enter the display 2 value
SAVE?
Save programmed units, input, and display values
OUTPUT
Program the meter’s available out-
puts
OPEN COLLECTR
Program the meter’s open collec-
tor outputs
OUTPUT1
Open collector 1 setup
OUTPUT2
Open collector 2 setup
DISABLE
Disable the open collector
PULSE
Program the open collector for pulse output
ALARM
Program the open collector for alarm output
TIMER
Program the open collector as a timer
Parameter
Action/Setting Description
TOT RST
Program the open collector for to­tal reset
RELAY
Program the meter’s relay outputs
OUTPUT1
Relay 1 setup
OUTPUT2
Relay 2 setup
DISABLE
Disable the relay
ALARM
Program relay for alarm functional­ity
SAMPLE
Program relay for sample function­ality
TIMER
Program relay as a timer
BATCH
Program the relay for batch control functionality
INFO
View relay run time and cycle count
4-20 mA
Program the meter’s 4-20 mA out­put
RATE
Transmit a value based on the rate display
TOTAL
Transmit a value based on the to­tal display
RETRANS
Retransmit the 4-20 mA input sig­nal
DISABLE
Disable the 4-20 mA output
CONTROL
Program manual or automatic op­eration for the outputs
OC1
Open collector 1
OC2
Open collector 2
RELAY1
Relay 1
RELAY2
Relay 2
4-20 mA
4-20 mA output
AUTO
Set selected output to automatic operation
MANUAL
Manually control selected output operation
ADVANCED
Program the meter’s advanced
features
RATE
Advanced 4-20 mA rate input pro­gramming
FUNCTION
Select linear, square root, or pro­grammable exponent function
LINEAR
Set meter for linear function and select number of linearization points
SQROOT
Set meter for square root extrac­tion
EXPONENT
Set meter for programmable expo­nent and enter exponent value
SCALE.CAL
Scale or calibrate the 4-20 mA in­put
SCALE RATE
Scale the rate 4-20 mA input
CAL RATE
Calibrate the rate 4-20 mA input
Page 14
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
14
Parameter
Action/Setting Description
TOTAL
Advanced total programming
COUNT
Program the totalizer functionality
LIMIT
Set the number of digits used for the total
8-DIGIT
Eight digits max (99999999)
13-DIGIT
Thirteen digits max (9999999999999) (Requires top line to display entire number, total will flash when number overflows to top line)
INITIAL
Set the total to start at a specific number
RESET
Enable or disable the ability to re­set the total
ENABLE
Enable total reset (default)
DISABLE
Disable total reset
GTOTAL
Advanced grand total program­ming
COUNT
Program the totalizer functionality
LIMIT
Set the number of digits used for the total
8-DIGIT
Eight digits max (99999999)
13-DIGIT
Thirteen digits max (9999999999999) (Requires top line to display entire number, total will flash when number overflows to top line)
INITIAL
Set the total to start at a specific number
RESET
Enable or disable the ability to re­set the grand total
ENABLE
Enable grand total reset (default)
DISABLE
Disable grand total reset
CUTOFF
Set low-flow cutoff
DISABLE
Disable low-flow cutoff
ENABLE
Enable low-flow cutoff
FILTER
Set noise filter value
2.0 SEC
2 seconds
4.0 SEC
4 seconds
8.0 SEC
8 seconds
16.0 SEC
16 seconds
OFF
Turn filter off
1.0 SEC
1 second
PASSWRD
Set a password for the meter
MAIN
Program the main meter password
TOTAL
Program the total reset password
GTOTAL
Program the grand total reset password
USER
Assign function keys and digital in­put
F1
Assign F1 function key
F2
Assign F2 function key
F3
Assign F3 function key
Parameter
Action/Setting Description
DI
Assign digital input
DISP FN
Set the function key or digital input to display a value
DISPLAY
Cycle max, min, rate, total, and grand total
D RATE
Display the rate
D TOTAL
Display the total
DISP GT
Display the grand total
PCT.RATE
Display the rate’s percentage of
max (20 mA)
D UNITS
Display the rate, total, and grand total units
D TAG
Display the tags
DISPMIN
Display the minimum rate value
DISPMAX
Display the maximum rate value
MIN MAX
Display the minimum and maxi­mum rate value
D mA IN
Display the current mA input value
D mAOUT
Display the current mA output value
MENU FN
Set the function key or digital input to access a menu
RLYINFO
Go to relay information menu (INFO)
MANCTRL
Go to output control menu (CON­TROL)
TIMER.FN
Set the function key or digital input to start or stop a timer
STRT.ALL
Start all timers
STOP.ALL
Stop all timers
S.STP.ALL
Start or stop all timers
OC1
Start/stop open collector 1 timer
OC2
Start/stop open collector 2 timer
RLY1
Start/stop relay 1 timer
RLY2
Start/stop relay 2 timer
START
Start the selected timer output
STOP
Stop the selected timer output
STR-STP
Start or stop the selected timer output
BATCH.FN
Set the function key or digital input to batch control
START
Start a batch
STOP
Stop a batch
STR-STP
Start or stop a batch
PRESET
Preset batch amount
ALARM.FN
Set the function key or digital input to acknowledge an alarm
ACK
Acknowledge all active alarms
HOLD FN
Set the function key or digital input to hold an output
HOLD.OUT
Hold all outputs
HLD.UNHLD
Hold or un-hold all outputs
Page 15
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
15
Parameter
Action/Setting Description
OC1+2
Hold/un-hold open collector out­puts
RLY1+2
Hold/un-hold relay outputs
mAOUT
Hold/un-hold 4-20 mA output
HOLD
Hold selected output
HLD.UNHLD
Hold or un-hold selected output
DISABLE
Disable the function key or digital input
RST FN
Set the function key or digital input to reset a value
RESET
Reset min, max, or max/min PV value
R MIN.MAX
Reset max and min PV value
RST T
Reset the total
RST GT
Reset the grand total
RST T.GT
Reset the total and grand total
HINT
Display hint text on first key press and execute action on second key press
OFF
Turn the hint function off
ON
Turn the hint function on
SYSTEM
Program system settings
AOUTCAL
Calibrate the analog output
DEFAULT
Reset meter to factory defaults
TOTAL
Enable or disable the totalizer
ENABLE
Enable the totalizer (Default)
DISABLE
Disable the totalizer (see PD6602 manual)
BACKLITE
Enable or disable the display back­light
ENABLE
Enable the backlight (default)
DISABLE
Disable the backlight
INFO
View meter software, version, and model, and change the meter iden­tifier tag
SFT
The software ID number
VER
The software version
MODEL
The meter hardware model num­ber
ID.TAG
The meter identifier tag Press Enter to edit tag
ICAL
Internal calibration used for scaling
DISPLAY
Program the meter’s display
UNITS
Change the display units within the selected unit class
DEC.PT
Change the decimal point location
RATE
Program the rate decimal point
TOTAL
Program the total decimal point
GTOTAL
Program the grand total decimal point
Parameter
Action/Setting Description
COMMA
Enable or disable the use of a comma to separate the thousands place on the bottom display
ENABLE
Enable comma (default)
DISABLE
Disable comma
TOP
Set what to display on the top line
RATE
Display the rate
RATE+U
Display the rate and its units alter­nating
TOTAL
Display the total
TOTAL+U
Display the total and its units alter­nating
TAG
Display the tag
UNITS
Display the units
PRESET
Display the preset value
BOTTOM
Set what to display on the bottom line
TOTAL
Display the total
TOTAL+U
Display the total and its units alter­nating
TOT+TAG
Display the total and its tag alter­nating
T+U+RU
Display the total, its units, and the rate units alternating
GTOTAL
Display the grand total
GT+UNITS
Display the grand total and its units alternating
GT+TAG
Display the grand total and its tag alternating
GT+U+RU
Display the grand total, units, and rate units alternating
RATE
Display the rate
RATE+TU
Display the rate and the total’s
units alternating
RATE+U
Display the rate and its units alter­nating
RATE+TAG
Display the rate and its tag alter­nating
R UNITS
Display the rate units
T UNITS
Display the total units
TAG
Display the tag
UNITS
Display the units
PRESET
Display the preset value
TAG+RU
Display the tag and rate units alter­nating
TAG+TU
Display the tag and total units al­ternating
OFF
Disable the bottom display
R PCT
Display the rates percentage of max (20 mA)
ma IN
Display the current mA input value
mA OUT
Display the current mA output value
Page 16
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
16

