Powerware PW5110 User Manual

Powerware 5110 UPS
USER'S MANUAL
The Powerware 5110 uninterruptible power system (UPS) protects your sensitive electronic equipment from power problems such as power failures, power sags, power surges, brownouts, and line noise.
Features:
Processor-controlled voltage regulation Six outlets
-Three with surge and backup protection
-Three with surge protection only
Telephone line surge protection jacks Cold start capability USB communication port User-replaceable batteries
SAFETY INSTRUCTIONS
Once you have received the Powerware 5110 UPS product, you should remove and inspect the product for shipping damage. If any damage is found, please notify the carrier and your dealer. Please keep the shipping carton and the packing foam in the event the product must be returned to the factory for service.
ATTENTION: Maintenance must be performed by a qualified personnel. Failure to do so could result in an electric shock. Replace Battery with Powerware supplied Battery ONLY!. Although the unit may be unplugged from utility power, hazardous voltage still may be present through the battery.
BATTERY CONNECTION REQUIRED BEFORE USE! Connecting the Battery:
22
22
44
11 22
33 4 4
4.5 AH, 5 AH batteries (350 VA, 500 VA models)
7 AH battery (700 VA models)
33
Push at the top Edge to remove the battery cover
Push at the top Edge to remove the battery cover
Slide down to remove the battery cover
Slide down to remove the battery cover
Pull out the battery and connect the battery wire to the battery terminal
Reinstall the battery cover
44
33
Pull out the battery and connect the battery wire to the battery terminal
Reinstall the battery cover
7AH x 2, 9AH x 2 batteries (1000VA, 1500VA models)
Push at the top Edge to remove the battery cover
Slide down to remove the battery cover
Connect the battery cable Reinstall the battery cover
INSTALLATION AND OPERATION:
INDICATORS
1.On/Off Push Button
Push button switch that controls power to the UPS and initiates the self-test function.
Depress the push button to turn on the UPS. Depress the push button again to turn off the UPS.
The UPS will perform a self-test for about 5 seconds when the UPS is turned on.
2.AC mode (Green) LED
Indicates that AC utility power is present and regulated power (AVR) is applied to the connected equipment.
3.Fault / Warning (Red) LED
Indicates that a fault condition has occurred.
-Flashing Red LED indicates an overload condition or that the battery should be replaced.
-Solid On LED indicates that the output is shorted or an internal UPS fault exits. See the Indicator Table below for further detail.
4.Backup mode (Yellow) LED
Indicates that the UPS is operating on battery and providing regulated AC power to the backup only outlets and the connected equipment.
5.Battery Backup & Surge Protection Outlets
Four Australian output receptacles that provide both backup and surge protection.
6.Surge Protection Outlets
Four Australian output receptacles that provide surge and spike protection only.
7.Phone/Fax Protection Connectors
8.USB Communication Port
The built-in USB port connects to your computer. The LanSafe monitoring and shutdown software provided can automatically save your files and shut down your computer in the event of a prolonged power outage. The software also provides information regarding the status of your utility power line.
9.Circuit Breaker (resetable)
The button will protrude when the overload condition occurs. If the button protrudes, disconnect some non-essential equipment and reset the circuit breaker by pushing the button inward.
10.Power Cord
Australian plug type detached 1.8 meter line cord
1. Place the Powerware 5110 UPS indoors in an area that has adequate airflow and is free from excessive dust. Do NOT allow the UPS to be exposed to moisture, rain, excessive heat or direct sunlight.
2. Use of the Powerware 5110 UPS product in life support applications where failure of this equipment can reasonably be expected to cause failure of life support equipment or to significantly affect its safety or effectiveness is NOT recommended.
3. Always disconnect the input power cord from the wall outlet before replacing the battery.
4. When replacing the battery, use the same number and type of battery.
5. Do NOT dispose of the battery in a fire: the battery may explode.
6. Do NOT open or mutilate the battery. Batteries contain an electrolyte that is toxic and harmful to both the skin and eyes.
7. Proper disposal of the battery is required. Please refer to your local laws/regulations regarding battery disposal.
8. Use tools with insulated handles to replace the battery to avoid personal injury. Due to energy hazards, please remove wristwatches and jewelry such as rings when replacing battery.
Following steps explain how to connect and operate the Powerware 5110 UPS.
1. Connect the UPS to a grounded power outlet. Note: It is recommended that the battery should be charged for minimum 8 hours to ensure full charge before placing the UPS in service.
2. Plug your computer, monitor or load to be protected into the “Battery Backup & Surge Protection” outlets. (These outlets will provide emergency battery backup power during power outages as well as protection from surges and spikes.)
CAUTION: Do NOT plug LASER PRINTERS into the “Battery Backup” outlets. CAUTION: Do NOT plug ACCESSORY SURGE strips into the “Battery Backup”
outlets.
3. Plug your peripheral equipment or non-critical loads (printer, scanner, fax, speaker, etc.) into the “Surge Protection” outlets. (These outlets provide surge and spike protection only, they will NOT provide battery backup power during a utility power failure).
4. Connect your computer to the UPS using USB cable provided.
5. With your equipment turned off, switch on the UPS.
6. When the “On/Off” LED light is illuminated, turn on the connected equipment.
7. Install Power management software provided with the UPS
1
2 3
4
5
5
6
6
7
8
9
10
BATTERY REPLACEMENT PROCEDURE:
1.Disconnect the UPS from the power source and slide the battery door open.
