Powerware Uninterruptible Power Supply, 9315 Installation And Operation Manual

9
Uninterruptible Power
Supply
500 kVA -- 750 kVA
315
Installation and Operation
Manual
164201244 Rev. D
------------------------------------------------------------------------
------------------------------------------------------------------------
----------------------------------
IMPORTANT SAFETY INSTRUCTIONS
Instructions Importantes Concernant La Sécurité
SAVE THESE INSTRUCTIONS
Conserver Ces Instructions
This manual contains important instructions for your Uninterruptible Power
Supply (UPS) system. You should follow these instructions during the
installation and maintenance of the UPS, options, accessories, and batteries.
Cette notice contient des instructions importantes
concernant la sécurité.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense.
WARNING: This is a product for restricted sales distribution to informed partners. Installation restrictions or additional measures may be needed to prevent disturbances.
ii
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Tabl e of C onte n ts
Introduction xi...............................................
Basic System Configurations xii...................................
Using This Manual xii............................................
Conventions Used in This Manual xiv...............................
Safety Considerations xiv.........................................
For More Information xv..........................................
Getting Help xv..................................................
Section I Installation
Getting Started 1---1..........................................
1
1.1 Installing the UPS 1--- 1......................................
1.1.1 Creating an Installation Plan 1--- 1.............................
1.1.2 Preparing Your Site 1---1.....................................
1.1.3 Environment Considerations 1--- 2.............................
1.1.4 Preparing for Wiring the UPS System 1--- 2.....................
1.1.5 Inspecting and Unpacking Each Cabinet 1--- 3..................
2 Installing the UPS System 2---1................................
2.1 Preliminary Installation Information 2--- 1........................
2.2 SingleModuleInstallation 2---2...............................
2.2.1 Installing the UPS Cabinet Sections 2--- 2.......................
2.2.2 Installing UPS Internal Power and Control Wiring 2--- 2...........
2.2.3 Installing UPS External Power and Control Wiring 2--- 3..........
2.2.4 Installing Input/Rectifier Customer Connections 2--- 4............
2.2.5 Installing Output/Inverter Customer Connections 2--- 4...........
2.2.6 Prepare for Installing Optional Accessories 2--- 5................
2.3 Multi-Module Installation 2--- 5.................................
2.3.1 Installing the UPS Cabinet Sections 2--- 5.......................
2.3.2 Installing UPS Internal Power and Control Wiring 2--- 5...........
2.3.3 Installing UPS External Power and Control Wiring 2--- 6..........
2.3.4 Installing Input/Rectifier Customer Connections 2--- 6............
2.3.5 Installing Output/Inverter Customer Connections 2--- 6...........
2.3.6 Prepare for Installing Optional Accessories 2--- 6................
2.4 Initial Startup 2--- 7...........................................
2.5 Completing the Installation Checklist 2---7......................
2.5.1 Installation Checklist 2--- 8....................................
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
iii
3 Installing Batteries 3---1.......................................
4 Installing a Remote Battery Disconnect 4---1...................
5 Installing a Remote EPO Control 5---1..........................
6 Installing a Remote Monitor Panel 6---1........................
7 Installing a Relay Interface Module 7--- 1.......................
8 Installing a Supervisory Contact Module 8---1..................
Section II Operation
9
Understanding UPS Operation 9---1............................
9.1 Looking Inside the Parallel Capacity/Redundant System 9--- 1.....
9.2 Normal, Battery, and Bypass Modes 9---2......................
9.3 Normal Mode 9---3..........................................
9 . 4 B y p a s s M o d e 9 --- 4..........................................
9.5 Battery Mode 9---5..........................................
10 Operational Controls and Features 10---1......................
10.1 General 10---1...............................................
10.2 UPS Standard Features 10--- 1.................................
10.2.1 Control Panel 10--- 1..........................................
10.2.2 UPS Circuit Breakers 10--- 3...................................
10.2.3 EMERGENCY UPM OFF 10--- 3................................
10.2.4 Customer Interface 10--- 3.....................................
10.2.5 Automatic Battery Charge Current Limit 10---3...................
10.2.6 Customer Convenience Outlet 10--- 4...........................
10.2.7 Installation Features 10--- 4....................................
10.3 Options and Accessories 10---4................................
10.3.1 5% Input Filter 10--- 4.........................................
10.3.2 Battery 10--- 4................................................
10.3.3 External Fused Battery Disconnect 10---4.......................
10.3.4 Upgrade Capability 10---4.....................................
10.3.5 Remote Monitor Panel 10 ---4..................................
10.3.6 Relay Interface Module 10---5..................................
10.3.7 Modem 10---5...............................................
10.4 Safety Considerations 10---5...................................
10.5 Symbols, Controls, and Indicators 10---6........................
iv
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11 U s i n g t h e C o n t r o l P a n e l 1 1 --- 1.................................
11.1 Description 11--- 1............................................
11.2 Using the LCD Screen 11--- 2..................................
11.3 Using the Pushbuttons 11 ---3..................................
11.4 Adjusting the Contrast 11---3..................................
11.5 Reading the Status Indicators 11---4............................
11.6 Using the Menu Options 11--- 5................................
11.6.1 System Meters Screen 11--- 6..................................
11.6.2 Load Amp Meters Screen 11--- 7...............................
11.6.3 Software Versions Screen 11---8...............................
11.6.4 System History Screen 11--- 9..................................
11.6.5 Active System Events Screen 11---10............................
11.6.6 Unit Statistics Screen 11---11...................................
11.6.7 Mimic Screen 11--- 12..........................................
11.6.8 T ime Setup Screen 11--- 13.....................................
11.6.9 Port Setup Screen 11--- 14......................................
12 UPS Operating Instructions 12--- 1.............................
12.1 Operation 12--- 1.............................................
12.2 Starting the UPS 12--- 1.......................................
12.3 Starting the UPS in Bypass Mode 12--- 3........................
12.4 Transfer to Bypass Mode 12---3................................
12.5 Transfer to Normal Mode 12 ---3................................
12.6 Transfer to Bypass with UPS Shutdown 12---4...................
12.7 UPS and Critical Load Shutdown 12--- 4.........................
12.8 Using the UPS EMERGENCY UPM OFF Pushbutton 12--- 4........
12.8.1 To Use the UPS EMERGENCY UPM OFF Pushbutton 12--- 5.......
12.8.2 Resetting the UPS System after an EMERGENCY UPM OFF 12---5.
13 Using Features and Options 13---1.............................
13.1 General 13---1...............................................
13.2 Building Alarm Monitoring 13 ---1...............................
13.3 General Purpose Relay Contacts 13--- 1.........................
13.4 Remote Monitor Panel 13---2..................................
13.5 Relay Interface Module 13---4..................................
13.6 Supervisory Contact Module 13--- 5.............................
13.7 Battery Racks 13--- 6..........................................
13.8 External Battery Disconnect 13--- 6..............................
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
v
14 Responding to System Events 14---1...........................
14.1 General 14---1...............................................
14.2 System Event Horns 14---1....................................
14.3 System Event Lights 14---1....................................
14.4 System Event Messages 14---2................................
15 Serial Communications 15---1.................................
15.1 Description 15--- 1............................................
15.2 Locating the Communications Panel 15--- 1......................
15.3 Connecting Equipment to a Serial Port 15--- 1....................
15.4 Configuring the Serial Ports 15--- 4..............................
15.4.1 Modes 15--- 5................................................
15.4.2 Rate 15--- 5..................................................
15.4.3 Data/Stop 15--- 6.............................................
15.4.4 Handshaking 15--- 6..........................................
15.4.5 Save 15--- 6..................................................
15.4.6 Default Settings 15--- 6........................................
15.5 Terminal Mode 15--- 7.........................................
15.5.1 Printing Selected Information 15---7............................
15.5.2 Entire Log (Ctrl + P) 15---8....................................
15.5.3 Meters Printout (Ctrl + M) 15--- 9...............................
15.5.4 System Information Printout (Ctrl + A) 15--- 9....................
15.6 System Configuration 15 ---10...................................
15.6.1 System Configuration Mode Main Menu 15--- 10...................
15.6.2 Program Building Alarms 15--- 10................................
15.6.3 Enable/Disable Default Functions 15 ---11.........................
15.6.4 Customize Alarm Messages 15---12.............................
15.6.5 Program Unit Name 15---13....................................
15.6.6 Change Password 15---13......................................
15.6.7 Battery T est Setup 15---14......................................
15.6.8 Modify Low Battery Time 15 ---15................................
15.7 Calibration Mode 15--- 15.......................................
15.8 Computer Mode 15--- 15........................................
15.9 Remote Monitor Mode 15 ---15..................................
vi
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
16 Remote Notification 16---1....................................
16.1 Description 16--- 1............................................
16.2 Remote Notification Features 16---2............................
16.3 Description of Operation 16 ---3................................
16.3.1 Call Answer 16---3............................................
16.3.2 Call Out 16--- 3...............................................
16.3.3 Housekeeping 16--- 4.........................................
16.4 Hardware Requirements 16---5.................................
16.5 Configuring the Modem 16--- 6.................................
16.5.1 Basic Modem Configuration 16--- 6.............................
16.5.2 Configuring the Modem to Call a Remote Computer 16 ---6........
16.5.3 Configuring the Modem to Call a Numeric Pager 16--- 7...........
16.5.4 Final Modem Configuration 16---8..............................
16.6 UPS Setup Configuration 16---9................................
16.6.1 User Selected Events 16--- 9...................................
17 Maintaining the UPS System 17--- 1............................
17.1 General 17 ---1...............................................
17.2 Important Safety Instructions 17--- 1.............................
17.3 Performing Preventive Maintenance 17--- 3.......................
17.4 Maintenance Training 17---4...................................
18 Product Specifications 18---1..................................
18.1 Model Numbers 18--- 1........................................
18.2 UPS System Input 18---1......................................
18.3 UPS System Output 18 ---2....................................
18.4 Environmental Specifications 18 ---3............................
A p p e n d i x A --- C u s t o m e r I n f o r m a t i o n A --- 1.........................
Warranty W---1..................................................
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
vii
List of Figures
F ig u r e 4 --- 1 . R e mo t e B a t t er y D i s c o nn e c t E n c lo s u r e 4 --- 1.......................
F ig u r e 5 --- 1 . R e mo t e E P O C o n t r ol 5 --- 1......................................
F ig u r e 6 --- 1 . R e mo t e M o n i to r Pa n el (R M P ) 6 --- 2...............................
Figure 6---2. Terminal Block Bracket 6--- 3....................................
F ig u r e 7 --- 1 . R e la y I n t e rf a c e M o d ul e 7 --- 1....................................
Figure 7---2. Terminal Block Bracket 7--- 2....................................
F ig u r e 8 --- 1 . S up e r v i s o r y C o n t a c t Mo d u le 8 --- 1...............................
Figure 8---2. Terminal Block Bracket 8--- 2....................................
F ig u r e 8 --- 3 . S up e r v i s o r y C o n t a c t Mo d u le TB 2 8 --- 4...........................
F ig u r e 9 --- 1 . M ai n El e me n t s o f t h e U P S Sy s t e m 9 --- 1..........................
Figure 9---2. Path of Current Through the UPS in Normal Mode 9--- 3............
Figure 9---3. Path of Current Through the UPS in Bypass Mode 9---4............
Figure 9---4. Path of Current Through the UPS in Battery Mode 9--- 5.............
F ig u r e 1 0 --- 1 . U P S C o n tr o l s a n d I n d ic a t o rs 1 0 --- 2...............................
F ig u r e 1 1 --- 1 . U P S C o n tr o l P a n el 1 1 --- 1........................................
F ig u r e 1 1 --- 2 . Pa r t s o f th e L C D Sc r e e n 1 1 --- 2...................................
F ig u r e 1 1 --- 3 . S ys t e m M e t er s Sc r e en 11 --- 6....................................
F ig u r e 1 1 --- 4 . L o ad Am p s M e t er s Sc r e en 11 --- 7.................................
F ig u r e 1 1 --- 5 . Ve r s i o n s S c r e en 11 --- 8..........................................
F ig u r e 1 1 --- 6 . E ve n t H i s t or y Lo g S c r e en 1 1 --- 9..................................
Figure 11---7. Active System Events Screen 11 ---10...............................
F ig u r e 1 1 --- 8 . U n i t St a t i s ti c s S c r e en 1 1 --- 1 1......................................
F ig u r e 1 1 --- 9 . M im i c S c r ee n 1 1 --- 1 2............................................
F ig u r e 1 1 --- 1 0. Ti m e S e t up S c r e e n 1 1 --- 1 3........................................
F ig u r e 1 1 --- 1 1. Po r t S e t u p S c r ee n 1 1 --- 1 4........................................
F ig u r e 1 3 --- 1 . R e mo t e M o n i to r Pa n el 13 --- 2.....................................
F ig u r e 1 3 --- 2 . R e la y I n t e rf a c e M o d ul e 1 3 --- 4....................................
F ig u r e 1 3 --- 3 . S up e r v i s o r y C o n t a c t Mo d u le 1 3 --- 5...............................
F ig u r e 1 5 --- 1 . Po r t 1 P i n As s i gn m e nt s 1 5 --- 2....................................
F ig u r e 1 5 --- 2 . Po r t 2 P i n As s i gn m e nt s 1 5 --- 3....................................
F ig u r e 1 5 --- 3 . S e t u p S e r i al Po r t 1 Sc r e en 1 5 --- 4.................................
F ig u r e 1 5 --- 4 . E ve n t H i s t or y Lo g 1 5 --- 8.........................................
