NOTE This equipment has been testedandfound to comply withthe limits for a Class Adigital device, pursuantto
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energyand, if notinstalled and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operationof this equipmentina residential area is likelyto cause harmful interference in whichcase
the userwill be required to correct theinterference athis own expense.
ICES-003
This ClassAInterference Causing Equipment meetsallrequirements of the Canadian Interference CausingEquipment
Regulations ICES-003.
Cet appareilnumérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
EN50091-2
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these
configurations, the following applies:
WARNING This isa ClassA-UPS Product.Ina domesticenvironment,this product may cause radiointerference, in
which case, the user may berequired to takeadditional measures.
Powerware, PowerPass, Powercare, OnliNet,and OnliSafe are registered trademarks ofPowerware Corporation.
IBM and AS/400 are registered trademarks of InternationalBusiness Machines Corp.
Novell is a registered trademark of Novell, Inc.
3Com is a registered trademark of 3Com Corporation.
.
Copyright 1995-2000 Powerware Corporation, Raleigh, North Carolina, USA. All rights reserved. No part of this
documentmaybe reproduced in any way without the express written approval ofPowerware Corporation.
QUICK INSTALL
UPS with PPDM Installation
CAUTION
Readthe safetyinstructions beginning on page 7 before installing the UPS.
1If you are connecting the UPS to an AS/400, the QUPSDLYTIM systemvalue for the UPS
Monitoring feature should be set. See “UPS Monitoring” on page 50 for instructions.
2
3
PowerPass
45
Distribution
ModelNumber
208: ___120/208V208
240: ___
Desired
Output
Voltage
100/200V200
110/220V220
115/230V
120/240V240
Voltage
Selector
Position
230
Quick Install
6
7
89
Quick Install
10 For the AS/400 interface, plug the AS/400 communications cable into the serial port on the
UPS rear panel. Plug the other end of the cable into the J14 connector on your AS/400.
Congratulations on the purchase of your Powerware9Prestige Series
uninterruptible power system (UPS). The Prestige UPS meets the
toughest measures of superiordesignand manufacturing, including
ISO 9001. You now own the most reliable power protectionavailable.
The Prestige 6000 providesa stea dy, well-regulated power supply for
yourcomputing and communications equipment, whileprotecting it
from the frequent irregularities that are inherent in commercially
available power. Voltage spikes, power surges, brownouts, and power
failures have the potential to corrupt critical data, destroy unsavedwork
sessions, and in some instances,damage expensivehardware.
Withthe Prestige 6000, you c an safely eliminate the effects of electrical
linedisturbances and guard the integrityof your systemsand
equipment. The PowerPass
Maintenance Bypass feature that supplies power to your equipment even
whenthe power processingunit (PPU)is removedfor maintenance or
upgrades. Figure 1 shows the Prestige 6000 UPS.
ThisUPSis designed to work withsingle-phase,three-wire,AC power
sources. There are two important considerations when selecting the UPS
model and battery configuration to properly safeguard your equipment:
:
Load requirements
:
Battery times
Load Requirements
The load is the equipmentto be protectedby the UPS. Select the UPS
model that meets the power consumptionrequirements of the load in
volt-amperes (VA). The total load VA shouldnotexceed the UPS VA
rating. To determine the total load requirements:
1. Obtain the load ratings fromeitherthenameplate or operator’s
manual of the equipment to be protected by the UPS. The
ratings are listed in either watts (W),amperes or amperes
max (A), or volt-amperes.
2. If the rating is in watts, multiplyby 1.4 to obtain the VA
requirement (thisis the typical relationship between wattsand
volt-ampere ratings in most computing equipment). However,
in some new computingequipment,thepower supply is
power-factor corrected and the watts rating equals the VA
requirement.Checkwith the manufacturer to determine
applicability.
If the rating is in amperes or amperesmax, multiplyby the
inputvoltage to obtain the VArequirement.
3. Add all of the resultant VA ratings together to obtain the total
load requirements of the equipmentto be protected(see
Figure 2).If the load consistsof the power-factorcorrected
supplies, it is recommended to use total watts for the load
requirements.
3 COMPUTERS3 MONITORSEXTERNAL
300 WATTS
EACH
3 x 300 WATTS X 1.4 = 1260 VA3x2AMPSx240V = 1440 VA50 VA
1260 V A+1440VA + 50 VA=2750 VA (Total Load Requirements)
2AMPS
EACH50 VA
MODEM
Figure 2. Volt-Amperes Calculation Example
If the totalload requirements of the equipmentexceeds the capacityof
the UPS, you must either reduce the number of pieces of equipment,or
use a UPSwitha larger load capacity.
Whendecidingonwhichpieces of equipment to remove from the UPS,
select equipmentthat has a lower priorityforpower protection.
Computers, monitors, and modems typically have a higher priority
becausethey could be processing or transmitting data whena power
outage occurs.
During a power failure, the UPS battery supplies power to your
equipment, providing time to complete computing activities prior to
UPS shutdown.The duration of thistime period is directlyrelatedto the
UPSbatteryconfiguration. By adding battery cabinets, you can
customize the UPS to provide enoughbattery time for normal p rocessing
activities.
To prepare for a power outage at your installation,ensurethat you have
sufficient battery time available.To do this,take a few minutesto
determine your approximate battery time by completing the following
steps:
Load
Requirements
(VA)
UPS ModelBatteryCabinetsTotalBattery Time
Prestige 6000(9910EP8)
Battery Time
Minutes(Approximate)
Figure 3. Determining Approximate Battery Time
1. See “Load Requirements” on page 2 for assistance in
determining the total load requirements for your UPS. Round
this number up to the next Load (VA) entry in the “Prestige
6000 with PPDM” table on page 5, and enter the number in
Figure 3.
2. In Figure3, enter the number of batterycabinetsthatyou
have installed. Find the intersection point of the appropriate
Load (VA)and number of batte ry cabinets in the “Prestige 6000
with PPDM” table on page 5. Enter this number in Figure 3,
Total Battery Time Minutes.
If changes take place in your installation, suchas different load
parametersor changesto battery cabinet configuration, take time to
reevaluate your approximate battery time availability.
NOTE Fordetailedinformationregardingcalculationof9910UPSbattery capacityand
run timeforyourload,reference: “AS/400Physical Planning,”SA41-5109,“AS/400
AdvancedSeriesBackup and Recovery-Advanced,” SC41-4305 (see Chapter 10),or
“AS/400eseries Backup and Recovery,” SC41-5304 (seeChapter37).
SAVE THESE INSTRUCTIONS.This manual containsimportantinstructions that you
shouldfollowduring installationoftheUPS.Pleasereadallinstructionsbefore
operatingtheequipmentandsavethismanual for future reference.
ThisUPScontains LETHAL VOLTAGES.Allrepairs and serviceshouldbeperformed
byAUTHORIZED SERVICE PERSONNEL ONLY.There are NO USERSERVICEABLE PARTS insidetheUPS.
:
Batteriescanpresentarisk of electricalshockorburnfromhighshortcircuit
current.Observe proper precautions.
:
Proper disposalofbatteriesis required. Refer to your localcodesfordisposal
requirements.
:
ThisUPScontains its own energy source(batteries). The output receptaclesmay
carrylive voltage even when the UPS isnotconnectedtoanACsupply.
:
Neverdispose of batteriesina fire.Batteriesmayexplodewhen exposedtoflame.
:
Neveropenor mutilatebatteries.Released electrolyteisharmfultotheskin and
eyes,andmaybeextremely toxic.
DANGER
CAUTION
:
To reduce the risk of fire or electricshock, installthisUPSin a temperatureand
humiditycontrolled,indoorenvironment,freeofconductivecontaminants.Ambient
temperaturemustnotexceed104F(40C).Donotoperatenearwateror
excessive humidity (95% max).
:
DonotremoveorunplugtheinputcordwhentheUPSisturnedon.This removes
the safetygroundfromtheUPSandtheequipmentconnectedtotheUPS.
:
The walloutletmustbewithin 2 meters of the equipment and accessibletothe
operator. The on/off switch on the UPSdoesnotelectrically isolatetheinternal
parts.Unplugtheinputcordfromthewall outlet when disconnectingtheunitfor
longperiodsoftime.
Onbuttonispressed,even if the input cord is disconnected.
7
Safety Warnings
:
To reduce theriskof fire, connecttheUPSandPPDM only tocircuits providedwith
30 amperesmaximumbranch-circuitovercurrentprotection.
:
For PPDM systems with hardwired outputs, overcurrent protection for the output
ACcircuit(s) istobeprovidedbyothers.
:
For PPDM systems with hardwired outputs, suitably rated disconnect switchesfor
the output ACcircuit(s) are to be provided by others.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER
GEM DISSE ANVISNINGER
DENNEBRUGERVEJLEDNING INDEHOLDERVIGTIGE
SIKKERHEDSANVISNINGER
DenneUPSindeholderLIVSFARLIG HØJSPÆNDING.Alle reparationer og
vedligeholdelse bør kun udføres af en AUTORISERETSERVICETEKNIKER.Ingenaf
UPS’ensindvendige dele kan repareres af brugeren.
DenneUPSindeholderegenenergiforsyning (batterier).Udgangsnetstikkene kan
ledestrøm,selv når UPS’en ikkeertilsatenAC-energikilde.
:
Skafdigaldrigafmedbatterierneved at brænde dem.Batteriernekaneksplodere
vedåbenild.
:
Batteriernebøraldrigåbneseller skilles ad. Elektrolyt, der slipper ud, er skadelig
for hud og øjne og kan væreoverordentliggiftig.
:
InstallérdenneUPSi et temperatur- og fugtighedskontrolleret indendørsmiljø, frit
for ledendeforureningsstofferforatformindske risikoenforbrand og elektrisk
stød.Rumtemperaturenmåikke overstige40°C.UPS’enbørikke betjenes nær
vandellerhøjfugtighed(maksimalt95%).
