Powerware 5125, PW5125 2400 RM, PW5125 3000 RM, PW5125 2400i RM, PW5125 3000i RM User Manual

...
Page 1
Powerware®5125
Two-in-One
User’s Guide
2400–3000 VA
www.powerware.com
Page 2
Requesting a Declaration of Conformity
:
Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 950 Second Edition, Amendments A1, A2, A3, and A4
:
EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Powerware Corporation Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452 661 Fax: +358-9-452 665 68
93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC
Powerware is a registered trademark and Advanced Battery Management Plus (ABM Plus), X-Slot, and ConnectUPS are trademarks of Powerware Corporation.
.
Copyright 2002 Powerware Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be
reproduced in any way without the express written approval of Powerware Corporation.
Page 3
Class A EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
EN50091-2
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies:
WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, in
which case, the user may be required to take additional measures.
VCCI Notice
Page 4
Special Symbols
The following are examples of symbols used on the UPS to alert you to important information:
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the
associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for
additional information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. The UPS may contain sealed, lead-acid batteries. Batteries must be recycled.
Page 5
TABLE OF CONTENTS
1 Powerware 5125 1................................................
2 Safety Warnings 3.................................................
3 Installation 17.....................................................
Inspecting the Equipment 17........................................................
UPS Setup 17..................................................................
Rack-Mount Setup 18..........................................................
Cabinet Setup 19.............................................................
Installing the UPS 24.............................................................
UPS Rear Panels 26..............................................................
4 Operation 29......................................................
Turning the UPS On 29............................................................
Starting the UPS on Battery 29....................................................
Turning the UPS Off 29...........................................................
Initiating the Self-Test 30..........................................................
Operating Modes 30.............................................................
Normal Mode 31.............................................................
Battery Mode 31.............................................................
Bypass Mode 32..............................................................
Standby Mode 32.............................................................
5 Additional UPS Features 33..........................................
X-Slot Modules 33...............................................................
Single-Port Module 34.........................................................
Load Segments 36...............................................................
Remote Emergency Power-Off 37....................................................
6 UPS Maintenance 39...............................................
UPS and Battery Care 39..........................................................
Storing the UPS and Batteries 39..................................................
Replacing the Electronics Module 40..................................................
When to Replace Batteries 41......................................................
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
i
Page 6
Table of Contents
Replacing Batteries 41............................................................
How to Replace Extended Battery Modules 42.........................................
How to Replace Internal Batteries 43...............................................
Testing New Batteries 44..........................................................
Recycling the Used Battery 45......................................................
7 Specifications 47..................................................
8 Troubleshooting 51.................................................
Audible Alarms and UPS Conditions 51................................................
Silencing an Audible Alarm 51....................................................
Service and Support 54...........................................................
ii
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 7
CHAPTER 1
POWERWARE 5125
The Powerware95125 uninterruptible power system (UPS) protects your sensitive electronic equipment from basic power problems such as power failures, power sags, power surges, brownouts, and line noise.
Power outages can occur when you least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware — causing
hours of lost productivity and expensive repairs. With the Powerware 5125, you can safely eliminate the effects of power
disturbances and guard the integrity of your equipment. The Powerware 5125 is designed for critical applications such as PCs, severs, workstations, and telecommunications equipment. Figure 1 shows the Powerware 5125 UPS with an optional Extended Battery Module (EBM).
Figure 1. The Powerware 5125
Providing outstanding performance and reliability, the Powerware 5125’s unique benefits include the following:
2U rack height conserves valuable rack space.
:
Advanced Battery Management Plus (ABM PlusZ) doubles battery
:
service life, optimizes recharge time, and provides a warning before the end of useful battery life.
Hours of extended run time with up to four EBMs.
:
Hot-swappable batteries simplify maintenance by allowing you to
:
replace batteries safely without powering down the critical load.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
1
Page 8
Powerware 5125
Start-on-battery capability allows you to power up the UPS even if
:
utility power is not available. Advanced power management with the Software Suite CD for graceful
:
shutdowns and power monitoring. Sequential shutdown and load management through separate
:
receptacle groups, called load segments. Emergency shutdown control through the Remote Emergency
:
Power-Off (REPO) port. Optional X-SlotZmodules provide enhanced communication
:
capabilities for increased power protection and control. The Powerware 5125 is backed by worldwide agency approvals.
:
2
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 9
CHAPTER 2
SAFETY WARNINGS
Read the following precautions before you install the UPS.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
This UPS contains LETHAL VOLTAGES. Allrepairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
: This UPS contains its own energysource (batteries). The output receptacles may
carry live voltage even when the UPS is not connected to an AC supply.
: Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
: To reduce the risk of fire or electric shock,install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40C (104F). Do not operate near water or excessive humidity (95% max).
: To comply with international standardsand wiring regulations, the total equipment
connected to the output of this UPS must nothave an earth leakage current greater than 2.5 milliamperes.
DANGER
WARNING
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
3
Page 10
Safety Warnings
: Batteries can present a risk of electrical shock or burn from high short-circuit
current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteriesand required precautions. Keep unauthorized personnel away from batteries.
: Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
: Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE SIKKERHEDSANVISNINGER
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør kun udføres afen AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan repareres af brugeren.
CAUTION
FARE
ADVARSEL!
: Denne UPS indeholder egen energiforsyning (batterier).Udgangsnetstikkene kan
lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.
: Netledningen må ikke fjernes og stikketmå ikke trækkes ud, mens UPS’en er
tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.
: Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit
for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød. Rumtemperaturen må ikke overstige 40C. UPS’en bør ikke betjenes nær vand eller høj fugtighed (maksimalt 95%).
: I overensstemmelse med internationale normer og bestemmelser for el-installation
må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 2,5 milliampere.
4
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 11
: Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj
kortslutningsspænding. De korrekte forholdsregler bør overholdes.
: Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for
bortskaffelsesprocedurer.
: Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere
ved åben ild.
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD.
Safety Warnings
ADVARSEL
GEVAAR
WAARSCHUWING
: Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen
kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten.
