SAVE THESE INSTRUCTIONS – This manual contains important instructions for
models PowerWalker VFI 1000/1500/2000/3000RT LCD that should be followed
during installation and maintenance of the UPS and batteries.
Please read carefully the following user manual and the safety
instructions before installing the unit or using the unit!
1.1 Installation
•This product is specially designed for PCs and it is not recommended for use
in any life-supporting system and other specific important equipment.
•Do not connect household or other appliances or items of equipment which
would overload the UPS (e.g. laser printers, hair dryers, etc) to the UPS
output.
•This unit intended for installation in a controlled environment (temperature
controlled, indoor area free of conductive contaminants).
•Condensation may occur if the UPS is moved directly from a cold to a warm
environment. The UPS must be absolutely dry before being installed. Please
allow an acclimatization time of at least two hours.
•Risk of electric shock, do not remove cover. No user serviceable parts inside.
Refer servicing to qualified service personnel.
•The utility power outlet shall be near the equipment and easily accessible. To
isolate UPS from AC input, remove the plug from the utility power outlet.
•If UPS is to be stored for a long time, it is recommended to recharge the
batteries (by connecting the utility power to UPS, switch “ON”), once a month
for 24 hours to avoid a full battery discharge.
• Please do not use the UPS in excess of the rated load capacity.
• The UPS contains large-capacity batteries. So the shell shall not be opened,
otherwise such dangers as electric shock will be caused. If any internal
overhaul or replacement of the battery is required, please contact the
distributor.
•The internal short circuiting of the UPS will lead to dangers such as electric
shock or fire, therefore, no water containers (such as a water glass) shall be
placed on the top of the UPS so as to avoid such dangers as electric shock.
•Do not dispose of battery or batteries in a fire. The battery may explode.
1
Page 6
2
EN
•Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic.
• Icon Φ on the rating label stands for phase symbol.
• A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on batteries :
• Remove watches, rings, or other metal objects from the hand.
• Use tools with insulated handles.
• Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep
unauthorized personnel away from batteries.
•When replacing batteries, replace with the same type and number of the
sealed lead-acid batteries.
•This pluggable type A equipment with battery already installed by the supplier
is operator installable and may be operated by laymen.
•During the installation of this equipment it should be assured that the sum of
the leakage currents of the UPS and the connected loads does not exceed
3.5mA.
•Attention, hazardous through electric shock. Also with disconnection of this
unit from the mains, hazardous voltage still may be accessible through supply
from battery. The battery supply should be therefore disconnected in the plus
and minus pole of the battery when maintenance or service work inside the
UPS is necessary.
•The mains socket outlet that supplies the UPS shall be installed near the UPS
and shall be easily accessible.
• Place cables in such a way that no one can step on or trip over them.
• Assure to connect the UPS and external battery pack with the earth reliably
• Do not block ventilation openings in the UPS´s housing. Ensure the air vents
on the front and rear of the UPS are not blocked. Allow at least 25cm of space
on each side.
•In case smoke is found coming out from the device, please cut off the power
supply quickly and contact the distributor.
•An appropriate disconnect device as short-circuit backup protection should be
provided in the building wiring installation. Please see the disconnect device
specification in chapter 5.2
•Do not keep or use this product in any of the following environments:
oAny area with combustible gas, corrosive substance, heavy dust,
Page 7
EN
standing water or running water.
oAny area with extraordinarily high or low temperature (above 40˚C or
below 0˚C) and humidity of more than 90%.
oAny area exposed to direct sunshine or near any heating apparatus.
(Maximum ambient temperature rating is 40°C.)
o Any area with serious vibrations.
o Outdoor.
•In the event that there is fire occurring in the vicinity, please use dry-power
extinguishers. The use of liquid extinguishers may give rise to the danger of
electric shock.
★
1.1.1 Inspection of Unit
Inspect the UPS upon receiving. If the UPS is apparently damaged during the
shipment, please keep the box and packing material in original form for the
carrier and notify the carrier and dealer immediately.
1.1.2 Unpacking the Cabinet
To unpack the system:
1. Open the outer carton and remove the accessories packaged with the
cabinet.
2. Carefully lift the cabinet out of the outer carton and set it on a flat, stable
surface.
3. Discard or recycle the packaging in a responsible manner, or store it for
future use.
1.1.3 UPS Setup
All model series are designed for tower and rack purpose. They can be
installed into a 19 inches equipment rack. Please follow the instruction for
Tower Setup and Rack-Mount Setup.
Tower setup
This series of UPS can be placed horizontally and vertically. As a tower
configuration, it is provided with the optional UPS stands to stabilize the UPS
when the UPS is positioned in vertical. The UPS stand must be attached to the
bottom of the tower. Use the following procedure to install UPS in UPS stands.
1. Slide down the UPS vertically and put two UPS stands at the end of the tower.
2. Place down the UPS into two stands carefully.
3
Page 8
4
EN
3. Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then
push it back in the front panel.
Page 9
EN
Rack-mount setup
The series can be installed in 19 inches racks. Both the UPS and external battery
enclosure need 2U of rack space.
Use the following procedure to install UPS in a rack.
1. Align the mounting ears with screw holes on the side of the UPS, and tighten
the screw.