F ig u r e 1 5 --- 5 . S ys t e m M e t er s Sc r e en 15 --- 9....................................
viii
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
List of Tables
Table 4---1. Remote Battery Disconnect Power Terminations 4---3...................
Table 4---2. Remote Battery Disconnect Circuit Breaker Ratings 4---3................
Ta b le 5 --- 1 . Re m o t e E P O W i r e Te r mi n a t io n s 5 --- 2.................................
Ta b le 5 --- 2 . Re m o t e E P O 5 --- 2.................................................
Ta b le 6 --- 1 . Op t i o na l M o n i t or i n g A c ce s s o r i e s 6 --- 1................................
Ta b le 6 --- 2 . RM P W ir e Te rm i n a ti o n s 6 --- 4........................................
Ta b le 7 --- 1 . RI M W ir e Te r m i n a ti o n s 7 --- 3.........................................
Table 8 ---1. Supervisory Contact Module Wire Terminations 8--- 3...................
Ta b le 13 --- 1 . O p t io n a l M o n it o r i ng Ac c e s so r i e s 13 --- 2...............................
Ta b le 15 --- 1 . P i n A s s ig n m en t s f o r Po r t 1 ( D B --- 9 ) 1 5 --- 2.............................
Ta b le 15 --- 2 . P i n A s s ig n m en t s f o r Po r t 2 ( D B --- 2 5 ) 15 --- 3............................
Ta b le 15 --- 3 . O p t io n s Av ai l a b l e fo r E a c h C o m mu n i ca t i o n P o rt 1 5 --- 5..................
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
ix
This Page Intentionally Left Blank.
x
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Introduction
Congratulations on your purchase of a Powerware 9315 (500 kVA--- 750 kVA) Uninterruptable Power Supply! The Powerware online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and/or minimize the adverse effect on equipment production due to unexpected power problems.
The Powerware UPS System continually monitors incoming electrical power and removes the surges, spikes, sags, and other irregularities that are inherent in commercial utility power. Working with your building’s electrical system, the UPS System supplies clean, consistent power that your sensitive electronic equipment requires for reliable operation. And during brownouts, blackouts, and other power interruptions, optional battery strings provide emergency power to safeguard your operation.
The UPS system is housed in a free-standing cabinet, divided into three sections to facilitate shipping. The cabinet sections line up and match in style and color, and have safety shields behind the doors for hazardous voltage protection. The following illustration depicts a typical Powerware 9315 (500 kVA---750 kVA) UPS System.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
MODULE
BYPASS
CABINET
OUTPUT
INVERTER
CABINET
INPUT
RECTIFIER
CABINET
Typical Powerware 9315 (500 kVA--- 750 kVA) UPS System
xi
Basic System Configurations
These basic UPS system configurations are possible:
· Single Module UPS and one battery string
· Multi-Module (Parallel for Capacity/Redundancy) UPS System consisting of two
or more UPS modules, with one battery string for each module and a Hot---Sync Capacity module
· Multi-Module (Parallel for Capacity/Redundancy) UPS System consisting of two
or more UPS modules, with one common battery string and a Hot ---Sync Capacity module
The optional Hot---Sync Capacity system (Parallel for Capacity/Redundancy), using a System Bypass Module (SBM), allows two or more UPMs to operate in parallel to provide more capacity than a single UPM and as backup for each other. The Parallel Capacity/Redundant system can supply up to 4000 Amps, depending on the SBM used. In addition, when one UPM is taken out of service for maintenance or is not operating properly, the redundant UPM continues to supply uninterrupted power to the critical load.
You can enhance any of these system configurations by adding optional accessories, such as a Remote Monitor Panel (RMP), Relay Interface Module (RIM), Supervisory Contact Module (SCM), or Remote Emergency Power Off (EPO) control.
Using This Manual
Your UPMs function automatically and require very little attention during normal operation. However, you should read and understand the procedures described in this manual to ensure trouble-free operation. In particular, you should be thoroughly familiar with the Emergency UPM Off procedure described in Chapter 7 of this manual.
The information in this manual is divided into the sections and chapters listed. The system you are installing dictates which parts of this manual you should read. Everyone should read the Introduction, Chapters 1 and 2 and Chapters 7 through 12.
Introduction
The Introduction provides a brief description of the UPS system, a description of the content of each chapter, safety, text conventions used in the manual and reference information.
Section I
· Chapter 1 -- Getting Started -- tells you how to prepare your site for the
installation of your UPS system. It discusses equipment environmental requirements, inspecting, and unpacking cabinets.
· Chapter 2 -- Installing the UPS System -- describes how to install the UPS
cabinets and optional equipment.
· Chapter 3 -- Installing Batteries -- provides battery safety and installation
information.
· Chapter 4 -- Installing a Remote Battery Disconnect -- describes how to
install the UPS battery disconnect.
xii
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
· Chapter 5 -- Installing a Remote EPO Control -- contains information for
installing the optional Remote Emergency Power Off (EPO) control.
· Chapter 6 -- Installing a Remote Monitor Panel -- contains information for
installing the optional Remote Monitor Panel (RMP).
· Chapter 7 -- Installing a Relay Interface Module -- contains information for
installing the optional Relay Interface Panel (RIM).
· Chapter 8 -- Installing a Supervisory Contact Module -- contains information
for installing the optional Supervisory Contact Module (SCM).
Section II
· Chapter 9 -- Understanding UPS Operation -- provides information on
understanding parallel operation.
· Chapter 10 -- Operational Controls and Features -- describes the standard
and optional operational features and controls of the UPS system.
· Chapter 11-- Using the Control Panel -- describes the controls and indicators
found on the Control Panel and shows the various information screens displayed on the LCD screen.
· Chapter 12 -- UPS Operating Instructions -- contains startup and shutdown
procedures for the UPS system.
· Chapter 13 -- Using Features and Options -- contains descriptions and
instructions for the UPS system features and options.
· Chapter 14 -- Responding to System Events -- lists all the alarm, messages
and notices that occur during operation of the UPS system.
· Chapter 15 -- Serial Communications -- describes the serial communications
features of the UPS system.
· Chapter 16 -- Remote Notification -- contains instructions for using the
remote notification feature of the UPS system.
· Chapter 17 -- Maintaining the UPS System -- contains maintenance
instructions for the UPS system.
· Chapter 18 -- Product Specifications -- provides detailed specifications for
the UPS system.
· Appendix A --Customer Information -- contains important information on
wiring requirements and recommendations, and important diagrams of the cabinet’s mechanical details and electrical access.
· Warranty -- provides the Powerware warranty for this product.
Read through each procedure before you begin. Perform only those procedures that apply to the UPS system you are installing or operating.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
xiii
Conventions Used in This Manual
The text in this manual uses these conventions:
· Bold type highlights important concepts in discussions, key terms in
procedures, and menu options.
· Italic type highlights notes and new terms where they are defined.
· Rectangular boxes containing bold type are warnings or cautions that pertain to
the Parallel Capacity system or its electrical connections.
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system refers to the entire power protection system—the UPS modules, battery strings and options or accessories installed.
Safety Considerations
The UPS cabinet is designed for industrial or computer room applications, and contain safety shields behind the doors. However, the UPS system is a sophisticated power system and should be handled with appropriate care, following these guidelines:
· Keep surroundings clean and free from excess moisture.
· Do not operate the UPS system close to gas or electric heat sources.
· The system is not intended for outdoor use.
· The operating environment should be maintained within the parameters
stated in this manual.
· Keep the cabinet doors closed and locked to ensure proper cooling airflow
and to protect personnel from dangerous voltages inside the unit.
· The UPS system contains it s own power source. Lethal voltages are
present even when the UPS is disconnected from utility power.
WARNING:
Only AUTHORIZED SERVICE PERSONNEL should perform maintenance on or service the UPS system.
If service or routine maintenance is required:
· Ensure all power is disconnected before performing installation or service.
· Ensure the area around the UPS system is clean and uncluttered.
· Battery maintenance or battery replacement should be performed only by
authorized service personnel.
· Observe all DANGER, CAUTION, and WARNING notices affixed to the
inside and outside of the equipment.
xiv
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
For More Information
This manual describes how to install and operate your UPS system. For more information about the installation and operation of the Powerware Hot Sync --­Capacity system, refer to the following:
164201150 Powerware
and Operation
Provides installation instructions for the System Bypass Module (SBM) cabinet, and optional components and accessories. Site preparation, planning for installation, and wiring and safety information are supplied. Detailed illustrations of cabinet and optional accessories, including dimensional and connection point drawings are provided.
Describes the SBM Control Panel and explains the functions of the SBM; discusses the standard features of the SBM and optional accessories; provides procedures for starting and stopping the parallel for capacity redundancy system, and information about maintenance and responding to system events.
A ls o de s c ri b e d a r e t h e R S --- 4 8 5 a n d R S --- 2 3 2 s e ri a l communications capabilities of the SBM; discusses the two communications ports on the Customer Interface Panel inside the SBM and how to connect optional remote accessories to your SBM; provides information about enabling, disabling, and customizing building alarms.
Parallel Capacity/Redundant System Installation
Contact your local Powerware Field Service office for information on how to obtain copies of this manual.
Getting Help
If you need to schedule initial startup, need regional locations and telephone numbers, have a question about any of the information in this manual, or have a question this manual does not answer, please call Powerware Corporation at:
United States 1-800-843-9433 Canada 1-800-461-9166 Outside the U.S. Call your local representative
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
xv
This Page Intentionally Left Blank.
xvi
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Section I
Installation
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
This Page Intentionally Left Blank.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
n
Getting Started
1.1 Installing the UPS
The cabinet sections of the UPS are shipped on separate pallets. Use a forklift or pallet jack, rated to handle the weight of the cabinets (refer to Drawing 164201244--- 3 in Appendix A for cabinet weights), to move the packaged cabinet sections to the installation site, or as close as possible to the site, before unloading from the pallet.
This is the basic sequence of the installation steps:
1. Create an installation plan for the UPS system (Chapter 1).
2. PrepareyoursitefortheUPSsystem(Chapter1).
3. Inspect, unpack, and unload the UPS cabinet sections (Chapter 1).
4. Wire the system (Chapter 2).
1
5. Install features, accessories, and/or options, as applicable (Chapter 3).
6. Complete the Installation Checklist (Chapter 2).
7. Have authorized service personnel perform preliminary operational checks and
startup.
NOTE: Startup and operational checks should be performed only by authorized
service personnel. This service is usually offered as part of the sales contract for your UPS. Contact service in advance (usually a two week notice is required) to reserve a preferred startup date.
1.1.1 Creating an Installation Plan
Before beginning to install the UPS system, read and understand how this manual applies to the system being installed. Use the procedures and illustrations in the following chapters to create a logical plan for installing the system.
1.1.2 Preparing Your Site
For your UPS system to operate at peak efficiency, your installation site should meet the environmental parameters outlined in this manual. If you intend to operate the system at an altitude higher than 1500 meters (5000 feet), contact your local sales or service office for important information about high altitude operation. The operating environment must meet the size and weight requirements shown in Drawing 164201244---8, and Table P of Appendix A.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
1--1
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range: 0 --- 4 0 ˚C (32--- 104˚F)
Recommended Operating Range: 20---25˚C (68---77˚F)
Maximum Relative Humidity: 95%
The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the front of the cabinet, and outlets are in the top. You must allow clearance in front of and above each cabinet for proper air circulation.
1.1.3 Environment Considerations
The life of the UPS system is adversely affected if the installation does not meet the following guidelines:
1. The system must be installed on a level, sealed concrete pad or on a sealed
concrete floor.
2. The system must be installed in a temperature-controlled indoor area free of
conductive contaminants.
Failure to follow guidelines may invalidate UPS warranty.
1.1.4 Preparing for Wiring the UPS System
For external wiring requirements, including the minimum AWG size of external wiring, refer to Table A or B in Appendix A. The power wiring connections for this equipment are rated at 90˚C. Ifwireisruninanambienttemperaturegreaterthan 30˚C,highertemperaturewireand/orlargersizewiremaybenecessary.Control wiring for EPO and optional accessories (such as building alarms, and monitoring interface) should be connected at the customer interface panels and terminal blocks located inside the UPS.
1--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
1.1.5 Inspecting and Unpacking Each Cabinet
The first task in preparing for installation is inspecting and unpacking the UPS sections. The UPS sections are shipped bolted to wooden pallets and protected with outer protective packaging material, as shown in Figure 1---1, and a plastic inner covering.
WOODEN PALLET
OUTER
PACKAG I NG
Figure 1 ---1. Cabinets as Shipped, with Outer Packaging and Pallet
1. Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION: Do not install a damaged cabinet. Report any damage to the carrier and contact your local sales or service office immediately.
2. Use a forklift or other material handling equipment to move the cabinet to a
convenient unpacking area. Insert the forklift jacks between the pallet supports on the bottom of the unit.
CAUTION: Do not tilt cabinets more than 10 degrees from vertical.
3. Set each pallet on a firm, level surface, allowing a minimum clearance of
4.6m (15 ft) on each side for removing the cabinets from the pallets.
4. If outer packaging is secured with steel bands, cut and remove the bands from
around each cabinet.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
1--3
5. Remove the protective cardboard covering from the cabinets, cutting where
indicated, using a knife blade no longer than 25 mm (1 in.).
6. Remove the plastic bag and foam packing material, and discard or recycle
them in a responsible manner.
7. After removing the protective covering, inspect the contents for any evidence
of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact the Powerware, Inc. Customer Service Department immediately to determine the extent of the damage and its impact upon further installation.
NOTE: While awaiting installation, protect the unpacked UPS cabinets from
moisture, dust, and other harmful contaminants. Failure to store and protect the UPS properly may invalidate the warranty.
