Power Walker VFI 10000 CG PF1 User Manuals

Page 1
PowerWalker
VFI 6000 CG PF1
VFI 10000 CG PF1
User Manual
Version: 1.1
Page 2
Please comply with all warnings and operating
instructions in this manual strictly. Save this
m a n u a l pr op e r ly a n d r e a d car e f u ll y the f ol lowin g
instructions before installing the unit. Do not
operate this unit before reading through all
safety information and operating instructions
carefully.
Page 3
Table of Contents
1. SAFETY AND EMC INSTRUCTIONS ......................................................................................................................... 1
1-1. TRANSPORTATION AND STORAGE ................................................................................................................................... 1
1-2. PREPARATION ................................................................................................................................................................ 1
1-3. INSTALLATION ............................................................................................................................................................... 1
1-4.
CONNECTION WARNINGS ................................................................................................................................... 2
1-5. OPERATION ................................................................................................................................................................... 3
1-6. STANDARDS ................................................................................................................................................................... 3
2. I NSTALLATION AND OPERATION ........................................................................................................................... 4
2-1. UNPACKING AND INSPECTION ......................................................................................................................................... 4
2-2. REAR PANEL VIEW ........................................................................................................................................................ 4
2-3. SI NGLE UPS INSTALLATION ........................................................................................................................................... 5
2-4. UPS INSTALLATION FOR PARALLEL SYSTEM .................................................................................................................... 6
2-5. SOFTWARE INSTALLATION .............................................................................................................................................. 7
3. OPERATIONS .................................................................................................................................................................. 8
3-1. BUTTON OPERATI ON ...................................................................................................................................................... 8
3-2. LED INDICATORS AND LC D PANEL ................................................................................................................................. 8
3-3. AUDIBLE ALARM .......................................................................................................................................................... 10
3-4. SINGLE UPS OPERATI ON ............................................................................................................................................. 10
3-5. PARALLEL OPERATION .................................................................................................................................................. 14
3-6. ABBREVIATION MEAN ING IN LCD DISP LA Y ................................................................................................................... 15
3-7. LCD SETTING ............................................................................................................................................................. 16
3-8. OPERATING MODE/STATUS DESCRIPTION .................................................................................................................... 20
3-9. FAULT CODE ............................................................................................................................................................... 22
3-10. WARNING INDICATOR ............................................................................................................................................... 22
3-11 WARNING CODE ......................................................................................................................................................... 23
4. TROUBLE SHOOTING ................................................................................................................................................ 24
5. STORAGE AND MAINTENANCE .............................................................................................................................. 25
5-1. STORAGE .................................................................................................................................................................... 25
5-2. MAINTENANCE ............................................................................................................................................................. 25
6. SPECI FI CATIONS........................................................................................................................................................ 26
Page 4
1
1. Safety and EMC instructions
P lease read carefully the following user manual and the safety instructions before installing the unit or using the unit!
1-1. Transportation and Storag e
Please t ransport t he UPS system only in t he or iginal package to prot ect again st shock and
impact.
The UPS must be stored in the room where it is ventilated and dry.
1-2. Preparation
Co n den sat io n m ay occur i f th e UPS syst em i s m o ved d ir ect l y f r o m col d to w ar m env ir o n m en t . The UPS system must b e absol utely dry bef ore being installed. Please allow at least two hou rs for the UPS system to acclimate the env ironme nt.
Do not install t he UPS system near wate r or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or nearby heater.
Do not block ventilation holes in the UPS housing.
1-3. I nstallation
Do not connect appliances or devices which would overload the UPS (e.g. big motor-type equipment)) to the UPS output sockets or terminal.
Place cabl es in such a way that no o ne can step on or trip over them.
Do not block air vents in the housing of UPS. The UPS must be installed in a location with good ventilation. Ensure eno ugh space on each side for ventilation.
UPS has provide d earthed terminal, in th e final install ed system configuration, equipotential earth bonding to the exter nal UPS battery cabinets.
The UPS can be installed only by qualified maintenance personnel.
An appropr iate disconnect device as short-circuit backup protecti on shoul d be provided in the building wiring installation.
An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of oper a tion should be provided in the buildin g wiring installation.
Connect t he earth before connecting to the building wiring terminal.
Installation and Wiring must be performed in accordance with the local electrical laws and regulations.
Page 5
2
1-4.
Connecti on Warnings
There is no standard backfeed protection inside of the UPS. Please isolate the UPS before working
according to Diagram 1. The isolation dev ice must be able to carry the UPS input current.
Diagram 1: External backfeed protection wiring
This UPS should be connect e d with TN earthing system.
The power supply for this unit must be single-phase rated in accordance with the equipment nameplate.
It also must be suitably grounde d.
Use of this equ ipment in life support applications where failure of this equipment can reasonably be
expe cted to cause the failure of the life suppor t equipment or to significantly aff ect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixtur e with air, oxygen o r nitrous oxide.
Connect your UPS power modu le’s grounding terminal to a ground ing electrode conductor.
The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS
is not connected to an AC supply.
Before working on this circuit
- Isolate Uninterruptible Power System (UPS)
- Then check for Hazardous Voltage between all
terminals in cluding the protective earth.
Risk of Voltage Backfeed
Page 6
3
1-5. Operation
Do not disconnect the earth conductor cable on the UPS or the building wiring terminals i n any time since t his would cancel the protective earth of the UPS system and of all connected load s.
The UP S system features its own, internal current source (batteries). The UP S output sockets or output terminal bl ocks may be electrically live even if the UPS system is not conne cted to the building wiring outlet.
In order to fully disconnect the UP S system, first press the “OFF ” button and then disconnect the mains.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The UPS can be operated by an y individuals with no previous experience.
1-6. Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission............... ............. ...:IEC/EN 62040-2
Category C3
Radiated Emission.......... ............... .........:IEC/EN 62 040-2
Category C3
* EMS
ESD.........................................................:IEC/EN 61000-4-2
Level 4
RS........................................................ ...:IEC/EN 61000-4-3
Level 3
EFT......................................................... :IEC/EN 61000-4-4
Level 4
SURGE................................................... :IEC/EN 61000-4-5
Level 4
CS........................................................... :IEC/EN 61000-4-6
Level 3
P ower-frequency Magnetic field.............. :IEC/EN 61000-4-8
Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning: Th is is a produ ct for commercial and indu st rial applica
tion in t he
second environment-
installation restrictions or additional measures may be
neede d to prevent disturbances.
Page 7
4
2. I nstallation and Operation
There are two different types of o nline UPS: standard and long-run models. Please refer to the following model table.
Model
Type
Model
Type
6K
standard model
6KL
Long-run model
10K
10KL
Parallel function is also available for these two types and related installation and operation of Parallel function will be described in detail in the following content.
2-1. Unpacking and I nspection
Unpack the package and check the package contents. The shipping pack a ge contains:
One UPS
On e user manual
● One monitoring software CD
On e RS-232 cable (option)
On e USB cable
One parallel cable (only available for parallel model)
One share current cable (only available for parallel model)
● One battery cable (option)
NOTE: Before installation, please inspect the unit. Be sure t hat nothing inside the p ackage is damaged
du ring transportation. Do not tu rn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts. Please keep the original package in a safe place for future use.
2-2. Rear Panel View
Diagram 1: 6K/ 10K Diagram 2: 6KL/ 10KL
Rear Panel Rear Panel
1) Share current port (only available for parallel model)
2) Parallel port (only available for parallel model)
3) External battery connector
4) Intelligent slot
5) RS-232 communication port
6) USB communication port
7)
Emergency power off function connector (EPO
connector)
8) Maintenance bypass switch
9) Cooling fan
10) Input circuit breaker
11) Out put terminals
12) Ground
13) Input terminals
Page 8
5
2-3. Single UPS Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the fo llowing instructions by professional personnel.
1) Mak e su re t he m ain s w ir e and br eaker s in t h e b uil din g are eno ugh f or t he rat ed capacity of UPS t o avoid the hazards of electric sh ock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than
the UPS’s maximum input current. Otherwise the receptacle may be b urned and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
Model
Wiring spec (AWG)
Input
Output
Battery
Ground
6K
10
10 10
6KL
10
10
10
10
10K 8 8 8
10KL 8 8 8 8
NOTE 1 : The cabl e f o r 6K/6 KL shou ld b e ab l e t o w i th st an d o ver 40 A cu r r en t. It i s r eco m m en d ed to
use 10AWG or thi cker w ire f or safety and efficiency.
NOTE 2: The cable for 10K/10KL should be able to withstand over 63A current. It is recommended to
use 8AWG or thicker wire for safety and eff iciency.
NOTE 3: The selections for color of wires should be followed by the local electrical laws and
regulations.
5) Remo v e th e ter m i n al b lo ck cov er on the r ear pan el of UPS. Th en co nn ect t h e w i r es accor di ng to th e fo l lo win g t erm inal b l ock diagram s: (Connect th e ear th w i r e first w h en m ak ing wire con n ectio n . Discon n ect the earth wir e last when making wire disconnection!)
Terminal Block wiring diagram
NOTE 1: Make sure that the wires are connected tightly with the terminals. NOTE 2: Please inst all t he o utp ut break er bet w een t he ou tpu t ter minal and th e load, and th e br eaker
should be qualified with leakage cu rr ent protective function if necessary.
6) Put the terminal block cover back to the rear panel of the UPS.
Input Neutral
Input Line
Ground
Output Line
Output Neut ral
Page 9
6
Warning: (Only for standard model)
● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring
connection.
● Do not try to modify the standar d model to the long-run m o d e l . Particul arly , d o no t t ry t o con nect t he
standard internal battery to the external battery. The battery type and voltage may be different. If you connect them together, it maybe causes the hazard of electric shock or fire!
Warnin g: (Only for long-run model)
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed. If
not, please install it carefully. Switch off the battery breaker befor e installation.
Warnin g:
For standard battery pack, there is one DC breaker to disconnect the battery pack and the UPS. But for
other external bat tery p ack, m ake sure a DC breaker or oth er prot ection device bet ween UPS an d external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before installation.
NOTE: Set the battery p ack breaker in “OFF” positio n and then install the battery pack.
● Pay highly attention to the rated battery vo ltag e m ar k ed on t h e r ear pan el . If y o u w an t to ch an g e the
numbers of t he batt ery pack, please make sure you m odify t he settin g simulta neou sly. The connection wi t h wr on g bat t er y volt ag e m ay cause per ma nent dam ag e of t he UPS. Mak e sur e t he vol tag e of t he battery pack is correct.
