Powerware Prestige 9 Series User Manual

02/20/2001
powerware®9
Prestige Series
User’s Guide
2500/3000 VA, 200-240V
www.powerware.com
The Powerware99 Prestige Series UPS configurations vary. Some configurations may or may not be classified by the Federal Communications Commission (FCC). If your Prestige unit is classified by these standards, the corresponding information applies:
Class A
NOTE This equipment has been tested and foundto comply with the limits for a Class A digital device, pursuantto
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energyand, if not installed andusedin accordance withthe instruction manual, may cause interference to radio communications. Operationof this equipmentin a residentialarea is likely tocause interferencein which case the user will be required to correct the interference at his own expense.
European EMC Statement
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies:
WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, in
which case, theusermay be requiredtotake additional measures.
EC Declaration of Conformity
Units that are labeled with a CE mark comply with the following EU directives: 73/23/EEC Council Directive on equipment designed for use within certain voltage limits.
93/68/EEC Amending Directive 73/23/EEC. 89/336/EEC Council Directive relating to electromagnetic compatibility.
The EC Declaration of Conformity is availableupon request forproducts witha CE mark. For copies of theE C Declaration of Conformity, contact:
Powerware Corporation Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452661 Fax: +358-9-452-66395
Powerware, PowerPass, Powercare, OnliNet, and OnliSafe are registered trademarksofPowerware Corporation. IBM and AS/400 are registered trademarks of International BusinessMachines Corp. Novell is a registered trademark of Novell, Inc. 3Com is a registered trademark of 3Com Corporation.
.
Copyright 1994-99 Powerware Corporation, Raleigh, North Carolina. All rights reserved. No part of this document may
be reproduced in any way withoutthe express writtenapproval of Powerware Corporation.
UPS QUICK INSTALLATION
1
UPS Cabinet
Battery Cabinet
2
ON
OFF
I
Battery Breaker
O
I
ON
,
21
OFF
O
UPS Quick Installation
3
Power Strip
4 The UPS output voltage is factory-configured for 230V.If you need to change the output
voltage, see “U PS Startup” on page 32.
5
UPS with PPDM Quick Installation
UPS WITH PPDM QUICK INSTALLATION
1
UPS Cabinet
Battery Cabinet
PowerPass Distribution Module (PPDM, 60 Hz)
2
3
ON
OFF
Bypass Switch (NORMAL Position)
I
Battery Breaker
O
I
ON
,
21
OFF
O
UPS with PPDM Quick Installation
4
5 The UPS output voltage is factory-configured for 230V.If you need to change the output
voltage, see “UPS with Optional PowerPass Module Startup” on page 42.
6
UPS with PPIM Quick Installation
UPS WITH PPIM QUICK INSTALLATION
1
PowerPass Isolation Module
(PPIM, 50 Hz)
UPS Cabinet
Battery Cabinet
UPS with PPIM Quick Installation
2
Bypass Switch (NORMAL Position)
3
ON
OFF
I
Battery Breaker
O
I
ON
,
21
OFF
O
4
5 The UPS output voltage is factory-configured for 230V.If you need to change the output
voltage, see “UPS with Optional PowerPass Module Startup” on page 42.
6
TABLE OF CONTENTS
1 Introduction 1....................................................
UPSModelandBatteryConfigurations 2..............................................
LoadRequirements 2.........................................................
BatteryTimes for the Prestige3000 3..............................................
BatteryTimes for the Prestige3000withPPDM 4.....................................
SpecialSymbols 5..............................................................
2 Safety Warnings 7.................................................
Sikkerhedsanvisninger 8.........................................................
Belangrijke Veiligheidsinstructies 10..................................................
Tärkeitäturvaohjeita 11..........................................................
Consignesde sécurité 13..........................................................
Sicherheitswarnungen 14.........................................................
РспейдпрпйЮуейт БуцЬлейбт
Avvisidi sicurezza 18.............................................................
Viktig Sikkerhetsinformasion 20.....................................................
RegulamentosdeSegurança 21.....................................................
Предупреждения по мерам безопасности 23...................................
Advertenciasde Seguridad 25......................................................
Säkerhetsföreskrifter 26..........................................................
3 Installation 29.....................................................
Unpackingand Inspection 29.......................................................
UPSandBatteryCabinetStorage 29...............................................
Selectingan Installation Option 29...................................................
UPSandBatteryCabinetInstallation 30...............................................
UPSStartup 32..............................................................
REPOInstallation 34...........................................................
UPSwithOptionalPowerPass Module Installation 35.....................................
UPSwithOptionalPowerPass Module Startup 42......................................
Troubleshooting Tips 44...........................................................
16................................................
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
i
Table of Contents
4 UPS Operation 45..................................................
UPSFrontPanel 45..............................................................
OperatingModes 46.............................................................
NormalMode 46.............................................................
BypassMode 47.............................................................
BatteryMode 47.............................................................
Diagnostics 48.................................................................
BatteryTest on Demand 48......................................................
BatteryStart 48................................................................
UPSShutdown 49...............................................................
ChangingtheOutputVoltage 49.....................................................
UsingthePowerPassModule 50....................................................
UsingMaintenance Bypass 51....................................................
5 Communication 57.................................................
InitialCommunicationsSettings 57...................................................
FrontPanelCommunications Access 58...............................................
UPSSerialCommunications Menu 60.................................................
PowerManagementSoftware 63....................................................
UPSCommunications Interface Port 64................................................
Communications Mode ReferenceChart 65.............................................
6 Specifications 67..................................................
Prestige3000Model2500 Specifications 67............................................
Prestige3000Model3000 Specifications 67............................................
Prestige3000UPSPhysical Specifications 67...........................................
Model2500 Specifications with the 60-Hz PPDM 68......................................
Model2500 Specifications with the 50-Hz PPIM 68.......................................
Model3000 Specifications with the 60-Hz PPDM 69......................................
Model3000 Specifications with the 50-Hz PPIM 69.......................................
Prestige3000UPSTechnicalSpecifications 70..........................................
7 Troubleshooting 71.................................................
ResettingtheUPS 73............................................................
Silencing the Alarm 73...........................................................
Serviceand Support 74...........................................................
Index 75.........................................................
ii
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
CHAPTER 1
INTRODUCTION
Congratulations on the purchase of your Powerware99 Prestige Series uninterruptible power system (UPS). The Prestige UPS meets the toughest measuresof superiordesignand manufacturing, including ISO 9001. Younow own the most reliable power protectionavailable.
The Prestige 3000 provides a steady, well-regulate d powe r supply for yourcomputing and communications equipment,whileprotecting it from the frequent irregularities that are inherent in commercially available power.Voltage spikes, power surges, brownouts, and power failures have the potentialto corrupt critical data, destroy unsaved work sessions, and in some instances,damageexpensivehardware.
Withthe Prestige 3000, you can safely eliminate the effects of electrical linedisturbances and guard the integrityof your systems and equipment. The optional PowerPass PowerPass IsolationModule (PPIM)have a MaintenanceBypassfeature that suppliespower to your equipmenteven when the UPS electronics areremovedfor maintenanceor upgrades.Figure 1 showsthe Prestige 3000 UPS.
9
DistributionModule(PPDM)and
Figure1.Prestige3000 UPS
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
1
Introduction
UPS Model and Battery Configurations
ThisUPS is designed to work with single-phase, three-wire, AC power sources. There are two importantconsiderations whenselectingthe UPS model and battery configuration to properly safeguard your equipment:
:
Load requirements
:
Battery times
Load Requirements
The load is the equipment to be protectedby the UPS. Select the UPS model that meets the power consumption requirements of the load in volt-amperes (VA). The total load VA shouldnot exceed the UPSVA rating. To determinethe total load requirements:
1. Obtainthe load ratingsfrom either the nameplate or operator’s manual of the equipment to be protected by the UPS. The ratings are listed in either watts (W), amperes or amperes max (A), or volt-amperes.
2. If the rating is in watts, multiplyby 1.4 to obtain the VA requirement (thisis the typicalrelationship between watts and volt-ampere ratings in most computing equipment). However, in some new computing equipment, the power supply is power-factor corrected and the watts ratingequalsthe VA requirement.Check with the manufacturer to determine applicability.
If the ratingis in amperesor amperes max, multiply by the inputvoltage to obtain the VArequireme nt.
3. Add all of the resultant V A ratings together to obtain the total load requirements of the equipment to be protected(see Figure 2). If the load consistsof the power-factorcorrected supplies, it is recommended to use total watts for the load requirements.
2
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Introduction
)
Load(VA
)
3 COMPUTERS 3 MONITORS EXTERNAL
200 WATTS
EACH
3x200WATTSx1.4=840VA 3x1AMPx240=720VA 50VA
840 VA+ 720 VA+ 50 VA= 1610 VA(Total Load Requirements)
1AMP
EACH AT 240V 50 VA
MODEM
Figure 2. Volt-Amperes Calculation Example
If the total load requirements of the equipment exceeds the capacity of the UPS, you must eitherreducethe number of pieces of equipment,or use a UPS with a larger load capacity.
Whendecidingon which pieces of equipmentto removefromthe UPS, select equipmentthat has a lower priorityforpower protection. Computers, monitors, and modems typically have a higher priority becausethey could be processing or transmitting data when a power outage occ urs.
Battery Timesfor the Prestige 3000
During a power failure, the UPS battery supplies power to your equipment, providing time to complete computing activities prior to UPS shutdown.The duration of this time period is directly related to the UPSbattery configuration. By addingbattery cabinets,you can customize the UPS to provide enoughbattery time for normal processing activities.
Load(VA
at.7PF*
600 420 36.8 88 146
800 560 27.6 66 110 1200 840 18.4 44 73 1600 1120 13.7 33 54 2000 1400 10.7 26 42 2500 1750 8.3 20 33 3000 2100 6.5 16 27
*
T ypicalPower Factor (PF)
NOTE
Battery times shown also apply to the Prestige 3000with PPIM.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
Load(W)
Average BatteryTime (inMinutes)
1Cabinet 2Cabinets 3Cabinets
3
Introduction
Battery Timesfor the Prestige 3000 with PPDM
Load(VA) Load(W)
600 402 36.8 88 146
800 533 27.6 66 110 1200 800 18.4 44 73 1600 1067 13.7 33 54 2000 1333 10.7 26 42 2500 1667 8.3 20 33 3000 2000 6.5 16 27
Average BatteryTime (inMinutes)
1Cabinet 2Cabinets 3Cabinets
4
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Special Symbols
Introduction
The following common symbols ma y be found on the UPS:
LOAD ON - Press the button with this symbol to energize the
outputreceptacles (OutputOn).
LOAD OFF - Pressthe button with this symbol to de-energize
the output receptacles (OutputOff).
SAFETY EARTHINGTERMINAL - Indicates the primary safety
ground.
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric
shock is presentand the associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your
operator’s manual for additional information.
BYPASS - Indicates bypass control switches.
INPUT BREAKER - Indicates the input breaker,whichshuts
off utility power to the UPS electronics.
BATTERY BREAKER - Indicates the battery breaker, which
shutsoff battery power (power transmission throughthe battery cord).
BATTERYCONNECTOR - Indicates the battery connector,
which remainselectrically “hot” even with the battery breaker off. Keep covered when not in use.
OUTPUT BREAKER - Indicates an output breaker.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
5
Introduction
6
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
CHAPTER 2
SAFETY WARNINGS
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.This manual containsimportantinstructions that you shouldfollowduring installationofthe UPS.Pleasereadallinstructions before operatingthe equipmentand savethismanualforfuturereference.
ThisUPScontainsLETHAL VOLTAGES.Allrepairsand serviceshould be performed byAUTHORIZED SERVICEPERSONNEL ONLY.There are NO USER SERVICEABLE PARTS insidetheUPS.
:
Batteriescanpresentariskof electricalshock or burn from high short circuit current.Observeproper precautions.
:
Proper disposalofbatteriesisrequired. Refer to your local codesfor disposal requirements.
:
ThisUPScontainsits own energy source (batteries).The output receptaclesmay carrylivevoltage even when the UPS is not connected to an AC supply.
:
Neverdispose of batteriesinafire.Batteriesmayexplodewhenexposedtoflame.
DANGER
CAUTION
:
Neveropen or mutilatebatteries.Released electrolyteis harmful to the skinand eyes,andmaybeextremelytoxic.
:
Useonly the power supplycordprovided with thisUPS.Thepowercordis wiredin accordancewithNational ElectricalCode(NEC)specifications.Be sure the wall outletto be used with the UPS iswiredinaccordancewiththese same specifications in order to avoid damage to your equipment. Be sure that overcurrentprotectionfortheACoutletisprovidedat the timeof installation.Be surethe input plug iscompletelyinserted into the wall outlet.Useasingle-phase, three-wire,groundedACoutletonly.
:
To reducethe riskoffireor electricshock, installthisUPSinatemperatureand humiditycontrolled,indoorenvironment,freeofconductivecontaminants.Ambient temperaturemustnotexceed104F(40C).Donotoperatenear water or excessive humidity (95% max).
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
7
Safety Warnings
:
Donot removeor unplug the input cord when the UPS is turned on. This removes the safetyground from the UPS and the equipment connected to the UPS.
:
To complywithinternationalstandardsand wiringregulations,the totalequipment connectedtotheoutput of this UPS mustnot have an earth leakage current greater than 2.75 milliamperes.
:
The walloutletmustbewithin2metersoftheequipmentandaccessible to the operator. The on/offswitchontheUPSdoesnotelectrically isolatethe internal parts.Unplugtheinputcordfromthewalloutletwhendisconnecting the unit for longperiodsoftime.
:
Pleasenotethat the output socketsonthe UPS are electricallylivewheneverthe UPSOutput
:
For PowerPass systems with hardwired outputs, overcurrent protection for the output ACcircuit(s) is to be provided by others.
:
ForPowerPasssystemswithhardwiredoutputs,suitablyrated disconnectswitches for the output AC circuit(s)are to be providedbyothers.
Sikkerhedsanvisninger
Onbutton ispressed,eveniftheinputcordisdisconnected.
VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER DENNEBRUGERVEJLEDNING INDEHOLDERVIGTIGE SIKKERHEDSANVISNINGER
FARE
DenneUPSindeholderLIVSFARLIGHØJSPÆNDING.Alle reparationer og vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ensindvendige dele kan repareres af brugeren.