2. Assemble the rack rails with the rack-mounting.
3. Slide in the UPS into the rack rail and lock it in the Rack-mounting.
4. Tighten the screw, and then the load can be connected.
1.1.4 EBM Installation (Optional)
Connecting the EBM in Tower form:
1. Slide down the UPS and EBM vertically and place two UPS stands with the
extend part at the end of the tower.
2. Tighten the screw on the metal sheet for stabilization
3. Connect the Earth line from UPS (port A ) to EBM (port B)
4. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. Users need to remove the small gate(C)
5
Page 10
6
EN
on side of the front panel to allow the outlet wire of the EBM to pass through
the gate and then reassemble front panel.
A
A
B
C
B
Page 11
EN
5
Connecting the EBM in a rack form
1. Using the same method as assembling UPS in a rack form, assemble EBM
into the rack-mounting on the top or bottom of the UPS.
2. Connect the earth line from UPS (port A ) to EBM (port B )
3. Take off the LCD box, and unscrew the internal screws.
4. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. Users need to remove the small gate(C)
on side of the front panel to allow the outlet wire of the EBM to pass through
the gate and then reassemble front panel.
5. After installing the UPS into rack, the load can then be connected to UPS.
Please make sure the load equipment is turned off before plugging all loads
into the output receptacle
B
A
Unscrew
Unscrew
B
A
C
Connecting the Multiple EBMs
1000VA/1500VA/2000VA and 3000VA UPS include external battery port that
allows users to connect multiple EBM in order to provide additional backup
time. Follow the procedure to install multiple EBM as below.
7
Page 12
8
EN
Connecting multiple EBMs in Tower form
1. Connect Earth line between UPS and the first EBM, and then connect Earth
Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. And then connect the battery terminal
(D) from the first EBM to the battery terminal (E) from the second EBM.
Users need to remove the small gate(C) on side of the front panel to allow
the outlet wire of the EBM to pass through the gate and then reassemble
front panel.
D
C
A
B
E
Connecting the Multiple EBMs in rack form
1. Connect Earth line between UPS and the first EBM, and then connect
Earth Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. And then connect the battery terminal
(D) from the first EBM to the battery terminal (E) from the second EBM.
Users need to remove the small gate(C) on side of the front panel to allow
the outlet wire of the EBM to pass through the gate and then reassemble
front panel.
Page 13
EN
E
B
D
A
C
Note: Three or more EBMs can be connected to the UPS in the same way as
shown above.
Note: After connect the EBMs, please do not forget to set the number of
EBMs on LCD, please refer to chapter 7 “Setting by LCD module” for setting
method. If use the nonstandard EBMs,
setting method.
please call local dealer or distributor for
1.2 Operation
★ Do not disconnect the mains cable on the UPS or the building wiring
socket (grounded shockproof socket) during operation as this would
remove the ground to the UPS and of all connected loads.
★ The UPS features its own, internal current source (batteries). You may be
electric shock when you touch the UPS output sockets or output terminal
block even if the UPS is not connected to the building wiring socket.
★ In order to fully disconnect the UPS, first press the OFF button to turn off
the UPS, then disconnect the mains lead.
★ Ensure that no liquid or other foreign objects can enter the UPS.
★ Do not remove the enclosure. This system is to be serviced by qualified
service personnel only.
★ Remove the protective panel only after disconnecting the terminal
connections.
9
Page 14
EN
★ Use No. 12 AWG (for 3KS input wire), 90°C copper wire and 4.4 lb-in
Torque force when connecting to terminal block.
★ Use No. 10AWG (for all models battery wire), 90°C copper wire and
Anderson PP45 connectors for user’s external battery cabinet.
1.3 Maintenance, servicing and faults
★ The UPS operates with hazardous voltages. Repairs may be carried out
only by qualified maintenance personnel.
★ Caution - risk of electric shock. Even after the unit is disconnected from
the mains power supply (building wiring socket), components inside the
UPS are still connected to the battery which are potentially dangerous.
★ Before carrying out any kind of service and/or maintenance, disconnect
the batteries. Verify that no current is present and no hazardous voltage
exists in the capacitor or BUS capacitor terminals.
★ Batteries must be replaced only by qualified personnel.
★ Caution - risk of electric shock. The battery circuit is not isolated from the
input voltage. Hazardous voltages may occur between the battery
terminals and the ground. Verify that no voltage is present before
servicing!
★ Batteries have a high short-circuit current and pose a risk of shock. Take
all precautionary measures specified below and any other measures
necessary when working with batteries:
- remove all jewellery, wristwatches, rings and other metal objects
- use only tools with insulated grips and handles.
★ When changing batteries, replace with the same quantity and the same
type of batteries.
★ Do not attempt to dispose of batteries by burning them. It could cause
explosion.
★ Do not open or destroy batteries. Effluent electrolyte can cause injury to
the skin and eyes. It may be toxic.
★ Please replace the fuse only by a fuse of the same type and of the same
amperage in order to avoid fire hazards.
★ Do not dismantle the UPS, except the qualified maintenance personnel.