: Verwijder de ingangsnoer niet of haalde stekker van de ingangsnoer er niet uit
terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben.
: Teneinde de kans op brand of elektrische schokte verminderen dient deze UPS in
een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max. 95%).
: Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de
gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan 2,5 milliampère hebben.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
5
Page 12
Safety Warnings
: Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als
gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op.
: De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw
plaatselijke voorschriften.
: Nooit batterijen in het vuur gooien.De batterijen kunnen ontploffen.
Tarkeita Turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI
SÄILYTÄ NÄMÄ OHJEET TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ.Kaikki korjaukset ja huollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.
OPGELET
VAARA
VAROITUS
: Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla
jännite, kun UPS ei ole liitettynä verkkojännitteeseen.
: Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa
turvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.
: Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,
joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia. Ympäristön lämpötila eisaa ylittää 40 C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi).
: Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän
UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 2,5 milliampeeria (mA).
6
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 13
: Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään
oikosulkuun. Noudata asianmukaisia ohjeita.
: Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia
määräyksiä.
: Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.
Safety Warnings
VARO
DANGER!
AVERTISSEMENT!
: Cet onduleur renferme sa propre source d’énergie (batteries). Les prises de sortie
peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le secteur.
: Ne pas retirer le cordon d’alimentation lorsque l’onduleur est soustension sous
peine de supprimer la mise à la terre de l’onduleur et du matériel connecté.
: Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit pas dépasser 40C. Ne pas utiliser à proximité d’eau ou dans une atmosphère excessivement humide (95 % maximum).
: Afin d’être conforme aux normes et règlements internationaux de câblage, le
courant de fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 2,5 mA.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
7
Page 14
Safety Warnings
: Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par
des courts-circuits de haute intensité. Prendre lesprécautions nécessaires.
: Une mise au rebut réglementaire des batteries est obligatoire. Consulter les
règlements en vigueur dans votre localité.
: Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire
exploser.
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN. DIESES HANDBUCH ENTHÄLT WICHTIGE
SICHERHEITSANWEISUNGEN.
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten sollten nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer zu wartenden Komponente
ATTENTION!
WARNUNG
ACHTUNG
: Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den
Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an einer Wechselspannungsquelle angeschlossen ist.
: Das Eingangskabel nicht entfernen oder abziehen,während die USV eingeschaltet
ist, weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird.
: Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden
mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40C nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %) betreiben.
: Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an
den Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdschlußstrom von insgesamt 2,5 Milliampere nicht überschreiten.
8
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 15
: Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder
Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind unbedingt zu beachten.
: Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbeisind die örtlichen
Bestimmungen zu beachten.
: Batterien niemals verbrennen, da sie explodieren können.
РспейдпрпйЮуейт БуцЬлейбт
УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ ЦХЛБОФЕ БХФЕУ ÔÉÓ ПДЗГЙЕУ ÔÏ РБСПН ЕГЧЕЙСЙДЙП РЕСЙЕЧЕЙ УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ
Áõôü ôï UPS ресйЭчей ИБНБФЗЦПСБ ÔÁÓÇ. ¼ëåò ïé ерйукехЭт êáé ïé ухнфзсЮуейт рсЭрей íá гЯнпнфбй ÌÏÍÏ ÁÐÏ ЕОПХУЙПДПФЗМЕНП ÃÉÁ ÔÇ УХНФЗСЗУЗ РСПУЩРЙКП. Ôï UPS ÄÅÍ РЕСЙЕЧЕЙ КБНЕНБ ЕОБСФЗМБ ÐÏÕ ÍÁ МРПСЕЙ ÍÁ ЕРЙУКЕХБУФЕЙ ÁÐÏ ÔÏ ЧСЗУФЗ.
Safety Warnings
VORSICHT!
КЙНДХНПУ
РСПЕЙДПРПЙЗУЗК
:
Ôï ухгкексймЭнп UPS ресйЭчей ôç äéêÞ ôïõ ðçãÞ енЭсгейбт (ухуущсехфЭт). Ïé сехмбфпдьфет еоьдпх мрпсеЯ íá Эчпхн енесгь ôÜóç бкьмз êáé üôáí ôï UPS äåí еЯнбй ухндедемЭнп óå ðçãÞ енбллбууьменпх сеэмбфпт (AC).
:
Ìçí вгЬжефе áðü ôçí рсЯжб ôï кблюдйп фспцпдпуЯбт üôáí ôï UPS еЯнбй бнпйчфь. Ì UPS êáé áðü ôïí еопрлйумь ðïõ еЯнбй ухндедемЭнпт ìå ôï UPS.
:
Ãéá íá мейюуефе ôïí кЯндхнп рхскбгйЬт Þ злекфспрлзоЯбт, егкбфбуфЮуфе ôï ухгкексймЭнп UPS óå еущфесйкь ÷þñï ìå елегчьменз иесмпксбуЯб êáé хгсбуЯб, ï прпЯпт íá ìçí ресйЭчей бгюгймб хлйкЬ. Ç иесмпксбуЯб ресйвЬллпнфпт äåí рсЭрей íá оереснЬей ôïõò 40C. Ìç чсзуймпрпйеЯфе ôï UPS кпнфЬ óå íåñü Þ хресвплйкЮ хгсбуЯб (мЭгйуфз ôéìÞ: 95%).
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
áõôü ôïí фсьрп бцбйсеЯфе ôç геЯщуз буцблеЯбт áðü ôï
9
Page 16
Safety Warnings
:
:
:
:
Avvisi di sicurezza
IMPORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI SICUREZZA
Ãéá íá ухмцщнеЯ ìå ôá дйеинЮ рсьфхрб êáé ôïõò кбнпнйумпэт кблщдЯщузт, ôï сеэмб дйбсспЮт ðñïò ôç ãç пльклзспх ôïõ еопрлйумпэ, ðïõ еЯнбй ухндедемЭнпт ìå ôçí Эопдп ôïõ ухгкексймЭнпх UPS, äåí рсЭрей íá еЯнбй мегблэфесп áðü 2,5 mA.