ADVARSEL
:
Batterierkanudgøreenfare forelektriskstødeller forbrændingerforårsagetaf høj kortslutningsspænding.Dekorrekteforholdsregler bør overholdes.
:
Korrektbortskaffelseafbatterierer påkrævet.Overholdgældendelokalereglerfor bortskaffelsesprocedurer.
:
DenneUPSindeholderegenenergiforsyning (batterier). Udgangsnetstikkene kan ledestrøm,selvnår UPS’en ikkeer tilsatenAC-energikilde.
8
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Safety Warnings
:
Skafdigaldrigafmedbatteriernevedatbrændedem.Batterierne kaneksplodere vedåben ild.
:
Batteriernebøraldrigåbnesellerskillesad. Elektrolyt, derslipper ud, er skadelig for hud og øjne og kan være overordentliggiftig.
:
Brugkunden netledning,somblevleveret medUPS’en.Dennenetledninger tilsluttetifølge specifikationernefor NEC (NationalElectrical Code). Sørg for,at stikket,somskalbrugestilUPS’en, er tilsluttetifølge de sammespecifikationer for at undgå skade på dit udstyr. Sørg for,atderer overstrømsbeskyttelse på AC-stikket på monteringstidspunktet. Sørg for,atstikket er sat helt ind i stikkontakten. Brug en enfaset,-treledetAC-kilde, som er jordet.
:
Installérdenne UPSiettemperatur- og fugtighedskontrolleretindendørsmiljø,frit for ledende forureningsstofferforatformindskerisikoen for brand og elektrisk stød.Rumtemperaturenmåikke overstige40°C.UPS’en bør ikkebetjenesnær vandellerhøjfugtighed(maksimalt 95%).
:
Netledningenmåikkefjernes og stikketmå ikketrækkesud, mens UPS’ener tændt.Dettefjernersikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.
:
Ioverensstemmelsemedinternationalenormerogbestemmelserforel-installation mådet udstyr, der er forbundet tiludgangen af denne UPS, tilsammenikke overskride en jordafdelingsspænding på mere end 2,75 milliampere.
:
Stikkontakten måhøjstvære2meterfra udstyretogtilgængelig for brugeren. UPS’ensafbryderkontakt isolererikkeelektrisk de indvendigedele.Træk derfor stikketud af kontakten,hvisenheden er slukketilangtidadgangen.
:
Bemærkvenligst, at stikkontakternepåUPS’enerstrømførende,når knappenUPS “Output
On”er trykket ned, selvomindgangsnedledningenikke er tilsluttet.
:
Med hensyn tilBypass-systemer med direkte forbundneudgange,skal overstrømsbeskyttelsenfor AC-kredsen(e)komme andetsteds fra.
:
Med hensyn tilBypass-systemer med direkte forbundneudgange,skal afbryderkontaktertilAC-kredsløbetmedpassendemærkeeffektkommeandetsteds fra.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
9
Safety Warnings
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAARDEZE INSTRUCTIES DEZEHANDLEIDINGBEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES
DezeUPSbevatLEVENSGEVAARLIJKE ELEKTRISCHESPANNING. Allereparatiesen onderhoud dienen UITSLUITEND DOOR ERKENDSERVICEPERSONEELte worden uitgevoerd.Erbevindenzich GEENONDERDELEN in de UPSdieDOOR DE GEBRUIKER kunnenwordenGEREPAREERD.
:
Batterijenkunnengevaarvoorelektrische schokof brandwonden veroorzakenals gevolgvanunhoge kortsluitstroom. Volgdedesbetreffendeaanwijzingenop.
:
Debatterijenmoetenop dejuistewijzewordenopgeruimd.Raadpleeghiervooruw plaatselijke voorschriften.
:
DezeUPSbevatzijneigen energiebron (batterijen).Deuitgangsaansluitingen kunnenonder spanningstaan wanneerdeUPSnietopeenwisselstroomvoedingis aangesloten.
:
Nooitbatterijeninhetvuurgooien.Debatterijenkunnen ontploffen.
:
Nooitbatterijenopenenof beschadigen.Vrijkomendelektrolytisschadelijkvoorde huiden ogen, en kan uiterstgiftigzijn.
:
Uitsluitend het elektriciteitssnoer gebruikendat bijdezeUPSwordtgeleverd.Het snoeris volgensde specificatiesvandeIEC (InternationalElectricalCode)bedraad. ControleerofwandcontactdooswaaropdeUPSwordtaangesloten,volgens deze zelfdespecificaties isbedraad teneinde schadeaan uw apparatuur te voorkomen. Controleerofhet wandcontactdoosvoldoendeis afgezeherd. Controleer of de voedingsstekker goed in het stopcontactisgestoken. Gebruikuitsluitend een enkelfasiggeaard wandcontactdoosmetrandaarde.
GEVAAR
OPGELET
10
:
Teneinde de kansopbrand of elektrischeschokte verminderen dient deze UPS in een gebouw met temperatuur-envochtigheidregeling te worden geïnstalleerd,
waargeen geleidendeverontreinigingen aanwezigzijn.Deomgevingstemperatuur mag40ECnietoverschrijden.Niet gebruikenindebuurtvan water ofbijzeerhoge vochtigheid(max. 95%).
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Safety Warnings
:
Verwijder de ingangsnoer niet of haal de stekkervandeingangsnoerernietuit terwijlde UPSaanstaat.Hierdoorzoude UPSenuwaangeslotenapparatuurgeen aardebeveiliging meer hebben.
:
Omaande internationalenormenenbedradingsvoorschriften te voldoenmagde geheleapparatuur die op de uitgang van deze UPS is aangesloten,geen aardlekstroom van meer dan 2,75 milliampèrehebben.
:
Dehoofdvoedingcontactdoosmoet zich op minder dan 2 meter van de apparatuur bevindenenmakkelijkbereikbaar zijn voor de gebruiker.De aan/uit-schakelaarop de UPSbiedtgeen elektrischeisolatievoorde inwendigeonderdelen.Destekker uitde voedingcontactdooshalen wanneer het apparaat voor lange tijdnietwordt gebruikt.
:
Neemer nota van dat de uitgangaansluit punten op de UPS altijd onder stroom staanwanneerde belastingschakelaar ( aanwezigheidvandevoeding.
:
Voor Bypass systemenmet vast-bedrade uitgangen, moet de overstroombeveiliging voorwisselstroom uitgangcircuit(s)door derden worden geleverd.
:
VoorBypass Module systemen met vast-bedrade uitgangen, moeten de juiste hoofdschakelaarsvoor wisselstroomuitgangcircuit(s)door derden worden geleverd.
|
)wordtingedrukt,ongeachtde
Tärkeitä turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI
SÄILYTÄ NÄMÄ OH JEET TÄMÄ OPAS SISÄLTÄÄTÄRKEITÄ TURVAOHJEITA
VAARA
Tämä UPSsisältääHENGENVAARALLISIAJÄNNITTEITÄ. Kaikkikorjaukset ja huollot on jätettäväVAIN VALTUUTETUNHUOLTOHENKILÖN TOIMEKSI. UPS eisisällä MITÄÄNKÄYTTÄJÄN HUOLLETTAVIAOSIA.
VARO
:
Akustosaattaaaiheuttaasähköiskun tai syttyätuleen,josakusto kytketään oikosulkuun. Noudata asianmukaisiaohjeita.
:
Akustotäytyy hävittää säädösten mukaisellatavalla.Noudata paikallisia määräyksiä.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
11
Safety Warnings
:
Tämä UPSsisältääoman energialähteen (akuston).Ulostuloliittimissä voi olla jännite,kunUPSei ole liitettynä verkkojännitteeseen.
:
Äläkoskaanheitä akkuja tuleen.Ne voivaträjähtää.
:
Äläavaatairikoakkuja. Paljastunutelektrolyytti on vahingollinen iholleja silmille ja voi olla erittäin myrkyllistä.
:
KäytävaintämänUPS-laitteen mukanatoimitettuavirtakaapelia,jokaonkytketty kansallisten määräysten mukaisesti. Varmista,että UPS-laitteen kanssa käytetty pistorasiaon johdotettunäidensamojenmääritysten mukaisesti,jottalaitteet eivätvahingoittuisi. Varmista myös, että asennuksenyhteydessävaihtovirran pistorasiavarustetaanylivirtasuojauksella.Työnnäkosketinkokonaanpistorasiaan. Käytä pelkästään yksivaihteista, kolmijohtoista,maadoitettuaverkkopistorasiaa.
:
Vähentääksesitulipalonjasähköiskunvaaraaasenna tämä UPS sisätiloihin, joissa lämpötilaja kosteus on säädettävissäjajoissa ei ole virtaa johtavia epäpuhtauksia.Ympäristönlämpötilaeisaaylittää40C.Äläkäytälähellä vettäja vältä kosteita tiloja (95 % maksimi).
:
Äläpoistataiirrotasisääntulojohtoa,kunUPSon kytkettynä.Tämä poistaa turvamaadoituksen UPS-laitteesta jasiihenliitetystä laitteistosta.
:
Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän UPS-laitteenulostulokytkentöjenyhteinenmaavuotovirta eiylitä 2,75 milliampeeria(mA).
:
Päävirtapistokkeen täytyyolla2m:nsäteellälaitteistosta ja käyttäjänsaatavilla. UPS-laitteenvirtakytkineierotasisäosia verkkojännitteestä.Irrota sisääntulopistoke,joskytketlaitteen pois käytöstäpitkähköksi ajaksi.
:
Otamyöshuomioon,että UPS-laitteenulostuloliittimissä on jännite aina kun painetaanUPSinlähtötehoPÄÄLLÄ -painiketta(
|
),riippumattasiitä, onko
tulokaapelikytkettynätaiei.
12
:
Tämänlaitteenmukanaeitoimitetalähdön ylivirtasuojausta kiinteänasennuksen ohitusjärjestelmissä.
:
Tämänlaitteenmukanaeitoimitetalähdön johdonsuojakatkaisijoita jakeluja vartenkiinteänasennuksen ohitusjärjestelmissä.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMP ORTANTES
CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES
CetonduleurcontientdesTENSIONSMORTELLES.Toute opération d’entretien et de réparationdoitêtre EXCLUSIVEMENT CONFIÉEAUNPERSONNEL QUALIFIÉ AGRÉÉ. AUCUNEPIÈCE RÉPARABLE PARL’UTILISATEURnesetrouvedansl’onduleur.
:
Lesbatteriespeuventprésenterunrisquededéchargeélectriqueoudebrûlurepar descourts-circuits de haute intensité.Prendre lesprécautionsnécessaires.
:
Unemiseaurebutréglementairedesbatteriesestobligatoire. Consulterles règlementsenvigueurdansvotrelocalité.
:
Cetonduleurrenfermesapropre sourced’énergie(batteries). Les prisesde sortie peuventêtre soustensionmêmelorsquel’onduleur n’est pas branchésurle secteur.
:
Ne jamaisjeterlesbatteries au feu. L’expositionauxflammesrisque de les faire exploser.
:
Ne jamaisouvrirou mutilerdesbatteries.L’électrolytedégagéestnuisible à la peau et aux yeuxet peut s’avérerextrêmementtoxique.
:
Utiliser uniquementlecordond’alimentationfourni avec l’onduleur. Ce cordon est câbléconformémentauxspécificationsduCode électriqueinternational(CEI). S’assurerquelecâblage de la prisesecteur devantêtre utiliséeavecl’onduleurest luiaussiconforme à ces spécificationspour éviter d’endommager le matériel. S’assurerque laprisesecteurestprotégéecontrelessurchargesau moment de l’installation. S’assurer quela prised’entrée est insérée à fond dans la prise secteur.Utiliser uniquementune prise secteuràtroisfils,monophasée et miseàla terre.
:
Pour réduire lesrisquesd’incendie et de déchargeélectrique,installerl’onduleur uniquementàl’intérieur,dansunlieudépourvudematériauxconducteurs,où la températureetl’humidité ambiantessontcontrôlées.Latempérature ambiantene doitpasdépasser40
excessivement humide (95 % maximum).
Safety Warnings
DANGER!
ATTENTION!
°
C.Ne pas utiliseràproximitéd’eau oudansuneatmosphère
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
13
Safety Warnings
:
Ne pas retirer le cordon d’alimentationlorsque l’onduleurestsoustensionsous peinede supprimerlamiseàlaterredel’onduleuretdumatérielconnecté.
:
Afind’êtreconformeauxnormesetrèglementsinternationaux de câblage,le courantde fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleurnedoitpasdépasser2,75 mA.
:
Laprisesecteurdoitsetrouveràmoinsde 2 m du matériel et être accessibleà l’utilisateur.L’interrupteur de ON/OFF(marche/arrêt) de l’onduleur n’assure pas l’isolation électrique des pièces internes. Débrancher le cordon d’alimentation de laprisesecteurencasdedéconnexion de l’appareilpendantunepériode prolongée.
:
Noter que les prisesdesortiedel’onduleursontsoustension lorsque Output
buttonestenfoncé,mêmesilecordond’alimentationestdébranchéde la prise secteur.
:
Pour lessystèmes de bypass dotésde sortie à bornier ,la protection contreles surintensitésdes circuitsdesortiedecourantalternatifestàseprocurerauprès d’unautre fournisseur.
:
Pourlessystèmesde bypassdotés de sortieàbornier,lesinterrupteurs adaptésau circuitde courantalternatifsontàseprocurerauprèsd’unautrefournisseur.
On
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGENANLEITUNGEN AUFBEWAHREN.DIESES HANDBUCH ENTHÄLT WICHTIGE
SICHERHEITSANWEISUNGEN.
DieUSV führt lebensgefährlicheSpannungen.Alle Reparatur- und Wartungsarbeiten solltennurvonKundendienstfachleuten durchgeführt werden. Die USVenthältkeine vomBenutzerzuwartendenKomponente
:
Batterienkönnenaufgrunddeshohen Kurzschlußstroms Elektroschocksoder Verbrennungenverursachen. DieentsprechendenVorsichtsmaßnahmensind unbedingtzubeachten.
:
DieBatterienmüssen ordnungsgemäßentsorgtwerden.Hierbeisind die örtlichen Bestimmungenzu beachten.en.
14
WARNUNG
VORSICHT!
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Safety Warnings
:
DieseUSVist mit einer eigenen Energiequelle(Batterie)ausgestattet. An den Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USVnichtan einerWechselspannungsquelleangeschlossen ist.