10
Page 15
EN
1.3.1 UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean
and dust-free. If the atmosphere is very dusty, clean the outside of the system
with a vacuum cleaner. For long battery life, keep the UPS at an ambient
temperature of 25°C (77°F)
1.3.2 Storing the UPS and Batteries
When the UPS is intended to store for a long period, recharge the battery
every 6 months by connecting the UPS to utility power. The batteries charge
to 90% capacity in approximately 4 hours. However, it is recommended that
the batteries charge for 48 hours after long-term storage.
1.3.3 Time to Replace Batteries
When the discharging time is less than 50% of specified after full charged, the
battery may need to be replaced. Please check the battery connection or
contact your local dealer to order new battery.
WARNING:
Turn off the UPS and disconnect the utility power cord from the wall outlet.
Servicing should be performed by qualified service personnel
knowledgeable of batteries and required precautions. Keep unauthorized
personnel away from batteries
Batteries can present a risk of electrical shock or burn from high short
circuit current. The following precautions should be observed:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Do not lay tools or metal parts on top of batteries.
4. Wear rubber gloves and boots.
5. Disconnect the charging source prior to connecting or disconnecting
battery terminal.
When replacing batteries, replace with the same type and number of
batteries or battery packs. Contact your service representative to order new
batteries.
Do not dispose of battery in a fire. Batteries may explode when exposed to
flame.
Proper disposal of batteries is required. Refer to your local codes for
disposal requirements.
Do not open or mutilate the battery. Released toxic electrolyte is harmful to
skin and eyes.
11
Page 16
EN
immediately.
5
7
Note: If you are not qualified service personnel to replace the battery, do not
attempt to open the battery cabin. Please call local dealer or distributor
1.3.4 Replacing UPS Internal Batteries
Follow the steps and Charts as below to replace batteries:
1. Take off the LCD box, and remove the screws.
2. Slide and Pull the front panel leftward and then take it off.
3. Disconnect the cable from the UPS and battery pack.
4. Remove the right inner battery bracket.
5. Pull the battery pack out onto flat area.
6. Install new battery pack into UPS.
7. Screw up the battery bracket and reconnect the battery cable A and B
8. Re-install the front panel back to UPS.
12
Page 17
EN
electrical shock and high short circuit curre
nt.
1.3.5 Testing New Batteries
For a battery test, please check:
The batteries must be fully charged.
The UPS must be in Normal mode with no active alarms.
Don’t take on/off the load.
To test batteries:
1. Connect the UPS to utility power for at least 48 hours to charge the
batteries.
2. Press and hold the “I” button 1 second to start the battery test on line mode
or HE mode. The status display string shows “TEST”
1.3.6 Recycling the Used Battery:
Warning:
Never dispose the batteries in a fire. It may explode.
Do not open or mutilate the batteries. Released electrolyte is harmful to
the skins and eyes. It may be toxic. A battery can present a risk of
To recycle properly the used battery, please do not discard the UPS, battery
pack and batteries into the trash bin. Please follow your local laws and
regulations; you may contact your local recycling waste management center
for further information to dispose properly of the used UPS, battery pack, and
batteries.
1.4 Transport
★ Please transport the UPS only in the original packaging (to protect against
shock and impact).
1.5 Storage
★ The UPS must be stockpiled in the room where it is ventilated and dry.
Low Frequency Signals.....................:IEC/EN 61000-2-2
14
Page 19
EN
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is advisable to
familiarize yourself with them and understand their meaning:
15
Page 20
EN
3. Introduction
This On-Line-Series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically for
Novell, Windows NT and UNIX servers.
The double-converter principle eliminates all mains power disturbances. A
rectifier converts the alternating current from the socket outlet to direct
current. This direct current charges the batteries and powers the inverter. On
the basis of this DC voltage, the inverter generates a sinusoidal AC voltage,
which permanently supplies the loads.
Computers and periphery are thus powered entirely by the mains voltage. In
the event of power failure, the maintenance-free batteries power the
inverter.
This manual covers the UPS listed as follows. Please confirm whether it is
the model you intend to purchase by performing a visual inspection of the
Model No. on the rear panel of the UPS.
Model No. Type Model No. Type
1K
1.5K 1.5KS
2K 2KS
3K 3KS
Standard
1KS
Extended backup
time
“S” Model: Extended backup time
16
Page 21
EN
4. Panel Description
Switch Function
ON-Button
OFF-Button
ON Button/
Alarm Silence
OFF-Button Select-Button Enter-Button
The Display Panel
Turn on UPS system: By pressing the ON-Button “I” the UPS
system is turned on.
Deactivate acoustic alarm: By pressing this Button an acoustic
alarm can be deactivated in the battery mode. By short touch this
Button all acoustic alarms can be deactivated in all mode.
Do the battery test: By pressing this Button the UPS can do the
battery test in the Line mode or ECO mode or Converter mode.
When mains power is normal, the UPS system switches to No
output or Bypass mode by pressing OFF-Button “ “, and the
inverter is off. At this moment, if Bypass is enabled, then the
output sockets are supplied with voltage via the bypass if the
mains power is available.
Deactivate acoustic alarm: By pressing this Button an acoustic
alarm can be deactivated in the bypass mode.
Release the UPS from fault mode and EPO status.
LCD Screen
Select-Button The output voltage, frequency, Bypass disable/enable and
operating mode in No output or Bypass mode, Two Load
Enter-Button
segments in output mode, The number of EBM in all mode, could
be selected by pressing Select-Button, and confirmed by
pressing Enter-Button.