РСПУПЧЗ
Ïé ухуущсехфЭт мрпсеЯ íá рспкблЭупхн злекфспрлзоЯб Þ Эгкбхмб áðü хшзль сеэмб всбчхкхклюмбфпт. ЛбмвЬнефе ôéò кбфЬллзлет рспцхлЬоейт.
БрбйфеЯфбй ущуфЮ дйЬиеуз ôùí ухуущсехфюн. ДеЯфе ôïõò фпрйкпэт кбнпнйумпэт ðïõ бцпспэн ôéò брбйфЮуейт дйЬиеуЮт ôïõò.
ÐïôÝ ìçí рефЬфе ôïõò ухуущсехфЭт óôç цщфйЬ, гйбфЯ мрпсеЯ íá ексбгпэн.
10
PERICOLO
la TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE.
AVVERTENZA
: Questo gruppo statico di continuità contiene una fonte di energia autonoma (le
batterie). Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuità non è collegato con una fonte di alimentazione a corrente alternata.
: Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di
continuità è acceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuità e dell’apparecchiatura ad esso collegata.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 17
Safety Warnings
: Per ridurre il rischio di incendio o discossa elettrica, installare il gruppo statico di
continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti contaminanti conduttivi. La temperatura ambiente non deve superare i 40C. Non utilizzare l’unità in prossimità di acqua o in presenza diumidità eccessiva (95% max).
: Per conformità con gli standard internazionali e con le norme in merito al
cablaggio, tutta l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere una corrente di dispersione di terra superiore a 2,5 milliampere.
ATTENZIONE
: Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da
alta corrente dovuta a corto circuito. Osservare le apposite istruzioni.
: Le batterie devono essere smaltite in modo corretto. Per irequisiti di smaltimento
fare riferimento alle disposizioni locali.
: Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle
fiamme.
Viktig Sikkerhetsinformasion
FARLIG
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅ NOEN AV DELENE i UPS’en.
FARLIG
: Denne UPS’en har en egen energikilde (batterier). Stikkontaktene kan være
strømførende selv om UPS’en ikke er tilsluttet en vekselstrømforsyning.
: Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på, slik at
ikke sikkerhetsjordingen fjernes fra UPS’en og det utstyret somer forbundet med den.
: For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende, forurensende stoffer. Romtemperaturen må ikke overskride 40C. Den må ikke brukes i nærheten av vann ellerved meget høy luftfuktighet (95% maks.).
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
11
Page 18
Safety Warnings
: Alt utstyr som er forbundet med utgangen avdenne UPS’en må ikke ha en sterkere
total lekkasjestrøm enn 2,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser.
: Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy
kortslutningsstrøm. Følg instruksene.
: Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om
fjerning av batterier.
: Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettesfor åpen ild.
Regulamentos de Segurança
INSTRUÇÕES DE SEGURANÇA IMPORTANTES
GUARDE ESTAS INSTRUÇÕES ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA IMPORTANTES
FORSIKTIG
12
CUIDADO
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
ADVERTÊNCIA
: Esta UPS contém sua própria fonte de energia (baterias). Os receptáculos de saída
podem conter voltagem ativa quando a UPS não se encontra conectada a uma fonte de alimentação de corrente alternada.
: Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto
removerá o aterramento de segurança da UPS e do equipamento conectado.
: Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente
interno com temperatura e umidade controladas e livres de contaminadores condutíveis. A temperatura ambiente não deve exceder 40C. Não opere próximo a água ou em umidade excessiva (máx: 95%).
: Para estar de acordo com os padrões internacionais e os regulamentos de fiação,o
equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 2,5 miliampères.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 19
PERIGO
: As baterias podem apresentar o risco de choque elétrico, ou queimaduras
provenientes de alta corrente de curto-circuito.Observe as instruções adequadas.
: Siga as instruções apropriadas ao desfazer-se dasbaterias. Consulte os códigos do
local para maiores informações sobre os regulamentos de descarte de produtos.
: Nunca jogue as baterias no fogo, porque há risco de explosão.
Предупреждения по мерам безопасности
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ СОХРАНИТЕ ЭТИ УКАЗАНИЯ ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
ОПАСНО
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ. Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.
Safety Warnings
ПРЕДУПРЕЖДЕНИЕ
: Данный ИБП содержит собственные источники энергии
(аккумуляторы). На выходных розетках может иметься напряжение, даже когда ИБП не подключен к сети переменного тока.
: Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки
при включенном ИБП. При этом защитное заземление отключается от ИБП и от оборудования, подключенного к ИПБ.
: Для снижения опасности пожара или поражения электрическим
током устанавливайте ИБП в закрытом помещении с контролируемыми температурой и влажностью, в котором отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40С. Не эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%).
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
13
Page 20
Safety Warnings
: Для обеспечения соблюдения требований международных
стандартов и требований к разводке электрических цепей, суммарная величина тока утечки на землю всего оборудования, подключенного к выходу ИБП, не должна превышать 2,5 миллиампера.
: Аккумуляторы могут вызвать опасность поражения электрическим
током или ожога от тока короткого замыкания. Соблюдайте соответствующие меры предосторожности.
: Необходимо соблюдать правила утилизации аккумуляторов.
Обратитесь к местным нормативным актам за информацией о требованиях к утилизации.
: Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут
взорваться под воздействием огня.
Advertencias de Seguridad
ОСТОРОЖНО
14
INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES
PELIGRO
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.
ADVERTENCIA
: Este SIE contiene su propia fuente de energía (las baterías). Los receptáculos de
salida pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a un suministro de corriente alterna (c.a.).
: No retire o desenchufe el cable de entrada mientras el SIE se encuentre
encendido. Esto suprime la descarga a tierra de seguridad del SIE y de losequipos conectados al SIE.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 21
Safety Warnings
: Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un
lugar cubierto, con temperatura y humedad controladas, libre de contaminantes conductores. La temperatura ambiente no debe exceder los 40C. No trabaje cerca del agua o con humedad excesiva (95% máximo).