:
Netledningenmåikke fjernes og stikketmåikketrækkes ud, mensUPS’ener
tændt.Dettefjernersikkerhedsjordenfra UPS’enogfradetudstyr, der er sat til.
Stikkontakten må højst være 2 meter fra udstyretog tilgængelig for brugeren.
UPS’ensafbryderkontakt isolererikkeelektrisk de indvendigedele.Trækderfor
stikketudafkontakten, hvisenheden er slukketilangtid ad gangen.
:
Bemærkvenligst, at stikkontakternepåUPS’en er strømførende, når knappenUPS
“Output
:
UPS’enogBypass-modulet må kun tilsluttesstrømkredse, somerforsynetmeden
overstrømsbeskyttelsepå maksimalt 30 Apr. afgreningsstrømkredsforat
formindskebrandfaren.
:
Med hensyn tilBypass-systemer med direkte forbundne udgange, skal
overstrømsbeskyttelsenforAC-kredsen(e) komme andetstedsfra.
:
Med hensyn tilBypass-systemer med direkte forbundne udgange, skal
afbryderkontaktertilAC-kredsløbetmedpassendemærkeeffektkommeandetsteds
fra.
On” er trykket ned, selvomindgangsnedledningenikke er tilsluttet.
DezeUPSbevatLEVENSGEVAARLIJKE ELEKTRISCHESPANNING.Alle reparaties en
onderhoud dienenUITSLUITEND DOOR ERKEND SERVICEPERSONEELteworden
uitgevoerd.Erbevinden zichGEENONDERDELEN inde UPSdieDOORDE GEBRUIKER
kunnenwordenGEREPAREERD.
Nooitbatterijenopenenofbeschadigen.Vrijkomendelektrolytisschadelijkvoor de
huidenogen,enkanuiterstgiftigzijn.
:
Teneinde de kans op brand of elektrischeschokteverminderen dient deze UPS in
een gebouw met temperatuur-envochtigheidregelingte worden geïnstalleerd,
waargeengeleidendeverontreinigingen aanwezigzijn.Deomgevingstemperatuur
mag40ECnietoverschrijden.Nietgebruiken indebuurtvan water ofbijzeerhoge
vochtigheid(max. 95%).
:
Verwijder de ingangsnoer niet of haal de stekkervandeingangsnoerernietuit
terwijlde UPSaanstaat.HierdoorzoudeUPSenuwaangesloten apparatuurgeen
aardebeveiliging meer hebben.
:
Dehoofdvoedingcontactdoos moet zich op minderdan 2 meter van de apparatuur
bevindenenmakkelijkbereikbaar zijnvoordegebruiker.Deaan/uit-schakelaar op
de UPSbiedtgeenelektrische isolatievoordeinwendigeonderdelen.De stekker
uitdevoedingcontactdooshalen wanneer het apparaat voor lange tijd niet wordt
gebruikt.
:
Neemer nota van dat de uitgangaansluitpuntenopdeUPSaltijd onder stroom
staanwanneerdebelastingschakelaar (
|
)wordtingedrukt,ongeacht de
aanwezigheidvandevoeding.
:
Teneinde de kans op brand te verminderen mogen de UPS en BypassModule
alleenopcircuits worden aangesloten met een overstroombeveiliging van
maximaal30ampère.
:
VoorBypass Module systemen met vast-bedrade uitgangen, moet de
overstroombeveiliging voor wisselstroom uitgangcircuit(s) door derden worden
geleverd.
:
VoorBypass Module systemen met vast-bedrade uitgangen, moeten de juiste
hoofdschakelaarsvoor wisselstroomuitgangcircuit(s)doorderdenworden
geleverd.
SÄILYTÄ NÄMÄ OHJEET
TÄMÄ OPASSISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA
Tämä UPSsisältää HENGENVAARALLISIAJÄNNITTEITÄ. Kaikkikorjaukset ja huollot
on jätettäväVAIN VALTUUTETUNHUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä
MITÄÄNKÄYTTÄJÄN HUOLLETTAVIAOSIA.
:
Akustosaattaaaiheuttaasähköiskuntaisyttyätuleen, jos akustokytketään
oikosulkuun. Noudata asianmukaisiaohjeita.
TämäUPSsisältää oman energialähteen (akuston).Ulostuloliittimissä voi olla
jännite,kunUPSei ole liitettynä verkkojännitteeseen.
:
Äläkoskaan heitä akkuja tuleen.Nevoivaträjähtää.
:
Äläavaatairiko akkuja. Paljastunutelektrolyyttion vahingollinen iholle ja silmille
ja voi olla erittäin myrkyllistä.
:
VähentääksesitulipalonjasähköiskunvaaraaasennatämäUPS sisätiloihin,joissa
lämpötilajakosteus on säädettävissäjajoissa ei ole virtaajohtavia
epäpuhtauksia.Ympäristönlämpötilaeisaaylittää40C.Äläkäytälähellä vettäja
vältä kosteita tiloja (95 % maksimi).
Safety Warnings
VAARA
VARO
:
Äläpoistataiirrota sisääntulojohtoa,kunUPSonkytkettynä. Tämä poistaa
turvamaadoituksen UPS-laitteestajasiihenliitetystä laitteistosta.
:
Päävirtapistokkeen täytyyolla2m:nsäteellä laitteistostajakäyttäjän saatavilla.
UPS-laitteenvirtakytkineierotasisäosia verkkojännitteestä.Irrota
sisääntulopistoke,joskytket laitteen pois käytöstäpitkähköksi ajaksi.
:
Otamyöshuomioon, että UPS-laitteen ulostuloliittimissäonjänniteainakun
painetaanUPSinlähtötehoPÄÄLLÄ-painiketta(
tulokaapelikytkettynä tai ei.
:
Palovaaranvähentämiseksi UPSjaohituslaite tulee kytkeävirtapiiriin, jonka
haaroitusjohtojenylivirtasuojauksen maksimiarvoon30A.
CONSERVER CES INSTRUCTIONS
CE MANUEL CONTIENTDES CONSIGNESDE SÉCURITÉ
IMPORTANTES
CetonduleurcontientdesTENSIONS MORTELLES.Toute opération d’entretienet de
réparationdoitêtreEXCLUSIVEMENT CONFIÉEAUNPERSONNELQUALIFIÉ AGRÉÉ.
AUCUNEPIÈCE RÉPARABLEPAR L’UTILISATEUR ne se trouve dans l’onduleur.
DANGER!
12
ATTENTION!
:
Lesbatteriespeuventprésenterunrisquede déchargeélectrique oudebrûlurepar
descourts-circuits de haute intensité.Prendrelesprécautions nécessaires.
Cetonduleurrenfermesapropresourced’énergie (batteries). Les prisesdesortie
peuventêtresoustensionmême lorsquel’onduleur n’est pas branché surle
secteur.
:
Ne jamaisjeterlesbatteries au feu. L’expositionauxflammes risquedelesfaire
exploser.
:
Ne jamaisouvrir ou mutilerdesbatteries. L’électrolytedégagéeestnuisible à la
peau et aux yeuxetpeuts’avérerextrêmement toxique.
:
Pour réduirelesrisquesd’incendie et de décharge électrique,installer l’onduleur
uniquementàl’intérieur,dansunlieu dépourvu de matériaux conducteurs,oùla
températureetl’humiditéambiantessont contrôlées.Latempérature ambiantene
doitpasdépasser 40°C.Nepasutiliser à proximitéd’eau oudansuneatmosphère
excessivement humide (95% maximum).
:
Ne pasretirerlecordond’alimentation lorsque l’onduleurestsoustension sous
peinedesupprimerlamise à la terre de l’onduleuretdumatérielconnecté.
Laprisesecteurdoit se trouver à moins de 2 m du matériel et être accessible à
l’utilisateur.L’interrupteur de ON/OFF (marche/arrêt) de l’onduleur n’assurepas
l’isolation électrique des piècesinternes. Débrancher le cordon d’alimentation de
laprisesecteurencas de déconnexion de l’appareilpendantunepériode
prolongée.
:
Noter que lesprisesdesortie de l’onduleursontsous tension lorsqueOutput
Afinderéduirelesrisques d’incendie,nebrancherl’onduleur et le bypass que sur
descircuits dérivés équipésd’undispositif de protection contrelessurintensités
de 30 A maximum.
:
Pour lessystèmes de bypass dotés de sortie à bornier,la protection contre les
surintensitésdes circuitsdesortiedecourantalternatif est à se procurer auprès
d’unautrefournisseur.
:
Pourlessystèmes de bypassdotésdesortie àbornier,lesinterrupteurs adaptésau
circuitdecourantalternatif sont à se procurer auprès d’un autre fournisseur.
DieUSVführt lebensgefährlicheSpannungen. Alle Reparatur- und Wartungsarbeiten
solltennurvonKundendienstfachleuten durchgeführt werden.DieUSVenthält keine
vomBenutzerzuwartendenKomponente
VORSICHT!
:
BatterienkönnenaufgrunddeshohenKurzschlußstromsElektroschocks oder
Verbrennungenverursachen. DieentsprechendenVorsichtsmaßnahmensind
unbedingtzubeachten.
:
DieBatterienmüssen ordnungsgemäß entsorgt werden.Hierbeisind die örtlichen
Bestimmungenzubeachten.en.
:
DieseUSVist mit einer eigenenEnergiequelle(Batterie) ausgestattet.Anden
Ausgangssteckdosen kann auchdann Spannung anliegen,wenndieUSV nicht an
einerWechselspannungsquelleangeschlossen ist.
UmdieBrand- oder Elektroschockgefahr zu verringern,diese USVnurinGebäuden
mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine
leitendenSchmutzstoffen vorhanden sind.DieUmgebungstemperatur darf 40EC
nichtübersteigen.Die USV nichtinderNähevonWasser oder in extrem hoher
Luftfeuchtigkeit (max. 95 %) betreiben.
:
DasEingangskabelnichtentfernenoder abziehen,währenddieUSV eingeschaltet
ist,weilhierdurch die SicherheitserdungvonderUSVunddendaran
angeschlossenen Geräten entfernt wird.
