Powerware UPS 1000 - 2200 User Manual

Page 1
UPS 100 0 - 2200 VA User’s Manual
Page 2
Page 3
Powerware 5125 User’s Manual 1000–2200 VA
1019297 Revision A
Table of contents
1. Introduction ............................................................................................................. 7
2. Installation ............................................................................................................... 8
Installing the UPS ......................................................................................................... 8
UPS Rear Panels ........................................................................................................... 9
3. Operation and Configuration.................................................................................. 1 0
Operating Models ....................................................................................................... 10
Stanby mode ................................................................................................................ 11
Normal Mode .............................................................................................................. 11
Buck and Double Boost Mode.................................................................................... 11
Battery Mode ............................................................................................................... 12
Sleep Mode .................................................................................................................. 12
UPS Configuration ...................................................................................................... 1 2
Turning the UPS On .................................................................................................... 1 2
Starting the UPS on Battery........................................................................................ 12
Turning the UPS Off .................................................................................................... 1 3
Initiating the Self-Test ................................................................................................. 13
Communication Port .................................................................................................. 13
Network Transient Protector ..................................................................................... 14
Load Segments ............................................................................................................ 15
4. UPS Maintenance .................................................................................................... 16
UPS and Battery Care ................................................................................................. 1 6
Storing the UPS and Batteries .................................................................................... 1 6
When to Replace Batteries ......................................................................................... 16
Replacing Batteries ...................................................................................................... 16
Testing New Batteries ................................................................................................. 19
Recycling the Used Battery ......................................................................................... 2 0
5. Troubleshooting ...................................................................................................... 20
Audible Alarms and UPS Conditions ......................................................................... 2 0
Silencing an Audible Alarm ........................................................................................ 2 1
6. Specifications .......................................................................................................... 23
Page 4
Copyright 2002
The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to make design modifications is reserved.
Page 5
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 950 Second Edition, Amendments A1, A2, A3, and A4
EU Directives: 73/23/EEC, Council Directive on equipment designed for use
within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Powerware Oy Koskelontie 13 FIN-02920 Espoo, Finland Phone: +358-9-452 661 Fax: +358-9-452 66 396
Class A EMC Statements (100 0–1500 VA Models)
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES–003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Page 6
Special Symbols
The following are examples of symbols used on the UPS to alert you to important information:
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions.
RJ-45 RECEPTACLE - For 230V units only: this r eceptacle provides network interface connections. Do not plug telephone or telecommunications equipment into this receptacle.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. The UPS may contain sealed, lead–acid batteries. Batteries must be recycled.
Page 7
1 P owe rware 51 25 – Introduction
The Powerware® 5125 uninterruptible power system (UPS) protects your sensitive electronic equipment from basic power problems such as power failures, power sags, power surges, undervoltage and overvoltage.
Power outages can occur when you least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware — causing hours of lost productivity and expensive repairs.
With the Powerware 5125, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. The Powerware 5125 was designed for critical applications such as PCs, severs, workstations, and telecommunications equipment. Figure 1 shows the Powerware 5125 UPS with an optional Extended Battery Module (EBM).
Figure 1. The Powerware 5125
Providing outstanding performance and reliability, the Powerware 5125’s unique benefits include the following:
Advanced Battery Management Plus (ABM Plus™) doubles battery service life,
optimizes recharge time, and provides a warning before the end of useful battery life.
Buck and Double Boost regulation ensures consistent voltage to your load by
correcting voltage fluctuations without using battery power .
Hours of extended run time with up to four EBMs.
Hot–swappable batteries simplify maintenance by allowing you to replace batteries
safely without powering down the critical load.
Start–on–battery capability allows you to power up the UPS even if utility power is
not available.
Advanced power management with the Software Suite CD for graceful shutdowns
and power monitoring.
Sequential shutdown and load management through separate receptacle groups,
called load segments.
Network Transient Pr otector guar ds your network communications equipment fr om
surges.
Optional X-Slot™ modules provide enhanced communication capabilities for
increased power protection and control.
The Powerware 5125 is backed by worldwide agency approvals.
