PowerWalker VI TW Series, VI TW 2K, VI TW 1.1K, VI TW 3K, VI TW 1.5K User Manual

Page 1
User Manual
PowerWalker VI TW Series
Uninterruptible Power Supply System
Version: 1.0
Page 2
Table of Contents
1-1. Transportation .......................................................................................................... 1
1-2. Preparation ............................................................................................................... 1
1-3. Installation ............................................................................................................... 1
1-4. Operation ................................................................................................................. 1
1-5. Maintenance, service and faults ................................................................................. 2
2-1. Rear panel view ........................................................................................................ 4
2-2. Operating principle ................................................................................................... 5
2-3. Setup the UPS .......................................................................................................... 5
3-1. Button operation ....................................................................................................... 7
3-2. LCD Panel................................................................................................................. 7
3-3. Audible Alarm ........................................................................................................... 8
3-4. LCD display wordings index ....................................................................................... 9
3-5. UPS Setting .............................................................................................................. 9
3-6. Operating Mode Description ..................................................................................... 12
3-7. Faults Reference Code ............................................................................................. 12
3-8. Warning indicator ................................................................................................... 13
Page 3
1
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully
1-1. Transportation
Please transport the UPS system only in the original package to protect against shock
and impact.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments. Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS system to
the UPS output sockets.
Place cables in such a way that no one can step on or trip over them. Do not connect domestic appliances such as hair dryers to UPS output sockets. The UPS can be operated by any individuals with no previous experience. Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked (or UL-marked for 110/115/120/127 VAC
models) mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked (or UL-marked for 110/115/120/127 VAC
models) power cables to connect the loads to the UPS system.
When installing the equipment, it should ensure that the sum of the leakage current
of the UPS and the connected devices does not exceed 3.5mA.
Temperature Rating - Units are considered acceptable for use in a maximum
ambient of 40°C (104°F).
For Pluggable Equipment - The socket-outlet shall be installed near the equipment
and shall be easily accessible.
1-4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
Page 4
2
1-5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
Caution - Do not dispose of batteries in a fire. The batteries may explode. Caution - Do not open or mutilate batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
a) Batteries may cause electric shock and have a high short-circuit current. Please
take the precautionary measures specified below and any other measures necessary when working with batteries: Remove watches, rings, or other metal objects.
b) Use tools with insulated handles. c) Wear rubber gloves and boots. d) Do not lay tools or metal parts on top of batteries. e) Disconnect charging source and load prior to installing or maintaining the
battery.
f) Remove battery grounds during installation and maintenance to reduce
likelihood of shock. Remove the connection from ground if any part of the battery is determined to be grounded.
When changing batteries, install the same number and same type of batteries.
Manufacture
Type
Rated
Toplite (Guangzhou) Technology Battery Co Ltd (MH29104)
NPW45-12
12 V dc, 9.0 Ah
UXW460-12
12 V dc, 9.0 Ah
NPW36-12
12 V dc, 7.2 Ah
UXW360-12
12 V dc, 7.2 Ah
NPW45-12 FR
12 V dc, 7.0 Ah
UXW460-12/FR
12 V dc, 7.0 Ah
NPW36-12 FR
12 V dc, 7.0 Ah
CSB Battery Co Ltd (MH14533)
UXW360-12/FR
12 V dc, 7.0 Ah
GP1272
12 V dc, 7.2 Ah
UPS 12460 F2
12 V dc, 9.0 Ah
UPS 12360 6
12 V dc, 6.5 Ah
UPS 12360 7
12 V dc, 6.5 Ah
HR 1234W
12 V dc, 8.5 Ah
HR 1234W FR
12 V dc, 8.5 Ah
Yuasa Battery (Guangdong) Co Ltd (MH29616)
NPW45-12
12 V dc, 8.0 Ah
NPW45-12FR
12 dc, 8.0 Ah
Page 5
3
For UPS with internally mounted battery
a) Instructions shall carry sufficient information to enable the replacement of the
battery with a suitable manufacturer and catalogue number.
b) Safety instructions to allow access by Service Personnel shall be stated in the
installation/service handbook.
c) If batteries are to be installed by Service Personnel, instructions for
interconnections, including terminal torque, shall be provided.
Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system. WARNING: This is a category C2 UPS product. In a residential environment, this
product may cause radio interference, in which case the user many be required to take additional measures. (only for 220/230/240 VAC system)
Only for 110/115/120/127 VAC system:
NOTE: This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
WARNING: Changes or modifications not expressly approved by the party responsible
for compliance could void the user's authority to operate the equipment.
Page 6
4
2. Installation And Setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use.
2-1. Rear panel view IEC Type
1.1K/1.5K 2K/3K
NEMA Type
1.1K/1.5K 2K
1. Programmable outlets: connect to non-critical loads.
2. Output receptacles: connect to mission-critical loads.
3. AC input
4. Emergency power off function connector (EPO)
5. USB communication port
6. RS-232 communication port
7. SNMP intelligent slot
8. External battery connector Output terminal
Page 7
5
2-2. Operating principle
The operating principle of the UPS is shown as below.
EMI/RFI Filters
Battery Charger
Battery
DC-to-DC
Converter
Inverter
AVR
TX
Output
The UPS is composed of mains input, EMI/RFI filters, inverter, battery charger, DC-to-DC converter, battery, AVR TX and UPS output
2-3. Setup the UPS
Before installing the UPS, please read below to select proper location to install UPS.
1. UPS should be placed on the flat and clean surface. Place it in an area away from vibration,
dust, humidity, high temperature, flammable liquids, gases, corrosive and conductive contaminants. Install the UPS indoors in a clean environment, where it is away from window and door. Maintain minimum clearance of 100mm in the bottom of the UPS to avoid dust and high temperature.
2. Maintain an ambient temperature range of 0ºC to 45ºC for UPS optimal operation. For every
5ºC above 45ºC, the UPS will derate 12% of nominal capacity at full load. The highest working temperature requirement for UPS operation is 50ºC.
3. It’s required to maintain maximum altitude of 1000m to keep UPS normal operation at full
load UPS. If it’s used in high altitude area, please reduce connected load. Altitude derating
power with connected loads for UPS normal operation is listed as below:
4. Place UPS:
It’s equipped with fan for cooling. Therefore, place the UPS in a well-ventilated area. It’s required to maintain minimum clearance of 100mm in the front of the UPS and 300mm in the back and two sides of the UPS for heat dissipation and easy-maintenance.
Page 8
6
Step 1: UPS input connection Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
Step 2: UPS output connection
There two kinds of outputs: programmable outlets and general outlets. Please connect non­critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting shorter backup time for non-critical devices.
Step 3: Communication connection Communication port:
USB port
RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options. Step 4: Disable and enable EPO function
This UPS is equipped with EPO function. By default, the UPS is delivered from factory with Pin 1 and pin 2 closed (a metal plate is connected to Pin 1 and Pin2) for UPS normal operation. To activate EPO function, remove two screws on EPO port and green connector will be removed. Note: The EPO function logic can be set up via LCD setting. Please refer to program 8 in UPS setting for the details.
Step 5: Turn on the UPS Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.
Step 6: Install software For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. Use supplied RS-232 or USB communication cable to connect RS-232/USB port of UPS and RS-232/USB port of PC. Then, follow below steps to install monitoring software.
1.
Insert the included installation CD into CD-ROM drive and then follow the on-screen instructions to proceed software installation. If there no screen shows 1 minute after inserting the CD, please execute setup.exe file for initiating software installation.
2.
Follow the on-screen instructions to install the software.
3.
When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.
It’s in closed status for UPS normal operation as default.
To activate EPO function, remove these two screws.
Page 9
7
3. Operations
3-1. Button operation
Button
Function
ON/MUTE Button
Turn on the UPS: Press and hold ON/Mute button for at least 2
seconds to turn on the UPS.
Mute the alarm: After the UPS is turned on in battery mode, press
and hold this button for at least 3 seconds to disable or enable the
alarm system. But it’s not applied to the situations when warnings or
errors occur.
Up key: Press this button to display previous selection in UPS setting
mode.
Switch to UPS self-test mode: Press and hold ON/Mute button for 3
seconds to enter UPS self-testing while in AC mode
OFF/ENTER
Button
Turn off the UPS: Press and hold this button at least 2 seconds to
turn off the UPS
Confirm selection key: Press this button to confirm selection in UPS
setting mode.