● Pay highly attention to the polarity m arki ng on ext ernal batt ery ter min al block, and make su re t he
correct bat tery pol arity is conne cted. Wrong connection m ay cause permanent damage of th e UPS.
● Make sure the protective earth ground wiring is correct. The wire current spec, color, position,
connecti on and conductance reliability should be checked careful ly.
● Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection
and co nd u ct an ce r el iab il it y shou ld b e check ed car ef u ll y. Make sur e th e L/N sit e i s cor r ect, no t r ev er se and short-circuited.
2-4. UPS I nstallation for Para llel System
If the UPS is only available for single operation, you may sk ip this section to the next.
1) Install and wires the UPSs according to the section 2-3.
2) Connect the output wires of each UPS to an output breaker.
3) Co nnect all out put break ers t o a majo r ou tpu t breaker. Th en t his m ajor outp ut breaker w ill d irect ly
connect to the loads.
4) Each UPS is connected to an independent battery pack.
5) Remove the cover of parallel share current cable port on the UPS , connect each UP S one by one with the
parallel cable and share current cable, and then screw the cover back again.
NOTE: The parallel system can not use one battery pack. Otherwise, it will cause system permanent failure.
Page 10
7
6) Refer to the following wiring diagram:
Diagram 1: Power cable connection
Diagram2: Wiring diagram of parallel system
2-5. Software I nstallation
For optimal computer system protection, install UPS monito ring software to fully configure UPS shutdown.
Page 11
8
3. Operations
3-1. Button Operation
Button Function
ON/Enter Button
Turn on the UPS: P ress and hold the button more than 0 .5s to turn on the UPS.
Enter Key: Press this button to confirm the selection i n setting menu.
OFF/ESC Button
Turn off the UP S: Press and hold the button more than 0.5s to turn off the UP S.
Esc key: Press this button to return to last men u in setting menu.
Test/Up Button
Battery test: P ress and hold the button more than 0.5s to test the battery while
in AC mode, or CVCF mode.
UP key: Press this button to display next selection in setting menu.
Mute/Down Button
Mute the alarm: Press and hold the button more than 0.5s to mute the buzzer.
Please refer to section 3-4-9 for details.
Down key: Press thi s button to display previous selection in setting menu.
Test/Up +
Mute/Down Button
Press and hold the two b uttons simultaneous more than 1 s to enter/escape the
setting menu.
* CVCF mode means converter mode.
3-2. LED I ndicators and LCD Panel
There are 4 LEDs on front panel to show the UPS working status: Mode LED Bypass Line Battery Fault
UPS Startup
● ● ●
No Output mode
○ ○ ○
Bypass mode
○ ○ ○
AC mode
○ ● ○
Battery mode
○ ● ○
CVCF mode
○ ● ○
Battery Test
● ● ●
ECO mode
Fault
○ ○ ○
Note: means LED is lighting, and means LED is faded.
LCD panel
LED in dicator s
Page 12
9
LCD Panel:
Display
Function
Backup time information
Indicates battery discharge time in numbers.
H: hours, M: minutes, S: seconds
Fault information
Indicates that the warning and fault occurs.
Indicates the fault codes, and the codes are listed in details in section 3-9.
Mute operation
Indicates that t he UPS alarm is disabled.
Output & Battery voltage information
Indicates the output vo lt age, frequency or bat tery voltage.
Vac: ou tput voltage, Vdc: battery voltage, Hz: frequency
Load information
Indicates the loa d level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load o r the output is short.
Mode operation information
Indicates the UPS connects to the ma ins. Indicates the battery is working.
Indicates the bypass circuit is wor king.
Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the ou tput is working.
Page 13
10
Battery information
Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is not connected.
Indicates low batter y level and low battery voltage.
I nput & Battery voltage information
Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery vo ltage, Hz: input frequency
3-3. Audible Alarm
Description
Buzzer status
Muted
UPS status
Bypass mode
Beeping once every 2 minutes
Yes
Battery mode
Beeping once every 4 seconds
Fault mod e
Beeping continuously
Warning
Overload
Beeping twice every second
Yes
Others
Beeping once every second
Fault
All Beeping continuously
Yes
3-4. Single UPS Ope ration
3-4-1. Turn on the UPS with utility power supply (in AC mode)
1) After power supply is connected correctly, set the breaker of the battery pack at “ON” position (the step o n ly available f o r l on g - r u n m o d el). Th en set t h e i n pu t b r eake r at “ON” position. At this tim e the fan is running and the UPS enter to power on mode for initialization, several seconds later , UP S operates in Bypass mode and supplies power to the l oads via the bypa ss.
NOTE: Wh en UPS i s in Bypa ss mo de, t h e ou t put v olt ag e w i ll di rect ly pow er fr om ut i lit y af t er y ou
swit ch on t he i nput b reaker. I n Bypass m ode, t he l oad i s not p rot ected by UPS. To pr ot ect your pr e cious devices, you should turn on the UPS. Refer to next step.
2) Press and hold the “ON” button for 0.5s to turn on the UPS and the buzzer will beep once.
3) A f ew second s l ater, the UPS will ent er to AC m od e. If t h e util i t y power is ab n o r mal, th e UPS wil l operate in Battery mode without interruption.
NOTE: When the UPS is running out battery, it will shut down automatically at Battery mode. When the
utility power is restored, the UPS will auto restart in AC mode.
3-4-2. Turn on the UPS without utility power supply (in Battery mode)
1) Make sure that the breaker of the battery pack is at “ON” position (only for long-run model).
2) Press the “ON” b u tton t o set up th e po wer su p p l y for t he UPS, UPS wil l en ter t o pow er on mod e. After initialization UPS will enter to No Output mode, then P ress and hold the “ON” button for 0.5s to tu rn on the UPS, and the buzzer will beep once.
3) A few seconds later, the UPS will be turned on and enter to Battery mode.
Page 14
11
3-4-3. Connect devices to UPS
After the UPS is turned on, you can connect devices to the UPS.
1) Tu r n on th e UPS fi r st and th en switch on th e dev i ces o n e b y on e, the LCD p anel will d i spl ay total load level.
2) I f i t is necessary t o conn ect t he ind uct ive lo ads such as a pr in te r, t he in -r ush cur rent shoul d b e calcul ated carefully to see i f i t meets the capaci ty of the UPS, because th e power co n sumpti o n of this kind of loads is too big.
3) If the UPS is overload, the buzzer will beep twice every second.
4) When the UPS is overload, please remove some loads immediately . It is recommended to have the total loads conn e cted to the UPS less than 80% of i ts nominal power capacity to prev ent overload for system safety.
5) If the overload time is longer than acceptable time listed in spec at AC mode, the UPS will automatically transfer to Bypass mode. After the overload is removed, it will return to AC mode. If the overload time is lon ger than accept able t ime listed in spec at Battery mode, the UPS will become fault status. At this time, if bypass is enabled and the voltage and frequency in the range of it is set value, the UP S will power to the load via bypass. If bypass function is disabled or the input power is not within bypass acceptable range, it will cut off output directly.
3-4-4. Charge the batteries
1) After the UP S is connected to the utility power and working on the AC mode, the charger will charge the batteries automatically except in Battery mod e or during battery self-test.
2) Suggest t o charge bat teries at least 10 h ours bef ore use. Ot her wise, th e backu p t ime may be shorter t han expected time.
3) Make sure the battery numbers setting on the control board (Please refer to the section 3-4-12 for detailed setting) is consistent t o real connection.
3-4-5. Battery mode operation
1) When the UP S is in Battery mode, the buzzer will beep according to different battery capacity. If the bat ter y cap acity is m ore t han 25% , t he b uzzer w ill beep once ev ery 4 second s; If t he batt ery voltage drops to the alarm level, the buzzer will beep quickly (once every sec) to remind users that t he batt er y is at l ow lev el an d t h e UPS wil l sh ut d ow n au t o m atical ly soo n . User s cou l d sw itch of f some non-critical loads to disable t he sh utdown alarm and prolong the backup time. If there is no mo re l o ad t o be swi tched off at th at time, you have to shut down all load s as soo n as p ossibl e to protect the devices or save data. Otherwise, the re is a risk of data loss or load failure.
2) In Battery mode, if buzzer sound ann oys, users can press the Mute button to disable the buzzer.
3) The backup t ime of the long-run model depen ds on the external battery capacity.
4) The backup time may vary from different environment temperature and load type.
5) When setting backup time for 16.5 hours (990min in LCD setting menu 09), after discharging 16.5 hours, UPS w il l shu t d ow n autom a t ical ly to p r ot ect t h e b at t er y. This bat ter y d isch arg e p ro t ectio n can be enabled or disabled through LCD panel control. (Refer to 3- 7 LCD setting section)
3-4-6. Test the batteries
1) If you need to check the battery status when the UPS is running in AC mode/CV C F mode/E C O mode, you could press the “Test” button to let the UPS do battery self-test.
2) T o keep the system reliable, the UP S can perform the battery self-test periodically while connect the
Page 15
12
monitorin g software.
3) Users also can set battery self-test through monitoring softwa re.
4) I f th e UPS is at batt ery self- test , t he LCD display and buzzer i ndicat ion will be the same as at Battery mode except that the battery LE D is flashing.
3-4-7. Turn off the UPS with utility power supply in AC mode
1) T urn off the inverter of the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will
beep once. The UPS will turn into Bypass mode.
NOTE 1 : If t h e UPS has been set t o en able t h e b ypass o ut pu t , it w ill by pass vol t age fr om ut ili ty
power to output termi nal even though you have turned off the UPS (inverter).
NOTE 2 : Af ter tu r n in g o f f th e UPS, p l ease be aw ar e th at th e UPS i s worki n g at Bypass mod e an d
there is risk of power lo ss for connected devices.
2) I n Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the in p u t b reaker. A few second s later, there is no d ispl ay shown o n th e d ispl ay pan el and UPS is complete off.
3-4-8. Turn off the UPS without utility power supply in Battery mode
1) Turn off the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once.
2) Then UPS will cut off power to output and there is no display shown on th e display panel.
3-4-9. Mute the buzzer
1) T o mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the buzzer is muted, the buzzer will beep again.
2) Some w ar n i n g al ar m s can ’t b e muted u n less th e erro r is fix ed . Please r efer to sect io n 3 -3 f or the details.