:
Batterienniemalsverbrennen, da sie explodierenkönnen.
:
Batteriennieöffnenoderanderweitigbeschädigen.DerdarinenthalteneElektrolyt wirktätzendaufHautundAugen.EsbestehtVergiftungsgefahr!
:
Nur das Netzkabelverwenden,dasdieser USVbeiliegt.DiesesKabelistgemäß den Spezifikationendes International ElectricalCode (IEC)verdrahtet. Sicherstellen, daß die Wandsteckdose,die für die USV verwendet wird,gemäß den selbenSpezifikationen verdrahtet ist, um eine eschädigungder Gerätezu vermeiden.Sicherstellen,daßbeiInstallation ein Überstromschutzfürdie Wechselstromsteckdosevorhandenist.Sicherstellen,daß der Eingangsstecker vollständig in die Wandsteckdoseeingesteckt wurde. Nur eine einphasige, geerdete Dreileiter-Wechselstromsteckdoseverwenden.
:
UmdieBrand- oder Elektroschockgefahr zu verringern,dieseUSV nur inGebäuden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitendenSchmutzstoffen vorhandensind.DieUmgebungstemperatur darf 40EC nichtübersteigen.Die USV nichtinder Nähe von Wasseroderinextremhoher Luftfeuchtigkeit (max. 95 %) betreiben.
:
DasEingangskabelnichtentfernen oder abziehen,währenddieUSVeingeschaltet ist,weilhierdurch die SicherheitserdungvonderUSVunddendaran angeschlossenen Geräten entfernt wird.
:
Uminternationale Normen und Verdrahtungsvorschriftenzuerfüllen,dürfendiean den AusgangdieserUSVangeschlossenen Geräte zusammeneinen Erdschlußstrom von insgesamt 2,75 Milliampere nicht überschreiten.
:
DieNetzsteckdose,diezurHauptversorgungverwendetwird,darfsichnichtweiter als2Meter vomGerätwegbefindenund muß für den Bediener erreichbar sein. DerEin-/Aus-SchalterderUSVbietet keineelektrische Isolationder internenTeile. WenndasGerätlängereZeitnichtbenutzt wird,sollte esvonder Netzsteckdose abgezogenwerden.
:
Beachten,daß die Ausgangssteckdosen aufderUSVjedesmalStrom führen,wenn der Belastungsschalter (
|
)gedrücktwird,ungeachtet dessen, ob die USV mit
Stromversorgtwird.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
15
Safety Warnings
:
FürBypass-Systememitfestverdrahteten Eingängen mußder Überstromschutzfür dieAusgangswechselstromkreiseanderweitig bereitgestelltwerden.
:
FürBypass-Systememitfestverdrahteten AusgängenmüssenTrennschalterfürdie Ausgangswechselstromkreise mitpassendemNennwertanderweitigbereitgestellt werden.
РспейдпрпйЮуейт БуцЬлейбт
УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ ЦХЛБОФЕ БХФЕУ ÔÉÓ ПДЗГЙЕУ ÔÏ РБСПН ЕГЧЕЙСЙДЙП РЕСЙЕЧЕЙ УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ
Áõôü ôï UPS ресйЭчей ИБНБФЗЦПСБ ÔÁÓÇ. ¼ëåò ïé ерйукехЭт êáé ïé ухнфзсЮуейт рсЭрей íá гЯнпнфбй ÌÏÍÏ ÁÐÏ ЕОПХУЙПДПФЗМЕНП ÃÉÁ ÔÇ УХНФЗСЗУЗ РСПУЩРЙКП. Ôï UPS ÄÅÍ РЕСЙЕЧЕЙ КБНЕНБ ЕОБСФЗМБ ÐÏÕ ÍÁ МРПСЕЙ ÍÁ ЕРЙУКЕХБУФЕЙ ÁÐÏ ÔÏ ЧСЗУФЗ.
КЙНДХНПУ
16
РСПУПЧЗ
:
Ïé ухуущсехфЭт мрпсеЯ íá рспкблЭупхн злекфспрлзоЯб Þ Эгкбхмб áðü хшзль сеэмб всбчхкхклюмбфпт. ЛбмвЬнефе ôéò кбфЬллзлет рспцхлЬоейт.
:
БрбйфеЯфбй ущуфЮ дйЬиеуз ôùí ухуущсехфюн. ДеЯфе ôïõò фпрйкпэт кбнпнйумпэт ðïõ бцпспэн ôéò брбйфЮуейт дйЬиеуЮт ôïõò.
:
Ôï ухгкексймЭнп UPS ресйЭчей ôç äéêÞ ôïõ ðçãÞ енЭсгейбт (ухуущсехфЭт). Ïé сехмбфпдьфет еоьдпх мрпсеЯ íá Эчпхн енесгь ôÜóç бкьмз êáé üôáí ôï UPS äåí еЯнбй ухндедемЭнп óå ðçãÞ енбллбууьменпх сеэмбфпт (AC).
:
ÐïôÝ ìçí рефЬфе ôïõò ухуущсехфЭт óôç цщфйЬ, гйбфЯ мрпсеЯ íá ексбгпэн.
:
ÐïôÝ ìçí бнпЯгефе Þ кбфбуфсЭцефе ôïõò ухуущсехфЭт. Ï злекфсплэфзт ðïõ èá брелехиесщиеЯ мрпсеЯ íá рспкблЭуей влЬвз óôï дЭсмб êáé ôá мЬфйб, êáé мрпсеЯ íá еЯнбй еобйсефйкЬ фпойкьт.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Safety Warnings
:
ЧсзуймпрпйеЯфе ìüíï ôï кблюдйп фспцпдпуЯбт ðïõ рбсЭчефбй ìáæß ìå ôï UPS. Ôï кблюдйп áõôü еЯнбй кбфбукехбумЭнп уэмцщнб ìå ôéò рспдйбгсбцЭт ôïõ Еинйкпэ Злекфсйкпэ Кюдйкб (National Electrical Code) (NEC). ВевбйщиеЯфе üôé ç енфпйчйумЭнз рсЯжб ðïõ рськейфбй íá чсзуймпрпйЮуефе ìå ôï UPS еЯнбй кблщдйщмЭнз уэмцщнб ìå ôéò Ядйет рспдйбгсбцЭт, þóôå íá брпцехчиеЯ фхчьн влЬвз óôïí еопрлйумь óáò. ВевбйщиеЯфе üôé хрЬсчей уэуфзмб рспуфбуЯбт áðü хресЭнфбуз ãéá ôçí рсЯжб енбллбууьменпх сеэмбфпт (AC) ôçí þñá ôçò егкбфЬуфбузт. ВевбйщиеЯфе üôé ï сехмбфплЮрфзт ейуьдпх Ý÷åé фпрпиефзиеЯ ущуфЬ óôçí рсЯжб фпЯчпх. ЧсзуймпрпйЮуфе ìüíï мпнпцбуйкЮ, фсйуэсмбфз, гейщмЭнз рсЯжб AC.
:
Ãéá íá мейюуефе ôïí кЯндхнп рхскбгйЬт Þ злекфспрлзоЯбт, егкбфбуфЮуфе ôï ухгкексймЭнп UPS óå еущфесйкь ÷þñï ìå елегчьменз иесмпксбуЯб êáé хгсбуЯб, ï прпЯпт íá ìçí ресйЭчей бгюгймб хлйкЬ. Ç иесмпксбуЯб ресйвЬллпнфпт äåí рсЭрей íá оереснЬей ôïõò 40° C. Ìç чсзуймпрпйеЯфе ôï UPS кпнфЬ óå íåñü Þ хресвплйкЮ хгсбуЯб (мЭгйуфз ôéìÞ: 95%).
:
Ìçí вгЬжефе áðü ôçí рсЯжб ôï кблюдйп фспцпдпуЯбт üôáí ôï UPS еЯнбй бнпйчфь. Ì
áõôü ôïí фсьрп бцбйсеЯфе ôç геЯщуз буцблеЯбт áðü ôï
UPS êáé áðü ôïí еопрлйумь ðïõ еЯнбй ухндедемЭнпт ìå ôï UPS.
:
Ãéá íá ухмцщнеЯ ìå ôá дйеинЮ рсьфхрб êáé ôïõò кбнпнйумпэт кблщдЯщузт, ôï сеэмб дйбсспЮт ðñïò ôç ãç пльклзспх ôïõ еопрлйумпэ, ðïõ еЯнбй ухндедемЭнпт ìå ôçí Эопдп ôïõ ухгкексймЭнпх UPS, äåí рсЭрей íá еЯнбй мегблэфесп áðü 2,75 mA.
:
Ç рсЯжб фпЯчпх äåí рсЭрей íá всЯукефбй óå брьуфбуз мегблэфесз áðü 2 мЭфсб áðü ôïí еопрлйумь êáé рсЭрей íá еЯнбй рспурелЬуймз óôï чсЮуфз. Ï дйбкьрфзт on/off ôïõ UPS äåí брпмпнюней злекфсйкЬ ôá еущфесйкЬ ìÝñç. ¼ôáí брпухндЭефе ôç мпнЬдб ãéá мегЬлб чспнйкЬ дйбуфЮмбфб, вгЬжефе ôï кблюдйп ейуьдпх áðü ôçí рсЯжб.
:
Узмейюуфе üôé ïé хрпдпчЭт еоьдпх ôïõ UPS всЯукпнфбй õðü енесгь ôÜóç ьрпфе еЯнбй рбфзмЭнп ôï рлЮкфспEопдпт ЕнесгпрпйзмЭнз ( бкьмз êáé áí ôï кблюдйп фспцпдпуЯбт еЯнбй брпухндедемЭнп.
:
Ãéá ухуфЮмбфб РбсЬкбмшзт ìå кблщдйщмЭнет еоьдпхт, ç рспуфбуЯб áðü ôçí хресЭнфбуз ãéá ôï кэклщмб (ôá кхклюмбфб) еоьдпх AC рсЭрей íá рбсЭчефбй áðü фсЯфпхт.
:
Óôá ухуфЮмбфб РбсЬкбмшзт ìå кблщдйщмЭнет еоьдпхт, ïé дйбкьрфет брпуэндеузт ðïõ еЯнбй кбфЬллзлпй ãéá ôï кэклщмб (кхклюмбфб) еоьдпх AC рсЭрей íá рбсЭчпнфбй áðü фсЯфпхт.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
|
),
17
Safety Warnings
Avvisidi sicurezza
IMPORTANTIISTRUZIONI DI SICUREZZA CONSERVAREQUESTE ISTRUZIONI QUESTO MANUALE CONTIENEIMPORTANTI ISTRUZIONIDI SICUREZZA
laTENSIONEcontenutainquestogruppostaticodi continuità è LETALE.Tuttele operazionidiriparazionee dimanutenzionedevonoessereeffettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO.All’internodel gruppo staticodicontinuità NON vi sono PARTIRIPARABILIDALL’UTENTE.
:
:
:
:
PERICOLO
ATTENZIONE
lebatteriepossonopresentarerischio di scossaelettricaodiustioniprovocate da altacorrentedovutaa corto circuito.Osservareleappositeistruzioni.
lebatteriedevonoesseresmaltite inmodocorretto.Perirequisitidi smaltimento fare riferimentoalledisposizioni locali.
questogruppo staticodicontinuità contieneunafonte di energia autonoma (le batterie).Lepresediuscita possono condurre tensione energizzataquando il gruppo staticodicontinuità non è collegatoconuna fonte di alimentazionea correntealternata.
non gettare mai le batterie nel fuoco poichèpotrebbero esplodereseespostealle fiamme.
18
:
maiaprirenèmutilarelebatteriepoichèl’elettrolita da esse rilasciatoènocivo allacuteeagliocchie può esserealtamentetossico.
:
usareesclusivamente il cavodialimentazionein dotazione con il gruppo staticodi continuità.Il cavo di alimentazioneècablatoinconformità conlespecifiche del CodiceElettrico Internazionale(IEC). Assicurarsiche la presa a muro nella quale si deveinserireilgruppo staticodicontinuità sia cablata in conformitàconle medesimespecificheondeevitaredidanneggiarel’apparecchiatura.Accertarsiche al momento dell’installazione la presa a corrente alternata sia protetta contro le sovracorrenti.Assicurarsi chelaspinadiingressosiacompletamente inseritanella presaa muro.Usareesclusivamente una presa a corrente alternata monofase, a tre fili,collegata a terra.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Safety Warnings
:
per ridurre ilrischiodi incendio o di scossaelettrica,installareilgruppostaticodi continuitàinunambienteinternoatemperaturaedumiditàcontrollata,privo di
agenticontaminanticonduttivi.Latemperaturaambientenondevesuperarei 40EC.Nonutilizzarel’unità in prossimitàdiacquaoinpresenzadiumidità eccessiva (95% max).
:
non rimuoverenèscollegareil cavo di ingressoquandoilgruppostaticodi continuitàèaccesopoichè in tal modo si disattiverebbeilcollegamento a terra di sicurezzadelgruppostaticodi continuitàedell’apparecchiaturaad essocollegata.
:
per conformitàconglistandardinternazionali e con le norme in merito al cablaggio,tutta l’apparecchiatura collegataconl’uscita del gruppo staticodi continuitànondeveavereunacorrentedidispersionedi terra superiorea 2,75 milliampere.
:
lapresadialimentazioneprincipalenon deve trovarsiaoltre2 metri dall’apparecchiatura e deve essere accessibile all’operatore.L’interruttore on/off delgruppo staticodicontinuità non isolaelettricamentei componenti interni. Scollegarel’unità dalla presa dialimentazionequandorimaneinriposoper lunghi periodiditempo.
:
sinotichelepresedialimentazione di uscita delgruppo staticodi continuitàsono elettricamenteenergizzateogniqualvoltavienepremutol’interruttore azzurrodi( attivazioneuscita, a prescinderedalfatto che ilgruppo staticodicontinuità sia alimentatoomeno.
:
neisistemiBypassprovvistidi uscitecablate,idispositividiprotezioneda sovracorrenteperil/icircuito/iacorrentealternatainuscitadevono essere forniti da terzi.
:
neisistemiBypassprovvistidi uscitecablate,isezionatoridi corrente nominale adeguata per il/icircuito/i a corrente alternata in uscita devono esserefornitida terzi.
|
)
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
19
Safety Warnings
Viktig Sikkerhetsinformasion
DenneUPS’eninneholderLIVSFARLIGE SPENNINGER.Allreparasjon og servicemå kun utføresavAUTORISERTSERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICEPÅNOENAV DELENE i UPS’en.
