NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing
Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du
Canada.
EN 50091-2
Some configurations are classified under EN 50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For
these configurations, the following applies:
WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, in
which case, the user may be required to take additional measures.
Powerware, ABM, LanSafe, and FERRUPS are registered trademarks and X-Slot and ConnectUPS are trademarks of
Eaton Power Quality Corporation. Modbus is a registered trademark of Modicon. AS/400 is a registered trademark
of International Business Machines Corp.
ECopyright 2004–2005 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be
reproduced in any way without the express written approval of Eaton Corporation.
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
S Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 60950 Third Edition
S EU Directives:73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC
Declaration of Conformity, contact:
Eaton Power Quality Oy
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452 661
Fax: +358-9-452 665 68
93/68/EEC, Amending Directive 73/23/EEC
89/336/EEC, Council Directive relating to electromagnetic compatibility
92/31/EEC, Amending Directive 89/336/EEC relating to EMC
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the
associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for
additional information, such as important operating and maintenance
instructions.
RJ-45 RECEPTACLE - For 230V models only: this receptacle provides network
interface connections. Do not plug telephone or telecommunications equipment
into this receptacle.
This symbol indicates that you should not discard the UPS or the UPS batteries
in the trash. This product contains sealed, lead-acid batteries and must be
disposed of properly. For more information, contact your local recycling/reuse or
hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local
recycling/reuse or hazardous waste center.
Two-Year Limited Warranty (US and Canada)67..................................................
Ten-Year Pro-Rated Limited Warranty (US and Canada)69..........................................
Load Protection Guarantee (US and Canada)71..................................................
ii
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 1Introduction
The Powerware®9125 uninterruptible power system (UPS) protects
your sensitive electronic equipment from the most common power
problems including power failures, power sags, power surges,
brownouts, line noise, high voltage spikes, frequency variations,
switching transients, and harmonic distortion.
Power outages can occur when you least expect it and power
quality can be erratic. These power problems have the potential to
corrupt critical data, destroy unsaved work sessions, and damage
hardware — causing hours of lost productivity and expensive repairs.
With the Powerware 9125, you can safely eliminate the effects of power
disturbances and guard the integrity of your equipment. Figure 1 shows
the Powerware 9125 UPS with an optional Extended Battery Module
(EBM).
Figure 1. The Powerware 9125 UPS with Optional EBM
Providing outstanding performance and reliability, the Powerware 9125’s
unique benefits include the following:
S Online UPS design with pure sine wave output. The UPS filters and
regulates incoming AC power and provides consistent power to your
equipment without draining the battery.
S 2U rack height that conserves valuable rack space.
S Two-in-one form factor for using the UPS in a rack-mount
configuration or as a standalone cabinet.
S ABM
®
technology that uses advanced battery management to
increase battery service life, optimize recharge time, and provide a
warning before the end of useful battery life.
S Hours of extended runtime with up to four EBMs.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
1
INTRODUCTION
S Start-on-battery capability for powering up the UPS even if utility
power is not available.
S Hot-swappable batteries that simplify maintenance by allowing you to
replace batteries safely without powering down the critical load.
S Emergency shutdown control through the remote emergency
power-off (REPO) port.
S Optional X-Slott cards with enhanced communication capabilities for
increased power protection and control.
S Network transient protector that guards your network
communications equipment from surges. Low voltage models can
also protect modems, fax machines, or other telecommunications
equipment.
S Advanced power management with the Software Suite CD for
graceful shutdowns and power monitoring.
S Sequential shutdown and load management through separate
receptacle groups, called load segments.
S Flash memory provides easy upgrades or reconfiguration capability
without requiring a service call.
S Backed by worldwide agency approvals.
2
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 2Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed byAUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.
S This UPS contains its own energy source (batteries). The output receptacles may carry
live voltage even when the UPS is not connected to an AC supply.
S For 220–240V models, the output receptacles may remain electrically live. If the input
power source in your application is wired line-to-neutral (as in most European
applications), the voltage to the output receptacles is 0V. With line-to-line input wiring,
the voltage to the output receptacles is 110–120V (measured from line-to-ground or
line-to-neutral, depending on the UPS wiring).
S Do not remove or unplug the input cord when the UPS is turned on. This removes the
safety ground from the UPS and the equipment connected to the UPS.
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature
must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95%
maximum).
S To comply with international standards and wiring regulations, the total equipment
connected to the output of this UPS must not have an earth leakage current greater than
1.5 milliamperes.
S For UPS models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.
S For UPS models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to be provided by others.
DANGER
WARNING
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
3
SAFETY WARNINGS
S Batteries can present a risk of electrical shock or burn from high short-circuit current.
Observe proper precautions. Servicing should be performed by qualified service
personnel knowledgeable of batteries and required precautions. Keep unauthorized
personnel away from batteries.
S Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER
GEM DISSE ANVISNINGER
DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE
SIKKERHEDSANVISNINGER
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør
kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan
repareres af brugeren.
CAUTION
FARE
ADVARSEL!
S Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene kan lede
strøm, selv når UPS’en ikke er tilsat en AC-energikilde.
S Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er tændt.
Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.
S Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit for
ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød.
Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller høj
fugtighed (maksimalt 95%).
S I overensstemmelse med internationale normer og bestemmelser for el-installation må
det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en
jordafdelingsspænding på mere end 1,5 milliampere.
S For UPS systemer med hårdledningsudgange, skal overstrømsbeskyttelse for
vekslestrømmens udgangskredsløb forsynes af andre.
S For UPS systemer med hårdledningsudgange, skal egnede, nominelle afbryderkontakter
for vekslestrømmens udgangskredsløb forsynes af andre.
4
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
S Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj
kortslutningsspænding. De korrekte forholdsregler bør overholdes.
S Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for
bortskaffelsesprocedurer.
S Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved
åben ild.
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES
BEWAAR DEZE INSTRUCTIES
DEZE HANDLEIDING BEVAT BELANGRIJKE
VEILIGHEIDSINSTRUCTIES
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en
onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd.
Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden
GEREPAREERD.
SAFETY WARNINGS
ADVARSEL
GEVAAR
WAARSCHUWING
S Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen kunnen
onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten.
S Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de
UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen
aardebeveiliging meer hebben.
S Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een
gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen
geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°Cniet
overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max.
95%).
S Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele
apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van
meer dan 1,5 milliampère hebben.
S Voor UPS systemen met vast-bedrade uitgangen, moet de overstroombeveiliging voor
wisselstroom uitvoercircuit(s) door anderen worden geleverd.
S Voor UPS systemen met vast-bedrade uitgangen, moeten de juiste hoofdschakelaars
voor wisselstroom uitvoercircuit(s) door anderen worden geleverd.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
5
SAFETY WARNINGS
S Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als gevolg
S De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw
S Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.
Tarkeita Turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI
SÄILYTÄ NÄMÄ OHJEET
TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on
jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN
KÄYTTÄJÄN HUOLLETTAVIA OSIA.
OPGELET
van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op.
plaatselijke voorschriften.
VAARA
VAROITUS
S Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla jännite,
kun UPS ei ole liitettynä verkkojännitteeseen.
S Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa
turvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.
S Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin, joissa
lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia.
Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä ja vältä kosteita tiloja
(95 % maksimi).
S Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän UPS-laitteen
ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 1,5 milliampeeria (mA).
S UPS-järjestelmissä kiintealla asennuksella: kuormana olevien laitteiden ylivirtasuojaus ja
erotuskytkimet tulee toteuttaa kuormapiireissa.
VARO
S Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään oikosulkuun.
Noudata asianmukaisia ohjeita.
S Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä.
S Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.
6
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ
IMPORTANTES
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.
AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.
S Cet onduleur renferme sa propre source d’éner gie (batteries). Les prises de sortie
S Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous peine de
S Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur
S Afin d’être conforme aux normes et règlements internationaux de câblage, le courant de
S Pour les models UPS ayant des sorties câblées, la protection contre une surintensité pour
S Pour les models UPS ayant des sorties câblées, les interrupteurs de déconnexion
SAFETY WARNINGS
DANGER!
AVERTISSEMENT!
peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le secteur.
supprimer la mise à la terre de l’onduleur et du matériel connecté.
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la
température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit
pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère
excessivement humide (95 % maximum).
fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas
dépasser 1,5 mA.
le(s) circuit(s) de sortie de courant alternatif doit être fournie par un autre fournisseur.
convenables pour le(s) circuit(s) de sortie de courant alternatif doivent être fournie par un
autre fournisseur.
ATTENTION!
S Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des
courts-circuits de haute intensité. Prendre les précautions nécessaires.
S Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements
en vigueur dans votre localité.
S Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire
exploser.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
7
SAFETY WARNINGS
Sicherheitswarnungen
Dieses Handbuch enthält wichtige Hinweise, welche Sie bei der Installation und Wartung
die USV beachten sollten. Bitte lesen Sie alle Anweisungen des Handbuches bevor sie mit
dem Gerät arbeiten. Bewaren Sie das Handbuch zum Nachlesen auf.
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten sollten
nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer
zu wartenden Komponenten.
S Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den
Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an einer
Wechselspannungsquelle angeschlossen ist.