3-4-10. Operation in warning status
1) Wh en Fault LED f lashes and t h e bu zzer b eeps on ce ev ery secon d, it m eans t hat t h ere ar e some problems for UPS operation. Users can get the warning code from LCD panel. Please check the 3-11 warning code table and the trouble shooting table in chapter 4 for details.
2) Some war n ing al ar ms can’t b e m u ted u n l ess t h e er r o r i s fi xed . Please ref e r to sect io n 3 -3 f or the detail s.
3-4-11. Operation in Fault mode
1) When F ault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in the UPS. Users can g et t h e f aul t code fr om d ispl ay p an el. Please che ck th e 3-9 f au l t cod e tab le and the trouble shooting table in chapter 4 for details.
2) Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try to turn on the UP S again before solving the problems. If the problems can’t be fixed, please contact the distributor or service people immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output immediately to avoid more risk o r danger.
3-4-12. Operation of changing battery numbers
1) This operation is only available for professional or qua lifie d technicians.
2) Tur n o ff th e UPS. I f t he lo ad cou ldn’t b e cut of f, you shou ld rem ove t he cover of main tena nce
Page 16
13
bypass switch on the rear panel and turn the mai ntenance switch to “BPS” position first.
3) Switch off the input breaker , and switch off the battery breaker (only available for long-run model).
4) Remove the cabinet cover and disconnect battery wire for standard model. Then, modify the jumper on the control board to set the battery numbers as below table.
Battery Number
in series
JP1
pin1 & pin2
pin3 & pin4
Pin5 & pin6
pin7 & pin8
Pin9 & pin10
16 X X 1 0
0
17 X X 0 1
1
18 X X 0 1 0 19 X X 0 0
1
20 X X 0 0
0
Note: 0 = no jumper; 1 = connect with jumper; x = the pins are for other fun ctions.
5) Modify the battery pack to meet the setting number in control board carefully.
6) Modify charger voltage according to below table to meet the setting number in control board. There are 5 jumpers on the charger board. Please refer to the below table to modify charger voltage.
Battery Number
in series
C harge
voltage (V)
JP01 JP02 JP03 JP04 JP05
16
218 0 0 0 1 0 17
232 0 0 1 0
0
18
245 0 1 0 0
0
19
259 1 0 0 0 0 20
273 0 0 0 0
0
Note: 0 = no jumper; 1 = connect with jumper.
7) Aft er com plet e the above steps, pu t t he cover back, swit ch on t he batt er y b reaker f or lo ng- run model and sw it ch on t he i npu t b reaker. Th en, t h e UPS w il l en t er Bypass m od e. I f t h e UPS is in mai nt en ance Bypass m od e, t u rn t he m ain t enan ce sw it ch to “UPS” posit i on an d t h en t ur n o n t he UPS.
3-4-13. Operation of changing charging current:
1) This operation is only available for professional or qua lifie d technicians.
2) Tur n o ff th e UPS. I f t he lo ad cou ldn’t b e cut of f, you shou ld rem ove t he cover of main tena nce bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
3) Switch off the input breaker, and switch off the battery breaker (only available for long-run model).
4) Remove the cabinet cover, and disconnect bat tery wire for standard model. Then modify the jumpers on the charger board to set the charging current (refer to table below). Be careful that the maximum charge current shou ld not exceed the battery accep ted charging current.
Charge current (A)
JP06 JP07 JP08
1A
0 0 1
2A 0 1 0
3A
1 0 0
4A 0 0 0
Note: 0 = no jumper; 1 = connect with jumper.
Page 17
14
3-5. Parallel Operation
3-5-1. Parallel system initial startup
First of all, please make sure all of the UPSs are p arallel mode ls and have the same configuration.
1) Turn on each UPS to AC mode respectively (Refer to section 3-4-1). Then, measure the output voltage of each UPS to check if the voltage difference between actual output and setting value is less than 1.5V (typical 1V) with multimeter. If the difference is more than 1.5V, please calibrate the voltage by confi guring inverter voltage adjustment (Refer to Prog ram 15, section 3-7) in LCD setting. If voltage differ ence remains more than 1.5V after calibration, ple a se contact your local distributor or service center for help.
2) Calibrate the output voltage measuremen t by configuring output voltage calibration (Refer to Program 16, section 3-7) in LCD setting to make sure the error bet ween real output voltage and detected value of UPS is less than 1V.
3) Turn off each UPS (Refer to section 3-4-7.). Then, follow the wiring procedur e in section 2-4.
4) Remove the cover of paralle l share current cable port o n the UPS, connect each UPS one by on e with the parallel cable a nd share current cable, and then screw the cover back.
3-5-2. Turn on the parallel system in AC mode
1) Turn on th e input breaker of each UPS. After all UPSs ente r to bypass mode, measu re the voltage between outp ut L1 of each UPS with multimeter. If the voltage difference is less than 1V, that means all connections are cor rect. Otherwise, please check if the wirings are connected correctly.
2) Turn on th e output breaker of each UPS. Before turning on each UPS in turns, check if PARXXX is displayed in each UPS sequentially. If no “PARXXX” exists in any UPS, please check if the parallel cables are conn e cted correctly.
3) Turn on each UPS in turns. After a whi le, the UPSs will enter to AC mode synchronously and then, the parallel system is complete d.
3-5-3. Turn on the parallel system in Battery mode
1) Turn on the battery b reaker (only availa ble in long-run model) and output breaker of each UPS.
NOTE: It’s not allo wed t o sh ar e o n e batter y p ack fo r long- run UPSs in par al l el syst em. Each UPS
should be connected to its battery pack.
2) Turn on any UPS. A few seconds later, the UPS will enter to battery mode.
3) Press the “ON” button to set up the power supply for another UPS, check if PARXXX is displayed. If not, please ch eck if th e par allel cable s a r e con nect ed cor rect l y. Then Turn on ano th er UPS. A f ew seconds later, the UPS will enter to battery mode and add to the paral lel system.
4) If you have the third UP S, follow the same procedure of 3). Then, the parallel system is complete.
3-5-4. Add one new unit into the parallel system
1) Y ou can not add one new unit into the parallel system when whole system is running. You must cut off the load and shu tdown the system.
2) Make sure all of the UPS are the p aralle l models, and follow the wiring refer to section 2-4.
3) Install the new parallel system refers to the previous section.
3-5-5. Remove one unit from the parallel system
There are two method s to remove one unit from the parallel system: First method :
1) Press t he “OFF” k ey twice an d each time sh ou l d l ast f o r m or e t h a n 0 . 5s. The n , th e UPS will ent er
into bypass mode without output.
2) Turn off the output breaker of t his unit, an d then turn off the input breaker of this unit.
Page 18
15
3) Aft er it shut s dow n, you can t ur n o ff th e bat ter y b reaker (f or l ong- run mo del) and rem ove th e
parallel cable and share current cable. Then, remove the u nit from the parallel system.
Second method :
1) If the b ypass is abnormal, you can not remov e the UPS without in terruption. You must cut off the load and shut down the syste m.
2) Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UP S s will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance switches from “UPS” to “BPS”. Turn off the input breakers and battery breake rs.
3) Remove the UPS that you want.
4) Turn on the input breaker of the remaining UPSs and the system will transfer to Bypass mode.
5) Set t h e m ain ten ance sw itch es f r om “BPS” t o “UPS and p ut th e m ain ten an ce by p ass cover s b ack. Turn on the re maining UPSs and fin ish the parallel system connection.
Warning: (Only for the parallel system)
● Before turning on the parallel system to activate inverter, make sure that all unit’s maintenance switch
at the same position.
● When parallel system is tu rne d on to wor k th rou gh inv e rter, please do not operat e the maintenance
switch of any unit.
3-6. Abbreviation M eaning in LCD Display
Abbreviation Display content Meaning
ENA
Enable
DIS
Disable
ATO
Auto
BAT
Battery
NCF
Normal mode (not CVCF mode)
CF
CVCF mode
S UB
Subtract
ADD
Add
ON
On
OFF
Off
FBD
Not allowed
OPN
Allow
RES
Reserved
OP.V
Output voltage
P AR
Parallel
Page 19
16
3-7. LCD Setting
There are three parameters to set up the UPS. Refer to follo wing diagram.
Programs available list for parameter 1:
Code Description
Bypass/
No output
AC ECO CVCF Battery
Battery
Test
01
Output voltag e
Y
02 Output frequency Y
03
Voltage range for bypass
Y
04 Frequency range for bypass Y
05
ECO mode enable/disable
Y
06 Voltage range for ECO mode Y
07
ECO mode frequency range setting
Y
08 Bypass mode setting Y Y
09
Battery backup time setting
Y Y Y Y Y
Y
10 Reserved Reserved for future
11
Reserved
Rese rved for future
12 Hot standby function enable/disable Y Y Y Y Y Y
13
Battery voltage adjustment
Y Y Y Y Y
Y
14 Charger volt a ge adjustment Y Y Y Y Y Y
15
Inverter voltage adjustment
Y Y Y
16 Output voltage calibration Y Y Y
*Y means that t his program can be set in this mode.
Note: All parameter settings will be saved only when UPS shuts down normally with internal or external battery connection. (Normal UPS shutdown means turning off input breaker in bypass mode).
01: Output voltage
I nterface
Setting
Parameter 3: Output voltage
You may choose the f ollowing output voltage in parame ter 3:
208: Presents output volta ge is 20 8Vac 220: Presents output voltage is 220Vac 230: Presents output voltage is 230Vac 240: Presents output volta ge is 24 0Vac
Parameter 1
Parameter 2
Parameter 3
Parameter 1: It’s for program alternatives. There are 16 programs to set up. Refer to below table.
Parameter 2 and parameter 3 are the setting options or values for each program.
Page 20
17
02: Output frequency
I nterface
Setting
60 Hz, CVCF mode
50 Hz, Normal mode
ATO
Parameter 2: Output Frequency
Setting the output frequency. You may choose following three options i n parameter 2:
50.0Hz: The output frequency is setting f or 50.0Hz.
60.0Hz: The output frequency is setting for 60.0Hz. ATO: If selected, output frequency will be decided accordin g to
the latest normal utility frequency. If i t is from 46Hz to 54Hz, the output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the output frequency will be 60.0Hz. ATO is defaul t setting.
Parameter 3: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You may choose following two options in parameter 3:
CF: Setting UPS to CVCF mode. If selected, the output frequency
will be fixed at 50Hz or 60Hz according to setting in parameter 2. The input frequency could be from 46Hz to 64Hz.
