PowerWalker VFI 1000 LE User Manual

Page 1
CONTENT
1. Product Introduction ...................................................... 3
1.1 Functions description .................................................................... 3
1.2 Mode description ........................................................................... 4
1.3 Front panel .................................................................................... 5
1.4 Rear panel ..................................................................................... 9
1.6 Communication port .................................................................... 13
2. Installation ..................................................................... 14
2.1 Installation Safety Instructions .................................................... 14
2.2 Unpacking and Inspection ........................................................... 15
2.3 Installation steps for standard model .......................................... 16
2.4 Installation steps for long back up time model ............................ 16
2.5 Installation for communication software (optional) ..................... 17
3. Operation ...................................................................... 18
3.1 Operation Safety Instructions...................................................... 18
3.2 Start the UPS with mains (AC source) ........................................ 19
3.3 Start the UPS with battery (DC source) only .............................. 19
3.4 Connect loads to UPS ................................................................. 20
3.5 Charge the batteries ................................................................... 21
3.6 Discharge the batteries ............................................................... 21
3.7 Test the batteries ......................................................................... 21
3.8 Turn off the UPS with mains (AC source) ................................... 22
3.9 Turn off the UPS with battery (DC) only ...................................... 23
3.11 Operation in warning status ...................................................... 23
3.12 Operation in fault mode ............................................................. 24
3.13 Indication summary in normal operation ................................... 25
- 1 -
Page 2
4. Maintenance .................................................................. 26
4.1 Maintenance Safety Instructions ................................................. 26
4.2 Typical Trouble Shooting ............................................................. 28
4.3 Battery Maintenance ................................................................... 31
4.4 Contact the service center .......................................................... 31
5. Transport and Storage ................................................. 32
- 2 -
Page 3
1. Product Introduction
1.1 Functions description
This product is a true online double-conversion UPS (Uninterruptible
Power Supply). It provides perfect protection for critical load such as computer system. It can eliminate almost all mains power disturbances. The input AC current can be corrected to a wave following the mains voltage, so it is a high power factor system. Through the PWM control technology, the output voltage can be a pure & stable sine wave AC voltage.
When the mains input become abnormal, the controller will stop the
AC/DC and start the DC/DC section immediately to make sure the DC/AC (inverter) section can continue to work. After the mains input comeback to normal range, the DC/DC will be stopped and the AC/DC works again. So the load is always power-supplied through inverter without any interrupt if the UPS is turned on.
The UPS also provides an internal bypass way to make the load can be
powered by mains input directly when the UPS is off or failed.
The UPS have an internal charger for batteries, the charger will charge
the batteries when the mains is in a reasonable range on “bypass mode” or “line mode”.
- 3 -
Page 4
1.2 Mode description
Bypass mode
Bypass mode means that the UPS provides the power through the internal bypass way to load directly without any regulation. If the controller detects the mains is abnormal, it will shut off the output to protect the load. The bypass voltage/frequency range and default output status (on/off) could be set by communication software.
Line mode
Line mode means that the mains input is rectified/converted by the AC/DC section and then inverted to stable output by DC/AC section. In line mode, the output is clean and good to the loads. If the mains get abnormal, the UPS will transfer to battery mode without interrupt.
Battery mode
Battery mode means that the battery power goes through the DC/DC section to the inverter (DC/AC) and get a stable backup output when the mains input is not usable. If the mains input recovered, the UPS will transfer to line mode without interrupt.
Battery test mode
In this mode, the UPS will stop the AC/DC section and discharge the battery while mains input is normal. If the controller found the battery is error, it will transfer back to line mode immediately, and warning by display to see whether the battery needs to be replaced. The battery test mode could be trigged in line mode by pressing the button or by the communication command.
Fault mode
If the UPS generates some internal failure and have to stop its inverter, it will go into fault mode and alarm by display and buzzer.
In fault mode, the loads have the risk of power loss because the output will come from the bypass after UPS fault.
- 4 -
Page 5
1.3 Front panel
1.3.1 Front view
1K/1KS 2K/2KS/3K/3KS
- 5 -
Page 6
LED display
1.3.2
LED definition
There are total 6 LEDs to indicate the status of UPS.
LED No. Colour Name Function
Indicate the load level in line mode
1~3 Green
Load/Battery level LED
or bypass mode. Indicate the battery level in battery
mode.
