PowerWalker VFI 1000RM LCD User Manual [en, ru, de, es, fr, it]

EN
Online UPS
PowerWalker VFI 1000RM LCD PowerWalker VFI 1500RM LCD PowerWalker VFI 2000RM LCD PowerWalker VFI 3000RM LCD
User Manual (EN, ES, DE, FR, IT, PT, RU)
Uninterruptible Power Supply System
EN
Table of Contents
1. Important Safety Warning…………………………………………………
2
1-1. Transportation
2
1-2. Preparation
2
1-3. Installation
2
1-4. Operation
2
1-5. Maintenance, service and faults
3
2. Installation and setup……………………………………………………..
4
2-1. Rear panel view
4
2-2. Rack-mounted the UPS
4
2-3. Setup the UPS
5
2-4. Battery replacement
7
2-5. Battery kit assembly (option)
8
3. Operations…………………………………………………………………..
10
3-1. Button operation
10
3-2. LCD Panel
10
3-3. Audible Alarm
12
3-4. LCD display wordings index
12
3-5. UPS Setting
12
3-6. Operating Mode Description
15
3-7. Faults Reference Code
15
3-8. Warning indicator
16
4. Troubleshooting…………………………………………………………....
18
5. Storage and Maintenance…………………………………………………
18
6. Specifications……………………………………………………………….
19
1
2
EN
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully
1.1. Transportation
Please transport the UPS system only in the original package to protect against
shock and impact.
1.2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.  Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1.3. Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.  Do not connect domestic appliances such as hair dryers to UPS output sockets.  The UPS can be operated by any individuals with no previous experience.  Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
When installing the equipment, it should ensure that the sum of the leakage current
of the UPS and the connected devices does not exceed 3.5mA.
1.4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS
output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
EN
1.5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary when working with batteries:
remove wristwatches, rings and other metal objects
 use only tools with insulated grips and handles.  When changing batteries, install the same number and same type of batteries.  Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.
3
4
EN
2. Installation and setup
Model
Type
Model
Type
1K
Standard
1K-L
Long-run
2K
2K-L
3K
3K-L
1K(L) & 2K(L)
3K(L)
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use. NOTE: There are two different types of online UPS: standard and long-run models. Please refer to the following model table.
2.1. Rear panel view
1. Programmable outlets: connect to non-critical loads.
2. Output receptacles: connect to mission-critical loads.
3. AC input
4. Input circuit breaker
5. Network/Fax/Modem surge protection
6. Emergency power off function connector (EPO)
7. USB communication port
8. RS-232 communication port
9. SNMP intelligent slot
10. External battery connection (only available for L model)
2.2. Rack-Mounted the UPS
This UPS can be mounted in the 19” rack chassis. Please follow below steps to position this
UPS.
Step 1 Step 2
EN
Step 1
Step 2
Step 3
Remove front panel.
Connect the AC input and re-connect battery wires.
Put the front panel back to the unit.
2.3. Setup the UPS Step 1: Connect battery wires
For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before install the UPS, please follow below steps to re-connect battery wires first.
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package. For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input
plug is a NEMA 5-15P for 1K and 1K-L models, NEMA 5-20P for 2K and 2K-L models.
Note: For Low voltage models: Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated when the UPS is plugged into an improperly wired utility power outlet (Refer to Troubleshooting section). Please also install a circuit breaker (40A) between the mains and AC input in 3K model for safety operation.
Step 3: UPS output connection
For socket-type outputs, there two kinds of outputs: programmable outlets and general
outlets. Please connect non-critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting shorter backup time for non-critical devices.
For terminal-type input or outputs, please follow below steps for the wiring configuration:
a) Remove the small cover of the terminal block b) Suggest using AWG14 or 2.1mm2 power cords. Suggest using AWG12-10 or
3.3mm2-5.3mm2 power cords for NEMA type.
c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 4: Communication connection Communication port:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
5
6
EN
It’s in closed status for UPS
normal operation.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options.
