PowerWalker VFI 1000RT LCD User Manual [en, de, fr]

On-Line UPS
PowerWalker VFI 1000RT LCD PowerWalker VFI 1500RT LCD PowerWalker VFI 2000RT LCD PowerWalker VFI 3000RT LCD
EN, DE, FR
2
EN
CONTENT
USER MANUAL .................................... Fehler! Textmarke nicht definiert.
1. Safety and EMC Instructions ............................................................ 1
1.1 Installation .......................................................................................... 1
1.2 Operation ............................................................................................ 9
1.3 Maintenance, servicing and faults .................................................... 10
1.4 Transport .......................................................................................... 13
1.5 Storage ............................................................................................. 13
1.6 Standards ......................................................................................... 14
2. Description of Commonly Used Symbols ..................................... 15
3. Introduction ...................................................................................... 16
4. Panel Description ............................................................................. 17
5. Connection and Operation .............................................................. 19
5.1 Inspection ......................................................................................... 19
5.2 Connection ....................................................................................... 19
5.3 Battery charge .................................................................................. 21
5.4 Turn on the UPS ............................................................................... 21
5.5 Test function ..................................................................................... 21
5.6 Turn off the UPS ............................................................................... 22
5.7 Audible alarm mute function ............................................................. 22
5.8 Operation procedure of external battery for long backup time model
(“S” model) ............................................................................................. 22
6. Operating Mode for All Models ....................................................... 24
6.1 Line mode ......................................................................................... 24
6.2 Battery mode .................................................................................... 25
6.3 Bypass mode .................................................................................... 25
6.4 NO output mode ............................................................................... 26
6.5 EPO (Emergency Power Off) ........................................................... 26
6.6 ECO mode (Economy mode) ........................................................... 26
6.7 Converter mode ................................................................................ 27
6.8 Abnormal mode ................................................................................ 27
7. Setting by LCD Module .................................................................... 28
8. Trouble Shooting .............................................................................. 30
9. Maintenance ...................................................................................... 32
EN
9.1 Operation .......................................................................................... 32
9.2 Storage ............................................................................................. 32
9.3 Battery Replace ................................................................................ 32
10. Technical Data ................................................................................ 33
10.1 Electrical specifications .................................................................. 33
10.2 Operating Environment .................................................................. 33
10.3 Typical backup time (Typical values at 25°C in minutes:) ................. 33
10.4 Dimensions and weights .................................................................. 34
11. Communication Port ...................................................................... 35
11.1 RS-232 and USB communication ports ......................................... 35
11.2 RS-232 port .................................................................................... 35
11.3 USB port ......................................................................................... 36
11.4 Installing a Serial Network Management Card (optional) .............. 36
11.5 Dry Contact port ........................................................................... 36
12. Software Installation ...................................................................... 38
Appendix: Rear panel .......................................................................... 39
EN
1. Safety and EMC Instructions
SAVE THESE INSTRUCTIONS – This manual contains important instructions for models PowerWalker VFI 1000/1500/2000/3000RT LCD that should be followed during installation and maintenance of the UPS and batteries.
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
1.1 Installation
This product is specially designed for PCs and it is not recommended for use in any life-supporting system and other specific important equipment.
Do not connect household or other appliances or items of equipment which would overload the UPS (e.g. laser printers, hair dryers, etc) to the UPS output.
This unit intended for installation in a controlled environment (temperature controlled, indoor area free of conductive contaminants).
Condensation may occur if the UPS is moved directly from a cold to a warm environment. The UPS must be absolutely dry before being installed. Please allow an acclimatization time of at least two hours.
Risk of electric shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel.
The utility power outlet shall be near the equipment and easily accessible. To isolate UPS from AC input, remove the plug from the utility power outlet.
If UPS is to be stored for a long time, it is recommended to recharge the batteries (by connecting the utility power to UPS, switch “ON”), once a month for 24 hours to avoid a full battery discharge.
Please do not use the UPS in excess of the rated load capacity.
