Low Frequency Signals.............:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application
in the second environment-installation restrictions or additional
measures may be needed to prevent disturbances.
5
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is
advisable to familiarize yourself with them and understand their
meaning:
6
3. Introduction
3.1 System and model description
This Online Series is an uninterruptible power supply incorporating
double-conversion technology. It provides perfect protection
specifically for computer equipment, communication systems to
computerized instruments.
Its true online double-conversion design eliminates all mains power
disturbances. A rectifier converts the alternating current from the
utility power to direct current. This direct current powers the inverter.
On the basis of this DC voltage, the inverter generates a pure
sinusoidal AC voltage, which is constantly powering the loads.
Computers and Peripherals are thus powered entirely by the UPS. In
the event of power failure, the maintenance-free batteries power the
inverter.
This manual is applicable to the PowerWalker VFI 10000-20000 TP
3/1 models and PowerWalker VFI 10000TCP 3/1 model.
The tower 3-phase series UPS providing outstanding performance
and reliability, the UPS’s unique benefits include:
Online UPS design with pure sine wave output.
True online double-conversion technology with high power density,
utility frequency independence, and generator compatibility.
Overall high efficiency > 93%, saving the operating cost.
True three-phase power factor correction and high input power
factor (PF>0.99). Save the installation cost and reduce the
pollution back feed into upstream power system.
7
High output power factor (0.9), to adapt more type load.
Intelligent Battery Management technology that uses advanced
battery management to increase battery service life, optimize
recharge time.
Selectable High Efficiency mode (ECO mode) or CVCF mode
operation.
Combo input (single phase or three phase) auto detection
Back-feed protection
Start-on-battery capability for powering up the UPS even if utility
power is not available.
Standard communication options: one RS-232 communication port,
one USB communication port.
Optional connectivity cards with enhanced communication
capabilities.
Remote shutdown control through the Remote Power-off (RPO)
port.
For tower PowerWalker VFI 10000-20000 TP 3/1, Maintenances are
simplified by allowing the safe replacement of batteries without
powering down the UPS. But PowerWalker VFI 10000TCP 3/1 model
have no this function.
N+X parallel redundancy to increase the reliability and flexibility.
The max parallel number is 4.
User-friendly LCD display and LED indicators.
For tower PowerWalker VFI 10000-20000 TP 3/1, easily battery
exchange or extension and available to extend the backup time. But
PowerWalker VFI 10000TCP 3/1 model have no this function.
The appearance of tower 3-phase series
Refers to Fig. 3-1
8
PowerWalker VFI 10000 TP 3/1 REAR VIEW
PowerWalker VFI 20000 TP 3/1 REAR VIEW
9
Intelligent Slot
Maintenance and Output
Parallel Port
(Optional)
EPO、、RS232 USB
Fan
Input Breaker
External Battery
AS400
IEC Connector
Switch Cover
Terminal Blocks
Cover
PowerWalker VFI 10000TCP 3/1 REAR VIEW
Fig. 3-1 the rear view of the tower 3-phase series UPS
3.2 Product Specification and Performance
1) General Specification
Model
PowerWalker VFI
10000TP 3/1
Power Rating 10KVA/9KW 20KVA/18KW 10KVA/9KW
Frequency (Hz)
PowerWalker VFI
20000TP 3/1
50/60
PowerWalker VFI
10000TCP 3/1
Battery Voltage
Input
Voltage (110-276)VAC (Depends on Load Level)
Current L1/L2/L3:23A MAX L1/L2/L3:46A MAX L1/L2/L3:23A MAX
288VDC 240VDC
10
PowerWalker VFI
PowerWalker VFI
PowerWalker VFI
Current
Voltage
Output
(WxDxH) mm
Net Weight (kg)
Current
Dimension
2) Electrical Performance
Model Voltage Frequency Power Factor
10000TP 3/1
20000TP 3/1
10000TCP 3/1
*:If
output voltage be set 200V, output power will derating to 90% of power
rating
45A/48.1A/45.5A/4
Three-phase 50/60 Hz±10%
43A MAX 86A MAX 51.8A MAX
200VAC/208VAC/220VAC/230VAC/ 240VAC*
90A/96.2A/90.9A/8
3.5A/41.7A
350x650x890 260*550*708
127 188 85
Input
7.0A/83.3A
45A/48.1A/45.5A/4
3.5A/41.7A
>0.99(@Full load)
11
Output
Voltage
Regulation
±1% 0.9 lag
Power
Factor
Frequency
tolerance.
Synchronized
50/60Hz±10%
in Line mode
(AC mode)
±0.1% of
normal
frequency in
Battery mode
Distortion Overload capacity
100%-110% load
transfers to Bypass
mode after 5
minutes
THD<2%
Full load
(Linear
Load)/
<5% for
reference
non-linear
load
110%-130% load
transfers to Bypass
mode after 1
minutes
130%-150% load
transfers to Bypass
mode after 10
second
>150% load
transfers to Bypass
mode after 2 second
Current
crest ratio
3) Operating Environment
Temperature Humidity Altitude Storage temperature
0°C-45°C
<95% <1000m
-15°C-50°C
3:1
Note: if the UPS is installed or used in a place where the altitude is
above than 1000m, the output power must be derated in use, please
refer to the following:
The system may be installed and wired only by qualified
electricians in accordance with applicable safety regulations!