1019297 Revision A
1000 - 2200 VA
User’s Manual
7
Page 8
2 Installation
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
Installing the UPS
The following steps explain how to install the UPS. See “UPS Rear Panels” on page 9 for the rear panel of each model.
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty.
1. If installing an optional EBM, continue to Step 2; otherwise, skip to Step 4.
2. Plug the EBM cable into the battery connector on the UPS rear panel.
3. If a second EBM is to be installed, plug the EBM cable of the second cabinet into
the battery connector on the first EBM. Up to four EBMs may be connected to the UPS.
4. If you are installing power management software, connect your computer to the UPS communication port using the supplied communication cable.
5. Plug the detachable UPS power cord, into the input connector on the UPS rear panel.
6. Plug the UPS power cord into a power outlet. The front panel indicators cycle through a startup sequence while the UPS conducts a self–test.
When the self-test is complete, the indicator flashes, indicating the UPS is in Standby mode with the equipment offline. If the alarm beeps or a UPS alarm indicator stays on, see T able 2 on page 22.
7. Plug the equipment to be protected into the appropriate UPS output receptacles (see page 15 for more information on load segments).
DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements.
8. Press and hold the On button until you hear the UPS beep (approximately one second). The indicator stops flashing and the bar graph indicators display the percentage of load being applied to the UPS.
The UPS is now in Normal mode and supplying power to your equipment.
8
1000 - 2000 VA
User’s Manual
1019297
Revision A
Page 9
NOTE. The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 24 hours after installation or long-term storage.
NOTE. If more than two EBMs are installed, an external battery charger is recommended for faster recharge times.
Figure 2. Installation
UPS Rear Panels
This section shows the rear panels of the Powerware 5125 models.
Figure 3. PW5125 1000i and PW5125 150 0i Rear Panel
1019297 Revision A
1000 - 2200 VA
User’s Manual
9
Page 10
Figure 4. PW5125 2200i Rear Panel
3 Operation and Configuration
Operating Modes
Powerware 5125’s front panel indicates the UPS status through the UPS indicators. Figure 5 shows the UPS front panel indicators and controls.
Figure 5. UPS Front Panel
10
1000 - 2000 VA
User’s Manual
1019297
Revision A
Page 11
Standby Mode
When the UPS is turned off and remains plugged into a power outlet, the UPS is in Standby mode. The indicator flashes and the bar graph indicators are off, indicating that power is not available from the UPS output receptacles. The battery rechar ges when necessary.
Normal Mode
During Normal mode, the indicator illuminates and the front panel displays the percentage of UPS load capacity being used by the pr otected equipment (see Figur e 6). The UPS monitors and charges the batteries as needed and provides power protection to your equipment.
Figure 6. Load Level Indicators
When all of the bar graph indicators and the indicator are illuminated, power requirements exceed UPS capacity; see page 22 for more information.
Buck and Double Boost Mode
With the Buck and Double Boost feature, the UPS accepts a wide input voltage range (-30%/+20% of nominal) and provides consistent, clean voltage to your equipment. The UPS operates normally from utility power and alerts you of the voltage fluctuations. The indicator alternates between green and red while in Buck, Single Boost, or Double Boost mode as shown in Figure 7.
Figure 7. Buck and Double Boost Indicators
1019297 Revision A
1000 - 2200 VA
User’s Manual
11
Page 12
Battery Mode
When the UPS is operating during a power outage, the alarm beeps once every four seconds and the indicator illuminates. When the utility power returns, the UPS switches to Normal mode operation while the battery recharges.
If battery capacity becomes low while in Battery mode, the indicator flashes and the alarm beeps twice every two seconds. Immediately complete and save your work to prevent data loss and similar difficulties. When utility power is restored after the UPS shuts down, the UPS automatically restarts.
Sleep Mode
If the UPS is on battery for approximately five minutes and supporting a small electrical load (≤ 10%), the UPS shuts down the load. After three minutes in Sleep mode, the UPS initiates a shutdown warning (two beeps every two seconds). This feature conserves battery power. To enable this feature, contact your service repr esentative.