The UPS contains large-capacity batteries. So the shell shall not be opened,
otherwise such dangers as electric shock will be caused. If any internal overhaul or replacement of the battery is required, please contact the distributor.
The internal short circuiting of the UPS will lead to dangers such as electric shock or fire, therefore, no water containers (such as a water glass) shall be placed on the top of the UPS so as to avoid such dangers as electric shock.
Do not dispose of battery or batteries in a fire. The battery may explode.
1
2
EN
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
Icon Φ on the rating label stands for phase symbol.
A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on batteries :
Remove watches, rings, or other metal objects from the hand.
Use tools with insulated handles.
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, replace with the same type and number of the sealed lead-acid batteries.
This pluggable type A equipment with battery already installed by the supplier is operator installable and may be operated by laymen.
During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed
3.5mA.
Attention, hazardous through electric shock. Also with disconnection of this unit from the mains, hazardous voltage still may be accessible through supply from battery. The battery supply should be therefore disconnected in the plus and minus pole of the battery when maintenance or service work inside the UPS is necessary.
The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible.
Place cables in such a way that no one can step on or trip over them.
Assure to connect the UPS and external battery pack with the earth reliably
Do not block ventilation openings in the UPS´s housing. Ensure the air vents
on the front and rear of the UPS are not blocked. Allow at least 25cm of space on each side.
In case smoke is found coming out from the device, please cut off the power supply quickly and contact the distributor.
An appropriate disconnect device as short-circuit backup protection should be provided in the building wiring installation. Please see the disconnect device specification in chapter 5.2
Do not keep or use this product in any of the following environments:
o Any area with combustible gas, corrosive substance, heavy dust,
EN
standing water or running water.
o Any area with extraordinarily high or low temperature (above 40˚C or
below 0˚C) and humidity of more than 90%.
o Any area exposed to direct sunshine or near any heating apparatus.
(Maximum ambient temperature rating is 40°C.)
o Any area with serious vibrations. o Outdoor.
In the event that there is fire occurring in the vicinity, please use dry-power extinguishers. The use of liquid extinguishers may give rise to the danger of electric shock.
1.1.1 Inspection of Unit
Inspect the UPS upon receiving. If the UPS is apparently damaged during the shipment, please keep the box and packing material in original form for the carrier and notify the carrier and dealer immediately.
1.1.2 Unpacking the Cabinet
To unpack the system:
1. Open the outer carton and remove the accessories packaged with the cabinet.
2. Carefully lift the cabinet out of the outer carton and set it on a flat, stable surface.
3. Discard or recycle the packaging in a responsible manner, or store it for future use.
1.1.3 UPS Setup
All model series are designed for tower and rack purpose. They can be installed into a 19 inches equipment rack. Please follow the instruction for Tower Setup and Rack-Mount Setup.
Tower setup This series of UPS can be placed horizontally and vertically. As a tower
configuration, it is provided with the optional UPS stands to stabilize the UPS when the UPS is positioned in vertical. The UPS stand must be attached to the bottom of the tower. Use the following procedure to install UPS in UPS stands.
1. Slide down the UPS vertically and put two UPS stands at the end of the tower.
2. Place down the UPS into two stands carefully.
3
4
EN
3. Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then
push it back in the front panel.
EN
Rack-mount setup
The series can be installed in 19 inches racks. Both the UPS and external battery enclosure need 2U of rack space. Use the following procedure to install UPS in a rack.
1. Align the mounting ears with screw holes on the side of the UPS, and tighten
the screw.
2. Assemble the rack rails with the rack-mounting.
3. Slide in the UPS into the rack rail and lock it in the Rack-mounting.
4. Tighten the screw, and then the load can be connected.
1.1.4 EBM Installation (Optional)
Connecting the EBM in Tower form:
1. Slide down the UPS and EBM vertically and place two UPS stands with the
extend part at the end of the tower.