Main Menu

The main menu consists of all the meter’s programmable functions: Input, Output, Advanced, and Dis­play. Press Menu button to enter Pro-
gramming Mode then press the
Right-Arrow button to move for­ward through the menu and the Up-Arrow button to move back.
Press Menu at any time to exit and
return to Run Mode. Changes made to settings prior to pressing Enter are not saved.
Changes to the settings are saved
to memory only after pressing En- ter/F3 to confirm the setting or pressing Enter/F3 at the SAVE? screen when available.

Setting Numeric Values

The numeric values are set using the Right and Up-Arrow buttons. Press Right-Arrow to select next digit and Up-Arrow to increment digit value. The selected digit will flash.
Press and hold Up-Arrow to auto-increment the display value. If you have made a mistake or would like to enter a new value, select the left-most digit and press and hold the Right-Arrow button until all digits reset to zero.
Press the Enter button at any time to accept a setting or Menu button to exit without saving changes. Note: the underscore in the graphic below is provided to show which digit would be flashing.
DSP 1
+00,000.00
DSP 1
00,000.00
Select
Digit to
Change
DSP 1
00,050.00
Increment
Selected
Digit
SCALE
INPUT 1
Accept Setting
52.86
38,418.2
SETUP
INPUT
SETUP
OUTPUT
SETUP
ADVANCED
SETUP
DISPLAY
SCALE
RATE
OPEN
COLLECTR
ADV
RATE
DSPLY
UNITS
OUT
RELAY
OUT
4-20 mA
OUT
CONTROL
CUTOFF
FILTER
PASSWRD
USER
SYSTEM
DSPLY
DEC.PT
DSPLY
COMMA
DSPLY
TOP
DSPLY
DOTTOM
SCALE
UNITS
SCALE
INPUT 1
SCALE
DISP 1
SCALE
INPUT 2
SCALE
DISP 2
SAVE?
ADV
TOTAL
ADV
GTOTAL
Run Mode
Page 17
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
17

Setting Up the Input Signal (INPUT)

It is very important to read the following information, before proceeding to program the meter:
The meter is factory calibrated prior to shipment to display 0-100 gal/s, which corresponds to the 4-20
mA input. The calibration equipment is certified to NIST standards. A calibrated signal source is not needed to scale the meter. Enter the Input menu to scale the meter to display the 4-20 mA input. The input is capable of accepting
any signal from 4 to 20 mA.
SETUP
INPUT
SCALE
RATE
SCALE
UNITS
SCALE
INPUT 1
SCALE
DISP 1
TIME
/SECOND
UNIT
GAL/S
/SECOND /MINUTE /HOUR /DAY
Rate Time
Bases
INP 1
04.000
INP 1
mA
Flashes Units
Momentarily
DSP 1
+00,000.00
SCALE
INPUT 2
INP 2
20.000
SCALE
DISP 2
DSP 2
+00,100.00
SAVE? SETUP
INPUT
GAL/(T) L/(T) IGAL/(T)
Rate Units
M3/(T) BBL/(T) BUSH/(T)
cuYD/(T) cuFt/(T) cuIn/(T)
LiBBL/(T) BBBL/(T) HECtL/(T)
AF/(T) CUSTM/(T)
Page 18
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
18

Available Unit Classes and Units

The meter has six available preprogrammed unit classes, volume, height, temperature, pressure, weight, and rate. Each unit class has the following available units to choose from:
Rate Time Bases (TIME)
/SECOND
Units per second
/MINUTE
Units per minute
/HOUR
Units per hour
/DAY
Units per day
Rate Units (RATE)
GAL/(T)
Gallons per time unit (T)
L/(T)
Liters per time unit (T)
IGAL/(T)
Imperial gallons per time unit (T)
M3/(T)
Cubic meters per time unit (T)
BBL/(T)
Barrels per time unit (T)
BUSH/(T)
Bushels per time unit (T)
cuYD/(T)
Cubic Yards per time unit (T)
cuFt/(T)
Cubic Feet per time unit (T)
cuIn/(T)
Cubic Inches per time unit (T)
LiBBL/(T)
Liquid barrels per time unit (T)
BBBL/(T)
Beer barrels per time unit (T)
HECtL/(T)
Hectoliter per time unit (T)
AF/(T)
Acre-Foot per time unit (T)
CUSTM/(T)
Custom unit per time unit (T)

Setting Custom Units (CUSTM)

When the desired unit of measure is not available, a custom unit may be programmed. Select the CUSTOM menu in order to enter a custom unit name.
Text values are set using the Right and Up-Arrow buttons. Press Right-Arrow to select next character and Up-Arrow to increment character value. The selected character will flash. Press and hold the Up or
Right-Arrow buttons to auto-increment or decrement the character. Press Enter to accept the character.
Notes:
Press and hold the Right Arrow while no character is being edited to erase all characters to the
right of the flashing character
Press and hold Up or Right Arrow to auto-increment or decrement a selected character.
All text values, including tags and alarm messages, are set in a similar fashion.

Scaling the 4-20 mA Input

The 4-20 mA input can be scaled to the appropriate values for a given application. The 4-mA input (input
1) should have a corresponding display value (display 1) which represents the low end of the process value range being measured by the transmitter. Likewise, the 20-mA input (input 2) should have a display value (display 2) which represents the high end of the process value range.
For example: If the meter is setup to accept a 4-20 mA input and display the flow of a pipe whose rate of flow is between 0 and 100 gal/s, the transmitter would send a 4-mA signal when there is zero flow and a 20-mA signal when there is maximum flow. The meter should be programmed to interpret these inputs on a display range of 0-100, so that at 4-mA the meter will display 0 and at 20-mA the meter will display 100.
Processes which require a non-linear scale can be accommodated using the linear (LINEAR), exponent (EXPONENT), and square root (SQROOT) functions available in the Advanced menu. See Signal Input Conditioning Functions (FUNCTION) on page 32.
A signal source is not needed to scale the meter; simply program the inputs and corresponding display values.
C.UNIT
ABC
C.UNIT
ABC
Select
Character
to Change
C.UNIT
ACC
Increment
Selected
Character
C.UNIT
ABC
Decrement
Selected
Character
C.UNIT
ABC
Accept
Character
Change
Accept
Custom Unit
Name
Page 19
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
19

Setting the Display Features (DISPLAY)

The meter’s display functions may be programmed using the Display menu. This menu consists of the following submenus: Units, Decimal Point, Comma, Bargraph (PD6624 Only), Top, and Bottom.