SELECT Button
Switch LCD message: Press this button to change the LCD message
for input voltage, input frequency, battery voltage, battery capacity, ambient temperature, output voltage, output frequency, load current and load percentage.
Setting mode: Press and hold this button for 3 seconds to enter UPS
setting mode when UPS is off.
Down key: Press this button to display next selection in UPS setting
mode.
ON/Mute + Select Button
Exit setting mode or return to the upper menu: When working in
setting mode, press ON/Mute and Select buttons simultaneously for
0.2 seconds to return to the upper menu. If it’s already in top menu,
press these two buttons at the same time to exit the setting mode.
3-2. LCD Panel
Display
Function
Backup time information
Indicates the estimated backup time.
H: hours, M: minute, S: second.
Page 10
8
Configuration and fault information
Indicates the configuration items, and the configuration items are listed in details in section 3-5.
Indicates the warning and fault codes, and the codes are listed in details in section 3-7 and 3-8.
Mute operation
Indicates that the UPS alarm is disabled. Input, Battery, Temperature, Output & Load information
Indicate the input voltage, input frequency, battery voltage, battery capacity, ambient temperature, output voltage, output frequency, load current and load percentage.
k: kilo, W: watt, V: voltage, A: ampere, %: percent, : centigrade degree, Hz: frequency
Load information
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
Indicates overload. Programmable outlets information
Indicates that programmable management outlets are working.
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates charging status
Indicates the ECO mode is enabled.
Indicates the UPS is working in boost mode
Indicates the UPS is working in buck mode
Indicates the AC to DC circuit is working.
Indicates the inverter circuit is working.
Indicates the output is working.
Battery information
Indicates the battery level by 0-24%, 25-49%, 50-74%, and 75-100%.
Indicates low battery.
3-3. Audible Alarm
Battery Mode
Sounding every 10 seconds
Low Battery
Sounding every 2 seconds
Overload
Sounding every second
Fault
Continuously sounding
Page 11
9
3-4. LCD display wordings index
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
AO Active Open
AC Active Close
OK OK
ON ON
BL Battery Low
OL Over Load
NC No Connect
OC Over Charge
SF Site wiring fault
EP EPO
TP Temperature
CH Charger
BF Battery Fault
BR Battery Replace
EE EEPROM error
3-5. UPS Setting
Parameter 1
Parameter 2
There are two parameters to set up the UPS. Parameter 1: It’s for program alternatives. Refer to below table. Parameter 2 is the setting options or values for each program.
01: Output voltage setting
Interface
Setting
Parameter 2: Output voltage
For 208/220/230/240 VAC models, you may choose the following output voltage:
208: presents output voltage is 208Vac 220: presents output voltage is 220Vac 230: presents output voltage is 230Vac (Default) 240: presents output voltage is 240Vac
For 110/115/120/127 VAC models, you may choose the following output voltage: 110: presents output voltage is 110Vac
Page 12
10
115: presents output voltage is 115Vac 120: presents output voltage is 120Vac (Default) 127: presents output voltage is 127Vac
02: Programmable outlets enable/disable
Interface
Setting
Parameter 2: Enable or disable programmable outlets. ENA: Programmable outlets enable DIS: Programmable outlets disable (Default)
03: Programmable outlets setting
Interface
Setting
Parameter 2: Set up backup time limits for
programmable outlets. 0-999: setting the backup time limits in minutes from 0­999 for programmable outlets which connect to non­critical devices on battery mode. (Default: 999)
04: Maximum charger current setting
Interface
Setting
Parameter 2: Set up the charger maximum current. 1/2/4/6/8: setting the maximum charger current at 1/2/4/6/8 Ampere. (Default: 8A) Note: This setting is only effective for super charger.
06: Autonomy limitation setting
Interface
Setting
Parameter 2: Set up backup time on battery mode for
general outlets. 0-999: setting the backup time in minutes from 0-999 for general outlets on battery mode. DIS: Disable the autonomy limitation and the backup time will depend on battery capacity. (Default) Note: When setting as “0”, the backup time will be only 10 seconds.
07: Battery total AH setting
Interface
Setting
Parameter 2: Set up the battery total AH of the UPS. 7-999: setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external battery bank is connected.
