Please read carefully the following user manual and the
safety instructions before installing the unit or using the
unit!
1.1 Installation
★ See installation instructions before connecting to the supply.
★ Condensation may occur if the UPS is moved directly from a cold
to a warm environment. The UPS must be absolutely dry before
being installed. Please allow an acclimatization time of at least
two hours.
★ Do not install the UPS near water or in damp environment.
★ Do not install the UPS where it would be exposed to direct
sunlight or near heat.
★ Do not connect appliances or items of equipment which would
overload the UPS (e.g. laser printers, etc) to the UPS output.
★ Place cables in such a way that no one can step on or trip over
them.
★ Assure to connect with the earth reliably.
★ Assure external battery source must be earthed.
★ Connect the UPS only to an earthed shockproof socket outlet.
★ The building wiring socket outlet (shockproof socket outlet) must
be easily accessible to close to the UPS.
★ With the installation of the equipment, the sum of the leakage
current of the UPS and the connected load does not exceed
3.5mA.
★ Do not block ventilation openings in the UPS’s housing. Ensure
the air vents on the front, side and rear of the UPS are not
blocked. Allow at least 25cm of space on each side.
1
★ UPS has provided earthed terminal, in the final installed system
configuration, equipotential earth bonding to the external UPS
battery cabinets.
★ An appropriate disconnect device as short-circuit backup
protection should be provided in the building wiring installation.
Please see the disconnect device specification in chapter 5.2.
★ Equipment the powered more than one source.
1.2 Operation
★ Do not disconnect the mains cable on the UPS or the building
wiring socket (grounded shockproof socket) during operation as
this would remove the ground to the UPS and of all connected
loads.
★ The UPS features its own, internal current source (batteries). You
may be electric shock when you touch the UPS output sockets or
output terminal block even if the UPS is not connected to the
building wiring socket.
★ In order to fully disconnect the UPS, first press the OFF button to
turn off the UPS, then disconnect the mains lead.
2
★ Ensure that no liquid or other foreign objects can enter the UPS.
★ Do not remove the enclosure. This system is to be serviced by
qualified service personnel only.
★ Remove the protective panel only after disconnecting the terminal
and 12 lb-in Torque force when connecting to terminal block.
★ Use No. 12 AWG (for 3KS input wire), 90℃ copper wire and
4.4 lb-in Torque force when connecting to terminal block.
1.3 Maintenance, servicing and faults
★ The UPS operates with hazardous voltages. Repairs may be
carried out only by qualified maintenance personnel.
★ Caution - risk of electric shock. Even after the unit is
disconnected from the mains power supply (building wiring
socket), components inside the UPS are still connected to the
battery which are potentially dangerous.
★ Before carrying out any kind of service and/or maintenance,
disconnect the batteries. Verify that no current is present and no
hazardous voltage exists in the capacitor or BUS capacitor
terminals.
★ Batteries must be replaced only by qualified personnel.
★ Caution - risk of electric shock. The battery circuit is not isolated
from the input voltage. Hazardous voltages may occur between
the battery terminals and the ground. Verify that no voltage is
present before servicing!
★ Batteries have a high short-circuit current and pose a risk of
shock. Take all precautionary measures specified below and
any other measures necessary when working with batteries:
- remove all jewellery, wristwatches, rings and other metal
objects
3
- use only tools with insulated grips and handles.
★ When changing batteries, replace with the same quantity and the
same type of batteries.
★ Do not attempt to dispose of batteries by burning them. It could
cause explosion.
★ Do not open or destroy batteries. Effluent electrolyte can cause
injury to the skin and eyes. It may be toxic.
★ Please replace the fuse only by a fuse of the same type and of
the same amperage in order to avoid fire hazards.
★ Do not dismantle the UPS, except the qualified maintenance
personnel.
1.4 Transport
★★★★
Please transport the UPS only in the original packaging (to
protect against shock and impact).