2. Tighten the screw on the metal sheet for stabilization
3. Connect the Earth line from UPS (port A ) to EBM (port B)
4. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. Users need to remove the small gate(C)
5
6
EN
on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
A
A
B
C
B
EN
5
Connecting the EBM in a rack form
1. Using the same method as assembling UPS in a rack form, assemble EBM
into the rack-mounting on the top or bottom of the UPS.
2. Connect the earth line from UPS (port A ) to EBM (port B )
3. Take off the LCD box, and unscrew the internal screws.
4. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. Users need to remove the small gate(C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
5. After installing the UPS into rack, the load can then be connected to UPS.
Please make sure the load equipment is turned off before plugging all loads into the output receptacle
B
A
Unscrew
Unscrew
B
A
C
Connecting the Multiple EBMs
1000VA/1500VA/2000VA and 3000VA UPS include external battery port that allows users to connect multiple EBM in order to provide additional backup time. Follow the procedure to install multiple EBM as below.
7
8
EN
Connecting multiple EBMs in Tower form
1. Connect Earth line between UPS and the first EBM, and then connect Earth
Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. And then connect the battery terminal (D) from the first EBM to the battery terminal (E) from the second EBM. Users need to remove the small gate(C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
D
C
A
B
E
Connecting the Multiple EBMs in rack form
1. Connect Earth line between UPS and the first EBM, and then connect
Earth Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. And then connect the battery terminal (D) from the first EBM to the battery terminal (E) from the second EBM. Users need to remove the small gate(C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
EN
E B
D
A
C
Note: Three or more EBMs can be connected to the UPS in the same way as shown above.
Note: After connect the EBMs, please do not forget to set the number of EBMs on LCD, please refer to chapter 7 “Setting by LCD module” for setting method. If use the nonstandard EBMs,
setting method.
please call local dealer or distributor for
1.2 Operation
Do not disconnect the mains cable on the UPS or the building wiring
socket (grounded shockproof socket) during operation as this would remove the ground to the UPS and of all connected loads.
The UPS features its own, internal current source (batteries). You may be
electric shock when you touch the UPS output sockets or output terminal block even if the UPS is not connected to the building wiring socket.
In order to fully disconnect the UPS, first press the OFF button to turn off
the UPS, then disconnect the mains lead.
Ensure that no liquid or other foreign objects can enter the UPS. Do not remove the enclosure. This system is to be serviced by qualified
service personnel only.
Remove the protective panel only after disconnecting the terminal
connections.
9
EN
Use No. 12 AWG (for 3KS input wire), 90°C copper wire and 4.4 lb-in
Torque force when connecting to terminal block.
Use No. 10AWG (for all models battery wire), 90°C copper wire and
Anderson PP45 connectors for user’s external battery cabinet.
1.3 Maintenance, servicing and faults
The UPS operates with hazardous voltages. Repairs may be carried out
only by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from
the mains power supply (building wiring socket), components inside the UPS are still connected to the battery which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect
the batteries. Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals.
Batteries must be replaced only by qualified personnel. Caution - risk of electric shock. The battery circuit is not isolated from the
input voltage. Hazardous voltages may occur between the battery terminals and the ground. Verify that no voltage is present before servicing!
Batteries have a high short-circuit current and pose a risk of shock. Take
all precautionary measures specified below and any other measures necessary when working with batteries:
remove all jewellery, wristwatches, rings and other metal objects use only tools with insulated grips and handles.
When changing batteries, replace with the same quantity and the same
type of batteries.
Do not attempt to dispose of batteries by burning them. It could cause
explosion.
Do not open or destroy batteries. Effluent electrolyte can cause injury to
the skin and eyes. It may be toxic.
Please replace the fuse only by a fuse of the same type and of the same
amperage in order to avoid fire hazards.
Do not dismantle the UPS, except the qualified maintenance personnel.
10
EN
1.3.1 UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For long battery life, keep the UPS at an ambient temperature of 25°C (77°F)
1.3.2 Storing the UPS and Batteries
When the UPS is intended to store for a long period, recharge the battery every 6 months by connecting the UPS to utility power. The batteries charge to 90% capacity in approximately 4 hours. However, it is recommended that the batteries charge for 48 hours after long-term storage.