:
DieNetzsteckdose,die zurHauptversorgung verwendetwird, darfsichnichtweiter
als2MetervomGerätwegbefindenundmußfürdenBedienererreichbar sein.
DerEin-/Aus-SchalterderUSVbietet keineelektrischeIsolationder internenTeile.
WenndasGerätlängereZeitnicht benutzt wird, sollteesvonderNetzsteckdose
abgezogenwerden.
:
Beachten,daßdie Ausgangssteckdosen aufderUSV jedesmalStrom führen,wenn
der Belastungsschalter (
|
)gedrücktwird,ungeachtet dessen, ob die USVmit
Stromversorgtwird.
:
UmdieBrandgefahr zu verringern,die USVundBypass ModulenuranStromkreise
miteinemZweigleitungsüberstromschutzvonmaximal 30 Ampere anschließen.
:
FürBypass-Systememitfestverdrahteten Eingängen mußderÜberstromschutz für
dieAusgangswechselstromkreiseanderweitig bereitgestelltwerden.
:
FürBypass-SystememitfestverdrahtetenAusgängenmüssenTrennschalter fürdie
Ausgangswechselstromkreise mitpassendemNennwertanderweitigbereitgestellt
werden.
IMPORTANTIISTRUZIONI DI SICUREZZA
CONSERVAREQUESTE ISTRUZIONI
QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONIDI
SICUREZZA
laTENSIONEcontenutainquesto gruppo staticodicontinuità è LETALE.Tuttele
operazionidiriparazione e di manutenzione devono essereeffettuate
ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO.All’interno del gruppo
staticodicontinuità NON visonoPARTI RIPARABILI DALL’UTENTE.
lebatteriepossonopresentarerischio di scossaelettrica o di ustioniprovocateda
altacorrentedovutaacortocircuito. Osservareleappositeistruzioni.
lebatteriedevonoesseresmaltite in modo corretto.Per irequisitidismaltimento
fare riferimentoalledisposizionilocali.
Safety Warnings
:
questogruppostaticodicontinuità contiene una fonte di energia autonoma (le
batterie).Lepresediuscita possonocondurretensioneenergizzata quandoil
gruppo staticodicontinuità non è collegato con una fonte di alimentazionea
correntealternata.
:
non gettare mailebatterienelfuocopoichèpotrebberoesplodere se esposte alle
fiamme.
:
maiaprirenèmutilarelebatterie poichè l’elettrolitadaesserilasciato è nocivo
allacuteeagliocchi e può essere altamente tossico.
:
per ridurreilrischio di incendioo discossaelettrica, installareilgruppostatico di
continuitàinunambienteinterno a temperaturaedumiditàcontrollata, privo di
agenticontaminanticonduttivi.Latemperaturaambientenondevesuperarei
40EC.Nonutilizzare l’unità in prossimitàdiacqua o inpresenzadiumidità
eccessiva (95% max).
:
non rimuoverenèscollegare il cavodiingressoquandoilgruppostatico di
continuitàèacceso poichè in tal modo sidisattiverebbe il collegamentoaterradi
sicurezzadel gruppostaticodicontinuitàedell’apparecchiaturaadesso collegata.
:
lapresadialimentazione principalenondevetrovarsiaoltre2metri
dall’apparecchiatura e deve essere accessibile all’operatore.L’interruttoreon/off
delgruppostaticodicontinuità non isola elettricamenteicomponenti interni.
Scollegarel’unità dalla presa dialimentazione quandorimaneinriposoperlunghi
periodiditempo.
:
sinotichelepresedia limentazionediuscitadelgruppo staticodicontinuitàsono
elettricamenteenergizzateogniqualvoltavienepremutol’interruttore azzurrodi(
attivazioneuscita, a prescinderedalfattocheilgruppostatico di continuità sia
alimentatoomeno.
|
)
:
per ridurreilrischio di incendio,collegareil gruppo statico dicontinuitàeil
sistemaBypass Module esclusivamente con circuitiprovvisti di protezioneda
sovracorrentemassima di 30 ampere per circuitoderivato.
:
neisistemiBypass provvistidi uscite cablate,idispositividiprotezioneda
sovracorrenteperil/i circuito/iacorrentealternatainuscita devono essere forniti
da terzi.
:
neisistemiBypass provvistidiuscite cablate,isezionatori di corrente nominale
adeguata per il/icircuito/i a corrente alternatainuscitadevonoessere forniti da
terzi.
DenneUPS’eninneholder LIVSFARLIGE SPENNINGER.Allreparasjon og servicemå
kun utføres avAUTORISERTSERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE
SERVICEPÅNOEN AV DELENE i UPS’en.
Batteriermå aldriåpnesellerødelegges. Frigjorteelektrolyttererskadeligeforhud
og øyneog kanværeekstremtgiftige.
:
Foråreduserefare for brannellerelektriskestøt,børdenneUPS’en installeresiet
innendørsmiljømed kontrollert temperatur og luftfuktighetsomerfrittfor
ledende,forurensendestoffer.Romtemperaturenmåikke overskride40C.Denmå
ikkebrukesi nærheten av vann eller vedmegethøyluftfuktighet(95% maks.).
:
Strømforsyningskabelen må ikkefjerneseller trekkes ut når UPS’ener på,slikat
ikkesikkerhetsjordingenfjernesfraUPS’en og detutstyretsomerforbundet
medden.
:
Stikkontakten må befinne seg innen 2 m fra utstyret og må være tilgjengelig for
operatøren.Av/På-bryteren på UPS’en isolererikke de internedelene.Trekkut
ledningenfrastikkontakten når utstyret frakoplesoverlengretidsrom.
FARLIG
FORSIKTIG
18
:
UPS’ensstikkontakterfor utgangsstrømforsyning er strømførende når
lastbryteren(
:
Foråreduserefareforbrann,måUPS’enogPPDMbaretilsluttes strømkretser
meduttaksomharoverstømvern på maksimalt 30 ampere.
:
For PPDM systemer med fastkoplete uttak, må overstrømvern for
vekselstrømuttak(ene)stilles til rådighet avandre.
:
For PPDM systemer med fastkoplete uttak, må passende utkoplingsbryterefor
vekselstrømuttak(ene)stilles til rådighet avandre.
GUARDE ESTASINSTRUÇÕES
ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA
IMPORTANTES
AUPScontémVOLTAGEM MORTAL. Todososreparose assistênciatécnica devemser
executadosSOMENTEPOR PESSOALDAASSISTÊNCIATÉCNICAAUTORIZADO. Não
há nenhuma PEÇAQUEPOSSA SER REPARADA PELO USUÁRIOdentro daUPS.
:
Asbateriaspodemapresentar oriscodechoqueelétrico, ou queimaduras
provenientesdealtacorrentedecurto-circuito.Observeasinstruções adequadas.
EstaUPScontém suaprópriafontedeenergia(baterias).Osreceptáculos desaída
podemcontervoltagemativa quando aUPSnãoseencontraconectadaauma
fonte de alimentaçãodecorrentealternada.
:
Nuncajogueasbateriasnofogo,porquehárisco de explosão.
Para reduziroriscodeincêndios ou choques elétricos,instale a UPS em ambiente
internocomtemperaturaeumidadecontroladase livres de contaminadores
condutíveis. A temperatura ambiente não deve exceder40EC.Nãooperepróximo
a água ou em umidadeexcessiva (máx: 95%).
:
Não removaoudesconecteocabodeentradaquandoaUPSestiver ligada. Isto
removeráoaterramentodesegurançadaUPSedoequipamentoconectado.
:
Osoquetedealimentação principaldeve estar no máximo doismetrosdo
equipamentoeacessível ao operador.Ointerruptor on/offdaUPSnãoisola
eletricamenteaspeças internas. Desconecte-odosoquetedealimentação senão
for usá-loporumlongoperíodo.
:
Favorobservarqueosoquetedealimentação de saída na UPS estará
eletricamenteativo todas as vezes que o interruptor (
indiferenteàpresençadeenergiaelétrica na rede de alimentação.
Para reduziroriscodeincêndios, conecteaUPSsomenteaumcircuito com
proteçãodesobrecargadederivação denomáximo30ampères.
:
Para sistemasBypass comsaídasconectadas, a proteção de sobrecarga para
circuitosde saídadecorrentealternadadeveser fornecida por outros.
:
Para sistemasBypass comsaídasconectadas, interruptores de desconexão
devidamentequalificadosparacircuitosde saídade correntealternadadevemser
fornecidosporoutros.
Предупреждения по мерам безопасности
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
СОХРАНИТЕ ЭТИ УКАЗАНИЯ
ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ
УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
ОПАСНО
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ.
Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО
УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ.
Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.
20
ОСТОРОЖНО
:
Аккумуляторы могут вызвать опасность поражения электрическим
током или ожога от тока короткого замыкания. Соблюдайте
соответствующие меры предосторожности.
:
Необходимо соблюдать правила утилизации аккумуляторов.
Обратитесь к местным нормативным актам за информацией о
требованиях к утилизации.
:
Данный ИБП содержит собственные источники энергии
(аккумуляторы). На выходных розетках может иметься напряжение,
даже когда ИБП не подключен к сети переменного тока.
:
Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут
взорваться под воздействием огня.
:
Никогда не открывайте и не деформируйте аккумуляторы.
Вытекающий электролит опасен для кожи и глаз, и может быть
крайне токсичным.
Для снижения опасности пожара или поражения электрическим
током устанавливайте ИБП в закрытом помещении с
контролируемыми температурой и влажностью, в котором
отсутствуют проводящие загрязняющие вещества. Температура
окружающего воздуха не должна превышать 40°С. Не
эксплуатируйте устройство около воды или в местах с повышенной
влажностью (макс. 95%).
:
Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки
при включенном ИБП. При этом защитное заземление отключается
от ИБП и от оборудования, подключенного к ИПБ.