1--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Installing the UPS System
2.1 Preliminary Installation Information
WARNING:
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
· Refer to Appendix A of this manual for installation drawings and additional
installation notes.
· Dimensions in this manual are in millimeters and (inches).
· Do not tilt the UPS cabinet sections more than 10˚ during installation.
· The conduit landing plates are to be removed to add conduit landing holes as
required. Plate material is 14 gauge steel (0.075 in. thick).
· The EMERGENCY UPM OFF (EPO)andtheRemoteEmergencyPowerOff
(REPO) pushbuttons normally open all breakers in the UPS, shutdown the UPS, and isolate power from the critical load. However, the EPO and REPO may be configured to transfer the UPS to bypass and shutdown the UPS. Local electrical codes may also require tripping protective devices upstream from the UPS.
2
· The UPS cabinet sections must be installed on a level, sealed concrete pad or
floor.
· If perforated floor tiles are required for ventilation, place them in front of the
UPS. Refer to Table P in Appendix A for equipment weight and point loading.
· Details about control wiring are provided in each procedure for connecting
options and features. Drawing 164201244--- 2 and Tables K through O in Appendix A identify the control wiring terminations.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
2--1
2.2 Single Module Installation
To install a single module UPS system, perform the procedures in the following paragraphs. If a multi-module system is being installed, proceed to paragraph 2.3.
2.2.1 Installing the UPS Cabinet Sections
Each UPS cabinet section is bolted to a wooden pallet. To remove the pallets, perform the following procedure:
WARNING: The UPS cabinet sections are extremely heavy. Refer to Drawing 164201244 --3 in Appendix A for weight of sections. If unloading instructions are not closely followed, the cabinet may tip and cause serious injury.
1. Move UPS cabinet sections to the final installed location using a forklift.
2. Remove hardware securing each cabinet section to respective pallet.
CAUTION: Lift only with forklift or cabinet damage may occur.
3. Using forklift, raise the UPS cabinet section until the cabinet bottom clears the
pallet by approximately 3 mm (1/8 in.).
4. Once UPS cabinet section is clear of the pallet, pull the pallet from under the
UPS cabinet. Discard or recycle them in a responsible manner.
5. Carefully lower the UPS cabinet section until the cabinet base contacts the
floor.
6. Repeat steps 3 through 5 for remaining cabinet sections
2.2.2 Installing UPS Internal Power and Control Wiring
NOTE: The cables used in steps 2 through 4 are coiled inside the Input/Rectifier
cabinet and are attached at the factory to the output of the rectifier. The cables used in steps 7 and 8 are coiled inside the Module Bypass Cabinet (MBC) and are attached at the factory to the input of the MBC.
1. Remove the plastic shield covering the inverter input section of the
Output/Inverter cabinet.
2. Route DC Link cables from the rectifier output (Input/Rectifier cabinet) through
cutout in cabinet sides to the inverter input (Output/Inverter cabinet).
3. Connect positive DC Link power wiring to the inverter input. Connect two
cables to each inverter. Refer to Appendix A of this manual for terminal locations and tightening torque.
4. Connect negative DC Link power wiring to the inverter input. Connect two
cables to each inverter. Refer to Appendix A of this manual for terminal locations and tightening torque.
5. Reinstall inverter input section plastic shield.
2--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
6. Remove the plastic shield covering the inverter output section of the
Output/Inverter cabinet.
7. Route the MBC input cables from the MBC through cutout in cabinet sides to
the inverter output (Output/Inverter cabinet).
8. Connect phase A, B, and C and Neutral power wiring from MBC to the
respective inverter output. Refer to Appendix A of this manual for terminal locations and tightening torques.
9. Route ground braid from top of Output/Inverter cabinet to Input/Rectifier
cabinet through cabinet cutouts. Braid is secured at the factory to the Output/Inverter cabinet mounting stud.
10. Connect ground braid to Input/Rectifier cabinet mounting stud and secure.
11. Route ground braid from top of MBC to Output/Inverter cabinet through
cabinet cutouts. Braid is secured at the factory to the MBC mounting stud.
12. Connect ground braid to Output/Inverter cabinet mounting stud and secure.
13. Reinstall inverter output section plastic shield.
14. Connect the Output/Inverter 15-pin control wiring harness connector to the
Input/Rectifier 15-pin control wiring harness connector. Refer to Appendix A of this manual for connector locations.
15. Connect the MBC 15-pin control wiring harness connector to the
Output/Inverter 15-pin control wiring harness connector. Refer to Appendix A of this manual for connector locations.
16. Connect 3-pin control wiring harness connector P6 from the MBC to connector
J6 on Inverter number 2 control board. Refer to Appendix A of this manual for connector locations.
2.2.3 Installing UPS External Power and Control Wiring
1. Remove the sheetmetal shield covering the input terminal area in the
Input/Rectifier cabinet to gain access to the Battery I/O Customer Interface and CB2TB. Refer to Appendix A for location of the shield.
NOTE: Remove Input/Rectifier cabinet conduit landing plate to punch conduit holes.
2. Connect phase A, B, and C power wiring from source to respective rectifier
inputs in the Input/Rectifier cabinet. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information.
3. Connect positive and negative DC power wiring from batteries to the
respective DC inputs in the Input/Rectifier cabinet. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information.
NOTE: Remove entire MBC top panel to punch conduit holes.
4. Connect phase A, B, and C power wiring from bypass source to respective
bypass inputs in the MBC cabinet. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information.
5. Connect phase A, B, and C and Neutral power wiring from MBC output to
critical load. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
2--3
6. Connect control wiring (battery breaker open and close signals and shunt
DC disconnect) between external battery disconnect and the UPS. Refer to Appendix A of this manual for wiring requirements and wiring access information.
7. After wiring the UPS system to the facility power and critical load, be sure to
ground the system according to local and/or national electrical wiring codes.
8. Install batteries in accordance with all applicable codes and regulations,
including the National Electrical Code (NEC), Article 480.
2.2.4 Installing Input/Rectifier Customer Connections
If you are installing connections to the Battery I/O terminal connections and terminal board CB2TB you must install conduit between each device and the UPS cabinet for wiring these options. Refer to Appendix A for the location of the interface points within the UPS cabinet.
To prepare the UPS for wiring to Customer Connec tions:
1. Be sure the UPS system is turned off and all power sources are removed.
(See the operation section of this manual for shutdown instructions.)
2. Remove the sheetmetal shield covering the input terminal area in the
Input/Rectifier cabinet to gain access to the Battery I/O Customer Interface and CB2TB. Refer to Appendix A for location of the shield.
3. Refer to Appendix A of this manual for terminal assignments, and wiring and
termination requirements.
2.2.5 Installing Output/Inverter Customer Connections
If you are installing connections to a Remote Emergency Power Off (EPO) device, Building Alarm or Relay contacts, conduit must be installed between each device and the UPS cabinet. Refer to Appendix A for the locations of the interface points within the UPS cabinet.
To prepare the UPS for wiring to Customer Connec tions:
1. Be sure the UPS system is turned off and all power sources are removed.
(See the operation section of this manual for shutdown instructions.)
2. Refer to Appendix A of this manual for terminal assignments, and wiring and
terminal requirements.
2--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
2.2.6 Prepare for Installing Optional Accessories
If you are installing optional accessories, such as a Remote Monitor Panel (RMP), a Relay Interface Module (RIM), or a Supervisory Contact Module (SCM), you must
install conduit between each device and the UPS cabinet for wiring these options. Refer to Appendix A for the location of the Customer Interface Panel within the UPS cabinet.
To prepare the UPS for wiring to an RMP, RIM, or SCM:
1.
Be sure the UPS system is turned off and all power sources are removed. (See the operation section of this manual for shutdown instructions.)
2. Remove the access plate on top of the UPS Input/Rectifier cabinet to gain
access to the Customer Interface Panel (refer to Appendix A for location of the access plate).
3. Refertochapters6,7,or8asapplicableforinstallationinstructions.
2.3 Multi-Module Installation
To install a multi-module UPS system using a System Bypass Module, perform the procedures in the following paragraphs.
2.3.1 Installing the UPS Cabinet Sections
Refer to paragraph 2.2.1 for procedure.
2.3.2 Installing UPS Internal Power and Control Wiring
NOTE: The cables used in steps 2 through 4 are coiled inside the Input/Rectifier
cabinet and are attached at the factory to the output of the rectifier.
1. Remove the plastic shield covering the inverter input section of the
Output/Inverter cabinet.
2. Route DC Link cables from the rectifier output (Input/Rectifier cabinet) through
cutout in cabinet sides to the inverter input (Output/Inverter cabinet).
3. Connect positive DC Link power wiring to the inverter input. Connect two
cables to each inverter. Refer to Appendix A of this manual for terminal locations and tightening torque.
4. Connect negative DC Link power wiring to the inverter input. Connect two
cables to each inverter. Refer to Appendix A of this manual for terminal locations and tightening torque.
5. Reinstall inverter input section plastic shield.
6. Route ground braid from top of Output/Inverter cabinet to Input/Rectifier
cabinet through cabinet cutouts. Braid is secured at the factory to the Output/Inverter cabinet mounting stud.
7. Connect ground braid to Input/Rectifier cabinet mounting stud and secure.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
2--5
8. Connect the Output/Inverter 15-pin control wiring harness connector to the
Input/Rectifier 15-pin control wiring harness connector. Refer to Appendix A of this manual for connector locations.
9. Remove the plastic shield covering the inverter output section of the
Output/Inverter cabinet.
10. Refer to the applicable SBM Installation and Operation manual referenced in
the Introduction of this manual for SBM input wiring procedures.
11. Reinstall inverter output section plastic shield.
2.3.3 Installing UPS External Power and Control Wiring
1. Remove the sheetmetal shield covering the input terminal area in the
Input/Rectifier cabinet to gain access to the Battery I/O Customer Interface and CB2TB. Refer to Appendix A for location of the shield.
NOTE: Remove Input/Rectifier cabinet conduit landing plate to punch conduit holes.
2. Connect phase A, B, and C power wiring from source to respective rectifier
inputs in the Input/Rectifier cabinet. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information.
3. Connect positive and negative DC power wiring from batteries to the
respective DC inputs in the Input/Rectifier cabinet. Refer to Appendix A of this manual for wiring and termination requirements and wiring access information.
4. Connect control wiring (battery breaker open and close signals and shunt DC
disconnect) between external battery disconnect and the UPS. Refer to Appendix A of this manual for wiring requirements and wiring access information.
5. Refer to the applicable SBM Installation and Operation manual referenced in
the Introduction of this manual for SBM output wiring procedures.
6. After wiring the UPS system to the facility power and critical load, be sure to
ground the system according to local and/or national electrical wiring codes.
7. Install batteries in accordance with all applicable codes and regulations,
including the National Electrical Code (NEC), Article 480.
2.3.4 Installing Input/Rectifier Customer Connections
Refer to paragraph 2.2.4 for procedure.
2.3.5 Installing Output/Inverter Customer Connections
Refer to paragraph 2.2.5 for procedure.
2.3.6 Prepare for Installing Optional Accessories
Refer to paragraph 2.2.6 for procedure.
2--6
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
2.4 Initial Startup
Startup and operational checks should be performed only by authorized service personnel. Contact service in advance (usually a two week notice is required) to reserve a preferred startup date.
2.5 Completing the Installation Checklist
The final step in installing your UPS system is completing the following Installation Checklist. This checklist ensures that you have completely installed all hardware, cables, and other equipment. Completing all items listed on the checklist will ensure a smooth installation. You should make a copy of the Installation Checklist before filling it out, and retain the original.
After your installation is complete, a service representative will be able to verify the operation of your UPS system and commission it to support your critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters. Service personnel may request a copy of the completed Installation Checklist to be sure you have completed all applicable equipment installation.
NOTE: The Installation Checklist MUST be completed prior to starting the UPS
system for the first time.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
2--7
2.5.1 Installation Checklist
-All packing materials and restraints have been removed from each cabinet.
-Each cabinet in the UPS system is placed in its installed location.
-A ground bond is installed between any cabinets that are bolted together.
-All switchboards, conduits, and cables are properly routed to the UPS and auxiliary
cabinets.
-All power cables are properly sized and terminated.
-A ground conductor is properly installed.
-If bypass input neutral connection is used, no other N ---G bonds exist downstream
from the UPS.
-Battery cables and harness are terminated on E4 and E5.
-Internal battery cabinet connections have been completed (bus bars, plugs, etc.).
-Shunt trip signal wiring is connected from UPS to battery breaker(s).
-Air conditioning equipment is installed and operating correctly.
-The area around the installed UPS system is clean and dust-free. (It is recommended
that the UPS be installed on a level, sealed concrete pad or a sealed concrete floor.)
-Adequate workspace exists around the UPS and other cabinets.
-Adequate lighting is provided around all UPS equipment.
-A 120V service outlet is located within 25 feet of the UPS equipment.
-Each Remote Monitor Panel (RMP) is mounted in its installed location. (OPTIONAL)
-The control wiring for each RMP is terminated inside the UPS cabinet. (OPTIONAL)
-The Remote Emergency Power Off (EPO) device is mounted in its installed location
and its wiring terminated inside the UPS cabinet. (OPTIONAL)
-Summary alarms and/or building alarms are wired appropriately. (OPTIONAL)
-A Relay Interface Module (RIM) is mounted in its installed location and its wiring is
terminated inside the UPS cabinet. (OPTIONAL)
-A remote battery disconnect control is mounted in its installed location and its wiring is
terminated inside the UPS and battery cabinet. (OPTIONAL)
-Debris shields covering ventilation grills removed from all cabinets.