Changing the Units (UNITS)

It is possible to change the display units without the need to re-scale the meter. When selecting a new unit from within the DISPLAY menu (e.g. changing from gallons/sec. (GAL/s) to liters/sec. (L/s)), the meter will automatically convert the display values to display the new unit. Enter the UNITS menu, select a new unit of measure from the list of predefined units, and press the Enter button. If entering a custom unit (CUSTM), a custom conversion factor will need to be entered.

Changing the Decimal Point Location (DEC.PT)

The decimal point may be set with up to seven decimal places or with no decimal point at all. Pressing the Right Arrow moves the decimal point one place to the right until no decimal point is dis­played, and then it moves to the leftmost position. Pressing the Up-Arrow moves the decimal point one place to the left. The decimal point location is set independently for the rate, total and grand total.

Enabling or Disabling the Comma on the Bottom Display (COMMA)

The bottom display is set to show a comma separating the thousands and millions place by default if a numeric value is being displayed. This feature can be disabled or enabled using the Comma menu.

Programming the Bargraph (PD6624 Only)

The PD6624 comes equipped with a bargraph display for applications where a visual representation of
the rate, or total’s percentage of full scale is desirable. This feature can be changed to represent either
rate or total, or disabled, using the Bargraph menu (BARGRAPH). If the bargraph is set to represent total, the total full scale will need to be set.
DEC.PT
222222.22
DEC.PT
1111111.1
Move Decimal
to the Right
DEC.PT
222222.22
DSPLY
COMMA
Accept Decimal Location
DEC.PT
RATE
Move Decimal
to the Left
DSPLY
BARGRAPH
GRAPH
RATE
GRAPH
TOTAL
GRAPH
OFF
SETUP
DISPLAY
DSPLY
UNITS
DSPLY
DEC.PT
DSPLY
COMMA
DSPLY
TOP
DSPLY
DOTTOM
DSPLY
BARGRAPH
PD6624 Only
Page 20
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
20

Changing What is Displayed (TOP and BOTTOM)

The two display lines (Top and Bottom) can be programmed to display different values. Use the Top and Bottom menus to make these changes. If PV2 is enabled, additional options will be available for display-
ing the second PV on the bottom display.
The top display (TOP) can display:
Rate  Rate and its units alternating  Total  Total and its units alternating  Tag  Units  Preset batch value
The bottom display (BOTTOM) can display:
Total (with units or tag alternating)  Total, its units, and the rate units alternating  Grand total (with units or tag alternating)  Grand total, units, and rate units alternating  Rate (with units or tag alternating)  Rate and the total’s units alternating Rate or total units  Tag  Units  Preset batch value  Tag and rate units alternating  Tag and total units alternating  Nothing  Rate's percentage of max scale  mA input value  mA output value
DSPLY
TOP
DSPLY
DOTTOM
DSPLY
RATE
DSPLY
RATE+U
DSPLY
TOTAL
DSPLY
TOTAL+U
DSPLY
TAG
DSPLY
PRESET
DSPLY
UNITS
DSPLY
TOTAL
DSPLY
TOTAL+U
DSPLY
TOT+TAG
DSPLY
T+U+TAG
DSPLY
GTOTAL
DSPLY
GT+UNITS
DSPLY
GT+TAG
DSPLY
RATE
DSPLY
GT+U+RU
DSPLY
RATE+U
DSPLY
RATE+TU
DSPLY
RATE+TAG
DSPLY
R UNITS
DSPLY
T UNITS
DSPLY
TAG
DSPLY
UNITS
DSPLY
PRESET
DSPLY
TAG+TU
DSPLY
TAG+RU
DSPLY
R PCT
DSPLY
OFF
DSPLY
mA OUT
DSPLY
mA IN
Page 21
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
21

Programming the Outputs (OUTPUT)

Depending on the purchased model, the meter may be available with two open collector outputs, two solid state relays, and one 4-20 mA output. The Output menu will only show options for the available out­puts. See Ordering Information on page 4 for details.
SETUP
OUTPUT
OPEN
COLLECTR
OUT
RELAY
OUT
4-20 mA
OUT
CONTROL
OC.OUT
OUTPUT1
OC.OUT
OUTPUT2
RELAY
OUTPUT1
RELAY
OUTPUT2
RELAY
INFO
4-20
RATE
4-20
RETRANS
4-20
DISABLE
CTRL
OC1
CTRL
OC2
CTRL
RELAY1
CTRL
RELAY2
CTRL
4-20 mA
4-20
TOTAL
Page 22
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
22

Open Collector Outputs (OPEN COLLECTR)