:
Batterierkanforårsakeelektriske støt eller forbrenning på grunn av høy kortslutningsstrøm. Følginstruksene.
:
Batteriermåfjernespåkorrektmåte.Selokale forskriftervedrørendekravom fjerningavbatterier.
:
DenneUPS’enharenegen energikilde(batterier). Stikkontaktenekanvære strømførendeselvom UPS’enikke er tilsluttetenvekselstrømforsyning.
:
Kastaldribatterieriflammer,dade kan eksplodere,hvisde utsettes for åpen ild.
:
Batteriermåaldriåpnesellerødelegges.Frigjorteelektrolyttererskadeligeforhud og øyne og kan væreekstremtgiftige.
:
BrukkundenstrømforsyningskabelensomfølgermeddenneUPS’en.Strømkabelen er kobletioverensstemmelse med spesifikasjonene iIECs(InternationalElectrical Code)bestemmelser.Sjekkat stikkontaktensomanvendesforUPS’ener kobleti overensstemmelsen med de samme spesifikasjonenefor å unngå skade på utstyr. Sjekkogså at det finnesoverstrømvernforvekselstrømkontaktenunder installeringen. Sjekkat støpseleterført helt inn i stikkontakten.Bruk kun en en-faset,tre-trådet,jordetvekselstrømkontakt.
:
Foråreduserefare for brann ellerelektriske støt,børdenneUPS’eninstalleresiet innendørsmiljømed kontrollert temperatur og luftfuktighetsomerfrittfor ledende,forurensende stoffer.Romtemperaturenmåikkeoverskride40C.Denmå ikkebrukesi nærheten av vann eller ved meget høy luftfuktighet(95%maks.).
FARLIG
FORSIKTIG
20
:
Strømforsyningskabelen må ikkefjernesellertrekkesut når UPS’enerpå,slikat ikkesikkerhetsjordingenfjernesfraUPS’enogdetutstyretsomerforbundet medden.
:
Altutstyr somerforbundetmedutgangen av denne UPS’enmåikkehaensterkere total lekkasjestrøm enn2,75 milliampere for å være i overensstemmelse med internasjonalestandarder og forkablingsbestemmelser.
:
Stikkontakten måbefinneseginnen2 m fra utstyret og må være tilgjengeligfor operatøren.Av/På-bryteren på UPS’enisolererikke de interne delene. Trekk ut ledningenfrastikkontakten når utstyretfrakoplesover lengre tidsrom.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
:
UPS’ensstikkontakter forutgangsstrømforsyning er strømførende når lastbryteren
|
(
) trykkes, uavhengig av strømforsyningen.
:
For PowerPass systemer med fastkoplete uttak, må overstrømvern for vekselstrømuttak(ene)stilles til rådighet av andre.
:
ForPowerPasssystemer med fastkopleteuttak,måpassendeutkoplingsbryterefor vekselstrømuttak(ene)stilles til rådighet av andre.
Regulamentos de Segurança
INSTRUÇÕES DE SEGURANÇA IMPORTANTES
GUARDE ESTASINSTRUÇÕES ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA IMPORTANTES
AUPScontémVOLTAGEM MORTAL.Todososreparose assistência técnicadevemser executadosSOMENTEPOR PESSOALDAASSISTÊNCIA TÉCNICAAUTORIZADO. Não há nenhuma PEÇAQUEPOSSASER REPARADAPELO USUÁRIOdentro da UPS.
Safety Warnings
CUIDADO
PERIGO
:
Asbateriaspodemapresentaroriscode choqueelétrico,ou queimaduras provenientesdealtacorrentedecurto-circuito. Observeasinstruçõesadequadas.
:
Sigaasinstruçõesapropriadasao desfazer-se dasbaterias.Consulteos códigosdo localparamaioresinformações sobre os regulamentosdedescartedeprodutos.
:
EstaUPScontém suaprópriafontedeenergia(baterias). Osreceptáculosde saída podemcontervoltagemativaquandoaUPSnãoseencontraconectadaauma fonte de alimentaçãodecorrentealternada.
:
Nuncajogueasbateriasnofogo,porquehá riscodeexplosão.
:
Nuncaabra ou danifique as baterias.Oeletrólito liberadoéprejudicialà pele e aosolhosepodeserextremamentetóxico.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
21
Safety Warnings
:
Utilize somente o cabo de alimentação elétricafornecidocoma UPS.Estecabofoi fabricadodeacordocomasespecificações do IEC (InternationalElectrical Code). Certifique-sede que a tomada de parede foi montada de acordo com estas mesmasespecificaçõesafimde evitardanosaoseuequipamento.Nahorada instalação,verifiquesefoifornecidaumaproteçãocontrasobrecargadecircuito para a tomada de corrente alternada. Verifiqueseopluguedeentradaestá completamenteinserido na tomada de parede. Utilize somente uma tomada de correntealternadaaterrada,trifilar,monofásica.
:
Para reduziro riscodeincêndiosou choqueselétricos, instale a UPS em ambiente internocomtemperaturae umidadecontroladaselivresde contaminadores condutíveis. A temperatura ambiente não deve exceder 40EC.Nãoopere próximo a água ou em umidade excessiva(máx: 95%).
:
Não removaou desconecteocabode entrada quando a UPS estiver ligada.Isto removeráoaterramento de segurançada UPS e do equipamento conectado.
:
Paraestardeacordocomospadrõesinternacionaise osregulamentosde fiação,o equipamentototalconectadoàsaídadestaUPSnão deveteruma correntedefuga à terra maiorque 2,75 miliampères.
:
Osoquetede alimentaçãoprincipal deve estar no máximo doismetrosdo equipamentoeacessível ao operador. O interruptor on/off da UPSnão isola eletricamenteas peças internas. Desconecte-odosoquetedealimentação se não for usá-loporum longo período.
:
FavorobservarqueosoquetedealimentaçãodesaídanaUPSestará eletricamenteativo todas as vezes que o interruptor (
|
)estiverpressionado,
indiferenteàpresençadeenergiaelétricanarededealimentação.
:
Para sistemasBypass comsaídasconectadas, a proteçãode sobrecargapara circuitosde saída de corrente alternada deve ser fornecida por outros.
22
:
Para sistemasBypass comsaídasconectadas, interruptores de desconexão devidamentequalificadospara circuitosde saída de correntealternadadevemser fornecidosporoutros.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Предупреждения по мерам безопасности
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ СОХРАНИТЕ ЭТИ УКАЗАНИЯ ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
ОПАСНО
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ. Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.
ОСТОРОЖНО
:
Аккумуляторы могут вызвать опасность поражения электрическим током или ожога от тока короткого замыкания. Соблюдайте соответствующие меры предосторожности.
:
Необходимо соблюдать правила утилизации аккумуляторов. Обратитесь к местным нормативным актам за информацией о требованиях к утилизации.
:
Данный ИБП содержит собственные источники энергии (аккумуляторы). На выходных розетках может иметься напряжение, даже когда ИБП не подключен к сети переменного тока.
:
Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут взорваться под воздействием огня.
:
Никогда не открывайте и не деформируйте аккумуляторы. Вытекающий электролит опасен для кожи и глаз, и может быть крайне токсичным.
:
Пользуйтесь только сетевым шнуром, поставляемым в комплекте с ИБП. Разводка сетевого шнура выполнена в соответствии с требованиями Международных электрических норм (IEC). Во избежание повреждения Вашего оборудования убедитесь в том, что разводка настенной розетки, которая будет использоваться с ИБП, выполнена в соответствии с теми же требованиями. Убедитесь во время установки в том, что розетка оснащена средствами защиты от перегрузки по току. Убедитесь в том, что входная вилка надежно вставлена в настенную розетку. Пользуйтесь только однофазной трехпроводной заземленной розеткой переменного тока.
Safety Warnings
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
23
Safety Warnings
:
Для снижения опасности пожара или поражения электрическим током устанавливайте ИБП в закрытом помещении с контролируемыми температурой и влажностью, в котором отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40°С. Не эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%).
:
Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки при включенном ИБП. При этом защитное заземление отключается от ИБП и от оборудования, подключенного к ИПБ.
:
Для обеспечения соблюдения требований международных стандартов и требований к разводке электрических цепей, суммарная величина тока утечки на землю всего оборудования, подключенного к выходу ИБП, не должна превышать 2,75 миллиампера.
:
Настенная розетка должна находиться в пределах 2 метров от оборудования и быть доступной для оператора. Выключатель ИБП не отключает внутренние узлы от входного электропитания. При отключении оборудования на продолжительные интервалы времени отсоедините входной сетевой шнур от настенной розетки.
:
Пожалуйста, обратите внимание на то, что выходные розетки ИБП находятся под электрическим напряжением, если была нажата кнопка включения выхода (
|
) ИБП, даже если входной сетевой
шнур отключен.
:
Для блока байпаса с неразъемными выходами защита от перегрузки по току выходной(ых) цепи(ей) переменного тока должна обеспечиваться сторонними организациями.
24
:
Для блока байпаса с неразъемными выходами сторонними организациями должны быть обеспечены выключатели выходной(ых) цепи(ей) переменного тока, рассчитанные на соответствующий номинал.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Advertencias de Seguridad
INSTRUCCIONESDE SEGURIDAD IMPORTANTES GUARDE ESTASINSTRUCCIONES ESTEMANUAL CONTIENEINSTRUCCIONESDE SEGURIDAD IMPORTANTES
EsteSIEcontieneVOLTAJES MORTALES.Todaslasreparaciones y el serviciotécnico deben ser efectuadosSOLAMENTEPOR PERSONALDESERVICIO TÉCNICO AUTORIZADO. Nohay NINGUNAPARTEQUE EL USUARIO PUEDA REPARAR dentro del SIE.
:
Lasbaterías pueden presentarunriesgodedescargas eléctricaso de quemaduras debidoa la alta corrientede cortocircuito. Preste atención a las instrucciones correspondientes.
:
Esnecesariodesechar lasbateríasdeunmodoadecuado.Consultelasnormas localespara conocerlosrequisitos pertinentes.
:
EsteSIEcontienesupropiafuentedeenergía(lasbaterías). Los receptáculosde salidapueden transmitircorrienteeléctricaauncuando el SIE no esté conectadoa un suministrode corrientealterna(c.a.).
:
Nuncadesechelasbateríasen elfuego.Lasbateríaspuedenexplotarsise las exponea la llama.
Safety Warnings
PELIGRO
PRECAUCIÓN
:
Nuncaabra ni dañe lasbaterías.Elelectrolito que seliberaesperjudicial para la pielylosojos, y puede serextremadamentetóxico.
:
Utilice solamente el cablede entrada quese suministra con este SIE. El cable está instaladosegúnlasespecificacionesdel NEC (Código EléctricoNacional). Asegúresedequeeltomacorrientedelapareda utilizar con elSIE esté instalado segúnestasmismas especificacionesa fin de evitardañosensusequipos. Asegúresedequesecolocaunaprotección contrasobreintensidadpara el tomacorrientedec.a.en elmomentode la instalación.Asegúrese de que el enchufede entrada se inserte por completodentro del tomacorrientedelapared. Utilice solamente un tomacorriente monofásico con tres cablesdecargaen c.a. con descarga a tierra.
:
Para reducirelriesgodeincendioodechoqueeléctrico, instale este SIE en un lugarcubierto,contemperaturayhumedadcontroladas, libre de contaminantes conductores.Latemperatura ambientenodebeexcederlos40EC.No trabajecerca delagua o con humedad excesiva(95%máximo).
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
25
Safety Warnings
:
No retire o desenchufe el cabledeentrada mientraselSIEseencuentre encendido.Estosuprime ladescargaatierradeseguridad delSIEyde losequipos conectadosalSIE.
:
Para cumplirconlosestándares internacionalesylasnormas de instalación, la totalidaddelosequiposconectados a lasalidadeesteSIEnodebetener una intensidaddepérdidaatierrasuperioralos2,75miliamperios.
:
Eltomacorrientedebe encontrarseamenosde 2 metrosdelequipoyseraccesible para el operador.El interruptor de encendido/apagado del SIE no tiene aislación eléctricade laspartesinternas.Desenchufeelcablede entrada deltomacorriente de la pared cuando desconectelaunidadduranteperíodoslargos.
:
Tenga en cuenta que los receptáculosdesalidadel SIE tienen corriente eléctrica siemprequeseoprimeelbotónpulsadordeconexiónde salidadelSIE(Output ON),auncuandoelcabledeentradaestédesconectado.
:
Para lossistemasde bypass con salidascableadas, la protección por sobreintensidadpara el(los)circuito(s)delasalida de c.a.sedeberáadquiriraun tercero.
:
Para lossistemasde bypass con salidascableadas, los interruptores de desconexiónregulados adecuadamente para el (los)circuito(s) de la salidade c.a. deberán ser adquiridosauntercero.
Säkerhetsföreskrifter
VIKTIGA SÄKERHETSFÖRESKRIFTER
SPARA D ESSA FÖRESKRIFTER DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA SÄKERHETSFÖRESKRIFTER
DennaUPS-enhetinnehållerLIVSFARLIG SPÄNNING.ENDASTAUKTORISERAD SERVICEPERSONAL får utföra reparationer eller service.Detfinnsinga delar som ANVÄNDAREN KAN UTFÖRASERVICEPÅ inuti UPS-enheten.
:
Batteriernakange elektriskastötareller brännskadorfrån högkortslutningsström. Följ tillämpliga anvisningar.
:
Batteriernamåsteavyttrasenligt anvisningarnailokallagstiftning.
26
FARA
VIKTIGT
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Safety Warnings
:
DennaUPS-enhetharenegenenergikälla(batterier).Deutgående kontakternakan varaströmförandenärUPS-enheteninteäranslutentillen växelströmkälla.
:
Användabatterierfåraldrigbrännasupp.Dekanexplodera.
:
Öppnaaldrigbatteriernaellertaisärdem.Utsläppt elektrolytärskadlig för hud ochögon och kanvaramycket giftig.