17
Page 22
EN
The LCD Display
Display Function Display Function
Input Information Output Information
It indicates input
voltage/frequency value,
which are displayed
alternately.
It indicates the input is
connected with mains,
and the input power is
supplied from the mains.
It indicates the Number of
the input supplied from
the mains.
Battery Information Load Information
Mode/Fault/Warning Information Else
It indicates the battery
capacity. Every grid
represents the capacity of
20%.
It Indicates the operating
mode or Fault kind or
Warning kind, several
warning kinds at the same
time could be displayed
alternately.
It indicates output
voltage/frequency value,
which are displayed
alternately.
It indicates the Number of
It indicates the Output
plug.
the output connected with
load.
It indicates the load level.
Every grid represents the
level of 20%.
It indicates the UPS is in
setting mode.
It indicates the UPS is in
Fault mode or has some
warnings.
18
Page 23
EN
in accordance with applicable safety regulations!
amperage of your incoming feeder
.
5. Connection and Operation
The system may be installed and wired only by qualified electricians
When installing the electrical wiring, please note the nominal
5.1 Inspection
Inspect the packaging carton and its contents for damage. Please inform the
transport agency immediately should you find signs of damage.
Please keep the packaging in a safe place for future use.
Note: Please ensure that the incoming feeder is isolated and secured to
prevent it from being switched back on again.
5.2 Connection
(1) UPS Input Connection
If the UPS is connected via the power cord, please use a proper socket with
protection against electric current, the user can refer to below table. If the
UPS is connected via wires, it is recommended to select the 2.5mm2 wire,
and the “GND” terminal should be grounded first.
The UPS System has no input breaker on the standard cabinet. When
installing the UPS, the user needs to connect the external breakers and
protective components in the input terminals. It is recommended to select
the NFB(Non-Fuse Breaker) instead of the traditional combination kit
including breaker and fuse.
When selecting the NFB, the user can refer to below table.
The output of the UPS is IEC socket-types. Simply plug the load power cord
to the output sockets to complete connection. Use one cord for every 5A
load.
Model No. Output Socket (pcs)
1K(S)/1.5K(S)/ 2K(S) 8 * IEC320 C13
3K(S) 8 * IEC320 C13 + 1 * C19
The wiring configuration is shown as the
following procedure:
a) Remove the small cover of the terminal block
b) Use 2.5mm2 wires for wiring configuration
c) Upon completion of the wiring configuration,
please check whether the wires are securely
affixed
d) Put the small cover back to the rear panel
Caution:
Do not connect equipment which would overload the UPS system (e.g. laser
printers)
Connection diagram
(3) EPO Connection:
User can select the polarity of EPO, EPO is Normally close as default setting.
NO
Normally the EPO connector is open on the rear panel. Once the connector is
closed with a wire, the UPS would stop the output until the EPO status is disabled.
Disable the EPO status Enable the EPO status
20
Page 25
EN
NC
Normally the EPO connector is closed with a wire on the rear panel. Once
the connector is open, the UPS would stop the output until the EPO status is
disabled.
Enable the EPO status Disable the EPO status
5.3 Battery charge
Fully charge the batteries of the UPS system by leaving the UPS system
connected to the mains for 1-2 hours. You may use the UPS system directly
without charging it but the stored energy time may be shorter than the
nominal value specified.
5.4 Turn on the UPS
(1) With utility power connecting:
Press “I” button continuously for more than 1 second to turn on the UPS, the
UPS will get into the inverter mode, the LCD screen will indicate the state of
the UPS.
(2) Without utility power connecting:
If UPS is cold start without utility power connecting, user need to push “I”
button twice, first pushing “I” button is for UPS to get power, LCD screen
show ‘INIT’. And second pushing “I” button continuously for more than 1
second is for UPS to turns on, the UPS will get into the inverter mode. In fact,
the two pushing “I” button is to make further sure user operation for turning
on UPS, the LCD screen will indicate the state of the UPS.
Note: The default setting for bypass mode is no output after UPS is
connecting utility power and breaker is turned on. This can be configured by
monitoring the LCD panel or firmware.
5.5 Test function
(1) Real time detection
UPS could do real-time detection when battery connected or disconnected. If
the battery connection status is changed, in floating mode, UPS will detect the
21
Page 26
EN
change within 30 seconds; in resting mode, UPS will detect the change within
3 minutes;
(2) Manual test
Test the function of the UPS system by pressing the On-Switch “I” for more
than 1 second, the UPS would detect whether the battery is connected or the
battery is low immediately. Also the UPS could do the test automatically and
periodically, the period time could be set by user, the default value is 7 days.
5.6 Turn off the UPS
(1) In Inverter Mode:
Press “ ” button continuously for more than 1 second to turn off the UPS, the
UPS will get into no output or bypass mode. At this time, the UPS might has
output if bypass is enabled. Disconnect the utility power to turn off the output.
(2) In Battery Mode:
Press “ ” button continuously for more than 1 second to turn off the UPS, the
UPS will be turned off completely.
5.7 Audible alarm mute function
If the alarm is too annoying in battery mode, you may press “I” button
continuously for more than 1 second to clear it. Moreover, the alarm will be
enabled when the battery is low to remind you to shutdown the load soon.