PS. USB port and RS-232 port can’t work at the same time.
Step 5: Network connection Network/Fax/Phone surge port
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line
cable.
Step 6: Disable and enable EPO function
Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the wire between pin 1 and pin 2.
Step 7: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.
Step 8: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software. If not, please follow steps below to download and install monitoring software from the internet:
1. Go to the website http://www.power-software-download.com
2. Click ViewPower software icon and then choose your required OS to download the software.
3. Follow the on-screen instructions to install the software.
4. When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.
Step 8: External battery connection (for long-run models only) Follow below chart to make external battery connection.
EN
Step 1
Step 2
Step 3
Remove front panel.
Disconnect battery wires.
Pull out the battery box by removing two screws on the front panel.
Step 4
Step 5
Step 7
Remove the top cover of battery box and replace the inside batteries.
After replacing the batteries, put the battery box back to original location and screw it tightly.
Re-connect the battery wires.
2.4 Battery replacement NOTICE: This UPS is equipped with internal batteries and user can replace the batteries
without shutting down the UPS or connected loads.(hot-swappable battery design) Replacement is a safe procedure, isolated from electrical hazards.
CAUTION!! Consider all warnings, cautions, and notes before replacing batteries. Note: Upon battery disconnection, equipment is not protected from power outages.
7
8
EN
Step 8
Put the front panel back to the unit.
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by following below chart.
Step 3: Put assembled battery packs on one side of plastic shells.
Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.
Tapes
2.5 Battery kit assembly (option) NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select
correct battery kit procedure below to assemble it.
2-battery kit
EN
4-battery kit
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by following below chart.
Step 3: Put assembled battery packs on one side of plastic shells.
Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by following below chart.
Step 3: Put assembled battery packs on one side of plastic shells.
Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.
Tapes
Tapes
Tapes
Tapes
6-battery kit
9
10
EN
3. Operations
3.1. Button operation
Button
Function
ON/Mute Button
Turn on the UPS: Press and hold ON/Mute button for at least 2
seconds to turn on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold
this button for at least 5 seconds to disable or enable the alarm
system. But it’s not applied to the situations when warnings or errors
occur.
Up key: Press this button to display previous selection in UPS setting
mode.
Switch to UPS self-test mode: Press and hold ON/Mute buttons for 5
seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
OFF/Enter Button
Turn off the UPS: Press and hold this button at least 2 seconds to
turn off the UPS in battery mode. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.
Confirm selection key: Press this button to confirm selection in UPS
setting mode.
Select Button
Switch LCD message: Press this button to change the LCD message
for input voltage, input frequency, battery voltage, output voltage and output frequency. It will return back to default display when pausing for 10 seconds.
Setting mode: Press and hold this button for 5 seconds to enter UPS
setting mode when UPS is in standby mode or bypass mode.
Down key: Press this button to display next selection in UPS setting
mode.
ON/Mute + Select Button
Switch to bypass mode: When the main power is normal, press
ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS will enter to bypass mode. This action will be ineffective when the input voltage is out of acceptable range.
3.2. LCD Panel
EN
Display
Function
Backup time information
Indicates the remaining backup time in pie chart.
Indicates the remaining backup time in numbers.
H: hours, M: minute, S: second
Fault information
Indicates that the warning and fault occurs.
Indicates the warning and fault codes, and the codes are listed in details in 3-5 section.
Mute operation
Indicates that the UPS alarm is disabled.
Output & Battery voltage information
Indicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the UPS output is short circuit.
Programmable outlets information
Indicates that programmable management outlets are working.
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the output is working. Battery information
Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is fault.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
11
12
EN
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Bypass Mode
Sounding every 10 seconds
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
HLS
High loss
LLS
Low loss
BAT
Battery
CF Converter
EP EPO
FA Fan
TP Temperature
CH
Charger
There are three parameters to set up the UPS.
Parameter 1: It’s for program alternatives.
There are 10 programs to set up. Refer to below table. Parameter 2 and parameter 3 are the setting options or values for each program.
