Powerware 9155, UPS20-30kVA User Manual

User’s Guide UPS 20 - 30 kVA, 230 V 50/60 Hz output (3-phase input/1-phase output)
©2007 Eaton Corporation All Rights Reserved
The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to make design modifications is reserved.
User’s Guide UPS 20 - 30 kVA, 230 V 50/60 Hz output (3-phase input/1-phase output
1026743 revision B
1. Safety instructions ....................................................................................................................................................................... 5
Audience ........................................................................................................................................................................................ 5
CE marking ..................................................................................................................................................................................... 5
User precautions ........................................................................................................................................................................... 6
Environment ................................................................................................................................................................................... 6
Inquiries .......................................................................................................................................................................................... 6
2 Introduction ................................................................................................................................................................................... 7
System description ....................................................................................................................................................................... 7
Feature: Active-Front Technology .............................................................................................................................................. 7
Feature: Advanced Battery Management (ABM)™ ................................................................................................................ 8
Feature: Hot Sync® technology .................................................................................................................................................. 8
Basic system configuration ......................................................................................................................................................... 9
)
3. Mechanical installation ..............................................................................................................................................................
Delivery check ............................................................................................................................................................................... 10
Unpacking and visual inspection ............................................................................................................................................... 10
4. Planning before installation .......................................................................................................................................................
5. Cabinet installation .....................................................................................................................................................................
Maintenance bypass switch ....................................................................................................................................................... 15
External battery cabinet option .................................................................................................................................................. 15
Battery racks ................................................................................................................................................................................. 15
6. Electrical installation ..................................................................................................................................................................
Power cables and protective fuses ........................................................................................................................................... 17
Wiring procedure .......................................................................................................................................................................... 18
The installation procedure: ......................................................................................................................................................... 18
External Battery Cabinet (EBC) installation procedure .......................................................................................................... 21
7. Software and connectivity ..........................................................................................................................................................
Communication cables ................................................................................................................................................................. 22
Connection to the standard RS-232 port (X53) ......................................................................................................................... 23
LanSafe software .......................................................................................................................................................................... 23
External control connections ...................................................................................................................................................... 24
Emergency Power Off (EPO) ................................................................................................................................................... 24
Relay outputs ............................................................................................................................................................................. 25
Programmable signal inputs ................................................................................................................................................... 25
XSlot communication ................................................................................................................................................................... 26
Web/SNMP Module (optional) ............................................................................................................................................... 27
AS/400 Relay Module (optional) ............................................................................................................................................. 27
Single Serial Port Module (optional) ..................................................................................................................................... 28
Modbus/Jbus Module (optional) ............................................................................................................................................ 28
10
12
13
16
22
8. User operations ............................................................................................................................................................................. 29
Display functions ........................................................................................................................................................................... 29
User Settings ................................................................................................................................................................................. 30
Changing language ....................................................................................................................................................................... 32
Using relay outputs ....................................................................................................................................................................... 32
Normal start-up ............................................................................................................................................................................. 32
Battery start-up ............................................................................................................................................................................. 33
Start-up after EPO ......................................................................................................................................................................... 33
Shutdown ....................................................................................................................................................................................... 33
9. Maintenance ................................................................................................................................................................................. 34
Regular service/intervals ............................................................................................................................................................. 34
Batteries ..................................................................................................................................................................................... 35
Cooling fan ................................................................................................................................................................................. 35
LED Indicators ............................................................................................................................................................................... 35
Maintenance bypass switch (MBS) operation ........................................................................................................................ 36
Turn UPS from normal mode to maintenance bypass mode (service bypass mode) ................................................... 36
Turn UPS from maintenance bypass to normal mode ........................................................................................................ 37
10. Parallel systems ............................................................................................................................................................................... 39
Overview ......................................................................................................................................................................................... 39
Aux. MBS contacts ....................................................................................................................................................................... 42
XSlot Hot Sync card: installing and wiring ............................................................................................................................... 43
Start-up and operation ................................................................................................................................................................. 45
Start-up procedure ................................................................................................................................................................... 45
Operating system bypass switch ........................................................................................................................................... 46
Shut-down procedure .............................................................................................................................................................. 47
Local tie panel solutions .......................................................................................................................................................... 48
11. Recycling the used UPS or batteries ........................................................................................................................................
12. Dimensional drawings ................................................................................................................................................................
13. Technical data ...............................................................................................................................................................................