If the alarm is too annoying in bypass mode, you may press “ “button
continuously for more than 1 second to clear it. The action doesn’t affect the
warning and fault alarm.
If all alarm is too annoying, you can short touch “I” button, all alarms are
disable, if alarms need to be resumed, short touch “I” button again.
5.8 Operation procedure of external battery for long backup
time model (“S” model)
(1) Use the battery pack with voltage: 36VDC for 1KS (12V×3 batteries),
48VDC for 1.5KS/ 2KS (12V×4 batteries), 72VDC for 3KS (12V×6
batteries). Connection of batteries more than or less than required
will cause abnormality or permanent damage.
(2) One hard wiring type battery terminal on the rear panel is used for
connecting the battery pack.
22
Page 27
EN
(3) The battery connection procedure is very important. Any
incompliance may result in the risk of electric shock. Therefore, the
following steps must be strictly complied with.
(4) Make sure the mains input is cut off, if there is a battery breaker then
turn it off first.
(5) Remove front panel, connect the battery via Anderson PP45
connectors. Prepare the battery cable which should be able to carry
the current of >50A for all models, the cross section area should be
great than 4 mm2 for all model. And battery wire color is
recommended as following:
+
+ GND ----
++
Red wire Green/Yellow wire Black wire
(6) The red wire is connected to the "+" terminal of the battery. The black
wire is connected to the "-" terminal of the battery. (Note: the
green/yellow wire is grounded for protection purpose.)
(7) Make sure the wires are fasten, install the terminal block cover on the
rear panel of the UPS.
(8) Connect the UPS to the load. Then, turn on the mains switch or
connect the power cord of the UPS to utility power supply, the battery
would start to be charged.
Caution:
A DC breaker must be connected between the UPS and external battery.
Caution:
The output sockets of the UPS system may still be electrically live even if the
power supply system has been disconnected or the Bypass switch is on
“OFF” position.
23
Page 28
EN
6. Operating Mode for All Models
The different string could be displayed on the LCD screen corresponding to
their own operating modes, and they are illustrated as the following table. At
any time, only one normal operating string or fault string is presented. But the
warning, even several warnings could appear in a certain normal operating
mode at one time. And the normal operating mode string and the warning
string would be shown circularly. Once one fault is come forth, then all
previous warnings would not be shown again but only the fault string is
presented.
Normal operating mode Code
No output mode STbY
Bypass mode bYPA
Line mode LINE
Battery mode bATT
Battery test mode TEST
ECO mode ECO
Converter mode CVCF
6.1 Line mode
The LCD display in Line mode is shown in the following diagram. The
information about the utility power, the battery level, the UPS output and the
load level could be displayed. The “LINE” string indicates the UPS is working
in Line mode.
■
■ The Line mode
■■
If output overloaded, alarm will keep twice every second. You should get rid of
some unnecessary loads one by one to decrease the loads connected to the
UPS less than 90% of its nominal power capacity.
24
Page 29
EN
■■■■
The B
ypass mode
Note: Please follow the following steps to connect the generator:
● Activate the generator and wait until the operation is stable before supplying
power of the generator to the UPS (be sure that the UPS is in idle mode).
Then turn on the UPS according to the start-up procedure. After the UPS is
turned on, then the loads can be connected to the UPS one by one.
● The power capacity of the AC generator should be at least twice of the UPS
capacity.
6.2 Battery mode
The LCD display in battery mode is shown in the following diagram. The
information about the utility power, the battery level, the UPS output and the
load level could be displayed. The “bATT” string indicates the UPS is working
in the battery mode.
When the UPS is running in battery mode, the buzzer beeps once every 4
seconds. If the “ON” button on the front panel is pressed for more than 1
second again, the buzzer will stop beeping (in silence mode). Press the “ON”
button once again for more than 1 second to resume the alarm function.
■■■■
The Battery mode
6.3 Bypass mode
The LCD display in bypass mode is shown in the following diagram. The
information about the utility power, the battery level, the UPS output and the
load level could be displayed. The UPS will beep once every 2 minutes in
bypass mode. The “bYPA” string indicate the UPS is working in the bypass
mode.
25
Page 30
EN
The UPS does not have the backup function when it is in bypass mode.
The power used by the load is supplied from the utility power via internal
filter.
6.4 NO output mode
The LCD display in No output mode is shown in the following diagram.
The information about the utility power, the battery level, the UPS output
and the load level could be displayed. The “STbY” string indicates the
UPS is working in the No output mode.
■■■■
The No output mode
6.5 EPO (Emergency Power Off)
It is also called RPO (Remote Power Off). On LCD display, the mode
string is “EPO”.
It is a special status in which the UPS would shut the output off and alarm.
The UPS could not be turned off by pressing “OFF” button on the panel,
only after releasing EPO status by turning off the EPO switch.
6.6 ECO mode (Economy mode)
It is also called high efficiency mode. In ECO mode, on LCD display, the
mode sting is “ECO”.
After the UPS is turned on, the power used by the load is supplied from
the utility power via internal filter while the utility power is in normal range,
so the high efficiency could be gained in the ECO mode. Once the mains
is loss or abnormal, the UPS would transfer to battery mode and the load
is supplied continuously by the battery.