S Bei Modellen mit 220–240 Volt können die Ausgangssteckverbinder stromführend
bleiben. Wenn die Eingangsstromquelle in Ihrer Anlage mit Masseleitung verkabelt ist
(wie in den meisten europäischen Anlagen), beträgt die Spannung an den
Ausgangssteckverbindern 0 Volt. Bei einer Verkabelung mit Außenleitern beträgt die
Spannung an den Ausgangssteckverbindern 110–120 Volt (gemessen von Leitung zu
Masse oder Leitung zu Masseleiter, abhängig von der UPS (USV)-Verkabelung.
S Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet ist,
weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen
Geräten entfernt wird.
S Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mit
kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden
Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen.
Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %)
betreiben.
S Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an den
Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdableitstrom von
insgesamt 1,5 Milliampere nicht überschreiten.
S Für UPS-Systeme mit festverdrahteten Eingängen muß der Überstromschutz für die
Ausgangswechselstromkreise anderweitig bereitgestellt werden.
S Für UPS-Systeme mit festverdrahteten Ausgängen müssen Trennschalter für die
Ausgangswechselstromkreise mit passendem Nennwert anderweitig bereitgestellt
werden.
WICHTIGE SICHERHEITSANWEISUNGEN
AUFBEWAREN
WARNUNG
ACHTUNG
8
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Avvisi di sicurezza
SAFETY WARNINGS
VORSICHT!
S Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder
Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind unbedingt
zu beachten. Wartungsarbeiten sollten nur von qualifiziertem Fachpersonal, welches sich
mit dieser Art von Batterien und den entsprechenden Sicherheitsvorkehrungen auskennt,
durchgeführt werden. Bitte halten Sie unqualifiziertes Personal von den Batterien fern.
S Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen
Bestimmungen zu beachten.
S Batterien niemals verbrennen, da sie explodieren können.
IMPORTANTI ISTRUZIONI DI SICUREZZA
CONSERVARE QUESTE ISTRUZIONI
QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI
SICUREZZA
PERICOLO
La TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni
di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA
PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi
sono PARTI RIPARABILI DALL’UTENTE.
AVVERTENZA
S Questo gruppo statico di continuità contiene una fonte di energia autonoma (le batterie).
Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di
continuità non è collegato con una fonte di alimentazione a corrente alternata.
S Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di continuità è
acceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza del
gruppo statico di continuità e dell’apparecchiatura ad esso collegata.
S Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di
continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti
contaminanti conduttivi. La temperatura ambiente non deve superare i 40°C. Non
utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max).
S Per conformità con gli standard internazionali e con le norme in merito al cablaggio, tutta
l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere
una corrente di dispersione di terra superiore a 1,5 milliampere.
S Nei sistemi UPS provvisti di uscite cablate, i dispositivi di protezione da sovracorrente
per il/i circuito/i a corrente alternata in uscita devono essere forniti da terzi.
S Nei sistemi UPS provvisti di uscite cablate, i sezionatori di corrente nominale adeguata
per il/i circuito/i a corrente alternata in uscita devono essere forniti da terzi.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
9
SAFETY WARNINGS
S Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da alta
corrente dovuta a corto circuito. Osservare le apposite istruzioni.
S Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare
riferimento alle disposizioni locali.
S Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle
fiamme.
Viktig Sikkerhetsinformasion
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun
utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅ
NOEN AV DELENE i UPS’en.
S Denne UPS’en har en egen energikilde (batterier). Stikkontaktene kan være strømførende
selv om UPS’en ikke er tilsluttet en vekselstrømforsyning.
S Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på, slik at ikke
sikkerhetsjordingen fjernes fra UPS’en og det utstyret som er forbundet med den.
S For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende,
forurensende stoffer. Romtemperaturen må ikke overskride 40°C. Den må ikke brukes i
nærheten av vann eller ved meget høy luftfuktighet (95% maks.).
S Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere total
lekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse med internasjonale
standarder og forkablingsbestemmelser.
S For UPS systemer med fastkoplete uttak, må overstrømvern for vekselstrømuttak(ene)
stilles til rådighet av andre.
S For UPS systemer med fastkoplete uttak, må passende utkoplingsbrytere for
vekselstrømuttak(ene) stilles til rådighet av andre.
ATTENZIONE
FARLIG
FARLIG
10
FORSIKTIG
S Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy
kortslutningsstrøm. Følg instruksene.
S Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av
batterier.
S Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Regulamentos de Segurança
INSTRUÇÕES DE SEGURANÇA IMPORTANTES
GUARDE ESTAS INSTRUÇÕES
ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA
IMPORTANTES
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser
executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há
nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
S Esta UPS contém sua própria fonte de energia (baterias). Os receptáculos de saída
podem conter voltagem ativa quando a UPS não se encontra conectada a uma fonte de
alimentação de corrente alternada.
S Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto
removerá o aterramento de segurança da UPS e do equipamento conectado.
S Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente
interno com temperatura e umidade controladas e livres de contaminadores condutíveis.
A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em
umidade excessiva (máx: 95%).
S Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o
equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à
terra maior que 1,5 miliampères.
S Para sistemas UPS com saídas conectadas, a proteção de sobrecarga para circuitos de
saída de corrente alternada deve ser fornecida por outros.
S Para sistemas UPS com saídas conectadas, interruptores de desconexão devidamente
qualificados para circuitos de saída de corrente alternada devem ser fornecidos por
outros.
SAFETY WARNINGS
CUIDADO
ADVERTÊNCIA
PERIGO
S As baterias podem apresentar o risco de choque elétrico, ou queimaduras provenientes
de alta corrente de curto-circuito. Observe as instruções adequadas.
S Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do local
para maiores informações sobre os regulamentos de descarte de produtos.
S Nunca jogue as baterias no fogo, porque há risco de explosão.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
11
SAFETY WARNINGS
Предупреждения по мерам безопасности
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
СОХРАНИТЕ ЭТИ УКАЗАНИЯ
ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ
УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
ОПАСНО
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Все
работы по ремонту и обслуживанию должны выполняться ТОЛЬКО
УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ. Внутри
ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.
ПРЕДУПРЕЖДЕНИЕ
S Данный ИБП содержит собственные источники энергии
(аккумуляторы). На выходных розетках может иметься напряжение,
даже когда ИБП не подключен к сети переменного тока.
S Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки
при включенном ИБП. При этом защитное заземление отключается
от ИБП и от оборудования, подключенного к ИПБ.
S Для снижения опасности пожара или поражения электрическим
током устанавливайте ИБП в закрытом помещении с
контролируемыми температурой и влажностью, в котором
отсутствуют проводящие загрязняющие вещества. Температура
окружающего воздуха не должна превышать 40°С. Не эксплуатируйте
устройство около воды или в местах с повышенной влажностью
(макс. 95%).
S Для обеспечения соблюдения требований международных стандартов
итребованийкразводкеэлектрических цепей, суммарная величина
тока утечки на землю всего оборудования, подключенного к выходу
ИБП, не должна превышать 1,5 миллиампера.
12
ОСТОРОЖНО
S Аккумуляторы могут вызвать опасность поражения электрическим
током или ожога от тока короткого замыкания. Соблюдайте
соответствующие меры предосторожности.
S Необходимо соблюдать правила утилизации аккумуляторов.
Обратитесь к местным нормативным актам за информацией о
требованиях к утилизации.
S Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут
взорваться под воздействием огня.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Advertencias de Seguridad
INSTRUCCIONES DE SEGURIDAD IMPORTANTES
GUARDE ESTAS INSTRUCCIONES
ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD
IMPORTANTES
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben
ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay
NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.
S Este SIE contiene su propia fuente d e energía (las baterías). Los receptáculos de salida
pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a un
suministro de corriente alterna (c.a.).
S No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido. Esto
suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE.
S Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un lugar
cubierto, con temperatura y humedad controladas, libre de contaminantes conductores.
La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o con
humedad excesiva (95% máximo).
S Para cumplir con los estándares internacionales y las normas de instalación, la totalidad
de los equipos conectados a la salida de este SIE no debe tener una intensidad de
pérdida a tierra superior a los 1,5 miliamperios.
S Para los sistemas UPS con salidas cableadas permanentamente, la protección contra
exceso de corriente para el/los circuito(s) de CA de salida será suministrada por terceros.
S Para los sistemas UPS con salidas cableadas permanentemente, los interruptores de
desconexión debidamente clasificados para el/los circuito(s) de CA de salida serán
suministrados por terceros.
SAFETY WARNINGS
PELIGRO
ADVERTENCIA
PRECAUCIÓN
S Las baterías pueden presentar un riesgo de descargas eléctricas o de quemaduras
debido a la alta corriente de cortocircuito. P reste atención a las instrucciones
correspondientes.
S Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales
para conocer los requisitos pertinentes.
S Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a
la llama.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
13
SAFETY WARNINGS
Säkerhetsföreskrifter
VIKTIGA SÄKERHETSFÖRESKRIFTER
SPARA DESSA FÖRESKRIFTER
DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA
SÄKERHETSFÖRESKRIFTER
Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD
SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som
ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.
S Denna UPS-enhet har en egen energikälla (batterier). De utgående kontakterna kan vara
S Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort skyddsjordningen
S Minska risken för brand eller elektriska stötar genom att installera denna UPS-enhet
S För att överensstämma med internationell standard och installationsföreskrifter får inte
S Överströmsskydd för de utgående växelströmskretsarna ska tillhandahållas av andra för
S Bortkopplingsswitchar med passande dimensionering för de utgående
FARA
VARNING
strömförande när UPS-enheten inte är ansluten till en växelströmkälla.
från både UPS-enheten och den anslutna utrustningen.
inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande
föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte
utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).
den totala utrustning som anslutits till uttagen på denna UPS-enhet ha läcksström som
överstiger 1,5 milliampere.