:
Настенная розетка должна находиться в пределах 2 метров от
оборудования и быть доступной для оператора. Выключатель ИБП
не отключает внутренние узлы от входного электропитания. При
отключении оборудования на продолжительные интервалы времени
отсоедините входной сетевой шнур от настенной розетки.
:
Пожалуйста, обратите внимание на то, что выходные розетки ИБП
находятся под электрическим напряжением, если была нажата
кнопка включения выхода (
|
) ИБП, даже если входной сетевой
шнур отключен.
:
Для снижения опасности пожара подключайте ИБП и блок байпаса
только к цепям, оснащенным защитой от перегрузки по току,
рассчитаннойнамаксимальныйтокветви30ампер.
:
Для блока байпаса с неразъемными выходами защита от перегрузки
по току выходной(ых) цепи(ей) переменного тока должна
обеспечиваться сторонними организациями.
:
Для блока байпаса с неразъемными выходами сторонними
организациями должны быть обеспечены выключатели
выходной(ых) цепи(ей) переменного тока, рассчитанные на
соответствующий номинал.
INSTRUCCIONESDE SEGURIDAD IMPORTANTES
GUARDE ESTASINSTRUCCIONES
ESTEMANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD
IMPORTANTES
EsteSIEcontieneVOLTAJES MORTALES. Todaslasreparaciones y elservicio técnico
deben serefectuadosSOLAMENTE POR PERSONALDESERVICIO TÉCNICO
AUTORIZADO. No hay NINGUNA PARTEQUE EL USUARIO PUEDAREPARAR dentrodel
SIE.
:
Lasbateríaspueden presentarunriesgodedescargas eléctricaso de quemaduras
debidoalaaltacorrientedecortocircuito. Presteatenciónalasinstrucciones
correspondientes.
:
Esnecesariodesechar las bateríasde un modo adecuado.Consultelasnormas
localesparaconocer los requisitospertinentes.
:
EsteSIEcontienesupropia fuente deenergía(lasbaterías). Losreceptáculosde
salidapuedentransmitircorrienteeléctricaauncuandoelSIE no esté conectadoa
un suministrodecorriente alterna (c.a.).
:
Nuncadesechelasbaterías en el fuego. Las bateríaspuedenexplotarsise las
exponealallama.
PELIGRO
PRECAUCIÓN
22
:
Nuncaabranidañelasbaterías.El electrolitoque seliberaesperjudicial para la
pielylosojos, y puede ser extremadamentetóxico.
:
Para reducirelriesgodeincendio o de choque eléctrico,instale esteSIEenun
lugarcubierto,contemperaturayhumedad controladas, libredecontaminantes
conductores.Latemperaturaambientenodebeexcederlos40EC.Notrabajecerca
delaguao conhumedadexcesiva (95% máximo).
:
No retireo desenchufeelcabledeentradamientrasel SIE se encuentre
encendido.Estosuprime ladescargaatierradeseguridad delSIEydelosequipos
conectadosalSIE.3
:
Eltomacorriente debe encontrarseamenosde 2 metrosdelequipoyser accesible
para eloperador. El interruptor de encendido/apagadodelSIEnotieneaislación
eléctricade laspartesinternas.Desenchufeelcabledeentrada deltomacorriente
de lapared cuandodesconectelaunidad duranteperíodoslargos.
Tenga en cuentaquelosreceptáculos de salidadelSIEtienencorrienteeléctrica
siemprequeseoprimeelbotónpulsador de conexión de salidadelSIE(Output
ON),auncuandoelcable de entrada estédesconectado.
:
Para reducirelriesgode incendio,conecteelSIE y elbypasssolamente a circuitos
conprotecciónporsobreintensidad de las ramasdeun máximode30A.
:
Para lossistemas de bypass consalidascableadas, la protecciónpor
sobreintensidadparael(los) circuito(s) de la salidade c.a.sedeberáadquirir aun
tercero.
:
Para lossistemas de bypass consalidascableadas, losinterruptoresde
desconexiónregulados adecuadamente para el (los)circuito(s)delasalidadec.a.
deberán seradquiridosauntercero.
Säkerhetsföreskrifter
VIKTIGA SÄKERHETSFÖRESKRIFTER
SPARA DESSA FÖRESKRIFTER
DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA
SÄKERHETSFÖRESKRIFTER
Safety Warnings
FARA
DennaUPS-enhetinnehållerLIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD
SERVICEPERSONAL får utföra reparationer ellerservice.Det finns inga delar som
ANVÄNDAREN KAN UTFÖRASERVICE PÅ inuti UPS-enheten.
Minska risken för brand ellerelektriska stötar genom att installeradenna
UPS-enhetinomhus, därtemperaturochluftfuktighetärkontrolleradeochdäringa
ledandeföroreningarförekommer.Omgivandetemperaturfårejöverstiga 40C.
Användinteutrustningennäravatteneller vid hög luftfuktighet(max95%).
:
Ta aldrig bort nätsladden när UPS-enheten är påslagen.Dettatarbort
säkerhetsjordningen från både UPS-enhetenochdenanslutnautrustningen.
:
Vägguttagetfårvara högst2meter frånutrustningenoch måstevarainomräckhåll
för användaren.UPS-enhetensströmbrytare isolerarinteelektriskt de interna
delarna.Vid längre avstängning bör nätsladdendrasurvägguttaget.
On button) trycks ned, oberoende av om spänningskällan är
tillkopplad ellerinte.
:
Minskabrandrisken genom att ansluta UPS-enheten ochförbikopplingsmodulentillkretsar som försettsmedöverströmsskyddi form av en
avgreningskoppling på max 30 ampere.
:
Överströmsskyddfördeutgåendeväxelströmkretsarnaskatillhandahållasavandra
för fast anslutna förbikopplingssystem.
:
Strömbrytareförbortkopplingmedpassande dimensionerförde utgående
växelströmkretsarna ska tillhandahållas av andra för fast anslutna
förbikopplingssystem.
The following sectionsdescribe UPS storage requirements and the
installationand startup of the UPS.
Unpacking and Inspection
Carefully unpack the UPS and any other cabinets, making sure to retain
the packagingmaterials. Examineeach unit carefully for any signs of
damage and immediately notify your distributor if damage is present.
For assistance with the IBM 9910 UPS, see Chapter 8, “Service and
Support”on page 75.
UPS and Battery Cabinet Storage
If you plan to store the UPS or battery ca binets prior to use, store them
in a cool,dry environment. Storage temperature shouldnotexceed
35C(95F)inordertopreservebatterylife.Forlongertermstorage,
energize the power processingunit and battery cabinet for
approximately 8 hoursevery 90 days in order to maintain battery
charge.
Whenever the unitsare not energized,verify the circuit breakeron all
battery cabinets is returned to the OFF (O) position (see Figure 9 on
page 36).
UPS with PowerPass Distribution Module Installation
The PPDMhas a Maintenance Bypassfeature that suppliespower to
your equipment even when the PPU is removed for maintenance or
upgrades. TherearethreePPDMmodels: the L6-30R/IEC 320-C19
PPDM, the IEC 309 PPDM, and the L6-30R/5-15R PPDM. The rear
panels of these models are shown in Figure 5 on page 33, Figure 7 on
page 34, and Figure 8 on page 35, respectively.
Use the following procedure to install the PPU and battery cabinets with
the PPDM:
1. Place the UPS nearthe equipmentto be protected.The UPS
should be well ventilated and away from direct sunlight or
otherheat source.
Stack the PPU, battery cabinets,and PPDM as shown in
Figure 4.
If more than two batteriesareto be used, place the batteries
next to the other batteries. (See the FCC Statement in the front
of this manual for more information on radio-frequency
emissions.)
32
NOTE Donotconnectmorethansixstandard battery cabinets to the PPU.For
extendedbatteryruntimes,contact your localdistributorforadditional battery
cabinets.Do not placemorethansixcabinets in one stack(thePPUisequalto two
cabinetsandthePPDMisequalto twocabinets).
3. For L6-30R/IEC320-C19 PPDM ModelsOnly: The factory default for
the PPDM output neutral is grounded. In some countries, the
output neutral should not be grounded. If your application
requires an ungrounded output neutral, continue with Step 3;
otherwise, skip to Step 4.
For ungrounded output neutral applications only. Remove the
ground screw, rotate the ground cover until it snaps into place,
and reinstall the ground screw in the ungrounded position (see
Figure 6).
5. Select the correct UPS output voltage accordingto the PPDM
model:
PPDMModelNumberUPS Voltage SelectorSwitch Position*
L6-30R/IEC 320-C19 208: 120/208
L6-30R/5-15R 208: 120/208
IEC 309/IEC 320-C13 240: 240Set to 220V for 220V PPDM output
Set to 230V for 230V PPDM output
Set to 240V for 240V PPDM output
L6-30R/5-15R 240: 240Set to 200V for 100/200V PPDM output
Set to 220V for 110/220V PPDM output
Set to 230V for 115/230V PPDM output
Set to 240V for 120/240V PPDM output
*
The UPS output voltage shouldbesetaccordingtolocalmainsvoltage.
208
Using a screwdriver, turn the switch to the corresponding
positionof the output voltage required (see Figure10). The
output voltage is factory-set to 220V.
CAUTION
DonotturntheVoltageSelector switchwhilethe UPSis operating (see“Changingthe
OutputVoltage” on page 49). Changing the output voltagewhiletheUPSisoperating
maycauseanemergencypower-off.
6. Plug the input and output power cords of the PPDM into the
input and output power connectors on the PPU rear panel.
Figure 19 on page 52 shows the PPDM and PPU rear panel
connections.
7. The e quipment to be protected by the UPS should be powered
off.Plugtheequipmentintothepower output receptacleson
the PPDM rear panel.
NOTES
:
UsetheIEC320-C19/C20outputcordprovided with the PPDM to connect the
AS/400tothePPDM.
:
Youmayhave to use the output cordprovidedwiththePPDM for230Vusage.
:
WhenusingthePPDM,itis recommended that the equipment not be plugged
intothePPU.