The meter is equipped with two NPN open collector outputs that may be set up for pulse outputs, alarms, timed pulses, total reset, or turned off. Pulse outputs can be set to transmit the rate, total, or grand total. Output 2 may be used to generate a quadrature output based on the other open collector output. An output test mode is also selectable to generate pulses at a constant programmable frequency. Alarms are available based on the PV value or the digital input. The alarm status will show on the display even if the output is not wired. A timer output turns the open collector on and off at a specified frequency to act as a timer. A total reset output generates a pulse whenever the total is reset, regardless of the reset method used. The On time is programmable between 0 and 9,999 seconds. The output may be disabled by selecting DISABLE.
SETUP
OUTPUT
OPEN
COLLECTR
OC.OUT
OUTPUT1
OC.OUT
OUTPUT2
OUT 1
PULSE
PULSE
RATE
PULSE
QUAD
*Available for output
2 only.
*
OUT 1
ALARM
OUT 1
TIMER
OUT 1
DISABLE
ALARM
RATE
ALARM
D.INPUT
TIMER
OFF.DLAY
TIMER
ON TIME
TIMER
MODE
TIMER
START
MODE
CONT
MODE
ONE.SHOT
PULSE
TEST
OUT 1
TOT RST
TIME
0000 SEC
PULSE
TOTAL
PULSE
GTOTAL
ALARM
TOTAL
ALARM
GTOTAL
Page 23
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
23
Pulse (PULSE)
Pulse outputs may be assigned to output the rate, total, or grand total at a programmable factor. The fac­tor determines the number of pulses per second which should be generated per unit of measure. For ex­ample, if the meter display shows 100 gallons and the factor is set to 2, the number of pulses generated per second would be 200. The maximum frequency is 250 Hz. Setting output 2 to quadrature will duplicate the other open collector output, but lag by 90 degrees out of phase. The other output should be programmed as desired for the quadrature output function, and must be a pulse (PULSE) output selection. The quadrature maximum frequency for both outputs is 125 Hz.
The TEST option will output a fixed number of pulses per second based on the FREQ value entered.
OUT 1
PULSE
PULSE
TEST
PULSE
QUAD
*Available
for output
2 only.
*
FACTR
GAL/S
Flashes
Units
FACTR
+0,001.000
FREQ
100.0
PULSE
RATE
PULSE
TOTAL
PULSE
GTOTAL
Page 24
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
24
Alarm (ALARM)
Alarm outputs may be assigned to the rate, total, grand total, or the digital input. When assigned to the rate, the alarm may be set as either a high alarm or a low alarm. Alarm actions (AUTO, AUTO.MAN, LATCH, L-CLEAR) determine how and when the alarm should be reset. They operate as follows:
Automatic (AUTO): Alarm will reset automatically once the alarm condition has cleared.  Automatic/Manual (AUTO.MAN): Alarm will reset automatically once the alarm condition has
cleared but can also be reset using the Enter button (or whichever function key is set to acknowledge).
Latching (LATCH): Alarm will not reset automatically even if the alarm condition is cleared. Press
the Enter button at any time to clear the alarm.
Latching w/ Clear (L-CLEAR): Alarm will not reset automatically. Press the Enter button once
the alarm condition has cleared to reset the alarm.
If the alarm is set to rate, a set and reset point must be programmed. The set point is the display value at which the alarm will turn on and the reset point is the display value at which the alarm will turn off. If the set point is lower than the reset point, the alarm will be a low alarm; if the set point is higher than the reset point, the alarm will be a high alarm. If the alarm is set to total or grand total, only a set point needs to be programmed. The digital input alarm will engage whenever the digital input is triggered. For all alarms, a delay before the alarm is turned on or off may be set, as well as a failsafe feature which will inverse the on/off programming. Alarm states will be displayed on the meter even if no open collector output is physically connected. The alarm indicator (!) will display as well as optional red LED backlight, flashing rate, total, or grand total value (rate, total, or grand total alarms only), and a programmable alarm message.
OUT 1
ALARM
ALARM
D.INPUT
ALARM
ACTION
ACTN
AUTO
ACTN
AUTO.MAN
ACTN
LATCH
ACTN
L-CLEAR
SET
+00,040.00
SET
GAL
Flashes
Units
ALARM
RESET
ALARM
SET
RESET
+00,030.00
ALARM
DELAY
DELAY
ON
TIME
0000 SEC
DELAY
OFF
TIME
0000 SEC
ALARM
FAILSAFE
Rate, Total, GTotalAlarm Only
FSAFE
OFF
ALARM
DISPLAY
RED
ON
FLASH
ON
ALARM
GTOTAL
Rate Alarm Only
Rate, Total, Gr.
ALARM
RATE
ALARM
TOTAL
MSG
ON
MSG
ALARM 1
TotalAlarm Only
Page 25
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
25
Timer (TIMER)
The timer output produces a constant width pulse at a constant frequency. Program the Off Delay (OFF.DLAY) from 1 second to 99 hours 59 minutes and 59 seconds. This is the time it takes from selecting START to turning on the output and for how long the output is off in continuous mode.
Program the On Time (TIME) for the active low pulse from 1 second to 99 hours 59 minutes and 59 seconds (pulse width). This is the period of time for which the output will remain on.
The timer output may be set to generate the timed pulse only once (ONESHOT) or continuously (CONT). Select Start (START) to begin outputting the constant timed pulse. Select Stop (STOP) to end outputting the constant timed pulse. Function keys or the digital input may be assigned to start and stop timer functions (see the USER menu
in Advanced).
OUT 1
TIMER
TIMER
OFF.DLAY
TIMER
ON TIME
TIMER
MODE
TIMER
START
MODE
CONT
MODE
ONE.SHOT
H.MM.SS
00.01.00
H.MM.SS
00.00.01
TIMER
STOP
Page 26
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
26

Solid State Relay Outputs (RELAY)

The meter is optionally equipped with two solid state relays that may be set up for alarms, sample, timer, or batch control. Alternatively, they may be disabled. Alarms are available based on the rate, total, or grand total value, or the digital input. The alarm status will show on the display even if the output is not wired. Sample will engage the relay for a programmed period of time when either the total or the grand total have reach a programmed amount. A timer output turns the relay on and off at a specified frequency to act as a timer. For use in batch control applications, the meter relays may be set to batch. This will enable the batch control features of the meter. The output may be disabled by selecting DISABLE.
Caution!
During setup, the relays do not follow the input and they will remain in the state found prior to entering the Relay menu.
!
SETUP
OUTPUT
OPEN
COLLECTR
OUT
RELAY
RELAY
OUTPUT1
RELAY
OUTPUT2
RELAY
INFO
INFO
RELAY 1
INFO
RELAY 2
RLY 1
DISABLE
RLY 1
ALARM
RLY 1
SAMPLE
RLY 1
TIMER
ALARM
RATE
ALARM
D.INPUT
TIMER
OFF.DLAY
TIMER
ON TIME
TIMER
MODE
TIMER
START
SAMPL
TOTAL
SAMPL
GTOTAL
RLY 1
BATCH
BATCH
COUNT
BATCH
MAXIMUM
BATCH
MODE
BATCH
PRESET
BATCH
DELAY
ALARM
TOTAL
ALARM
GTOTAL
Page 27
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
27
Alarm (ALARM)
Alarm outputs may be assigned to the rate, total, or grand total values, or the digital input. When assigned to the rate, the alarm may be set as either a high alarm or a low alarm. Alarm actions (AUTO, AUTO.MAN, LATCH, L-CLEAR) determine how and when the alarm should be reset. They operate as follows:
Automatic (AUTO): Alarm will reset automatically once the alarm condition has cleared.  Automatic/Manual (AUTO.MAN): Alarm will reset automatically once the alarm condition has
cleared but can also be reset using the Enter button (or whichever function key is set to acknowledge).
Latching (LATCH): Alarm will not reset automatically even if the alarm condition is cleared. Press
the Enter button at any time to clear the alarm.
Latching w/ Clear (L-CLEAR): Alarm will not reset automatically. Press the Enter button once
the alarm condition has cleared to reset the alarm.
If the alarm is set to rate, a set and reset point must be programmed. The set point is the display value at which the alarm will turn on and the reset point is the display value at which the alarm will turn off. If the set point is lower than the reset point, the alarm will be a low alarm; if the set point is higher than the reset point, the alarm will be a high alarm. If the alarm is set to total or grand total, only a set point needs to be programmed. The digital input alarm will trigger whenever the digital input is triggered. For all alarms, a delay before the alarm is turned on or off may be set, as well as a failsafe feature which will inverse the on/off programming. Alarm states will be displayed on the meter even if no relay output is physically connected. The alarm in­dicator (!) will display as well as optional red LED backlight, flashing rate, total, or grand total value (rate, total, or grand total alarms only), and a programmable alarm message.
RLY 1
ALARM
ALARM
D.INPUT
ALARM
ACTION
ACTN
AUTO
ACTN
AUTO.MAN
ACTN
LATCH
ACTN
L-CLEAR
SET
+00,040.00
SET
GAL
Flashes
Units
ALARM
RESET
ALARM
SET
RESET
+00,030.00
ALARM
DELAY
DELAY
ON
TIME
0000 SEC
DELAY
OFF
TIME
0000 SEC
ALARM
FAILSAFE
Rate, Total, GTotalAlarm Only
FSAFE
OFF
ALARM
DISPLAY
RED
ON
FLASH
ON
ALARM
GTOTAL
Rate Alarm Only
Rate, Total, Gr.
ALARM
RATE
ALARM
TOTAL
MSG
ON
MSG
ALARM 1
TotalAlarm Only
Page 28
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
28
Sample (SAMPLE)
A relay set to sample will trigger when the total or grand total value has incremented by a programmed amount. The relay can be programmed to stay on for a specified amount of time. For example: if a relay is set to sample the total with a COUNT of 1,000 and a TIME of 10 seconds, the relay will engage for 10 seconds whenever the total has incremented by 1,000 (e.g. 1000, 2000, 3000).
Timer (TIMER)
The timer output produces a constant width pulse at a constant frequency. Program the Off Delay (OFF.DLAY) from 1 second to 99 hours 59 minutes and 59 seconds. This is the time it takes from selecting START to turning on the output and for how long the output is off in continuous mode.
Program the On Time (TIME) for the active low pulse from 1 second to 99 hours 59 minutes and 59 seconds (pulse width). This is the period of time for which the output will remain on.
The timer output may be set to generate the timed pulse only once (ONESHOT) or continuously (CONT). Select Start (START) to begin outputting the constant timed pulse. Select Stop (STOP) to end outputting the constant timed pulse. Function keys or the digital input may be assigned to start and stop timer functions (see the USER menu
in Advanced).
TOTAL
COUNT
COUNT
GAL
COUNT
0,001,000.0
SAMPL
TIME
TIME
0010 SEC
RLY 1
SAMPLE
SAMPL
TOTAL
SAMPL
GTOTAL
Flashes
Units
RLY 1
TIMER
TIMER
OFF.DLAY
TIMER
ON TIME
TIMER
MODE
TIMER
START
MODE
CONT
MODE
ONE.SHOT
H.MM.SS
00.01.00
H.MM.SS
00.00.01
TIMER
STOP
Page 29
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
29
Batch Control (BATCH)
Selecting batch control for relay 1 will enable batching features on the meter. The top display will be changed to show the total and the bottom display will be changed to display the preset batch amount. The function keys will be changed so that F1 starts a batch, F2 opens the preset menu to allow the preset value to be changes, and F3 stops the currently running batch. Enabling batch control for relay 1 will al­low access to the BATCH menu under relay 2 (this menu does not appear by default).
Batch Control Relay 1
The batch total can be set to count UP or DOWN. The batch MAXIMUM is the max preset amount that can be batched. Batching can be set to either manual or automatic operation (MANUAL or AUTO). If setting batching to automatic, a delay before the next batch is started must be programmed. The PRESET amount is the value at which the batch will stop and can be programmed up to the value assigned in the MAXIMUM menu. An on and off delay may be set for batching relays.
Batch Control Relay 2
The BATCH option only appears under relay 2 if relay 1 has also been set to batch control. The second relay may be programmed as a preclose relay or as another batching relay with its own preset amount.
RLY 1
BATCH
BATCH
COUNT
BATCH
MAXIMUM
BATCH
MODE
BATCH
PRESET
COUNT
UP
COUNT
DOWN
MAX
GAL
MAX
0,010,000.0
Flashes
Units
MODE
MANUAL
MODE
AUTO
PSET
GAL
PSET
0,001,000.0
Flashes
Units
BATCH
DELAY
DELAY
ON
TIME
0000 SEC
DELAY
OFF
TIME
0000 SEC
DELAY
9999 SEC
RLY 2
BATCH
BATCH
PRECLOSE
YES
PRECLOSE
NO
PRECLOSE
CLOSE
GAL
CLOSE
0,000,800.0
Flashes
Units
BATCH
DELAY
DELAY
ON
TIME
0000 SEC
DELAY
OFF
TIME
0000 SEC
BATCH
PRESET2
PSET2
GAL
PSET2
0,000,800.0
Flashes
Units
Page 30
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
30
Relay Information (INFO)
The relay information menu shows run times and cycle counts for each relay. These values may be cleared at any time by selecting the Clear option (CLEAR?).