UPS-system med fasta utgångar.
växelströmskretsarna ska tillhandahållas av andra för UPS-system med fasta utgångar.
14
VIKTIGT
S Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström. Följ
tillämpliga anvisningar.
S Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.
S Använda batterier får aldrig brännas upp. De kan explodera.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 3Installation
This section explains:
S Equipment inspection
S UPS internal battery connection
S UPS setup and installation
S Extended Battery Module (EBM) installation
S Remote emergency power-off (REPO) installation
S UPS rear panels
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping
cartons and packing materials for the carrier or place of purchase and file
a claim for shipping damage. If you discover damage after acceptance,
file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to your service representative.
NOTE Check the battery recharge date on the shipping carton label. If the date has expired
and the batteries were never recharged, do not use the UPS. Contact your service
representative.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
15
INSTALLATION
Connecting the UPS Internal Battery
To ensure proper battery operation before installing the UPS:
1.Verify that the UPS is off and unplugged.
2.Remove the UPS front cover by pulling on both ends (see Figure 2).
Figure 2. Removing the UPS Front Cover
3.Connect the internal battery connector (see Figure 3).
UPS Setup
16
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Figure 3. Connecting t he Internal Battery Connector
4.Replace the UPS front cover (see Figure 4).
Figure 4. Replacing the UPS Front Cover
5.Continue to the following section, “UPS Setup.”
The Powerware 9125 UPS is designed for flexible configurations and can
be installed in a rack or as a standalone cabinet.
If you are installing the UPS in a rack, continue to the following section
“Rack-Mount Setup;” otherwise, continue to “Tower Setup” on
page 18.
INSTALLATION
Rack-Mount Setup
The UPS can be installed in 19-inch racks and needs only 2U of valuable
rack space.
CAUTION
The UPS and EBM are heavy (see page 61). A minimum of two people are required to lift the
cabinets into the rack.
NOTE Mounting rails are required for each UPS and EBM cabinet. If rails are not already
installed in your rack, contact your local d istributor to order rail kits.
To install the UPS and optional EBMs in a rack:
1.Place the UPS on a flat, stable surface with the front of the UPS
facing toward you.
2.Attach the supplied mounting handles to the mounting brackets and
secure with the supplied screws (see Figure 5).
3.Align the mounting brackets with the screw holes on the side of the
UPS and secure with the supplied screws (see Figure 5).
4.If installing optional EBMs, repeat Steps 1 through 3 for each
cabinet.
Mounting
Bracket
Mounting
Handle
Figure 5. Installing the Mounting Handles and Brackets
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
17
INSTALLATION
NOTE The EBMs must be installed below the UPS as shown in Figure 6.
5.Slide the UPS and any optional EBMs into the rack.
6.Secure the cabinets to the rack according to the rail kit instructions.
UPS
Optional
EBMs
Figure 6. Rack-Mount UPS with EBMs
7.If installing optional EBMs, continue to “Extended Battery Module
Installation” on page 22. Otherwise, continue to “Plug-Receptacle
UPS Installation” on page 25 or “Hardwired UPS Installation” on
page 27 to complete the installation.
18
Tower Setup
The setup varies depending on the number of cabinets you are installing:
1.For one cabinet, the pedestals must be installed. Continue to Step 2.
For two cabinets, the pedestals and the joining brackets must be
installed. Skip to Step 6.
For three or more cabinets, the joining brackets must be installed. Skip
to Step 9.
2.Place the UPS cabinet horizontally so that the left end of the cabinet
is accessible (see Figure 7).
3.Align the pedestals with the screw holes on the end of the UPS
cabinet. Secure the pedestals with the screws provided in the
accessory kit.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
INSTALLATION
Figure 7. Installing UPS Pedestals (for One Cabinet)
4.Carefully position the cabinet upright with the air vents at the top
(see Figure 8).
5.Continue to “Plug-Receptacle UPS Installation” on page 25 or
“Hardwired UPS Installation” on page 27 to complete the
installation.
Air Vents
Figure 8. Pedestals with One Cabinet
6.Place the UPS cabinet horizontally so that the left end of the cabinet
is accessible (see Figure 9).
Figure 9. Installing UPS Pedestals (for Two Cabinets)
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
19
INSTALLATION
7.Place the EBM cabinet upside down so that the right end of the
cabinet is accessible (see Figure 10).
Figure 10. Installing EBM Pedestals
8.Align the pedestals with the screw holes on the end of the EBM
cabinet. Secure the pedestals with the screws provided in the
accessory kit.
9.Carefully position the cabinets upright with the air vents at the top
(see Figure 11 or Figure 12).
20
Air Vents
Figure 11. Pedestals with Two Cabinets
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
INSTALLATION
NOTE Pedestals are required for installations with one or two cabinets. Joining brackets
are required for installations with two or more cabinets.
Air Vents
Figure 12. Tower Setup with Three Cabinets
10. Align each joining bracket with the adjacent corner screw holes and
secure with the supplied screws (see Figure 13).
UPS
EBM
Joining Bracket
Joining Bracket
Figure 13. Installing the Joining Brackets (Top View with Pedestals)
11. If installing additional EBMs, repeat Step 10 for each cabinet.
12. If installing optional EBMs, continue to the following section,
“Extended Battery Module Installation.” Otherwise, continue to
“Plug-Receptacle UPS Installation” on page 25 or “Hardwired UPS
Installation” on page 27 to complete the installation.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
21
INSTALLATION
Extended Battery Module Installation
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and
will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and
firmly.
To install the optional EBMs:
1.If installing an EBM with an E/EH UPS model, skip to Step 4;
otherwise, continue to Step 2.
2.Plug the EBM cable(s) into the battery connector(s) as shown in
Figure 14. Up to four EBMs may be connected to the UPS.
3.Continue to “Plug-Receptacle UPS Installation” on page 25 or
“Hardwired UPS Installation” on page 27.
CAUTION
UPS Battery Connector
22
UPS
EBM Cable
EBM
EBM
EBM Battery
Connectors
Figure 14. Typical EBM Installation (120V UPS Model Shown)
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
INSTALLATION
4.E/EH UPS models have a battery connector cover that must be
removed before installing the EBM(s). Remove the cover from the
rear panel as shown in Figure 15.
NOTE Keep the battery connector cover and screws for future use. If the UPS is stored or
used without an EBM, the battery connector cover must be installed as a safety precaution.
5.Remove the cover from the EBM cable as shown in Figure 16.
NOTE Keep the EBM cable cover and screws for future use. If the EBM is stored or
removed from the UPS, the EBM cable cover must be installed as a safety precaution.
EBM Cable with Cover
Figure 16. EBM Cable Cover (E/EH UPS Models Only)
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
23
INSTALLATION
6.Plug the EBM cable into the UPS battery connector (see Figure 17).
7.Attach the fixed cover plate (supplied in the accessory kit) to the
EBM cable as shown in Figure 17.
UPS Battery Connector
UPS
EBM Cable
EBM Cable with
Fixed Cover Plate
EBM Battery
Connector with
Cover
Fixed Cover Plate
EBM
EBM
Figure 17. EBM Installation for E/EH UPS Models Only
24
8.If additional EBMs are to be installed, remove the EBM battery
connector cover. Remove the cover from the EBM cable of the
second cabinet and plug the EBM cable into the battery connector
on the first EBM. Attach the fixed cover plate to the EBM cable.
Repeat for each additional EBM. Up to four EBMs may be
connected to the UPS.
9.Continue to the following section, “Plug-Receptacle UPS
Installation” or “Hardwired UPS Installation” on page 27.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Plug-Receptacle UPS Installation
NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage
may occur to your equipment and void your warranty.
Figure 18 shows a typical installation only. See “UPS Rear Panels” on
page 33 for the rear panel of each model.
To install a plug-receptacle UPS:
1.If you are installing power management software, connect your
computer to the UPS communication port using the supplied
communication cable.
INSTALLATION
Output Receptacles
Power Cord
UPS
EBM
EBM
Communication Port
Figure 18. Typical Installation (120V UPS Model Shown)
2.Plug the equipment to be protected into the appropriate UPS output
receptacles (see page 50 for more information on load segments).
NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
3.If an emergency power-off (disconnect) switch is required by local
codes, see “Remote Emergency Power-off Installation” on page 31
to install the REPO switch before powering on the UPS.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
25
INSTALLATION
4.For 208/230V models only. Plug the detachable UPS power cord into
the input connector on the UPS rear panel.
5.Plug the UPS power cord into a power outlet.
All front panel indicators flash briefly and the UPS conducts a
self-test. When the self-test is complete, the
indicator flashes,
μ
indicating the UPS is in Standby mode with the equipment offline. If
the
orindicator flashes, see page 65.
Battery Service
Indicator
Figure 19. Fault I ndicators
Site Wiring Fault
Indicator
6.Press the On button.
The
indicator illuminates solid and the bar graph indicators
μ
display the percentage of load being applied to the UPS. The UPS is
now in Normal mode and supplying power to your equipment.
To change the factory-set defaults, see “Configuration” on page 41.
NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long-term storage.