Page 13
11
08: EPO logic setting
Interface
Setting
Parameter 2: Set up the EPO function control logic. AO: Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in open status. AC: Active Close. When AC is selected as EPO logic, it will activate EPO function with Pin 1 and Pin 2 in close status.
00: Exit setting
Interface
Setting
Exit the setting mode.
Steps for setting programmable outlet
Step 1:
Before entering setting mode, the UPS should be in Stand-by mode (off-charging) and make sure the battery is connected. The LCD display is shown as right.
Step 2:
Press and hold the “Selection” button for 3 seconds to enter
Setting mode.
Step 3:
Press the “Up“ button (ON/MUTE) to switch to "02" of program list. Then press “Enter“ button to enter value setting of parameter
2. Press the “Up” button to change the value to “ENA” to enable the programmable outlet function. Then press “Enter” button
again to confirm the setting.
Step 4:
Press the “Up“ button (ON/MUTE) again to switch to "03" of program list. Then press “Enter“ button for setting programmable outlet time. Push “Up” button to change the value of backup time
according your demand. Then press “Enter” to confirm the setting.
Step 5:
Press “Up“ button (ON/MUTE) to switch to "00" of program list. Then press “Enter” button to exit setting menu.
Step 6:
Disconnect AC input and wait until the LCD display is off. The new setting will be activated when turning on the UPS again.
Page 14
12
3-6. Operating Mode Description
Operating mode
Description
LCD display
ECO mode
When the input voltage is within voltage regulated range, UPS will power the output directly from the mains. ECO is an abbreviation of Efficiency Corrective Optimizer. In this mode, when battery is fully charged, the fan will stop working for energy saving.
Buck mode when AC is normal.
When the input voltage is higher than the voltage regulation range but lower than high loss point, the buck AVR will be activated.
Boost mode when AC is normal.
When the input voltage is lower than the voltage regulation range but higher than low loss point, the boost AVR will be activated.
Battery mode
When the input voltage is beyond the acceptable range or power failure, UPS will backup power from battery and alarm is sounding every 10 seconds.
Standby mode
UPS is powered off and no output supply power, but still can charge batteries.
Fault mode
When a fault occurs, the ERROR icon and the fault code will be displayed.
3-7. Faults Reference Code
Fault event
Fault code
Icon
Fault event
Fault code
Icon
Bus start fail
01
x
Inverter output short
14
x
Bus over
02
x
Battery voltage too high
27
x
Bus under
03
x
Battery voltage too low
28
x
Inverter soft start fail
11
x
Over temperature
41
x
Inverter voltage high
12
x
Over load
43
Inverter voltage Low
13
x
Charger failure
45
x
Page 15
13
3-8. Warning indicator
Warning
Icon (flashing)
Code
Alarm
Low Battery
Sounding every 2 seconds
Overload
Sounding every second
Battery is not connected
Sounding every 2 seconds
Over Charge
Sounding every 2 seconds
Site wiring fault
Sounding every 2 seconds EPO enable
Sounding every 2 seconds
Over temperature
Sounding every 2 seconds
Charger failure
Sounding every 2 seconds
Battery fault
Sounding every 2 seconds (At this time, UPS is off to remind users something wrong with battery)
Battery replacement
Sounding every 2 seconds
EEPROM error
Sounding every 2 seconds
NOTE: “Site Wiring Fault” function can be enabled/disabled via software. Please check
software manual for the details.
Page 16
14
4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom
Possible cause
Remedy
No indication and alarm even though the mains is normal.
The AC input power is not connected well.
Check if input power cord firmly connected to the mains.
The AC input is connected to the UPS output.
Plug AC input power cord to AC input correctly.
The icon and the warning
EPO function is activated.
Set the circuit in closed
code flashing on LCD display and alarm is sounding every 2
position to disable EPO function.
seconds.
The icon , and the warning code flashing on
LCD display and alarm is sounding every 2 seconds.
Line and neutral conductors of UPS input are reversed.
Rotate mains power socket by 180° and then connect to UPS system.
The icon , and the warning code flashing on
LCD display and alarm is sounding every 2 seconds.
The external or internal battery is incorrectly connected.
Check if all batteries are connected well.
Fault code is shown as 27 on LCD display and alarm is continuously sounding.
Battery voltage is too high or the charger is fault.
Contact your dealer.
Fault code is shown as 28 on LCD display and alarm is continuously sounding.