:
Användendastdennätsladdsommedföljer denna UPS-enhet.Nätsladdenär kompatibelmed IEC-specifikationerna (InternationalElectrical Code). Kontrollera att det vägguttag som skaanvändasmedUPS-enhetenärdragetenligtsamma specifikationer,så att skadapåutrustningenundviks. Kontrollera att det finns överspänningsskyddför växelströmsuttaget vidinstallationstillfället. Kontrollera att UPS-kontaktenärordentligtinskjuten i vägguttaget. Använd endast ett enfasigt,jordatväxelströmsuttag.
:
Minskarisken för brand ellerelektriska stötargenomatt installeradenna UPS-enhetinomhus, där temperaturochluftfuktighet ärkontrolleradeochdäringa ledandeföroreningarförekommer. Omgivandetemperaturfårejöverstiga40C. Användinteutrustningennäravattenellervid hög luftfuktighet(max95%).
:
Ta aldrigbortnätsladdennärUPS-enhetenärpåslagen.Dettatarbort säkerhetsjordningen från både UPS-enheten och den anslutna utrustningen.
:
Föratt överensstämmamedinternationell standard och dragningsföreskrifterfår inteden totala utrustningsomanslutitstilluttaget på denna UPS-enhet ha jordanslutningsström som överstiger2,75milliampere.
:
Vägguttagetfår varahögst2 meterfrånutrustningenoch måstevarainomräckhåll för användaren.UPS-enhetensströmbrytare isolerarinteelektriskt de interna delarna.Vidlängre avstängning bör nätsladden dras ur vägguttaget.
:
ObserveraattUPS-enhetensuttag är strömförande när laddningsström­brytaren(Output
On button) trycksned,oberoende av om spänningskällan är
tillkopplad ellerinte.
:
Överströmsskyddfördeutgåendeväxelströmkretsarnaskatillhandahållasavandra för fast anslutna förbikopplingssystem.
:
Strömbrytareförbortkopplingmedpassandedimensioner för de utgående växelströmkretsarna ska tillhandahållasav andra för fastanslutna förbikopplingssystem.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
27
Safety Warnings
28
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
CHAPTER 3
INSTALLATION
The following sections describe UPS storage requirements and the installationand startup of the UPS.
Unpacking and Inspection
Carefully unpack the UPS and battery cabinets,makingsureto retain the packaging materials.Examine each unitcarefully for any signsof damage and immediately notify your distributor if damage is present.
UPS and Battery Cabinet Storage
If you plan to store the UPS or battery cabinets prior to use, store them in a cool, dry environment. Storagetemperature shouldnot exceed 35C(95F)inordertopreservebatterylife.Forlongertermstorage, energize the UPS and battery cabinet for approximately8 hoursevery 90 days in order to maintainbatterycharge.
Whenever the units are not energized, verifythe circuitbreakeronall battery cabinets is returned to the OFF (O) position (see Figure 4 on page 31).
Selecting an Installation Option
In addition to the standard Prestige 3000 UPS, the unit has two optional PowerPass Modules: the PowerPass Distribution Module and the PowerPass IsolationModule.Usethe followingflow chart to decide which installation option is right for you.
Do you have an optional PowerPass Module?
No
See the following section, “UPS and
Battery Cabinet Installation.”
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
Yes
See“UPS with Optional PowerPass Module Installation” on page35.
29
Installation
UPS and Battery Cabinet Installation
Use the following procedure to installtheUPS and battery cabinets:
1. Place the UPS near the equipment to be protected.The UPS should be well ventilated and away from direct sunlight or otherheat source.
Figure 3 shows the different UPS stacking configurations.
NOTE Donot placemore than three battery cabinetsinone stack.TheUPScabinet mustbeplacedontop of or beside the battery cabinets.
UPS Cabinet
Battery Cabinet
Air Vents
30
Battery Cabinet UPS Cabinet
Figure 3. Cabinet Setup
NOTE Youcaninstall additional battery cabinetswhilethe UPSisoperating,but
confirmtheUPSisnotinBatterymode(seepage 47).
2. Verify the circuit breaker on all battery cabinetsis in the OFF (O) position (see Figure 4).
3. Remove the ba ttery connector guard.Plug the battery cord into the externalbattery connector on the UPS. All battery connectors are polarized to preventincorrect connection.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Power Input Connector
Installation
Serial Port
Battery Connector
Input Circuit Protector
UPS Cabinet
Circuit Breaker
Breaker Tie
Battery Cabinet
Tie Wrap Mounts
Power Output Receptacle
REPO Receptacle (Optional)
External Battery Connector
Battery Cord
Figure 4. UPS Rear Panel
4. If additional battery cabinets are to be used, plug the battery cordof the second cabinet into the externalbattery connector of the firstbatterycabinet.Followthisprocedure for each additional battery cabinet.
5. Remove the breaker tie from the circuitbreakeron all battery cabinets.
6. Switchthe circuit breaker on all battery cabinets to the ON (
|
position.
7. Two tie wraps are included with the UPS to secure the power cordsto the inputand output receptacles.Insertthe tie wrap through the slot on each tie wrap mount.
8. Plugthe optionaloutputreceptaclepower strip or the optional Extended Power Distribution Module (EPDM 320-C20P) into the UPS power output receptacle (see Figure 4).
)
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
31
Installation
9. Verify that the load plugis fully seated. If power cord locking is required: loop the tie wrap aroundthe
power cordand tighten to secure the cord to the rear panel. Allowsufficient slack in the cord between the receptacle and the tie wrap. At least 122(30 cm) of slack is recommended.
10. The equipment to be protected by the UPS should be powered off.Plugthe equipmentinto the outputreceptaclepower strip or EPDM.
DO NOT protect laser printers with the UPS because of the exceptionally highpower requirements of the heatingelements.
11. If you are using a Remote Emergency Power-Off (REPO) switch, follow the instructions in “REPO Installation” on
page 34.
12. Start the UPS accordingto the following “UPS Startup” procedure.
UPS Startup
To start up the UPS:
1. Plug the UPS power supply cord into the input connector on the UPS rear panel.
If power cord locking is required: loop the tie wrap aroundthe power cordand tighten to secure the cord to the rear panel. Allowsufficient slack in the cord between the receptacle and the tie wrap. At least 122(30 cm) of slack is recommended.
32
NOTE Steps2 through 7 are for changingtheoutput voltage.Theoutput voltageis
factory-configuredfor 230V. If you do not need to change the output voltage, skipto Step8.
2. Plug the other end of the power supply cord into a grounded, three-wire, A C receptacle that has been wired in accordance withNEC specificationsor nationalwiring rules.
3. Press the Output
Off button until the alarm beeps.
All indicatorsflashsimultaneously.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
4. Press and hold the Output On button until the alarm beeps again.
Two indicators, corresponding with the current setting,remain flashing.The output voltage is factory-configured for 230V.
When selecting 200V, the UPS is derated to 2500 VA(see the Model 2500 table on page 67 for 200V specifications).
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
220V230V240V 208V 200V
Figure 5. Output VoltageIndicators
5. Press the Output Off button to scroll throughthe output voltage options, top to bottom. Each time you p ress the button, the UPS beeps and the next two indicatorsflash.
Installation
NOTE Ifyoudo not save a selectionwithintwominutes, the setupautomatically abortsand switchesback to the originalconfiguration.
6. Press and hold the Output On button until the alarm beeps to select and save the output voltage. Failure to releasethe button immediately after the beep will cause the UPS to abort the setup.
7. Continue to Step 9.
8. Plug the other end of the power supply cord into a grounded,
three-wire, A C receptacle that has been wired in accordance withNEC specificationsor nationalwiring rules.
9. Turnonthe equipmentthat is connectedto the UPS.
10. Press and hold the Output
beep (approximatelyone second).
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
On button until you hear the UPS
33
Installation
The
indicator remains lit and the Self Test indicator turns
on.The frontpanel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. See “Normal Mode” on page 46 for more
information.
REPO Installation
WARNING
Onlyqualified servicepersonnel(suchasalicensed electrician)shouldperform the hardwiredinstallation.
TheREPOswitchisa customer-suppliedswitchthatcan disconnectUPS outputvoltagefromyourprotectedequipment. If you are using a REPO switch, you need a junctionbox, exte rnal wiring, and a switch w ith the following specifications:
:
The switch shouldbe a wall-mounted,momentary -contact, normally open, pushbutton switch.
:
Minimumratingsof 240 Vac a nd 35 mA.
:
Wire should be 18 AWG (0.75 mm
2
) minimum.
CAUTION
:
Theblackand whiteREPOwiresareathigh-voltagepotential (240V).Refertoyour localelectrical code for proper installationofthe high-voltageREPOwires.
34
:
To ensurethe UPSstopssupplying powerto the load during any mode of operation,theinputpowermustbedisconnectedfrom the UPSwhen the emergencypower-offfunctionisactivated.
1. Place the conduit throughtheaccess hole on the junction box (see Figure 6). Connectthe exposed conduit wires to the corresponding compression terminals(see the following table). Tighten the compression terminals with a screwdriver .
2. Pivotthe REPO receptacle guard out of the way, plug the REPO plug/receptacle UPS connectorintothe REPO receptacle on the UPSrear panel and twist the connectorinplace (see Figure 4 on page 31).
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Installation
(
4-0
2
)
Mounting Holes
Access Hole for Conduit
T erminalBlock
Figure 6. OptionalREPO Cord Junction Box
PowerCableTerminations Tightening Torque
WireFunction Terminal
Position
REPO
*
Suggested wire size is #18-AWG (0.75 mm2)75C copper wire minimum.
NOTE
L1 TB1-4 L2 TB1-5 Ground
The REPO function activates when L1 and L2 areshortedtogether.
TB1-6
Terminal Wire
SizeRating*
12-22AWG
-
mm
UPS with Optional PowerPass Module Installation
The PowerPass Module is available in a 60-Hz Distribution Module or a 50-Hz IsolationModule,each with a plug/receptacle or hardwired option.ThePowerPass Moduleshave a Maintenance Bypass feature that supplies power to your equipment even whenthe UPS electronics are removed for maintenance or upgrades. The PowerPass Distribution Modulealso provides120V output.
Use the following procedure to install the UPS with a PowerPass Module:
1. Place the UPS near the equipment to be protected.The UPS should be well ventilated and away from direct sunlight or otherheat source.
Figure 7 and Figure 8 show the UPS stacking configurations with the PPDM and PPIM, respectively.
Plug/Receptacle UPS Connector
Three FootCord
Entrelec Phoenix
3.5- 5.3 lbin 5.6-6.8lb in
2
Contact
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
35
Installation
UPS Cabinet
Air Vents
Battery Cabinet
PPDM
Figure 7. Distribution Module Setup
UPS Cabinet
36
PPIM
Air Vents
Battery Cabinet
Figure 8. Isolation Module Setup
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Power Input Connector
Battery Connector
Input Circuit Protector
UPS Cabinet
Installation
2. V erify the Bypass switch on the PowerPass Module rear panel is in the NORMAL position (see Figure 9 or Figure 10).
Serial Port
Tie Wrap Mounts
Power Output Receptacle
REPO Receptacle (Optional)
Circuit Breaker
Breaker Tie
Battery Cabinet
Y-Cord
Power Output Receptacles
Utility Input Connector
PPDM (60Hz)
External Battery Connector
Battery Cord
Bypass Switch
Load Circuit Protectors
Figure 9. UPS withPPDM Rear Panel
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
37
Installation
Power Input Connector
Battery Connector
Input Circuit Protector
Battery Circuit Breaker
Breaker Tie
Battery Cabinet
TieWrap Mount
Battery Cord ExternalBattery
NOTE Youcaninstall additional battery cabinetswhilethe UPSisoperating,but confirmtheUPSisnotinBatterymode(seepage 47).
REPO Receptacle Serial Port
UPS Cabinet
Power Output Receptacle and TieWrap Mount
Y-Cord
Connector
Utility Input Connector
Figure 10. UPS with PPIM Rear Panel
Output Breaker
Input Breaker
Bypass Switch
PPIM (50Hz)
Power Output Receptacles
38
3. Verify the circuit breaker on all battery cabinetsis in the OFF (O) position.
4. Remove the ba ttery connector guard.Plug the battery cord into the externalbattery connector on the UPS. All battery connectors are polarized to preventincorrect connection.
5. If additional battery cabinets are to be used, plug the battery cordof the second cabinet into the externalbattery connector of the firstbatterycabinet.Followthisprocedure for each additional battery cabinet.
6. Remove the breaker tie from the circuitbreakeron all battery cabinets.
7. Switchthe circuit breaker on all battery cabinets to the ON (
|
position.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
)
Installation
8. Two tie wraps are included with the UPS to secure the Y-cord to the input and outputreceptacleson the UPS rearpanel. Insert the tie wrap through the slot on each tie wrap mount.
9. Plug the Y-cord of the PowerPass Module into the power connectors on the UPS rear panel as shown in Figure 9 or Figure 10.
10. Verify that the plugs are fully seated. If power cord locking is required: loop the tie wraps aroundthe
Y-cordconnections and tightento secure the cord to the rear panel.Allowsufficient slack in the cord between the receptacle and the tie wrap. At least 122(30 cm) of slack is recommended.
11. If yourPowerPass Module is a plug/receptacleunit,continue to Step 12. If your PowerPass Module is hardwired,skipto Step 16.
12. If an Extended Power Distribution Module is required, plug the EPDMintothe power outputreceptacle on the PowerPass Modulerearpanel.
13. The equipment to be protected by the UPS should be powered off.Plugthe equipmentinto the power outputreceptacleson the PowerPassModulerearpanel.
DO NOT protect laser printers with the UPS because of the exceptionally highpower requirements of the heatingelements.
14. If you are using a Remote Emergency Power-Off switch, follow the instructions in “REPO I nstallation” on page 34.
15. Start the UPS accordingto the “UPS with Optional PowerPass ModuleStartup”procedure on page 42.
16. Refer to your nationaland local electrical codes for acceptable externalwiring practices.
WARNING
Onlyqualified servicepersonnel(suchasalicensed electrician)shouldperform the hardwiredinstallation.
17. Remove the threescrewson the terminal block access cover with a Phillips screwdriver and remove the cover (see Figure 11).
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
39
Installation
Access Cover Screw
Input Breaker
2
Input
1/2 Conduit Access
Access Cover Screw
Figure 11. UPS with Hardwired PowerPass Module Rear Panel
CAUTION
For PowerPass systems with hardwired outputs, overcurrent protection and suitably rated disconnectswitches for the output ACcircuit(s) are to be providedbyeitherthe protectedequipmentorthe customer’sdistribution panel.