26
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Hardwired UPS Installation
Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
S For UPS models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.
S For UPS models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to be provided by others.
NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage
may occur to your equipment and void your warranty.
The Powerware 9125 hardwired models require a dedicated branch
circuit that meets the following requirements:
S 16A, 2-pole circuit breaker for EH and GH models/20A, 2-pole circuit
breaker for EUH models to provide short circuit and overcurrent
protection
S The protection device requires a two-pole disconnection device
between the UPS output and the load
S The breaker must be wall-mounted and readily accessible to the
operator
S For Europe, the breaker must be approved by the appropriate safety
agency (such as TÜV or VDE) and have a contact air gap of at least
3mm
S 200–240 Vac
S Single-phase
S 50/60 Hz
S Flexible metal conduit (recommended for ease of service and
maintenance)
INSTALLATION
WARNING
CAUTION
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
27
INSTALLATION
To hardwire the UPS:
1.If you are installing power management software, connect your
computer to the UPS communication port using the supplied
communication cable.
2.Switch off utility power at the distribution point where the UPS will
be connected. Be absolutely sure there is no power.
Communication PortTerminal Block Cover
UPS
EBM
EBM
28
Figure 20. Typical Hardwired UPS Installation
3.Remove the terminal block cover and the wiring knockouts (see
Figure 21). Retain the terminal block cover and screws.
Input Wiring AccessOutput Wiring Access
Terminal Block Cover Screws
Figure 21. Wiring Access and Terminal Block
4.Pull the input and output wires through separate conduit, leaving
approximately 0.5m (2 ft) of exposed wire. Attach a flexible metal
fitting to the end of each conduit.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
INSTALLATION
Wir
e
Termina
l
TerminalWir
e
Tightenin
g
p
(14–8AWG)4.38Nm(35lbin)
p
(14–8AWG)4.38Nm(35lbin)
5.Insert each conduit through a wiring access entry and attach the
conduit fitting to the panel. Strip 1.5 cm (0.5I) of insulation from the
end of each incoming wire.
6.Connect the input and ground wires to the input terminal block
according to Figure 22 and Table 1.
7.Connect the output and ground wires to the output terminal block
according to Figure 22 and Table 1.
Table 1. UPS Wiring Specifications
UPS Wire Function
Function
Input
Position
EUH ModelsEH and GH Models
1L2N
2GG
Output
3
4L2N
L1L
5GG
6
L1L
* Use 2.0 mm2(14 AWG) 75_C copper wire minimum.
8.Reinstall the terminal block cover.
9.If an emergency power-off (disconnect) switch is required by local
codes, see “Remote Emergency Power-off Installation” on page 31
to install the REPO switch before powering on the UPS.
INPUT
13
2465
OUTPUT
Figure 22. Terminal Block
Size Rating*
2–10 mm
2–10 mm
Torque
2
2
4.38 Nm (35 lb in)
4.38 Nm (35 lb in)
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
29
INSTALLATION
10. Switch the main utility breaker on.
All front panel indicators flash briefly and the UPS conducts a
self-test. When the self-test is complete, the
indicator flashes,
μ
indicating the UPS is in Standby mode with the equipment offline. If
the
orindicator flashes, see page 65.
Battery Service
Indicator
Figure 23. Fault I ndicators
Site Wiring Fault
Indicator
11. Press the On button.
The
indicator illuminates solid and the bar graph indicators
μ
display the percentage of load being applied to the UPS. The UPS is
now in Normal mode and supplying power to your equipment.
To change the factory-set defaults, see “Configuration” on page 41.
NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long-term storage.
30
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Remote Emergency Power-off Installation
The Powerware 9125 includes a REPO port that allows power to be
switched off at the UPS output from a customer-supplied switch in a
remote location.
The REPO feature shuts down the protected equipment immediately
and does not follow the orderly shutdown procedure initiated by any
power management software.
Any devices that are operating on battery power are also shut down
immediately. When the REPO switch is reset, the equipment will not
return to battery power until the UPS is manually restarted.
INSTALLATION
If the Off
remains in Standby mode when restarted until the On
button is pressed after the REPO is activated, the UPS
button is
pressed.
WARNING
The REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be
separated from any hazardous voltage circuits by reinforced insulation.
CAUTION
To ensure the UPS stops supplying power to the load during any mode of operation, the
input power must be disconnected from the UPS when the emergency power-off function is
activated.
NOTE The REPO function activates when the REPO contacts open.
NOTE If the REPO function is not needed, the REPO connector must remain installed in the
REPO port on the UPS rear panel.
NOTE For Europe, the emergency switch requirements are detailed in Harmonized
document HD-384-48 S1, “Electrical Installation of the Buildings, Part 4: Protection for Safety,
Chapter 46: Isolation and Switching.”
To install the REPO switch:
1.Verify that the UPS is off and and disconnected from utility power.
2.Remove the REPO connector from the REPO port on the UPS rear
panel.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
31
INSTALLATION
3.Connect isolated, normally-closed, dry contacts (rated to handle
60 Vdc maximum, 30 Vac RMS maximum, and 20 mA maximum)
across the REPO device to Pin 1 and Pin 2 (see Figure 24).
Use stranded, non-shielded wiring, size 0.75 mm
2
–0.5 mm
2
(18–20 AWG).
NOTE A separate contact must simultaneously cause UPS input AC power to be removed.
Pin 1Pin 2
Figure 24. REPO Connector
4.Reconnect the REPO connector to the REPO port.
32
5.Verify that the externally-connected REPO switch is not activated to
enable power to the UPS output.
6.Plug in the UPS (or switch the main utility breaker on for hardwired
units) and start the UPS by pressing the On
button.
7.Activate the external REPO switch to test the REPO function.
8.De-activate the external REPO switch and restart the UPS.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
UPS Rear Panels
INSTALLATION
This section shows the rear panels of the Powerware 9125 models.
Network
Transient
Protector
Network
Transient
Protector
REPO Port
Battery Connector
Fuse Holder
Communication Port
X-Slot Communication Bay
Circuit Protector
Two 5-20 Receptacles
Two 5-15 Receptacles
Power Cord with 5-30P
5-30 Receptacle
Figure 25. 2500/3000 VA, 120V Rear Panel
REPO PortBattery Connector
Communication Port
X-Slot Communication Bay
Four 10A, IEC 320-C13 Receptacles16A, IEC-320 Input Connector
16A, IEC 320-C19 Receptacle
Network
Transient
Protector
Figure 26. 2500/3000 VA, 208V Rear Panel
Battery Connector with Cover
REPO Port
Circuit Breakers
Communication Port
X-Slot Communication Bay
Four 10A, IEC 320-C13 Receptacles16A, IEC-320 Input Connector
16A, IEC 320-C19 Receptacle
Figure 27. 2500/3000 VA, 230V Rear Panel
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
33
INSTALLATION
Terminal BlockREPO Port
Communication Port
Network
Transient
Protector
Network
Transient
Protector
X-Slot Communication Bay
Battery Connector
Figure 28. 2500/3000 VA, 208–240V Hardwired Rear Panel
Terminal BlockREPO Port
Communication Port
X-Slot Communication Bay
Battery Connector with Cover
Figure 29. 2500/3000 VA, 230V Hardwired Rear Panel
34
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 4Operation
This section describes:
S Turning the UPS on and off
S Starting the UPS on battery
S Initiating the self-test
S Operating modes
Turning the UPS On
After the UPS is connected to utility power, it conducts a self-test and
enters Standby mode.
To turn on the UPS, press the On
indicator illuminates solid and the bar graph indicators display the
μ
percentage of load being applied to the UPS.
Starting the UPS on Battery
To turn on the UPS without using utility power, press and hold the
button for at least four seconds. The UPS starts up in Battery mode
On
and supplies battery power to your equipment. When the UPS starts on
battery, it does not conduct a self-test to conserve battery power.
button on the front panel. The
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
35
OPERATION
Turning the UPS Off
NOTE Pressing the Offbutton while the UPS is in Battery mode causes the UPS to shut
down immediately.
To turn off the UPS:
1.Prepare your equipment for shutdown.
2.Press and hold the Off
3.Unplug or remove utility power from the UPS; the UPS shuts down
Initiating the Self-Test
NOTE The batteries must be fully charged and the UPS must not be in Battery mode to
perform the self-test.
NOTE AC input power must be applied to the UPS for 24 hours before performing the
self-test.
Press and hold thebutton for three seconds to initiate the self-test.
During the five-second test, the bar graph indicators cycle through twice.
If the alarm beeps or a UPS alarm indicator stays on, see Table 11 on
page 64.
button for approximately three seconds.
The UPS transfers to Standby mode (if utility power is available) and
removes power from your equipment.
in five seconds. All front panel indicators flash briefly prior to
shutdown.
If you do not unplug or remove utility power from the UPS, it
remains in Standby mode.
36
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Operating Modes
OPERATION
Powerware 9125’s front panel indicates the UPS status through the UPS
indicators. Figure 30 shows the UPS front panel indicators and controls.
Normal Mode Indicator
Battery Mode Indicator
Bypass Mode Indicator
Test/Alarm Reset Button
Alarm Indicators (see page 63)
Bar Graph Indicators
Indicator Legend
Unlit
Lit
Flashing
On ButtonOff Button
Figure 30. UPS Front Panel
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
37
OPERATION
Normal Mode
During Normal mode, theμindicator illuminates and the front panel
displays the percentage of UPS load capacity being used by the
protected equipment (see Figure 31). The UPS monitors and charges the
batteries as needed and provides power protection to your equipment.