4.1 Unpacking and Inspection
1. Moving to the installation site
The tower 3-phase series UPS has wheels making it easy to move the
UPS to the installation site after it has been unpacked. However, if the
receiving area is far from the installation site, we recommend you to
move the UPS by using a pallet jack or a lifter before you start to
unpack the UPS.
2. Unpacking and inspection
1) At the installation site, the utmost care shall be taken when
removing the packaging in order to avoid damaging the equipment.
Check all packaging materials to ensure that no items are missing.
The shipping package contains:
● A UPS
● A user manual
● A communication cable
● Parallel port cover plate
13
Remove the packaging following the sequence illustrated in Fig. 4-1 to
Fig. 4-4. (only for PowerWalker VFI 10000-20000 TP 3/1)
Tools kit
Lifter
Scissors
Phillips screwdriver
Wrench
Fig. 4-1 Unpacking-step1 Fig. 4-2 Unpacking-step2
14
Fig. 4-3 Unpacking-step3 Fig. 4-4 Unpacking-step4
The shipping materials are recyclable. After unpacking,
save them for later use or dispose of them appropriately.
2) Inspect the appearance of the UPS to see if there is any damage
during transportation. Do not turn on the unit and notify the carrier
and dealer immediately if there is any damage or lacking of some
parts.
15
4.2 Input and Output Power Cords and Protective
Earth Ground Installation
1. Notes for installation
1) The UPS must be installed in a location with good ventilation, far
away from water, inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not
blocked. Allow at least 0.5m of space on each side.
3) Condensation to water drops may occur if the UPS is unpacked in a
very low temperature environment. In this case it is necessary to
wait until the UPS is fully dried inside out before proceeding
installation and use. Otherwise there are hazards of electric shock.
4) Once the installation is completed, the side mounting brackets
(used in shipping)shall be fixed back to ensure the stability of the
UPS enclosure. If impossible, additional stability can be added by
anchoring the mounting brackets to the floor with M8 bolts. See Fig.
4-5. (only for PowerWalker VFI 10000-20000 TP 3/1)
Fig. 4-5 Additional stability
2. Installation
Installation and wiring must be performed in accordance with the
local electric code and the following instructions by professional
personnel.
16
For safety, please cut off the mains power switch before installation.
1) Open the terminal block cover located on the rear panel of the
UPS, please refer to the appearance diagram.
2) For tower PowerWalker VFI 10000TCP 3/1 UPS, it is
recommended to select the UL1015 8AWG(10mm2) wire or other
insulated wire which complies with AWG Standard for the UPS
input and output wirings.
3) For PowerWalker VFI 20000TP 3/1 UPS, it is recommended to
select the UL1015 6AWG(25mm2) wire or other insulated wire
which complies with AWG Standard for the UPS input and output
wirings.
Note: Do not use the wall receptacle as the input power source
for the UPS, as its rated current is less than the UPS’s
maximum input current. Otherwise the receptacle may be
burned and destroyed.
4) Connect the input and output wires to the corresponding input
and output terminals according to the following diagram.
Note: you must make sure that the input and output wires and
the input and output terminals are connected tightly.
5) The protective earth ground wire refers to the wire connection
between the equipment which consumes electric equipment and
the ground wire. The wire diameter of protective earth ground
wire should be at least as above mentioned for each model and
green wire or green wire with yellow ribbon wire is used.
6) After having completed the installation, make sure the wiring is
correct.
7) Please install the output breaker between the output terminal
and the load, and the breaker should with leakage current
protective function if necessary.
17
8) To connect the load with the UPS, please turn off all the loads
first, then perform the connection and finally turn on the loads
one by one.
9) No matter the UPS is connected to the utility power or not, the
output of the UPS may have electricity. The parts inside the unit
may still have hazardous voltage after turning off the UPS. To
make the UPS have no output, power off the UPS, and then
disconnect the utility power supply.
10) Suggest charging the batteries for 8 hours before use. After
connection, turn the M1/M2/N input breaker (for PowerWalker
VFI 10000-20000TP 3/1), turn the input switch (for PowerWalker
VFI 10000TCP 3/1) in the "ON" position, the UPS will charge the
batteries automatically. You can also use the UPS immediately
without charging the batteries first, but the backup time may be
less than the standard value.
11) If it is necessary to connect the inductance load such as a
monitor or a laser printer to the UPS, the start-up power should
be used for calculating the capacity of the UPS, as its start-up
power consumption is too big when it is started.
PowerWalker VFI 10000-20000TP 3/1
18