: Para cumplir con los estándares internacionales y las normas de instalación, la
totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 2,5 miliamperios.
PRECAUCIÓN
: Las baterías pueden presentar un riesgo de descargaseléctricas o de quemaduras
debido a la alta corriente de cortocircuito. Preste atención a las instrucciones correspondientes.
: Es necesario desechar las baterías de un modo adecuado. Consulte las normas
locales para conocer los requisitos pertinentes.
: Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las
expone a la llama.
Säkerhetsföreskrifter
VIKTIGA SÄKERHETSFÖRESKRIFTER
SPARA DESSA FÖRESKRIFTER DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA SÄKERHETSFÖRESKRIFTER
FARA
Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING.ENDAST AUKTORISERAD SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.
VARNING
: Denna UPS-enhet har en egen energikälla (batterier). De utgående kontakterna kan
vara strömförande när UPS-enheten inte är ansluten till en växelströmkälla.
: Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort
skyddsjordningen från både UPS-enheten och den anslutna utrustningen.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
15
Page 22
Safety Warnings
: Minska risken för brand eller elektriska stötar genom att installera denna
UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40C. Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).
: För att överensstämma med internationell standard och installationsföreskrifter får
inte den totala utrustning som anslutits till uttagen på denna UPS-enhet ha läcksström som överstiger 2,5 milliampere.
VIKTIGT
: Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström.
Följ tillämpliga anvisningar.
: Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. : Använda batterier får aldrig brännas upp. De kan explodera.
16
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 23
CHAPTER 3
INSTALLATION
This section explains:
Equipment inspection
:
UPS setup and installation
:
UPS rear panels
:
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
UPS Setup
The Powerware 5125 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet.
If you are installing the UPS in a rack, continue to the following section,
“Rack-Mount Setup;” otherwise, continue to “Cabinet Setup” on page 19.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
17
Page 24
Installation
Rack-Mount Setup
The UPS can be installed in 19-inch racks and needs only 2U of valuable rack space.
CAUTION
The UPS and Extended Battery Module are heavy (see page 47). A minimum of two people are required to lift the UPS into the rack.
NOTE Fixed mounting rails are required for each cabinet. If fixed rails are not already installed in your rack, contact your local distributor to order a rail kit.
Use the following procedure to install the UPS in a rack:
1. Place the UPS on a flat, stable surface with the front of the UPS
facing toward you.
2. Attach the supplied mounting handles to the mounting
brackets (see Figure 2).
3. If installing optional EBMs, repeat Steps 1 and 2 for each
cabinet.
18
Mounting Handle
Mounting Bracket
Figure 2. Installing the Mounting Handles
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 25
Installation
NOTE The UPS and EBMs MUST be installed at the bottom of the rack. If placed in a rack with existing equipment, the rack must be reconfigured to allow the UPS installation at the bottom of the rack.
NOTE The EBMs must be installed below the UPS as shown in Figure 3.
4. Slide the UPS and any optional EBMs into the rack. Continue to
“Installing the UPS” on page 24 to complete the installation.
UPS
Optional EBMs
Figure 3. Rack-Mount UPS with EBMs
Cabinet Setup
The rack-mounting brackets must be removed before positioning the cabinets for the cabinet setup. Unscrew and remove the mounting brackets on each side of all cabinets as shown in Figure 4.
Figure 4. Removing the Mounting Brackets
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Mounting Bracket
19
Page 26
Installation
You can position the UPS cabinets horizontally or vertically. When positioning the cabinets horizontally, the EBMs must be placed below the UPS (see Figure 5).
UPS
Optional EBMs
Figure 5. HorizontalCabinet Setup
When positioning the cabinets vertically, the UPS and any optional EBMs must be stabilized with pedestals and/or EBM brackets. The vertical setup varies depending on the number of cabinets:
For one cabinet, both sets of pedestals must be installed.
1.
Complete Steps 2 through 4.
For two cabinets, the pedestals and the EBM brackets must be
installed. Skip to Step 5.
For three or more cabinets, skip to Step 8 to install the EBM
brackets.
2. Place the UPS cabinet horizontally so that the left end of the
unit is accessible (see Figure 6).
3. Position the pedestals over the end of the UPS cabinet so that
the weight of the unit is evenly distributed. Secure the pedestals with the screws provided in the accessory kit.
20
Figure 6. Installing Pedestals on a Single Cabinet
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 27
Installation
4. Carefully position the cabinet upright with the air vents at the
top (see Figure 7). Continue to “Installing the UPS” on page 24.
Air Vents
Figure 7. Pedestals with One Cabinet
5. Place the UPS cabinet horizontally so that the left end of the
unit is accessible (see Figure 8).
Figure 8. Installing UPS Pedestals with Two Cabinets
6. Place the EBM cabinet upside down so that the right end of the
unit is accessible (see Figure 9).
Figure 9. Installing EBM Pedestals
7. Position two of the pedestals over the edge of each cabinet so
that the weight of the unit is evenly distributed. Secure the pedestals with the screws provided in the accessory kit.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
21
Page 28
Installation
8. Carefully position the cabinets upright with the air vents at the
top(seeFigure10orFigure11).
Air Vents
Figure 10. Pedestals with Two Cabinets
NOTE Pedestals are required for one and two cabinet installations. EBM brackets are
required for all vertical EBM installations.
22
Air Vents
Figure 11. Vertical Cabinet Setup
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 29
Installation
9. Align each EBM bracket with the adjacent corner screw holes
and secure with the supplied screws.
UPS
EBM
EBM Bracket
EBM Bracket
Figure 12. Installing the EBM Brackets (Top View with Pedestals)
10. If installing additional EBMs, repeat Step 9 for each cabinet.
Continue to the following section, “Installing the UPS.”
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
23
Page 30
Installation
Installing the UPS
The following steps explain how to install the UPS. Figure 13 shows a typical installation only. See “UPS Rear Panels” on page 26 for the rear
panel of each model.
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty.
1. If installing an optional EBM, continue to Step 2; otherwise,
skiptoStep5.