UPS Configuration
Your PW5125 UPS can be configur ed by using a configuration softwar e that can be find on web (www.emea.powerware.com/product/PW5125.htm). This software is a DOS based program that can be executed from either a DOS box, from a Windows shortcut, or from the Windows Start, Run dialog box.
UPS setting that can be changed are as follow:
1. V oltage setting 220/230/240 V (230 V is factory default)
2. Enable/disable sleep mode (disable as factory default)
3. Enable/disable audible alarm, so that when disable no audible alarms will be given (Enable as factory default)
4. Enable/disable site wiring detection (not supported on European model)
Turning the UPS On
After the UPS is connected to a power outlet, it conducts a self–test and enters Standby mode. To turn on the UPS, press and hold the On button until you hear the UPS beep (approximately one second). The indicator stops flashing and the bar graph indicators display the percentage of load being applied to the UPS.
Starting the UPS on Battery
NOTE Before using this feature, the UPS must have been powered by utility power at least once.
To turn on the UPS without using utility power, press and hold the On button for at least four seconds. The UPS supplies power to your equipment and goes into Battery mode.
12
1000 - 2000 VA
User’s Manual
1019297
Revision A
Page 13
Turning the UPS Off
To turn off the UPS, press and hold the Off button until the long beep ceases (approximately five seconds). The indicator begins to flash and the UPS remains in Standby mode until you unplug the UPS from the power outlet.
Initiating the Self–Test
NOTE. The batteries must be fully charged to perform the self–test.
Press and hold the On button for three seconds to initiate the self–test. During the test, individual indicators illuminate as various parts of the UPS are checked. If the alarm beeps or a UPS alarm indicator stays on, see T able 2 on page 22.
Communication Port
The Powerware 5125 is factory-installed with a Single-Port Module. To establish communication between the UPS and a computer, connect your computer
to the UPS communication port using the supplied communication cable. When the communication cable is installed, power management software can exchange
data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.
The cable pins are identified in Figure 8 and the pin functions ar e described in Table 1.
Figure 8. Communication Port
niP
rebmuN
1ttaBwoLtcatnocyaleryrettaBwoLtuO 2DxRecivedlanretxeottimsnarTtuO
3DxTecivedlanretxemorfevieceRnI 4RTD
5DNG)sissahcotdeit(nommoclangiS— 6RSD)4niPotdeit(ecivedlanretxeoTtuO 7STRecivedlanretxemorfPnPtuO/nI
8liaFCAtcatnocyalerliaFCAtuO 9ecruoSrewoP)rewopCDstlov42ot8(V+tuO
emaNlangiS noitcnuF
ecivedlanretxemorf)yalPdnagulP(PnP
)6niPot deit(
nI
morfnoitceriD
SPUeht
Table 1. Communication Port Pin Assignment
1019297 Revision A
1000 - 2200 VA
User’s Manual
13
Page 14
Network Transient Protector
The Network Transient Pr otector, shown in Figure 9, is located on the rear panel and has jacks labeled IN and OUT . This featur e accommodates a single RJ–45 (10BaseT) network connector.
Connect the input connector of the equipment you are protecting to the jack labeled IN. Connect the output connector to the jack labeled OUT.
Figure 9. Network T ransient P rotector
14
1000 - 2000 VA
User’s Manual
1019297
Revision A
Page 15
Load Segments
Load segments are sets of receptacles that can be controlled by power management software, providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep key pieces of equipment running while you turn off other equipment. This feature allows you to save battery power. See your power management software manual for details.
NOTE. If the power management software is not used, the individual load segments cannot be controlled.
The following figures show the load segments for each UPS.
Figure 10. 1000 VA and 1500 VA Load Segments
Figure 11. 2200 V A Load Segments
1019297 Revision A
1000 - 2200 VA
User’s Manual
15
Page 16
4 UPS Maintenance
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean and dust–free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner .
For full battery life, keep the UPS at an ambient temperature of 25°C .
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every 6 months by plugging the UPS into a power outlet. The batteries charge to 90% capacity in approximately 3 hours. However, it is r ecommended that the batteries char ge for 24 hours after long­term storage.
Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative.
When to Replace Batteries
When the indicator flashes and there is a continuous audible alarm, the batteries may need replacing. Conduct a self–test by pressing and holding the button for three seconds. If the indicator stays on, contact your service representative to order new
batteries.
Replacing Batteries
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
With the hot–swappable battery feature, UPS batteries can be replaced easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the battery: 1) Press and hold the Off button until the long beep ceases (approximately five seconds), then unplug the UPS;
2) Wait 60 seconds while the internal processor shuts down before you disconnect the
battery. Consider all warnings, cautions, and notes before replacing batteries.
WARNING
Batteries can present a risk of electrical shock or burn from high short-circuit current. The following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries.
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury .
16
1000 - 2000 VA
User’s Manual
1019297
Revision A
Page 17
How to Replace Extended Battery Modules
Use the following procedure to replace EBMs:
1. Unplug the EBM cable from the UPS.
2. Replace the EBM. See “Recycling the Used Battery” on page 20 for proper disposal.
3. Plug the new EBM into the UPS as shown in Figure 12.
4. For additional EBMs, plug the EBM cable of the second cabinet into the battery
connector on the first EBM.
Figure 12. EBM Connections
How to Replace Internal Batteries
CA UTION
Pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it out of the UPS.
1019297 Revision A
1000 - 2200 VA
User’s Manual
17
Page 18
Use the following procedure to replace internal batteries:
1. Remove the UPS front panel by pulling the top.
2. Slide up and remove the metal battery cover .
3. 1000 VA units. Disconnect the r ed battery cable on the front of the battery. Pull the
battery out onto a flat, stable surface. Disconnect the black battery cable on the rear of the battery, then on the front of the battery. Disconnect the red battery cable on the rear of the battery. See “Recycling the Used Battery” on page 20 for proper disposal.
18
1000 - 2000 VA
User’s Manual
1019297
Revision A
Page 19
4. 1500 and 2200 VA units. Pull the battery out onto a flat, stable surface. Pr ess on the black tab on the battery cable connector to disconnect the battery. See “Recycling the Used Battery” on page 20 for proper disposal.
5. Install the new batteries in the reverse order of removal.
6. Reinstall the metal battery cover removed in Step 2. Replace the front panel.
Testing New Batteries
Press and hold the button for three seconds to initiate a self–test. After the test is finished, the indicator should turn off. If the indicator stays on, check the battery
connections. Call your service representative if the problem persists.
1019297 Revision A
1000 - 2200 VA
User’s Manual
19
Page 20
Recycling the Used Battery
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.
WARNING
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
CA UTION
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead–acid batteries and must be disposed of properly. For more information, contact your local recycling or hazardous waste center.
5 Troubleshooting
Audible Alarms and UPS Conditions
The UPS has an audible alarm feature to alert you of potential power problems. Use T able 2 to determine and r esolve the UPS alarms and conditions.
Figure 13. Alarm Indicators
20
1000 - 2000 VA
User’s Manual
1019297
Revision A
Page 21
Silencing an Audible Alarm
To silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing. The alarm does not silence if there is a low battery condition.