Standards ...................................................................................................................................................................................... 50
Environment ................................................................................................................................................................................... 50
Maintenance configuration ......................................................................................................................................................... 50
Characteristics .............................................................................................................................................................................. 50
AC input .......................................................................................................................................................................................... 51
DC circuit ........................................................................................................................................................................................ 51
AC output ........................................................................................................................................................................................ 51
14. Warranty ......................................................................................................................................................................................... 52
48
49
50
1. Safety instructions
The UPS operates with mains, battery or bypass power. It contains components that carry high currents and voltages. The properly installed enclosure is earthed and IP20 rated against electrical shock and foreign objects. However, only qualified personal is allowed to install and service the UPS.
Warning!
Operations inside the UPS must be performed by a service engineer from the manufacturer or from an agent authorised by the manufacturer.
Do not ever service inside the UPS when mains power is applied or the UPS is in battery mode. Use the optional Maintenance Bypass Switch (MBS) if installed to the system. Remember to open battery breaker. Always ensure by measuring with a multimeter that no dangerous voltages are present.
Audience
The intended audiences of this manual are people who plan the installation, install, commission, and use or service the UPS. The manual provides guidelines to check delivery, installing and commissioning of the UPS.
The reader is expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols. This manual is written for a global reader.
Note!
Read the manual before operating or working on the UPS.
CE marking
The product has the CE marking in compliance with the following European directives:
LV Directive (Safety) 73/23/EEC and 93/68/EEC
EMC Directive 89/336/EEC, 93/68/EEC and 92/31/EEC
Declaration of conformity with UPS harmonised standards and directives EN 62040-1-1 (Safety) and EN 50091-2 (EMC) are available on the web site (http://www.powerware.com).
1026743 Revision B
5UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
User precautions
The only user operations permitted are:
Start up and shut down of the UPS, excluding the commissioning start-up.
Use of the LCD control panel and Maintenance Bypass Switch (MBS)
Use of optional connectivity modules and their software
The user must follow the precautions and only perform the described operations. Any deviations from the instructions could be dangerous to the user or cause accidental load loss.
Warning!
The user is not permitted to open of any screws excluding connectivity plates and the MBS locking plate. Failure to recognise the electrical hazards could prove fatal.
Environment
The UPS must be installed according to the recommendations in this manual. Under no circumstances the UPS should be installed in an airtight room, in the presence of flammable gases, or in an environment exceeding the specification.
Excessive amount of dust in the operating environment of UPS may cause damage or lead to malfunction. The UPS should be always protected from the outside weather and sunshine. The recommended operating temperature is from +15 to +25 Celsius degrees.
Inquiries
Address any inquiries about the UPS and battery cabinet to the local office or agent authorised by the manufacturer. Please quote the type code and the serial number of the equipment.
6 UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
1026743
Revision B
2 Introduction
The product described in this manual is a transformerless Uninterruptible Power System (UPS). It is a true online, continuous duty, double conversion, solid state, three-phase system, providing conditioned and uninterruptible AC power to protect the customer’s load from all nine power failures.
System description
The UPSs are used to protect sensitive IT equipment and prevent loss of valuable electronic information, minimise equipment downtime, and minimise the adverse effect on production equipment due to unexpected power problems.
The UPS system continually monitors incoming electrical power and removes the surges, spikes, sags, and other irregularities that are inherent in commercial utility power. Working with a building‘s electrical system, the UPS system supplies clean, consistent power that sensitive electronic equipment requires for reliable operation. During brownouts, blackouts, and other power interruptions, batteries provide emergency power to safeguard operation.
The UPS system is housed in freestanding cabinets. The cabinets line up and match in style and colour, and have safety shields behind the doors for hazardous voltage protection.
Figure 1 UPS cabinet 20-30 kVA, 50/60 Hz (1-phase output), with an External Battery Cabinet.
Feature: Active-Front Technology
Traditional input THD filters are no longer needed with this UPS product. The built-in advanced rectifier technology of UPS modules provides perfect sinusoidal input power quality at 0.99 input power factor with harmonic content less than 5% THD(i). This leads to more reliable total system operation and savings in generator and transformer sizing as losses in the windings are minimised.
1026743 Revision B
User’s Guide
7UPS 20-30 kVA, 230 V 50/60 Hz output
Due to the active front rectifier, the UPS is comparable to a clean resistor load from the mains perspective. Thus, the high input power factor provides minimised cabling and fusing costs due to no reactive power consumption.
The low harmonic currents are due to high input power factor and provide the benefits:
No additional losses in wires and cables
No extra heating of transformers and generators with shortened service life
No false circuit breaker tripping and malfunction
No erratic operation of computers, telecommunication, monitors, electronic test equipment
etc.