Parameter 1
Parameter 2
Parameter 3
3.3. Audible Alarm
3.4. LCD display wordings index
3.5. UPS Setting
EN
01: Output voltage setting
Interface
Setting
Parameter 3: Output voltage
For 200/208/220/230/240 VAC models, you may choose the following output voltage:
200: present output voltage is 200Vac 208: present output voltage is 208Vac 220: present output voltage is 220Vac 230: present output voltage is 230Vac 240: present output voltage is 240Vac
For 100/110/150/120/127 VAC models, you may choose the following output voltage:
100: present output voltage is 100Vac 110: present output voltage is 110Vac 115: present output voltage is 115Vac 120: present output voltage is 120Vac 127: present output voltage is 127Vac
Interface
Setting
Parameter 2 & 3: Enable or disable converter mode. You may choose the following two options: CF ENA: converter mode enable CF DIS: converter mode disable
Interface
Setting
Parameter 2 & 3: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: present output frequency is 50Hz BAT 60: present output frequency is 60Hz
If converter mode is enabled, you may choose the following output frequency:
CF 50: present output frequency is 50Hz CF 60: present output frequency is 60Hz
Interface
Setting
Parameter 3: Enable or disable ECO function. You may choose
the following two options:
ENA: ECO mode enable DIS: ECO mode disable
Interface
Setting
Parameter 2 & 3: Set the acceptable high voltage point and low
voltage point for ECO mode by pressing Down key or Up key. HLS: High loss voltage in ECO mode in parameter 2. For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from +7V to +24V of the nominal voltage. For 100/110/115/120/127 VAC models, the setting range in parameter 3 is from +3V to +12V of the nominal voltage. LLS: Low loss voltage in ECO mode in parameter 2. For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from -7V to -24V of the nominal voltage. For 100/110/115/120/127 VAC models, the setting voltage in
02: Frequency Converter enable/disable
03: Output frequency setting
04: ECO enable/disable
05: ECO voltage range setting
13
14
EN
parameter 3 is from -3V to -12V of the nominal voltage.
Interface
Setting
Parameter 3: Enable or disable Bypass function. You may choose
the following two options:
ENA: Bypass enable DIS: Bypass disable
Interface
Setting
Parameter 2 & 3: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the Down key or Up key. HLS: Bypass high voltage point For 200/208/220/230/240 VAC models: 230-264: setting the high voltage point in parameter 3 from 230Vac to 264Vac. For 100/110/115/120/127 VAC models: 120-132: setting the high voltage point in parameter 3 from 120Vac to 132Vac LLS: Bypass low voltage point For 200/208/220/230/240 VAC models: 170-220: setting the low voltage point in parameter 3 from 170Vac to 220Vac For 100/110/115/120/127 VAC models: 85-115: setting the low voltage point in parameter 3 from 85Vac to 115Vac.
Interface
Setting
Parameter 3: Enable or disable programmable outlets. ENA: Programmable outlets enable DIS: Programmable outlets disable
Interface
Setting
Parameter 3: Set up backup time limits for programmable outlets. 0-999: setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on battery mode.
Interface
Setting
Parameter 3: Set up backup time on battery mode for general
outlets. 0-999: setting the backup time in minutes from 0-999 for general outlets on battery mode.
0: When setting as “0”, the backup time will be only 10 seconds. 999: When setting as “999”, the backup time setting will be
disabled.
06: Bypass enable/disable when UPS is off
07: Bypass voltage range setting
08: Programmable outlets enable/disable
09: Programmable outlets setting
10: Backup time setting for outlets
00: Exit setting
EN
Operating mode
Description
LCD display
Online mode
When the input voltage is within acceptable range, UPS will provide pure and stable AC power to output. The UPS will also charge the battery at online mode.
ECO mode
Energy saving mode: When the input voltage is within voltage regulation range, UPS will bypass voltage to output for energy saving.
Frequency Converter mode
When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery under this mode.
Battery mode
When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second, UPS will backup power from battery.