NCF: Setting UPS to normal mode (not CVCF mode). If selected,
the output frequency will synchronize with the input frequency within 46~ 54 Hz at 50Hz or within 56~ 64 Hz at 60Hz according to setting in parameter 2. If 50 Hz selected in parameter 2, UPS will transfer to battery mode when input frequency is not within 46~ 54 Hz. If 60Hz selected in parameter 2, UPS will transfer to battery mode when input frequency i s not within 56~ 64 Hz. *If Parameter 2 is ATO, the Parameter 3 will show the current
frequency.
Note: I f the UPS is set to CVCF mode, the bypass function will be disabled automatically. But when a single UPS without parallel function is powered on with mains and before the UPS finished the startup, there will be a few seconds of voltage pulse (same as the input voltage) on the bypass output. I f you need to remove the pulse on this mode to protect your load better, you could contact the dealer for help. For the UPS with parallel function, this pulse situation won’t happen.
03: Voltage range for bypass
I nterface
Setting
Parameter 2: Se t the acceptable low volt age for bypass. Setting
range is from 110V to 209V and the default value is 110V.
Parameter 3: Set the acceptable high voltage for bypass . Setting
range is from 231V to 276V and the default va lue is 264V.
04: Frequency range for bypass
I nterface
Setting
Parameter 2: Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49. 0Hz. 60 Hz system: Settin g range is from 56.0Hz to 5 9.0Hz. The default value is 46.0Hz/56.0Hz.
Parameter 3: Set t he acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz. 60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0 Hz/64. 0Hz.
Page 21
18
05: ECO mode enable/ disable
I nterface
Setting
Parameter 3: Enable or disable ECO function. You may choose
following two options:
DI S: disabl e ECO function ENA: enable ECO function
If ECO function is disabled, voltage range and frequency range for ECO mode still can be set, but it is meaningless unless the ECO
function is enabl ed.
06: Voltage range for ECO mode
I nterface
Setting
Parameter 2: Low voltage point in ECO mode. The setting range
is from 5% to 10% of the nominal voltage.
Parameter 3: High voltage point in ECO mode. The setting range
is from 5% to 10% of the nominal voltage.
07: Frequency range for ECO mode
I nterface
Setting
Parameter 2: Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz. 60 Hz system: Settin g range is from 56.0Hz to 5 8.0Hz. The default value is 48.0Hz/58.0Hz.
Parameter 3: Set high frequency point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz. 60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
08: Byp ass mode setting
I nterface Setting
Parameter 2:
OPN: Bypass allow ed. Wh en selected, UPS will run at Bypass
mode depen ding on bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it’s not allowed for
running in Bypass mode under any situations.
Parameter 3: ENA: Bypass enabled. When selected, Bypass mode is activated. DI S: Bypass disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass means users manually operate UPS for Bypass mod e. For example, pressing OFF button in AC mode to turn into Bypass
mode.
09: Battery backup time setting
I nterface
Setting
Parameter 3:
000~ 999: Se t the maximum backup time from 0min to 999min.
UPS will shut down to protect battery after backup time arrives.
DI S: Disable battery dischar ge protection and backup time will
depend on battery capacity. The default value is DIS.
Page 22
19
10: R eserved
I nterface
Setting
Reserved
11: R eserved
I nterface
Setting
Reserved
12: Hot standby function enable/ disable
I nterface Setting
Parameter 2: HS.H
Enable or disable Hot standby function. Y ou may choose following two options in Parameter 3:
YES: Hot standby function is enabled. It means that the current
UPS is set to host of the hot standby f unction, and it will restart after AC recovery ev en without battery connected.
NO: Hot stan dby function is disabled. The UPS is running at
normal mode and can’t restart without battery
13: Battery voltage adjustment
I nterface Setting
Parameter 2: Select “Add” or “Sub” function to adjust battery
vol tage to real figure.
Parameter 3: the voltage range i s from 0V to 5.7V, the defaul t
value is 0V.
14: Charger voltage adjustment
I nterface
Setting
Parameter 2: you may choose Add or Sub to adjust charger
voltage
Parameter 3: the voltage range is from 0V to 9.9V, the default
value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all batteries first to get the accurate charger voltage. *We strongly suggest to use the default value (0). Any
modification should be suitable to battery specifications.
Page 23
20
15: I nverter voltage adjustment
I nterface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter
voltage
Parameter 3: the voltage range i s from 0V to 6.4V, the defaul t
value is 0V.
16: Output voltage calibration
I nterface
Setting
When the output voltage can not be detected(less than 50VAC), this menu will be reserved, “
” will be displayed in parameter
2 and parameter 3.
Parameter 2: it always shows OP.V as output voltage.
Param eter 3: it sh ows t he int er
nal measur ement v alue of the
outp ut vol tag e, a n d y o u can calibrate i t by pressing Up or Down
accord ing to the measur ement f rom an ext ernal volt age m eter .
The calibration result will be effective by pressing Enter
. The
calib ration range is l i mited within + /-9V. T his functi on is no rm ally
used for parallel operation.
3-8. Operating Mode/ Status Description
If parallel UPS systems are successfully set up, it will show one more screen with “P AR” in parameter 2 and be assigned nu mber in paramet er 3 as b elow parallel screen diagram . The m ast er UPS will be default assigned as “001” and slave UPSs will be assigned as either “002” or “003”. Th e assigned numbers may be changed dynamically in the operation;
Operating mode/ status
AC mode Description When the input voltage is within acceptable range, UPS will provide pure
and st ab le AC po w er t o o u t p u t. Th e UPS w i ll al so ch ar ge t h e batter y at AC mode.
LCD display
Page 24
21
ECO m ode Description When the input voltage is within voltage regulation range and ECO mode
is enabled, UPS will bypass voltage to output for energy saving.
LCD display
CVCF mode Description When input fr equency is wi thin 46 to 64Hz, t he UPS can be set at a
constant out put f requency, 50 Hz or 60 Hz.
The UPS will st ill charge
battery u nder this mode.
LCD display
Battery mode Description When the input voltage is beyond the acceptable range or power failure,
UP S will backup power from battery and alarm will beep every 4 seconds.
LCD display
Bypass mode Description Wh en i nput v olt age i s w ith in acceptab le r ange and byp ass is en abled,
t ur n off t h e UPS and it wil l en t er Byp ass m od e. Alar m beep s ever y two
minutes.
LCD display
Battery Test Description W hen UPS is in AC m ode o r CVCF m o de, press “Test” key f or mo re than
0.5s. Th en the UPS w ill beep once and st art “ Bat tery Test”. T
he line
between I/P and inverter icon s w ill blink to remind users. Thi s operation
is used to check th e battery status.
LCD display
Fault stat u s Description When UPS has fault happened, it will display faul
t messages in LCD
panel.
Page 25
22
LCD display
3-9. Fault Code
Fault event
Fault code
I con
Fault event
Fault code
I con
Bus start failure
01
None
Battery SCR short circuited
21
None
Bus over
02
None
Inverter relay short circuited
24
None
Bus under
03
None
Charger short circuited
2a
None
Bus unbalance
04
None
Can communication fault
31
None
Inverter soft start failure
11
None
Parallel output current un balance
36
None High Inverter voltage
12
None
Over temperatu re
41
None
Low Inverter voltage
13
None
CPU communication failure
42
None
Inverter output short circuited
14
Overload
43
Negative power fault
1A
None
Battery turn-on failu re
6A
None
Inverter ov er current
60
None
PFC current failure in battery mode
6B
None Inverter waveform abnormal
63
None
Bus voltage changes too fast
6C
None
3-10. Warning Indicator
Warning
I con (flashing)
Alarm
Battery low
Beeping every second
Overload
Beeping twice every second
Battery unconnected
Beeping every second
Over ch arge
Beeping every second
EPO en able
Beeping every second
Fan failure/Over temperature
Beeping every second
Charger fai lure
Beeping every second
I/P fuse broken
Beeping every second
Overload 3 times in 30min
Beepin g every secon d
Page 26
23
3-11 Warning Code
Warning code
Warning event
Warning code
Warning event
01
Battery unconnected
10
L1 IP fuse broken
07 Over charge 21
Line situations are different in parallel system
08 Low batter y 22
Bypass situations are different in par allel system
09 Overload 33
Locked in bypass after overlo ad 3 times in 30min
0A
Fan f ai l u r e
3A
Cover of maintain switch is open
0B
EPO en able
3D
Bypass u nst able
0D Over temp erature
3E Boot loader is missing
0E
Charger fa ilure
Page 27
24
4. Trouble Shooting
If the UPS system does not o perate correctly, please sol ve the p roblem by using the table below.
Symptom
Possible cause
Remedy
No indication and alarm in the front
display panel even though the mains is
normal.
The AC input power is not
connected well.
Check if input cable firmly connected to the mains.
The icon
and the warning code
flash on LCD display and alarm
beeps every second .
EPO function is enabled.
Set the circuit in closed position to disable EPO
function.
The icon and
flash on
LCD display and alarm beeps every
second.
The external or internal battery is incorrectly
connected.
Check if all batteries are
connected well.
The icon and
flash on
LCD display and alarm beeps twice
every second.
UPS is overload.
R emove excess loads from UP S output.
UPS is overloaded. Devices conn ected to t he UPS ar e f ed directly by the electrical network via the Bypass.
R emove excess loads from UP S output.
Aft er r epetitive over loads, th e UPS is locked in the Bypass mode. Connect ed devices are fed directly by the mains.
R emove excess loads from UP S
output first. Then shut down
the UPS and restart it.
Fault code is shown as 43. The icon
lights on LCD display and
alarm beeps continuously.
UPS is overload too long and
becom es fau lt . T hen UPS shut down auto matically.
R emove excess loads from UP S output and restart it.
Fault code is shown as 14, the icon
lights o
n LCD display, and
alarm beeps continuously.
The UPS shut down automatically because short circuit occurs on the UPS output.
Check output wiring and if
conn ect ed d evi ces ar e in shor t circuit status.
Fau lt code i s sho wn as 01, 02, 03, 04, 11, 12, 13 , 14,1A, 2 1, 24 , 35, 36, 41 , 42 or 43
on LCD display and alarm
beeps conti nuously.
A UPS internal fault has occurred. There are two
possible results:
1. The load is still supplied, but
directly from AC power via
bypass.
2. The load is no longer supplied by power.
Contact your dealer.
Battery backup time is shorter than
nominal value
Batteries are not fully charged
Charge the batteries for at
least 7
hours and then check capacity. If the problem still persists, consult your dealer.