2. Plug the EBM cable into the UPS battery connector (see
Figure 13).
3. Plug the other end of the EBM cable into the EBM battery
connector.
4. For additional EBMs, plug the EBM cable into the battery
connector of each EBM. Up to four EBMs may be connected to the UPS.
24
Communication Port
X-Slot
UPS Battery Connector
EBM Battery Connectors
Ground Bonding Screw
Power Cord
Output Receptacles
Circuit Breakers
EBM Cable
Figure 13. Typical Installation with Two EBMs
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 31
Installation
5. If you are installing power management software, connect your
computer to the UPS communication port using the supplied communication cable.
For Rack-Mount Installations only. If your rack has conductors for
6.
grounding or bonding of ungrounded metal parts, connect the ground cable (not included) to the ground bonding screw.
7. Plug the equipment to be protected into the appropriate UPS
output receptacles (see page 36 for more information on load segments).
DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements.
For the PW5125 3000e and 3000g RM models only. Plug the detachable
8.
UPS power cord into the input connector on the UPS rear panel.
Install a 16A plug on the other end of the cord that meets your
electrical code requirements for the AC power source.
local
9. Plug the UPS power cord into a power outlet. All front panel
indicators flash briefly and the UPS conducts a self-test. When the self-test is complete, the
indicating the UPS is in Standby mode with the equipment offline. If the alarm beeps or a UPS alarm indicator stays on, see Table 8 on page 52.
10. Press and hold the On
(approximately one second). The and the load level indicators display the percentage of load being applied to the UPS.
The UPS is now in Normal mode and supplying power to your equipment.
button until you hear the UPS beep
indicator flashes,
indicator stops flashing
NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 24 hoursafter installation or long-term storage.
NOTE If more than two EBMs are installed, an external battery charger is recommended for faster recharge times.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
25
Page 32
Installation
UPS Rear Panels
This section shows the rear panels of the Powerware 5125 models.
X-Slot
X-Slot
Communication Port
REPO Port
Battery Connector
Figure 14. 2400–3000 VA, 100/120V Rear Panel
Communication Port
REPO Port
Battery Connector
Figure 15. 2400–3000 VA, 230V Rear Panel
5-15 Receptacles
Power Cord with L5-30P
IEC 320-C13 Receptacles
Power Cord with 16A, IEC-309 Plug
Circuit Breakers
L5-30 Receptacle
Circuit Breakers
IEC 320-C19 Receptacle
26
X-Slot
Communication Port IEC 320-C13 Receptacles
REPO Port
Battery Connector
16A, IEC 320-C20 Input Connector
Circuit Breakers
Figure 16. 3000 VA, 230V (PW5125 3000e RM) Rear Panel
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
IEC 320-C19 Receptacle
Page 33
Installation
Communication Port IEC 320-C13 Receptacles
X-Slot
REPO Port
Battery Connector
16A, IEC 320-C20 Input Connector
IEC 320-C19 Receptacle
Figure 17. 3000 VA, 200–240V (PW5125 3000g RM) Rear Panel
Circuit Breakers
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
27
Page 34
Installation
28
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 35
CHAPTER 4
OPERATION
This section describes:
Turning the UPS on and off
:
Starting the UPS on battery
:
Initiating the self-test
:
Operating modes
:
Turning the UPS On
After the UPS is connected to a power outlet, it conducts a self-test and enters Standby mode. To turn on the UPS, press and hold the
button until you hear the UPS beep (approximately one second).
On The
percentage of load being applied to the UPS.
Starting the UPS on Battery
NOTE Before using this feature, the UPS must have been powered by utility power at
least once.
indicator stops flashing and the load level indicators display the
To turn on the UPS without using utility power, press and hold the
button for at least four seconds. The UPS supplies power to your
On equipment and goes into Battery mode. When the UPS starts on battery, it does not conduct a self-test to conserve battery power.
Turning the UPS Off
To turn off the UPS, press and hold the Off button until the long beep ceases (approximately five seconds). The flash and the UPS remains in Standby mode until you unplug the UPS from the power outlet.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
indicator begins to
29
Page 36
Operation
Initiating the Self-Test
NOTE The batteries must be fully charged and the UPS must not be in Battery mode
to perform the self-test.
Press and hold the button for three seconds to initiate the self-test. During the test, individual indicators illuminate as various parts of the UPS are checked. If the alarm beeps or a UPS alarm indicator stays on, see Table 8 on page 52.
Operating Modes
Powerware 5125’s front panel indicates the UPS status through the UPS indicators. Figure 18 shows the UPS front panel indicators and controls.
Normal Mode Indicator (Solid Green)
Standby Mode Indicator (Flashing Green)
Bypass Mode Indicator (Solid Red)
Indicator Legend
Unlit Green Red Flashing
30
On Button
Off Button
Test/Alarm Reset Button
Load Level IndicatorsBattery Mode Indicator
Battery Service Indicator
Figure 18. UPS Front Panel
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 37
Operation
Normal Mode
During Normal mode, the displays the percentage of UPS load capacity being used by the protected equipment (see Figure 19). The UPS monitors and charges the batteries as needed and provides power protection to your equipment.
Figure 19. Load Level Indicators
When all of the load level indicators and the indicator are illuminated, power requirements exceed UPS capacity; see page 53 for more information.
indicator illuminates and the front panel
>100%
76–100%
51–75%
26–50%
0–25%
Battery Mode
When the UPS is operating during a power outage, the alarm beeps once every five seconds and the power returns, the UPS switches to Normal mode operation while the battery recharges.
If battery capacity becomes low while in Battery mode, the starts flashing and the alarm continues to beep every five seconds. Immediately complete and save your work to prevent data loss and similar difficulties. When utility power is restored after the UPS shuts down, the UPS automatically restarts.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
indicator illuminates. When the utility
indicator
31
Page 38
Operation
Bypass Mode
In the event of a UPS overload or internal failure, the UPS transfers your equipment to utility power. Battery mode is not available; however, the utility power continues to be passively filtered by the UPS. The alarm sounds and the Bypass mode when:
The UPS has an overtemperature condition.