18. Connectstandard half-inchconduit through the terminalaccess box (see Figure 11) and hardwireto the te rminal block. See Figure 12 for the 60-Hz hardwired PPDM wiring or Figure 13 for the 50-Hz hardwired PPIM wiring.
Input
Output
208V/240V
120V
Access Cover Screw
Bypass Switch
T erminalBlock Access Cover
1/22Output Conduit Access
40
Ground
Line 1
Line 2/Neutral
Ground Neutral Line 2 Line 1
Figure 12. 60-HzHardwired PPDM TerminalBlock
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Installation
1810AWG
p
Input
Ground
Line
Neutral
Output
220/230/240V
Ground Neutral Line
Figure 13. 50-HzHardwired PPIM TerminalBlock
19. See the following table for specifications and tightening torque.
PowerCableTerminations Tightening Torque
WireFunction Terminal
Position
Input
Output
*
Ground 1 22-12AWG
L1 2 L2/Neutral 3 L1 5 L2/Neutral 6 Ground 8 No
Connection
Use #16-AWG (1.5mm2)75C copper wire minimum.
4, 7
Terminal Wire
SizeRating*
(0.34- 4 mm
18-10AWG
(0.75- 6 mm2)
22-12AWG
(0.34- 4 mm
2
2
Entrelec Phoenix
3.5- 5.3 lbin 5.6- 6.8 lb in
)
3.5- 5.3 lbin 4.5 - 7.0 lbin
3.5- 5.3 lbin 5.6 - 6.8 lbin
)
Contact
20. Replace the terminalbox cover.
21. If you are using a Remote Emergency Power-Off switch, follow
the instructions in “REPO I nstallation” on page 34.
22. Start the UPS accordingto the following “UPS with Optional PowerPass Module Startup” procedure.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
41
Installation
UPS with Optional PowerPass Module Startup
To start up the UPS:
1. V erify the Bypass switch on the PowerPass Module rear panel is in the NORMAL position (see Figure9 on page 37 or Figure 10 on page 38).
2. Steps 3 through 8 are for changingthe output voltage. The output voltage is factory -configured for 230V. If you do not need to changethe output voltage, skip to Step 9.
Use the following table to select the correctoutputvoltage according to yourPowerPass Module.
PowerPassModule ModelNumber UPSVoltage Selection*
60-Hz PPDM 208: 120/208 208 60-Hz PPDM 208: 120/240 208
60-Hz PPDM 208: 120 208 60-Hz PPDM 240: 120/240 Set to 220V for 110/220V PPDM output
Set to 230V for 115/230V PPDM output Set to 240V for 120/240V PPDM output
42
60-Hz PPDM 240: 120 Set to 220V for 110V PPDM output
Set to 230V for 115V PPDM output
Set to 240V for 120V PPDM output 50-Hz PPIM 208 (Model 2500 only) 208 50-Hz PPIM 220 220 50-Hz PPIM 230 230 50-Hz PPIM 240 240
*
The UPS output voltage should be set according to local mains voltage.
3. If your PowerPass Module is a hardwired unit, supply utility power. You have 30 secondsafter supplyingpower to pressthe Output
Off button. Release the Output Off button when
the alarm beeps. All indicatorsflashsimultaneously.
4. If your PowerPass Module is a plug/receptacle unit, plug the input power supply cord into the utility input connector on the PowerPass Module rear panel.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Press and hold the Output Off button while plugging the other end of the power supply cord into a grounded,three-wire, AC receptacle that has been wiredin accordancewith NEC specifications or nationalwiring rules.Release the Output
Off buttonwhenthe alarm beeps. All indicators flash
simultaneously.
5. Press and hold the Output
On button until the alarm beeps
again. Two indicators, corresponding with the current setting,remain
flashing.The output voltage is factory-configured for 230V.
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
220V230V240V 208V
Figure 14. Output VoltageIndicators
Installation
6. Press the Output Off button to scroll throughthe output voltage options, top to bottom. Each time you p ress the button, the UPS beeps and the next two indicatorsflash.
NOTE Ifyoudo not save a selectionwithintwominutes, the setupautomatically abortsand switchesback to the originalconfiguration.
7. Press and hold the Output On button until the alarm beeps to select and save the output voltage. Failure to releasethe button immediately after the beep will cause the UPS to abort the setup.
8. Continue to Step 11.
9. If your PowerPass Module is a hardwired unit, supply utility
power.
10. If yourPowerPass Module is a plug/receptacle unit,plugthe input power supply cord into the utility input connector on the PowerPass Module rear panel.
Plug the other end of the power supply cord into a grounded, three-wire, A C receptacle that has been wired in accordance withNEC specificationsor nationalwiring rules.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
43
Installation
11. Turnon the equipment that is connected to the UPS.
12. Press and hold the Output
beep (approximatelyone second).
On button until you hear the UPS
Troubleshooting Tips
If you should encounter any problems during startup, see the troubleshooting chart on page 71.
The battery cabinets are shipped withthe batteries charged.However, batteriesmay lose some of the charge duringshipping and storage.You can use the UPS immediately after unpacking, butit may not providethe full-rated backup time duringa power failure.Uponinitial startup,the UPS may need to operate for approximately 8 hours before the battery is fullycharged and fullbattery-backup time is available.If the Battery Fault indicator flashes, operate the UPS for 24 hours to fully charge the battery.
The on.The frontpanel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. See “Normal Mode” on page 46 for more
information.
indicator remains lit and the Self Test indicator turns
44
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
CHAPTER 4
UPS OPERATION
Thischaptercovers the operationof the UPS including front panel functions, operatingmodes, usingthe Battery Start feature,shutting down the UPS, and using the PowerPass Module.
UPS Front Panel
The UPS front panel has three distinct functions:
:
Displays the UPS operationalmode (Normal,Bypass,or Battery).
:
Displays any alarm conditions present during operation (the indicators flash).
:
Displaysthe loading percentage during Normal mode and the battery capacity duringBatterymode.
You can also use the frontpanel to configure UPS communication options and to configure the UPS output voltage. See “Front Panel
Communications Access” on page 58 or “Changing the Output Voltage” on page 49.
Output On Button (UPS on, load online)
Output OffButton (UPS off, load offline)
Sine Wave Indicator Overload Indicator
Site Fault Indicator Overtemp Indicator Battery Fault Indicator Self TestIndicator
Battery Online Indicator
Figure 15. UPS FrontPanel
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
IndicatorLegend
Unlit Amber Green Flashing
45
UPS Operation
Operating Modes
Utility Power
Surge Suppression EMI/RFI Filters
Battery Cabinets
After you install and apply power to the UPS, the UPS filters and regulates incoming AC power ,eliminating noise and voltage spikes, and providesconsistent power to your equipment (see Figure 16). While power is applied to the UPS, the maintenance -free battery is automatically kept in a fully-charged condition.
Bypass Line
Rectifier
Inverter
UPS Load Outlet
46
Battery
Battery Charger
BatteryBattery
Figure 16. UPSBlock Diagram
Normal Mode
During Normal mode, the displaysthe percentage of UPS load capacity being used by the protected equipment (see Figure 17).
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
LOAD O N LOADON LOAD ON LOAD ON APPROX.
81-100% LOAD
Figure 17. Normal Operation Indicators
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
indicator illuminates and the front panel
APPROX. 61-80% LOAD
APPROX. 41-60% LOAD
APPROX. 0-40% LOAD
LOAD O FF NORMAL
UTILITY
UPS Operation
Bypass Mode
The indicating Bypassmode (see Figure 18). When the UPS is in Bypass mode, the load is powered by utility power. However,utility power continues to be passivelyfiltered by the UPS.
indicator and the indicator illuminate simultaneously,
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
LOAD O N UNITON
BYPASS
Figure 18. Bypass Operation Indicators
Battery Mode
Whenthe UPS is operatingduring a power outage, the alarm beeps several times initially, and then once every 10 seconds while in Battery mode. The approximate percentageof battery capacity remaining (see Figure19). When the utility power returns, the UPS switches to Normal mode operationwhile the batteryrecharges.
indicator illuminates. The front panel displays the
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
BATTER Y ONLINE
>75% CAPACITY REMAINS
BATTER Y ONLINE
>50% CAPACITY REMAINS
Figure 19. Battery Operation Indicators
If batterycapacity becomes low while in Battery mode, the Battery Fault indicator begins to flashand the Self Test indicatorremains lit, indicating approximately two minutesbefore UPS shutdown. The alarm beeps every two seconds.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
BATTER Y ONLINE
>25% CAPACITY REMAINS
BATTER Y ONLINE
LOW BATTER Y WARNING
BATTER Y ONLINE
SHUTDOWN IMMINENT
47
UPS Operation
Diagnostics
When shutdown is imminent, the Self Test indicator flashes. These warnings are approximate, and the actual time to shutdown may vary significantly. Once these warnings are indicated, immediatelycomplete and save your work to prevent data loss and similar difficulties. When utility power is restored after the UPS shuts down, the UPS automatically connectsto the load when the startupis complete.
The UPS periodically performs diagnostic tests while the unit is operating in Normal mode, ensuring proper operation.Thesetests include:
:
Self Test
:
Utility Verification Test
:
Battery Discharge Test
:
Over TemperatureTest
The UPS also runsa series of over 20 internaltests when power is first applied.If a diagnostic test fails,see Chapter 7, “Troubleshooting”on
page 71.
Battery Start
48
Battery Test on Demand
You can pe rform a battery test on the UPS while it is operating in Normal mode by pressing the Output automatically distributes some o f the load to the batteries for 30 seconds and tests the battery’sperformance.
NOTE Beforeusingthis feature, theUPSmusthavebeen powered by utility power at leastonce.
This feature allows you to start the UPS without utility power. After utility power has been unavailable for one minute, press and hold the Output
The UPS supplies power to your equipment and goes into Battery mode. The of battery capacity remaining to the UPS.This processshouldtake about 15 seconds.
On button until the alarm beeps.
indicator remainslit and the frontpanel displaysthe percentage
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
On button. The UPS
UPS Shutdown
UPS Operation
Performing a UPS shutdown turns off the power to your protected equipment. Confirmthe equipmentis prepared for a power-offbefore shutting down the UPS.
NOTE Donot perform a UPS shutdown if you want to use the Maintenance Bypass feature on the optional PowerPassModule(see“Using the PowerPassModule”on
page 50).
To perform a UPS shutdown:
1. Press and hold the Output ceases (approximately three seconds).
The offline.
2. Unplug the UPS. The UPS enters Battery mode for severalseconds.The
3. When all LEDs are no longer illuminated on the UPS, switch the circuit breaker to the OFF (O) positionon each battery cabinet.
indicator remains lit indicating Normal mode, load
indicator turns off and the UPS shuts down.
Off button until the long beep
Changing the Output Voltage
To change the operatingvoltageof the UPS:
1. Perform a UPS shutdown as described in the previous section.
2. Follow the instructions in “UPS Startup” on page 32. If you
have a PowerPass Module, see “UPS with Optional PowerPass ModuleStartup” on page 42.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
49
UPS Operation
Using the PowerPass Module
The PowerPass Module provides continuous online power for your equipment. Withthe PowerPassModule,youcan replace the UPS withoutlosing power to the load. Figure 20 and Figure 21 show the operation of the UPS with the PPDM or PPIM.
Utility Power
UPS
In
Out
Battery BatteryBattery
Figure 20. UPS and PPDM Block Diagram
PPDM
UPS Load
50
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Utility Power
UPS Operation
PPIM
UPS Load
UPS
In
Out
Battery BatteryBattery
Figure 21. UPS and PPIM Block Diagram
Using Maintenance Bypass
Use the following procedure to transfer the critical load to Maintenance Bypass (AC Line operation) and remove the UPS:
1. Turn the Bypass switch on the PowerPass Module to the BYPASS position (see Figure 22). The PowerPass Module is now powering your equipment from utility power.
2. Press and hold the Output ceases (approximately three seconds).The remains lit.
3. Remove the c ord connections to the back of the UPS. The UPS enters Battery mode for severalseconds.The
indicator turns off and the UPS shuts down.
4. Switchthe circuit breaker on all battery cabinets to the OFF (O) position.
5. Disconnect the battery connector on the UPS rear panel.
6. Remove the UPS.
Off button until the long beep
indicator
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
51
UPS Operation
Power Input Connector
Battery Connector
UPS Cabinet
Battery Circuit Breaker
Battery Cabinet
Power Output Receptacle
52
Y-Cord
PPDM (60Hz)
Bypass Switch
Figure 22. UPS with PowerPass Module Rear Panel
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
UPS Operation
Use the following procedure to reinstall the UPS and transfer the critical load from Maintenance Bypass (AC Line operation) to the UPS:
1. Reconnectthe battery cabinet to the battery connectoronthe UPSrear panel.
2. Switchthe circuit breaker on all battery cabinets to the ON (
|
position.
3. Steps 4 through 8 are for changingthe output voltage. The output voltage is factory -configured for 230V. If you do not need to change the UPS outputvoltage,skipto Step 9. Use the following table to select the correctoutputvoltage accordingto your PowerPass Module.
PowerPassModule ModelNumber UPS Voltage Selection*
60-Hz PPDM 208: 120/208 208 60-Hz PPDM 208: 120/240 208 60-Hz PPDM 208: 120 208 60-Hz PPDM 240: 120/240 Set to 220V for 110/220V PPDM output
Set to 230V for 115/230V PPDM output Set to 240V for 120/240V PPDM output
60-Hz PPDM 240: 120 Set to 220V for 110V PPDM output
Set to 230V for 115V PPDM output
Set to 240V for 120V PPDM output 50-Hz PPIM 208 (Model 2500 only) 208 50-Hz PPIM 220 220 50-Hz PPIM 230 230 50-Hz PPIM 240 240
*
The UPS output voltage should be set according to local mains voltage.
)
4. Press and hold the Output Off button while plugging the Y-cordof the PowerPass Module into the power connectorson the UPS as shown in Figure22.
Release the Output
Off button when the alarm beeps.
All indicatorsflashsimultaneously.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
53
UPS Operation
5. Press and hold the Output On button until the alarm beeps again.
Two indicators, corresponding with the current setting,remain flashing.The output voltage is factory-configured for 230V.
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
220V230V240V 208V
Figure 23. Output VoltageIndicators
6. Press the Output Off button to scroll throughthe output voltage options, top to bottom. Each time you p ress the button, the UPS beeps and the next two indicatorsflash.