<10%
10–25%
26–50%
51–75%
76–100%
>100%
38
Figure 31. Load Level Indicators
When all of the bar graph indicators are illuminated and theindicator
flashes, power requirements exceed UPS capacity; see page 65 for
more information.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
OPERATION
Battery Mode
When the UPS is operating during a power outage, the alarm beeps
once per second and the
displays the approximate percentage of battery capacity remaining (see
Figure 32).
When utility power returns, the UPS transfers to Normal mode operation
while the battery recharges.
+
---
indicator illuminates. The front panel
>75%
>50%
>25%
3-Minute Warning
Shutdown Imminent
Figure 32. Battery Capacity Indicators
If battery capacity becomes low while in Battery mode, theindicator
starts flashing and the alarm becomes continuous, indicating
approximately three minutes of battery time remaining. When shutdown
is imminent, the
indicator flashes.
NOTE Depending on the UPS load, the 3-minute warning may occur before the batteries
reach 25% capacity; the front panel immediately displays the 3-minute warning. For UPS and
Extended Battery Module (EBM) runtimes, see Table 10 on page 62.
These warnings are approximate, and the actual time to shutdown may
vary significantly. Once these warnings are indicated, immediately
complete and save your work to prevent data loss and similar difficulties.
When utility power is restored after the UPS shuts down, the UPS
automatically restarts.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
39
OPERATION
Bypass Mode
In the event of a UPS overload or internal failure, the UPS transfers your
equipment to utility power. Battery mode is not available; however, the
utility power continues to be passively filtered by the UPS. The
indicator illuminates. The UPS transfers to Bypass mode when:
S The UPS has an overtemperature condition.
S The UPS has an overload condition of 101 to 150% for 30 seconds.
S The UPS detects a fault in the battery or UPS electronics.
Standby Mode
When the UPS is turned off and remains connected to utility power, the
UPS is in Standby mode. The
indicators are off, indicating that power is not available to your
equipment. The battery recharges when necessary.
NOTE For 220–240V models, the output receptacles may remain electrically live (up to
110–120V). Unplug the UPS to ensure power is not available to the output receptacles.
indicator flashes and the bar graph
μ
40
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 5Configuration
When the UPS is in Configuration mode, the bar graph indicators
represent the configuration options. Use the control buttons
button andbutton) to modify the UPS configuration. Figure 33
(On
shows the LEDs and Table 2 explains the corresponding options.
NOTE The UPS can be configured while in Battery mode. If the UPS transfers to battery
power while in Configuration mode, the UPS remains in Configuration mode and indicates
Battery mode on the front panel after exiting Configuration mode.
To reconfigure the UPS default settings:
1.Press and hold the On
button and thebutton simultaneously
for one beep. The UPS transfers to Configuration mode.
The LEDs flash briefly and then display the enabled options.
2.Press the On
button to scroll through the options. Each time you
press the button, the UPS beeps. The LED for the selected option
indicates the current setting; flashing represents disabled options
(see Figure 33 and Table 2).
Scrolling past the last LED returns to the first configuration option.
If you press the On
button and nothing happens, the UPS is still in
Operation mode. Repeat Step 1 to enter Configuration mode, and
then perform Step 2.
3.Press the
button for approximately one second to select the
Voltage option or to toggle the Site Wiring Fault Alarm or AC Input
Failure Alarm on or off.
NOTE The UPS exits Configuration mode automatically after two minutes of inactivity.
4.Press and hold the On button and thebutton simultaneously to
exit Configuration mode at any time.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
41
CONFIGURATION
3
Press the Test/Alarm Reset
button to select an option.
Test/Alarm
On Button
Reset Button
2
Press the On button to
scroll to the next option.
Figure 33. Using Configuration Mode
Configuration Mode Indicators
&
1
4
Press and hold the On and Test/Alarm Reset
buttons simultaneously to toggle between
Configuration and Operation modes.
42
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Table 2. Configuration Mode LEDs and Options
Configuration Mode
LEDs
OptionLED StatusExplanation
CONFIGURATION
120, 208, or 230V
Nominal Input
Voltage
110, 220, or 230V
Nominal Input
Voltage
127 or 240V Nominal
Input Voltage
Site Wiring Fault
Alarm
On (default)Nominal input voltage is one of the following:
S 120V for U models
S 208V for EU/EUH and G/GH models
S 230V for E/EH models
All other nominal input voltages are disabled.
FlashingDisabled; one of the other input voltage options is
selected.
OnSelecting this option changes the nominal input voltage
to one of the following:
S 110V for U models
S 220V for E/EH models
S 230V for EU/EUH and G/GH models
FlashingDisabled; one of the other input voltage options is
selected.
OnSelecting this option changes the nominal input voltage
to one of the following:
S 127V for U models
S 240V for EU/EUH, E/EH, and G/GH models
FlashingDisabled; one of the other input voltage options is
selected.
On (default)Alarm sounds when the polarity of the outlet is reversed
or the ground connection is missing; have a qualified
electrician repair the outlet wiring.
Flashing*Alarm DOES NOT sound when the polarity of the outlet is
reversed or the ground connection is missing.
* For 208V or 230V models, flashing is the default; contact
your service representative to activate this alarm.
AC Input Failure
On (default)Alarm sounds when there is an AC input failure.
Alarm
FlashingAlarm DOES NOT sound when there is an AC input
failure.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
43
CONFIGURATION
44
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 6Additional UPS Features
This section describes:
S X-Slot cards
S Network transient protector
S Load segments
X-Slot Cards
X-Slot cards allow the UPS to communicate in a variety of networking
environments and with different types of devices. The Powerware 9125
is factory-installed with a Single-Port Card, which can be replaced with
one of the following X-Slot cards:
S ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities
t
as well as monitoring through a Web browser interface; connects to a
twisted-pair Ethernet (10/100BaseT) network. It has a built-in
switching hub that allows three additional network devices to be
connected to the network without the requirement of additional
network drops. In addition, a Powerware Environmental Monitoring
Probe can be attached to obtain humidity, temperature, smoke alarm,
and security information.
S Relay Interface Card - has isolated dry contact (Form-C) relay outputs
for UPS status: Utility failure, Low battery, UPS alarm/OK, or On
bypass.
S Modbus
®
Card - allows you to continuously and reliably monitor the
UPSs in your Building Management System (BMS).
S Multi-Server Card - has six serial communication ports that can
communicate simultaneously with other computers using Powerware
LanSafe
Suite CD).
®
Power Management Software (provided on the Software
S USB Card - connects to a USB port on your computer.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
45
ADDITIONAL UPS FEATURES
ConnectUPS-X Web/SNMP Card
Relay Interface Card
Modbus Card
Multi-Server Card
USB Card
Single-Port Card
The Powerware 9125 is factory-installed with a Single-Port Card,
enabling connection to a PC for power management control or to the
Powerware Expansion Chassis for multiple communication options.
To establish communication between the UPS and a computer, connect
your computer to the UPS communication port using the supplied
communication cable.
X-Slot Communication Bay
(Single-Port Card shown)
Figure 34. Optional X-Slot Cards
46
When the communication cable is installed, power management
software can exchange data with the UPS. The software polls the UPS
for detailed information on the status of the power environment. If a
power emergency occurs, the software initiates the saving of all data
and an orderly shutdown of the equipment.
The cable pins are identified in Figure 35 and the pin functions are
described in Table 3.
245
3
1
9
8
7
6
Figure 35. Communication Port
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
ADDITIONAL UPS FEATURES
Table 3. Communication Port Pin Assignment
Pin NumberSignal NameFunctionDirection from the UPS
The On-Bypass Relay Contact. You can enable the On-Bypass relay using
the jumper on the Single-Port Card. The jumper default is disabled.
To enable the On-Bypass relay:
1.Remove the Single-Port Card on the UPS rear panel. Retain the
screws (see Figure 36).
Figure 36. Removing the Single-Port Card
2.Move the J3 jumper to the AS/400®position to enable the
On-Bypass relay, as shown in Figure 37.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
47
ADDITIONAL UPS FEATURES
On-Bypass
Disabled
On-Bypass
Enabled
AS/400NORM
On-Bypass Relay Jumper
(J3)
Figure 37. On-Bypass Relay Jumper
3.To prevent electrostatic discharge (ESD), place one hand on a metal
surface such as the UPS rear panel.
Align the Single-Port Card with the slot guides and slide the card
into the slot until it is firmly seated.
48
4.Secure the Single-Port Card with the screws removed in Step 1.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Network Transient Protector
The network transient protector, shown in Figure 38, is located on the
rear panel and has jacks labeled IN and OUT. This feature
accommodates a single RJ-45 (10BaseT) network connector.
Low voltage models can also accommodate an RJ-11 telephone
connector that provides protection for modems, fax machines, or other
telecommunications equipment. As with most modem equipment, it is
not advisable to use this jack in digital PBX (Private Branch Exchange)
environments.
NOTE DO NOT connect any telephone or fax/modem equipment to the 230V models; only
network protection is available for 230V models.
1.Connect the input connector of the equipment you are protecting to
the jack labeled IN.
2.Connect the network or telephone cable (low voltage models only)
to the jack labeled OUT.