:
Donotprotectlaserprinterswith the UPS/PPDM becauseofthe exceptionally
highcyclic power requirementsofthe heatingelements.
8. Plug the battery cord into the battery co nnector on the PPU. All
batteryconnectors are polarized to prevent incorrect
connection.
9. If additional battery cabinets are to be used, plug the battery
cordof the secondcabinetintothe battery connectorof the first
cabinetafter pivoting the battery connector guardoutof the
way. Followthisprocedure foreach additional battery cabinet.
10. Remove the breaker tie from the circuit breaker on all battery
cabinets.
11. If you are using a REPO switch, follow the “REPO Installation”
instructions on page 41.
12. Forthe AS/400 interface,plugthe AS/400 communications
cable into the serial port on the UPS rear panel. Plug the other
end of the cable into the J 14 connector on your A S/400.
Specificlocations of the J14 serial port are listedbelow
according to the AS/400 model:
:
AS/400 Models 3xx/5xx - located on the base power supply
on the back of the system unit
:
AS/400 Models 600/S10/620/S20 - on the power supply
:
AS/400 Models 640/S30/650/S40/SB1 - onthe right side of the
regulator cage in the back of the tower
13. Startthe UPS accordingto the following“UPS with PPDM
Startup”procedure.
UPS with PPDM Startup
To start up the UPS:
1. If you are connectingthe UPS to an AS/400, the Q UPSDLYTIM
system value for the UPS Monitoring feature should be set. See
“UPS Monitoring” on page 50 for instructions.
2. Verifythe PPDM input breaker is in the OFF (O) position (does
not apply to the IEC 309 PPDM).
3. Confirm the correct UPS output voltage is selected (see Step 5
on page 37).
4. Turnonthe equipmentthat is connected to the UPS.
5. Confirm the Bypass switch on the PPDM rear panel is in the
NORMAL position.
6. Plug the input power supply cord into the utility input
receptacleon the PPDM rear panel.
7. Plug the other end of the power supply cord into a grounded,
three-wire, AC receptacle that has beenwiredin accordance
withNEC specifications or national wiringrules. See Chapter 6,
“Specifications” on page 65 for the input current/output voltage
requirements.
8. Switchthe circuit breakerto the ON (
on page 36)on each batterycabinetconnectedto the PPU.
Each battery cabinet performsa self-test and thenentersnormal
operation. The battery cabinet startup shouldtake about three
seconds.
9. Verify that the circuit protectors for output receptaclesare in
the ON position (pushed in).
10. Switchthe PPU inputbreakerto the ON (
Figure 9 on page 36).
11. Switch the PPDM input breaker to the ON (
not apply to the IEC 309 PPDM).
The UPS performs diagnostic tests and enters Normal mode
with the equipment (load) offline.The
lit. The startup should take about 15 seconds.
12. Press and hold the Output
beep (approximatelyone second).
On button untilyou hear the UPS
|
) position (see Figure 9
|
) position (see
|
) position (does
indicator remains
40
The
on.The frontpaneldisplaysthe percentage of full load being
applied to the UPS. The UPS is now in Normal mode with the
load online. See “Normal Mode” on page 46 for more
information.
13. If you connected a REPO switch to the UPS, test the switch
while the UPS is operating to ensure proper operation.
Press the REPO switch. The UPS shuts down and stops
providing power to the equipment. Torestart the UPS, follow
the startup procedure beginning on page 39.
NOTE Ifthe REPOtestfailsandtheUPSdoesnot shutdown,contact your service
representative.
indicator remains lit and the Self Test indicator turns
Installation
REPO Installation
TheREPOswitchisa customer-suppliedswitchthatcan disconnectUPS
outputvoltage from your protectedequipment. If you areusinga REPO
switch, you need a junctionbox, exte rnal wiring,and a switch w ith the
following specifications:
:
The switch shouldbe a wall-mounted, momentary-contact, normally
open, pushbutton switch.
:
Minimumratingsof 240 Vac and 35 mA.
:
Wire should be 18 AWG (0.75 mm
2
) minimum.
CAUTION
:
Theblackand whiteREPOwires are athigh-voltagepotential (240V).Refertoyour
localelectrical code for proper installationofthehigh-voltage REPO wires.
:
To ensure the UPS stops supplyingpowertotheloadduringanymodeof
operation,theinputpowermustbedisconnected from the UPS when the
emergencypower-offfunction isactivated.
The optional three-wire REPO cord (see Figure 11) can be ordered from
the manufacturer. The green wire is a safety ground for the REPO
conduit. The REPO functionactivateswhentheblack and white wiresof
the optional emergencypower-offcord are shorted together.
1. Groundthe green REPO wire to the junctionbox.
2. Connect the REPO cord to the conduit inside a junction box by
twistingthe ends of exposed wire together with the wire nuts
(see Figure 11). Twist the wires until tight.
3. Pivotthe REPO receptacle guard out of the way, plug the REPO
plug/receptacle PPU connector into the REPO receptacle on the
PPU rear panel and twist the connector in place (see Figure 9
on page 36).
If you are using the optional REPO cord junctionbox, place the conduit
through the access hole on the junctionbox. Connect the exposed
conduit wiresto the corresponding compression terminals (see the
following table). Tighten the compression terminals with a screwdriver
(see Figure 12).
If you should encounter any problems during startup, see the
troubleshooting chart on page 71.
The battery cabinets are shipped with the batteriescharged. However,
batteriesmay lose some of the charge duringshipping and storage. You
can use the UPS immediatelyafterunpacking, butit may not providethe
full-rated backup time during a power failure. Upon initialstartup, the
UPS may need to operate for approximately8 hours before the battery is
fullycharged and full battery-backuptime is available.If the Battery
Fault indicator flashes, operate the UPS for 24 hours to fully charge the
battery.
OptionalREPO Cord JunctionBoxConnections
Terminal Wire Size
Position
L1TB1-4
L2TB1-5
Ground
The REPO function activates when L1andL2are shorted together.
Thischaptercoversthe operationof the UPSincluding front panel
functions, operatingmodes,usingtheBatteryStartfeature, shutting
down the UPS, and using the PowerPass Distribution Module.
UPS Front Panel
The UPS front panel has three distinct functions:
:
Displays the UPS operational mode (Normal, Bypass,or Battery).
:
Displays any alarm conditions present during operation (the
indicators flash).
:
Displaystheloadingpercentage duringNormalmode and the battery
capacity duringBatterymode.
You can alsouse the front panel to configure UPS communication
options.See “Front Panel Communications Access” on page 56.
Output OnButton
(UPS on, load online)
Output OffButton
(UPS off, load offline)
Sine Wave Indicator
Overload Indicator
Site Fault Indicator
Overtemp Indicator
Battery Fault Indicator
Self T estIndicator
After you install and apply power to the UPS, the UPS filters and
regulates incoming AC power,eliminating noise and voltage spikes, and
providesconsistentpower to your equipment (see Figure 14). While
power is applied to the UPS,themaintenance-free battery is
automatically kept in a fully-charged condition.
Bypass Line
Utility
Power
Surge
Suppression
EMI/RFI
Filters
Receptacle
or
T erminal
Block
Rectifier
Inverter
Output
EMI/RFI
Filters
Receptacle
Battery Cabinets
Emergency
Power-Off
or
T erminal
Block
Battery
Charger
BatteryBattery
Figure 14. UPS Block Diagram
Normal Mode
During Normal mode, the
displaysthepercentage of UPS load capacity being used by the protected
equipment (see Figure15).
The
indicating Bypassmode (see Figure16).Whenthe UPS is inBypass
mode, the load is powered by utility power. However ,utility power
continues to be passively filtered by the UPS.
indicator and theindicator illuminate simultaneously,
OVERLOAD
SITE FAULT
OVERTEMP
BATTERY
SELF TEST
LOAD ON
UNITON
BYPASS
Figure 16. Bypass Operation Indicators
Battery Mode
Whenthe UPS is operating duringa power outage,thealarm beeps
several times initially, and then once every 10 seconds while in Battery
mode. The
approximate percentage of battery capacity remaining. You can calculate
the app roximate minutes of battery time by multiplying the “Total
Battery Time Minutes” (see Figure 3 on page 4) times the percentage
indicatedby the Battery Operation indicators(see Figure 17). When the
utility power returns, the UPS switches to Normal mode operation while
the battery recharges.
indicator illuminates. The front panel displays the
OVERLOAD
SITE FAULT
OVERTEMP
BATTERY
SELF TEST
BATTER Y
ONLINE
>75%
CAPACITY
REMAINS
BATTER Y
ONLINE
>50%
CAPACITY
REMAINS
BATTER Y
ONLINE
>25%
CAPACITY
REMAINS
BATTER Y
ONLINE
LOW
BATTER Y
WARNING
Figure 17. Battery Operation Indicators
If battery capacity becomes low while in Battery mode, the Battery Fault
indicator beginsto flash and the Self Test indicator remainslit,
indicating approximately two minutesbefore UPS shutdown.The alarm
beeps every two seconds.
When shutdown is imminent, the Self Test indicator flashes. These
warnings are approximate, and the actual time to shutdown may vary
significantly. For approximate battery times see the table on page 5.
Once these warningsareindicated,immediately complete and save your
work to prevent data loss and similar difficulties. When utility power is
restored afterthe UPS shuts down, the UPS automaticallyconnects to
the load when thestartupis complete.
The UPS periodically performs diagnostic tests while the unit is
operating in Normal mode, ensuringproperoperation. These tests
include:
:
Self Test
:
Utility Verification Test
:
Battery Discharge Test
:
Over Temperature Test
The UPS also runs a seriesof over 20 internaltestswhenpower is first
applied.If a diagnostictest fails,see Chapter 7, “Troubleshooting” on
page 71.
Battery Start
48
Battery Test on Demand
You c a n perform a battery test on the UPS while it is operating in
Normal mode by pressingthe Output
automatically distributes some of the load to the ba tteries for 30 sec onds
and tests the battery’s performance.
NOTE Before using thisfeature,theUPS must havebeenpoweredbyutilitypower at
leastonce.