:
The UPS has an overload condition of 103 to 110% for 30 seconds.
:
The UPS detects a fault in the battery or UPS electronics.
:
indicator illuminates red. The UPS switches to
Standby Mode
When the UPS is turned off and remains plugged into a power outlet, the UPS is in Standby mode. The indicators are off, indicating that power is not available from the UPS output receptacles. The battery recharges when necessary.
indicator flashes and the load level
32
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 39
CHAPTER 5
ADDITIONAL UPS FEATURES
This section describes:
X-Slot modules
:
Load segments
:
Remote Emergency Power-Off
:
X-Slot Modules
X-Slot modules allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 5125 is factory-installed with a Single-Port module and is compatible with any X-Slot module, including:
Multi-Server Module - has six serial communication ports that can
:
communicate with UPSs, terminals, computers, and modems. ConnectUPS -MX SNMP Module - has Ethernet, modem, and SNMP
:
capabilities. ConnectUPS-X and -BD SNMP/WEB Adapter - has SNMP capabilities
:
as well as monitoring through a web browser interface. USB Module - connects to a USB port on your computer.
:
Z
Multi-Server Module
ConnectUPS-MX
ConnectUPS-X and -BD
USB Module
Figure 20. Optional X-Slot Modules
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Single-Port Module
33
Page 40
Additional UPS Features
Single-Port Module
The Powerware 5125 is factory-installed with a Single-Port Module. To establish communication between the UPS and a computer, connect
your computer to the UPS communication port using the supplied communication cable.
When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.
The cable pins are identified in Figure 21 and the pin functions are described in Table 1.
3
245
1
9
87
6
Figure 21. Communication Port
34
Table 1. Communication Port Pin Assignment
Pin Number
1 Low Batt Low Battery relay contact Out 2 RxD Transmit to external device Out 3 TxD Receive from external device In 4 DTR PnP (Plug and Play) from external device
5 GND Signal common (tied to chassis)
6 DSR To external device (tied to Pin 4) Out 7 RTS PnP from external device (default) or
8 AC Fail AC Fail relay contact Out 9 Power Source +V (8 to 24 volts DC power) Out
Signal Name Function Direction
(tied to Pin 6)
On Bypass relay contact (jumper-selectable)
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
from the UPS
In
In / Out
Page 41
Additional UPS Features
The On-Bypass Relay Contact. You can enable the On-Bypass relay using the
jumper on the single-port module. The jumper default is disabled. To enable the On-Bypass relay:
1. Remove the single-port module on the UPS rear panel. Retain
thescrews(seeFigure22).
Figure 22. Removing the Single-Port Module
2. Move the J3 jumper to the AS/400 position to enable the
On-Bypass relay as shown in Figure 23.
On-Bypass
Disabled
On-Bypass Relay Jumper
Figure 23. On-Bypass Relay Jumper
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
On-Bypass
Enabled
AS/400NORM
(J3)
35
Page 42
Additional UPS Features
Load Segments
3. To prevent electrostatic discharge (ESD), place one hand on a
metal surface such as the UPS rear panel. Align the single-port module with the slot guides and slide the
module into the slot until it is firmly seated.
4. Secure the single-port module with the screws removed in
Step 1.
Load segments are sets of receptacles that can be controlled by power management software, providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep key pieces of equipment running while you turn off other equipment. This feature allows you to save battery power. See your power management software manual for details.
NOTE If the power management software isnot used, the individual load segments cannot be controlled.
36
Each UPS has three load segments as shown in Figure 24 and Figure 25.
Load Segment 1
Load Segment 2
Figure 24. UPS Load Segments (120V Model Shown)
Figure 25. UPS Load Segments (PW5125 3000g RM Model Shown)
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Load Segment 3
Load Segment 2
Load Segment 3Load Segment 1
Page 43
Remote Emergency Power-Off
The Powerware 5125 includes a REPO port that allows power to be switched off at the UPS output receptacles from a customer-supplied switch in a remote location.
The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown procedure initiated by any power management software.
Any devices that are operating on battery power are also shut down immediately. When the REPO switch is reset, the equipment will not return to battery power until the UPS is manually restarted.
If the Off remains in Standby mode when restarted until the On pressed.
The REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation.
button is pressed after the REPO is activated, the UPS
Additional UPS Features
button is
WARNING
CAUTION
To ensure the UPS stops supplying power to the load during any mode of operation, the input power must be disconnected from the UPS when the emergency power-off function is activated.
NOTE The REPO function activates when the REPO contacts close.
Use the following procedure to install the REPO switch:
1. Verify that the UPS is off and unplugged.
2. Remove the REPO connector from the REPO port on the rear
panel of the UPS.
3. Connect isolated, normally-open, dry contacts (rated at 60 Vdc
maximum, 30 Vac RMS maximum, and 20 mA maximum) across the REPO device to Pin 1 and Pin 2 (see Figure 26). Use stranded, non-shielded wiring, size 18–22 AWG
(0.75 mm
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
2
–0 mm2).
37
Page 44
Additional UPS Features
4. Reconnect the REPO connector to the REPO port.
Pin 1 Pin 2
Figure 26. REPO Connector
5. Verify that the externally-connected REPO switch is not
activated to enable power to the UPS output receptacles.
6. Plug in the UPS and start the UPS by pressing the On
button.
7. Activate the external REPO switch to test the REPO function.
8. De-activate the external REPO switch and restart the UPS.
38
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 45
CHAPTER 6
UPS MAINTENANCE
This section explains how to:
Care for the UPS and batteries
:
Replace the electronics module
:
Replace the batteries
:
Test new batteries
:
Recycle used batteries
:
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every 6 months by plugging the UPS into a power outlet. The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 24 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
39
Page 46
UPS Maintenance
Replacing the Electronics Module
The electronics module can be hot-swapped for easy replacement without losing power to your equipment. The UPS automatically switches to Bypass mode. Battery mode is not available; however, the utility power continues to be passively filtered by the UPS.