4 Green
5 Orange
6 Red
Inverter status LED
Bypass/Batter y mode LED
Fault/Warning mode LED
- 6 -
If it is turned on constantly, it shows that the load current is supplied from utility power or battery via the inverter.
If it is turned on constantly, it shows that the UPS is in battery mode, and the load current is from battery via the inverter.
If it is flashing, it shows that the UPS is in bypass mode, and the load current is directly from the utility power.
If it is turned on constantly, it shows that the UPS is in fault mode;
If it is flashing, it shows that the UPS is in warning status.
Page 7
LED action summary
LED No.
Bypass mode Line mode Battery mode Battery test mode Fault mode Warning
: Lightened according to load level : Lightened according to battery level : Depended on the fault/warning status : Depended on the original display
: Lightened constantly : Flashing
1 2 3 4 5 6
○ ○ ● ◎ ● ◎ ★ ◇ ● □
1.3.3 Button
There is only one button for ON/OFF/Mute function on this product. The controller can distinguish the command according to the operation time deference.
(1) Button action description
Button actions are distinguished with “short-press” and “long-press”. Please refer to the following tables for the detail.
Button action type Definition
Short-press Press the button more than 0.04s and less than 0.5s
Long-press Press the button more than 2s
Invalid press Press the button more than 0.5s and less than 2s.
- 7 -
Page 8
(2) UPS response to the button
Original mode Button action UPS response
Long-press Turn on the UPS into battery mode.
Power off (cold status)
Bypass mode
Other press
Long-press Turn on the UPS into line mode.
Short-press
The internal power supply is trigged for a short time and then shutdown.
Mute the buzzer if there is a warning or alarming.
Line mode
Battery mode
Battery test mode
Fault mode
Long-press Turn into bypass mode.
Short-press Turn into battery test mode.
Long-press Turn off the UPS.
Short-press Mute the buzzer.
Long-press Turn into bypass mode.
Short-press Turn into line mode.
Long-press
Short-press Change the beep status of buzzer.
Turn into bypass mode or shutdown, dependent on the fault type.
- 8 -
Page 9
1.4 Rear panel
1K 1KS
2K 2KS
- 9 -
Page 10
3K 3KS
/ Communication port (USB or RS232) Mains input protection Mains input power cord Output socket External battery terminal block
- 10 -
Page 11
1.5 Product specification
1.5.1 Model description
This manual is applicable to the following models:
Model
Power
name
rating
PowerWalker
VFI 1K
PowerWalker
VFI 1KS
1000VA/700W 2000VA/1400W 3000VA/2100W
PowerWalker
VFI 2K
PowerWalker
VFI 2KS
PowerWalker
VFI 3K
PowerWalker
VFI 3KS
Note: The model names without “S” represent standard model with internal
battery. The model names with “S” represent long backup time model with external battery.
1.5.2 Environment specification
Model name
Operating Temperature
Storage Temperature
Altitude
Relative Humidity
Noise Level <45dB @ 1 meter from front panel
PowerWalker
VFI 1K
PowerWalker
VFI 1KS
PowerWalker
VFI 2K
<1000m @ full load <2000m @ 90%load <3000m @ 80%load <4000m @ 70%load
PowerWalker
0-40°C
0-40°C
<95%
VFI 2KS
PowerWalker
VFI 3K
PowerWalker
VFI 3KS
1.5.3 Mechanical Specification
Model name
Dimension
(W×H×D)
(mm)
Weight
(Kg)
PowerWalker
VFI 1K
9.8 5.2 20 10.8 24.6 10.8
PowerWalker
VFI 1KS
144×220×345 190×318×369 190×318×369
PowerWalker
VFI 2K
PowerWalker
VFI 2KS
PowerWalker
VFI 3K
PowerWalker
VFI 3KS
- 11 -
Page 12
1.5.4 Electrical Specification
Model name
Power 1000VA/700W 2000VA/1400W 3000VA/2100W
Input
Current (Max.)
