Please comply with all warnings and operating instructions in this manual strictly. Save this
manual properly and read carefully the following instructions before installing the unit. Do not
operate this unit before reading through all safety information and operating instructions
carefully.
1-1. Transportation
Please transport the UPS system only in the original package to protect against shock
and impact.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please
allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by any individuals with no previous experience.
Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked (or UL-marked for 100/110/115/120/127 VAC
models) mains cable (e.g. the mains cable of your computer) to connect the UPS
system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked (or UL-marked for 100/110/115/120/127 VAC
models) power cables to connect the loads to the UPS system.
When installing the equipment, it should ensure that the sum of the leakage current
of the UPS and the connected devices does not exceed 3.5mA.
Temperature Rating - Units are considered acceptable for use in a maximum ambient
of 40°C (104°F).
For Pluggable Equipment - The socket-outlet shall be installed near the equipment
and shall be easily accessible.
1-4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not
connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
1
1-5. Maintenance, service and faults
Manufacture
Type
Rated
Toplite (Guangzhou)
Technology Battery Co Ltd
(MH29104)
NPW45-12
12 V dc, 9.0 Ah
UXW460-12
12 V dc, 9.0 Ah
NPW36-12
12 V dc, 7.2 Ah
UXW360-12
12 V dc, 7.2 Ah
NPW45-12 FR
12 V dc, 7.0 Ah
UXW460-12/FR
12 V dc, 7.0 Ah
NPW36-12 FR
12 V dc, 7.0 Ah
CSB Battery Co Ltd
(MH14533)
UXW360-12/FR
12 V dc, 7.0 Ah
GP1272
12 V dc, 7.2 Ah
UPS 12460 F2
12 V dc, 9.0 Ah
UPS 12360 6
12 V dc, 6.5 Ah
UPS 12360 7
12 V dc, 6.5 Ah
HR 1234W
12 V dc, 8.5 Ah
HR 1234W FR
12 V dc, 8.5 Ah
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the
battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals
of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, please verify that no voltage is present!
Caution - Do not dispose of batteries in a fire. The batteries may explode.
Caution - Do not open or mutilate batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary when
working with batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source and load prior to installing or maintaining the
battery.
f) Remove battery grounds during installation and maintenance to reduce
likelihood of shock. Remove the connection from ground if any part of the
battery is determined to be grounded.
When changing batteries, install the same number and same type of batteries or
battery packs.
2
Yuasa Battery (Guangdong)
Co Ltd (MH29616)
NPW45-12
12 V dc, 8.0 Ah
NPW45-12FR
12 V dc, 8.0 Ah
For UPS with internally mounted battery
a) Instructions shall carry sufficient information to enable the replacement of the
battery with a suitable manufacturer and catalogue number.
b) Safety instructions to allow access by Service Personnel shall be stated in the
installation/service handbook.
c) If batteries are to be installed by Service Personnel, instructions for
interconnections, including terminal torque, shall be provided.
Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.
WARNING: This is a category C2 UPS product. In a residential environment, this
product may cause radio interference, in which case the user many be required to
take additional measures. (only for 220/230/240 VAC system)
Only for 110/120 VAC system:
NOTE: This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his own expense.
WARNING: Changes or modifications not expressly approved by the party
responsible for compliance could void the user's authority to operate the equipment.
3
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use.
2-1. Rear panel view
Tower Models
IEC Type
1K/1.5K 2K 3K
NEMA Type
1K/1.5K 2K 3K
4
RT Models
EMI/RFI
Filters
Battery
Charger
Battery
DC-to-DC
Converter
Inverter
Rectifier
/PFC
Input
Output
TheUPSiscomposedofmainsinput,
EMI/RFIfilters,rectifier/PFC,
inverter,batterycharger,DC-to-DC
converter,battery,dynamicbypassand
UPSoutput.
Dynamic
Bypass
1K/
1.5K
2K
3K
IEC Type NEMA Type
1. Programmable outlets: connect to non-critical loads.
2. Output receptacles: connect to mission-critical loads.
3. AC input
4. Network/Fax/Modem surge protection
5. USB communication port
6. RS-232 communication port
7. SNMP intelligent slot
8. Emergency power off function connector (EPO)
9. External battery connection
2-2. Operating principle
The operating principle of the UPS is shown as below
The UPS is composed of mains input, EMI/RFI filters, rectifier/PFC, inverter, battery charger,
DC-to-DC converter, battery, dynamic bypass and UPS output.
5
2-3. Install the UPS (Only for RT Models)
Step 1
Step 2
Step 3
Remove front panel.
Connect the AC input and
re-connect battery wires.
Put the front panel back to the
unit.
Step 1
Step 2
Step 3
For safety consideration, the UPS is shipped out from factory without connecting battery wires.
Before install the UPS, please follow below steps to re-connect battery wires first.
This UPS can be either displayed on the desk or mounted in the 19” rack chassis. Please choose
proper installation to position this UPS.
Rack-mount Installation
Step 1 Step 2
Tower Installation
2-4. Setup the UPS
Before installing the UPS, please read below to select proper location to install UPS.
1. UPS should be placed on the flat and clean surface. Place it in an area away from vibration,
dust, humidity, high temperature, flammable liquids, gases, corrosive and conductive
contaminants. Install the UPS indoors in a clean environment, where it is away from
window and door. Maintain minimum clearance of 100mm in the bottom of the UPS to
avoid dust and high temperature.
6
2. Maintain an ambient temperature range of 0ºC to 45ºC for UPS optimal operation. For
every 5ºC above 45ºC, the UPS will derate 12% of nominal capacity at full load. The
highest working temperature requirement for UPS operation is 50ºC.
3. It’s required to maintain maximum altitude of 1000m to keep UPS normal operation at full
load UPS. If it’s used in high altitude area, please reduce connected load. Altitude derating
power with connected loads for UPS normal operation is listed as below:
4. Place UPS:
It’s equipped with fan for cooling. Therefore, place the UPS in a
well-ventilated area. It’s required to maintain minimum clearance of 100mm in the
front of the UPS and 300mm in the back and two sides of the UPS for heat dissipation and
easy-maintenance.
5. Connect to External Battery Pack
When connecting external battery packs, please be sure to connect polarity correctly. Connect
positive pole of battery pack to positive pole of external battery connector in UPS and negative
pole of battery pack to negative pole of external battery connector in UPS. Polarity
misconnection will cause UPS internal fault. It’s recommended to add one breaker between
positive pole of battery pack and positive pole of external battery connector in UPS to prevent
damage to battery packs from internal fault.
The required specification of breaker: voltage ≧ 1.25 x battery voltage/set; current ≧ 50A
Please choose battery size and connected numbers according to backup time requirement and
UPS specifications. To extend battery lifecycle, it’s recommended to use them in the
temperature range of 15ºC to 25ºC.
7