1.3.3 Time to Replace Batteries
When the discharging time is less than 50% of specified after full charged, the battery may need to be replaced. Please check the battery connection or contact your local dealer to order new battery.
WARNING:
Turn off the UPS and disconnect the utility power cord from the wall outlet.
Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries
Batteries can present a risk of electrical shock or burn from high short circuit current. The following precautions should be observed:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Do not lay tools or metal parts on top of batteries.
4. Wear rubber gloves and boots.
5. Disconnect the charging source prior to connecting or disconnecting
battery terminal.
When replacing batteries, replace with the same type and number of batteries or battery packs. Contact your service representative to order new batteries.
Do not dispose of battery in a fire. Batteries may explode when exposed to flame.
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery. Released toxic electrolyte is harmful to skin and eyes.
11
EN
immediately.
5
7
Note: If you are not qualified service personnel to replace the battery, do not attempt to open the battery cabin. Please call local dealer or distributor
1.3.4 Replacing UPS Internal Batteries
Follow the steps and Charts as below to replace batteries:
1. Take off the LCD box, and remove the screws.
2. Slide and Pull the front panel leftward and then take it off.
3. Disconnect the cable from the UPS and battery pack.
4. Remove the right inner battery bracket.
5. Pull the battery pack out onto flat area.
6. Install new battery pack into UPS.
7. Screw up the battery bracket and reconnect the battery cable A and B
8. Re-install the front panel back to UPS.
12
EN
electrical shock and high short circuit curre
nt.
1.3.5 Testing New Batteries
For a battery test, please check:
The batteries must be fully charged.
The UPS must be in Normal mode with no active alarms.
Don’t take on/off the load.
To test batteries:
1. Connect the UPS to utility power for at least 48 hours to charge the
batteries.
2. Press and hold the “I” button 1 second to start the battery test on line mode
or HE mode. The status display string shows “TEST”
1.3.6 Recycling the Used Battery:
Warning:
Never dispose the batteries in a fire. It may explode.
Do not open or mutilate the batteries. Released electrolyte is harmful to the skins and eyes. It may be toxic. A battery can present a risk of
To recycle properly the used battery, please do not discard the UPS, battery pack and batteries into the trash bin. Please follow your local laws and regulations; you may contact your local recycling waste management center for further information to dispose properly of the used UPS, battery pack, and batteries.
1.4 Transport
Please transport the UPS only in the original packaging (to protect against
shock and impact).
1.5 Storage
The UPS must be stockpiled in the room where it is ventilated and dry.
13
EN
1.6 Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission..........................:IEC/EN 62040-2 Category C1
Radiated Emission.............................:IEC/EN 62040-2 Category C1
Harmonic Current...............................:IEC/EN 61000-3-2
Voltage Fluctuation and Flicker..........:IEC/EN 61000-3-3
*EMS
ESD...................................................:IEC/EN 61000-4-2 Level 3
RS.....................................................:IEC/EN 61000-4-3 Level 3
EFT....................................................:IEC/EN 61000-4-4 Level 4
SURGE.............................................:IEC/EN 61000-4-5 Level 4
CS……………………………………...:IEC/EN 61000-4-6 Level 3 MS……………………………………..: IEC/EN 61000-4-8 Level 3 Voltage Dips………………………….: IEC/EN 61000-4-11
Low Frequency Signals.....................:IEC/EN 61000-2-2
14
EN
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourself with them and understand their meaning:
15
EN
3. Introduction
This On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers.
The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage, the inverter generates a sinusoidal AC voltage, which permanently supplies the loads.
Computers and periphery are thus powered entirely by the mains voltage. In the event of power failure, the maintenance-free batteries power the inverter.
This manual covers the UPS listed as follows. Please confirm whether it is the model you intend to purchase by performing a visual inspection of the Model No. on the rear panel of the UPS.