Batteries defect
Co nt act you r deal er t o r epla ce the battery.
The icon and f lash on LCD display and alarm beeps every second.
Fan is locked or not working;
or t h e UPS t em per at ur e is t o o
high.
Check fans and notify dealer.
Page 28
25
5. Storage and Maintenance
5-1. Storage
Befor e st orin g, charge th e UPS at l east 7 hour s. Stor e t he UPS cov ered and upr ight in a co ol, dry location. During storage, recharge the battery in accordance with the follow ing table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C
Every 3 mo nths
1-2 hours
40°C - 45°C
Every 2 mo nths
1-2 hours
5-2. Maintenance
The UPS system operates with hazardous vo ltages. Re pairs may be carr ied out only by qualified
maintenance personnel.
Even after the unit is disconnected from the mains, component s inside the UPS system are still
connected to the battery packs which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adeq uately familiar with batteri es and with the required precautionary measures may replace batter ies an d supervise operations. Unauthorized persons must be kept well away from the batteries.
Verify that no voltage between the battery terminals and the ground is present before maintenance or repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground.
Batteries may cause electric shock and have a high short-circuit current. Please remove all wristwatches, rings and other metal personal objects before maintenance or repair, and only use tools with insulated grips and han dles for maintaining or repairing.
When replace the batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The batteries must be right ly deposed according t o local regulation.
Do not open or destroy batteries. E scaping electrolyte can cause injury to the skin and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not disassemble the UPS system.
Page 29
26
6. Specifications
MODEL
VFI 6000 CG PF1
VFI 10000 CG PF1
CAPACITY*
6000 VA / 6000 W
10000 VA / 10000 W
I NPUT
Voltage Range
Line Loss
110~ 300Vac @ (0~ 60% ) Load
140~ 300V @ (60~ 80%) Load
176~ 300Vac @(80~100%)Load
Low Line Comeback
Low Line Loss Voltage + 10V
High Line Comeback
High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system
Phase
Single phase with ground
Power Factor
0.99 at 100% Load
OUTPUT
Output voltage
208/220/230/240VAC
AC Voltage Regulation
± 1%
Frequency Rang e (Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system 56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mo de
100% ~110% : 10min ; 110% ~130% : 1min ; >130% : 1sec
Battery mode 100% ~110% : 30sec ; 110%~ 130%: 10sec ; >130% : 1sec
Current Crest Ratio
3:1 max
Harmonic Distortion 1 % @ 100% Linear Load; 4 % @ 100% Non-linear Load
Transfer Time
Line Battery
0 ms
Inverter Bypass
0 ms
Inverter EC O
<10 ms
EFFICI ENCY
AC mo de
> 94%
Battery Mode
> 93%
BATTERY
Type
12 V / 9 Ah
12 V / 9 Ah
Numbers
16
20
Recharge Time 9 hours re co ver to 90% capacity
Charging Current
1 A ± 10% (max.)
Charging Voltage
(Battery number*13.65 V) ± 1%
PHYSICAL
Dimension, DXWXH(mm)
369 x 190 x 688
442 x 190 x 688
Net Weight (kgs)
57
67
ENVI RONMENT
Operation Temperature
0 ~ 40°C (the batter y life will down when > 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m
Acoustic Noise Level
Less than 55dB @ 1 Meter
Less than 58dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix , and MAC
Optional SNMP
Power management from SNMP manager and web browser
* De-r ate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjust ed to 208VAC. ** If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be de-rated one percent per 100m. ** * Product specification s are subject to change without further n otice.
Page 30
PowerWalker
VFI 6000 CG PF1
VFI 10000 CG PF1
Bedienungsanleitung
DE
Version: 1.1
Page 31
Alle Warnungen und Bedienungshinweise in
dieser Anleitung müssen unbedingt beachtet
werden. Bewahren sie diese Anleitung gut auf
und lesen Sie die folgenden Hinweise vor der
I nstallation sorgfältig durch. Nehmen Sie das
Gerät erst in Betrieb, wenn Sie alle
Sicherheitshinweise und die
Bedienungsanleitung sorgfältig durchgelesen
haben.
Page 32
Inhaltsverzeichnis
1. SI CHERHEIT UND EMV-HI NWEI SE ........................................................................................................................ 1
1-1. TRANSPORT UND LAG ERUNG ................................................................................................................................. 1
1-2. VORBEREITUNG ............................................................................................................................................................. 1
1-3. INSTALLATION ............................................................................................................................................................... 1
1-4.
ANSCHLUSS W ARNHINWEISE .............................................................................................................................. 2
1-5. BETRIEB ........................................................................................................................................................................ 3
1-6. STANDARDS ................................................................................................................................................................... 3
2. I NSTALLATION UND BETRIEB ................................................................................................................................. 4
2-1. AUSPACKEN UND ÜBERPRÜF EN ............................................................................................................................. 4
2-2. HINTERE KONSOLENANSICHT ............................................................................................................................. 4
2-3. USV EINZELINSTALLATION ..................................................................................................................................... 5
2-4. USV INSTALLATION FÜR PARALLELSYSTEM ......................................................................................................... 6
2-5. SOFTWARE INSTALLATION .............................................................................................................................................. 7
3. BEDIENUNG .................................................................................................................................................................... 8
3-1. TASTENBEDIENUNG ................................................................................................................................................. 8
3-2. LED ANZEIGEN UND LCD ANZEIGE ........................................................................................................................ 8
3-3. AKKUSTISCHER ALA RM .......................................................................................................................................... 10
3-4.
USV EINZELB ETRIEB
.................................................................................................................................................. 10
3-5.
PARALLEL BETRIEB
...................................................................................................................................................... 14
3-6. LCD-ANZEIGE INDEX DER FORMULIERUNGEN ............................................................................................................ 15
3-7. LCD EINSTELLUNG ................................................................................................................................................. 17
3-8.
BETRIEBSMODUS
/ZUSTANDSBESCHREIBUNG
.......................................................................................................... 22
3-9.
FEHLERCODE
............................................................................................................................................................... 24
3-10.
WARNANZEIGE
....................................................................................................................................................... 24
3-11
WARNCODE
.............................................................................................................................................................. 25
4. FEHLERBEHEBUNG ..................................................................................................................................................... 26
5. LAGERUNG UND I NSTANDHALTUNG ................................................................................................................... 27
5-1.
LAGERUNG
................................................................................................................................................................. 27
5-2.
WARTUNG
.................................................................................................................................................................. 27
6. SPEZIFI KATIONEN ..................................................................................................................................................... 28
Page 33
1
1. Sicherheits- und EMC Hinweise
Bitt e lesen Sie die folgenden Sicherheitshinweise und die Bedienungsanleit ung vor der Installat ion und Erstb enutzung aufmerksam durch!
1-1. Transport und Lagerung
Bitte transportieren Sie das USV-System nur in der Originalverpackung, um es vor Schlägen und
Stö ßen zu schützen.
Die USV muss in einem trockenen und gut belüfteten Raum aufbewahrt werden.
1-2. Vorbereitung
Wenn da s USV-System au s ein er kalt en Umgeb ung in d en Betri ebsraum g ebrach t w ird , kann eine Kondensat ion au ftret en. Das USV-System m uss vor der I nbet riebnahme absolut t rocken sein. Betreiben Sie das Gerät erst nach einer Akklimatisierungszeit von mindestens 2 Std.
Betreiben Sie das Gerät nicht in der Nähe von Wasser oder in einer feuchten Umgebung .
Stel len Sie da s USV- System ni cht in der Näh e von Wär m equ el len au f od er set zen Sie es n icht direkter Sonnen einstrahlung aus.
Halten Sie die Vent ilationsöffnungen des USV-Gehäuses frei.
1-3. I nstallation
Schließen Sie keine Geräte an die Ausgang-Buchse oder Klemmen an, die Die USV überlasten (z.B. Geräte hoher Leistung).
Platzieren Sie das Kabel so, dass niemand darauf treten oder darüber stol pern kann.
Halten Sie die Vent ilationsöffnungen des USV-Gehäuses frei. Die USV muss an einem Ort mit guter Belüftung installiert werden. Achten Sie auf ausreichend Platz für die Belüftung.
Die USV ist mit Erdungsklemmen im Endkonfigurations-System ausgestattet, mit Potenzialausgleich zur externen USV-Batteriebox.
Die USV darf nur von qualifiziertem Fachpersonal installiert we rden.
Für den Kurzschlussschutz sind b auseit s Sicherungen un d Last trenn scha lt er erforderlich.
Eine integrierte Notvorrichtung welche verhindert, dass die Spannung zu hoch wird, sollte vorgesehen sein.
Vor dem Anschluss des Gerätes an die Stromversorgung, zuerst die Erdung anschließen .
Die Installation und Verdrahtung ist gemäß den geltenden Bestimmungen unter Beachtung der örtlichen Vorschriften durchzuführen.
Page 34
2
1-4.
Anschluss Warnhinwei se
Innerhalb gibt es keinen Standard-Nachspeiseschu tz, b itte isolieren Sie die USV vor dem Betrieb
entsprechend. Die Trennv orrichtung muss in der Lage sein, den USV-Eingangsstrom zu führen.
Di agramm 1: Externe Nachspeise-Schutzverdrahtung
Diese USV sollte an ein TN Erdungssystem angeschlossen wer den.
Die Stromversorgung für dieses Gerät muss gemäß Typensch ild einphasig bewertet werden. Es muss
auch in geeigneter Weise geerdet werde n.
Die Nutzung dieses Geräts in lebenserhaltenden Anwendungen, denen ein Ausfall dieses Gerätes
zugemutet wird, kann dazu führen, dass diese Geräte versagen oder deren Sicherheit oder Wirksamkeit beeinträch tigt wird. Verwenden Sie dieses Gerät nicht in der Nähe von einer brennbaren Mischung von Anästhetika mit Luft, Sa uerstoff oder Stickstoffoxid.
Verbinden Sie Ihren USV-Erdungsanschluss de s Leistungsmoduls m it einem Erdungsleiter.
Die USV ist mit einer DC-Energiequelle (Batterie) v erbunden. Die Ausgangsklemmen können
stromführend sein, selbst, wenn die USV nicht an ein Stromnetz angeschlossen ist.
Vor dem Betrieb
- Unterbrechungsfr e ie Stromversorgung isoli eren (USV)
- Prüfen Sie dann auf gefährliche Spannung zwischen
allen Anschlüssen, einschließlich der Schutzerdung.