4-20 mA Output (4-20 mA)

The 4-20 mA menu is used to scale the 4-20 mA output based on display values. This menu is not present on models without a 4-20 mA output option.
The 4-20 mA analog output (if equipped) can be scaled to provide a 4-20 mA signal for the rate or total display range or to simply retransmit the 4-20 mA input. The output may be disabled (DISABLE), and will only output the minimum signal.
Overrange and underrange values determine what mA signal the meter will output if the mA input is underrange (<3.5 mA) or overrange (>20.5 mA). This value may be set to 1-mA, 3.5-mA, 3.8-mA, 20.5­mA, 20.8-mA, 23-mA, or disabled.
No equipment is needed to scale the analog output; simply program two display values and corresponding mA output signals.
Rate or Total (RATE or TOTAL)
To scale the analog output, enter display value 1 and a corresponding analog output value for this display, then enter display value 2 and a corresponding analog output value for this display value. This will provide a linearly scaled analog output.
Retransmit (RETRANS)
This option will retransmit the 4-20 mA analog input without the need to scale the output.

Output Control (CONTROL)

The Control menu is used to control the open collector outputs, 4-20 mA analog output, or the relays manually, ignoring the input. Each open collector, relay, and analog output can be programmed inde­pendently for manual control. Selecting automatic control sets all relays and analog output for automatic operation.
INFO
RELAY 1
RELAY
RUNTIME
Flashes
Momentarily
TIME
195.0 H
CYCLE
COUNT
CYCLE
51
RLY 1
CLEAR?
Flashes
Momentarily
SETUP
OUTPUT
OPEN
COLLECTR
OUT
RELAY
OUT
4-20 mA
4-20
RETRANS
4-20
DISABLE
DSP 1
+00,000.00
DSP 1
GAL
Flashes
Units
OUT 1
04.000
DSP 2
+00,100.00
OUT 2
20.000
AOUT
UNDER
U-RNG
DISABLE
AOUT
OVER
O-RNG
DISABLE
AOUT
SCALE
4-20
RATE
4-20
TOTAL
Page 31
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
31

Advanced Features Menu (ADVANCED)

To simplify the setup process, functions not needed for most applications are located in the Advanced Features menu. The options under advanced features include: advanced rate, total, and grand total setup, cutoff, filter, password, function key programming, and system settings.

Advanced Rate, Total, and Grand Total Setup (ADV RATE, TOTAL, GTOTAL)