Voltage Range
Frequency Range
Input Power Factor
Output
Voltage 208/220/230/240VAC (sine-wave)
Frequency
THD
Voltage Regulation
Overload Capacity
Efficiency
PowerWalker
VFI 1K
PowerWalker
VFI 1KS
5A 6A 10A 11A 15A 16A
176~276VAC @ full load (110~276VAC @ half load)
46 ~ 54Hz @ 50Hz system / 56 ~ 64Hz @ 60Hz system
PowerWalker
VFI 2K
Synchronizing mains input @ line mode
50/60Hz ± 0.2 Hz @ battery mode
Line mode: 60s @ 100%~130%; 1s @ > 130%
Battery mode: 10s @ 100%~130%; 1s @ >130%
PowerWalker
VFI 2KS
0.98 @ full load
4% ( Linear load )
± 2%
PowerWalker
VFI 3K
PowerWalker
VFI 3KS
Line Mode 86%
Battery Mode 80% 83% 83%
Battery & Charger @ 25℃℃℃
Total battery rating voltage 24VDC 48VDC 72VDC
Backup Time (Half Load) >9min >9min >9min
Recharge Time (to 90%) 5Hours 5Hours 5Hours
Charging Current (Max.) 1A 4A 1A 4A 1A 4A
Discharging Current (Max.) 44A 42A 42A
Rated Charging Voltage 27.3Vdc 54.6Vdc 81.9Vdc
- 12 -
Page 13
1.5.5 Standards
* Safety
IEC/EN 62040-1-1
* EMI
Conducted Emission........................:IEC/EN 62040-2 Category C1
Radiated Emission...........................:IEC/EN 62040-2 Category C1
Harmonic Current.............................:IEC/EN 61000-3-2 (Input Current16A)
Voltage Fluctuation and Flicker........:IEC/EN 61000-3-3 (Input Current16A)
*EMS
ESD.................................................... :IEC/EN 61000-4-2 Level 4
RS.......................................................:IEC/EN 61000-4-3 Level 3
EFT..................................................... :IEC/EN 61000-4-4 Level 4
SURGE.............................................. :IEC/EN 61000-4-5 Level 4
CS...................................................... :IEC/EN 61000-4-6 Level 3
Power-frequency Magnetic field......... :IEC/EN 61000-4-8 Level 3
Low Frequency Signals.......................:IEC/EN 61000-2-2
1.6 Communication port
The communication port is for the monitoring software. There are 2 options: RS232 or USB. There is only one option can work in the same time and same product.
RS232 (optional)
Pin assignment and description of DB-9 connector:
Pin# Definition
2 TXD (output) 3 RXD (input) 5 GND
USB (optional)
The USB port is compliance with USB 1.1 protocol for its communication software.
- 13 -
Page 14
2. Installation
2.1 Installation Safety Instructions
You must read the following safety instructions before installation!
Installation Personnel
This product must be installed only by qualified or professional personnel accord to safety instructions!
Installation Environment
Do not install and operate the UPS when water condensation happen which may occur if the UPS is moved directly from a cold to a warm environment. The UPS must be absolutely dry before being installed and operated. Please allow an acclimatization time of at least 2 hours. Otherwise there is hazard of electric shock!
Do not install the UPS in the environment where it is damp or would be exposed to direct sunlight or near heat. Ensure the UPS is far away from water, inflammable gas and corrosive agents.
Do not block air vents in the housing of UPS. The UPS must be installed in a location with good ventilation. Ensure enough space on each side for ventilation.
- 14 -
Page 15
Wiring & Grounding
Installation and Wiring must be performed in accordance with the
local electrical laws and regulations.
The UPS must be securely grounded. If there are external UPS battery cabinets, please make sure the battery cabinets have the equipotential earth bonding to the UPS main cabinet.
An appropriate switch device as backup protection for over-current or short-circuit should be provided in the input utility.
Battery
Strictly follow the principle of “same voltage, same type” when
paralleling multi battery packs.
DC breaker or fuse must be used as a protection device between the external battery pack and the UPS. The spec of protection must be matched to the UPS specification.
2.2 Unpacking and Inspection
2.2.1 Unpack the package and check the contents. The shipped package contains:
1 UPS 1 user manual
2.2.2 Inspect the appearance of the UPS to see if there is any damage during transportation. Do not turn on the unit and notify the dealer immediately if there is any damage or lack of some parts.
- 15 -
Page 16
2.3 Installation steps for standard model
1) Make sure the wire / circuit breaker / socket are enough for the current
rating of UPS to avoid the hazards of electric shock and fire.