Use the following procedure to replace the electronics module:
1. Disconnect the Extended Battery Module cable, the Remote
Emergency Power-Off cable, and the communication cable if installed.
2. Remove the UPS front panel by pulling on both ends.
40
3. Remove the two screws on the left of the electronics module.
4. Remove the electronics module.
5. Replace the electronics module and secure to the UPS chassis
with the screws removed in Step 3.
6. Replace the front panel.
7. Reconnect any cables removed in Step 1.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 47
When to Replace Batteries
When the indicator flashes and there is a continuous audible alarm, the batteries may need replacing. Conduct a self-test by pressing and holding the contact your service representative to order new batteries.
Replacing Batteries
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
With the hot-swappable battery feature, UPS batteries can be replaced easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the battery: 1) Press and hold the Off seconds), then unplug the UPS; 2) Wait 60 seconds while the internal processor shuts down before you disconnect the battery.
Consider all warnings, cautions, and notes before replacing batteries.
UPS Maintenance
button for three seconds. If the indicator stays on,
button until the long beep ceases (approximately five
WARNING
: Batteries can present a risk of electrical shock or burn from high short-circuit
current. The following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries.
: ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or
connectors. Attempting to alter wiring can cause injury.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
41
Page 48
UPS Maintenance
How to Replace Extended Battery Modules
Use the following procedure to replace EBMs:
1. Unplug the EBM cable from the UPS.
2. If the UPS is in a vertical configuration, remove the EBM
brackets from the top.
3. Replace the EBM. See “Recycling the Used Battery” on page 45
for proper disposal.
4. Reinstall the EBM brackets if removed in Step 2.
5. Plug the new EBM into the UPS as shown in Figure 27. Plug
the other end of the EBM cable into the EBM battery connector.
6. For additional EBMs, plug the EBM cable into the battery
connector of each EBM.
EBM Brackets
42
EBM Battery Connectors
EBM Cables
Figure 27. EBM Connections (120V Model Shown)
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
UPS Battery Connector
Page 49
UPS Maintenance
How to Replace Internal Batteries
CAUTION
Pull the battery out onto a flat,stable surface. The battery is unsupported when you pull it out of the UPS.
Use the following procedure to replace internal batteries:
1. Remove the UPS front panel by pulling on both ends.
2. Unscrew and set aside the battery retaining bracket.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
43
Page 50
UPS Maintenance
3. Pull the battery out onto a flat, stable surface. See “Recycling
4. Slide the new battery into the UPS.
5. Reinstall the battery retaining bracket and screws removed in
6. Replace the front panel.
Testing New Batteries
the Used Battery” on page 45 for proper disposal.
Step 2.
44
Press and hold the button for three seconds to initiate a self-test. After the test is finished, the
indicator should turn off. If the indicator stays on, check the battery connections. Call your service representative if the problem persists.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 51
Recycling the Used Battery
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.
: Do not dispose of the battery or batteriesin a fire. Batteries may explode. Proper
disposal of batteries is required.Refer to your local codes for disposal requirements.
: Do not open or mutilate the battery or batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling or hazardous waste center.
UPS Maintenance
WARNING
CAUTION
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
45
Page 52
UPS Maintenance
46
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 53
CHAPTER 7
SPECIFICATIONS
This section provides the following specifications for the Powerware 5125 models:
Electrical input and output
:
Weights and dimensions
:
Environmental and safety
:
Battery
:
Table 2. Model Specifications
Model Number
PW5125 2400 RM 2400 VA, 2250W 120V
PW5125 3000 RM 2880 VA, 2700W 120V PW5125 2400i RM 2400 VA, 2250W 230V PW5125 3000i RM 3000 VA, 2700W 230V
PW5125 3000e RM 3000 VA, 2700W 230V 180–288V
PW5125 3000g RM 3000 VA, 2700W 200–240V 160–288V
PW5125 3000j RM 2400 VA, 2250W 100V 82–120V
Power Levels
(rated at nominal inputs)
Nominal Voltage Input Voltage Range
90–144V
180–288V
Table 3. Weights and Dimensions
UPS EBM
Dimensions (WxDxH)
Weight 82 lb (37 kg) 121 lb (54.9 kg)
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
19.0” x 24.5” x 3.5” (2U) (48.3 x 62.2 x 8.9 cm)
19.0” x 24.5” x 3.5” (2U) (48.3 x 62.2 x 8.9 cm)
47
Page 54
Specifications
Table 4. Technical Specifications
Low Voltage Models High Voltage Models Operating Frequency 50/60 Hz, auto-sensing Frequency Range 46–64 Hz Noise Filtering MOVs and line filter for normal and common mode noise Input Connections 12-ft, L5-30P power cord 12-ft, 16A IEC-309 power cord
PW5125 3000e and 3000g RM models:
16A, IEC 320-C20 input connector
Regulation (Normal mode)
Regulation (Battery mode)
Voltage Waveform Sine wave Output Receptacles (1) L5-30R, (6) 5-15R (1) IEC 320-C19, (9) IEC 320-C13
-10% to +6% of nominal voltage
Nominal output voltage ±5%
Table 5. Environmentaland Safety
Low Voltage Models High Voltage Models
Operating Temperature 0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature 0°C to 25°C (32°F to 77°F) Transit Temperature -25°C to 55°C (-13°F to 131°F) Relative Humidity 5–95% noncondensing Operating Altitude Up to 2,000 meters above sea level Transit Altitude Up to 15,000 meters above sea level Audible Noise Less than 45 dBA Normal mode, typical load
Less than 50 dBA Battery mode
Surge Suppression ANSI C62.41 Category B (formerly IEEE 587), IEC 61000-4-5 Safety Conformance UL 1778, CAN/CSA C22.2, No. 107.1 UL 1778, CAN/CSA C22.2, No. 107.1;
EN 50091-1-1 and IEC 60950
Agency Markings UL, cUL UL and cUL; CE, TÜV-GS (model dependent) EMC FCC Part 15, ICES-003, VCCI EN 50091-2, FCC Part 15, ICES-003
48
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 55
Specifications
Table 6. Battery
Configuration (10) 12V, 5 Ah internal batteries EBM Configuration PW5125 120 EBM: 120V, 30A Type Sealed, maintenance-free, valve-regulated, lead-acid Charging Internal battery: less than 3 hours to 90% usable capacity at nominal line voltage after full load
discharge External battery: recharging at 80% load or less is recommended; no more than 16x discharge
time to 90% usable capacity at nominal line voltage after full load discharge; an external charger is recommended for faster recharge times when using more than 2 EBMs.
