PowerWalker VFI 10000P-RT LCD User Manual

USER MANUAL
On-Line UPS
PowerWalker VFI 6000RT LCD PowerWalker VFI 6000P/RT LCD PowerWalker VFI 10000RT LCD PowerWalker VFI 10000P/RT LCD
Contents
Uninterruptible Power Supply System
1. Introduction ............................................................................................. 1
2. Safety Warnings ...................................................................................... 4
2.1 Installation .......................................................................................... 4
2.2 Operation ............................................................................................ 5
2.3 Maintenance, servicing and faults ...................................................... 6
2.4 Transport ............................................................................................ 7
2.5 Storage ............................................................................................... 7
2.6 Standards ........................................................................................... 7
3. Installation ............................................................................................... 9
3.1 Inspecting the Equipment ................................................................... 9
3.2 Unpacking the Cabinet ....................................................................... 9
3.3 UPS Rear Panel ............................................................................... 12
3.4 UPS Front Panel............................................................................... 13
3.5 Rackmount Setup ............................................................................. 14
3.6 Tower Setup ...................................................................................... 18
3.7 Installation of UPS with AC inputs .................................................... 19
4. Power cables connection & Startup ................................................... 21
4.1 Access to terminal block ................................................................... 22
4.2 Common input sources connection .................................................. 22
4.3 Separate input sources connection .................................................. 23
4.4 Frequency converter connection ...................................................... 24
4.5 UPS Initial Startup ............................................................................ 24
4.6 Parallel operation ............................................................................. 25
5. Operation ............................................................................................... 25
5.1 Display Panel.................................................................................... 31
5.2 Operating mode ................................................................................ 33
5.3 Turning on and Turning off UPS ....................................................... 36
5.4 LCD operation .................................................................................. 38
6. UPS Maintenance .................................................................................. 47
6.1 UPS and Battery Care ...................................................................... 47
6.2 Transporting the UPS ....................................................................... 47
6.3 Storing the UPS and Batteries.......................................................... 48
6.4 Testing Batteries ............................................................................... 48
6.5 Recycling the Used Battery or UPS ................................................. 49
7. Specifications ........................................................................................ 50
2
8. Troubleshooting .................................................................................... 52
8.1 Typical Alarms and Conditions ......................................................... 52
9. Communication ..................................................................................... 57
9.1 RS-232 and USB Communication Ports .......................................... 57
9.2 Network Management Card (Optional) ............................................ 59
9.3 UPS Management Software ............................................................. 59
9.4 REPO Function................................................................................. 60
1. Introduction
This Online R/T Series is an uninterruptible power supply incorporating double-conversion technology. It provides perfect protection specifically for computer equipment, communication systems to computerized instruments. It protects your sensitive electronic equipment from basic power problems such as power failures, power sags, power surges, brownout, and line noise.
Power outages can occur when you least expect them and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware causing hours of lost productivity and expensive repairs.
With the Online R/T UPS, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. The UPS can handle array--network devices flexibility that makes it the best choice for protect your LANs, servers, workstations, and other electrical equipment.
Online R/T UPS as Rack installation:
Figure 1-1: Online R/T 6K UPS
1
Figure 1-2: Online R/T 10K UPS
Online R/T UPS as Tower installation.
Figure 1-3: Online R/T 6K UPS Figure 1-4: Online R/T 10K
UPS
2
Providing outstanding performance and reliability, the UPS’s unique benefits include:
Online UPS design with pure sine wave output.  True online double-conversion technology with high power
density, utility frequency independence, and generator compatibility.
Intelligent Battery Management technology that uses advanced
battery management to increase battery service life, optimize recharge time.
Selectable High Efficiency mode of operation.  Start-on-battery capability for powering up the UPS even if
utility power is not available.
Standard communication options: one RS-232 communication
port, one USB communication port.
Optional connectivity cards with enhanced communication
capabilities.
Extended runtime with up to four Extended Battery Modules
(EBMs) per UPS.
Optional installation method Rack & Tower.  Remote shutdown control through the Remote Emergent
Power-off (REPO) port.
Maintenances are simplified by allowing the safe replacement
of batteries without powering down the UPS.
Parallel with another Online R/T UPS, max amount is 2.  Optional Rack Slider.  PDU is standard configuration with maintenance bypass
switch.