ADDITIONAL UPS FEATURES
IN
OUT
Figure 38. Network Transient Protector
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
49
ADDITIONAL UPS FEATURES
Load Segments
Load segments are sets of receptacles that can be controlled by power
management software, providing an orderly shutdown and startup of
your equipment. For example, during a power outage, you can keep key
pieces of equipment running while you turn off other equipment. This
feature allows you to save battery power. See your power management
software manual for details (refer to the Software Suite CD or
www.powerware.com for the latest information).
NOTE If power management software is not used, the individual load segments cannot be
controlled.
For hardwired UPSs, there is only one load segment. The terminal block
serves as Load Segment 1.
Each plug-receptacle UPS has two load segments as shown in Figure 39
and Figure 40.
50
Load Segment 1
Load Segment 2
Figure 39. UPS Load Segments for 120V Models
Load Segment 2Load Segment 1
Figure 40. UPS Load Segments for 208/230V Models
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 7UPS Maintenance
This section explains how to:
S Care for the UPS and batteries
S Replace the batteries
S Test new batteries
S Recycle used batteries or UPS
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS
clean and dust-free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
NOTE If the UPS requires any type of transportation, verify that the UPS is unplugged and
turned off and then disconnect the UPS internal battery connector using the steps in
“Connecting the UPS Internal Battery” on page 16 in reverse order.
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the batteries every
12 months by plugging the UPS into a power outlet. The batteries
charge to 90% capacity in approximately 3 hours. However, it is
recommended that the batteries charge for 24 hours after long-term
storage.
Check the battery recharge date on the shipping carton label. If the date
has expired and the batteries were never recharged, do not use the
UPS. Contact your service representative.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
51
UPS MAINTENANCE
When to Replace Batteries
When theindicator flashes, the batteries may need replacing.
Conduct a self-test by pressing and holding the
seconds. After the five-second test is complete, the
turn off (it may take a few seconds to turn off). If the
continues flashing, contact your service representative to order new
batteries.
Replacing Batteries
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
With the hot-swappable battery feature, UPS batteries can be replaced
easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the batteries, see
“Turning the UPS Off” on page 36.
Consider all warnings, cautions, and notes before replacing batteries.
button for three
indicator should
indicator
52
WARNING
S Batteries can present a risk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal
objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of
batteries.
S ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
UPS MAINTENANCE
How to Replace UPS Internal Batteries
CAUTION
Pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it
out of the UPS.
To replace the UPS internal batteries:
1.Remove the UPS front cover by pulling on both ends (see
Figure 41).
Figure 41. Removing the UPS Front Cover
2.Push down on and unsnap the LED panel (see Figure 42).
3.Disconnect the battery cable from the UPS and cut the battery
cable wire tie.
Battery Cable
LED Panel
Figure 42. Disconnecting the Battery Cable
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
53
UPS MAINTENANCE
4.Unscrew and set aside the battery retaining bracket (see Figure 43).
Battery Retaining Bracket
Figure 43. Removing the Battery Retaining Bracket
5.Pull the battery trays out onto a flat, stable surface (see Figure 44).
See “Recycling the Used Battery or UPS” on page 57 for proper
disposal.
54
Figure 44. Removing the Battery Trays
6.Slide the new battery trays into the UPS.
The battery trays are keyed to prevent improper connection. The
battery tray with the battery cable goes in the bay to the right.
7.Reinstall the battery retaining bracket removed in Step 4.
8.Reconnect the battery cable. Secure the cable to the battery
retaining bracket with a tie wrap.
9.Snap the LED panel into place.
10. Replace the UPS front cover.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
UPS MAINTENANCE
How to Replace Extended Battery Modules
CAUTION
The Extended Battery Module (EBM) is heavy (see page 61). A minimum of two people are
required to lift the EBM when it is replaced.
To replace the Extended Battery Modules (EBMs):
1.Unplug the EBM cable from the UPS.
NOTE For 230V models, remove the fixed cover plate, and then unplug the EBM cable from
the UPS.
If additional EBMs are installed, unplug the EBM cable from the
battery connector on each EBM.
2.If the EBM is in a tower configuration, remove the joining brackets.
3.If the EBM has pedestals installed, remove the pedestals and
retain.
4.If the EBM is in a rack, install the mounting handles and brackets on
the new EBM.
5.Replace the EBM. See “Recycling the Used Battery or UPS” on
page 57 for proper disposal.
6.Reinstall the pedestals if removed in Step 3.
7.Reinstall the joining brackets if removed in Step 2.
8.Plug the EBM cable(s) into the battery connectors as shown in
Figure 45.
For E/EH UPS models, remove the cover from the EBM cable and
plug the EBM cable into the UPS. Attach the fixed cover plate to
the EBM cable.
9.For additional EBMs, plug the EBM cable into the battery connector
on the adjacent EBM.
For E/EH UPS models, remove the EBM battery connector cover.
Remove the cover from the EBM cable of the second cabinet and
plug the EBM cable into the battery connector on the first EBM.
Attach the fixed cover plate to the EBM cable.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
55
UPS MAINTENANCE
Testing New Batteries
Press and hold thebutton for three seconds to initiate a self-test.
After the five-second test is complete, the
(it may take a few seconds to turn off). If the
check the battery connections. Call your service representative if the
problem persists.
Joining Brackets
EBM Battery
Connectors
UPS Battery Connector
EBM Cables
Figure 45. EBM Connections (120V UPS Model Shown)
indicator should turn off
indicator stays on,
56
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Recycling the Used Battery or UPS
Contact your local recycling or hazardous waste center for information
on proper disposal of the used battery or UPS.
S Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper
disposal of batteries is required. Refer to your local codes for disposal requirements.
S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,
lead-acid batteries and must be disposed of properly. For more information, contact your
local recycling/reuse or hazardous waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper
disposal, contact your local recycling/reuse or hazardous waste center.
UPS MAINTENANCE
WARNING
CAUTION
CAUTION
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
57
UPS MAINTENANCE
58
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 8Specifications
This section provides the following specifications:
S Model list
S Electrical input and output
S Weights and dimensions
S Environmental and safety
S Battery
Table 4. Model Specifications
Model Number
Power Levels
(Rated at Nominal Inputs)
Nominal Voltage
Input Voltage
Range
PW9125-2500U2500 VA, 1750W
PW9125-3000U3000 VA, 2100W
PW9125-2500EU
PW9125-2500G
PW9125-3000EU
PW9125-3000G
PW9125-2500E2500 VA, 1750W
PW9125-3000E3000 VA, 2100W
PW9125-2500EUH
PW9125-2500GH
PW9125-3000EUH
PW9125-3000GH
PW9125-2500EH2500 VA, 1750W
PW9125-3000EH3000 VA, 2100W
2500 VA, 1750W
3000 VA, 2100W
2500 VA, 1750W
3000 VA, 2100W
120V default; 110, 120, 127V selectable80–144V
208V default; 230, 240V selectable160–288V
230V default; 220, 240V selectable160–288V
208V default; 230, 240V selectable160–288V
230V default; 220, 240V selectable160–288V
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
59
SPECIFICATIONS
PW912
5-2500U
t
t
t
PW912
5-3000E
U
PW9125-3000
E
Table 5. Power Connections
ModelInputConnection
Output Connections
Load Segment 1Load Segment 2
PW9125-2500U
PW9125-3000U
6-f
, 5-30P a
ached power cord(2) 5-15R and (2) 5-20R(1) 5-30R outputcord
PW9125-2500EU
PW9125-2500E
PW9125-3000E
PW9125-2500G
16A, IEC 320-C20 input connector
Country-specific, detachable
power cord
(4) 10A, IEC 320-C13(1) 16A, IEC 320-C19
PW9125-3000G
PW9125-2500EUH
PW9125-3000EUH
PW9125-2500EH
PW9125-3000EH
Terminal blockTerminal blockN/A
PW9125-2500GH
PW9125-3000GH
Table 6. Technical Specifications
Nominal Frequency45–65 Hz, 50/60 Hz auto-sensing
Noise FilteringMOVs and line filter for normal and common mode noise
Regulation
Nominal output voltage ±3%
(Normal Mode)
Regulation
Nominal output voltage ±3%
(Battery Mode)
Voltage WaveformNormal mode: Sine wave; <5% THD with full PFC and nonlinear load
60
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Table 7. Weights and Dimensions
UPSExtended Battery Module
Dimensions
(WxDxH)
43.2 × 60.7 × 8.9 cm
17.0”
× 23.9” × 3.5” (2U)
43.2 × 60.7 × 8.9 cm
17.0”
× 23.9” × 3.5” (2U)
Weights37 kg (81.5 lb)42.5 kg (93 lb)
Table 8. Environmental and Safety
120V Models208V Models230V Models
Operating Temperature0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature0°C to 25°C (32°F to 77°F)
Transit Temperature-25°C to 55°C (-13°F to 131°F)
Relative Humidity5–95% noncondensing
Operating AltitudeUp to 3,000 meters above sea level
Transit AltitudeUp to 10,000 meters above sea level
SPECIFICATIONS
Audible NoiseLess than 45 dBA Normal mode, typical load
Less than 50 dBA Battery mode
Surge SuppressionIEEE C62.41 Category BIEEE C62.41 Category B
ChargingInternal battery: approximately 3 hours to 90% usable capacity at nominal line voltage
after full load discharge
External battery: no more than 20x discharge time to 90% usable capacity at nominal line
voltage after full load discharge
MonitoringAdvanced monitoring for earlier failure detection and warning; auto detection of
additional EBMs
Table 10. Battery Runtimes (in Minutes at Full/Half Load)
ModelUPS Internal Batteries1EBM2EBMs3EBMs4EBMs
2500 VA/1750W7/1628/5748/9068/15088/200
3000 VA/2100W5/1325/5538/7254/12070/160
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
62
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 9Troubleshooting
This section explains:
S UPS alarms and conditions
S Howtosilenceanalarm
S Service and support
Audible Alarms and UPS Conditions
The UPS has an audible alarm feature to alert you of potential power
problems. Use Table 11 to determine and resolve the UPS alarms and
conditions.