Gefahr von Spannungsnachspeise
Page 35
3
1-5. Operation
Das Erdungskabel während des Betriebs n icht von der USV-Anlage abziehen, da sonst die Schutzerdung der USV-Anlage und aller angeschlossenen Verbraucher au fgehoben wird.
Das USV-System verfügt über eine eigene, interne Stromquelle (Batterien). Die USV
-Ausgangssteckdosen oder Ausgangsklemmen können stromführend sein, auch wenn die US V nicht an die Steckdose bzw. an die Einspeisung der Hausinstallation angeschlossen ist.
Zum v ölligen Abschalten der USV die „OFF“-Taste drücken und dann das Netzkabel herausziehen.
Stellen Sie sicher, dass keine Flüssigkei t oder sonstige Frem dkörper in die USV gelangen.
Die USV kann von allen Personen, ohne Vorkenntnisse, bedient werden.
1-6. Standards
* Sicherheit
IEC/EN 62040-1
* EMI
Leitungsgeführte Emissionen......................... :IEC/EN 62040-2
Kategorie C3
Emittierte S trahlung...................................... :IEC /EN 62040-2
Kategorie C3
* EMS
ESD......................................................... :IEC/EN 61000-4-2
Level 4
RS.............................................................:IE C/EN 61000-4-3
Level 3
EFT.......................................................... :IEC/EN 61000 -4-4
Level 4
Überspannung..... ............. ....................... :IEC/EN 61000-4-5
Level 4
CS........................................................... :IEC/EN 61000-4-6
Level 3
Netzfreq uenz Magnetfeld…………................ :IEC/EN 61000-4-8
Level 4
Niederfrequenz Signale...............................:IEC/EN 61000-2-2
Warnung: Dieses Produ kt i st zur in dust ri ellen u nd kom m erziell en Nut zung in
der zweiten Umwelt-Installationsbeschränkung oder es können zusätzliche
Maßnahmen erforderlich sein.
Page 36
4
2. I nstallation und Betrieb
Es gibt zwei unter schiedliche Arten von Online-USV: Standard und Long-run Modelle. Bitte beachten Sie folgende Modellübersich t.
Modell
Typ
Modell
Typ
6K
Standar dmodell
6KL
Long-run
Modell
10K
10KL
Optional bieten wir auf Anfrage für diese Typen auch eine “Parallel-Funktion” an. Die USV mit Par a llel-Funktion wi rd “Parallel-Modell ” genannt. Die Installation und der Betrieb werden im folgenden Kapitel ausführli ch beschrieben.
2-1. Auspacken und Überpr üfen
Packen Sie de n Inhalt aus und überprüfen Sie den Packungsinhalt. Das Paket enthä lt:
Eine USV
Eine Bedienungsanleitung
Eine Monitoring Software CD
Ein RS-232 Kabel (optional)
Ein USB-Kabel
Ein Parallelkabel (nur für das Parallel-Modell verfügbar )
Ein Stromkabel (nur für das Parallel-Modell verfügbar)
Ein Batteriekabel (optional)
HI NWEIS: Inspizieren Sie d as Gerät vor der Installation. Vergewissern Sie sich, dass ke in Teil in der
Packung während des Transport beschädigt wurde. Falls ein Teil fehlt oder schadhaft ist, schalten Sie die Einheit nicht ein und informieren Sie den Transporteur u nd Händler. Bitt e bewahren Sie die Original-Verpackung für weiteren Gebrauch auf.
2-2. HI NTERE KONSOLENANSI CHT
Diagramm 1: 6K/ 10K Diagramm 2: 6KL/ 10KL
Rückseite Rückseite
1) Geteilte Schnittstelle (nur für das Parallel-Modell
verfü gbar)
2) Parallel-Port (nur für das P arallel-Modell verfügbar)
3) Externer Batt erieanschluss
4) Intelligent Slot
5) RS-232 Kommunikationsschnittstelle
6) USB Kommunikationsschnittstelle
7) Stecker für Not -Aus-Schalter (EPO Verbinder)
8) Wartungs-Bypass-Schalter
9) Lüfter
10) Ei ngangsschutzschalter
11) Ausgangsterminal
12) Erdung
13) Ei ngangsterm inal
Page 37
5
2-3. USV Einzelinstallation
Die Installation und Verdrahtung ist gemäß d e n geltenden Bestimmungen unter Beachtu ng der örtlichen Vorschriften von einem Fachmann durchzuführen.
1) Stellen Sie sicher, dass die Nennleistung des Netzkabels und der Schalter ausreichend sind, um
Stromschlägen u nd Brandgefahr vorzubeugen.
HI NWEIS: Schli eßen Sie di e USV n i ch t a n die W an dsteck d o se an, w en n di e Nenn l ei stun g gering e r ist, als
der maximale Eingangsstrom de r USV. Andernfalls kann die Steckdose durchbrennen und zerstört werden.
2) Schalten Sie vor der Installation den Net zschalter aus.
3) Schalten Sie alle Geräte vor dem Anschluss an die USV aus.
4) Bereiten Sie die Verdrahtung gemäß nach folgender Tabelle vor:
Modell
Verdrahtung spec (AWG)
Input
Ausgang
Batterie
Erdung
6K
10
10 10
6KL
10
10
10
10
10K 8 8 8
10KL 8 8 8 8
HI NWEIS 1: Das Kabel für 6K/6KL sollte einer Spannung von 40 A standhalten. Es wird ein
Phasenkabel von AWG10 oder dicker empfohlen für Sicherheit und Effizienz.
HI NWEIS 2: Das Kabel für 10K/10KL sollte einer Spannung von 63A standh a lt en. Es wird ein
Phasenkabel von 8AWG oder dicker empfohlen für Sicherheit und Effizienz.
HI NWEIS 3: Die Farbauswahl der Phasenkabel sollte gemäß den lokalen Vorschriften für die
Installation von elektrischen Gerät en eing ehalten werden.
5) Entfernen Sie die Klemmenabdeckung auf der Rückseite der USV. Dann schließen Sie die Kabel gemäß
dem folgenden Klemmen-Diagramm an: (S chließen Sie vor der Verdrahtung zuerst das Erdungskabel an. Beim Trennen der Verdrahtung trennen Sie das Erdungskabel zum Schluss!)
Klemmen-Diagramm
HI NWEIS 1: Vergewissern Sie sich, dass die Leitungen fest mit den Klemmen verbunden sind. HI NWEIS 2: Bit te inst allier en Sie d en Tr ennschal ter zwischen der Ausgan gsklem me u nd Last , u nd der
Leistungsschalter sollte bei Bedarf mit ei ner Leckstromschutzfunktion ausgestattet werden.
6) Befestigen Sie die Klemmenabdeckung wieder an der Rückseite der USV.
Eingang Neutral
Eingangsleitung
Erdung
Ausgangsleitung
Ausgang Neutral
Page 38
6
WARNUNG: (nur für das Standardmodell)
Stell en Sie sich er, dass. Die USV v or d er I n stallat ion ausgeschalt et ist . Die USV soll te währ end der
Verdrahtung nicht eingeschaltet werden.
Versuchen Sie ni cht ein Sta ndard-Modell i n ein Lon g-run-Modell zu v erändern. Versuch en Sie nicht die
eing ebaute Batterie an eine externe Batterie anzuschließen. Batterietyp und Spannung können unterschiedlich sein. Wenn Sie sie miteinander verbinden, kann das zu S tromschlägen und Brandgefahr führen!
WARNUNG: (Nur für Long-run Modell)
St el len Sie sicher , dass. ein DC-Tren nschal t er od er ein e an der e Schut zvor r icht u ng zw ischen USV un d
externem Akku installi ert ist. Sollt e keiner vorhanden sein, in st a ll i eren Sie ih n bitte sorgfältig . Schalt en Sie den Batterieschutzschalter vo r der Instal lation aus.
WARNUNG:
Für Standard- Akkupacks gibt es einen DC-Trennschalter, um die Bat terie und die USV zu t rennen.
Stellen Sie sicher, dass für andere externe Akkus ein DC-Trennschalter oder eine andere
Schutzvorrichtung zwischen USV und externem Akku installiert ist. Sollt e k einer vo rha nden sein,
installieren Sie ihn bitte sorgfältig. Schalten Sie d en Batterieschutzschalter vor der Installation aus.
HI NWEIS: Stellen Sie den Batterieschalter in die “OFF” Position und installieren Sie dann den
Batterie-Pack.
B eachten S ie den Hinweis zur Batteriespannung auf der Rückseite des G erätes. Wenn Sie die Anzahl der
Akkus ändern wollen, stellen Sie sicher, dass. Sie auch gleichzeitig die Einstellung ändern. Ein Anschluss an ei n e f al sche Spannun g kan n dau erhaft e Schäden a n Ih rer USV v erursachen . Verg ewissern Sie sich , dass die Spannung der Batterie korrekt ist.
Acht en Sie auf di e Kennzeichn ung der r i ch tig en Polari sierun g au f der Klemmenab d e ckung . Ein falscher
Anschluss kann dauerh afte Schäden an Ihrer USV verursachen.
St el len Sie sich er, dass d ie Schu t zleit er -Verd ra ht un g k orr ekt au sgefü hr t ist . Die akt u elle Spezifik at ion ,
Farbe, Positi on, Anschluss und Leitfähigkeit, sollte sorgfältig überprüft werden.
Stellen Sie sicher, dass die Ein-/ Ausgangsverdrahtung korrekt ist. Die aktuelle Spezifikat ion, Farbe,
Position, Anschluss und Leitfähigkeit, sollte sorgfältig überprüft werden. Stellen Sie sicher, dass die L/N korrekt und ni cht umgekehrt oder kurzgeschlossen ist.
2-4. I nstallati on USV-Parallel-System
Ist die USV nur für den Einzelbetrieb verfügbar, können Sie diesen Abschnitt ü berspringen.
1) Installation und Verd rahtu ng der USVs gemäß Abschnitt 2-3.
2) Verbinden Sie die Ausgangskabel der ei nzelnen USV mit einem Ausgangsleistungsschalter.
3) Ver binden Sie alle Ausgangsschalter zu einem Haupt-Ausgangsschalt er. Danach w ird dieser Schalt er
direkt mit der Last verbunden.
4) Jede USV ist mit einer unabhängigen Batterie verbunden.
5) Entfernen Sie die Abdeckung vom Parallel-Anschluss der USV, verbinden Sie jede USV mit dem
Paralle lkabel und Stromkabel und schrauben Sie die Abdeckung wieder an.