-Startup and operational checks performed by authorized service personnel.
2--8
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Notes
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
2--9
This Page Intentionally Left Blank.
2--10
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Installing Batteries
3.1 Important Safety Instructions
This chapter describes installing the UPS batteries.
The installation of batteries should be performed or supervised by personnel knowledgeable of batteries and their associated precautions. Keep unauthorized personnel away from batteries.
Observe these precautions when working on or around batteries:
· Remove watches, rings, or other metal objects.
· Use tools with insulated handles.
· Wear rubber gloves and boots.
· Do not lay tools or metal parts on top of batteries.
· Disconnect the charging source prior to connecting or disconnecting terminals.
3
· Determine if the battery is inadvertently grounded. If it is, remove the source of
the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock is reduced if such grounds are removed during installation and maintenance.
· When replacing batteries, use the same number and type.
· Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
WARNING: Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to theskinandeyes,andmaybetoxic.
A battery can cause electrical shock, burn from high short-circuit current, or fire. Take proper precautions when working with batteries.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
3--1
ATTENTION: Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d’incendie. Suivre les précautions qui s’imposent.
· Pourleremplacement,utiliserlemêmenombreetmodéledesbatteries.
· L’élimination des batteries est règlementée. Consulter les codes locaux à cet
effet.
3.2 Installing Batteries
NOTE: 1. There is no DC disconnect device within the UPS.
2. The DC input to the UPS is protected by internal fuses F30 and F31.
Install batteries in accordance with the battery and battery rack manufacturers instructions.
3--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Installing a Remote Battery Disconnect
4.1 Installation Procedures
The remote battery disconnect is crated separately for shipping. The enclosure is designed to be free-standing, You can install a remote battery disconnect anywhere between the remote DC supply and the UPS, according to national and local codes. Figure 4---1 shows a typical remote battery disconnect enclosure.
The remote battery disconnect is set in accordance with the operation procedures contained in Chapter 12 --- UPS Operating Instructions of this manual. When service personnel are performing maintenance on the UPS or battery string, the disconnect should be set to the OFF position.
4
Operating Handle
ON Position
Figure 4---1. Remote Battery Disconnect Enclosure
Operating Handle
OFF Position
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
4--1
Installation Notes:
You should read and understand these general notes before beginning installation:
S There is no DC disconnect device within the UPS.
S The DC input to the UPS is only protected by internal fuses F30 and F31.
S The UPS DC disconnect trip signal from CB2TB, terminals 9 and 10 (shunt
trip) must be connected to the DC source disconnect device.
S Refer to Appendix A, drawing 164201244---13, for battery disconnect
dimensions.
S Refer to Appendix A, Table A of drawing 164201244---1, for specific ratings
and wiring requirements.
S The material and labor for external wiring requirements is to be supplied by
others.
S The knockout pattern for the disconnect is determined by others at the time
of installation.
S Power cables and control wiring must be installed in separate conduit.
S The ground conductor is to be sized per NEC Article 250 and local electrical
code requirements.
S The maximum current listed is at the minimum DC operating voltage.
S Nominal voltages listed in this chapter are for a lead-acid battery plant rated
per NEC at 2.00 VDC per cell.
S Battery strings must be installed in accordance with all applicable codes
and regulations, including the National Electrical Code (NEC), Article 480.
S The UPS to battery cable should be sized for a total maximum voltage drop
of 1% nominal DC link voltage at maximum current.
S Table 4--- 1 in this chapter details the power cable terminations.
S The remote battery disconnect weighs approximately 60.3 kg (133 lb).
It has an ampere interrupting capacity (AIC) of 100,000 at 500 VDC.
4--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Table 4 ---1. Remote Battery Disconnect Power Terminati ons
Ter mi nal Terminal Function Size of Termination
E4 (+) UPS Battery Input (+)
E 5( --- ) UPS Battery Input (---)
Breaker (+) Battery Disconnect (+)
B r e a k e r ( --- ) Battery Disconnect (---)
Breaker (jumper)
Battery Disconnect (jumper)
8 --- 1 Bolt Mounting Bus Bar
8 --- 1 Bolt Mounting Bus Bar
8 --- 1 Bolt Mounting Bus Bar
See Appendix A, Table D
See Appendix A, Table D
Table 4 --2. Remote Battery Disconnect Circuit Breaker Ratings
UPS Model Circuit Breaker Rating DC Voltage
9315--- 750/500 1600 384
9315--- 750/625 2000 384
9315--- 750/750 2000 384
Tightening
Torq u e
N-M (lb-ft)
76 (56) 1/2
76 (56) 1/2
76 (56) 1/2
Bolt
Size
(In.)
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
4--3
This Page Intentionally Left Blank.
4--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Installing a Remote EPO C ontrol
5.1 Installation Procedures
5
to UPM
to other equipment
Figure 5--- 1. Remote EPO Control
5.2 To i n s t a l l a R e m o t e E P O :
UNINTERRUPTIBLE POWER SYSTEM
EMERGENCY OFF
NOTE: Before installing a Remote EPO, be sure you have prepared the UPM
according to the instructions in Chapter 2.
To install a Remote E PO control:
1. Securely mount the Remote EPO station. Recommended locations include
operator’s consoles or near exit doors. Refer to Appendix A, Drawing 164201244--- 9, for enclosure dimensions and wiring knockouts.
2. Install wiring from the Remote EPO station using ½-in. conduit through the
cable entry panel on the top of the UPS Output/Inverter cabinet. Refer to Appendix A, Drawing 164201244 ---7, for conduit landing area and terminal board location, and Drawing 164201244 ---2 for terminal wiring assignments.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
5--1
3. Connect the Remote EPO wiring as shown in Tables 5--- 1 and 5---2:
(2)
wires(2
)
Table 5--- 1. Remote EPO Wire Terminations
To Cu st ome r In ter fa ce
From Remote
EPO Station(s)
Terminal Board CUSTTB in
UPS Output/Inverter Cabinet
Remarks
T B1 --- 4 C U S T T B --- 9
T B1 --- 5 C U S T T B --- 1 0
Table 5--- 2. Remote EPO
REMOTE
EPO
SWITCH
TWISTED
WIRES (2)
Remote EPO s witch rating is 24 VDC. 1 Amp minimum if supplied by user.
NOTE: This switch must be a dedicated switch not tied into any other circuits.
CUSTTB
Twis ted
wires
1 4 --- 1 8
gauge
9
10
4. If you are installing multiple Remote EPO stations, wire additional stations in
parallel with the first Remote EPO.
5. If required, install ½-in. conduit and wiring from the Remote EPO station to trip
circuitry of upstream protective devices. A normally open contact is provided, asshowninTable5---2. RemoteEPOswitchwiringmustbeinaccordance with UL Class II requirements.
6. Secure the UPS by reversing all steps taken to prepare it for Remote EPO
installation.
5--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Installing a Remote Monitor Panel
6.1 Installation Procedures
As an option, you can install Remote Monitor Panels (RMPs) to monitor the operation of the UPS system from virtually any location within your facility, up to 500 feet from the UPS. You can flush-mount or surface-mount an RMP on a desktop or on a wall, wherever you have a serial interface line. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 6---1 for the number of accessories permitted. Figure 6 ---1 shows an RMP. Drawing 164201244--- 10 in Appendix A shows the enclosure dimensions and knockout patterns.
Table 6---1. Optional Monitoring Accessories
Number and Type of Accessories Permitted
Remote Monitor Panel Relay Interface Module Supervisory Contact Module
2
6
2
2
1 1
1 1
1 1
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
6--1
FLUSH MOUNT
SURFACE MOUNT (FOR HANGING)
WIRES MUST BE TWISTED
Figure 6---1. Remote Monitor Panel (RMP)
6--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
6.2 To i n s t a l l a n R M P :
NOTE: Before installing an RMP, be sure you have prepared the UPS according to
the instructions in paragraph 2.2.6.
1. Securely mount the RMP(s).
2. Install wiring from the RMP using ½-in. conduit through the cable entry
knockout in the top of the UPS Input/Rectifier cabinet (refer to Appendix A, Drawing 164201244---7, for the location of the conduit landing area).
3. In the spare parts kit, locate the RMP adapter cable assembly
(see Figure 6--- 2). Mate the DB---9 connector on the back of the terminal block to the DB ---9 connector (Port 1) on the Customer Interface Panel of the UPS (refer to Drawing 164201244---2 in Appendix A). Use two screws from the spare parts kit to secure the terminal block bracket to the Customer Interface Panel.
Connect to
Po r t 1 (D B --- 9 ) o n
Customer Interface Panel
Figure 6--- 2. Terminal Block Bracket
FUSE
TERMINAL
BLOCK
(TB3)
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
6--3
4. Connect RMP wiring to the terminal block using terminations shown in
1
2TURNSPER
3INCHES
1
2TURNSPER
3INCHES
Ta b le 6 --- 2 .
Table6---2. RMPWireTerminations
From RMP A To U PS Remarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
From RMP B (if used) To U PS Remarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
T B3 --- 1
T B3 --- 2
T B3 --- 3
T B3 --- 4
T B3 --- 5
T B3 --- 6
T B3 --- 7
T B3 --- 8
TWISTED WIRES (4)
--­3INCHES
TWISTED WIRES (4)
--­3INCHES
5. To check the operation of the RMP, ensure that the UPS system is supplying
the load via the inverter or bypass. If the indicators on the RMP show the appropriate status, then it is operating correctly.
If the communications link between the UPS and the RMP is not present, the RMP will self-test (all indicators flash and the horn beeps at one-second intervals). If this occurs, check all harness connectors and the fuse for proper seating. If all connections are secure but the RMP continues to self-test, replacethefusewiththespareincludedinthehardwarekit. Ifthisdoesnot correct the problem, contact your local field service office for verification that the RMP is working correctly.
6. To test the indicator lamps, press the horn silence button and hold it for
3 seconds. All lamps should light, and the horn sound continuously until you release the button.
7. Repeat steps 1, 2, and 4 through 6 for each RMP you are installing.
8. If you are installing an RIM or SCM in addition to an RMP, proceed to Chapter 7
or 8, respectively; otherwise, secure the UPS cabinet by reversing the steps contained in paragraph 2.2.6.
6--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Installing a Relay Interface Module
7.1 Installation Procedures
The optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the UPS system. The module uses an RS422 serial interface line and may support up to eight critical loads. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. Refer to Table 6 ---1 for the number of accessories permitted. Figure 7---1 shows the RIM with its four 15-pin connectors labeled J1 through J4. Refer to Drawing 164201244--- 11 in Appendix A for enclosure dimensions and wiring knockouts.
FLUSH MOUNT
7
J1 J2 J3 J4
15-PIN D-SUB
CONNECTORS
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
SURFACE MOUNT FOR HANGING
Relay Interface Module
CONTINUES
AT UPS
Figure 7 ---1. Relay Interface Module
7--1
7.2 To i n s t a l l a R I M :
NOTE: Before installing a RIM, be sure you have prepared the UPS according to the
instructions in paragraph 2.2.6.
1. Securely mount the RIM.
2. Install wiring from the RIM using ½-in. conduit through the cable entry
knockout in the top of the UPS Input/Rectifier cabinet (refer to Appendix A, Drawing 164201244---7, for the location of the conduit landing area).
3. If not already installed, locate the RMP adapter cable assembly (see Figure
7--- 2) in the spare parts kit. Mate the DB---9 connector on the back of the terminal block to the DB---9 connector (Port 1) on the Customer Interface Panel of the UPS (refer to Drawing 164201244---2 in Appendix A). Use two screws from the spare parts kit to secure the terminal block bracket to the Customer Interface Panel.
Connect to
Po r t 1 (D B --- 9 ) o n
Customer Interface Panel
FUSE
TERMINAL
BLOCK
(TB3)
Figure 7--- 2. Terminal Block Bracket
7--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
4. Connect RIM wiring to the terminal block using the terminations shown in
12TURNSPE
R
12TURNSPE
R
Ta b le 7 --- 1 .
Table7---1. RIMWireTerminations
From RIM A To U PS Remarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
From RIM B (if used) To U PS Remarks
T B 1 --- 4
T B 1 --- 5
T B 1 --- 6
T B 1 --- 7
T B3 --- 1
T B3 --- 2
T B3 --- 3
T B3 --- 4
T B3 --- 5
T B3 --- 6
T B3 --- 7
T B3 --- 8
TWISTED WIRES (4)
1 --- 2 T U R N S P E R
3INCHES
TWISTED WIRES (4)
1 --- 2 T U R N S P E R
3INCHES
5. Contact your local field service office for verification and testing of the RIM
and its connections prior to making connections to J1--- J4.
You can order interface cables separately for connecting to the 15-Pin D-Sub Connectors.
6. Repeatsteps1through5foreachRIMyouareinstalling.
7. If you are installing an RMP or SCM in addition to an RIM, proceed to Chapter
6 or 8, respectively; otherwise, secure the UPS cabinet by reversing the steps contained in paragraph 2.2.6.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
7--3
This Page Intentionally Left Blank.
7--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Installing a Supervisory Contact Module
8.1 Installation Procedures
The optional Supervisory Contact Module (SCM) shown in Figure 8 ---1 provides contacts for monitoring UPS system status. A maximum of two monitoring accessories (RMPs, R IMs, or SCMs) can be installed. Refer to Table 6---1 for the number of accessories permitted. Refer to Appendix A, Drawing 164201244 ---12, for enclosure dimensions, side views, and knockout patterns.
8
TB2
Figure 8---1. Supervisory Contact Module
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
SURFACE MOUNT (FOR HANGING)
WIRES MUST BE TWISTED
8--1
8.2 To install a Supervisory Contact Module:
NOTE: Before installing an SCM, be sure you have prepared the UPS according to
the instructions in paragraph 2.2.6.