NOTE Some alarms, such as the Overtemperature and Overload alarms, must be cleared by
shutting down and restarting the UPS (see page 65 for more information).
Site Wiring Fault
Battery Service
Self-Test
Overtemperature
Overload
Test/Alarm
Reset Button
Figure 46. Alarm Indicators
Silencing an Audible Alarm
Before silencing an alarm, check the alarm condition and perform the
applicable action to resolve the condition (see Table 11).
To silence the alarm for an existing fault, press the
status changes, the alarm beeps, overriding the previous alarm silencing.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Indicator Legend
Unlit
Lit
Flashing
button. If UPS
63
TROUBLESHOOTING
;
Table 11. Troubleshooting G uide
Alarm or ConditionPossible CauseAction
Theindicator is not
μ
on; the UPS does not
start.
Theindicator is
μ
flashing; power is not
available at the UPS
output receptacles.
The UPS operates
normally, but some or all
of the protected
equipment is not on.
The power cord is not
connected correctly.
The wall outlet is faulty.
The main utility breaker is off.Verify that the main utility breaker is on.
The remote emergency
power-off (REPO) switch is
active.
The REPO connector is missing.Verify that the REPO connector is installed on the rear
The UPS is in Standby mode.
The equipment is not connected
to the UPS correctly.
The output receptacle circuit
breaker (if applicable) is open.
One of the load segments has
been turned off through the
power management software.
Check the power cord connections.
Have a qualified electrician test and repair the outlet.
Reset the REPO switch and restart the UPS.
panel.
Press the On button to supply power to the connected
equipment.
Verify that the equipment is plugged into the UPS
receptacles.
For hardwired models, contact a qualified electrician to
check connections to the power source.
Check the load. Disconnect faulty load equipment. Wait
several minutes before resetting the UPS circuit
breaker.
Reactivate the segment with the software.
|
The UPS does not
provide the expected
backup time.
Battery
Intermittent audible
alarm
Warning - Low Battery
64
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
The batteries need charging or
service.
The UPS is on battery (see
“Battery Mode” on page 39 for
more information).
Three-minute battery warning.Three minutes or less of battery power remains
Plugthe UPS into a power outlet(apply utility power on
hardwired models) for 24 hours to charge the batteries.
After charging the batteries, press and hold the
button for 3 seconds; then check theindicator.
If theindicator is still flashing, see “Replacing
Batteries” on page 52.
The UPS is powering the equipment with battery power.
Check the bar graph indicators for available battery
capacity and prepare your equipment for shutdown.
(depending on load configuration and battery charge).
Save your work and turn off your equipment.
Shutdown - Low Battery
TROUBLESHOOTING
ActionPossible CauseAlarm or Condition
Shutdown imminent.Prepare equipment for shutdown.
Bypass
Bypass
Battery Service
Site Wiring Fault
(120V models only)
Overtemperature
The UPS is in Bypass mode.The equipment is transferred to utility power; however,
the utility power continues to be passively filtered by the
UPS. Check for one of the following alarms:
Overtemperature, Overload, UPS Failure, or Battery
Service.
Bypass is not available. Input
voltage is not within ±12% of
nominal or input frequency is not
within ±3% of nominal.
The batteries may be fully
discharged.
The UPS is receiving utility power that may be unstable
or in brownout conditions. The UPS continues to supply
power to your equipment. If conditions worsen, the UPS
may switch to battery power.
Plug the UPS into a power outlet (apply utility power on
hardwired models) for 24 hours to charge the batteries.
After charging the batteries, press and hold the
button for 3 seconds; then check theindicator.
If theindicator is still flashing, see “Replacing
Batteries” on page 52.
The batteries are not connected
correctly.
Ground wire connection does
not exist or the line and neutral
wires are reversed in the wall
Check the battery connections. Call your service
representative if the problem persists.
Have a qualified electrician correct the wiring.
To disable this alarm, see “Configuration Mode” on
page 41.
outlet.
The UPS internal temperature is
too high. The UPS transfers to
Bypass mode, allowing the UPS
to cool.
Turn off the UPS. Unplug or remove utility power from
the UPS. Clear vents and remove any heat sources.
Ensure the airflow around the UPS is not restricted. Wait
at least 5 minutes and restart the UPS. If the condition
persists, contact your service representative.
Overload
Continuous audible
alarm
Power requirements exceed
UPS capacity (101–150% for
30 seconds) or the load is
defective.
Turn off the UPS. Unplug or remove utility power from
the UPS. Remove some of the equipment from the U PS.
Wait at least 5 seconds until all indicators are off and
restart the UPS.
If the overload condition persists (101–110% for
2 minutes or 111–150% for 30 seconds), the UPS
automatically shuts down.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
65
TROUBLESHOOTING
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor or the Help Desk at one of the following telephone numbers
and ask for a UPS technical representative.
United States:
1-800-356-5737 or 1-919-870-3149
Canada:1-800-461-9166 ext 260
All other countries:Call your local service representative
Please have the following information ready when you call the Help
Desk:
S Model number
S Serial number
S Version number (if available)
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization
(RMA) Number. This number must appear on the outside of the package
and on the Bill Of Lading (if applicable). Use the original packaging or
request packaging from the Help Desk or distributor. Units damaged in
shipment as a result of improper packaging are not covered under
warranty. A replacement or repair unit will be shipped, freight prepaid for
all warrantied units.
NOTE For critical applications, immediate replacement may be available. Call the Help
for the dealer or distributor nearest you.
Desk
66
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Chapter 10Warranty
Two-Year Limited Warranty (US and Canada)
Powerware UPS Models: 3105, 3110, 3115, 9104, 9120, 9125, and FERRUPS®up to 3.1 kVA
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation, a
Delaware Corporation company (“Company”).
LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”)
of any Powerware 3105, 3110, 3115, 9104, 9120, 9125, and FERRUPS up to 3.1 kVA Products (individually and
collectively, the “Product”) purchased on or after June 1, 2004 and cannot be transferred. This Warranty applies
even in the event that the Product is initially sold by Company for resale to an End-User.
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed [and currently located] in
the fifty (50) United States, the District of Columbia, and Canada is twenty-four (24) months from the date of
purchase.
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Product and battery (individually and
collectively, the ”Warranted Items”) are free from defects in material and workmanship. If, in the opinion of
Company, a Warranted Item is defective and the defect is within the terms of this Warranty, Company’s sole
obligation will be to repair or replace such defective Warranted Item (including by providing service, parts and labor,
as applicable), at the option of Company.
PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS: The Warranted Item will be repaired or
replacedataCompanysiteorsuchother location a s determined by Company.
If the Warranted Item is to be replaced by C ompany, and the End-User supplies a credit card number or purchase
order for the value of the replacement Product, Company will use commercially reasonable business efforts to ship
(via standard ground shipment and at no cost to the End-User) the replacement Warranted Item to the End-User
within one (1) business day after Company receives notice of the warranty claim. In such case, the End-User must
return (at Company’s expense) the defective Warranted Item to Company in the same packaging as the
replacement Warranted Item received by the End-User or as otherwise instructed by Company. If Company does
not receive the defective Warranted Item, Company will either charge the End-User’s credit card, or send the
End-User an invoice (which the End-User agrees to pay), for the value of the replacement Product.
If the Warranted Item is to be replaced by C ompany, but the End-User is unwilling or unable to supply a credit card
number or purchase order for the value of the replacement Product, Company will use commercially reasonable
business efforts to ship (via standard ground shipment and at no cost to the End-User) the replacement Warranted
Item to the End-User within one (1) business day after Company receives the defective Product from the End-User.
In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges for
return of defective equipment and replacement of Warranted Items. Any returned Warranted Item or parts that are
replaced may be new or reconditioned. All Warranted Items returned to Company and all parts replaced by
Company shall become the property of Company.
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
67
WARRANTY
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than
the date indicated on the packaging; (b) shipping and delivery of the Product i f shipping is FOB Factory; (c) neglect,
accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by
Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper
testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company
personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product
under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.
This Warranty is not valid if the Product’s serial numbers have been removed or are illegible. Any Warranted Items
repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty
subject to all the terms thereof.
Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.
COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE
APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO
END-USER.
COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT
CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT
SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN “OPEN SOURCE” MODEL OR IS DISTRIBUTED
PURSUANT TO AN OPEN SOURCE LICENSE.
THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE
PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER
WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE,
NON-INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON-CONFORMITIES IN
THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE
LIABILITY AND END-USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY
OBLIGATIONS, WHETHER CLAIMS OF THE END-USER ARE BASED IN CONTRACT, IN TORT (INCLUDING
NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.