3
2. Safety Warnings
CAUTION:
Before performing the procedures in this document, read and follow the safety instructions and important regulatory information in your Safety, Environmental, and Regulatory Information document.
IMPORTANT SAFETY INSTRUCTIONS FOR EACH STEP SAVE THESE INSTRRUCTIONS.
2.1 Installation
Condensation may occur if the UPS is moved directly from a
cold to a warm environment. The UPS must be absolutely dry before being installed. Please allow an acclimatization time of at least two hours.
Do not install the UPS near water or in damp environment.  Do not install the UPS where it would be exposed to direct
sunlight or near heat.
Do not block ventilation openings in the UPS’s housing.  Place cables in such a way that no one can step on or trip over
them.
UPS has provided earthed terminal, in the final installed system
configuration, equipotent earth bonding to the external UPS battery cabinets.
An integral single emergency switching device which prevents
further supply to the load by the UPS in any operation mode should be provided in the building wiring installation.
An appropriate disconnect device as short-circuit backup
protection should be provided in the building wiring installation.
For three-phase equipment connection to an IT power system,
a four-pole device which disconnect all phase conductors and
4
the neutral conductor should be provided in the building wiring installation.
This is permanently connected equipment , it must be installed
by qualified maintenance personnel.
For permanently connected equipment: make sure that a
readily accessible disconnect device is incorporated in the building installation wiring.
To reduce the risk of fire, connect only to a circuit provided with
branch circuit overcurrent protection with an ampere rating in accordance with the IEC/EN 60934 standard or your local electrical code and have a contact air gap of at least 3 mm.
Uninterruptible power supply
output power
6K
10K
You can connect four extended battery modules to the
uninterruptible power supply.
Earthing connection is essential before connecting to the
building wiring terminal.
2-pole circuit breaker
2-pole circuit breaker
240V
40 amp
63 amp
2.2 Operation
Do not disconnect the earth conductor cable from the UPS or
the building wiring terminals in any time since this would cancel the protective earthing of the UPS system and all connected loads.
The UPS output terminal block may be electrically active even if
the UPS system is not connected to the building wiring terminal.
In order to completely disconnect the UPS, firstly press the
OFF button, and then disconnect the mains lead.
5
Ensure that no liquid or other foreign objects can enter the
UPS.
The UPS can be operated by any individual without previous
experience.
2.3 Maintenance, servicing and faults
The UPS operates with hazardous voltages. Maintenance
should be carried out only by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is
disconnected from the mains power supply (building wiring terminal), components inside the UPS are still connected to the battery which have potentially dangerous.
Before carrying out any kind of service and/or maintenance,
please disconnect the batteries. Verify that no current is present and no hazardous voltage exist in the capacitor or BUS capacitor terminals.
Batteries must be replaced only by qualified personnel.  Caution – the risk of electric shock. The battery circuit is not
isolated from the input voltage. Hazardous voltage may occur between the battery terminals and the ground. Verify that no voltage is present before servicing!
Batteries have a high short-circuit current and pose a risk of
shock. Take all precautionary measures specified as below and any other measures necessary when working with batteries:
1) Remove all jewellery, wristwatches, rings and other metal objects
2) Use only tools with insulated grips and handles.
3) When changing batteries, replace with the same quantity and the same type of batteries.
4) Do not attempt to dispose of batteries by burning them. It could cause explosion.
6
5) Do not open or destroy batteries. Effluent electrolyte can cause injury to the skin and eyes. It may be toxic.
Please replace the fuse only with the same type and of the
same amperage in order to avoid fire hazards.
Do not dismantle the UPS, except the qualified maintenance
personnel.
2.4 Transport
Please transport the UPS only in the original packaging (to
protect against shock and impact).
2.5 Storage
The UPS must be stockpiled in the room where is ventilated
and dry.
2.6 Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission.........................:IEC/EN 62040-2 Category C2
Radiated Emission............................:IEC/EN 62040-2 Category C2
*EMS
ESD................................................:IEC/EN 61000-4-2 Level 4
RS..................................................:IEC/EN 61000-4-3 Level 3
EFT................................................ :IEC/EN 61000-4-4 Level 4
SURGE......................................... :IEC/EN 61000-4-5 Level 4
CS................................................. :IEC/EN 61000-4-6 Level 3
7
Power-frequency Magnetic field.... :IEC/EN 61000-4-8 Level 3
Low Frequency Signals..................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the second environment-installation restrictions or additional measures may be needed to prevent disturbances.