1) It could be enabled through the LCD setting or the software (Winpower,
etc.).
2) It is attention that the transfer time of UPS output from ECO mode to
battery mode is less than 10ms. But it is still too long for some sensitive
load.
26
Page 31
EN
6.7 Converter mode
In converter mode, on LCD display, the mode string is “CVCF”.
The UPS would free run with fixed output frequency (50Hz or 60Hz) in
converter mode. Once the mains is loss or abnormal, the UPS would transfer
to battery mode and the load is supplied continuously by the battery.
1) It could be enabled through the LCD setting or the software (Winpower,
etc.).
2) The load should be derating to 70% in converter mode.
6.8 Abnormal mode
In abnormal mode such as Bus fault etc., the corresponding fault string would
be shown to indicate the operating mode of the UPS, and the background light
become red. For example “SHOR” would be shown when the load or the UPS
output is short. The LCD display is shown in the following diagram.
27
Page 32
EN
7. Setting by LCD Module
The output voltage, frequency, Bypass status and operating mode in No
output mode or Bypass mode, Two Load segments in output mode, The
number of EBM in all mode could be set directly through LCD module. The
output voltage could be set to 208V, 220V, 230V and 240V. The output
frequency could be set to 50Hz and 60Hz. The bypass state could be set to
enable and disable. The operating mode of UPS could be set between the
Line mode, ECO mode and Converter mode. The number of EBM could be
set to 0 to 9. Two Load segments could be set to on and off.
In bypass or no output mode, pressing the “Enter” button on the LCD panel for
more than one second to enter setting mode. The LCD display is shown in the
following diagram. The string “OPV” indicates that the current setting is output
voltage. “230Vac” indicates the current default output voltage is 230Vac. if you
want to set output voltage, press the “Enter” button for more than one second,
a flickering string “208” would be shown, if the “Enter” button is pressed again,
the string “208” turn to flickerless, the output volt is changed to 208V; if the
“Select” button is pressed for more than one second, the next flickering string
“220” appear, the order of flickering string is 208 – 220 – 230 – 240 – 208,
Press “Enter” button to confirm the output volt what you want.
Exit the setting mode to short touch the “Enter” button; continue setting to
press “Select” button. if no any pressing on the “Select” or “Enter” button
lasting for more than 10 seconds, the setting mode exit automatically.
The output frequency string “OPF”, Bypass status string ” bYPA”, operating
mode string “MOdE”, EBM string EbM, Load segment string “LS1” and “LS2”
would be presented circularly. The only one voltage value could be selected in
“208V”, “220V”, “230V”, “240V” at any time; The only one frequency value
could be selected in “50Hz”, “60Hz” at any time; Bypass status could be
selected in “000” or “001”(Here 000 means Bypass Disable,001 means
Bypass Enable),The UPS would turn to bypass mode in several seconds after
28
Page 33
EN
“
Enter”
button to exit setting mode.
“Bypass Enable” is selected, and turn to no output mode in several seconds
after “Bypass Disable” is selected; Operating mode could be selected in
“UPS”, “ECO”, “CVF”(Here “UPS” means the normal inverter mode, “ECO”
means the high efficiency mode, and “CVF” means the converter mode), The
mode change would be active only after the UPS is turned on; The number of
EBM could be selected in “000” to “009”(Here “000” means no EBM
connected). Load segment 1 could be selected in “000” or “001”(Here 000
means load segment 1 off, 001 means load segment 1 on); Load segment 2 is
the same as Load segment 1.
■
■ Here is a example for changing the Operating mode from normal mode to
■■
converter mode through the LCD panel.
Step 1: “OPV” after pressing the “Enter” button; Step 2: “OPF” after pressing the “Select” button.
Step 3: “bYPA” after pressing the “Select” button; Step 4: “MOdE” after pressing the “Select” button,
press the “Enter” button to set mode, then “UPS”
flickering;
Step 5: “ECO” flickering after pressing
button the “Select” button;
Step 6: “CVF” flickering after pressing the
“Select” again. Press the “Enter” button to
make sure to change the mode. Short touch
29
Page 34
EN
8. Trouble Shooting
If the UPS system does not operate correctly, check the operating status on the LCD
display.
Warning String Fault String
Site fail SITE Inverter short SHOR
Fan fail FANF Overload fault OVLD
Battery over voltage (over charged) HIGH Inverter soft start fail ISFT
Battery low bLOW Bus soft start fail bSFT
Charge fail CHGF Over temperature fault OVTP
Inverter temperature high TEPH Inverter voltage low INVL
Ambient temperature high AMbH Inverter voltage high INVH
Battery open bOPN Bus voltage over bUSH
Overload OVLD Bus voltage Low bUSL
EPO EPO Bus voltage unbalance bUSE
Battery fault bATF Bus short bUSS
NTC open NTCO
If the UPS system does not operate correctly, please attempt to solve the problem
using the table below.
Problem Pzle cause Remedy
No indication, no
warning tone even
though system is
connected to mains
power supply
Display Mode
string ”STbY” in LCD,
even though the power
supply is available
Display Mode
string ”bATT” in LCD,
and audible alarm
sounding every 1 beep
in every 4 seconds
Emergency supply
period shorter than
nominal value
Fan fail Fan abnormal Check if the fan is running
Battery over voltage Battery is over charged Stop charging to battery
No input voltage Check building wiring socket outlet
Inverter not switched on Press On-Switch “I”.