Monitoring Advanced monitoring for earlier failure detection and warning; auto detection of additional EBMs
(if using LanSafe III Power Management Software, the EBM configurator must be used for accurate reporting of EBM batterytimes).
Table 7. Battery Run Times (in Minutes at Full/Half Load)
Model Internal UPS Batteries 1EBM 2EBMs 3EBMs 4EBMs
2400 VA 7/19 35/73 60/124 85/177 110/229 3000 VA 5/15 25/61 49/103 69/146 90/190
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
49
Page 56
Specifications
50
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 57
CHAPTER 8
TROUBLESHOOTING
This section explains:
UPS alarms and conditions
:
How to silence an alarm
:
Service and support
:
Audible Alarms and UPS Conditions
The UPS has an audible alarm feature to alert you of potential power problems. Use Table 8 to determine and resolve the UPS alarms and conditions.
Battery Service
On Battery
General Alarm
Site Wiring Fault
Power On
Indicator Legend
Unlit Green Red
Flashing
On Button
Load Level Indicators
Figure 28. Alarm Indicators
Silencing an Audible Alarm
To silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing. The alarm does not silence if there is a low battery condition.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Off Button
Test/Alarm Reset Button
51
Page 58
Troubleshooting
Table 8. TroubleshootingGuide
Alarm or Condition Possible Cause Action
The indicator is not
on; the UPS does not start.
The indicator is
flashing; power is not available at the UPS output receptacles.
The UPS does not provide the expected backup time.
Continuous audible alarm.
The power cord is not connected correctly.
The wall outlet is faulty. Have a qualified electrician test and repair the outlet.
The UPS is in Standby mode.
The batteries need charging or service.
The self-test failed. Plug the UPS into a power outlet for at least 3 hours to
UPS internal temperature is too high.
Check the power cord connections.
Press the On button to supply power to the connected equipment.
Plug the UPS into a power outlet for 24 hours to charge the battery. After charging the battery, press and hold the button for 3 seconds; then check the indicator.
If the indicator is still on, see “UPS Maintenance”
on page 39 to replace the battery.
charge the battery. After charging the battery, press and hold the button for 3 seconds; then check the indicator.
If the indicator is still on, shut down the UPS and contact your service representative.
The UPS switches to Bypass mode, allowing the UPS to cool. Turn off and unplug the UPS. Clear vents and remove any heat sources. Ensure the airflow around the UPS is not restricted. Wait at least 5 minutes and restart the UPS. If the condition persists, contact your service representative.
|
1 beep every 5 seconds.
1 beep every 5 seconds.
52
The UPS is on battery. The UPS is powering the equipment with battery
power. Prepare your equipment for shutdown.
The battery is running low. 3 minutes or less of battery power remains (depending
on load configuration and battery charge). Save your work and turn off your equipment. The
alarm cannot be silenced.
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Page 59
Troubleshooting
ActionPossible CauseAlarm or Condition
The UPS is running on battery power because the input voltage is too high or too low.
1 beep every 5 seconds.
The utility line voltage and frequency are out of specification.
1 beep every 5 seconds.
1 beep every 5 seconds. Ground wire connection does
1 beep every 5 seconds. Bypass is not available. Input
The battery may be fully discharged.
The battery is not connected correctly.
not exist or the line and neutral wires are reversed in the wall outlet.
voltage is not within ±12% of
nominal or input frequency is not within ±3% of nominal.
The UPS continues to operate on battery until the condition is corrected or the battery is completely discharged. If the condition persists, the input voltage in your area may differ from the UPS nominal.
Have a qualified electrician check the wiring.
Plug the UPS into a power outlet for 24 hours to charge the battery. After charging the battery, press and hold the button for 3 seconds; then check the indicator.
If the indicator is still on, shut down the UPS and contact your service representative.
Check the battery connections. Call your service representative if the problem persists.
Have a qualified electrician correct thewiring.
The UPS is receiving utility power that may be unstable or in brownout conditions. The UPS continues to supply power to your equipment. If conditions worsen, the UPS may switch to battery power.
UPS is in Bypass mode. The equipment is transferred to utility power. Battery
mode is not available; however, the utility power continues to be passively filtered by the UPS. Check for one of the following alarms: Overtemperature, Overload, UPS Failure, or Battery Service.
Power requirements exceed UPS capacity (103 to 110% for 30 seconds) or the load is defective.
UPS fault condition. Save your work and turn off your equipment. Turn off
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Turn off and unplug the UPS. Remove some of the equipment from the UPS. Wait at least 5 seconds until all LEDs are off and restart the UPS. You may need to obtain a larger capacity UPS.
and unplug the UPS. Contact your service representative. The alarm cannot be silenced.
53
Page 60
Troubleshooting
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor
and ask for a UPS technical representative.
or the Help Desk at one of the following telephone numbers
In the United States: Europe, Middle East, Africa: Asia: Australia:
1-800-356-5737or1-608-565-2100 +44-17 53 608 700 +852-2830-3030 +61-3-9706-5022
Please have the following information ready when you call the Help Desk:
Model number
:
Serial number
:
Version number (if available)
:
Date of failure or problem
:
Symptoms of failure or problem
:
Customer return address and contact information
:
If repair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid for all warrantied units.
NOTE For critical applications, immediate replacement may be available. Call the
Help Desk for the dealer or distributor nearest you.
54
Powerware®5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Loading...