Bypass mode
When input voltage is within acceptable range but UPS is overload, UPS will enter bypass mode or bypass mode can be set by front panel. Alarm is sounding every 10 second.
Standby mode
UPS is powered off and no output supply power, but still can charge batteries.
3.6. Operating Mode Description
15
16
EN
3.7. Faults Reference Code
Fault event
Fault code
Icon
Fault event
Fault code
Icon
Bus start fail
01
x
Inverter voltage Low
13
x
Bus over
02
x
Inverter output short
14
Bus under
03
x
Battery voltage too high
27
Bus unbalance
04
x
Battery voltage too low
28
Inverter soft start fail
11
x
Over temperature
41
x
Inverter voltage high
12
x
Over load
43
Warning
Icon (flashing)
Alarm
Low Battery
Sounding every second
Overload
Sounding twice every second
Battery is not connected
Sounding every second
Over Charge
Sounding every second
Site wiring fault
Sounding every second EPO enable
Sounding every second
Fan Failure
Sounding every second
Over temperature
Sounding every second
Charger failure
Sounding every second
Out of bypass voltage range
Sounding every second
3.8. Warning indicator
EN
4. Troubleshooting
Symptom
Possible cause
Remedy
No indication and alarm even though the mains is normal.
The AC input power is not connected well.
Check if input power cord firmly connected to the mains.
The AC input is connected to the UPS output.
Plug AC input power cord to AC input correctly.
The icon and the warning code flashing on LCD
display and alarm is sounding every second.
EPO function is activated.
Set the circuit in closed position to disable EPO function.
The icon and flashing on LCD display and alarm is sounding every second.
Line and neutral conductors of UPS input are reversed.
Rotate mains power socket by 180° and then connect to UPS system.
The icon and flashing on LCD display and alarm is sounding every second.
The external or internal battery is incorrectly connected.
Check if all batteries are connected well.
Fault code is shown as 27 and the icon is lighting on
LCD display and alarm is continuously sounding.
Battery voltage is too high or the charger is fault.
Contact your dealer.
Fault code is shown as 28 and the icon is lighting on
LCD display and alarm is continuously sounding.
Battery voltage is too low or the charger is fault.
Contact your dealer.
The icon and is flashing on LCD display and alarm is sounding twice every second.
UPS is overload
Remove excess loads from UPS output.
UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass.
Remove excess loads from UPS output.
After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains.
Remove excess loads from UPS output first. Then shut down the UPS and restart it.
Fault code is shown as 43 and The icon is lighting on
LCD display and alarm is continuously sounding.
The UPS shut down automatically because of overload at the UPS output.
Remove excess loads from UPS output and restart it.
If the UPS system does not operate correctly, please solve the problem by using the table below.
17
18
EN
Symptom
Possible cause
Remedy
Fault code is shown as 14 and the icon is lighting on
LCD display and alarm is continuously sounding.
The UPS shut down automatically because short circuit occurs on the UPS output.
Check output wiring and if connected devices are in short circuit status.
Fault code is shown as 1, 2, 3, 4, 11, 12, 13 and 41 on LCD display and alarm is continuously sounding.
A UPS internal fault has occurred. There are two possible results:
1. The load is still supplied, but directly from AC power via bypass.
2. The load is no longer supplied by power.
Contact your dealer
Battery backup time is shorter than nominal value
Batteries are not fully charged
Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer.
Batteries defect
Contact your dealer to replace the battery.
The icon and the warning code flashing on LCD
display and alarm is sounding every second.
Fan is locked or not working
Check fans and notify dealer!!