noitidnoCromralA esuaCelbissoP noitcA
ehTsirotacidni
seodSPUeht;noton
.tratston
sirotacidniehT
tonsirewop;gnihsalf
SPUehttaelbaliava
.selcatpecertuptuo
tonseodSPUehT
detcepxeehtedivorp
.emitpukcab
.edom
.ecivresro
tonsidrocrewopehT
.yltcerrocdetcennoc
.ytluafsiteltuollawehTriaperdnatsetnaicirtceledeifilauqaevaH
ybdnatSnisiSPUehT
gnigrahcdeenseirettabehT
deliaftset-flesehTtsaeltarofteltuorewopaotniSPUehtgulP
.snoitcennocdrocrewopehtkcehC
.teltuoeht
otrewopylppusotnottubnOehtsserP
|.tnempiuqedetcennoceht
42rofteltuorewopaotniSPUehtgulP
gnigrahcretfA.yrettabehtegrahcotsruoh nottubehtdlohdnasserp,yrettabeht
.rotacidniehtkcehcneht;sdnoces3rof
SPU"ees,nollitssirotacidniehtfI
.yrettabehtecalperot"ecnenetniaM
gnigrahcretfA.yrettabehtegrahcotsruoh3
rofnottubehtdlohdnasserp,yrettabeht .rotacidniehtkcehcneht;sdnoces3 nwodtuhs,nollitssirotacidniehtfI
ecivresruoytcatnocdnaSPUeht
.evitatneserper
.hgihoot
4yrevepeeb1
sdnoces
2yrevespeeb2
sdnoces
Table 2. Troubleshooting Guide
sierutarepmetlanretniSPU
.yrettabnoSPUhtiwtnempiuqeehtgnirewopsiSPUehT
.wolgninnursiyrettabehTsniamerrewopyrettabfosselrosetunim3
niyllacitamotuanwodstuhsSPUehT
.SPUehtgulpnudnaffonruT.sdnoces 01
.secruostaehynaevomerdnastnevraelC
tonsiSPUehtdnuorawolfriaehterusnE
tratserdnasetunim5tsaeltatiaW.detcirtser
tcatnoc,stsisrepnoitidnocehtfI.SPUeht
.evitatneserperecivresruoy
roftnempiuqeruoyeraperP.rewopyrettab
.nwodtuhs
dnanoitarugifnocdaolnognidneped(
ffonrutdnakrowruoyevaS.)egrahcyrettab
ebtonnacmralaehT.tnempiuqeruoy
.decnelis
1019297 Revision A
1000 - 2200 VA
User’s Manual
21
Page 22
noitidnoCromralA esuaCelbissoP noitcA
nogninnursiSPUehT
ehtesuacebrewopyrettab
rohgihootsiegatlovtupni
.woloot
.degrahcsidyletelpmoc
ehT.elbissopfi,egatlovtupniehttcerroC
litnuyrettabnoetarepootseunitnocSPU
siyrettabehtrodetcerrocsisnoitidnoceht
niegatlovtupnieht,stsisrepnoitidnocehtfI
.lanimonSPUehtmorfreffidyamaeraruoy
dnaegatlovenilytilituehT
fotuoeraycneuqerf
.gniriw
ehtkcehcnaicirtceledeifilauqaevaH
.noitacificeps
5yrevepeeb1
.sdnoces
.degrahcsid
yllufebyamyrettabehT
42rofteltuorewopaotniSPUehtgulP
gnigrahcretfA.yrettabehtegrahcotsruoh
nottubehtdlohdnasserp,yrettabeht
ehtkcehcneht;sdnoces3rof
.rotacidni
SPU"ees,nollitssirotacidniehtfI
.yrettabehtecalperot"ecnanetniaM
tonsiyrettabehT
.yltcerrocdetcennoc
ruoyllaC.snoitcennocyrettabehtkcehC
melborpehtfievitatneserperecivres
.stsisrep
noitcennoceriwdnuorG
enilehtrotsixetonseod
.gniriw
ehttcerrocnaicirtceledeifilauqaevaH
eraseriwlartuendna
.teltuollawehtnidesrever
100%
25%
deecxestnemeriuqerrewoP
rof%011–101(yticapacSPU
rof%051–111rosetunim 3
sidaolehtro)selcyc 01
.evitcefed
.SPUyticapacregral
emosevomeR.SPUehtgulpnudnaffonruT
tatiaW.SPUehtmorftnempiuqeehtfo
dnaffoerasDELllalitnusdnoces5tsael
aniatbootdeenyamuoY.SPUehttratser
.noitidnoctluafSPUruoyffonrutdnakrowruoyevaS