2) Make sure the mains switch in the building is cut off.
3) Make sure the UPS is not be turned on before wiring operation.
4) Turn off all load switches first before connecting the load to the UPS.
5) Make sure the protective earth ground is correct.
6) Connect the loads to the UPS through the outlet sockets.
7) Connect the input power cord of UPS to mains.
2.4 Installation steps for long back up time model
1) Make sure the wire / circuit breaker / socket are enough for the power
rating of UPS to avoid the hazards of electric shock and fire.
2) Make sure the mains switch in the building is cut off.
3) Turn off all load switches first before connecting the load to the UPS.
4) Make sure the protective earth ground is correct.
5) Install the external battery as following:
a) Warning: Make sure the mains input have been cut off. b) Switch off the battery breaker if there is a battery breaker. c) Remove the cover of external battery terminal of UPS. d) Warning: Pay highly attention to the rating battery voltage marked
on the rear panel, the connection with wrong battery voltage may cause permanent damage of the UPS.
e) Warning: Pay highly attention to the polarity marking on external
battery terminal block, and make sure the correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
- 16 -
Page 17
f) Prepare the external battery cable that should be able to carry the
current of >50A, the cross section area should be greater than 5.26 mm2. It is recommended to use 8 AWG wire or thicker for safety and efficiency. And battery wire color is recommended as following:
++
Red wire Yellow/Green wire Black wire
g) Connect the GND pole of external battery terminal block on the rear
panel of UPS to the earth point of battery pack. Note: Always connect the earth wire first!
h) Connect the Positive (+) pole of external battery terminal block on
the rear panel of UPS to the Positive polarity of battery pack;
i) Connect the Negative (-) pole of external battery terminal block on
the rear panel of UPS to the Negative polarity of battery pack.
j) Check the wiring and voltage of the battery pack. Make sure the
polarity and voltage is correct, and the wires are fastened.
k) Install the terminal block cover on the rear panel of the UPS.
6) Connect the loads to the UPS through the outlet sockets.
7) Connect the input power cord of UPS to mains
GND
----
2.5 Installation for communication software (optional)
1) Connect the communication cable between UPS and PC. If
the port is RS232, please lock the secure screw both on UPS and PC after connection. If the port is USB, it has Plug and Play function.
2) Please refer to the guide manual of software or contact the
service center for installation and operation of management (monitoring) software.
- 17 -
Page 18
3. Operation
3.1 Operation Safety Instructions
You must read the following safety instructions before operation!
Operation personnel
Laymen can operate this product.
Operation warning
Do not disconnect the earth conducting wire on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and all connected loads.
Do not try to disassemble the original part of the UPS before turn off and disconnect it from the mains power & external battery.
The UPS output socket may be electrically lived even if the UPS system is not connected to the mains power source.
Do not make any liquid and foreign objects enter the UPS.
Turn off the mains input switch and external battery switch
immediately at any accident of electric shock and fire related to the UPS.
- 18 -
Page 19
3.2 Start the UPS with mains (AC source)
1) If the UPS is a long back up time model, with external battery banks, please switch on the battery breaker first;
2) If the wiring is correct, turn on the mains breaker in your building. Then the power supply inside the UPS will be started automatically, the fans will run, and the panel will display with bypass mode.
Note 1: If the UPS have been set to enable the bypass output, the output socket will have the voltage directly from mains after you turn on the input breaker.
Note 2: In bypass mode, the load is not protected. You should go on to the next step to turn on the UPS for protecting your load.
3) Press the button of the UPS front panel continuously for more than 2 seconds. The buzzer will beep once, and all the LEDs will be lightened, and then black out one by one. After a few seconds of self-diagnoses, the UPS will be turned on to the normal mode (line mode) and output the spec voltage.
4) After the UPS is turned on to line mode normally, the Inverter LED will be on, the Bypass/Battery LED will be off. The Load/Battery level LEDs will be lightened according to the load capacity. There is no beep of buzzer.
Note: If the UPS is shutdown in battery mode automatically, when the mains power returned to the input, the UPS will start up and switch to line mode automatically.
3.3 Start the UPS with battery (DC source) only
This UPS can be started with DC source (battery) without AC source.
1) If the UPS is a long back up time model with external battery banks, please switch on the battery breaker first.