The Advanced Rate menu contains options to apply signal input conditioning functions to the input and scale/calibrate the input signal. The Advanced Total and Advanced Grand Total menus contain options to change how the value is incremented and if it can be manually reset by the user.
SETUP
ADVANCED
ADV
PV SETUP
CUTOFF
FILTER PASSWRD USER
SYSTEM
ADV
TOTAL
ADV
GTOTAL
ADV
RATE
RATE
FUNCTION
RATE
SCALE.CAL
ADV
TOTAL
LIMIT
13-DIGIT
RATE
LINEAR
RATE
SQROOT
RATE
EXPONENT
SCALE
RATE
CAL
RATE
ADV
GTOTAL
TOTAL
COUNT
TOTAL
RESET
COUNT
LIMIT
LIMIT
8-DIGIT
COUNT
INITIAL
COUNT
INITIAL
00000
0,000,000.0
COUNT
0,000,000.0
RESET
ENABLE
RESET
DISABLE
Page 32
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
32
Signal Input Conditioning Functions (FUNCTION)
The Function menu is used to select the signal input conditioner applied to the input: linear, square root, or programmable exponent calculation. Multi-point linearization is part of the linear function selection. Meters are set up at the factory for linear function with 2-point linearization. The linear function provides a display that is linear with respect to the input signal.
Square Root Linearization (SQROOT)
The square root function can be used to linearize the signal from a differential pressure transmitter and display flow rate in engineering units.
Programmable Exponent Linearization (EXPONENT)
The programmable exponent can be used to linearize the signal from level transmitters in open-channel flow applications using weirs and flumes.
Multi-Point Linearization (LINEAR)
Meters are set up at the factory for linear function with 2-point linearization. Up to 32 linearization points can be selected for the scaled value under the linear function. Multi-point linearization can be used to line­arize the display for non-linear signals to convert level to flow using weirs and flumes with complex expo­nent.
Advanced Total and Grand Total Programming (ADV TOTAL & ADV GTOTAL)
The advanced total and grand total menu contain the count (COUNT) and reset (RESET) menus. The count menu allows the digit limit to be selected between 8-digit (bottom line only) and 13-digit (uses top and bottom line to display full number) and an initial value at which the total or grand total should begin counting to be set. When using a 13-digit total or grand total, press the function key assigned to display (default: F1) to view the full amount once the value has exceeded 100,000,000 (decimal places are automatically truncated). If a 13-digit total or grand total is displayed on the bottom line and the value has exceeded nine digits, the truncated value will flash to indicate that it is not the complete value. The reset menu allows the resetting of total or grand total to zero to be enabled or disabled. Grand total reset may be permanently disabled by selecting YES at the PERMLOCK menu after disabling grand total reset. Use caution when selecting the PERMLOCK feature as once grand total reset has been perma­nently locked it cannot be unlocked.
Advanced Scaling and Calibration (SCALE.CAL)
This menu offers options to scale or calibrate the meter.
Scaling the Input (SCALE)
The scale menu in the Advanced menu is the same as the scale menu in the Input menu. See Setting Up the Input Signal (INPUT) on page 17 for details about scaling the meter.
Page 33
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
33
Calibrating the Input (CAL)
To scale the meter without a signal source, refer to Setting Up the Input Signal (INPUT), page 17.
The meter can be calibrated to display the process in engineering units by applying the appropriate input signal and following the calibration procedure. The CAL menu should be used with a live signal coming from a 4-20 mA transmitter connected to the process being measured.
During calibration, the mA input value will be displayed as INP 1 and INP 2. Adjust the input source un­til the desired mA value is shown. The use of a calibrated signal source is strongly recommended.
1. After accessing the SCALE.CAL menu, press the Right-Arrow button to scroll to the Calibration menu (CAL PV) and press Enter.
2. Select the appropriate units for the desired process variable, then press Enter. For information on units, see Available Unit Classes and Units on page 18.
3. The meter displays INP 1. Apply a known signal and press Enter. The display will flash while accepting the signal.
4. After the signal is accepted, the meter displays DSP 1. Enter a corresponding display value for the signal input, and press Enter to accept.
5. The meter displays INP 2. Apply a known signal and press Enter. The display will flash while accepting the signal.
6. After the signal is accepted, the meter displays DSP 2. Enter a corresponding display value for the signal input and press Enter to accept.
7. After completing calibration, the SAVE? display will need to be acknowledged using the Enter key before calibration will take effect.
RATE
SCALE.CAL
CAL
UNITS
TIME
/SECOND
UNIT
GAL/S
DSP 1
GAL/S
Flashes
Units
SCALE
RATE
CAL
RATE
INP 1
04.000 mA
DSP 1
+00,000.00
DSP 2
GAL
Flashes
Units
INP 2
20.000 mA
DSP 2
+00,100.00
SAVE?
Page 34
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
34

Low-Flow Cutoff (CUTOFF)

The low-flow cutoff feature allows the meter to be programmed so that the output from a flowmeter always displays zero on the meter at low flow rates. The cutoff value may be programmed from 0 to 999999.9. The meter will display zero below the cutoff value. Programming the cutoff value to zero disables the cutoff feature.

Noise Filter (FILTER)

The noise filter is available for unusually noisy signals that cause an unstable process variable display. The noise filter averages the input signal over a certain period. The filter level determines the length of time over which the signal is averaged. The filter level can be set between 1 and 16 seconds, or turned off. The higher the filter level, the longer the averaging time and so the longer it takes the display to settle to its final value. Setting the filter level to zero disables the filter function.
Noise Filter Bypass (BYPAS)
The noise filter bypass changes the behavior of the meter so that small variations in the signal are filtered out but large abrupt changes in the input signal are displayed immediately. The bypass value determines the minimum amount of signal change to be displayed immediately. All signal changes smaller than the bypass value are filtered or averaged by the meter. The noise filter bypass may be set between 0.0 and
99.9% of full scale.

Enabling Password Protection (PASSWRD)

The Password menu is used for programming security to prevent unauthorized changes to the pro­grammed parameter settings. There are three password types available: Main, Total, and Grand Total. The Main password prevents access to the meter Programming Mode. Total and Grand Total passwords prevent resetting of and changes to the total and grand total, respectively. In order to set a password, enter the Password menu and program a five-digit password. When the Main password has been enabled, the lock icon will display in the lower right of the display. For instructions on how to program numeric values see Setting Numeric Values, page 16.
Making Changes to a Password Protected Meter
If the Main password is enabled, the meter will display the message LOCKED when the Menu button is pressed. If the Total or Grand Total passwords are enabled, the meter will display the message LOCKED when trying to reset or change the total or grand total. Press the Enter button while the message is being displayed and enter the correct password to gain access to the menu. After exiting Programming Mode, the meter returns to its password protected condition.
Disabling Password Protection
To disable the Main, Total, or Grand Total passwords, access the Password menu and clear the desired password either by pressing and holding the Right Arrow button until all digits reset to zero or manually changing all of the digits to zero. When the Enter button is pressed, the meter will display UNLOCKED and will no longer require a password to access Programming Mode, or a password to reset or change the total or grand total, depending on which password was cleared.
Note: If the meter is password protected and the password has been forgotten, the password may be overridden using the master password: 50865
LOCKED
PASSWRD
PASS
MAIN
LOCK
00000
LOCK
12345
Enter Numeric
Password
PASSWRD
Flashes
Momentarily
Page 35
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
35

Programmable Function Keys User Menu (USER)