LIMITATION OF LIABILITY:
for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract,
in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the
Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of
customers of the End-User or any special, indirect, incidental or consequential damages whatsoever. The total
cumulative liability of Company hereunder whether the claims are based in c ontract (including indemnity), in tort
(including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability
is based.
Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s
reasonable control.
The remedies of the End-User set forth herein are exclusive and are the sole remedies
END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must use the Product
in a normal way; follow the Product’s user’s guide; and protect against further damage to the Product if there is a
covered defect.
OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by
Company of all payments due to it (including interest charges, if any). During such time as Company has not
received payment of any amount due to it for the Product, in accordance with the contract terms under which the
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this
Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any
overdue or unpaid amounts.
68
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
WARRANTY
COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services not
expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,
freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be
borne by the End-User.
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside
of the USA, call your local Powerware product sales or service representative, or call the Customer Reliability Center
in the USA at 919-870-3149. For comments or questions about this Warranty, write to the Customer Quality
Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
Ten-Year Pro-Rated Limited Warranty (US and Canada)
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation, a
Delaware Corporation company (“Company”).
LIMITED WARRANTY: This pro -rated limited warranty (this “Warranty”) applies only to the original End-User (the
“End-User”) of any Powerware 5115, 5125, 5140, 9104, 9120, 9125, 9155, 9170+, and FERRUPS Products
(individually and collectively, the “Product”) and cannot be transferred. This Warranty applies even in the event that
the Product is initially sold by Company for resale to an End-User.
WHAT THIS WARRANTY COVERS: In addition to the standard Two-Year Limited Warranty covering the applicable
Product, the warrantor warrants that the Product will have a service life (defined below) of ten years from the date
of purchase (the “Ten-Year Service Life”) when used in accordance with the storage, handling, installation,
operation and maintenance procedures prescribed in the Product’s user’s guide. “Service life” means the Product’s
ability to deliver at least 80% of its original rated backup time.
If Company finds, in its sole discretion, that any Product has not provided the Ten-Year Service Life, Company will,
as its sole obligation and the End-User’s sole remedy for Company’s breach of this warranty, repair or replace the
Product, at its option, F.O.B. Company’s factory, for a charge, payable by the End-User to Company pro-rated on the
following basis:
The End-User will be allowed a credit against Company’s list price of equivalent equipment at the time of return of
the Product to Company, in proportion to the percentage of Ten-Year Service Life remaining at the time of return of
the Product to Company. In calculating the available credit, the remaining portion of the Ten-Year Service Life will be
rounded up or down to the nearest whole year. The End-User will assume responsibility to pay the balance of the
list price; and Company reserves the right to require p ayment prior to delivery of the repaired or replacement
equipment.
For the avoidance of doubt, Company’s responsibilities under this Warranty are as follows:
Years 1-2 - Product repaired or replaced pursuant to terms of Limited Warranty
Years 3-10 - Unit Credit ($) = Current List Price
×Years of Unexpired Life
10 Years of Warranted Life
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
69
WARRANTY
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than
the date indicated on the packaging; (b) shipping and delivery of the Product i f shipping is FOB Factory; (c) neglect,
accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by
Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper
testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company
personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product
under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.
This Warranty is not valid: (a) unless the End-User returns to Company the Warranty Registration Card within
thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible. Any
Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the
original Warranty subject to all the terms thereof.
Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.
COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE
APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO
END-USER.
COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT
CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT
SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN “OPEN SOURCE” MODEL OR IS DISTRIBUTED
PURSUANT TO AN OPEN SOURCE LICENSE.
THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE
PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER
WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE,
NON-INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON-CONFORMITIES IN
THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE
LIABILITY AND END-USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY
OBLIGATIONS, WHETHER CLAIMS OF THE END-USER ARE BASED IN CONTRACT, IN TORT (INCLUDING
NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.
LIMITATION OF LIABILITY:
for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract,
in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the
Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of
customers of the End-User or any special, indirect, incidental or consequential damages whatsoever. The total
cumulative liability of Company hereunder whether the claims are based in c ontract (including indemnity), in tort
(including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability
is based.
Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s
reasonable control.
The remedies of the End-User set forth herein are exclusive and are the sole remedies
END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must use the Product
in a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the
Product if there is a covered defect.
70
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
WARRANTY
OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by
Company of all payments due to it (including interest charges, if any). During such time as Company has not
received payment of any amount due to it for the Product, in accordance with the contract terms under which the
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this
Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any
overdue or unpaid amounts.
COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services not
expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,
freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be
borne by the End-User.
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside
of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability
Center in the USA at 919-870-3149. Company will not accept any Product for return, credit or exchange unless
expressly authorized by Company in writing and delivered FOB Company factory. For comments or questions about
this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina
27616 USA.
GUARANTOR: The Guarantor for the load protection guaranty set forth herein is Eaton Power Quality Corporation, a
Delaware Corporation company (“Company”).
LIMITED GUARANTY: This load protection guaranty (this “Guaranty”) applies only to the original End-User (the
“End-User”) of any Powerware 3105, 3110, 3115, 5110, 5115, 5125, 9120, 9125, 9150, 9155, 9170+, and FERRUPS
Products (individually and collectively, the “Product”) and cannot be transferred. This Guaranty applies even in the
event that the Product is initially sold by Company for resale to an End-User.
WHAT THIS GUARANTY COVERS: For the lifetime of the Product, Guarantor promises to repair or replace, at
Guarantor’s option, the equipment (valued up to the limits s hown below*) that is damaged by an AC power line
surge, spike, or other transient when properly connected to Guarantor’s uninterruptible power system (“UPS”).
Reimbursement for or restoration of data loss excluded. This Guaranty applies only if all of the following
circumstances arise:
1. The UPS is plugged into properly grounded and wired outlets, using no extension cords, adapters, other ground
wires or other electrical connectors;
2. The installation of the UPS complies with all applicable electrical and safety codes described by the National
Electric Code (NEC);
3. The UPS was used under normal operating conditions and in accordance with all labels and instructions; and
4. The UPS was not damaged by accident (other than AC power line transient), misuse, or abuse.
*Cumulative Limits to be paid by Guarantor under this Load Protection Guaranty:
S $25,000 for Powerware UPS Models 3105, 3110, and 3115
S $150,000 for Powerware UPS Models 5110, 5115, and 5125
S $250,000 for Powerware UPS Models 9120, 9125, 9150, 9155, 9170+, and FERRUPS products
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
71
WARRANTY
WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-User’s equipment does not
include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or damages
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than
the date indicated on the packaging; (b) shipping and delivery of the Product i f shipping is FOB Factory; (c) neglect,
accident, abuse, misuse, misapplication, or incorrect installation of Product; (d) repair or alteration of Product not
authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or
Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind to the Product not
authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or
Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the
Product’s labels or instructions.
This Guaranty is not valid: (a) unless the End-User returns to Company the Warranty Registration Card within
thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible.
Company shall not be responsible for any charges for testing, checking, removal or installation of any items.
LIMITATION OF LIABILITY: THE REMEDIES OF THE END-USER SET FORTH HEREIN ARE EXCLUSIVE AND ARE THE SOLE
REMEDIES FOR ANY FAILURE OF COMPANY TO COMPLY WITH ITS OBLIGATIONS HEREUNDER. EXCEPT AS OTHERWISE
PROVIDED FOR IN THIS GUARANTY, IN NO EVENT SHALL COMPANY BE LIABLE IN CONTRACT, IN TORT (INCLUDING
NEGLIGENCE OR STRICT LIABILITY) OR OTHERWISE FOR DAMAGE TO PROPERTY OR EQUIPMENT OTHER THAN THE
PRODUCTS, INCLUDING LOSS OF PROFITS OR REVENUE, LOSS OF USE OF PRODUCTS, LOSS OF DATA, COST OF
CAPITAL, CLAIMS OF CUSTOMERS OF THE END-USER OR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL
DAMAGES WHATSOEVER. THE TOTAL CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS ARE
BASED IN CONTRACT (INCLUDING INDEMNITY), IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY) OR
OTHERWISE, SHALL NOT EXCEED THOSE SET FORTH ABOVE.
Company shall not be responsible for failure to provide repair or replacement under this Guaranty due to causes
beyond Company’s reasonable control.
END-USER’S OBLIGATIONS: In order to receive the benefits of this Guaranty, the End-User must use the Product in
a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the
Product if there is a covered defect.
OTHER LIMITATIONS: Company’s obligations under this Guaranty are expressly conditioned upon receipt by
Company of all payments due to it (including interest charges, if any). During such time as Company has not
received payment of any amount due to it for the Product, in accordance with the contract terms under which the
Product is sold, Company shall have no obligation under this Guaranty.
COSTS NOT RELATED TO GUARANTY: The End-User shall be invoiced for, and shall pay for, all services not
expressly provided for by the terms of this Guaranty, including without limitation, site calls involving an inspection
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,
freight charges, travel expenses or labor of Company representatives outside the terms of this Guaranty will be
borne by the End-User.
TO MAKE A CLAIM: In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA,
contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the
USA at 919-870-3149. For comments or questions about this Load Protection Guaranty, write to the Customer
Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
72
EATON Powerware®9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.