2) Press the button of the UPS front panel continuously for more than 2 seconds. The buzzer will beep once, and all the LEDs will be lightened, and then black out one by one. After a few seconds of self-diagnoses,
- 19 -
Page 20
the UPS will be turned on to the battery mode and output the spec voltage.
3) After the UPS is turned on to battery mode normally, both the Inverter LED and Bypass/Battery LED will be on. The Load/Battery level LEDs will be lightened according to the battery capacity. The buzzer will beep according to the battery level.
3.4 Connect loads to UPS
After the UPS is turned on, you can switch on the loads.
1) It is recommended to switch on the load one by one. The Load/Battery level LED will indicate the load capacity in line mode.
2) If it is necessary to connect the inductance load such as a printer to the UPS, the start-up power should be considered for calculating the capacity of the UPS, because the power consumption is too big when this kind of load is started.
3) If the UPS is overloaded, all the load level indication LEDs will flash and the buzzer will beep twice every second for alarming.
4) If the UPS is overloaded, some loads must be switched off or decreased immediately. It is recommend that the total loads connected to the UPS had better be less than 80% of its nominal power capacity to prevent the overload happen at the transient time, and it will make your system more safe.
5) If the overload time is over spec in line mode, the UPS will transfer to bypass, after the overload disappears, it will return to line mode. If the overload time is over spec in battery mode, the UPS will cut off the output and then shutdown according battery level.
- 20 -
Page 21
3.5 Charge the batteries
1) After the UPS is connected to normal mains, the charger will work and charge the batteries automatically in bypass mode or line mode.
2) Suggest charging the batteries for 10 hours before use. Otherwise the backup time may be less than the standard value.
3.6 Discharge the batteries
1) When the UPS is in battery mode, the buzzer will beep according to different battery level. If the battery voltage drops to the alarming level, the buzzer will beep hurry (once every sec) to remind the user that the battery is low level and the UPS will be shutdown automatically soon. The user could switch off some non-critical loads to avoid the shutdown alarming and prolong the backup time. If have no more load to be switched off at that time, you have to shutdown all loads as soon as possible to protect the loads or save data. Otherwise there is the risk of data loss or load failure.
2) In battery mode if the user don’t like the buzzer noise, the beep could be muted by short-press the button.
3) The backup time of the long backup time model is dependent on the external battery capacity except the load capacity mainly.
4) The backup time may vary from different environment temperature and
load type.
3.7 Test the batteries
1) If you need to check the battery level or aging status when the UPS is running on normal mode (line mode), you could short-press the button to let the UPS transfer to battery test mode.
2) To make the system more reliable, the UPS will perform the battery test
- 21 -
Page 22
automatically periodically. The default period is once per week.
3) The battery test could be performed by the command from monitoring software through the communication port.
4) If the UPS enter the battery test mode, the display and buzzer indication will be same as the battery mode except that the Bypass/Battery LED is flashing. So you can check the battery level at this mode.
3.8 Turn off the UPS with mains (AC source)
1) Firstly turn off the UPS (inverter) to bypass mode, please press the button
continuously for more than 2 seconds.
2) After you press the button, the buzzer will beep once. All the LEDs will be lightened, and then black out one by one. Then the panel will display the bypass mode.
Note 1: If the UPS have been set to enable the bypass output, the output socket will have voltage from mains directly after you turn off the UPS (inverter) to bypass mode.
Note 2: Because there is risk of power loss for the loads if you turn off the UPS to bypass mode, please make sure the loads are prepared for your operation.
3) If you want to turn off the output of UPS and shut down the UPS completely, you have to cut off the mains input of UPS.
Note: please make sure all the loads are prepared or turned off for your operation before you shutdown the UPS system.
4) After you cut off the mains input of UPS to shut down, all the LEDs will be lightened, and then black out one by one. Finally all the LEDs will be lightened to indicate the UPS is saving data to the memory. After the saving process, the UPS will be shutdown completely.
- 22 -
Page 23
3.9 Turn off the UPS with battery (DC) only
1) To turn off the UPS in battery mode, please press the button continuously for more than 2 seconds.
2) After you press the button, the buzzer will beep once. All the LEDs will be lightened, and then black out one by one. Finally all the LEDs will be lightened to indicate the UPS is saving data to the memory. After the saving process, the UPS will be shutdown completely.