.SPUehtgulpnudnaffonruT.tnempiuqe
ehT.evitatneserperecivresruoytcatnoC
.decnelisebtonnacmrala
22
1000 - 2000 VA
User’s Manual
1019297
Revision A
Page 23
6 Specifications
rebmuNledoM
sleveLrewoP
i00015215WPW007,AV0001V032 i00515215WPW0501,AV0051V032 i00225215WPW0061,AV0022V032
Table 3. Model Specifications
sledoMAV0001mm052x104x261gk51 sledoMAV0051mm052x764x261gk32
i00225215WPmm052x394x502gk13
eludoMyrettaBdednetxEmm052x474x261gk72
Table 4. Weights and Dimensions
)stupnilanimontadetar(
W(snoisnemiD x D x )H thgieW
noitcennoCtupnI selcatpeceRtuptuO
egatloVlanimoN egnaRegatloVtupnI
V882-451
)%02+/%03-(
i00015215WProtcennoctupni023-CEI,A0131C-023CEI,A01)6( i00515215WProtcennoctupni023-CEI,A0131C-023CEI,A01)6( i00225215WProtcennoctupni023-CEI,A0131C-023CEI,A01)9(
Table 5. Power Connections
ycneuqerFgnitarepOgnisnes-otua,zH06/05
egnaRycneuqerFzH5664
gniretliFesioN esionedomnommocdnalamronrofretlifenildnasVOM
noitalugeR
)edomlamroN(
noitalugeR
)edomyrettaB(
mrofevaWegatloVevaweniS
Table 6. Technical Specifications
egatlovlanimonfo%6+ot%01-
%5±egatlovtuptuolanimoN
1019297 Revision A
1000 - 2200 VA
User’s Manual
23
Page 24
erutarepmeTgnitarepOC°04otC°01
erutarepmeTegarotSC°52otC°0
erutarepmeTtisnarTC°55otC°52-
ytidimuHevitaleRgnisnednocnon%595
edutitlAgnitarepOlevelaesevobasretem000,3otpU
edutitlAtisnarT levelaesevobasretem000,51otpU
C°52:ecnamrofrepyrettablamitpO
esioNelbiduA
noisserppuSegruS 5-4-00016CEI,)785EEEIylremrof(ByrogetaC14.26CISNA
ecnamrofnoCytefaS
sgnikraMycnegA OKMED,SG/AGL,kciT-C,EC;LUcdnaLU
CME300-SECI,51traPCCF,2-19005NE
Table 7. Environmental and Safety
noitarugifnoC
2
noitarugifnoCMBE
P
epyT dicadael,detaluger–evlav,eerf–ecnanetniam,delaeS
gnigrahC
daollacipyt,edomlamroNABd04nahtsseL
edomyrettaBABd55nahtsseL
;)ylnoenilatad(A794LU,8771LU ;1.701.oN,2.22CASC/NAC 05906CEIdna1-1-19005 NE
seirettablanretnihA9,V42)2(:AV0001 seirettablanretnihA7,V84)4(:AV0051
seirettablanretnihA21,V84)4(:AV002
seirettabhA9,V42)8(:42-MBE5215WP seirettabhA9,V84)8(:84-MBE5215W
tayticapacelbasu%09otsruoh 3nahtssel:yrettablanretnI
egrahcsiddaolllufretfaegatlovenillanimon
sisselrodaol%08tagnigrahcer:yrettablanretxE
elbasu%09otemitegrahcsidx61nahteromon;dednemmocer na;egrahcsiddaolllufretfaegatlovenillanimontayticapac egrahcerretsafrofdednemmocersiregrahcyrettablanretxe
.sMBE2nahteromgnisunehwsemit
gnirotinoM ;gninrawdnanoitcetederuliafreilraerofgnirotinomdecnavdA
sMBElanoitiddafonoitcetedotua
Table 8. Battery
ledoM seirettaBSPUlanretnI MBE 1 sMBE 2 sMBE 3 sMBE 4
AV000141/506/54071/59 AV005171/697/33641/36471/29102/021
AV002241/606/62071/55891/18422/601
.egrahcyrettab
Table 9. Battery Run Times (in Minutes at Full/Half Load)
24
1000 - 2000 VA
User’s Manual
dnanoitarugifnocdaolehtnognidnepedyravdnaetamixorppaerasemityrettaBETON
1019297
Revision A
Loading...