5. Storage and Maintenance
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
EN
6. Specifications
MODEL
1000
1500
2000
3000
CAPACITY*
1000 VA / 800 W
1500 VA / 1200 W
2000 VA / 1600 W
3000 VA / 2400 W
INPUT
Voltage Range Low Line Transfer
80VAC/70VAC/60VAC/50VAC ± 5% or 160VAC/140VAC/120VAC/110VAC ± 5%
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback
85VAC/75VAC/65VAC/55VAC ± 5 % or 170VAC/150VAC/130VAC/120VAC± 5 %
High Line Transfer
150 VAC ± 5 % or 300 VAC ± 5 %
High Line Comeback
145 VAC ± 5 % or 290 VAC ± 5 %
Frequency Range
45Hz ~ 55 Hz or 56Hz ~ 65 Hz
Phase
Single phase with ground
Power Factor
0.99 @ 220-230 VAC or 110-120 VAC
OUTPUT
Output voltage
100/110/115/120/127 VAC or 200/208/220/230/240VAC
AC Voltage Regulation
± 1% (Batt. Mode)
Frequency Range (Synchronized Range)
48 ~ 52 Hz or 58 ~ 62 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz
Current Crest Ratio
3:1
Harmonic Distortion
2% (Linear load)
8% max (Bat mode before shut down)
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
86 %
88 %
Battery Mode
83 %
85 %
BATTERY
Standard Model
Battery Type
12 V / 7AH
12 V / 9AH
12 V / 7 AH
12 V / 9 AH
Numbers 3 3 6 6
Recharge Time
4 hours recover to 90% capacity (Typical)
Charging Current
1.0 A(max.)
Charging Voltage
41.1 VDC± 1%
82.1VDC ± 1%
82.1VDC ± 1%
Long-run Model
Battery Type & Numbers
Depending on the capacity of external batteries
Charging Current
8.0 A(max.)
Charging Voltage
41.1 VDC± 1%
82.1VDC ± 1%
82.1VDC ± 1%
PHYSICAL
Standard Model
Dimension, D X W X H mm
480 x 438 x 88
600 x 438 x 88
600 x 438 x 88
Net Weight (kgs)
18.4
18.5
25.7
29
Long-run Model
Dimension, D X W X H mm
480 x 438 x 88
600 x 438 x 88
600 x 438 x 88
Net Weight (kgs)
11.3
10.7
14.6
14.8
ENVIRONMENT
Operation Humidity
20-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC.
19
ES
SAI Online
PowerWalker VFI 1000RM LCD PowerWalker VFI 1500RM LCD PowerWalker VFI 2000RM LCD PowerWalker VFI 3000RM LCD
Manual de usuario
Sistema de Alimentación Ininterrumpida
ES
INDICE
1. Aviso importante sobre seguridad …………………………………...........
2
1.1. Transporte
2
1.2. Preparación
2
1.3. Instalación
2
1.4. Funcionamiento
2
1.5. Mantenimiento y reparación
3
2. Instalación y configuración ……………………………………..................
4
2.1. Vista del panel posterior
4
2.2. Montaje en rack del SAI
4
2.3. Configuración del SAI
5
2.4. Sustitución de baterías
7
2.5. Kit de baterías (opcional)
8
3.Operaciones ………………………………………………………………….....
10
3.1. Botones de funcionamiento
10
3.2. Panel LCD
10
3.3. Alarma acústica
12
3.4. Indicación del display LCD
12
3.5. Configuración del SAI
12
3.6. Descripción del modo operativo
15
3.7. Código de error
15
3.8. Indicadores de alerta
16
4. Solución de problemas …………………………………………..................
17
5. Almacenamiento y mantenimiento …………………………………….......
18
6. Especificaciones.………………………………………………………...........
19
1
2
ES
1. Aviso importante sobre seguridad
Siga estrictamente todas las advertencias e instrucciones de este manual. Guarde este manual y lea atentamente las siguientes instrucciones antes de instalar la unidad. No utilice este aparato sin antes leer con atención toda las instrucciones y la información sobre seguridad.
1.1. Transporte
Por favor, transporte el SAI en la caja original para protegerlo de cualquier posible
choque o golpe.
1.2. Preparación
Cuando el SAI pasa de un ambiente cálido a otro frío se puede crear condensación.