NOTE Ifyoudo not save a selectionwithintwominutes, the setupautomatically abortsand switchesback to the originalconfiguration.
54
7. Press and hold the Output On button until the alarm beeps to select and save the output voltage. Failure to releasethe button immediately after the beep will cause the UPS to abort the setup.
8. Continue to Step 10.
9. Plug the Y-cord of the PowerPass Module into the power
connectors on the UPS as shown in Figure 22.
10. Press and hold the Output
On button until you hear the UPS
beep (approximatelyone second).
The
indicator remains lit and the Self Test indicator turns
on.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
UPS Operation
11. Turn the Bypass switch on the PowerPass Module to the NORMAL position.
The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
55
UPS Operation
56
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
CHAPTER 5
COMMUNICATION
The UPS is equipped with a communications interfaceport that allows communication with a wide variety of externaldevicesincluding:
:
Videoordumbterminal
:
Serial printer
:
Computerwithpower managementor shutdown software
The serial port enables you to monitorand recorddiagnostic data with the following communication interfaces:
:
SerialCommunications Interface
Terminal Mode Data Dump Mode PrinterMode, 2400 Baud, with Novell Contacts (default) PrinterMode, 19200 Baud, with Novell Contacts
:
LAN Configuration
Novell-Style Network Interface 3Com-Style Network Interface AS/400-Style Network Interface CustomUser-Configurable Interface
9
9
9
Initial Communications Settings
The UPS is factory-configured for one of several communication interfaces (usually determined by the customer).To determine the initial UPS communications configuration, you can:
:
Look at the box label with the serial number (communication mode is shown in the upper right corner).
:
Use t he Display Configuration option on the UPS Serial Communications Menu (see page 60).
:
Call the
If you want to change the UPS configurationsettings, use the front panel or the UPS Serial Communications Menu.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
Help Desk at one of the telephone numbers on page 74.
57
Communication
Front Panel Communications Access
Before you access the front panel, reviewthe followingconfigurations and note the indicatorthat corresponds with the communication mode.
NOTE OnlythePrintermodefrontpaneloptionschangethebaud rate. Usethe UPS SerialCommunications Menu to select other baud rates (see page 60).
PrinterMode, 2400 Baud, NovellContacts
Select this mode for the OnliNet9or LanSafe software.
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
Novell-StyleLAN Contacts
Any baud rate other than 2400 or 19200 with Printer mode, or not Printer mode.
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
AS/400-Style LAN Contacts, No Serial
Select this mode for the OnliSafe9software.
FRONTPANEL COMMUNICATION OPTIONS
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
IndicatorLegend
Unlit Amber Green Flashing
3ComLANManager
Any communication mode and baud rate option.
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
PrinterMode, 19200 Baud (network devices), NovellContacts
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
58
Figure 24. Front Panel Communication Options
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Communication
To access the front panel communicationoptions, performthe following steps:
1. If the UPS is powered on, prepare your equipment for shutdown.
Press and hold the Output
Off button until the long beep
ceases (approximately three seconds). Unplug the UPS. Wait until all indicators turn off and then
continue to the next step.
2. Plug in the UPS while pressing the Output
Off button until
the alarm beeps. All indicatorsbeginflashing.
3. Press and hold the Output
Off button a second time untilthe
alarmbeeps again. A single indicator, corresponding with the current setting,
remains flashing.
4. Press the Output
Off button to scroll throughthe communicationoptions, top to bottom. Each time you press the button, the UPS beeps and the next indicatorflashes.
NOTE Ifyoudo not save a selectionwithintwominutes, the setupautomatically abortsand switchesback to the originalconfiguration.
5. Press and hold the Output On button until the alarm beeps to select and save a communication option.Failure to release the buttonimmediately after the beep willcause the UPS to abort the setup.
6. Press the Output
On button again to returnthe UPS to
Normalmode.
NOTE Printermode selectionsare the onlyserialcommunication modes available fromthe front panel.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
59
Communication
UPS Serial Communications Menu
With the UPS Serial Communications (Main) Menu, you can view or select UPS communication modes, baud rates,and LAN configurations. To change or display the current communications configuration:
1. Connectthe UPS serial port to a video monitorwitha serial interface or to yourcomputer’sserial port. If you are using
OnliNetor LanSafe software,the UPS should alreadybe connectedto your computer.
2. Set your terminalso that it matches the baud rate of the UPS (usually2400 baud, 8 bits, No parity, 1 stop bit). Refer to your terminal or operating system documentationfordetailson configuring your terminal communication settings.
3. At the te rminal prompt, press Communications Menu appears.
836 6(5,$/ &20081,&$7,216 0(18 6(/(&7 23(5$7,21 02'(
!' ',63/$< &21),*85$7,21 !
&217,18286 '803
!
!
!
$
!
%
!
3
!
/
!
=
!
4
!
6 (17(5 6(/(&7,21!!!
Control-C until the UPS Serial
32//(' '803 60$57 '803 $6&,, 7(50,1$/ 97 7(50,1$/ 35,17(5 '803 /$1 &21),*85$7,21 6(7 %$8' 5$7( 48,7 :,7+287 6$9,1* 1(: &21),*85$7,21 6$9( $1' 5(67$57
60
4. Select a menu option by typingthe corresponding letter or numberkey. All menu selections are single keystrokesand are not case-sensitive.
D > Display Configuration displays the current communication
settings and the new settings that you have selected prior to saving them. The new settings are not effective until you select save from the Main Menu.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Communication
&DWDORJ  '& 6HULDO  9HUVLRQ  &200 PRGH %DXG [ /$1 PRGH 6LWH )DXOW 'HWHFWLRQ 'LVDEOHG
1HZ &200 $6&,, 1HZ %DXG 1HZ /$1
3UHVV VSDFH EDU WR FRQWLQXH
%3&  6HUB3ULQW  1RYHOO
 1RYHOO
NOTE Catalog#,Serial#,andVersion # are allidentification numbers unique to your UPSandcanalsobefound on the UPS nameplate.
1 > Continuous Dump The UPS regularly transmits status
informationto the c omputer. Baud rates of 1200 to 2400 are recommended to reducehost computer overheadwhenusing this mode.
2 > Polled Dump Status information is transmitted only when
requested by a poll character (Control-E).
3 > Smart Dump Status information is transmitted when polled, as
in the previous mode. However,the transmission also occurs automatically wheneverUPSstatuschanges.Forexample,if there is a power outage, UPS status informationchanges and is therefore, automaticallytransmitted.
A > ASCII Terminal TheUPSdisplaystheformatteddataonthe
attached video terminal.
B > VT100 Terminal TheUPSdisplaystheformatteddataonthe
attached video terminal.
P > Printer Dump The UPS printsthe formatted data on the
attached printer.
L > LAN Configuration allows you to configure the UPS for a new
LAN mode and displays the Select LAN Configuration Menu.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
61
Communication
6(/(&7 /$1 &21),*85$7,21
! 129(//
! 4
(17(5 6(/(&7,21 !!
$6
!
&20/$1 0$1$*(5
!
&86720 &21),*85$7,21
!
72 48,7 7+,6 0(18
Select the AS400 option if you are usingOnliSafe softwareto monitor the UPS.
The
Custom Configuration option has two screens: the first screen
has options available for inverter shutdown, and the second screenhas options available for the contact configuration. Consult your shutdown software documentation for details on the required signal states for configuring LAN communications.
6(/(&7 &86720 /$1 &21),*85$7,21
,QVWUXFWLRQV &KRRVH WKH GHVLUHG LQYHUWHU VKXWGRZQ IXQFWLRQ :DUQLQJ ,W LV UHFRPPHQGHG WKDW WKLV IHDWXUH VKRXOG QRW EH XVHG ZLWK QRUPDO 56 FRPPXQLFDWLRQV FRQIOLFWV PD\ RFFXU
62
!
$
,QYHUWHU VKXWGRZQ FRQWURO LV HQDEOHG DFWLYH +,*+ 9 ,QYHUWHU VKXWGRZQ FRQWURO LV HQDEOHG DFWLYH /2: 9
!
%
,QYHUWHU VKXWGRZQ FRQWURO LV GLVDEOHG
!
&
72 48,7 7+,6 0(18
!
4
(17(5 6(/(&7,21 ! !
6(/(&7 &86720 /$1 &21),*85$7,21
,QVWUXFWLRQV &KRRVH WKH GHVLUHG FRQWDFW FRQILJXUDWLRQ
! 87,/B)$,/ LV DFWLYH FORVHG /2:B%$77 LV DFWLYH FORVHG
!
87,/B)$,/ LV DFWLYH RSHQ /2:B%$77 LV DFWLYH FORVHG
!
87,/B)$,/ LV DFWLYH FORVHG /2:B%$77 LV DFWLYH RSHQ
!
87,/B)$,/ LV DFWLYH RSHQ /2:B%$77 LV DFWLYH RSHQ
4
!
72 48,7 7+,6 0(18
(17(5 6(/(&7,21 ! !
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Communication
Z > Set Baud Rate allows you to select a new baud rate.The Select
Baud Rate Menu displays a list of baud rate options.
6(/(&7 %$8' 5$7(
!  4
(17(5 6(/(&7,21 !!

!

!

!

!

!
48,7 7+,6 0(18
!
5. To save the configuration settings, type S at the Main Menu prompt.TheUPS operates and communicatesunderthe new configuration,and defaults to these settingseach time it is started.
If you want to abandon the selections you have made, type
Q to
quit.
NOTE AnychangesyoumaketotheUPScommunications configurationmust correspondtothe communications equipment you are using. In particular, new baud rate selectionsfor the UPSmustmatchyourcommunications equipment.
Power Management Software
Powermanagementsoftware allows you to monitorUPS operations automatically. To use OnliNet or LanSafe software,theUPS must be configured for any one of the Data Dump, Terminal, or Printer modes; however, Printer mode is preferred.
OnliNet provides multiple levels of UPS monitoring and control, as well as automatic shutdownfor many differentoperatingsystems. If you have any questions or would like further information, call the at one of the telephone numberson pa ge 74.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
Help Desk
63
Communication
UPS Communications Interface Port
In addition to configuring the UPS for specific communication options, you must also ensure proper use of the serial port when connecting the UPS to your network or monitoring equipment.
The serialportLANcontactsare transistorsand are rated at a maximum current of 50 mA and a maximum of +40 Vdc.Donotexceedtheseratingsorapplyany
negativevoltageorACvoltageto thesecontacts;otherwise, damage may occurto yourUPS.
Use only the pins specified for your communications configuration. The use of any additionalpins for any of the following interfacescan cause interference with system communications.
Eventhoughyournetwork uses the specified signallines,thepins assigned to these signalsat the network end of the cable may vary with those of the UPS serial port. The connector body and style may vary as well.
CAUTION
64
NOTE Standard,pin-for-pin cables may not work correctly. Consult your network
softwareorservermanualsforsystem shutdown pinassignments.
The UPS serial port complies with EIA RS-232 standards.RS-232 specifiesa maximum cable lengthof 50 feet (15m).See Figure 25 for the locationof the serialport.
UPS Rear Panel
Serial Port
Serial Port Detail
Figure 25. Serial Port Location
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Communications Mode Reference Chart
The following chart defines the UPS serial port contacts.Serial communicationis not available with 3Com and AS/400 network configurations.Use only the applicablepins for the selected communication mode; otherwise, interference problemsmay occur.
CommunicationMode Function SignalName PinNo. True Condition
Serial
Novell (Default)
Novell (Custom)
3Com (Default)
AS/400
NOTE
Pin numbers separated byaforwardslash(/)areconnected together internally.