No Resonance with power factor correction capacitors
Feature: Advanced Battery Management (ABM)™
The ABM monitors the status of the battery and charges it only when the battery needs charging. This is the key to long battery life with the ABM due to low generation of corrosion inside the battery. It also monitors that the load never crashes because of bad or defected battery.
The main cause for corrosion is current flowing through battery. The more current going through battery, the shorter the battery life. Current flows through battery when it is discharged or charged. There is very little that can be done for discharging, because it depends on number of power outages in utility line.
The ABM is very valuable feature since most of the time battery does not need any charging. The charging is controlled and initiated on the following occasions:
- When turning the unit on
- After 18 days without charging
- If the open cell voltage decreases below predetermined voltage level
Hence, the function of ABM system is to prolong the battery life considerably compared to traditional system that uses float-charging technology. This means that there is no current going through batteries all the time and causing corrosion. In a traditional online UPS the inverter also causes ripple-current to be fed to batteries causing corrosion.
Feature: Hot Sync® technology
The UPS product features U.S. #5,745,365 patented paralelling technology that provides N+X redundancy without introducing a single-point-of-failure. The products utilising the Hot Sync are completely autonomous and the only thing common among them is the critical output power bus.
The Hot Sync is 100% mathematical firmware that makes it more reliable than traditional paralleling techniques. Because the solution is implemented intrinsically, and Hot Sync is always active, the UPS modules can operate with or without redundant units.
8 UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
1026743
Revision B
A parallel UPS system means the linking together of two or more UPS units in parallel so that in the unlikely event one fails the other can automatically take up the load. Traditionally a parallel redundancy configuration is achieved by having a random or fixed master-slave relationship among the UPS units. This master logic gives out individual commands to all the slaves units. Unfortunately this can lead to a single-point-of-failure for the whole system because if the master logic or communication to slaves fails, and causes the whole UPS system to be in trouble.
The Hot Sync® technology was developed to allow parallel capacity system and to maintain the highest system availability. An industry leading paralleling technology in its own right, the patented Hot Sync enables you to set up a parallel redundant system giving you 100% conditioned power at all times. Its unique digital design eliminates the system level single point of failure inherent in traditional parallel UPS modules, and exponentially increases the reliability of the overall system.
Hot Sync allows up to four UPS units to cover the same load in parallel and redundant configuration. No vulnerable master logic is needed in this patented design. It provides automatic load sharing and module level redundancy with nothing other than the power connecting the Hot Sync version of UPS modules.
Basic system configuration
The following basic UPS system configurations are available:
A single UPS system:
- UPS cabinet with 0-4 battery strings 20-30 kVA
- Runtime with internal batteries 20 kVA: up to 31 minutes 30 kVA: up to 20 minutes
- External battery cabinet For longer runtimes
- LCD display for easy configuration Standard
- Remote display Optional
A parallel UPS system
- Up to four units can be paralled
Figure 2 UPS configuration with two External Battery Cabinets.
Adding optional accessories can enhance the UPS system configuration. These include for example XSlot communication adapters.
1026743 Revision B
9UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
3. Mechanical installation
The UPS and accessories are delivered on a specifically designed pallet that is easy to move with a forklift or a pallet jack. Keep the UPS always in upright position and do not drop the equipment. Do not either stack the pallets because of high-energy batteries involved and the heavy weight
Delivery check
The UPS is delivered with the following items:
Plastic bag containing:
Quick Installation Guide, paper format, multilingual (coming later) User’s Guide, paper format, English language User’s Guide, CD-ROM format, multilingual (coming later) Residual voltage warning stickers Software Suite, CD-ROM format, English language RS-232 serial cable for the Software Suite
Delivery documents
Unpacking and visual inspection
Check that there are no signs of shipping damages. The outside ’Tip&Tel’ indicator should be intact if the equipment has been transported in the upright position.
Note!
A claim for shipping damage must be filed immediately and the carrier must be informed within 7 days of receipt of the equipment. The packing materials should be stored for further investigation.
Unpack the equipment by removing the packing and shipping materials. Make a visual inspection and check that the inside ‘Drop&Tell’ indicator is intact. Remove the equipment from the pallet and make sure that the floor surface is solid and suitable for the wheeling and heavy weight.
10 UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
1026743
Revision B
Figure 3 Unloading the equipment from the pallet.
Check the information on the type designation label of the equipment to verify that the unit is of the correct type. The type designation label includes ratings, a CE marking, a type code, a part number and a serial number. The serial number is important when making inquiries. It allows individual recognition of the equipment.