1.5 Storage
★ The UPS must be stockpiled in the room where it is ventilated
Low Frequency Signals..........................:IEC/EN 61000-2-2
5
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is
advisable to familiarize yourself with them and understand their
meaning:
6
3. Introduction
This On-Line-Series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically
for Novell, Windows NT and UNIX servers.
The double-converter principle eliminates all mains power disturbances.
A rectifier converts the alternating current from the socket outlet to direct
current. This direct current charges the batteries and powers the
inverter. On the basis of this DC voltage, the inverter generates a
sinusoidal AC voltage, which permanently supplies the loads.
Computers and periphery are thus powered entirely by the mains
voltage. In the event of power failure, the maintenance-free batteries
power the inverter.
This manual covers the UPS listed as follows. Please confirm whether it
is the model you intend to purchase by performing a visual inspection of
the Model No. on the rear panel of the UPS.
Model No. Type Model No. Type
PowerWalker
VFI 1000T LCD
PowerWalker
VFI 2000T LCD
PowerWalker
VFI 3000T LCD
“L” Model: Extended backup time
Standard
PowerWalker VFI
1000T LCD L
PowerWalker VFI
2000T LCD L
PowerWalker VFI
3000T LCD L
Extended
backup time
7
4. Panel Description
The Display Panel
Switch Function
Turn on UPS system:
By pressing the ON-Button “I” the UPS system is turned
on.
Deactivate acoustic alarm:
ON-Button
OFF-Button
Select-Button
Enter-Button
8
By pressing this Button an acoustic alarm can be
deactivated in the battery mode.
Do the battery test:
By pressing this Button the UPS can do the battery test
in the Line mode or ECO mode or Converter mode.
When mains power is normal, the UPS system switches
to No output or Bypass mode by pressing OFF-Button
“ “, and the inverter is off. At this moment, if Bypass is
enabled, then the output sockets are supplied with
voltage via the bypass if the mains power is available.
Deactivate acoustic alarm:
By pressing this Button an acoustic alarm can be
deactivated in the bypass mode.
If the UPS system is No output or Bypass mode, the
output voltage and frequency and Bypass
disable/enable and operating mode could be selected by
pressing Select-Button, and confirmed by pressing
Enter-Button.
Display Function
Input Information
The LCD Display
Indicates the input Line voltage value, which could
be displayed from 0 to 999Vac
Indicates the frequency value of input Line
voltage, which could be displayed from 0 to 99Hz
Indicates the input Line voltage is higher than the
SPEC range, and the UPS would be working in
Battery mode
Indicates the input Line voltage is lower than the
SPEC range, and the UPS would be working in
Battery mode
Output Information
Load Information
Indicates the UPS output voltage value, which
could be displayed from 0 to 999Vac
Indicates the frequency value of the UPS output
voltage, which could be displayed from 0 to 99Hz
Indicates the load percent in Watt or VA, only the
maximum value of them could be displayed from 0
to 199%
Indicates the load or the UPS output is short and
the UPS would shut down
9
Battery Information
Indicates the load is over the SPEC range
Indicates the battery voltage value, which could
be displayed from 0 to 999Vdc
Indicates the battery capacitance percent, which
could be displayed from 0 to 199%
Indicates the battery is over charged, and the
UPS would be switched to Battery mode
Indicates the battery is weak, and the UPS would
shut down soon
Mode/Fault/Warning code Information
Indicates the operating mode of the UPS, Mode
code or Fault code or Warning code could be
displayed, and the codes are illuminated in detail
in the following chapter
Inverter operating Information
Indicates the circuit of the inverter is working
Bypass operating Information
Indicates the circuit of Bypass is working
Output voltage and frequency and Bypass disable/enable
selection Information
10
The four value of the output voltage could be
selected when the UPS is in No output or Bypass
mode, and only one of them could be active in the
same time
The two frequency value of the output voltage
could be selected when the UPS is in No output or
Bypass mode, and only one of them could be
active in the same time
Bypass disable or enable could be selected when
the UPS is in No output or Bypass mode, and only
one of them could be active in the same time