Note: please make sure all the loads are prepared or turned off for your operation before you shutdown the UPS system.
3.10 Mute the buzzer
1) To mute the buzzer, please short-press the button. If you short-press it again after the buzzer muted, the beep will be returned.
2) It is not anytime the buzzer can be muted. If it is in warning/battery­low/overload, the buzzer can’t be muted unless the trouble is solved.
3) If it is in fault mode, short-press the button could transfer the continuous beep to once-every-second.
3.11 Operation in warning status
1) In case the Fault/Warning LED is flashing and the buzzer is beeping once every second, it shows that the UPS system have some troubles, please check the troubleshooting table in chapter 4 to find out what happen to the UPS.
2) If the warning happens, the UPS will continue work in the original mode,
the operation will not be interrupted. If the error is corrected, the warning alarm will stop.
- 23 -
Page 24
3.12 Operation in fault mode
1) In case the Fault/Warning LED is lightened constantly and the buzzer beep continuously, it shows that there is must a fatal error happen to the UPS and it is operating in abnormal mode.
2) If fault happens, please notes and record what the display shows, the display information is very important for the trouble shooing. Please refer to the troubleshooting table in chapter 4 for detail.
3) Please check your loads, wiring, ventilation, mains, battery and so on after the fault happens. Don’t try to turn on the UPS again before find out the reason. If the trouble can’t be shoot, please contact the distributor or service people.
4) In the emergency case, please cut off the connection from mains /
external battery / output immediately to avoid more risk or danger.
- 24 -
Page 25
3.13 Indication summary in normal operation
Operatin
g mode
Line
mode
Bypass
mode
Battery
mode
Battery
test mode
Load level
0~50% 50~75% 75~100% >100%
No output
0~50% 50~75% 75~100% >100% 0~100% 0~25% 0~100% 25~50% 0~100% 50~75% 0~100% 75~100% >100% 0~100% 0~25% 0~100% 25~50% 0~100% 50~75% 0~100% 75~100% >100%
Battery
level
LED
1 2 3 4 5 6
● ★ ★ ★ ●
● ★ ★ ★ ★
● □ ● ★
★ □
None
None
None Every 0.5 sec
*
★ ★ ★ ★
Buzzer beep
once
Every 2 min
Every 2 min Every 2 min Every 2 min Every 0.5 sec Every sec Every 4 sec Every 4 sec Every 4 sec Every 0.5 sec Every sec Every 4 sec Every 4 sec Every 4 sec Every 0.5 sec
: Lightened constantly : Flash once every 4 seconds. : Flash once every second : Depended on the original display
*Note: In this case, it indicates there is no output in bypass mode. The causes may be that the mains input is out of range or the output is set to disable in bypass mode. Check the mains input, check the bypass output setting, or turn on the UPS.
- 25 -
Page 26
4. Maintenance
4.1 Maintenance Safety Instructions
You must read the following safety instructions before maintenance!
Maintenance Personnel
This product must be maintained only by qualified professional personnel accord to safety instructions!
Risk of electric shock
No matter the UPS is connected to the utility power or not, the output may have electricity. The parts (battery, capacitor) inside the unit may still have hazardous voltage after turning off the UPS.
Make sure to disconnect the batteries before carrying out any kind of
maintenance or repair. In this product, the battery is dangerous.
Verify that no voltage between the battery terminals and the ground is present before maintenance or repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground.
Verify that no hazardous voltage exists in the energy storage
capacitor before maintenance or repair.
- 26 -
Page 27
Remove all jewellery, wristwatches, rings and other metal personal goods before maintenance or repair.
Only use tools with insulated grips and handles when maintaining or repairing.
Battery
Only qualified personnel can replace the batteries!
Do not short the positive and negative of the battery electrode. Batteries have a high short-circuit current and may cause a risk of serious shock or fire.
When changing batteries, replace with the same quantity and the same type of batteries.
Do not attempt to dispose of batteries by burning them. It could cause explosion. The batteries must be rightly deposed according to local regulation.
Do not open or destroy batteries. Effluent electrolyte can cause injury to the skin and eyes. It may be toxic.
Fuse
Please replace the fuse only by a fuse of the same type and of the
same amperage in order to avoid fire hazards.