Model No. Type Model No. Type
1K
1.5K 1.5KS 2K 2KS 3K 3KS
Standard
1KS
Extended backup
time
“S” Model: Extended backup time
16
EN
4. Panel Description
Switch Function ON-Button
OFF-Button
ON Button/ Alarm Silence
OFF-Button Select-Button Enter-Button
The Display Panel
Turn on UPS system: By pressing the ON-Button “I” the UPS system is turned on. Deactivate acoustic alarm: By pressing this Button an acoustic alarm can be deactivated in the battery mode. By short touch this Button all acoustic alarms can be deactivated in all mode. Do the battery test: By pressing this Button the UPS can do the battery test in the Line mode or ECO mode or Converter mode. When mains power is normal, the UPS system switches to No output or Bypass mode by pressing OFF-Button “ “, and the inverter is off. At this moment, if Bypass is enabled, then the output sockets are supplied with voltage via the bypass if the mains power is available. Deactivate acoustic alarm: By pressing this Button an acoustic alarm can be deactivated in the bypass mode. Release the UPS from fault mode and EPO status.
LCD Screen
Select-Button The output voltage, frequency, Bypass disable/enable and
operating mode in No output or Bypass mode, Two Load
Enter-Button
segments in output mode, The number of EBM in all mode, could be selected by pressing Select-Button, and confirmed by pressing Enter-Button.
17
EN
The LCD Display
Display Function Display Function
Input Information Output Information It indicates input
voltage/frequency value, which are displayed alternately.
It indicates the input is
connected with mains, and the input power is supplied from the mains.
It indicates the Number of
the input supplied from the mains.
Battery Information Load Information
Mode/Fault/Warning Information Else
It indicates the battery capacity. Every grid represents the capacity of 20%.
It Indicates the operating mode or Fault kind or Warning kind, several warning kinds at the same time could be displayed alternately.
It indicates output
voltage/frequency value, which are displayed alternately.
It indicates the Number of
It indicates the Output plug.
the output connected with load.
It indicates the load level. Every grid represents the level of 20%.
It indicates the UPS is in setting mode.
It indicates the UPS is in Fault mode or has some warnings.
18
EN
in accordance with applicable safety regulations!
amperage of your incoming feeder
.
5. Connection and Operation
The system may be installed and wired only by qualified electricians
When installing the electrical wiring, please note the nominal
5.1 Inspection
Inspect the packaging carton and its contents for damage. Please inform the transport agency immediately should you find signs of damage.
Please keep the packaging in a safe place for future use. Note: Please ensure that the incoming feeder is isolated and secured to
prevent it from being switched back on again.
5.2 Connection
(1) UPS Input Connection
If the UPS is connected via the power cord, please use a proper socket with protection against electric current, the user can refer to below table. If the UPS is connected via wires, it is recommended to select the 2.5mm2 wire, and the “GND” terminal should be grounded first.
The UPS System has no input breaker on the standard cabinet. When installing the UPS, the user needs to connect the external breakers and protective components in the input terminals. It is recommended to select the NFB(Non-Fuse Breaker) instead of the traditional combination kit including breaker and fuse.
When selecting the NFB, the user can refer to below table.
Model No.
UPS INPUT NFB & Power Cord & Socket
VOLTAGE CURRENT
1K(S) 300Vac 10A
1.5K(S) 300Vac 12A 2K(S) 300Vac 16A 3K(S) 300Vac 20A
19
EN
(2) UPS Output Connection
The output of the UPS is IEC socket-types. Simply plug the load power cord to the output sockets to complete connection. Use one cord for every 5A load.
Model No. Output Socket (pcs)
1K(S)/1.5K(S)/ 2K(S) 8 * IEC320 C13
3K(S) 8 * IEC320 C13 + 1 * C19
The wiring configuration is shown as the following procedure:
a) Remove the small cover of the terminal block b) Use 2.5mm2 wires for wiring configuration c) Upon completion of the wiring configuration,
please check whether the wires are securely affixed
d) Put the small cover back to the rear panel
Caution:
Do not connect equipment which would overload the UPS system (e.g. laser printers)
Connection diagram
(3) EPO Connection:
User can select the polarity of EPO, EPO is Normally open as default setting.