8
3. Installation
This chapter explains:
Equipment inspection  Unpacking the cabinet  Checking the Accessory  UPS setup and installation  Connecting the internal battery  Connecting the EBM(Extended Battery Modules)  Installation requirements
3.1 Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
Note: Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use the UPS. Contact your service representative.
3.2 Unpacking the carton
CAUTION: If the carton unpacks in a low-temperature of
environment it may cause condensation of moisture in or on the cabinet of UPS. Do not install the UPS until the inside and outside of the cabinet is absolutely dry to prevent hazard of electric shock.
CAUTION: The cabinet is heavy. Refer following instruction to unpack and move the cabinet from packing carton.
Be careful when moving and opening the carton. The unpacking steps are shown as below:
9
Step 1:
Open the outer carton and remove the accessories out of the carton (see Figure 3-1&3-2). Online R/T 6K UPS:
Figure 3-1: Unpacking the carton of 6K UPS
Online R/T 10K UPS
Figure 3-2: Unpacking the carton of 10K UPS
10
CAUTION:
The cabinet is heavy. Lifting the cabinet out of the carton required two persons at least.
Step 2:
With one person on each side, carefully lift the cabinet out of the outer carton using the handles on the cardboard and set it on a flat, stable surface (see Figure 3-3&3-4).
Place the cabinet in a protected area that has adequate airflow and is free of humidity, flammable gas, and corrosion.
Lifting the Cabinet:
Figure 3-3: Lifting the Cabinet out of 6K UPS carton
11
Figure 3-4: Lifting the Cabinet out of 10K UPS carton
Step 3:
Discard or recycle the packaging in a responsible manner, or store
it for future use.
3.3 UPS Rear Panel
This section shows the rear panel of the Online R/T models.
6K model:
Figure 3-5: Online R/T 6K Rear Panel
12
10K model:
Figure 3-6: Online R/T 10K Rear Panel
3.4 UPS Front Panel
This section shows the front panel of the Online R/T UPS. The Online series have the same LCD panel and the same control button.
Figure 3-7: The Online R/T UPS Front Panel
13
3.5 Rack mount Setup
CAUTION:
The cabinet is heavy, so:
1) Remove the battery tray from the UPS before lifting.
2) Lifting the cabinets into the rack requires a minimum of two people.
CAUTION: Removing the batteries requiered precautions, which should be performed or supervised by personnel with knowledge of batteries . Keep unauthorized personnel away from batteries.
CAUTION: If installing an EBM(Extended Battery Module), install the EBM directly below the UPS.
3.5.1 Install the UPS and EBM (Extended Battery Modules) in
a rack:
1. Open the front panel and put it above the UPS.
Figure 3-8. Open the front panel (left: 6K Model, right: 10K Model)
2. Remove the battery protection plate:
Figure 3-9. Removing the Battery Protection Plate
14
3. Pull the battery tray out using the plastic tabs and then remove the battery tray.
Figure 3-11: Removing the Battery Tray
4. Install the PDU’s ears to the UPS
Figure 3-12. Install the PDU’s ears to the UPS
5. Select the proper holes in the rail for positioning the cabinet in
the desired location in the rack. Locate the rails at the bottom of the 3U space allocated for the each UPS and EBM.
6. Install the sliding rails in the rack, then install the UPS in the sliding rail.
15
Figure 3-13. Install the sliding rails
7. For 10K---Install the battery pack and battery protection plate, then replace the front panel.
Figure 3-14. Installing the Cabinet
8. For 6K---Replace the battery tray, and connect the internal battery connector, then replace the protection plate and the front panel.
9. If installing additional UPSs, repeat from Step 1 to Step 8 for each cabinet.
3.5.2 Installing the EBMs
Note: A little of arcing may occur when connecting an EBM to the
UPS. That is normal and not harmed. Plug the EBM cable into the UPS battery connector quickly and firmly.
16
Loading...
+ 44 hidden pages