See pictures 1 and 2.
2.Disconnect the battery and remove as indicated below. See pictures 3 and 4
3.Insert the replacement battery and reconnect the battery cables. See pictures 6 and 7
NOTE: It is important that the connectors be firmly attached to new batteries.
4.Reposition the battery door and slide closed. See pictures 8 and 9.
NOTE: Properly recycle used battery.
4.5AH, 5AH batteries (350VA, 500VA models)
STATUS INDICATORS
The UPS provides both visual and audible status indicators. Visual indicators consist of three LEDs to represent the following conditions: On utility power operation On battery power operation UPS fault/alarm
LED Indicator Table
On Utility (AC mode) On Battery (Backup mode) Low Battery Fault/Output Short Overload/Check Battery
Green Lighting Yellow Lighting Yellow Flashing Red Lighting Red Flashing
LED Audible Alarm Table
Backup mode Battery low Overload Replace battery Fault or output short circuit Battery over charge
Sounding every 5 seconds Sounding (two beeps) every 5 seconds Sounding every 0.5 seconds Sounding (three beeps) every 30 seconds Continuous sounding Sounding (three beeps) every 5 seconds
7AH x 2, 9AH x 2 batteries (1000VA, 1500VA models)
7AH x 1 battery (700VA models)
11 22 33
44 55 66
77 88 99
11 22 33
4 4 5 5 66
77 88 99
11 22 33
44 55 66
77 88 99
SPECIFICATIONS
PW5110 350A PW5110 500A PW5110 700A PW5110 1000A PW5110 1500A
Model Numbers
350 VA / 210W 500 VA / 300W 700 VA / 420W 1000 VA / 600W 1500 VA / 900W
Capacity
Nominal Output Voltage
Nominal Input Voltage
240Vac
240Vac
Automatic Voltage Regulation (AVR)
Frequency
Outlets
15%
50 / 60 Hz auto sensing
6 Outlets (3 Battery Backup & Surge Protection;
3 Surge Protection only)
Lighting / Surge Protection
Transfer time to Battery/AC
Battery Type
476 Joules
6ms typical
Maintenance free lead-acid battery
Battery Specification
Typical Backup Time
LAN / Phone / Fax Protection
Short Circuit Protection
Communication Port
Operation Temperature
Operation Relative Humidity
Storage Temperature
350 VA: 12V 4.5 Ah
500 VA: 12V 5 Ah
750 VA: 12V 7 Ah 1000 VA: (2) 12V 7 Ah x 2 1500 VA: (2) 12V 9 Ah x 2
3 MINUTES MINIMUM AT FULL RATED LOAD
RJ11
Circuit Breaker
USB
0 C~40 C
0 to 95% non-condensing
-15 C~50C
350 VA: 5.9 kg 500 VA:6.1 kg
700 VA: 7.5 kg 1000 VA: 13.2 kg 1500 VA: 13.7 kg
350/500/700 VA: 270 x 87 x 259mm
1000/1500 VA: 270 x 87 x 384mm
Net Weight
Dimensions (HxWxD)
* Due to continuing product improvement programs, specifications are subject to change without notice.
TROUBLESHOOTING
Symptom
Possible Cause
Action to Take
Ensure the UPS is securely connected to an AC outlet. Reduce the amount of equipment plugged into the “Battery Backup & Surge Protection” outlets of the UPS. Reset the circuit breaker by pushing it back in. Switch the UPS back on.
The UPS is not connected to the power source. Circuit Breaker has tripped.
UPS will not turn on
UPS is making a continuous sound and the “Overload” indicator is on
The “Battery Backup & Surge Protection” outlets are overload.
Turn off the UPS and reduce the amount of equipment connected to these outlets.
The UPS battery is discharged due to a power outage and has not recharged.
Charge the battery for 8 hours. The UPS runtime is reduced until the battery is fully charged.
Unplug non-essential equipment (printers, scanners, etc) from the Battery Backup outlets and plug into 'Surge Only' outlets
UPS does not provide expected runtime
Disconnect non-essential equipment from the UPS. Reset (push in) the circuit breaker and switch the UPS on. Plug equipment in one-at-a-time. If the circuit breaker trips again, disconnect the device that caused the breaker to trip. Replace the battery or the battery module. Unplug device from 'Surge Only' outlet and move to a 'Battery Backup outlet.
The UPS circuit breaker
tripped .
The battery has reached the end of its life. Equipment plugged into a Surge Only outlet.
Red LED Indicator ON
Internal UPS fault.
Contact Technical Support (see Service and Support below).
UPS does not power essential equipment during an outage
SERVICE AND SUPPORT
MA6B412008(2005/01/20)
Devices plugged into Back up & surge protection receptacles exceed the rated load for the UPS run time
Please have the following information ready:
Model number and serial number Symptoms of failure or problem Customer contact information
For additional information and to register your warranty, please visit
www.powerware.com.au
Register your warranty within 30 days and receive an extended pro-rated warranty and load protection guarantee.
Eaton Power Quality Pty Ltd 119-127 Wicks Road, North Ryde NSW 2113
For service and support please call your local distributor or the Powerware Australia National Service and Repair Centre.
Australia freecall 1300 303 059.
Loading...