1. Securely mount the SCM.
2. Install wiring from the SCM using ½-in. conduit through the cable entry
knockout in the top of the UPS cabinet (refer to Appendix A, Drawing 164201244--- 7, for the location of the conduit landing area).
3. If not already installed, locate the RMP adapter cable assembly (see
Figure 8---2) in the spare parts kit. Mate the DB---9 connector on the back of the terminal block to the DB---9 connector (Port 1) on the Customer Interface Panel of the UPS (refer to Drawing 164201244 ---2 in Appendix A). Use two screws from the spare parts kit to secure the terminal block bracket to the Customer Interface Panel.
Connect to
Po r t 1 (D B --- 9 ) o n
Customer Interface Panel
FUSE
TERMINAL
BLOCK
(TB3)
Figure 8--- 2. Terminal Block Bracket
8--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
4. Connect the SCM wiring to the terminal block using the terminations shown in
1
2TURNSPER
1
2TURNSPER
Ta b le 8 --- 1 .
Table 8 ---1. Supervisory Contact Module Wire Terminations
From SCM A To U PS Remarks
T B 1 --- 4
T B 1 --- 5
T B3 --- 1
T B3 --- 2
TWISTED WIRES (4)
---
T B 1 --- 6
T B 1 --- 7
From SCM B (if used) To UPS Remarks
T B 1 --- 4
T B 1 --- 5
T B3 --- 3
T B3 --- 4
T B3 --- 5
T B3 --- 6
3INCHES
TWISTED WIRES (4)
---
T B 1 --- 6
T B 1 --- 7
T B3 --- 7
T B3 --- 8
3INCHES
5. Contact your local field service office for verification and testing of the SCM
and its connections prior to making connections to terminal strip TB2 shown in F ig u r e 8 --- 3 .
6. Repeatsteps1through5foreachSCMyouareinstalling.
7. If you are installing an RMP or RIM in addition to an SCM, proceed to Chapter
6 or 7, respectively; otherwise, secure the UPS cabinet by reversing the steps contained in paragraph 2.2.6.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
8--3
SYSTEM NORMAL
NO REDUNDANCY
ON GENERATOR
BYPASS NOT AVAILABLE
ON BATTERY
UPS ALARM
ON BYPASS
SHUTDOWN IMMINENT
Note: Supervisory contacts are rated at 2.0 amps at 28 Vdc or 120 Vac and 0.15 amp at 115 Vdc.
Supervisory contacts require external power s upply. Internal 24 Vdc is not capable of supplying contact current.
Figure 8---3. Supervisory Contact Module TB2
8--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Section II
Operation
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
This Page Intentionally Left Blank.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Understanding UPS Operation
9
9.1 Looking Inside a Parallel Capacity/Redundant System
The Powerware 9315 is a continuous duty, solid-state UPS that supports the following equipment: process control, data processing, telecommunications/PBX, research, and medical. The Powerware 9315 maintains power to the critical loads during commercial electrical power brownout, blackout, overvoltage, undervoltage, and out-of-tolerance frequency conditions.
In this manual, the power required by your equipment is called the critical load.The UPS supplies the critical load with conditioned power that is synchronized with your utility power. Figure 9 ---1 shows the main elements of the UPS.
BA TTER Y STRING
BATTERY
BREAKER
CB2
AC INPUT TO
RECTIFIER/
CHARGER
AC INPUT TO
BYPASS
INPUT/RECTIFIER OUTPUT/INVERTER
INPUT
TRANSFORMER
INPUT
BREAKER
CB1
INPUT
FILTER
RECTIFIER/
CHARGER
METERING
DIGITAL
BACKFEED
PROTECTION
BREAKER
FBP
F30 F31
INVERTER
POWER
PROCESSING
STATIC
SWITCH
BYPASS
BREAKER
CB4
UNIT
OUTPUT
TRANSFORMER
OUTPUT
FILTER
OUTPUT
BREAKER
CB3
MODULE BYPASS CABINET
Figure 9 ---1. Main Elements of the UPS System
AC OUTPUT TO CRITICAL
LOAD
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
9--1
The emergency bypass consist of a static switch, a wraparound bypass breaker (CB4) and a backfeed protection breaker (FBP). The backfeed protection breaker is located in series with the static switch. If an SCR shorts, the breaker opens so that the UPS cannot backfeed the bypass source.
For manual transfers to bypass, the static s witch is not used. During the transfer, CB4 is closed and verified and then inverter output breaker CB3 is opened. For transfers of the load from bypass to the UPS, CB3 is closed and verified and then CB4 is opened. The static switch is armed and ready during both types of transfers.
If utility power is interrupted or falls outside the parameters specified in Chapter 18, “Product Specifications,” the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or until the utility power returns. For extended power outages, the backup battery supply allows you to either transfer to an alternative power system (such as a generator) or shut down your critical load in an orderly manner.
9.2 Normal, Battery, and Bypass Modes
The UPS system functions automatically to supply AC electrical power to the critical load. There are three standard operation modes:
· In Normal mode, the critical load is supplied by the inverter, which derives its power
from rectified utility AC power. In this mode, the rectifier also provides charging current for the battery.
· In Battery mode, the battery cabinet provides DC power, which maintains inverter
operation. The battery supports the critical load.
· In Bypass mode, the critical load is directly supported by utility power.
The UPS continually monitors itself and the incoming utility power, and automatically switches between these modes as required, with no operator intervention. The sophisticated detection and switching logic inside the UPS ensures that operating mode changes are automatic and transparent to the critical load. The UPS switches operating modes in response to these system events:
· A command is an intervention that is externally initiated by an operator or by some site
action. A command causes the UPS to switch operating modes; it usually does not require any further action by you.
· A notice is a minor system event that may or may not require your attention.
· An alarm is a system event that requires immediate operator intervention.
System events, alarm horns, and indicator lights are described in Chapter 14, “Responding to System Events.”
The following descriptions provide the differences in UPS operating modes.
9--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
9.3 Normal Mode
In Normal mode, utility AC power is supplied to the rectifier. The rectifier supplies DC power to the inverter, which then supplies the critical load with AC power. The rectifier also provides charging power to the battery. The battery charge condition is monitored by the UPS and reported by a status indicator on the Control Panel. The message “System Normal” appears in the status area of the Control Panel LCD screen.
Figure 9--- 2 shows the path of electrical power through the UPS system when the UPS is operating in Normal mode.
CB4
(open)
BYPASS
STATIC SWITCH
Rectifier
Input
Bypass
Input
(closed)
RECTIFIER INVERTER
FBP
CB1
(closed)
Path of electrical power
INPUT
TRANSFORMER
LINK
CB2
(closed)
BATTERY
DC
OUTPUT
TRANSFORMER
CB3
(closed)
Output
Figure 9--- 2. Path of Current Through the UPS in Normal Mode
If the utility AC power is interrupted or is out of s pecification, the UPS automatically switches to Battery mode to support the critical load with no interruption. When utility power returns, the UPS returns to Normal mode.
If the UPS becomes overloaded or unavailable, the UPS switches to Bypass mode. The UPS automatically returns to Normal mode when the error condition is cleared and system operation is restored within specified limits.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
9--3
9.4 Bypass Mode
The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to the load directly.
Figure 9---3 shows the path of electrical power through the UPS system when operating in Bypass mode.
CAUTION: The critical load is not protected while the UPS is in Bypass mode.
Bypass
Input
Rectifier
Input
CB1
(open)
INPUT
TRANSFORMER
CB4
(closed)
BYPASS
STATIC SWITCH
FBP
(closed)
RECTIFIER INVERTER
DC
LINK
OUTPUT
TRANSFORMER
CB3
(open)
Output
9--4
CB2
(open)
Path of electrical power
BATTERY
Figure 9---3. Path of Current Through the UPS in Bypass Mode
TheUPScanbetransferedfromNormalmodetoBypassmodemanually. However, the UPS switches automatically to Bypass mode whenever the inverter can no longer supply the critical load. Initially, the static switch fires and conducts power from breaker FBP to the load. When breaker CB4 closes, the static switch stops conducting and breaker FBP opens. If the UPS transfers to Bypass mode from Normal mode due to any reason other than operator intervention, the UPS automatically attempts to transfer back to Normal mode (up to three times within a 10-minute period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to transfer.
Bypass mode is a normal operating mode, and not an alarm condition. However, if the UPS is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition is recorded.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
9.5 Battery Mode
The UPS transfers to Battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the inverter converts to AC power. When the UPS switches to Battery mode, the alarm indications depend on the cause and condition of the battery charge. The length of time the system can operate in Battery mode depends on loading and the battery supply capacity.
Figure 9---4 shows the path of electrical power through the UPS system when operating in Battery mode.
Bypass
Input
Rectifier
Input
CB1
(closed)
INPUT
TRANSFORMER
CB4
(open)
BYPASS
STATIC SWITCH
FBP
(open)
RECTIFIER INVERTER
DC
LINK
OUTPUT
TRANSFORMER
CB3
(closed)
Output
CB2
(closed)
Path of electrical power
BATTERY
Figure 9---4. Path of Current Through the UPS in Battery Mode
When the discharging battery voltage reaches the lower limit of UPS operation capability, the critical load transfers to Bypass mode if it is available. If Bypass input is not available, a “Shutdown Imminent” warning occurs. The warning time before critical load loss occurs is approximately 2 minutes, depending on battery capacity and the amount of loading.
If incoming power returns to within specified parameters, the UPS automatically returns to Normal mode and alarm indications clear. However, the process of returning to Normal mode is not instantaneous. The rectifier gradually draws increasing power from the incoming utility until Normal mode is achieved.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
9--5
This Page Intentionally Left Blank.
9--6
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Operational Controls and Features
10.1 General
The UPS system should function automatically and require very little attention during normal operation. The controls and indicators identified in this section are used during startup, to monitor normal operation and during abnormal events.
Figure 10---1 identifies and shows the location of the controls and indicators on the UPS. The descriptions provide a brief overview of the UPS controls, and standard and optional features.
NOTE: Read the Operation section of this manual and have thorough knowledge
of UPS operation before attempting to operate any of the UPS controls or optional components.
10.2 UPS Standard Features
The UPS has many standard features that provide cost-effective and consistently reliable power protection:
10
10.2.1 Control Panel
The Control Panel on the front of the UPS contains an LCD screen to display the current status of the U PS system. You can view a statistical history and log of system events and display a real-time graphic representation of power flowing through the system components. Backlit status indicators show the operating mode of the UPS and alert you to system events. The BATTERY switch controls the application of battery power to the UPS. The MODE switch, also located on this panel, is used to start and stop the system and transfer the load between normal UPS operation and bypass operation. The EMERGENCY UPM OFF pushbutton is located at the top of the control panel, and the PUSH IN TO RESET button for the EMERGENCY UPM OFF is located between the BATTERY and MODE switches. The Control Panel is described in Chapter 11, “Using the Control Panel”.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
10--1
CONTROL PANEL
INPUT BREAKER CB1 (OPTIONAL)
OUTPUT BREAKER CB3 (OPTIONAL)
BYPASS BREAKER CB4
BACKFEED PROTECTION BREAKER
INPUT/RECTIFIER OUTPUT/INVERTER MBC
Figure 10--- 1. UPS Controls and Indicators
10--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
10.2.2 UPS Circuit Breakers
The UPS can contain as many as four circuit breakers, the UPM Input Breaker (CB1), the UPS Output Breaker (CB3), the System Bypass Breaker (CB4), and the Backfeed Protection Breaker (FBP).
CB1 controls the input to the UPS rectifier, while CB3 controls the output of the UPS inverter. CB1 is optional and may be either motor operated or manual controlled.
CB4 and the FBP are used in single module applications and are contained in the Module Bypass section of the UPS. CB4 is used as the bypass supply in the event the output of the UPS is not available and to supply the critical load during maintenance. The FBP is used to prevent power feedback to the UPS input supply when the UPS is operating in the battery mode. These breakers are electrically controlled by the UPS and are automatic in operation.
Multi-module systems replace the Module Bypass section of the UPS with a System Bypass Module (SBM). Refer to the applicable SBM Installation and Operation manual referenced in the Introduction of this manual for SBM circuit Breakers.
In addition, a remote mounted external battery disconnect is used to connect the battery string to the UPS. This disconnect is manually operated.
10.2.3 EMERGENCY UPM OFF
An EMERGENCY UPM OFF pushbutton is provided for situations where you must instantaneously control the UPS output. The pushbutton is located on the front of the UPS for quick access and is covered with a clear plastic shield to prevent inadvertent operation. The shield must be raised before pressing the pushbutton. The EMERGENCY UPM OFF pushbutton is described in detail in Chapter 12, “UPS Operating Instructions.”
10.2.4 Customer Interface
Computer Interface
Two serial communications ports are standard on all units, and are electrically isolated from the UPS. You can use these ports to link the UPS to the features described in Chapter 15, Serial Communicationsand Chapter 16, “Remote Notification.”
Building Alarm Monitoring
You can connect your facility’s alarm system contacts to four inputs in the UPS. The UPS uses these inputs to monitor your building alarms in addition to the UPS status. This feature is described further in Chapter 13, “Using Features and Options.”
Summary Alarm Contacts
Alarm contacts a re provided for connection to equipment at your facility, such as a light, an audible alarm, or a computer terminal. The equipment you connect to these contacts alerts you to an UPS alarm. This feature is described further in Chapter 13, “Using Features and Options.”