El equipo debe estar completamente seco antes de su instalación. Por favor, deje el SAI, por lo menos dos horas, para climatizarlo.
No instale el SAI cerca de agua o en ambientes húmedos.  No instale el SAI en un lugar directamente expuesto a la luz solar o cerca de fuentes
de calor.
No bloquee los orificios de ventilación del SAI.
1.3. Instalación
No conecte la toma de salida del SAI a dispositivos que puedan sobrecargarlos (por
ejemplo: impresoras láser).
Coloque los cables de manera que no se puedan pisar o tropezar con ellos.  No conecte a la toma del SAI aparatos como secadores de pelo.  El SAI puede ser usado por cualquier persona, incluso sin experiencia.  Conecte el SAI únicamente a un enchufe con toma de tierra que sea fácilmente
accesible y cercano al SAI, de manera que no se pisotee el cable.
Por favor, use sólo cables de alimentación con homologación VDE y CE para
conectar el SAI a la toma de red (con toma de tierra).
Use sólo cables de alimentación con homologación VDE y CE para conectar las
cargas al SAI.
Al instalar el SAI, debe asegurarse de que la suma de la corriente de fuga del SAI y
del equipo conectado a él no sea superior a 3.5mA.
1.4. Funcionamiento
No desconecte el cable de alimentación del SAI, de lo contrario se anulará la
protección que la masa de tierra proporciona al SAI y a todas sus cargas.
El SAI tiene su propia de fuente de alimentación interna (baterías). En la toma de
salida del SAI o terminales de voltaje de salida puede haber tensiones, incluso si el SAI no está conectado a la red.
Para desconectar completamente el SAI, presione el interruptor OFF/Enter.  Impida la entrada de líquidos u objetos extraños al interior del SAI.
ES
1.5. Mantenimiento y reparación
El SAI funciona con voltajes peligrosos. Cualquier reparación debe ser realizada
exclusivamente por personal cualificado.
Precaución - Riesgo de descarga eléctrica. Incluso después de desconectarse de
la red, el cableado interno continúa conectado a la batería y la tensión es peligrosa.
Antes de realizar cualquier tipo de servicio y/o mantenimiento, desconecte las
baterías, verificando que no haya corriente ni exista riesgo de voltaje, incluidas las creadas por los condensadores de alta capacidad.
Sólo las personas habilitadas para tratar con baterías y que lo hagan con las
medidas y precauciones necesarias, pueden sustituir las baterías y controlar las operaciones. Las personas no autorizadas no deben tener contacto con las baterías.
Precaución - Riesgo de descarga eléctrica. La batería no está aislada del circuito
de la tensión de entrada. Puede haber voltajes peligrosos entre los terminales de la batería y la toma de tierra. ¡Antes de tocar nada, por favor, compruebe que no haya tensión!
Las baterías pueden causar descargas eléctricas y cortocircuitos. Por favor, tome
las precauciones abajo detalladas y cualquier otra medida necesaria cuando se trabaje con las baterías:
Quitar relojes, anillos y otros objetos metálicos
 Utilice sólo herramientas con asas y mangos aislados.  Cuando cambie las baterías, instale la misma cantidad y el mismo tipo de baterías.  No intente tirar a la basura o quemar las baterías porque podrían explotar.  No abra o destruya las baterías. El electrolito que se desprende puede dañar la piel
y los ojos. La batería puede ser tóxica.
Por favor, reemplace el fusible únicamente por otro del mismo tipo y amperaje para
evitar riesgo de incendio.
No desmonte el SAI bajo ningún concepto.
3
4
ES
2. Instalación y configuración
Modelo
Tipo
Modelo
Tipo
1K
Estándar
1K-L
Autonomía
extendida
2K
2K-L
3K
3K-L
1K(L)/1.5K(L) IEC & 2K(L)
3K(L)
NOTA: Antes de la instalación, por favor, compruebe la unidad. Asegúrese de que no haya
nada dañado en el interior del embalaje. Por favor, mantenga el embalaje original en un lugar seguro para un futuro uso. NOTA: Hay dos tipos diferentes de SAI On-line Rack: estándar y de larga autonomía. Consulte el modelo en la siguiente tabla.