This feature allows you to start the UPS withoututilitypower.After
utility power has been unavailable for one minute, press and hold the
Output
The UPS supplies power to your equipment and goes into Battery mode.
Theindicator remains lit and thefront panel displays the percentage
of battery capacity remainingto the UPS. This process shouldtake about
15 seconds.
Performing a UPS shutdown turns off the power to your protected
equipment. Confirm the equipment is prepared for a power-off before
shutting down the UPS.
NOTE Donotperforma UPSshutdownifyouwanttousetheMaintenanceBypass
feature on the PPDM (see“Using the PPDM”onpage51).
To perform a UPS shutdown:
1. Press and hold the Output
ceases (approximately threeseconds).
The
offline.
2. Switchthe input breakeron the powerprocessing unit to the
OFF (O) position.
The UPS enters Battery mode forseveralseconds.The
3. Unplug or remove utility power from the UPS.
4. When all LEDs are no longer illuminated on the UPS, switch
the circuit breakerto the OFF (O) positionon each battery
cabinet.
indicator remains lit indicating Normal mode, load
indicator turns off and the UPS shuts down.
Off button untilthe long beep
Changing the Output Voltage
To change the operating voltageof the UPS:
1. Perform a UPS shutdown as described in the previous section.
2. Select the new voltage(see Step 5 on page 37).
3. Restart the UPS by performing a UPS startup as describedon
UPS monitoring is a standard fe atureof the AS/400 operating system.
QUPSDLYTIM is a timer in the AS/400 that tells the system how long to
run on UPS power before shutting down. Each AS/400 system is initially
assigned a defaultvaluefor QUPSDLYTIM.
To determine the default value for your system or to change the value,
refer to the Uninterruptible Power Supply section in one of the
following IBM documents:
:
“AS/400Advanced Series Backup and Recovery - Advanced,”
SC41-4305 (for AS/400 Models 3xx a nd 5xx)
:
“AS/400e series Backup and Recovery,” SC41-5304
(for AS/400 6xx and Sxx)
V4R1 Bac k up and Recovery information (AS/400 Models 3xx, 5xx, 6xx
and Sxx) is alsoavailableon the CustomerDocumentation AS/400
Softcopy Library CD (SK3T-0118) and on the Internet at:
The PPDM provides c ontinuous online powe r for your equipment. With
the PPDM, you can replace or upgrade the PPU without losing power to
your equipment. Figure 18 shows the operation of the UPS with the
PPDM.
Utility
Power
In
PPU
Out
PPDMUPS Load
Battery
Figure 18. UPS and PPDM Block Diagram
Battery
Disconnecting the UPS
Use the following procedure to transfer the critical load to Maintenance
Bypass (AC Line operation) and remove the PPU:
1. Turn the Bypass switch on the PPDM to the BYPASS position
(see Figure 19). The PPDM is now powering your equipment
from utility power.
2. Press and hold the Output
ceases (approximately threeseconds). The
remains lit.
3. Switch the PPU input breaker to the OFF (O) position.
The UPS enters Battery mode forseveralseconds.The
Use the following procedure to reinstall the PPU and transfer the critical
load from Maintenance Bypass (AC Line operation) to the PPU:
1. Reconnectthe battery cabinet to the battery connectoronthe
PPU rear panel.
2. Switchthe circuit breakeron all battery cabinets to the ON (
position.
3. Confirm the correct UPS output voltage is selected according to
the PPDM model:
PPDMModelNumberUPS Voltage SelectorSwitch Position*
L6-30R/IEC 320-C19 208: 120/208
L6-30R/5-15R 208: 120/208
IEC 309/IEC 320-C13 240: 240Set to 220V for 220V PPDM output
Set to 230V for 230V PPDM output
Set to 240V for 240V PPDM output
L6-30R/5-15R 240: 240Set to 200V for 100/200V PPDM output
Set to 220V for 110/220V PPDM output
Set to 230V for 115/230V PPDM output
Set to 240V for 120/240V PPDM output
208
|
)
*
The UPS output voltage shouldbesetaccordingtolocalmainsvoltage.
Using a screwdriver, turn the switch to the corresponding
positionof the output voltage required (see Figure20). The
output voltage is factory-set to 220V.
CAUTION
DonotturntheVoltageSelector switchwhilethe UPSis operating (see“Changingthe
OutputVoltage” on page 49). Changing the output voltagewhiletheUPSisoperating
maycauseanemergencypower-off.
The UPS is factory-configured for one of several communication
interfaces (usually determined by the customer). To determine the
initial UPS communications configuration, you can:
:
Look at the box label with the serial number (communicationmode
is shown in the upper right corner).
:
Use the Display Configurationoptionon the UPS Se rial
Communications Menu (see page 58).
:
For assistance with IBM 9910 UPSs, see Chapter 8, “Service and
Support”on page 75.
If you want to change the UPS configuration settings, use the front panel
or the UPS Serial Communications Menu.
To access the frontpanelcommunication options,performthe following
steps:
1. If the UPS is powered on, prepare your equipment for
shutdown.
Press and hold the Output
Off button untilthe long beep
ceases (approximately threeseconds).
The
indicator remains lit indicating Normal mode, load
offline.
Switchthe inputbreakeron the power processing unit to the
OFF (O) position.Wait until all indicatorsturnoffand then
continue to the next step.
|
2. Switchthe PPU input breaker to the ON (
pressing the Output
Off button untilthe alarm beeps. All
) position while
indicators beginflashing.
3. Press and hold the Output
Off button a second time untilthe
alarmbeeps again.
A single indicator, corresponding with the current setting,
remains flashing.
4. Press the Output
Off button to scroll through the
communicationoptions,top to bottom. Each time you pressthe
button, the UPS beeps and the next indicator flashes.
NOTE Ifyoudonotsaveaselection within 30 seconds,thesetupautomatically
abortsandswitchesback to the original configuration.
5. Press and hold the OutputOn button until the alarm beeps to
select and save a communicationoption. Failure to release the
buttonimmediately after the beep will cause the UPS to abort
the setup.
6. Press the Output
On button again to returnthe UPS to
Normalmode.
NOTE Printermodeselections are the only serialcommunication modes available
fromthe front panel.
With the UPS Serial Communications (Main) Menu, you can view or
select UPS communication modes,baud rates, and LAN configurations.
To change or displaythe current communications configuration:
1. Connectthe UPS serial port to a videomonitorwitha serial
interface or to yourcomputer’sserial port. If you are using
OnliNetor LanSafesoftware, the UPS should alreadybe
connectedto your computer.
2. Set your terminalso that it matches the baud rate of the UPS
(usually2400 baud, 8 bits, No parity, 1 stop bit). Refer to your
terminal or operatingsystemdocumentation fordetailson
configuring the terminal communication settings.
3. At the terminal prompt,press
Communications Menu appears.
NOTE Catalog#,Serial#,andVersion# are allidentification numbers unique to your
UPSandcanalsobefoundontheUPSnameplate.
1 > Continuous Dump The UPS regularly transmits status
informationto the computer.Baud rates of 1200 to 2400 a re
recommended to reduce host computer overheadwhen using
this mode.
2 > Polled Dump Status information is transmitted only when
requested by a poll character (Control-E).
3 > Smart Dump Status information is transmitted when polled, as
in the previousmode. However,the transmission also occurs
automatically whenever UPS statuschanges.Forexample,if
there is a power outage, UPS status informationchanges and is
therefore, automatically transmitted.
A > ASCII Terminal TheUPSdisplaystheformatteddataonthe
attached video terminal.
B > VT100 Terminal TheUPSdisplaystheformatteddataonthe
attached video terminal.
P > Printer Dump The UPS prints the formatte d data on the
attached printer.
L > LAN Configuration allows you to configure the UPS for a new
LAN mode and displays the Select LAN Configuration Menu.
Select the AS400 option if you are using OnliSafe software to
monitor the UPS.
The
Custom Configuration option has two screens: the first screen
has options available for inverter shutdown, and the second
screenhas options available for the contact configuration.
Consult your shutdown software documentation for details on
the required signal states for configuring LAN communications.
Z > Set Baud Rate allowsyouto select a new baud rate.The Select
Baud Rate Menu displays a list of baud rate options.
6(/(&7%$8'5$7(
!4
(17(56(/(&7,21!!
!
!
!
!
!
48,77+,60(18
!
5. To save the configuration settings, type S at the MainMenu
prompt.TheUPSoperates and communicatesunderthe new
configuration,and defaultsto these settings each time it is
started.
If you want to abandon the selections youhave made, type
quit.
Q to
NOTE Anychangesyoumake to the UPScommunications configurationmust
correspondtothecommunications equipment youare using.Inparticular,newbaud
rate selectionsfortheUPS must match your communicationsequipment.
Power Management Software
Powermanagement softwareallowsyouto monitorUPS operations
automatically. To use OnliNetor LanSafe software,theUPS must be
configured for any one of the Data Dump, Terminal, or Printer modes;
however ,Printer mode is preferred.
OnliNet provides multiple levels of UPS monitoring and control, as well
as automatic shutdownformany different operatingsystems. If you
have any questions or would like further information, see Chapter 8,
“Serviceand Support” on page 75 for the numberto call in your
location.
In addition to configuring the UPS for specific communication options,
you must also ensure proper use of the serial port when connecting the
UPS to your network or monitoring equipment.
NOTE Semiconductorswitch contactsarerated at a maximumcurrent of 50mAanda
maximum of 40 Vdc.
Use only the pins specified for your communications configuration. The
use of any additional pins for any of the followinginterfaces can cause
interference with system communications.
Eventhough yournetworkusesthe specified signallines,thepins
assigned to these signals at the network end of the cable may vary with
those of the UPS serial port. The c onnector body and style may vary as
well.
NOTE Standard,pin-for-pin cablesmaynotworkcorrectly.Consultyournetwork
softwareorservermanualsfor system shutdown pin assignments.