10.2.5 Automatic Battery Charge Current Limit
A preset limit restricts battery charging current to protect batteries from damage due to high current charging. Charging at high currents can overheat and damage batteries.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
10--3
10.2.6 Customer Convenience Outlet
An uninterruptible 120VAC, 0.2 amp, fuse-protected convenience outlet is provided to supply power to the optional modem. It is located on the Customer Interface Panel.
10.2.7 Installation Features
Power wiring can be routed through the top of each cabinet. External sensing and monitoring control wire must be installed in accordance with Class 2 wiring methods. Class 2 wiring can be routed through the top of each cabinet.
10.3 Options and Accessories
Contact your sales representative for information about any of these available options:
10.3.1 5% Input Filter
Your unit may be equipped with an input filter.Aninput filter yields power factor correction that allows you to save on your initial installation and operating costs. The filter also reduces input harmonic current distortion and minimizes upstream interference that can damage sensitive hardware components.
10.3.2 Battery
You can enhance the protection provided by your UPS with one or more backup battery supplies equipped with sealed lead-acid, maintenance-free batteries.
10.3.3 External Fused Battery Disconnect
An optional DC disconnect, enclosed in a freestanding cabinet, provides an automatic or manual means of disconnecting batteries that are located remotely from the UPS. This option is described further in Chapter 13, “Using Features and Options.”
10.3.4 Upgrade Capability
The UPS is available in various output power ratings in both 50 and 60 Hz models. If your power requirements increase, you can upgrade your UPS system to provide more output power with a minimum impact on your facility.
10.3.5 Remote Monitor Panel
An optional Remote Monitor Panel (RMP) contains backlit status indicators and a local horn, allowing you to monitor the operational status and alarm condition of the UPS from virtually any location within your facility. You can install multiple RMPs at remote locations to increase your monitoring capabilities. This option is described further in Chapter 13, “Using Features and Options.”
10--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
10.3.6 Relay Interface Module
An optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the UPS. The module uses a serial interface line and may support up to eight critical loads. This option is described further in Chapter 13, “Using Features and Options.”
10.3.7 Modem
An optional modem is available for use with the Remote Notification feature described in Chapter 16, “Remote Notification”. Refer to the manual supplied with the modem for modem operating instructions.
10.4 Safety Considerations
The UPS enclosure is designed for industrial or computer room applications, and contain safety shields. However, the system is sophisticated and should be handled with appropriate care, following these guidelines:
· Keep surroundings clean and free from excess moisture.
· Do not operate the system close to gas or electric heat sources.
· The system is not intended for outdoor use.
· The system operating environment should be maintained within the
parameters stated in this manual.
· Keep t he sy stem doors closed to ensure proper cooling airflow and to
protect personnel from dangerous voltages inside the unit.
· The system contains its own power source. Lethal voltages are present
even when the system is disconnected from utility power.
WARNING: Only AUTHORIZED SERVICE PERSONNEL should perform service or maintenance on the UPS.
If service or routine maintenance is required:
· Ensure all power is disconnected before performing installation or service.
· Ensure the area around the UPS is clean and uncluttered.
· Battery cabinet maintenance or battery replacement should be performed
only by authorized service personnel.
· Observe all DANGER, CAUTION, and WARNING notices affixed to the
inside and outside of the equipment.
· Always conform to the more detailed safety precautions described in
“Important Safety Instructions” section of Chapter 17.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
10--5
10.5 Symbols, Controls, and Indicators
These symbols may appear on your UPS system or on labels inside the UPS. They are accepted by most international safety agents. Everyone in your organization who works with your system should understand the meaning of these symbols:
ON
The principal power switch is in the “On” position.
OFF
The principal power switch is in the “Off” position.
PHASE
The word “phase.”
CAUTION: REFER TO MANUAL
Stop and refer to the Operator’s Manual for more information.
RISK OF ELECTRIC SHOCK
There is a risk of electric shock present, and you should observe associated warnings. The UPS contains high voltages.
10--6
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Using the Control Panel
11.1 Description
This chapter describes the UPS Control Panel, including controls and indicators, and how to monitor UPS operation. The Control Panel is a black square area on the front of the SBM (see Figure 11---1).
1
2
3
4
11
5
6
7
Figure 11--- 1. UPS Control Panel
The Control Panel contains the red EMERGENCY UPM OFF pushbutton switch (1),
flat Liquid Crystal Display (LCD) screen (2), horizontal row of pushbutton switches (3), a vertical column of backlit status indicators (4), the MODE key switch (5), the PUSH IN TO RESET pushbutton switch (6), and the BATTERY switch (7). The following sections describe using the UPS Control Panel to monitor the UPS. Refer to Chapter 12 --- UPS Operating Instructions for use of the operational controls.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11- -1
11.2 Using the LCD Screen
The LCD screen at the top of the Control Panel provides an operator interface with the UPS system. Figure 11 ---2 identifies the display fields discussed in the following sections.
Uninterruptible Power System
System Normal
A
ALARM: NONE NOTICES: NONE
4 MAY 1999 09:25:42
F
B
C D
E
Battery Minutes
Meters
System
Load Amps Versions
Meters
Input Output
48.6
Events Statistics Graphics Setup
VAB
VBC VCA
nnn
nnn nnn
IA IB IC
nnn
KVA nnn
VAB nnn
KW
nnn
Bypass Battery
VBC VCA nnn nnn
nnnnnn
PF
0.nn
FREQ nn.n
VAB
VBC VCA
nnn
nnn nnn
IA IB IC
nnn nnnnnn
KVA nnnKWnnnPF0.nn
V
nnn
FREQ nn.n
IN
nnn
I
+
nn
Figure 11--- 2. Parts of the LCD Screen
A The UPS status area contains three lines that display the current state of the UPS. The first line
shows the present operational mode of the UPS. The second line shows the highest level of the current active alarms, and the third line shows a ny notices the UPS has posted. (For more information about alarms and notices, refer to Chapter 14, “Responding to System Events.”)
G
B The battery charge box shows the minutes of battery capacity available.
C The menu box shows the currently selected menu and lists the options available on t hat menu.
The title at the top of the menu box is also shown below on the menu bar (E). Press the and pushbuttons to scroll up and down through the options in the menu box.
D The currently selected option is highlighted in the menu box. Press t he and pushbuttons
to move the highlight up or down. The data in the information area (G) changes accordingly.
E The menu bar lists the titles of the menus. The title of the menu currently displayed in the
menu box is highlighted. When you press the left or right, the data in the menu box and the information area change accordingly.
11- -2
and pushbuttons to move the highlight
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
F The time stamp shows the current date and time. This date and time are recorded in the Event
Log when a notice or alarm is activated.
G The information area contains data about UPS status and operations. Select a menu option to
display statistics or graphics.
You can use the LCD screen and the pushbuttons beneath it to:
· Monitor UPS operation
· Look at a log of UPS events (alarms, notices, and commands).
11.3 Using the Pushbuttons
The pushbuttons below the LCD screen are labeled with arrows indicating their functions:
· Press the and pushbuttons to move through the options in a menu, or to
scroll through the list of alarms and notices in the event log.
· Press the and pushbuttons to move through the menu titles on the
menu bar. Press them simultaneously to silence the horn, or to test the lamps behind the status indicators.
· Press the pushbutton to toggle the use of the and pushbuttons
between the menu box and the information area.
11.4 Adjusting the Contrast
· Use the pushbuttons to adjust the contrast on the LCD screen. Hold down the
pushbutton, then press the pushbutton to increase the contrast or the
pushbutton to decrease the contrast.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11- -3
11.5 Reading the Status Indicators
The six symbols on the left side of the monitor panel are status indicators.Theyare backlit by colored light emitting diode (LED) lamps, and they work in conjunction with the alarm horn to let you know the operating status of the UPS.
This green symbol is lit when the UPS is operating in
NORMAL
Battery
Bypass
Notice
Normal mode. The power processing unit (PPU) is supplying power to the critical load.
This yellow symbol is lit when the UPS is operating in Battery mode. Because Battery mode is a normal condition of the UPS, the Normal indicator also remains lit.
This yellow symbol is lit when the UPS is operating in Bypass mode. The critical load is supported by the bypass source. The Normal indicator is not lit when the system is in Bypass mode.
This yellow symbol is lit when the system needs attention. The LCD screen shows all active notices. Some notices may be accompanied by an audible horn. To silence the horn, press the a nd the pushbuttons simultaneously. The Notice indicator may be lit along with other indicators.
This red symbol is lit when a situation requires immediate attention. The LCD screen shows the highest priority active
Alarm
Standby
alarms. All alarms are accompanied by an audible horn. To silence the horn, press the and the pushbuttons simultaneously. The Alarm indicator may be lit along with other indicators.
This yellow symbol is lit when electricity is present in the PPU of the UPS and the Normal indicator is not lit. During normal startup, this indicator illuminates until the the UPS transfers to Normal mode, at which point the Normal indicator is lit. During normal shutdown, the Standby indicator is lit until all energy in the UPS is dissipated and shutdown is complete.
For more information about audible horns, refer to the “System Event Horns” section of Chapter 14.
To test the LED lamps behind the status indicators, press the
and pushbuttons simultaneously for 3 seconds. All the indicators should light while you hold down these pushbuttons. If any indicator does not light, its LED may need to be replaced. Contact Customer Service if you have a problem with the indicator lamps.
11- -4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11.6 Using the Menu Options
The UPS menus allow you to display data in the information area to help you monitor and control UPS operation. The following menus and options are available:
· Meters Displays performance meters for the system or critical load.
· Events Displays the list of Active System Events and a historical log of
system events.
· Statistics Displays statistical information about UPS operations for the
battery, load, or line.
· Graphics Displays a real-time graphic representation of the flow of current
through the internal UPS components.
· Setup Allows you to configure the UPS communications port and set
the date and time for the time stamp.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11- -5
11.6.1 System Meters Screen
Figure 11---3 shows the LCD screen as it appears when you first start the UPS. The Meters menu is displayed in the menu box, with the System option highlighted. In the information area, the system meters show their current readings.
Uninterruptible Power System
System Normal
ALARM: NONE NOTICES: NONE
4 MAY 1999 09:25:42
Battery
Minutes
Meters
System
Load Amps Versions
Meters
48.5
Events Statistics Graphics Setup
VAB nnn
Input Output
VBC VCA nnn nnn
IA IB IC
nnn
KVA nnn
VAB nnn
KW
nnn
Bypass Battery
VBC VCA nnn nnn
nnnnnn
PF
0.nn
FREQ nn.n
VAB nnn
IA IB IC
nnn nnnnnn
VBC VCA nnn nnn
KVA nnnKWnnnPF0.nn
V
nnn
I
+
nn
FREQ nn.n
IN
nnn
Figure 11---3. System Meters Screen
The Input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the KVA, KW, and power factor measurements. The output area shows the same information for the power being output by the UPS.
TheBypassareashowsthephase-to-phasevoltageofthebypasssource. The Battery area displays the DC voltage (V) and the DC current (I).
11- -6
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11.6.2 Load Amp Meters Screen
Select Load Amps from the Meters menu to see a real-time bar graph of the output current of the UPS. The graph shows the current for each phase.
Figure 11---4 shows the Load Amps Meters screen.
Uninterruptible Power System
System Normal
ALARM: NONE NOTICES: NONE
4 MAY 1999 09:25:42
Battery Minutes
48.5
Meters
System
Load Amps
Versions
Events Statistics Graphics SetupMeters
Output Current
125%
100%
75%
50%
25%
0%
Phase A Phase B Phase C
Figure 11---4. Load Amps Meters Screen
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11- -7
11.6.3 Software Versions Screen
Select Versions from the Meters menu to see the software versions installed on the UPS.
Figure 11---5 shows the Versions screen.
Uninterruptible Power System
System Normal
ALARM: NONE NOTICES: NONE
4 MAY 1999 09:25:42
Battery Minutes
48.5
Meters
History
System Load Amps Versions
EventsMeters
Software Versions
Version
Monitor
Rectifier
Inverter
Statistics Graphics Setup
01.17
*****
*****
Part Number
143650369
143650347
143650348
Figure 11--- 5. Versions Screen
11- -8
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11.6.4 System History Screen
Select History from the Events menu to display the Event History Log. The Event History Log lists up to 400 system events in chronological order, with the most recent event listed last. The end of the log (the most recent events) appears when you display the screen, and you must scroll upward to view older event listings.
Figure 11---6 shows the Event History Log screen.
Uninterruptible Power System
System Normal
ALARM: NONE NOTICES: NONE
4 MAY 1999 09:25:42
Battery
Minutes
48.5
Events
History
Active
EventsMeters
Date / Time May
03
16:41:19.3
03
16:41:20.1
03
16:41:22.4
03
16:41:25.5
03
16:41:26.8
03
16:41:27.8
03
16:41:30.4
16:41:29.1
03
Statistics Graphics Setup
Event History Log
Event Description
COMMAND: Keyswitch On
STATUS: Auto Mode
COMMAND: Rectifier Commanded On
STATUS: Inverter On
STATUS: Rectifier On
STATUS: Output Breaker (CB3) Closed
STATUS: Bypass Breaker (CB4) Open
STATUS: Inverter Normal
Figure 11---6. Event History Log Screen
A small return arrow ( ) appears in the upper right corner of the information area of the Event History Log screen. This arrow is a reminder that you can press the
pushbutton on the Monitor Panel to toggle the scroll bar between the menu box and the information area. When the scroll bar is in the information area, the return arrow is in the menu box. When the scroll bar is in the menu box, the return arrow is in the information area.
When the scroll bar is in the information area, you can press the pushbuttons to scroll through the Event History log.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
and
11- -9
11.6.5 Active System Events Screen
Select Active from the Events menu to display a listing of all system events that are currently active. The most recent system event is listed first. As events clear, they areremovedfromtheActiveSystemEventslisting.