Mains power supply has
failed, or Input power
and/or frequency are out
of tolerance
Batteries not fully charged
/ batteries defect
and input cable.
Switching to battery mode
automatically.
Check input power source and inform
dealer if necessary.
Charge the batteries for at least
5 - 8 hours and then check capacity.
If the problem still persists, consult
your dealer.
automatically, and after the battery
voltage is normal and the mains is
normal, charge automatically again.
30
Page 35
EN
Battery low Battery voltage is low When audible alarm sounding every
Charge fail The charge is broken Notify dealer.
Inverter temperature
high
Ambient temperature
high
Battery open Battery pack is not
Battery fault Battery may need to be
Overload Overload Check the loads and remove some
Site fail Phase and neutral
EPO active EPO function is enabled Turn off the EPO switch.
Bus fault(Low/high/
Unbalance/soft start)
Inverter
fault(Low/high/soft
start)
Over temperature fault Over temperature Check the ventilation of the UPS,
NTC open UPS internal fault Notify dealer
Inverter short Output short circuit Remove all the loads. Turn off the
Bus short UPS internal fault Notify dealer
Inside temperature of the
UPS is too high
The ambient temperature
is too high
connected correctly
replaced
conductor at input of UPS
system are reversed
UPS internal fault Notify dealer
UPS internal fault Notify dealer
second, battery is almost empty.
Check the ventilation of the UPS,
check the ambient temperature.
Check the environment ventilation.
Check the battery bank is connected
to the UPS.
Check the battery breaker is turn on.
Notify dealer
non-critical loads.
Check whether some loads are failed.
Rotate mains power socket by 180°
or connect UPS system.
check the ambient temperature and
ventilation.
UPS. Check whether the output of
UPS and loads is short circuit. Make
sure the short circuit is removed, and
the UPS has no internal faults before
turning on again.
Please have the following information at hand before calling the After-Sales
Service Department:
1. Model number, serial number
2. Date on which the problem occurred
3. LCD display status, Buzzer alarm status
4. Utility power condition, load type and capacity, environment temperature,
ventilation condition
5. The information (battery capacity, quantity) of external battery pack if the UPS
is “S” model
6. Other information for complete description of the problem
31
Page 36
EN
9. Maintenance
9.1 Operation
The UPS system contains no user-serviceable parts. If the battery service life
(3~5 years at 25°C ambient temperature) has been ex ceeded, the batteries
must be replaced. In this case please contact your dealer.
9.2 Storage
If the batteries are stored in temperate climatic zones, they should be charged
every three months for 1~2 hours. You should shorten the charging intervals
to two months at locations subject to high temperatures.
9.3 Battery Replace
If the battery service life has been exceeded, the batteries must be replaced.
Battery replacement should be performed only by qualified personnel.
It recommends to shut off the UPS completely before the replacement. If there
is a battery breaker then turn it off first. Disconnect the battery cable carefully
and make sure no any exposed wires can be touched. Reconnect the new
batteries to the UPS by following section 5.8. Then turn on the battery breaker
and start the UPS.
If it needs to replace the batteries while the UPS is running, make sure the
UPS would not shut down during the replacement. If there is a battery breaker
then turn it off first. Disconnect the battery cable carefully and make sure no
any exposed wires can be touched. Reconnect the new batteries to the UPS
by following section 5.8. Then turn on the battery breaker and press the ON
switch to make the UPS do the battery test, check whether the battery
information is normal.
32
Page 37
EN
10. Technical Data
Specyfikacja elektryczna
WEJŚCIE
Model No. 1000VA 1500VA2000VA 3000VA
Phase 1
Częstotliwość(45~55)/(54~66) Hz
Max Current(A) 7.5 10.5 13.5 20
WYJŚCIE
Model No. 1000VA 1500VA 2000VA 3000VA
Power rating 1kVA/0.9kW 1.5k/1.35kW 2kVA/1.8kW 3kVA/2.7kW
Voltage 208/220/230/240×(1 士 1%)VAC
Frequency 50/60(±0.2)Hz (Battery mode)
Wave form sinusoidal
BATTERIES
Model No. 1K 1.5K 2K 3K
Number and type 3×12V 7Ah 4×12V 7Ah 4×12V 9Ah 6×12V 9Ah
To establish communication between the UPS and a computer, connect a
computer to one of the UPS communication ports by using an applicable
communication cable.
NOTE:
Only one of the communication ports can be active at one time. The USB port has
priority over the RS-232 port.
When a communication cable is installed, the power management software can
exchange data with the UPS. The software polls the UPS for detailed information
on the status of the power environment. If a power emergency occurs, the
software initiates the saving of all data and an orderly shutdown of the equipment
11.2 RS-232 port
The RS-232 port is available for UPS monitoring, control, and firmware
updates. To establish communication between the UPS and a computer,
connect one end of the serial communication cable that comes with the UPS
to the RS-232 port on the UPS. Connect the other end of the serial cable to
the RS-232 port on a computer.
The cable pins for the RS-232 communication port are identified in the
following illustration.