NO
Normally the EPO connector is open on the rear panel. Once the connector is closed with a wire, the UPS would stop the output until the EPO status is disabled.
Disable the EPO status Enable the EPO status
20
EN
NC
Normally the EPO connector is closed with a wire on the rear panel. Once the connector is open, the UPS would stop the output until the EPO status is disabled.
Enable the EPO status Disable the EPO status
5.3 Battery charge
Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1-2 hours. You may use the UPS system directly without charging it but the stored energy time may be shorter than the nominal value specified.
5.4 Turn on the UPS
(1) With utility power connecting:
Press “I” button continuously for more than 1 second to turn on the UPS, the UPS will get into the inverter mode, the LCD screen will indicate the state of the UPS.
(2) Without utility power connecting:
If UPS is cold start without utility power connecting, user need to push “I” button twice, first pushing “I” button is for UPS to get power, LCD screen show ‘INIT’. And second pushing “I” button continuously for more than 1 second is for UPS to turns on, the UPS will get into the inverter mode. In fact, the two pushing “I” button is to make further sure user operation for turning on UPS, the LCD screen will indicate the state of the UPS.
Note: The default setting for bypass mode is no output after UPS is connecting utility power and breaker is turned on. This can be configured by monitoring the LCD panel or firmware.
5.5 Test function
(1) Real time detection
UPS could do real-time detection when battery connected or disconnected. If the battery connection status is changed, in floating mode, UPS will detect the
21
EN
change within 30 seconds; in resting mode, UPS will detect the change within 3 minutes;
(2) Manual test
Test the function of the UPS system by pressing the On-Switch “I” for more than 1 second, the UPS would detect whether the battery is connected or the battery is low immediately. Also the UPS could do the test automatically and periodically, the period time could be set by user, the default value is 7 days.
5.6 Turn off the UPS
(1) In Inverter Mode:
Press “ ” button continuously for more than 1 second to turn off the UPS, the UPS will get into no output or bypass mode. At this time, the UPS might has output if bypass is enabled. Disconnect the utility power to turn off the output.
(2) In Battery Mode:
Press “ ” button continuously for more than 1 second to turn off the UPS, the UPS will be turned off completely.
5.7 Audible alarm mute function
If the alarm is too annoying in battery mode, you may press “I” button continuously for more than 1 second to clear it. Moreover, the alarm will be enabled when the battery is low to remind you to shutdown the load soon. If the alarm is too annoying in bypass mode, you may press “ “button continuously for more than 1 second to clear it. The action doesn’t affect the warning and fault alarm. If all alarm is too annoying, you can short touch “I” button, all alarms are disable, if alarms need to be resumed, short touch “I” button again.
5.8 Operation procedure of external battery for long backup time model (“S” model)
(1) Use the battery pack with voltage: 36VDC for 1KS (12V×3 batteries),
48VDC for 1.5KS/ 2KS (12V×4 batteries), 72VDC for 3KS (12V×6 batteries). Connection of batteries more than or less than required will cause abnormality or permanent damage.
(2) One hard wiring type battery terminal on the rear panel is used for
connecting the battery pack.
22
EN
(3) The battery connection procedure is very important. Any
incompliance may result in the risk of electric shock. Therefore, the following steps must be strictly complied with.
(4) Make sure the mains input is cut off, if there is a battery breaker then
turn it off first.
(5) Remove front panel, connect the battery via Anderson PP45
connectors. Prepare the battery cable which should be able to carry the current of >50A for all models, the cross section area should be great than 4 mm2 for all model. And battery wire color is recommended as following:
GND ----
++
Red wire Green/Yellow wire Black wire
(6) The red wire is connected to the "+" terminal of the battery. The black
wire is connected to the "-" terminal of the battery. (Note: the green/yellow wire is grounded for protection purpose.)