Figure11---7showstheActiveSystemEventsscreen.
Uninterruptible Power System
System Normal
ALARM: ON BATTERY SHUTDOWN IMMINENT
NOTICES: NONE
4 MAY 1999 09:25:42
Battery Minutes
48.5
Events
History
Active
Events Statistics Graphics SetupMeters
Active System Events
NOTICE: Input power unavailable NOTICE: Bypass Not Available ALARM: Shutdown Imminent
Figure 11---7. Active System Events Screen
11- -10
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11.6.6 Unit Statistics Screen
Select Unit from the Statistics menu to display a listing of statistics about UPS operation.
Figure 11---8 shows the Unit Statistics screen.
Uninterruptible Power System
UPS System Normal
ALARM: NONE NOTICES: NONE
4 MAY 1999 09:25:42
Battery Minutes
48.5
Statistics
Unit
Events Statistics Graphics SetupMeters
Number of Incidents:
On Battery < 1 Min. On Battery 1-4 Min.
On Battery > 4 Min. Full Batt. Discharge Building Alarm 1 Building Alarm 2 Building Alarm 3 Building Alarm 4 Building Alarm 5 Building Alarm 6
Start Date: 04 MAY 1999
Month Total DAYS HR MNTime On:
0
0 1 0 0 2 2 3 2 3 3
UPS
0
Bypass
0
Battery
0
Generator
11
Logic 9 8 5
Availability 8
UPS 9
Bypass
0035 20 59 0000 00 30 0000 00 02 0000 00 00 0035 21 30
0.99
0.81
Figure 11--- 8. Unit Statistics Screen
The left column shows the number of UPS incidents for the current month and since the start date shown at the top of the screen. The top right column shows the time that the UPS was on bypass, battery, or generator, and the amount of time the U PS logic has been functioning since the start date. The lower right column shows the percent of availability of the UPS and the bypass source.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11- -11
11.6.7 Mimic Screen
Select Mimic from the Graphics menu to display a real-time graphical representation of the flow of current through the UPS.
Figure 11---9 shows the Mimic screen.
Uninterruptible Power System
UPS System Normal Alarm: None Notice: None
Battery
Percent
100%
Graphics
Mimic
CB1 CB3
Rectifier Inverter
Bypass
CB2
4 MAY 1999 09:25:42
Battery
Events Statistics Graphics SetupMeters
Figure 11--- 9. Mimic Screen
The Mimic screen shows the internal components of the UPS cabinet. The flow of current through the components is highlighted.
11- -12
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11.6.8 Time Setup Screen
Select Time from the Setup menu to display the Time Setup screen. The Time Setup screen allows you to set the internal time stamp of the UPS. The time stamp is used for logging events in the Event History Log. Figure 11---10 shows the Time Setup screen.
Uninterruptible Power System
UPS System Normal ALARM: NONE NOTICES: NONE
Battery Minutes
48.5
Setup
Port 1
Port 2
Time
Language
Set Time & Date
DAY DT MON 07
MON APRYR99
HR:MN 15:06
4 MAY 1999 09:25:42
SAVE
YES
EventsMeters
Statistics Graphics Setup
Figure 11--- 10. Time Setup Screen
The small return arrow ( ) appears in the upper right corner of the Time Setup screen. This arrow is a reminder that you can press the Monitor Panel to toggle the pushbuttons between the menu box and the information area. When the scroll bar is in the information area, the return arrow is in the menu box. When the scroll bar is in the menu box, the return arrow is in the information area.
When the scroll bar appears in the information area, you can use the pushbuttons to change the time stamp settings. To change a setting in the time stamp, press the the setting (make it a higher value), press the setting (make it a lower value), press the
and pushbuttons to highlight the setting you want to change. To increase
pushbutton. To decrease the
pushbutton. If you want to save the
settings upon exit from this screen, be sure the SAVE field is set to YES.
pushbutton on the
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
11- -13
11.6.9 Port Setup Screen
Select Port 1 or Port 2 from the Setup menu to display one of the Port Setup screens. The Port Setup screens allow you to specify settings for the two serial communication ports on the UPS. Figure 11---11 shows the Setup Serial Port 1 screen.
Uninterruptible Power System
UPS System Normal Alarm: None
Notice: None
Battery Minutes
48.5
Setup
Port 1
Port 2 Time
Language
MODE
TERMINAL
Setup Serial Port 1
RATE
DATA/STOP
9600
81
4 MAY 1999 09:25:42
HANDSHAKING XON / XOFF
SAVE NO
EventsMeters
Statistics Graphics Setup
Figure 11--- 11. Port Setup Screen
The small return arrow ( ) appears in the upper right corner of the Port Setup screen. This arrow is a reminder that you can press the Monitor Panel to toggle the pushbuttons between the menu box and the information area. When the scroll bar is in the information area, the return arrow is in the menu box. When the scroll bar is in the menu box, the return arrow is in the information area.
When the scroll bar appears in the information area, you can use the pushbuttons to change the port configur ation. To chang e a setting, press the to move the highlight to the setting you want to change. To scroll through the available options for that setting, press the
or pushbutton. To save the
settings upon exit from this screen, be sure the SAVE field is set to YES.
The setup screens for Port 1 and Port 2 are identical. For detailed information about configuring the serial ports, refer to Chapter 15, “Serial Communications.”
pushbutton on the
and pushbuttons
11- -14
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
UPS Operating Instructions
12.1 Operation
The following procedures provide instructions for operating the UPS system. Refer to Chapters 10 and 11 of this manual for a description of the UPS controls and monitor panel functions.
NOTE: 1. Before starting the UPS ensure all installation tasks are complete and a
preliminary startup has been performed by authorized service personnel. The preliminary startup verifies all electrical interconnections to ensure the installation was successful and the UPS operates properly.
2. The following procedures are applicable for systems with the optional internally installed rectifier input breaker CB1 and inverter output breaker CB3.
3. For operation of the System Bypass Module (SBM) in a Multi-module system, refer to the applicable SBM Installation and Operation manual referenced in the “Introduction” of this manual.
12.2 Starting the UPS
To start the UPS system, perform the following procedure:
NOTE: This procedure assumes Automode is enabled.
1. Ensure the UPS circuit breakers are set as follows:
12
UPS Input Breaker (CB1) UPS Battery Breaker or
Battery Disconnect (CB2) UPS Output Breaker (CB3) OPEN UPS Bypass Breaker (CB4) OPEN Backfeed Protection Breaker (FBP) OPEN
NOTE: When feeder power is applied in steps 3 and 5, UPS circuit breakers CB1,
CB2, CB3, CB4 and FBP will charge, if not already charged.
2. Ensure the Emergency UPM Off PUSH TO RESET pushbutton is pressed in.
3. Close the UPS input feeder circuit breaker.
4. Observe UPS monitor screen becoming active as an indication of logic power.
5. Close UPS Bypass input feeder circuit breaker. Breakers CB4 and FBP will
close as soon as charged.
The critical load is immediately supplied by the bypass source, in Bypass mode, until the inverter turns on and the UPS transfers to Normal mode. The status indicator on theUPSControlPanelindicatestheUPSisinBypassmode.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
OPEN OPEN
12--1
6. On the UPS, set BATTERY switch to ENABLE.
7. If system is equipped with motor operated breaker CB1, proceed to step 8;
otherwise, proceed to step 11.
8. On the UPS, turn the MODE key switch to NORMAL for one second.
NOTE:
If system is equipped with Inrush Protection Option, the inrush contactor will close before CB1 closes.
9. Confirm UPS breaker CB1 has closed, by viewing breaker position on LCD
Mimic screen.
The rectifier and the input/rectifier cooling blowers turn on.
10. Proceed to step 13.
11. Close UPS breaker CB1.
The input/rectifier cooling blowers turn on.
12. On the UPS, turn the MODE key switch to NORMAL for one second.
The rectifier turns on.
13. If system is equipped with motor operated breaker CB2, proceed to step 14;
otherwise, proceed to step 16.
14. Confirm UPS Battery Breaker CB2 has closed by viewing breaker position on
LCD Mimic screen.
The inverter and output/inverter cooling blowers turn on. When the inverter reaches full voltage, UPS breaker CB3 closes and breaker CB4 opens supplying power to the critical load. It t akes less than 1 minute for the UPS to achieve Normal mode. If UPS is not in Automode, turn the MODE key switch to NORMAL for one second to transfer UPS to Normal mode.
12--2
15. Proceed to step 18.
16. When UPS Battery Disconnected alarm and notification is received, close UPS
Battery Disconnect CB2.
17. On the UPS, turn the MODE key switch to NORMAL for one second.
The inverter and output/inverter cooling blowers turn on. When the inverter reaches full voltage, UPS breaker CB3 closes and breaker CB4 opens supplying power to the critical load. It t akes less than 1 minute for the UPS to achieve Normal mode. If UPS is not in Automode, turn the MODE key switch to NORMAL for one second to transfer UPS to Normal mode.
18. UPS is now operating in Normal mode.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
12.3 Starting the UPS in Bypass Mode
If the Inverter output of the UPS is not available and the critical load needs to be energized, perform the following procedure:
1. Ensure the UPS circuit breakers are set as follows:
UPS Input Breaker (CB1) UPS Battery Breaker or
Battery Disconnect (CB2) UPS Output Breaker (CB3) OPEN UPS Bypass Breaker (CB4) OPEN Backfeed Protection Breaker (FBP) OPEN
2. Close UPS Bypass input feeder circuit breaker. Breakers CB4 and FBP will
close as soon as charged. If breakers do not close, turn the MODE key switch to BYPAS S for one second.
The critical load is immediately supplied by the bypass source, in Bypass mode, until the inverter turns on and the UPS transfers to Normal mode. The status indicator on theUPSControlPanelindicatestheUPSisinBypassmode.
3. UPS is now operating in Bypass mode. No backup is available.
12.4 Transfer to Bypass Mode
NOTE: In the following step, holding the MODE switch in the BYPASS position for
three seconds will transfer the load to Bypass and shutdown the UPS.
1. On UPS, turn the MODE key switch to BYPASS for one second.
2. Confirm UPS breaker CB4 closes and UPS breaker CB3 opens.
The UPS switches to Bypass mode. If the bypass source is not available, the power processor remains on and an alarm sounds.
OPEN OPEN
3. On UPS monitor screen, verify “On Bypass” message appears and the
BYPAS S mode indicator illuminates on the Control Panel
now on bypass and UPS power processor remains on.
WARNING: Power is present inside Input/Rectifier and Output/Inverter cabinet sections
12.5 Transfer to Normal Mode
1. On UPS, turn the MODE key switch to NORMAL for one second.
2. Confirm UPS breaker CB3 closes and UPS breaker CB4 opens.
The UPS switches to Normal mode. If the power processor unit is not available, the system remains on bypass and an alarm sounds.
3. On UPS monitor screen, verify “Normal” message appears and the NORMAL
mode indicator illuminates on the Control Panel mode.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
. System is
.
. System is now in normal
12--3
12.6 Transfer to Bypass with UPS Shutdown
1. On UPS, turn the MODE key switch to BYPASS for one second.
2. Confirm UPS breaker CB4 closes and UPS breaker CB3 opens.
The UPS switches to Bypass mode. If the bypass source is not available, the power processor unit remains on and an alarm sounds.
3. On UPS monitor screen, verify “On Bypass” message appears and the Bypass
mode indicator illuminates on the Control Panel
. System is now on bypass.
4. On UPS, turn the MODE key switch to BYPASS for one second.
5. Observe UPS breaker CB1 and Battery Disconnect CB2 open.
The bypass source supplies the critical load, the power processor unit de-energizes and cooling blowers shutdown.
WARNING: Power is present at UPS CB1, until
breaker is opened.
the upstream UPS input feeder circuit
12.7 UPS and Critical Load Shutdown
To perform maintenance or service on the critical load, shut down power to the load by performing the following procedure:
1. Transfer critical load to bypass by performing procedure in paragraph 12.4.
2. Turn off all equipment that is being powered by the UPS.
3. Press the EMERGENCY UPM OFF pushbutton on the Control Panel.
WARNING: Power is present at the UPS CB1 input, until
circuit breaker is opened.
the upstream UPS input feeder
4. Open the UPS input feeder circuit breaker.
12.8 Using the UPS EMERGENCY UPM OFF Pushbutton
An UPS Emergency UPM Off is initiated by the covered, red EMERGENCY UPM OFF pushbutton on the UPS Control Panel. This pushbutton is protected by a
clear plastic shield to prevent accidental activation. In an emergency, you can press this pushbutton to instantaneously control the UPS output. The UPS EMERGENCY UPM OFF pushbutton functions differently, depending on the Emergency Power Off (EPO) option specified when ordered. The options available are as follows:
12--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
S Power to the critical load is de-energized and the UPS powered
down. UPS breakers CB1, CB3, and FBP, and Battery Disconnect CB2 trip and the UPS is cut off from utility power.
S The critical load is transferred to bypass and the UPS powered
down. U PS breakers CB1 and CB3, and Battery Disconnect CB2 trip and the UPS is cut off from utility power.
The UPS (including Bypass) remains locked off until you reset the EMERGENCY UPM OFF pushbutton.
To restart the UPS after pressing the EMERGENCY UPM OFF pushbutton, follow the procedure, “Resetting the UPS System after Emergency UPM Off”, of this chapter, before starting the system.
NOTE: The Remote Emergency Power Off option functions the same way as the
EMERGENCY UPM OFF pushbutton on the UPS Control Panel.