Data to UPS RS232 TxD 2 N/A Data from UPS RS232RxD 3 N/A Signal Ground 7 Battery On ON.AC 14/16 Open Low Battery Signal Ground 7/15/25 Battery On ON.AC 14/16 Closed Low Battery Signal Ground 7/15/25 Shutdown (Remote) SHUT.DOWN 2 PositiveVoltage Low Battery Battery On PWR.FAIL 10 Positive Voltage Signal Ground 7 UPS Available UPS Available 11/13 Closed Battery On Utility Failure 14/16 Closed Bypass UPS Offline 17/19 Closed Low Battery Low Battery 23/24 Closed Signal Ground 12/15/18/25
Communication
TWO.MIN 23/24 Closed
TWO.MIN 23/24 Closed
LOW.BATT 9 Positive Voltage
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
65
Communication
66
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
CHAPTER 6
SPECIFICATIONS
Prestige 3000 Model 2500 Specifications
Voltage
In:Out
200 2500 1750 11.30A 12.50A 814 1222 208 2500 1750 10.90A 12.00A 814 1222 220 2500 1750 10.30A 11.40A 814 1222 230 2500 1750 9.80A 10.90A 814 1222 240 2500 1750 9.40A 10.40A 814 1222
VA Watts InputCurrent OutputCurrent Online
(BTU/Hr)
On Battery
(BTU/Hr)
Prestige 3000 Model 3000 Specifications
Voltage
In:Out
208 3000 2100 13.00A 14.42A 1081 1574 220 3000 2100 12.30A 13.64A 1006 1574 230 3000 2100 11.70A 13.04A 968 1574 240 3000 2100 11.30A 12.50A 923 1574
VA Watts InputCurrent OutputCurrent Online
(BTU/Hr)
On Battery
(BTU/Hr)
Prestige 3000 UPS Physical Specifications
Parameter UPS Cabinet BatteryCabinet PowerPass Module Height 252 mm (9.91 in) 252mm (9.91 in) 252 mm (9.91 in) Width 142.5 mm (5.61 in) 142.5 mm (5.61 in) 142.5 mm (5.61 in) Depth 400 mm (15.75 in) 400 mm (15.75 in) 400 mm (15.75 in) Weight 7.4kg(16.25lb) 23.6 kg (52lb) 21.4 kg (47lb)
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
67
Specifications
Input
VoltageIn:Out
Model 2500 Specifications with the 60-Hz PPDM
OutputCurrent
VoltageIn:Out
208:120/208 10.9A 12.0A 10.4A 10.4A 240:120/240 9.4A 10.4A 10.4A 10.4A 208:120 10.9A 20.8A 10.4A 10.4A 240:120 9.4A 20.8A 10.4A 10.4A 208:120/208 10.9A 10.4A 10.4A 12.0A 208:120/240 10.9A 10.4A 10.4A 10.4A 240:120/240 9.4A 10.4A 10.4A 10.4A 240:120/240 9.4A 10.4A 10.4A 10.4A
Input
Current
240V
L14-30R
208V
L6-30R
(Total nottoexceed 1750 Watts, 2500 VA)
120V
L5-30R
120V
2x5-15R
120V
2x5-15R
208V
L6-20R
240V
L6-20R
240V
L6-30R
Model 2500 Specifications with the 50-Hz PPIM
VoltageIn:Out
208:208 10.9A 12.0A/10.0A 12.0A 220:220 10.3A 11.4A/10.0A 11.4A 230:230 9.8A 10.9A/10.0A 10.9A 240:240 9.4A 10.4A/10.0A 10.4A
68
Input
Current
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
(Total nottoexceed 1750 Watts, 2500 VA)
IEC-320-C19/IEC-320-C13 Hardwired
OutputCurrent
Specifications
Input
VoltageIn:Out
Model 3000 Specifications with the 60-Hz PPDM
OutputCurrent
VoltageIn:Out
208:120/208 13.0A 14.4A 12.5A 12.5A 240:120/240 11.3A 12.5A 12.5A 12.5A 208:120 13.0A 25.0A 12.5A 12.5A 240:120 11.3A 25.0A 12.5A 12.5A 208:120/208 13.0A 12.5A 12.5A 14.4A 208:120/240 13.0A 12.5A 12.5A 12.5A 240:120/240 11.3A 12.5A 12.5A 12.5A 240:120/240 11.3A 12.5A 12.5A 12.5A
Input
Current
240V
L14-30R
208V
L6-30R
(Total nottoexceed 2000 Watts, 3000 VA)
120V
L5-30R
120V
2x5-15R
120V
2x5-15R
208V
L6-20R
240V
L6-20R
240V
L6-30R
Model 3000 Specifications with the 50-Hz PPIM
VoltageIn:Out
220:220 12.9A 13.6A/10.0A 13.6A 230:230 12.3A 13.0A/10.0A 13.0A 240:240 11.9A 12.5A/10.0A 12.5A
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
Input
Current
IEC 320-C19/IEC320-C13 Hardwired
(Total nottoexceed 2100 Watts, 3000 VA)
OutputCurrent
69
Specifications
Prestige 3000 UPS TechnicalSpecifications
InputVoltage Range 160 to276Vac PowerPassIsolationModule
InputVoltage Range InputPower Factor 0.95 T ypical FrequencyRange 50/60 Hz ±3 Hz Surge Protection IEC 801-4 OutputWaveform Sinewave OutputVoltage
(withoutPowerPassModule) Common Mode Noise
Rejection TransverseMode Noise
Rejection InputCord Detachable 2-meter cord Outlets(UPS Cabinet) IEC 320(1) OutputVoltagesandOutlets
(withPPDM)
OutputVoltagesandOutlets (withPPIM)
Batteries (10)per cabinet 12 Vdc, 5 Ah, maintenance-free rechargeable lead acid BatteryCabinet 120 Vdc OperatingEnvironment T emperature: 10Cto40C
AgencyApprovals Safety: EN50091-1
120/208V: L6-30R or L14-30R, 4x5-15R 120/240V: L6-30R or L14-30R, 4x5-15R
(208V available with Model 2500 only) 220/230/240V: 1 x IEC 320-C19
220/230/240V Hardwired: 220/230/240V 220/230/240V Hardwired: 220/230/240V
Humidity: 5 to95%
EMC: FCC Part 15 Class A
187 to276Vac
200/208/220/230/240 Vac±3%
>60 dB @ 100 kHz
>80 dB @ 100 kHz
120: L5-30R,4x5-15R 208V Hardwired: 120/208V 240V Hardwired: 120/240V
3 xIEC 320-C13
(50
F to104F)
(noncondensing)
UL 1778 cUL
EN50091-2
70
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
CHAPTER 7
,
g
TROUBLESHOOTING
The Prestige UPS is designedfor durable, automaticoperationand also alertsyou wheneverpotentialoperating problemsmay occur. Use the following troubleshooting chart to determine the UPS alarm condition.
IndicatorLegend
Unlit Amber Green Flashing
Condition PossibleCause Action
UPS does not turn on.
Load doesnot turn on. UPS has not been activated.
UPS beeps occasionally. Normal operation. None.UPS is protecting your
UPS input breaker trips. Load fault. Check the load.
indicator remains lit, even though line voltage is present.
UPS does not provide the expected backup time.
UPS is not plugged in. Plug UPS into working outlet. Dead wall socket. Test wall socket, repair as required. UPS input breaker is tripped. Reduce load, then reset breaker.
Pressthe Output second, then release.
equipment.
Disconnect faulty load equipment. Wait severalminutes beforeresetting the UPS input breaker. Restart the load.
Utility line is out of specification.
UPS input breaker is tripped. Low battery capacity. Allow battery to charge for 24 hours,
Protected equipment power requirements exceed UPS capacity .
Test wall socket, repair as required.
Reduce load, then reset breaker.
then retest. Reduce load, then retest.
|
On button for one
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
71
Troubleshooting
ActionPossible CauseCondition
Communications do not function properly.
No output load voltage.
OVERLOAD SITE FAULT OVERTEMP BATTERY SELF TEST
OVERLOAD
Incorrect communications
Verify cable integrity (see page 64).
cabling. Incorrect baud rate. Select a new baud rate (see page 63). Incorrect communication mode. Select a new communication mode
(see Chapter 5). Load plug(s) not fully seated. Verify load plug(s) are fully seated. Load circuit protectors tripped. Reset load protectors. Power requirements exceed UPS
capacity . If overload is greater
Your UPS continuesto operate.
Reduce load. than 105%, the alarm beeps every second and the UPS may switch to Bypass mode.
The UPS switched to Bypass mode because the overload increased (above 105%). The alarm beeps.
Reduce load.
If the Overload indicator remains lit,
reset the UPS by pressing the
Output
|
On button until the alarm beeps. You may need to obtain a larger capacity UPS.
The utility line voltage and frequency are out of specification.
The inverter remains online, deriving power from the utility until it is no longer acceptable. Checkthe unit configuration. Refer to the product specifications (see page 67).
72
OVERTEMP
BATTERY
UPS internal temperature is too high. The alarm beeps and the UPSswitchestoBypassmodefor approximately 10 minutes, allowing the UPS to cool down.
Weak battery while in Normal mode. The alarm beeps.
Shut down the UPS. Clear vents. Remove any heat sources. Wait approximately 5 minutes and retry. Contact your service representative if condition persists.
Allow the battery to chargefor 24 hours, then retest. Have batteries replaced if condition persists.
Battery breaker is open (O). Make sure the battery cabinet breaker
Battery cabinet is not properly connected to the UPS.
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
is in the ON ( Make sure battery cords are
connected.
|
) position.
Troubleshooting
ActionPossible CauseCondition
BATTERY
SELF TEST
Resetting the UPS
To reset the UPS while an alarm condition is present,pressthe Output
Silencing the Alarm
To silence the alarm for an existing fault, press and hold the Output If UPS statuschanges,thealarm beeps, overridingprevious alarm silencing. Press the Output
Weak battery while in Bypass mode.
Self Test failure. UPS internal problem.
This usually indicates that the batteries need replacing or the UPS requires service. Contact your service representative.
The UPS may switch to Bypass mode, depending on the circumstances. Reset the UPS by pressing the Output
|
On button until the alarm beeps. Contact your service representative if condition persists.
On button untilthe UPS alarm beeps.
On button for one second. The alarm becomes quiet.
On button again to silence the alarm.
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
73
Troubleshooting
Service and Support
The troubleshootingchart on page 71 covers most of the difficulties you may encounter during normal operations. If you have any questions or problems with the UPS,call your of the following telephone numbers and ask for a UPS technical representative.
Local Distributor or the Help Desk at one
In the United States In Canada All other countries
1-800-365-4892 1-800-461-9166 1-919-870-3149
Pleasehave the following information readywhenyou call the Help Desk:
:
Model number
:
Serial number
:
Version number (if available)
:
Date of failureor problem
:
Symptoms of failure or problem
:
Customer returnaddressand contact information
If repair is required, you will be given a Returned Material Authorization (RMA) Number.This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Help Desk or distributor.Unitsdamaged in shipment as a result of improperpackaging are not coveredunder warranty. A replacementor repair unit will be shipped, freight prepaid for all warrantied units.
NOTE Foranywarrantyclaimto be valid,theWarrantyRegistration Card must be on file,orProofand Dateof Purchasemustbe returned with the failed unit.
74
Forcriticalapplications, immediate replacementmay be available.Call
Help Desk for the dealer or distributornearest you.
the
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
INDEX
Numeric
3Com Network Interface
frontpanel configuration, 58 LAN Configuration Menu, 62
A
AC Line
Bypass switch, 51 operation, 51
alarm
silencing,73 UPS, 72
Alarm Conditions
Battery Fault, 72 Overload, 72 Overtemperature, 72 Self Test Failure, 73 Utility Out of Spec, 72
AS/400 Network Interface
frontpanel configuration, 58 LAN Configuration Menu, 62
ASCII Terminal Mode, 61
B
battery
circuitbreaker, 31 configuration, 2 extensiontime, 3 input connector, 31 installation, 30
output connector, 31 storage, 29
Battery Fault
alarm, 72
indicator, 45 Battery Mode, 47 Battery Online, indicator, 45 Battery Start, 48 Battery Test on Demand, 48 baud rates, 60, 63 BypassMode, 47 Bypass switch, 37, 38
C
changingthe output voltage, 49 communication
interfaceport, 64
modes, 60
UPS, 57 Communications Mode Reference
Chart, 65
configuration settings
abandoning,63
displaying,60
frontpanel, 58
saving, 63 contact configuration, serial port, 64 Continuous Dump Mode, 61 Control Keys
Control-C,60
Control-E, 61
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
75
Index
cord, power, 32, 42, 43, 70 Custom LAN Configuration
Menu, 62
customerservice, 74
D
Data Dump Modes, 61 diagnostics, 48 Display Configuration Screen, 61
E
exiting Main Menu, 63
F
frontpanel
configuring communications, 58 controls,45 display functions, 45 indicators,45
frontpanel configuration
3Com, 58 AS/400, 58 Novell, 58 printer mode, 58
H
I
indicators, frontpanel, 45 inputcord, 32, 42, 43, 70 Inverter Shutdown Control, 62
L
LAN Configuration
Main Menu option, 60
menu, 62 laser printers, 32, 39 load
definition, 2
requirements, 2 LOW_BA TT, 62
M
Main Menu, 60 Maintenance Bypass feature
See also PowerPass Distribution
Module (PPDM); PowerPass Isolation Module (PPIM)
activating, 51
deactivating, 53 Menu
Custom LAN Configuration, 62
LAN Configuration, 62
Main, 60
Serial Communications,60
Set Baud Rate, 63
76
hardwired PowerPass Module
rear panel, 40 terminationblocks, 40
Help Desk, 74
Mode
ASCII Terminal, 61
Battery, 47
Bypass, 47
Communications, 60
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
Index
Data Dump, 61 Normal, 46 Printer, 59, 61 Terminal, 61 VT100 Ter minal, 61
N
Normal Mode
indicator, 45 operation, 46
Novell Network Interface
frontpanel configuration, 58 LAN Configuration Menu, 62
O
OperatingModes, 46 Operation
Battery, 47 Bypass, 47 Normal, 46
UPS with PowerPass Module, 50 Output Off Button, 5, 45 Output On Button, 5, 45 outputvoltage
changing, 49
initial setting, 32, 42 Overload
condition, 72
indicator, 45 Overtemperature
alarm, 72
indicator, 45
P
plug/receptacleUPS, installation
optional REPO cord junction
box, 35
REPO switch, 34 Polled Dump Mode, 61 Power Management Software
LanSafe, 58, 63
OnliNet,58, 63
OnliSafe,58, 62 PowerPass Distribution Module
(PPDM) AC Line operation, 51 block diagram, 50 installation, 35 MaintenanceBypass feature,35 operation, 50 power output receptacles, 37 rear panel
hardwired, 40
plug/receptacle,37 startup, 42 utilityinput connector, 37
PowerPass Isolation Module (PPIM)
AC Line operation, 51 block diagram, 51 installation, 35 MaintenanceBypass feature,35 operation, 50 power output receptacles, 38 rear panel
hardwired, 40
plug/receptacle,38 startup, 42 utilityinput connector, 38
Printer Mode
frontpanel configuration, 59 Main Menu configuration, 61
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
77
Index
R
rear panel
hardwired, 40 PPDM connectors, 37 PPIM connectors, 38 UPS connectors, 31
Remote Emergency Power-Off
switch. See REPO switch
REPO switch, plug/receptacle
UPS, 34 resetting the UPS, 73 Returned Material Authorization
(RMA) Number, 74
S
Safety Warnings, 7 Self Test
failure,73
indicator, 45 serial cable, 64 serial port
contact ratings, 64
description,64 service, 74 Set Baud Rate Menu, 63 shutdown, 49 Site Fault, indicator, 45 Smart Dump Mode, 61 specifications, 67 StartupTests, 48 storage temperature,29
Switch,Bypass,37, 38 systemrequirements, 2
T
Terminal Modes, 61 Tests
Battery(on demand), 48
Startup, 48 transistors, contact ratings, 64 troubleshooting
chart, 71
tips, 44
U
uninterruptible power system, 1 UPS
alarm silencing, 73
alarms, 72
block diagram, 46
changingoutputvoltage, 49
communication, 57
Communications Mode Reference
Chart, 65 external battery connector,31 frontpanel, 45 input breaker, 31 installation, 30 operation with PPDM, 50 operation with PPIM, 51 operations,45 power input connector,31 power output receptacles, 31 rear panel, 31 resetting, 73 Serial Communications Menu, 60 serial port, 31, 64
78
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com
shutdown, 49 special symbols, 5 startup, 32 storage, 29
unpacking and inspection, 29 UTIL_FAIL, 62 Utility Out of Spec, 72
V
volt-amperes, 2 VT100 Terminal Mode, 61
Index
Powerware®9PrestigeSeriesUser’sGuide (2500/3000VA):www.powerware.com
79
Index
80
Powerware®9 Prestige SeriesUser’sGuide (2500/3000VA):www.powerware.com