- 27 -
Page 28
4.2 Typical Trouble Shooting
(1) Trouble shooting according to warning indication.
LED
1-3 4 5 6
: Depended on the original display ☆: Flash every 4 seconds
Possible cause Action
Fan abnormal, or internal temperature is too high
I/P fuse open
Battery low abnormally or battery not connected (line mode), or battery discharged over 14 hours
Battery over voltage, or charger failed
Check the fans. Check the loads.
Check the ventilation, ambient
temperature.
Check the I/P fuse and related
power component.
Check the battery. If the UPS is
a long back up model, check
whether the external battery
protection (breaker of fuse) is
open. If the battery is damaged
or aged, replace the battery.
Check the charger output,
battery input.
: Flash every second
Note 1: when the UPS warning, the red Fault/Warning LED will flash, and the
buzzer will beep once every second.
Note 2: When the UPS warning, the UPS is still working on the original mode
with the original display except the inverter LED maybe flash.
Note 3: If the warning can’t be shoot, please contact the distributor or service
center.
- 28 -
Page 29
(2) Trouble shooting according to fault indication
LED
1 2 3 4 5 6
Possible cause Action
Output short
circuit
Internal fault
(inverter failed)
Internal fault (inverter relay
short)
Overload
Internal over
temperature
Remove all the loads. Turn off the UPS. Check whether the output of UPS and loads is short circuit. Make sure the short circuit is removed, and the UPS has no internal faults before turning on again.
Contact the distributor or service center.
Contact the distributor or service center.
Check the loads and remove some non-critical loads.
Check whether some loads are failed.
Check whether the UPS is overloaded, the air vents are blocked, and the ambient
temperature is over 40. If the overload or block is
removed, please make the UPS cool down for 10 minutes before turning on again.
It is not recommended the UPS is operated at the ambient
temperature of over 40.
: Lightened constantly
Internal fault (bus voltage
fault)
Other internal
fault
Contact the distributor or service center.
Contact the distributor or service center.
- 29 -
Page 30
Note 1: when the UPS failed, the red Fault/Warning LED will be lightened
constantly, and the buzzer will beep continuously.
Note 2: When the UPS is fault, it will stop the power conversion of mains or
battery, the original Load/Battery level LED will code the fault cause.
Note 3: If the fault can’t be shoot, please contact the distributor or service
center.
(3) Trouble shooting in else cases.
Problem Possible cause Action
Battery discharging time diminishes
The UPS cannot power on after pressing the button
Battery not yet been fully charged.
UPS overloaded.
Battery aged. Replace the batteries.
Charger failed
The button is pressed too briefly.
Battery is not connected or battery voltage is too low, or Charger failed.
UPS fault.
Keep UPS connected to utility power persistently for more than 10 hours to recharge the batteries.
Check the loads and remove some non-critical loads.
Check the charger. Contact the distributor or service center.
Press the button continuously for more than 2 seconds.
Check the charger and battery.
Contact the distributor or service center.
- 30 -
Page 31
4.3 Battery Maintenance
1) The battery used for standard models are valve regulated sealed lead-acid maintenance free battery. It should be charged regularly in order to maximize the expected life of the battery. When being connected to the utility power, whether the UPS is turned on or not, the UPS keeps charging the batteries and also offers the protective function of overcharging and over-discharging.
2) The UPS should be charged once every 4 to 6 months if it has not been used for a long time.
3) In the regions of hot climates, the battery should be charged/ discharged every 2 months. The charging time should be >12 hours.
4) In normal conditions, the battery life lasts 3 to 5 years. If the battery is found in bad condition, earlier replacement should be made.
5) Do not replace the battery individually. All batteries should be replaced at the same time following the instructions of the supplier.
4.4 Contact the service center
If contact the service center for trouble shooting, please provide the information as following:
1) Model name of product.
2) Serial number of product.
3) The date when the problem found.
4) LED display status.
5) Buzzer alarm status.
6) Mains power condition
7) Load type and capacity.
8) Environment temperature, ventilation status.
9) The information (battery capacity, quantity) of the external battery pack
if the UPS is long back up model.
10) Other information for complete description of the problem.
- 31 -
Page 32
5. Transport and Storage
5.1 Please transport the UPS only in the original packaging.
5.2 The UPS must be stored in the room where it is ventilated and dry.
- 32 -