2.1. Vista panel posterior
1. Salidas programables: conexión a cargas no críticas.
2. Conectores de salida: conectar a las cargas críticas.
3. Entrada de red AC (Corriente Alterna)
4. Disyuntor de entrada
5. Protección contra sobretensión de red / fax / módem
6. Conector con función de apagado de emergencia (EPO – Emergency Power Off)
7. Puerto de comunicación USB
8. Puerto de comunicación RS-232
9. Slot inteligente SNMP
10. Conector de batería externa (sólo disponible en modelo L, larga autonomía)
2.2. Montaje en Rack del SAI
EL SAI puede colocarse en un armario rack 19”. Por favor siga las siguientes instrucciones para colocar el SAI en rack.
Paso 1 Paso 2
ES
Paso 1
Paso 2
Paso 3
Quite el panel frontal
Conecte la entrada AC y reconecte las conexiones de las baterías.
Coloque nuevamente el panel frontal
2.3. Configuración del SAI Paso 1: Conexión de las baterías
Por razones de seguridad, el SAI viene embalado de fabrica con las baterias desconectadas. Antes de conectar el SAI, por favor siga los siguientes pasos para conectar las baterías.
Paso 2: Conexión de entrada al SAI
Conecte el SAI únicamente a una toma de dos polos, tres cables, con toma a tierra.
Evite el uso de cables de extensión.
Para los modelos de 208/220/230/240VAC: el cable se suministra con el SAI. Para los modelos de 110/115/120/127VAC: el cable viene insertado directamente en el
SAI. El enchufe es del tipo NEMA 5-15P para los modelos 1K y 1K-L y NEMA 5-20P
para los modelos 2K y 2K-L. Nota: Para los modelos de baja tensión. Compruebe si el indicador de fallo de conexión del panel LCD está encendido. Se ilumina cuando el SAI está enchufado a una toma de red inapropiada. (Consulte la sección de resolución de problemas). Instale también, por favor, un disyuntor (40A) entre la red y la entrada AC en los modelos de 3K para un uso seguro.
Paso 3: Conexión de salida del SAI
Las tomas de salida son de dos tipos: tomas de corriente generales y enchufes
programables. Conecte las cargas no críticas a las salidas programables y los
dispositivos críticos a las tomas generales. En caso de fallo eléctrico, puede programar
el SAI para aumentar el tiempo de autonomía a las cargas críticas y reducirlo para las
cargas no críticas.
Para los SAIs 3K, siga los pasos abajo detallados para acceder a la configuración de
los terminales de entrada y salida:
a) Quitar la tapita del bloque de terminales en la parte trasera del SAI.
b) Se recomienda usar cables tipo AWG14 o 2.1mm2, mientras que para las
conexiones tipo NEMA, se aconseja utilizar cables AWG12-10 o 3.3mm2 - 5.3mm2. c) Al concluir las conexiones, compruebe que los cables están bien sujetos. d) Vuelva a colocar la tapita del bloque de terminales.
Paso 4: Conectores de comunicación Puertos de comunicación:
Puerto USB Puerto RS-232 Slot Inteligente
Para controlar el SAI a través del PC, conecte el cable de comunicación desde el PC a un
5
6
ES
Habitualmente apagado para el funcionamiento normal del SAI.
puerto USB/RS-232 del SAI. Con el software de control instalado en su PC, puede programar el encendido / apagado del SAI y controlar su estado a través del PC.
El SAI está equipado con una ranura (slot) para tarjetas inteligentes AS400 o SNMP para tener una comunicación avanzada o una mejor opción de controlar el SAI.
Nota: los puertos USB y RS-232 no pueden funcionar simultáneamente.
Paso 5: Conectar red Puertos de protección Red/ Fax/Teléfono
La conexión es para una sola línea de módem, teléfono o fax. IN es la entrada de la línea de comunicación, OUT es la salida del cable que se conecta el módem, teléfono o fax.