The User menu allows the user to assign the front panel function keys F1, F2, and F3, and the digital in­put (located on the signal input connector) to access most of the menus or to activate certain functions immediately (e.g. reset max & min, hold relay states, etc.). This allows the meter to be greatly customized for use in specialized applications.
Function Keys & Digital Input Available Settings
Refer to the following table for descriptions of each available function key or digital input setting.
Display
Description
DISP FN
Set the function key or digital input to display a value
DISPLAY
Cycle max, min, rate, total, and grand total
D RATE
Display the rate
D TOTAL
Display the total
DISP GT
Display the grand total
PCT.RATE
Display the rate’s percentage of max
(20 mA)
D UNITS
Display rate, total, and grand total units
D TAG
Display the tags
DISPMIN
Display the minimum rate value
DISPMAX
Display the maximum rate value
MIN MAX
Display the minimum and maximum rate value
D mA IN
Display the current mA input value
D mAOUT
Display the current mA output value
MENU FN
Set the function key or digital input to access a menu
RLYINFO
Go to relay information menu (INFO)
MANCTRL
Go to output control menu (CONTROL)
TIMER.FN
Set the function key or digital input to start or stop a timer
STRT.ALL
Start all timers
STOP.ALL
Stop all timers
S.STP.ALL
Start or stop all timers
OC1
Start/stop open collector 1 timer
OC2
Start/stop open collector 2 timer
RLY1
Start/stop relay 1 timer
Display
Description
RLY2
Start/stop relay 2 timer
START
Start the selected timer output
STOP
Stop the selected timer output
STR-STP
Start or stop the selected timer output
BATCH.FN
Set the function key or digital input to batch control
START
Start a batch
STOP
Stop a batch
STR-STP
Start or stop a batch
PRESET
Preset batch amount
ALARM.FN
Set the function key or digital input to acknowledge an alarm
ACK
Acknowledge all active alarms
HOLD FN
Set the function key or digital input to hold an output
HOLD.OUT
Hold all outputs
HLD.UNHLD
Hold or un-hold all outputs
OC1+2
Hold/un-hold open collector outputs
RLY1+2
Hold/un-hold relay outputs
mAOUT
Hold/un-hold 4-20 mA output
HOLD
Hold selected output
HLD.UNHLD
Hold or un-hold selected output
DISABLE
Disable function key or digital input
RST FN
Set the function key or digital input to reset a value
RESET
Reset min, max, or max/min PV value
R MIN.MAX
Reset max and min PV value
RST T
Reset the total
RST GT
Reset the grand total
RST T.GT
Reset the total and grand total
USER
USER
F1
USER
F2
USER
F3
USER
DI
USER
HINT
F1
DISP FN
F1
MENU FN
F1
TIMER.FN
F1
ALARM.FN
F1
HOLD FN
F1
RST FN
F1
DISABLE
HINT
OFF
HINT
ON
Page 36
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
36
Enabling the Function Key Hint Feature (HINT)
Enabling the function key hint feature will cause a hint message to be displayed when pressing the F1, F2, or F3 function keys. This text gives a brief description of what the button is programmed to do. Press­ing that function key a second time will execute that action. The hint feature does not affect the digital input (DI) which is intended for immediate execution.

Changing System Settings (SYSTEM)

The System menu contains the following menus: Analog Output Calibration, Restore Factory Defaults, Totalizer, Backlight, Information, and Internal Calibration.
Analog Output Calibration (AOUTCAL)
To perform the analog output calibration, it is recommended to use a milliamp meter with a resolution of at least 0.1 µA to measure the output current. The values saved internally during this procedure are used for scaling the 4-20 mA output in the Setup menu.
Resetting the Meter to Factory Defaults (DEFAULT)
When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults. To load factory defaults, enter the DEFAULT menu under the SYSTEM menu and press enter twice in quick succession. The meter will load the default settings and restart.
Disabling the Totalizer (TOTAL)
The totalizer can be disabled using the TOTAL menu. With the totalizer disabled, the meter will behave as a PD6602 or PD6604 process meter. Refer to the PD6602/4 instruction manual for instructions about pro­gramming a PD6602 or PD6604 process meter.
Enabling or Disabling the Backlight (BACKLITE)
The backlight may be enabled or disabled using the Backlight menu. The backlight is enabled by default, but the input must be wired appropriately in order for the backlight to function. See Current Loop (4-20 mA) Connections on page 9. The voltage drop is the same if the backlight is not wired or if it is disabled in the software.
Viewing System Information (INFO)
System information, such as software number, software version, and model number, may be viewed in the INFO menu. Press the Right Arrow button to cycle through all available meter information. Press En- ter to go back to the previous menu.
SYSTEM
SYSTM
AOUTCAL
SYSTM
DEFAULT
SYSTM
TOTAL
SYSTM
BACKLITE
SYSTM
INFO
SYSTM
ICAL
SYSTEM
SYSTM
AOUTCAL
SYSTM
DEFAULT
LOAD?
DEFAULT
RESET
DFAULT?
Meter Loads
Default Settings
and Restarts
Page 37
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
37
Calibrating the Internal mA Reference (ICAL)
The meter is factory calibrated prior to shipment to dis­play 0 to 100, which corresponds to the 4-20 mA input. The calibration equipment is certified to NIST standards.
The use of calibrated signal sources is necessary to calibrate the internal source of the meter. The me­ter’s internal source is what allows the user to scale the meter without applying a signal. Check calibration of the meter at least every 12 months. Note: Allow the meter to warm up for at least 15 minutes before performing the internal source calibration procedure. The Internal Calibration menu is part of the Advanced menu. Internal Calibration is performed as follows:
1. Press the Menu button to enter Programming Mode.
2. Press the Right Arrow button twice and press Enter to access the Advanced menu.
3. Press the Up-Arrow button and press Enter to access the System menu.
4. Press the Up-Arrow button and press Enter to access the ICAL menu.
5. The meter displays low input current message (4.000 mA). Apply a 4-mA signal and press Enter. The display flashes for a moment while the meter is accepting the low input signal.
6. After the display stops flashing, the display moves to the high input calibration (20.000 mA). Ap­ply the high input signal and press Enter. The display will flash again while the meter is accepting the high input signal.
SYSTM
ICAL
ICAL
4.000 mA
Display
Flashes While
Accepting Input
ICAL
20.000 mA
Display
Flashes While
Accepting Input
Apply 4-mA
Signal
Apply 20-mA
Signal
Page 38
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
38

Meter Operation

The meter is capable of accepting a 4-20 mA current signal and displaying it in engineering units from ­99,999 to 999,999 on the top line or from -9,999,999 to 99,999,999 on the bottom line. For example, a 4­20 mA signal could be displayed as -50.000 to 50.000.
The dual-line display can be customized by the user to operate in such a way as to satisfy a specific appli­cation. Typically, the top line is used for the rate variable while the bottom line is used for total, grand total, engineering units, or custom tag.

Front Panel Buttons Operation

Button Symbol
Description
Press to enter or exit Programming Mode, view set­tings, or exit max/min readings
Press to display max/min readings or other parame­ter/function assigned through the User menu
Press to reset max/min readings or other parame­ter/function assigned through the User menu
Press to acknowledge alarms or other parame­ters/function assigned through the User menu

Function Keys Operation

During operation, the programmable function keys operate according to the way they have been pro­grammed in the Advanced Features – User menu. The table above shows the factory default settings for F1, F2, and F3.
A hint message may be enabled in order to provide a description of what each function key does prior to executing their assigned function. See Enabling the Function Key Hint Feature (HINT) on page 36.

Digital Input Operation

A digital input is standard on the meter. This digital input is programmed identically to function keys F1, F2, and F3. The input is triggered with a contact closure between DI+ and DI-, or with an active low sig­nal. During operation, the digital input operates according to the way it has been programmed in the Ad- vanced Features User menu.

Maximum/Minimum Readings

The max & min readings (peak & valley) reached by the rate variable can be displayed either continu­ously or momentary:
1. Display briefly by pressing the F1 key (default) or assigning to any of the other function keys or to the digital input in the User menu.
2. Display continuously by pressing the Enter button while the max/min is being displayed to lock the display. Press Enter again to unlock.
Any of the F1-F3 function keys (buttons) and the digital input can be programmed to reset the max & min readings. The meters are set at the factory to display the max reading by pressing the Right Arrow/F1 button and to use the Up-Arrow/F2 button to access the Reset menu. Press the Right Arrow button to cy­cle through the available parameters to reset.

Changing Engineering Units

It is possible to change the display units without the need to re-scale the meter. The UNITS menu within the DISPLAY menu allows the unit of measure to be changed (e.g. from gallons/second (GAL/s) to li­ters/second (L/s)) and the meter will automatically convert the display values to the new unit of measure. If entering a custom unit (CUSTM), a custom conversion factor will need to be entered. See Changing the Units (UNITS) on page 19.
Page 39
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
39

Troubleshooting

Due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with what an operator expects to see. If the meter is not working as expected, refer to the recommendations below.