RS-232 communication port pin assignments
Pin Signal name Function
1 Unused Not applicable
2 Tx Transmit to external device Out
3 Rx Receive from external device In
4 Unused Not applicable
5 GND
Signal common
(tied to chassis)
6 Unused Not applicable
7 Unused Not applicable
8 Unused Not applicable
9 Unused Not applicable
Direction from
the UPS
Not applicable
35
Page 40
EN
11.3 USB port
The UPS can communicate with a USB-compliant computer by using
HID-compatible power management software. To establish communication
between the UPS and a computer, connect the USB cable that comes with the
UPS to the USB port on the UPS. Connect the other end of the USB cable to
the USB port on a computer.
11.4 Installing a Serial Network Management Card (optional)
Each UPS has one available communication bay, which supports the optional
Serial Network Management Card. After you install a Serial Network
Management Card, you can connect an environmental monitoring probe to
the UPS.
Note: You do not have to shut down the UPS before you install a
communication card.
To install the Network Management Card, complete the following steps:
1. Locate the UPS communication bay.
2. Remove the two screws that secure the communication bay cover to the
UPS and save the screws.
3. Insert the Serial Network Management Card into the slot on the UPS.
4. Secure the Serial Network Management Card to the UPS with both
screws.
For more information about the Serial Network Management Card, see the
Serial Network Management Card User's Guide.
11.5 Dry Contact port
The UPS incorporates build-in single programmable relay output with
potential free contact for remote alarm indication: Dry out port; And
incorporates single signal input: Dry in port. See figure in the UPS rear
panel for the locations of the ports.
The relay output can be configured by protocol command setting, the
default output contact is “Summary Alarm”; The signal input to control UPS
On/Off status does not need to be configured, its function is the same as
one button to control UPS On/Off status.
Note:
connected circuits. Reinforced insulation to the utility is required. The relay
output contact has a maximum rating of 30Vac/1A and 60Vdc/2A normal
values.
The relay output contact must not be connected to any utility
36
Page 41
EN
The following figures show schematic of the dry out/in contacts.
Dry out contact schematic
Dry in contact schematic
The following table shows the options for the dry out/in contacts
Dry out signal Description
Summary Alarm Activated when any warning happens
On Battery Activated when the UPS operates on battery
Battery Low Activated with the “bLOW” alarm
UPS ok Activated when the UPS has no alarms and no
fault.
On Bypass Activated when the UPS has bypass output.
Dry in signal Description
UPS On/Off One second pulse activate, if active, the UPS
turns off when UPS is on inverter; the UPS turns
on when UPS is not on inverter. It is the same as
a remote button to control UPS On/Off status.
37
Page 42
EN
12. Software Installation
WinPower is UPS monitoring software, featuring user-friendly interface to
monitor and control your UPS. This unique software provides complete
power protection for computer system while power failure. With the
software users can monitor any UPS status on the same LAN.
Furthermore, a UPS can provide security protection for more than one
computer on the same LAN at the same time, such as shutting down
system in security, saving application data and shutting down the UPS
when power fails.
Software Installation on your PC:
Connected by USB to a PC or notebook, the Software enables communication
between the UPS and the computer. The UPS software monitors the status of the
UPS, shuts down the system before the UPS is exhausted and can remotely observe
the UPS via the Network (enabling users to manage their system more effectively).
Upon AC failure or UPS battery low, UPS takes all necessary actions without
intervention from the system administrator. In addition to automatic file saving and
system shut-down functions, it can also send warning messages via pager, e-mail
etc.
• Use the bundled CD and follow the on-screen instructions to install the software
WinPower.
• Enter the following serial No. to install software: 511C1-01220-0100-478DF2A
• After the software is successfully installed, the communication with UPS has
been established and an green icon will appear in the system tray.
• Double-click the icon to use the monitor software (as above).
• You can schedule UPS shutdown/start-up and monitor UPS status through PC.
• Detail instructions please refer to the e-manual in the software.
Check www.powerwalker.com/winpower.html from time to time to get the latest
version of monitoring software.
38
Page 43
EN
Appendix: Rear panel
The UPS rear panel description table and pictures are shown as below:
No. Function(1000VA &1500VA&2000VA&3000VA)
1 AC Output
2 EPO / Dry in Communication Port
3 USB Port
4 AC Input
5 Dry out
6 SNMP slot
7 RS232
8 Modem/Network Surge Protection
9 Earth Line Port
1000VA /1500VA/2000VA Standard
& 1000VA /1500VA Super charger model rear panel
2000VA Super charger model rear panel
39
Page 44
EN
~
250V 16A
DRYIN
~
EPO
DRYOUT
RS232
INTELLIGENT SLOT
USB
250V 10A
LS2AC OUTPUT
~
250V 10A
LS1AC OUTPUT
3000VA Standard model rear panel
~
250V 16A
DRYIN
EPO
DRYOUT
RS232
INTELLIGENTS LOT
USB
250V 10A~
LS2AC OUTPUT
~
250V 10A
LS1AC OUTPUT
3000VA Supper charger model rear panel
The EBM rear panel description table and picture are shown as below:
AC INPUT
USECOPPERCONDUCTORONLY.FORSUPPLYCONNECTIONS,
USEWIRESSUITABLEFORATLEAST75℃.REFERTO