HI NWEIS: Für das Parallel-System kann kein Akku-P ack verwendet werden. Ansonsten kann dies zu einem
dauerhaften Ausfall des Systems füh ren.
Page 39
7
6) Beacht en Sie folgenden Schaltplan:
Diagramm 1: Netzkabelanschluss
Diagramm 2: Anschlussdiagramm für das Parallel-System
2-5. Software I nstallation
Für einen optimalen Computersystemschutz, installieren Sie die USV Überwachungssoftware, um das Abschalten der USV programmieren zu können.
Page 40
8
3. Betr ieb
3-1. Tastenbedienung
Taste Funktion
ON/ENTER-Taste
Anschalten der USV: Drücken und halten Sie die Taste für mindesten 0.5
Sekunden, um die USV einzuschalten.
Enter Taste : Drücken Sie diese Taste um die vorangegangene
Auswahloptionen in den USV Einstellungen zu bestätigen.
OFF/ESC Button
USV ausschalten: Drücken und halten Sie die Taste für mindesten 0.5
Sekunden, um die USV auszuschalten.
ESC-Taste: Drücken Sie diese Taste um in das Auswahlmenü zurückzukehren.
OFF/ESC Taste
Batterietest: Drücken und halten Sie die Taste für mindesten 0.5 Sekunden
um die Batterie im AC Modus und CVCF* Modus zu testen.
UP Taste: Drücken Sie diese Taste, um die nächste Auswahl im
Einstellungsmenü anzuzeigen.
Test/Up Taste
Stummschalten des Alarms: Drücken und halten Sie die Taste für mindesten
0.5 Sekunden um den Signalton abzuschalten. Siehe Abschnitt 3-4- 9 für
Einzelheiten.
Down Taste: Drücken Sie diese Taste, um die vorherige Auswahl im
Einstellungsmenü anzuzeigen.
Mute/Down Taste
Drücken und halten Sie die beiden Tasten gleichzeitig für mehr als 1 Sekunde,
um in das Einstellungsmenü zu kommen.
* CVCF Modus bedeutet Konverter-Modus.
3-2. LED Anzeige und LCD Panel
Es gibt 4 LEDs am vorderen Bedienfeld, um den USV-Betriebsstatus anzuzeigen:
Modus LED
Bypass
Line
Batterie
Fehler
UPS Startup
● ● ●
USV An
○ ○ ○
Kein Ausgabemodus
○ ○ ○
Bypass Modus
○ ● ○
AC Modu s
○ ● ○
Batteriebetrieb
○ ● ○
CVCF Modus
● ● ●
Batterietest
Fehler
○ ○ ○
HINWEIS: bedeutet LED leuchtet, und bedeutet LED ist aus.
LCD Panel
LED Anzeige
Page 41
9
LCD Panel:
Anzeige
Funktion
Backup-Zeitinformation
Zeigt die Batterieentladezeit in Zahlen
H: Stunden, M: Min uten, S: Se kunden
Fehlerinformation
Zeigt Warnungen und Fehler an.
Zeigt die Fehlerkodierung, und die Kodes wie in Abschnitt 3-9 beschrieben.
Stummschaltung
Zeigt an, dass der USV-Alarm ausgescha ltet ist.
Ausgangs- und Akkuspannung
Zeigt die Ausgangsspannung, Frequenz oder Akkuspannung an.
Vac: Ausgangsspannung, Vdc: Akkuspannung, Hz: Frequenz
Last-I nformation
Zeigt die Last in 0-25%, 26-50%, 51-75% und 76-100% an.
Zeigt Überlastung an.
Zeigt einen Kurzschluss in Last und Ausgang an.
Betriebsmodus Information
Zeigt an, dass das die USV an das Stromnetz angeschlossen ist.
Zeigt an, dass der Akku einwandfrei funktioniert.
Zeigt an, dass der Bypass einwandfrei funktioniert.
Zeigt an, dass der ECO Modus akt iviert ist.
Zeigt an, dass der Inverterstromkreis einwandfrei funktioniert.
Zeigt an, dass der Ausgang funktion iert.
Batterie-I nformation
Page 42
10
Zeigt den Ladungszustand des Akkus in 0-25%, 26-50%, 5 1-75%, und
76-100% an.
Zeigt an, dass der Akku nicht angeschlossen ist.
Zeigt einen niedrigen Ladezust a nd und Spannung des Akkus an.
Eingangs- & Akkuspannung I nformation
Zeigt die Eingangsspannung oder -frequenz oder die Akk uspannung an. Vac: Eingangsspannu ng, Vdc: Akkuspannung, Hz: Eingangsfrequenz
3-3. Akustischer Alarm
Beschreibung
Statusanzeige
stumm
UPS Status
Bypass-Modus
Signalton ertönt alle 2 Sekunden
Ja
Akkumodus
Signalton ertönt alle 4 Sekunden
Fehlermodus
Dauer Piepton
WARNUNG
Überlastung
Signalton ertönt zweimal pro Sekunde
Ja
Sonstige
Signalton ertönt jede Sekunde
Fehler
Alle
Dauer Piepton
Ja
3-4. USV Einzelplatzbetrieb
3-4-1. USV Stromversorgung (im AC Modus)
1) Nachdem die St romversorg ung ordnungsgemäß an geschlossen ist , st ellen Sie den Schalt er des Akku s au f d ie “ON” Po sit i on (di es ist n u r bei Long - r u n Mod el len ver f ü gb ar ) . Dan n st ellen Sie d en Schalter des Line-Eingangs auf die “ON” Position (bei einer dualen Eingabeeinheit stellen Sie a uch den Byp ass-Schalt er auf “ON”) . Zum j etzigen Zeitp u n k t läu f t d er Lüf ter u n d d ie USV ist b er ei t f ü r die Initialisierung. Einige Sekunden später arbeitet die US V im Bypass-Modus und versorgt die Last via Bypass mit Spannung.
HI NWEIS: Ist die USV im Bypass-Modus, zieht die Ausgangsspannung, nach drücken des
Eing an gsschalter s, d ie Spannu n g d i rek t au s d en Verbrau ch er n . Im Bypass-Mod u s i st d ie Last n ich t dur ch di e USV g eschüt zt . Um Ih re ko stb aren Gerät e zu schü t zen, sol lt en Sie d ie USV ein schalt en . Sieh e nächster Schritt.
2) Drü cken und hal ten Sie di e „ ON“ Tast e an d er USV f ür m ind estens 0.5 Sekund en b is der Alar m einmal pie pt.
3) Nach einigen Sekunden schaltet die USV in den AC Modus. Falls die Stromversorgung abnormal ist, läuft die USV o hne Unterbrechung im Akkubetr ieb.
HI NWEIS: Ist der Akku entladen, schaltet die USV den Akkubetrieb automatisch ab. Ist die
Stromversorgung wiederhergestellt, aktiviert die USV automatisch einen Neustart im AC-Modus.
3-4-2. USV Stromversorgung (im Akkumodus)
1) Stellen S ie sicher , dass der Schalter des Akkus auf der “ON” Position steht (nur für Long-run Modelle verfü gbar).
2) Drücken Sie die “ON” Taste zum Einrichten der Stromversorgung, die USV wechselt in den
Page 43
11
Betriebsmodus. Nach der Initialisierung wechselt die US V in den kein Eingabemodus. Drücken und halten Sie die „ON“ T as te an der USV für mindestens 0.5 Sekunden bis die USV einschaltet und der Akustischer Warnton einmal piept.
3) Nach einigen Sekunden schaltet die USV ein und wechselt in den Akkubetrieb.
3-4-3. Geräte an die USV anschließen
Wenn die USV eingeschaltet ist, können Sie beliebige Geräte anschl ießen.
1) Schalten Sie zuerst die USV ein und dann nacheinander die Geräte, das LCD Panel zeigt die
Gesamtlast an.
2) Wenn es not wendig ist eine induktive Last, wie einen Drucker, anzuschließen, sollt e überprüf t
werden ob der Eingangsstr o m fü r USV ausrei chend ist, da der Strom v erbrauch die ser Lasten seh r hoch ist.
3) Ist die USV überlastet, ertönt zweimal in der Sekunde ei n Akustischer Warnto n.
4) Ist di e USV ü berl astet, beseitigen un v erzügl i ch die Lasten. Es w i rd em p foh le n , die Gesamtlast auf
die USV unter 80% der nominalen Leistungskapazität zu halten, um eine Überlastung der Systemsicherheit zu vermeiden.
5) Ist die Überlastzeit überschritten, schaltet die US V automatisch in den Bypass-Modus. Nachdem die Überl ast ent f ern t ist , w echselt die USV in den AC Modus. Wenn d ie akzept abl e Über last un gszeit überschr itten ist , bringt die USV ein e Fehler meld ung . Wen n zu di eser Zeit der Bypass aktiv i ert i st,
bezieht die Last der USV die Spannung über den Bypass. Wenn die Bypass-Funktion deaktiviert ist oder die Eingangsleistung nicht innerhalb des akzeptablen Bereichs liegt, wird unmittelbar abgeschaltet.
3-4-4. Batterien laden
1) Nachdem d ie USV an di e Net zver sor gu ng ang eschlossen ist , w i rd die Bat t er ien au t om at i sch ü ber das Ladegerät aufgeladen, außer im Batteriebetrieb oder während d es Batterie-Selbsttests.
2) Die Batterien mindestens 10 Stunden vor der ersten Nutzung aufladen. Ansonsten kann die
Back-up Zeit kürzer sein al s erwartet.
3) Stell en Sie sicher, d ass die Bat t eri eeinst el lun g auf dem Kont r oll pan el ( siehe Abschni tt 3- 4- 12 der Beschreibung) mit dem tatsächliche n Anschluss übereinstimmt.
3-4-5. Batteriebetrieb
1) Im Batteriebetrieb piept der Akustischer Warnton je nach Batteriekapazität. Bei einer K apazität von mehr als 25% piept der Akustischer Warnton alle 4 Sekunden; Sinkt die Batteriespannung, wird der Akustischer Warnton schneller (einmal pro Sekunde) um den Anwender daran zu erinnern, dass bei
niedriger Batteriespannung die USV heruntergefahren wird. Die Anwender können einige un kritischen Last en ab schalten um den Alarm zu deaktivi eren un d d ie Back-up Zeit zu verlängern. Gibt es zu diesem Zeit pun kt keine Last die abgeschalt et werden kann, mü ssen Sie sobald wie mö glich al le Lasten t ren nen , um die Dat en zu speicher n u nd di e Gerät e zu schü t zen. Ansonst en besteht die Gefahr eines Datenverlustes oder Lastfehler.