62
The UPS serial port complies with EIA RS-232 standards.RS-232
specifiesa maximum cable length of 50 ft (15m). See Figure 22 for the
locationof the serial port.
The following chart definesthe UPS serial port contacts. Serial
communicationis not available with 3Com a nd AS/400 network
configurations.Use only the applicable pins for the selected
communication mode; otherwise, interference problemsmay occur.
CommunicationMode FunctionSignal Name PinNo.True Condition
Serial
Novell
(Default)
Novell
(Custom)
3Com
(Default)
AS/400
NOTE
Pin numbers separatedbyaforwardslash( / ) are connected togetherinternally.
Data toUPSRS232 TxD2N/A
Data from UPSRS232RxD3N/A
Signal Ground7
Battery OnON.AC14/16Open
Low Battery
Signal Ground7/15/25
Battery OnON.AC14/16Closed
Low Battery
Signal Ground7/15/25
Shutdown (Remote) SHUT.DOWN2Positive Voltage
Low Battery
Battery OnPWR.FAIL10Positive Voltage
Signal Ground7
UPS AvailableUPS Available 11/13Closed
Battery OnUtility Failure14/16Closed
BypassUPS Offline17/19Closed
Low BatteryLowBattery23/24Closed
Signal Ground12/15/18/25
ParameterPPUBatteryCabinetPPDM
Height283mm(11.13”)142.5 mm (5.61”)283mm(11.13”)
Width252mm (9.91”)252 mm (9.91”)252 mm (9.91”)
Depth406mm (16”)400 mm (15.75”)406 mm (16”)
Weight18 kg(39lb)23.6 kg(52lb)37 kg(82lb)
Electrical Specifications for the Prestige 6000 with PPDM
Use the following tables to determine load wiring requirements when
the PPDM is used with the UPS. The distribution of your load on the
available outputsof the PPDMmayaffect the maximum load obtainable.
Prestige 6000PPDM Ratings with a Model 6000 UPS
PPDMModelInput UtilityVoltage
and SelectedUPS
OutputVoltage
208:120/208
L6-30R/IEC 320-C19 PPDM
208:120/208
L6-30R/5-15R PPDM
240:240
IEC 309 PPDM
240:120/240
L6-30R/5-15R PPDM
*
Ratings based on4000WloadonPPDM,plussufficientlinearinductiveloadto achieve the current rating oftheinput
All models include power processing unit, PowerPass Distribution Module (208V or 240V) input line cord, AS/400
communications cable, operator’s manual, and two battery packs.
ModelIBM Part
Number
VAWattsVoltsFrequencyDescription
50-60Prestige 6000
dependent
Model 6000
Standard Accessories
IBMPartNumberIBM Type/ModelDescription
N/A9910-6603Prestige6000 Full Battery Pack (Qty. 2)
17G17969910-6558Prestige 6000 PowerPass Distribution Module
(120/240 IEC 309)
17G17959910-6557Prestige 6000 PowerPass Distribution Module
(120/208 L630R/IEC 320-C19)
21H84419910-6555Prestige 6000 PowerPass Distribution Module
(120/208 L6-30R/5-15R)
21H84429910-6556Prestige 6000 PowerPass Distribution Module
The Prestige UPS is designed for durable, automaticoperationand also
alertsyouwheneverpotential operating problemsmayoccur. Use the
following troubleshooting chart to determine the UPS alarm condition.
IndicatorLegend
Unlit
Amber
Green
Flashing
ConditionPossible CauseAction
UPS does not turn on.
Load doesnotturn on.UPS has not been activated.
UPS beeps occasionally.Normal operation.None. UPS is protectingyour
UPS is not correctly connected to
the power source.
UPS input breaker is off.Reduce load, then reset breaker.
Check connections to the power source.
PresstheOutput
second, then release.
equipment.
|
On button for one
indicator remains
lit, even though line
voltage is present.
Utility line is out of specification.Test wall socket, repair as required.
UPS input breaker is tripped.
Battery circuit breakers are in the
OFF (O) position.
Low battery capacity.Allow battery to charge for 24 hours,
Protected equipment power
requirements exceed UPS capacity.
Incorrect communications cabling.Verify cable integrity (see page 62).
Incorrect baud rate.
Incorrect communication mode.Select a new communication mode (see
Reduce load, then reset breaker.
Switch the battery circuit breaker to the
ON (
|
) position for all connected
battery cabinets.
then retest.
Reduce load, then retest.
Select a new baud rate (see page 61).
Chapter 5).
71
Troubleshooting
g
RemoteEmergency
Power-Off switch does not
shut down the UPS.
PowerPass Distribution
Module does not deliver
expected voltage.
OVERLOAD
SITE FAULT
OVERTEMP
BATTERY
SELF TEST
ActionPossible CauseCondition
REPO switch is not wired properly.Check connections and contact your
service representative.
Voltage Selector switch on the
power processing unit is not set
properly.
Circuit protectorsorinput
breakers on the PPDM are tripped
or off.
Power requirements exceed UPS
capacity . If overload is greater than
Shut down the UPS (see page 49). Select
proper voltage position (see page 37)
and restart the UPS (see page 39).
Check the load for a fault condition,
then reset circuit protectors or input
breaker.
Your UPS continues to operate.
Reduce load.
105%, the alarm beeps every
second and the UPS may switch to
Bypass mode.
OVERLOAD
OVERTEMP
BATTERY
The UPS switched to Bypass mode
because the overload increased
(above 105%). The alarm beeps.
Reduce load.
If the Overload indicator remains lit,
reset the UPS by pressing the
Output
|
On button until the alarm
beeps.
You may need to obtain a larger capacity
UPS.
The utility line voltage and
frequency are out of specification.
The inverter remains online, deriving
power from the utility until it is no
longer acceptable.
Checkthe unit configuration.
Refer to the product specifications (see
page 65).
UPS internal temperature is too
high. The alarmbeeps and the UPS
switches to Bypass mode for
approximately 10 minutes,
allowing the UPS to cool down.
Weak battery while in Normal
mode. The alarm beeps.
Shut down the UPS. Clear vents.
Remove any heat sources. Wait
approximately 5 minutes and retry.
Contact your service representative if
condition persists.
Allow the batteryto chargefor 24 hours,
then retest. Have batteries replaced if
condition persists.
Battery breaker open (O).Verify that the battery cabinet breaker is
Battery cabinet is not properly
connected to the UPS.
This usually indicates that the batteries
need replacing or the UPS requires
service. Contact your service
representative.
SELF TEST
NORMAL
REPLACE
Resetting the UPS
To reset the UPSwhilean alarm condition is present,pressthe
Output On buttonuntiltheUPS alarm beeps.
Silencing the Alarm
To silence the alarm for an existing fault, press and hold the
Output On buttonfor one second. The alarm becomes quiet.
If UPS status changes, the alarm beeps, overriding previousalarm
silencing. Press the Output
Self Test failure. UPS internal
problem.
Weak battery.Verify that the battery is connected and
The UPS may switch to Bypass mode,
depending on the circumstances.
Reset the UPS by pressing the
Output
|
On button until the alarm
beeps.
Contact your service representative if
condition persists.
the battery circuit breaker is in the
ON (
|
) position. If battery is properly
connected, allow the battery to charge
for 24 hours. Retest. Have batteries
replaced if condition persists.
The following sections describe the methods for obtaining service for
your UPS and warranty information.
Warranty
The warrantyserviceon Powerware Corporation UPSsis element
exchange.Ifthe UPS becomes inoperative, the modulethat is
inoperative willbe replaced. For the 6 kVA UPSs,thiswouldeitherbe
the I/O, battery, or PowerPassDistributionModule.The process for
obtaining a replacementmodulevariesby country. Under NO
CONDITIONSare IBM Customer Engineers authorized to remove the
covers.
The warrantyon the replacementunit,should yourequire one,is for the
remaining period of warranty of the original unit. See page 84 for a
detailed description of the warranty.
Installation Instructions
Installation instructions are in pictorial form on the Quick Install pages
in the front of this manual and also in written form beginning on
page 31. Safety instructions are providedin multiplelanguages and
beginon page 7. Publications may be orderedfromtheIBM
Mechanicsburg Distribution Center.
Connected Equipment Insurance
Withthisprogram,Powerware Corporation provides a $25,000
Powerware Protection Guarantee.See page 85 for specifictermsand
conditions of the Powerware Protection Guarantee.
If, in PowerwareCorporation’s opinion, the unit fails to meet published
specifications and the defect iswithinthetermsof the limitedwarranty
(attached),thedefectivepart(s)willbe repairedor replaced at the
optionof Seller with no charge for replacement parts. The battery is
warranted to haveat least 70% of originalfullload capacity at the end of
fiveyears fromdate of installation or 66 monthsafter manufacture,
whichever comes first. The warranty is invalid if the battery is subject to
misuse, abuse, or physical damage.
Obtaining Service
The troubleshootingchart on page 71 covers most of the difficulties you
may encounter during normal operations.
For further assistance with IBM 9910 UPSs, se e the following section
that applies to you.Forcriticalapplications, expedited replacement may
be available.
Pleasehave the followinginformation ready when you call forservice:
::::::
Warranty
ModelPartNumberCoverageArea5 Year3Year
EP821H1572
AP, Canada, LA, USX
EMEAX
Model number
Serial number
Version number (if available)
Date of failure or problem
Symptoms of failure or problem
Customer return addressand contact information
3. The FSS will confirm that the unit is listed in the customer
profileand notify Powerware.
4. Powerware will promptlycallthe customer and ask for the
serialnumber.Powerware willalso attempt to determinethe
nature of the problem. The problemmay be relatedto improper
operationas opposed to a defect.
5. If the unitrequires replacement,Powerware willsenda
replacement unit.
6. The customer is expected to installthe replacementunit. To
returnthe defective unit see the instructions on the bottom of
the ReturnMaterialAuthorization (RMA).The packaging
materialusedfor the replacementunitcan be used for this
purpose.
Shipping
Powerware will pay all shipping costs incurred (both to and from the
customersiteor IBM Designated Location)to replace the defective UPS
system.