Paso 6: Habilitar y deshabilitar la función EPO
Para el funcionamiento normal del SAI, mantenga apagados los pines 1 y 2. Para activar la función EPO, mantenga abiertos los pines 1 y 2.
Paso 7: Encender el SAI
Pulse el interruptor ON/Mute de la parte frontal durante 2 segundos para encender el SAI. Nota: La batería se carga por completo en 5 horas de funcionamiento normal del SAI. No realice experimentos de descargas de la batería durante el periodo de carga ni espere tener la batería a pleno rendimiento durante el periodo de carga inicial.
Paso 8: Instalar el software
Para una protección óptima del sistema, instale el software de control del SAI en su PC para configurar el apagado del SAI. Inserte el CD suministrado en la unidad CD-Rom para instalar el software de control. Si no, siga los siguientes pasos para descargar el software de internet:
1. Introducción de la página web http://www.power-software-download.com
2. Haga clic en ViewPower y elija el sistema operativo (OS) para transferir el software a su PC.
3. Siga las instrucciones en la pantalla del monitor para instalar el software.
4. Cuando reinicie su PC, verá un icono de color naranja, en el área de notificaciones, cerca del reloj de su PC (abajo a la derecha).
Paso 8: Conexión de la batería externa (sólo para modelos de larga autonomía) Para la conexión de batería externa, véase la siguiente figura.
ES
Paso 1
Paso 2
Paso 3
Retire el panel frontal
Desconecte los cables de batería.
Quite los 2 tornillos colocados en el chasis del panel frontal y saque la caja de baterías hacia fuera.
Paso 4
Paso 5
Paso 6
Quite la tapa superior de la caja de baterías y reemplace las baterías que se encuentran dentro de la caja.
Después de reemplazar las baterías, coloque la caja de baterías en su lugar de origen y atornille los 2 tornillos que quitó
Conecte nuevamente los cables de batería.
2.4. Cambio de baterías
NOTA: El SAI está equipado con baterías internas y el usuario puede reemplazarlas sin
necesidad de desconectar las cargas conectadas al SAI (extracción de baterías en caliente). ¡¡PRECAUCIÓ N!! La sustitución es un procedimiento seguro y desprovisto de peligros electricos, aún así, tome en consideración todas las advertencias, precauciones y notas antes de reemplazar las baterias. Nota: Al desconectar la batería el equipo queda desprotegido contra cortes de energía.
7
8
ES
en el paso 3.
Paso 7
Coloque nuevamente el panel frontal.
Paso 1: Quite las cintas adhesivas.
Paso 2: Conecte todos los terminales de las baterías tal como se muestra en el gráfico.
Paso 3: Coloque las baterías sobre uno de los laterales de la carcasa de plástico.
Paso 4: Cubra el otro lado con la tapa del kit de baterías.
Adhesivos
2.5. Kit de baterías adicional (opcional)
AVISO: Por favor ensamble el kit de baterías primero, antes de colocarlo en el SAI. Seleccione el procedimiento correcto dependiendo del tipo de kit para colocar las baterías.
Kit de 2 baterías
ES
Kit de 4 baterías
Paso 1: Quite las cintas adhesivas.
Paso 2: Conecte todos los terminales de las baterías tal como se muestra en el gráfico.
Paso 3: Coloque las baterías sobre uno de los laterales de la carcasa de plástico.
Paso 4: Cubra el otro lado con la tapa del kit de baterías.
Paso 1: Quite las cintas adhesivas.
Paso 2: Conecte todos los terminales de las baterías tal como se muestra en el gráfico.
Paso 3: Coloque las baterías sobre uno de los laterales de la carcasa de plástico
Paso 4: Cubra el otro lado con la tapa del kit de baterías.
Adhesivos
Adhesivos
Adhesivos
Adhesivos
Kit de 6-baterías
9
Loading...
+ 110 hidden pages