1026743 Revision B
11UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
4. Planning before installation
The equipment must be installed in upright position. The equipment requires space to front and back to enable cooling airflow. Service and maintenance require 500 mm clearance on right hand side. All cooling air enters at front and exits at unit rear. The required min. clearance from unit rear to an obstruction is 250 mm. Because the service and user access is in the front there should be reserved enough space (min 600 mm).
It is required to arrange ventilation of the UPS room. Sufficient amount of air cooling is needed to keep the max. room temperature rise at desired level:
Temperature rise of max. +5
Temperature rise of max. +10°C requires the airflow of 300 m3 per 1 kW of losses.
°C requires the airflow of 600 m3 per 1 kW of losses.
An ambient temperature of 15 to 25 Celsius degrees is recommended to achieve a long life of the UPS and batteries. The cooling air entering the UPS must not exceed +40 °C. Avoid high ambient temperature, moisture and humidity.
The floor material should be non-flammable and strong enough to support the heavy load. The UPS has (4) leveling feet that should be used when finalising the installation. The diameter of a single leveling foot is 29 mm.
Equipment Weight Point Distributed Note
20-30 kVA 20-30 kVA 20-30 kVA UPS w/o BAT 200 kg 7.57 kg/cm UPS+1 BAT 300 kg 11.35 kg/cm UPS+2 BAT 400 kg 15.14 kg/m UPS+3 BAT 500 kg 18.92 kg/cm UPS+4 BAT 600 kg 22.71 kg/cm EXT BAT 0 150 kg 5.67 kg/cm EXT BAT 1 510 kg 19.29 kg/cm EXT BAT 2 870 kg 32.90 kg/cm
2
2
2
2
2
2
2
2
531 kg/m 797 kg/m 1063 kg/m 1328 kg/m 1594 kg/m 401 kg/m 1362 kg/m 2323 kg/m
2
2
2
2
2
2
2
2
No Batteries installed 1 Battery string installed 2 Battery strings installed 3 Battery strings installed 4 Battery strings installed No Batteries installed 1 Battery string installed 2 Battery strings installed
Table 1 The floor surface must tolerate loading.
12 UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
1026743
Revision B
5. Cabinet installation
The required distance for UPS units next to each other is ten millimetres. The same applies to the optional battery cabinets that should be installed next to the UPS cabinet. It is recommended to install the battery cabinet on the left hand side of the UPS.
Figure 4 UPS and external battery cabinets.
Note!
UPS cabinets can fall over if the shipping brackets are not used. Both rear and front shipping brackets must be used to secure the UPS cabinet to the floor.
The UPS family has several alternative battery cabinets and configurations depending on the selected back-up time and quality of batteries.
1026743 Revision B
13UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
Figure 5 Powerware 9155 20-30 kVA layout: 1:Graphical LCD; 2:XSlot-1; 3:XSlot-2; 4:Fans; 5:Input (rectifier) breaker “F2 MAINS”; 6:Battery start button; 7:Battery breaker “F1 BATTERY”; 8-13: Connectivity terminals; 14:Ground terminal; 15:MBS; 16:Power cable terminals
14 UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
1026743
Revision B
Maintenance bypass switch
The maintenance bypass switch (MBS) shall be mounted in the bottom of the UPS cabinet. It can be ordered factory installed.
External battery cabinet option
It’s recommended to install external battery cabinet(s) next to the UPS unit. The external battery can be placed on either side of the UPS unit, but it is recommended to instal on left hand side. Check before the installation that the battery voltage values in the type plate of the UPS and external battery cabinets are the same. The cables are delivered with the external battery cabinet.
Warning!
The UPS contains high DC voltages. A qualified person must do the connections between the UPS and the external battery cabinet(s). The battery cabinet is connected electrically in parallel with the internal batteries of the UPS.
Warning!
If available, the internal battery has to be disconnected first because the external battery terminals may be hazardous due to parallel battery strings.
Battery racks
External battery racks shall be sized to take the voltage drop in the cable into account. To obtain support and help contact the local office or agent authorised by the manufacturer.
1026743 Revision B
15UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
6. Electrical installation
The customer has to supply the wiring to connect the UPS to the local power source. The electrical installation procedure is described in the following text. The installation inspection and initial start up of the UPS and extra battery cabinet must be carried out by a qualified service personnel such as a licensed service engineer from the manufacturer or from an agent authorised by the manufacturer.
Warning!
Physical injury or death may follow, or damage may occur to the UPS, or the load equipment if these instructions are ignored.
Figure 6
Location of the power terminals. S1:Service Bypass Switch; S2:Static Bypass Input Switch; S3:UPS Output Switch. Make sure battery breaker is open and disconnect all internal battery strings before operating with the terminal X4.
16 UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
1026743
Revision B
Loading...
+ 36 hidden pages