12.8.1 To Use the UPS EMERGENCY UPM OFF Pushbutton
1. Raise the clear plastic shield covering the red UPS EMERGENCY UPM OFF
pushbutton on the UPS Control Panel.
2. Press the EMERGENCY UPM OFF pushbutton.
The breakers open (you can hear them opening) and the Emergency UPM Off PUSH IN TO RESET pushbutton on the UPS Control Panel pops out.
12.8.2 Resetting the UPS System after an EMERGENCY UPM OFF
CAUTION: Do not attempt to restart the system after of the emergency has been identified and cleared.
The Emergency UPM Off PUSH IN TO RESET pushbutton is a small white button on the UPS Control Panel. The PUSH TO RESET pushbutton pops out when the Emergency UPM Off pushbutton on the UPS Control Panel is activated.
To r es et t he UP S sy st em :
1. Press the Emergency UPM Off PUSH IN TO RESET pushbutton until it clicks
in and remains recessed.
2. Breakers CB4 and FBP charge and close.
3. Reset tripped circuit breakers on UPS systems with manual CB1 and CB2
breakers.
4. The UPS system is now reset. To restart the UPS system, follow the procedure
at the beginning of this chapter.
Emergency UPM Off until the cause
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
12--5
This Page Intentionally Left Blank.
12--6
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Using Features and Options
13.1 General
The many standard features of your UPS system provide consistent, economical, and dependable power protection. In addition, you can add available options to enhance the performance of your system. This chapter provides descriptions of some of the features and options introduced earlier in this manual. Refer to drawings 164201244---1, 164201244---2, and 164201244 ---7 in Appendix A for location of the customer interface panel and terminals and for terminal wiring information.
13.2 Building Alarm Monitoring
This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or overtemperature alarms. The customer interface terminals for external connections are located inside the UPS.
Regardless of how you assign the building alarms, they display as Building Alarm 1, Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You should use twisted pair wires for each alarm input and common.
13.3 General Purpose Relay Contacts
13
Two general purpose relay contacts are provided as a standard feature on the UPS. The alarm contacts (one notice and one alarm) are located inside the UPS on the customer interface terminal board.
You can specify that each contact be either normally closed (NC) or normally open (NO). If the state of the contact changes from the state you specify as normal, an signal is issued. You can connect these contacts to equipment at your facility (such as a light or an alarm bell) to let you know when an alarm is active on the UPS. This feature is useful if the UPS is located in a remote area where the UPS alarm horn may not be heard immediately.
CAUTION: Contacts should not be operated in excess of 30 VAC or 42.4V peak AC or DC @1Amaximum.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
13--1
13.4 Remote Monitor Panel
As an option, you can install Remote Monitor Panels (RMPs) to monitor the operation of the UPS system from virtually any location within your facility, up to 500 feet from the UPS. Each RMP contains backlit status indicators and a local horn. You can flush-mount or surface-mount an RMP on a desktop, wall, or wherever you have a serial interface line. A maximum of two monitoring accessories (RMPs, Relay Interface Modules (RIMs), or Supervisory Contact Modules (SCMs)) can be installed. See Table 13---1 for the number of accessories permitted. Figure 13---1 shows an RMP.
Figure 13--- 1. Remote Monitor Panel
Table 13--- 1. Optional Monitoring Acce ssories
Number and Type of Accessories Permitted
Remote Monitor Panel Relay Interface Module Supervisory Contact Module
2
2
2
1 1
1 1
1 1
13--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
The RMP contains a local horn and the following backlit status indicators:
SYSTEM NORMAL
The UPS is energized (either with utility power or battery backup) and is supplying conditioned power to the critical load.
NO REDUNDANCY
This indicator applies only to parallel systems when one cabinet is not functioning. This feature is not available on this system.
ON GENERATOR
This alarm means that the UPS input and bypass are being supplied by the power from the generator, instead of from the utility power.
ON BYPASS
Thebypasssourceissupplyingthecritical load. Usually this means that the UPS is not energized. The load is not protected in Bypass mode, and a horn sounds after 30 seconds.
UPS ALARM
The UPS system is issuing an alarm. Conditions that affect the current UPS mode are indicated by the alarm lamps and horn on the UPS.
ON BATTERY
The UPS battery backup is supplying the critical load. The utility power is either interrupted or out of specification. The SYSTEM NORMAL indicator is also lit.
BYPASS UNAVAILABLE
The UPS system is in Normal mode, but a bypass source is not within specification. A horn sounds after 30 seconds.
SHUTDOWN IMMINENT
The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This light is accompanied by an audible alarm horn.
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
13--3
13.5 Relay Interface Module
An optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the Parallel Capacity/Redundant system . A maximum of two monitoring accessories (RMPs, RI Ms, or SCMs) can be installed. See Table 13---1 for the number of accessories permitted. Figure 13--- 2 shows the RIM with its four 15-pin connectors labeled J1 through J4.
Figure 13--- 2. Relay Interface Module
TheRIMcanprovidethesesignals:
· UPS AVAILABLE (pins 1 and 12) Contacts are closed when the UPS is
offline.
· UPS OFF LINE (pins 3 and 13) Contacts are closed when the UPS is
operating in Normal mode.
· UTILITY FAILURE (pins 6 and 15) Contacts are closed when Utility Failure is
detected.
· BATTERY WEAK (pins 5 and 14) Contacts are closed when approximately
2 minutes of battery time is remaining, before the critical load is lost.
13--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
13.6 Supervisory Contact Module
An optional Supervisory Contact Module (SCM) establishes an interface between the Parallel Capacity/Redundant system manufacturer’s equipment and the customer’s monitor. This interface allows the customer to monitor operational status of the Parallel Capacity/Redundant system equipment. A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 13---1 for the number of accessories permitted. Figure 13 ---3 shows the SCM, input connections on TB1, and output connections on TB2.
TB2
Figure 13--- 3. Supervisory Contact Module
The SCM provides signals for the following indications:
· SYSTEM NORMAL T B2 --- 1 th r o u gh TB 2 --- 3
· NO REDUNDANCY TB 2 --- 4 th r o ug h T B 2 --- 6
· ON GENERATOR T B 2 --- 7 th r o ug h TB 2 --- 9
· BYPASS NOT AVAILABLE T B2 --- 1 0 t h r o ug h TB 2 --- 1 2
· ON BATTERY T B2 --- 1 3 t h r o ug h TB 2 --- 1 5
· UPS ALA RM T B 2 --- 1 6 t h ro u g h T B 2 --- 1 8
· ON BYPASS T B 2 --- 1 9 th r o ug h T B 2 --- 2 1
· SHUTDOWN IMMINENT T B 2 --- 2 2 th r o ug h T B 2 --- 2 4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
13--5
13.7 Battery Racks
You can enhance the protection time provided by your UPS system by adding one or more battery racks. The battery racks should be equipped with sealed lead-acid, maintenance-free batteries. An external battery disconnect switch must be used. Refer to Chapter 3 in this manual for UPS battery requirements and installation instructions.
13.8 External Battery Disconnect
An optional external DC disconnect provides an automatic or manual means of disconnecting a battery string from the UPS. The disconnect is enclosed in a floor mounted freestanding box. You can install it anywhere between the remote DC supply and the UPS, according to national and local codes.
The breaker switch on the remote battery disconnect is set in accordance with the operation procedures contained in Chapter 12 --- UPS Operating Instructions of this manual. When service personnel are performing maintenance on the UPS or battery cabinet, the switch should be set to the OFF position. Refer to Chapter 4 in this manual for battery disconnect requirements and installation instructions.
13--6
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Responding to System Events
14.1 General
When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused the change from Normal mode. System events on the UPS can be indicated by horns, lights, messages, or all three.
Select Active from the Events menu on the LCD screen to look at the Active System Events screen. This screen shows any currently active alarms, notices, or commands.
14.2 System Event Horns
The system event horn beeps according to the type of event it is signifying:
· When the UPS detects an alarm that requires your attention, the horn beeps at
½-second intervals.
· When a notice occurs, the horn beeps at 2-second intervals.
14.3 System Event Lights
14
The status indicators on the UPS Control Panel work in conjunction with the event horn to let you know when the UPS system is operating in any mode other than Normal. Only the Normal indicator is visible during normal UPS system operation. The others light to indicate alarms or events. When an alarm occurs, you should first check these indicators to see what type of event has taken place. (For descriptions of the status indicators, refer to the “Reading the S tatus Indicators” section of Chapter 11.)
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
14--1
14.4 System Event Messages
When a system event occurs, a message is added to the Event History Log. A message may also appear on the Monitor Panel of the UPM. The Event History Log contains all system event messages, whether or not they were displayed on the Monitor Panel. The following list contains the programmable events displayed on the Active screen of the Monitor panel.
INVERTER ALARMS
Inverter Failure
Inverter AC Over Voltage
Inverter AC Under Voltage
Inverter Over Frequency
Inverter Under Frequency
Inverter DC Over Voltage
Bypass Phase Rotation
Inverter Phase Rotation
Service Required
UPS Tripped
Shutdown Imminent
UPS Off
Battery Contactor (K2) Failed
Bypass Contactor (K4) Failed
Inverter Contactor (K3) Failed
Bypass Control Failed
Check Unit Setup
Bypass Contactor (K4) Fail
Battery Ground Fault
100% Overload Shutdown
125% Overload Shutdown
Over Temperature Shutdown
Network Sync Failure
Inverter Calibration Required
Inverter Setup Required
14--2
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
RECTIFIER ALARMS
Rectifier Failure Rectifier DC Over Voltage Rectifier DC Under Voltage Input Phase Rotation Over Temperature Over Temperature Warning Temperature Sensor Failure Rectifier Calibration Required Rectifier Setup Required
MONITOR ALARMS
Overload Warning Load Over 100% Load Over 125% Battery Test Failed Battery Test Failed EEPROM Write Failed Logic Power Supply Failure Fan Failure UPS Failure Other UPS is On Bypass Other UPS Status is Unknown Emergency Bypass Failure Redundant Module Failure Check KW Sensing Check Parallel Setup Parallel System Overload On Battery more than 30 Seconds Check UPM Breaker (CBS) AUX Check Bypass Breaker (CBP) AUX Monitor Calibration Required Monitor Setup Required
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
14--3
PNODE ALARMS
PowerNode Board Failure Bypass Brkr (CBP) Will NOT Open Bypass Brkr (CBP) Will NOT Close UPM Breaker (CBS) Will NOT Open UPM Breaker (CBS) W ill NOT Close Bkfeed Brkr (FBP) Will NOT Open Bkfeed Brkr (FBP) Will NOT Close UPM Phase Rotation Bypass Phase Rotation PowerNet Channel A RX Down PowerNet Channel B RX Down PowerNet Channel A TX Down PowerNet Channel B TX Down STSW NOT Available STSW SCR SHORTED Load Over 100% Load Over 125% STSW Disconnected K1 Relay Failure PowerNode Calibration Required PowerNode Setup Required
14--4
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
UPM ALARMS
UPM 1 Not Reporting UPM 2 Not Reporting UPM 3 Not Reporting UPM 4 Not Reporting UPM 5 Not Reporting UPM 6 Not Reporting UPM 7 Not Reporting UPM 8 Not Reporting UPM 1 Alarm UPM 2 Alarm UPM 3 Alarm UPM 4 Alarm UPM 5 Alarm UPM 6 Alarm UPM 7 Alarm UPM 8 Alarm UPM 1 Phone Home UPM 2 Phone Home UPM 3 Phone Home UPM 4 Phone Home UPM 5 Phone Home UPM 6 Phone Home UPM 7 Phone Home UPM 8 Phone Home
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
14--5
INVERTER NOTICES
Input Breaker (CB1) Open Bypass Mode Bypass AC Over Voltage Bypass AC Under Voltage Bypass Over Frequency Bypass Under Frequency Bypass is Not Available Battery Discharged Battery DC Under Voltage Battery Disconnected Battery Not Charged Phase A Current Limit Phase B Current Limit Phase C Current Limit Battery Voltage Low Inv. Logic Power Failure
RECTIFIER NOTICES
Input A C Over Voltage Input AC Under Voltage Input Over Frequency Input Under Frequency PowerSupplyOverVoltage Power Supply Under Voltage Input Transient DC Voltage Low DC Voltage High Equalizing Battery Testing Battery Battery Test Failed Input/Battery Current Limit Reduced Input Current Limit Rct. Logic Power Failure
14--6
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
MONITOR NOTICES
Output AC Over Voltage Output AC Under Voltage Output Over Frequency Output Under Frequency ThreeWireACOverVoltage ThreeWireACUnderVoltage ThreeWireUnderFreq. PowerNode Network Down Power Off Switch Rectifier Network Down Inverter Network Down Monitor Network Down Battery Time Low Batt Test Requires Calibration Battery Time Low MonitorLogicPowerFailure Building Alarm 1 Active Building Alarm 2 Active Building Alarm 3 Active Building Alarm 4 Active Building Alarm 5 Active Building Alarm 6 Active Testing Battery Battery Test Aborted (load) Battery Test Aborted (utility) Battery Passed Test ##Printing Sampled Data Other UPS Bypass Not Available Loss of Redundancy
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
14--7
PNODE NOTICES
UPM AC Over Voltage UPM AC Under Voltage UPM Over Frequency UPM Under Frequency Bypass AC Over Voltage Bypass AC Under Voltage Bypass Over Frequency Bypass Under Frequency Bypass is Not Available Not Enough UPMs System NOT Redundant PowerNode Calibration Fail PowerNode Calibration Pass No Bypass Sync Check EPO Reset Pn. Logic Power Failure
14--8
Powerware 9315 (500 kVA--750 kVA) Installation and Operation
164201244 REV. D 030101
Loading...