Reset Meter to Factory Defaults

When the parameters have been changed in a way that is difficult to determine what’s happening, it might
be better to start the setup process from the factory defaults. To load factory defaults:
1. Press the Menu button to enter Programming Mode.
2. Press the Right Arrow button twice and press Enter to access the Advanced menu.
3. Press the Up-Arrow button and press Enter to access the System menu.
4. Press the Right Arrow button and press Enter to access the Default menu.
5. Press Enter twice in quick succession. The meter will load default settings and restart.

Determining Software Version

To determine the software version of a meter:
1. Press the Menu button to enter Programming Mode.
2. Press the Right Arrow button twice and press Enter to access the Advanced menu.
3. Press the Up-Arrow button and press Enter to access the System menu.
4. Press the Up-Arrow button twice and press Enter to access the Info menu.
5. Press the Right Arrow button to cycle through the meter information. When done, press the Menu button to return to the previous menu.
SYSTEM
SYSTM
AOUTCAL
SYSTM
DEFAULT
LOAD?
DEFAULT
RESET
DFAULT?
Meter Loads
Default Settings
and Restarts
Page 40
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
40

Factory Default Settings

The following table shows the factory setting for most of the programmable parameters on the meter.
Parameter
Display
Default Setting
Input Menu
Rate Units
UNITS
Gallons/second
Input 1
INP 1
4.000 mA
Display 1
DSP 1
0.00
Input 2
INP 2
20.000 mA
Display 2
DSP 2
100.00
Output Menu
Open Collector Output 1
OUTPUT 1
Disabled
Pulse Factor
FACTOR
1.0
Test Frequency
FREQ
100
Alarm
ALARM
PV
Alarm Action
ACTION
AUTO
Set Point
SET
20.00
Reset Point
RESET
10.00
Alarm On Delay
DELAY ON
0 seconds
Alarm Off Delay
DELAY OFF
0 seconds
Alarm Failsafe
FAILSAFE
OFF
Red LED
RED
ON
Flash PV
FLASH
ON
Alarm Message
MSG
ON
Message Text
MSG EDIT
ALARM 1
Timer Off Delay
OFF.DLAY
1 minute
Timer On Time
ON TIME
1 second
Timer Mode
MODE
Continuous
Open Collector Output 2
OUTPUT 2
Disabled
Set Point
SET
40.00
Reset Point
RESET
30.00
Message Text
MSG EDIT
ALARM 2
Relay Output 1
RELAY 1
Disabled
Alarm
ALARM
PV
Alarm Action
ACTION
AUTO
Set Point
SET
70.00
Reset Point
RESET
60.00
Alarm On Delay
DELAY ON
0 seconds
Alarm Off Delay
DELAY OFF
0 seconds
Alarm Failsafe
FAILSAFE
OFF
Red LED
RED
ON
Flash PV
FLASH
ON
Alarm Message
MSG
ON
Message Text
MSG EDIT
ALARM 3
Sample Count
TOTAL COUNT
1,000 gallons
Sample Time
TOTAL TIME
10 seconds
Parameter
Display
Default Setting
Batch Count
BATCH COUNT
Up
Batch Max
BATCH MAXIMUM
10,000
Batch Mode
BATCH MODE
Manual
Batch Preset
BATCH PRESET
1,000
Batch On Delay
DELAY ON
0 seconds
Batch Off Delay
DELAY OFF
0 seconds
Timer Off Delay
OFF.DLAY
1 minute
Timer On Time
ON TIME
1 second
Timer Mode
MODE
Continuous
Relay Output 2
RELAY 2
Disabled
Set Point
SET
90.00
Reset Point
RESET
80.00
Message Text
MSG EDIT
ALARM 4
4-20 mA Output
4-20 mA
PV
Advanced Menu
Signal Condi­tioning Function
FUNCTION
Linear (2 pts)
Count Limit
COUNT LIMIT
8-Digit
Count Initial
COUNT INITIAL
0
Total Reset
TOTAL RESET
Enabled
GTotal Reset
GTOT RESET
Disabled
Grand Total Reset Lockout
PERMLOCK
No
Low Cutoff
CUTOFF
Disabled
Filter
FILTER
2.0 seconds
Filter Bypass
BYPAS
00.4 PCT
Main Password
MAIN
00000
Total Password
TOTAL
00000
GTot Password
GTOTAL
00000
Function Key 1
F1
Display
Function Key 2
F2
Reset
Function Key 3
F3
Acknowledge
Digital Input
DI
Reset Total
Function Key Hint Feature
HINT
Disabled
Totalizer
TOTAL
Enabled
Backlight
BACKLIGHT
Enabled
Display Menu
Unit of Measure
UNITS
Gallons
Decimal Point Location
DEC.PT
2
Comma
COMMA
Enabled
Top Line
TOP
PV
Bottom Line
BOTTOM
Units
Page 41
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
41

Troubleshooting Tips

Symptom
Check/Action
No display at all
1. Check that the 4-20 mA current loop is providing at least 3.5 mA to the meter.
2. Check that the voltage drop of all devices con­nected to the 4-20 mA current loop does not ex­ceed the max rating of the loop power supply.
Not able to change setup or program­ming, LOCKED is displayed
Meter is password-protected, enter correct five-digit password to unlock.
Meter display flashes:
1. 999999
2. -99999
Check that the number of digits required for the scaled value does not exceed the maximum digits for the display line. If it does, try adjusting the deci­mal point location for less precision or changing the PV display to the bottom line.
Display is unstable
Check:
1. Input signal stability and value.
2. Display scaling vs. input signal.
3. Filter and bypass values (increase).
Display response is too slow
Check filter and bypass values
Display reading is not accurate
Check:
1. Signal input conditioner selected: Linear, square root, etc.
2. Scaling or calibration
Display does not respond to input changes, reading a fixed number
Check display assignment. It might be displaying max, min, or set point.
Display shows MAX, MIN, RATE, TOTAL, or GTOT and a number
Max or min display has been locked. Press Enter to unlock max/min display readings.
Relay operation is reversed
Check fail-safe settings in Output menu
Relays do not respond to signal
Check:
1. Relay action in Output menu
2. Set and reset points
If the display locks up or the meter does not respond at all
Cycle the power to reboot the microprocessor.
Other symptoms not described above
Call Technical Support for assistance.
Note: Certain sequences of events can cause unexpected results. To solve these issues, it is best to start fresh from factory defaults and map changes ahead of time, rather than at random. See Reset Meter to
Factory Defaults on page 39 for details on resetting the meter.
Page 42
Loop Leader PD6622/4 Loop-Powered Rate/Totalizer Instruction Manual
PRECISION DIGITAL CORPORATION
233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
LIM6622_A
SFT124 Ver 1.000 & up
12/16
How to Contact Precision Digital
For Technical Support please
Call: (800) 610-5239 or (508) 655-7300 Fax: (508) 655-8990 Email: support@predig.com
For Sales Support or to place an order please
contact your local distributor or Call: (800) 343-1001 or (508) 655-7300 Fax: (508) 655-8990 Email: sales@predig.com
For the latest version of this manual please visit
www.predig.com