Battery voltage is too low or the charger is fault.
Contact your dealer.
The icon , and the warning code flashing on
LCD display and alarm is sounding every second.
UPS is overload
Remove excess loads from UPS output.
UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass.
Remove excess loads from UPS output.
After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains.
Remove excess loads from UPS output first. Then shut down the UPS and restart it.
Fault code is shown as 43 and the icon is lighting on LCD display. Alarm is continuously sounding.
The UPS shut down automatically because of overload at the UPS output.
Remove excess loads from UPS output and restart it.
Page 17
15
Symptom
Possible cause
Remedy
Fault code is shown as 14 on LCD display and alarm is continuously sounding.
The UPS shut down automatically because short circuit occurs on the UPS output.
Check output wiring and if connected devices are in short circuit status.
Fault code is shown as 01, 02, 03,
A UPS internal fault has
Contact your dealer
11, 12, 13 and 41 on LCD display
occurred. There are two
and alarm is continuously
possible results:
sounding.
1. The load is still supplied,
but directly from AC power
via bypass.
2. The load is no longer
supplied by power.
Battery backup time is shorter than nominal value.
Batteries are not fully charged
Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer.
Batteries defect
Contact your dealer to replace the battery.
Fault code is shown as 45 on LCD display. At the same time, alarm is continuously sounding.
The charger does not have output and battery voltage is less than 10V/PC.
Contact your dealer.
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
Be sure to deliver the spent battery to a recycling facility or ship it to your
dealer in the replacement battery packing material.
Page 18
16
6. Specifications
MODEL
1.1K
1.5K
2K
3K*
CAPACITY
1100 VA / 770 W
1500 VA / 1050 W
2000 VA / 1400 W
3000 VA / 2100 W
INPUT
Acceptable Voltage Range
81-134 VAC/86-139 VAC/89-145AVC/102-152 VAC
or 162-268 VAC/162-268 VAC/170-280AVC/177-290 VAC
Frequency Range
60/50 Hz ± 5 Hz (auto sensing)
OUTPUT
Voltage Regulation (AC Mode)
110 (-15%/+10%) /115(-14%/+10%)/120(-14%/+10%)/127(-12%/+10%) VAC
or 208 (-10%/+16%) /220(-15%/+10%)/230(-15%/+10%)/240(-15%/+10%) VAC
Voltage Regulation (Batt. Mode)
110/115/120/127 VAC or 208/220/230/240 VAC ± 1.5%(before battery alarm)
Frequency Range (Batt. Mode)
50 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1
Harmonic Distortion
2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery
alarm)
Transfer Time
Typical 2-6 ms, 10ms max.
Waveform (Batt. Mode)
Pure Sine Wave
Overload capacity AC mode
103%~120% (-5%/+10%) 5 minutes
120%~150% (-5%/+10%) 10 sec
>150%(-5%/+10%) 1 sec
Battery mode
103%~110% (-5%/+10%) 1 minutes
110%~150% (-5%/+10%) 10 sec
>150%(-5%/+10%) 0.5 sec
EFFICIENCY
AC Mode
96%
Buck & Boost Mode
95%
Battery Mode
88%, up to 90% @ nominal battery voltage
BATTERY
Battery Type & Number
12 V/7 Ahx2
12 V/9 Ahx2
12 V/7 Ahx4
12 V/9 Ahx4
Charging Voltage
27.4 VDC ± 1%
54.8 VDC ± 1%
Recharge Time
4 hours recover to 90% capacity
PROTECTION
Full Protection
Overload, short, discharge, and overcharge protection
ALARM
Battery Mode
Sounding every 10 seconds
Low Battery
Sounding every 2 seconds
Overload
Sounding every second
Battery Replacement Alarm
Sounding every 2 seconds
Fault
Continuously sounding
PHYSICAL
Dimension, DXWXH (mm)
397 x 145x 220
455 x 145x 220
Net Weight (kg)
11.65
12.35
18.1
20.3
ENVIRONMENT
Operating Humidity
0-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 45dB
MANAGEMENT
Smart RS-232/USB
Supports Windows® 2000/2003/XP/Vista/2008, 7/8/10, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Only available for 208/220/230/240VAC system. Product specifications are subject to change without further notice.
Loading...