1. Customercallsthe local IBM office servicingaccount.
2. The IBM CE responds, determines the problem,and resolves
the problem.
Customer Process for Service
1. Customercallsthe local IBM office servicingaccount.
2. The IBM CE responds, determines the problem,and resolves
the problem.
EMEA
Customer Process for Service
1. Customercallsthe local IBM office servicingaccount.
2. The IBM CE responds, determines the problem,and resolves
the problem.
S/390 9910 UPS Service and Support
The following sectionsdescribeinstallation, service,and supportfor the
UPS and warranty information.
Installation
Installationof the UPS is provided by the IBM S/390 Customer Engineer.
The processis the same for IBM North America, IBM Asia Pacific,IBM
Europe/Middle East/Africaand IBM Latin America.
Service and Support
Warranty
The warrantyserviceon Powerware Corporation UPSsis element
exchange.Ifthe UPS becomes inoperative, the modulethat is
inoperative willbe replaced. For 6 kVA UPSs,thiswouldeitherbe the
battery, the PowerPass Distribution Module, the Power Processing Unit,
the TransformerModule, or interconnectioncable between the UPSand
the optionalbattery cabinets.UnderNO CONDITIONS areIBM
Customer Engineers authorized to remove the covers from any of the
UPSmodules.TheUPSsfor thisprogram are warranted by Powerware
Corporation for up to five(5) years. Warranty time may varyfrom
country to country as per local regulations. W arranty time starts when
the UPS is delivered to the customer, not to exceed 66 monthsfromdate
of manufacture.
Connected Equipment Insurance
Withthisprogram,Powerware Corporation provides a $25,000
Powerware Protection Guarantee.See page 85 for specifictermsand
conditions of the Powerware Protection Guarantee.
The UPS, when installedwitha S/390 processor,willusually be placed
in a raisedfloordata center. A cable access will need to be cut in the
raisedfloortileto allow for connection to customer power and the S/390
equipment. The following figures represent approximate dimensions of
cable access cuts for3 standard raised floor tile sizes.
177 mm
177 mm
(7in
l
465 mm Tile
18.25 in
l
7in)
75 mm
(3in)
610 mm
24 in
177 mm
177 mm
(7in
l
or 600 mm
23.6 in
l
7in)
127 mm
(5in)
Tile
The UPS can be positioned on the rightside of the S/390 since S/390
growth adds frames to the left. A recommendeddistance between the
UPS is one floor tile.
See Chapter 3, “Installation” on page 31.
There are some parts for the S/390applicationwhich are not addressed
in Chapter 3, “Installation” on page 31. When installing a 9910 for a
S/390, the castor plate should be positioned a nd the 9910 modules
stacked in the following order; PowerPass Distribution Module on the
castor plate , Power Processing Unit on the PowerPass Distribution
Module, battery cabinetson the Power Processing Unit.
Service and Support
T opCover
Battery Cabinet
Battery Cabinet
Power Processing
Unit
PowerPass
Distribution
Module
Castor Plate
Battery Warranty
The warranty period is five years from the date of installation or 66
months from the date of manufacture, whichever occurs first. If, in
Powerware Corporation’s opinion, the unit fails to meet published
specifications and the defect iswithinthetermsof the limitedwarranty
(attached),thedefectivepart(s)willbe repairedor replaced at the
optionof Seller with no charge for replacement parts. The battery is
warranted to haveat least 70% of originalfullload capacity at the end of
fiveyears fromdate of installation or 66 monthsafter manufacture,
whichever comes first. The warranty is invalid if the battery is subject to
misuse, abuse, or physical damage.
Warrantytime may varyfromcountry to countryas per local
regulations. Warranty time starts when the battery is delivered to the
customer,not to exceed 66 monthsfrom date of manufacture.
There are many configurations of UPS and S/390 models and options.
The following are basic examples of the PowerwareCorporation UPSs
and IBM S/390 processors.
The type and part number of the line cord, sense and power cable will
varydependinguponcustomerpowerconnection, S/390model,and
features. See “Part Numbers” on page 83 fordetail.
9910
E80,
E81
Line Cord
One 9910 with optional battery cabinetsand one S/390
Applies only to electronics (unit) installed in the 50 UnitedStates of America, Canada, LatinAmerica, and Asia Pacific:
Powerware Corporation warrants the unit against defects in material and workmanship for a period of five years from the
date of startup or sixty-six (66)months from the date of completion of manufacture, whichever period expires first.
If, in Powerware Corporation’s opinion, the unit failstomeet published specifications and the defect is within the terms of
thislimited warranty, the defective part(s) will be repaired or replaced at theoption of Seller withno charge for
replacement parts. There willbe no charge for replacement equipmentinstallation ordefective part repair inconnection
withdefectscovered by this Limited Warranty. Equipment sold, butnot manufactured, by Seller (e.g. batteries,battery
racks), shall be warranted only by the manufacturer of such equipment, Prestige 6000 Powerware Corporation’s line up
and matchbatteries are warranted for 5 years from start-up or 66 months from manufacture subject to the terms attached
hereto. Equipment repaired or replaced pursuant to this Limited Warrantywill be warranted for theunexpired portionof
the original warranty subject to all the terms thereof.
This warranty does not apply toanyunit that hasbeensubject to neglect,accident, abuse, misuse, misapplication,
incorrect connection, or that has been subject to repair oralteration notauthorized in writing by Powerware Corporation
personnel. THIS WARRAN TYIS THE PURCHASER’S (USER’S) SOLE REMEDY AND IS EXPRESSLYIN LIEU OF ANY
OTHER WARRANTY, AND THERE ARE NO OTHER EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES
INCLUDING ANY IMPLIED W ARRANTY OF MERCHANTABILITY OF FITNESS FOR PURPOSE. Powerware
Corporation’s liability on any claim of any kind relating to the unit, batteries or otherwise for any loss or damage arising
out oforin connectionwith or resulting from thisAgreement or from the performance orbreach thereofshall in no case
exceed the priceallocable to the goodsorservices or unitthereof which givesrise to the claim.
Seller’sobligations underthis Limited Warranty are conditioned upon receipt by Seller of all paymentsdue(including
interest charges, if any).During such timeasSeller has not receivedpayment of any amount duetoSeller in accordance
with the Contract terms under which the equipment is sold, Seller shall have no obligation under said warranty; also
during this time the period of said warranty shall continue to run and the expiration of said warranty shall not be
extended upon payment of the overdue amount. These limitations to said warranty apply even in the event that the
equipmentis sold by Seller for resale to an ultimateuser.
In no eventshall Seller be liableforany indirect, incidental, special, or consequential damages. Seller shallnot be
responsible for failure to provide service orparts due to causes beyond Seller’s reasonable control.
Any advice furnished the Purchaser (user) beforeorafter delivery in regard to use or application of Powerware
Corporation equipment,isfurnished without charge and on the basis that it represents Powerware Corporation’s best
judgmentunder the circumstances. The use of any verbaladvice by the Purchaser (user) is solely and entirely at its own
risk.
Preventive Maintenance (PM) is not required on the product to maintain the warranty.
This limited warranty applicable only to products purchased from the IBM Corporation.
Attached Equipment Protection Program Terms and Conditions
Program Summary: Powerware Corporation guarantees to repair or replace (at the option of Powerware Corporation)
any equipment that is damaged by AC powerdisturbances when saidequipment is properly connected to a Powerware
Corporation uninterruptible power supply (UPS) covered by the Powerware Protection Guarantee. This program provides
for reimbursement of repair or replacement expenses up to $25,000.00 and applies only to component or physical system
damage.
Products Covered: The Powerware Protection Guarantee applies to all Powerware Corporation Prestige 6000 UPS
systems that are covered under the original IBM AS/400 Powercare Limited warranty during the manufacturer’s warranty
period.
Applicability: The Powerware ProtectionGuarantee applies onlyto units installed in the UnitedStates of America, Latin
America, Canada,Asia Pacific and were sold by IBMCorporation withAS/400 systems. Further, thisPowerware
Protection Guarantee applies only to end-users of the UPS product(s) who have returned the warranty registration card
within30 -days after productdelivery. This program does notapply to damage resulting from any cause otherthan AC
power disturbances and is independentof the PowerwareCorporation manufacturer’s warranty or service contract. The
Powerware ProtectionGuarantee applies to the following AC power disturbances as defined by the American National
Standards Institute(ANSI): power line transients; electrical spikes;electrical surges; brownout; blackout. UPS products
must be properly maintainedaccording to themanufacturers’recommendationssetforth in the operator’s manual and the
UPS installation mustadhere to electricalsafety requirements set forthbythe National Electrical Code (NEC) or
applicable local code(s). The UPSmustbe properly c onnected to a properly installed e lectrical outlet or otherconnection
per the NEC or applicable localcode (s). The equipmentcovered by this guarantee mustbe connec ted directly to the
outputof the PowerwareCorporation UPSproduct withnointerveningelectrical devices. The Powerware Protection
Guarantee is null and void if the UPS product has been: misapplied; improperly maintained; mishandled; abused;
improperly installed; altered in any way subjectedtoaccident or misuse; used inother than normaloperating conditions
described inthe UPS productspecifications. The Powerware Protection Guarantee is independent of all otherwarranties
and there are no other warranties expressed or implied, including warranties of merchantability and fitness for a particular
purpose. IN NO EVENT SHALL POWERWARE CORPORATION BE LIABLE FOR ANY DIRECT, INDIRECT , SPECIAL,
INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF ITS’ PRODUCTS, EVEN IF ADVISED
OF THE POSSIBILITY OF SUCH DAMAGE. Direct, indirect, special, incidentalorconsequentialdamagesinclude, but are
not limited to, lost profits or revenue, loss of equipment, loss of use of equipment, software loss, loss of data in whole or
in part, recovery of data in whole or in part, restoration of data in whole or in part, corruption of data in whole or in part,
cost of substitutes or rental equipment, claims by third parties or otherwise.