(7) Make sure the wires are fasten, install the terminal block cover on the
rear panel of the UPS.
(8) Connect the UPS to the load. Then, turn on the mains switch or
connect the power cord of the UPS to utility power supply, the battery would start to be charged.
Caution:
A DC breaker must be connected between the UPS and external battery.
Caution:
The output sockets of the UPS system may still be electrically live even if the power supply system has been disconnected or the Bypass switch is on “OFF” position.
23
EN
6. Operating Mode for All Models
The different string could be displayed on the LCD screen corresponding to their own operating modes, and they are illustrated as the following table. At any time, only one normal operating string or fault string is presented. But the warning, even several warnings could appear in a certain normal operating mode at one time. And the normal operating mode string and the warning string would be shown circularly. Once one fault is come forth, then all previous warnings would not be shown again but only the fault string is presented.
Normal operating mode Code
No output mode STbY Bypass mode bYPA Line mode LINE Battery mode bATT
Battery test mode TEST ECO mode ECO Converter mode CVCF
6.1 Line mode
The LCD display in Line mode is shown in the following diagram. The information about the utility power, the battery level, the UPS output and the load level could be displayed. The “LINE” string indicates the UPS is working in Line mode.
The Line mode
■■
If output overloaded, alarm will keep twice every second. You should get rid of some unnecessary loads one by one to decrease the loads connected to the UPS less than 90% of its nominal power capacity.
24
EN
Note: Please follow the following steps to connect the generator
Activate the generator and wait until the operation is stable before supplying
power of the generator to the UPS (be sure that the UPS is in idle mode). Then turn on the UPS according to the start-up procedure. After the UPS is turned on, then the loads can be connected to the UPS one by one.
The power capacity of the AC generator should be at least twice of the UPS
capacity.
6.2 Battery mode
The LCD display in battery mode is shown in the following diagram. The information about the utility power, the battery level, the UPS output and the load level could be displayed. The “bATT” string indicates the UPS is working in the battery mode. When the UPS is running in battery mode, the buzzer beeps once every 4 seconds. If the “ON” button on the front panel is pressed for more than 1 second again, the buzzer will stop beeping (in silence mode). Press the “ON” button once again for more than 1 second to resume the alarm function.
■■■■
The Battery mode
6.3 Bypass mode
The LCD display in bypass mode is shown in the following diagram. The information about the utility power, the battery level, the UPS output and the load level could be displayed. The UPS will beep once every 2 minutes in bypass mode. The “bYPA” string indicate the UPS is working in the bypass mode.
■■■■
The Bypass mode
25
EN
The UPS does not have the backup function when it is in bypass mode. The power used by the load is supplied from the utility power via internal filter.
6.4 NO output mode
The LCD display in No output mode is shown in the following diagram. The information about the utility power, the battery level, the UPS output and the load level could be displayed. The “STbY” string indicates the UPS is working in the No output mode.
■■■■
The No output mode
6.5 EPO (Emergency Power Off)
It is also called RPO (Remote Power Off). On LCD display, the mode string is “EPO”. It is a special status in which the UPS would shut the output off and alarm. The UPS could not be turned off by pressing “OFF” button on the panel, only after releasing EPO status by turning off the EPO switch.
6.6 ECO mode (Economy mode)
It is also called high efficiency mode. In ECO mode, on LCD display, the mode sting is “ECO”. After the UPS is turned on, the power used by the load is supplied from the utility power via internal filter while the utility power is in normal range, so the high efficiency could be gained in the ECO mode. Once the mains is loss or abnormal, the UPS would transfer to battery mode and the load is supplied continuously by the battery.
1) It could be enabled through the LCD setting or the software (Winpower,
etc.).
2) It is attention that the transfer time of UPS output from ECO mode to
battery mode is less than 10ms. But it is still too long for some sensitive load.
26
Loading...
+ 113 hidden pages