2) Wenn der Piept on im Batt erieb etr ieb stör t, k ann der Anwen der di e Mut e-Taste dr ücken um den
Alarm zu deaktivieren.
3) Die Backup-Zeit von Long-run Modell en hängt von der externen Batteriekapazität ab.
4) Die Ba ck up- Zeit kan n au fgr und unt erschiedli cher Umgeb ungst emper atur en un d Belast ung sar ten
variieren.
5) Wenn di e Backup -Zeit auf 16 ,5 St und en ei ngest ellt ist ( St andar dw ert des LCD Pan els) nach d er
Page 44
12
Entladung 16,5 Stunden, schaltet die USV zum Schutz des Akkus automatisch ab. Dieser Batterieentladungsschutz kann aktiviert oder über die LC D-P anel S teuerung deaktiviert sein. (S iehe 3-7 LCD-Einstell ung sabschnit t)
3-4-6. Batterie testen
1) Wenn Sie während des Netzbetriebes / CVCF Modus den Batteriestatus überprüfen möchten, drücken Sie die “Test” Taste um einen Se lbsttest durchzuführen .
2) Damit das System zuverlässig arbeitet, kann die USV den die Batterie-Selbsttest während der Verbindung der Überwachungssoftware i n regelmäßigen Abständen durchführen.
3) Benutzer können den Batterie-Selbsttest über die Monitoring-Software einstellen.
4) Befindet sich die USV im Batterie-Selbsttest, erscheint die gleiche Anzeige für LCD und Piepton wie im Batteriebetrieb, außer dass die Batte rie-LED blinkt.
3-4-7. Ausschalten im AC Modus
1) Drücken Sie di e “Of f” Ta st e f ü r min d estens 5 Sekun d en b i s d er Aku st i scher Warn ton 3 Mal er tö nt.
Die USV schaltet in den Bypass-Modus.
HI NWEIS 1: Wenn d i e USV au f d i e Bypass-Freig ab e ein g estell t i st , sch altet d i e Bypass Spann u n g
von der Versorgung sspan nung zur Ausgangsklemme (Inverter).
HI NWEIS 2: Beachten Sie bitte nach dem Ausschalten, dass die US V im Bypass-Modus arbeitet und
die Gefahr einer Stromunterbrechung für die angeschlo ssenen Geräte besteht.
2) Im Bypass-Modus, ist immer noch Ausgangsspannung der USV vorhanden. Um den Ausgang auszuschalt en, schalt en Si e den Leit un gseingan g ab ( bei ein er d ualen Eingab eeinhei t, au ch d en Bypass-Schalter abschalten). Einige Sekunden später wird auf dem Display angezeigt, dass die US V komplett ausgeschalte t wird.
3-4-8. Ausschalten im Batteriebetrieb
1) Drücken Sie die “Off” Taste für mindestens 5 Sekunden bis zum Erlöschen des Akustischer Warntons.
2) Danach schaltet die USV ab und die Anzeige erlischt.
3-4-9. Akustischer Warnton stumm schalten
1) Drücken Sie die “Mute” Taste für mindestens 0,5 Sekunden, um den Akustischer Warnton auszuschalten. Wenn Sie die Taste erneut drücken, wenn der akustische Warnton ausgeschaltet ist, ertönt ei n Piep.
2) Einige WARN- Alarme können nicht stummgeschaltet werden, bis die Fehlerursache beseitigt ist.
3-4-10. Betrieb im Alarmzustand
1) Wenn die Fehler LE D blinkt und einmal pro Sekunde ein Akustischer Warnton ertönt bedeutet dies, dass ein Probl em im USV-Bet rieb best eht . Die Warnan zeige erscheint auf dem LCD Pan el. Bitte überprüfen Sie die WARNUNGEN 3-11 der Codetabelle und die Hinweise im Kapitel 4 Fehlerbehandlung.
2) Einige WARN-Alarme können nicht stummgeschaltet werden, bis die Fehler behoben sind. Wir verweisen auf den Absch nitt 3-3.
3-4-11. Betrieb im Fehler-Modus
1) Wenn die Fehler LED blinkt und der Akustischer Warnton kontinuierlich piept, liegt ein schwerwiegender Fehler in der USV vor. Der Fehlerkode erscheint auf dem LCD Panel. Bitte
Page 45
13
überprüfen Sie die WARNUNGEN 3-11 der Codetabelle und die Hinweise im Kapitel 4 Fehlerbehandlung.
2) Nachdem der Fehler auftritt überprüfen Sie bitte die Lasten, Verdrahtung, Lüftung, P rogramme und Batterie. Schalte n Sie die USV nicht ein, bevor die Prob leme gelöst sind. Wenn di e Probleme nicht behoben werden können, wenden Sie sich bitte unverzüglich an den Händler oder den Kundendienst.
3) Trennen Sie bi tt e im Not fall unv erzüg lich die Ver bin dung zum Prog ramm , ext ern en Bat ter ie und Ausgang, um größere Schäden zu vermeiden.
3-4-12. Ändern der Batterieanzahl
1) Diese Funktion steht nur professionellen oder qualifizierten Technikern zur Verfügung.
2) USV au sschalt en . Kann di e Last n ich t u n ter b r och en werd en , entf er n en Sie d i e Abd ecku n g au f d er Rückseite und stellen Sie zuerst den Wartungsschalter in die “BPS” Position.
3) Schalten Sie den Eingangsschalter und den Batterieschalter aus (nur für Long-run Modelle verfügbar.
4) Entf ernen Sie die Gehäuseabd eckun g un d t rennen Sie das Bat teriekabel des Standard- Modells. Dann ändern Sie den Jumper (Drahtbrücke) auf der Steuerplatine, um die Batterieanzahl zu wählen, wie in fol gender Tab elle dargestellt.
Batterieanzahl
serienmäßig
JP1
Pin1 & Pin2 Pinv3 & Pin4 Pin5 & Pin6 Pin7 & Pin8 Pin9 & Pin10
16 X X 1 0
0
17 X X 0 1 1
18 X X 0 1
0
19 X X 0 0 1
20 X X 0 0
0
HINWEIS: 0 = kein Jumper; 1 = Verbindung mit Jumper; x = Pins sind für andere Funktionen.
5) Änder n Sie d en Batter iep ack f ür d i e Einstel lu n g . Dana ch schl ießen Sie d ie Abd ecku n g w i eder un d schalten den Batterieschalter an, für Long-run Modelle.
6) Ändern der Ladespann un g g em äß f ol gen der Tab ell e. Es g ibt 5 Jum per au f dem Ladebo ard . Bitte beachten Sie die untenstehende Tabelle, um die Ladespannung zu ändern
Batterieanzahl
serienmäßig
Ladespannung
(V)
JP01 JP02 JP03 JP04 JP05
16 218 0 0 0 1 0
17
232
0 0 1 0 0
18 245 0 1 0 0 0
19
259
1 0 0 0 0
20 273 0 0 0 0 0
HINWEIS: 0 = kein Jumper; 1 = Verbindung mit Jumper.
7) Nach der Durchführung der o.g. Schritte, bringen Sie die Abdeckung w ieder an, schalt en den Batterieschalter und den S chalter für Long-run Modelle an. Die USV arbeitet nun im Bypass -Modus. Wenn die USV i m Wartungs-Bypass-Mod us ist , schalt en Sie den Wart u ngsschalt er auf die "USV" Position un d schalte n Sie die USV an.
3-4-13. Betrieb im Ladestromwechsel:
1) Diese Fun ktion steht nur profe ssionellen oder qualifizierten Technikern zur Verfügung.
Page 46
14
2) USV au sschalt en . Kann di e Last n ich t u n ter b r och en werd en , entf er n en Sie d i e Abd ecku n g au f d er Rückseite und stellen Sie zuerst den Wartungsschalter in die “BPS” Position.
3) Schalten Sie den Eingangsschalter und den Batterieschalter aus (nur für Long-run Modelle verfügbar).
4) Entf ernen Sie die Gehäuseabd eckun g un d t rennen Sie das Bat teriekabel des Standard- Modells. Dann ändern Sie den Jumper (Drahtbrücke) auf der Steuerplatine, um die Batterieanzahl zu wählen, wie in folgender Tabelle dargestellt. Achten Sie darauf, dass der maximale Ladestrom der Batterie, nicht den akzeptierten Ladestrom überschreitet.
Ladestrom (A)
JP06
JP07
JP08
1A 0 0 1
2A
0 1 0
3A 1 0 0
4A
0 0 0
HINWEIS: 0 = kein Jumper; 1 = Verbindung mit Jumper.
3-5. Parallelbetrieb
3-5-1. Erstinbetriebnahme Parallel-System
Stellen Sie zunächst sicher, dass alle USVs Parallel-Modelle sind und die gleiche Konfiguration haben.
1) Schalten Sie alle USVs in den AC Modus (siehe Abschnitt 3-4(1)). Dann messen Sie für jede Phase bei jeder USV die Inverterausgangsspannung um zu prüf en, ob die Spannungsdi fferenz zwischen der tatsächlichen Leistung und dem Einstellungswert unter 1,5 V (üblich 1 V) mit Mult imeter liegt. Ist die Differenz über 1,5 V, kalibriere n Sie bitte die Spannung über die Inverterspannu ng in der LCD Einstellung (siehe Programm 15, Abschn itt 3-7). Ist die Spannungsdi fferenz nach der Kalibrierung weiterhin hö her als 1,5 V, kontaktiere n Sie bitte Ihren lokalen Händler oder einen Kundendienst.
2) Kalibrie ren Sie die Ausgangsspannung über die Konfiguration in der LCD Einstellung (siehe Programm 16, Abschnitt 3-7) um sicherzustellen, dass die Differenz der tatsächlichen Leistung des erfassten Wertes der USV wen iger als 1 V beträgt.
3) Schalten Sie alle USVs aus (siehe Abschnitt 3-4-7 ). Befolgen Sie dann di e Vorgehensweise für die Verdr a htung, wie in Abschnitt 2-4 beschrieben.
4) Entfernen Sie die Abdeckung an der Pa rallelschnittstelle, schließen Sie jede USV nacheinander an und schließen Sie die Abdeckung wieder.
3-5-2. Parallel-System im Netzbetrieb
1) Schalten Sie den Eingangs-Leistungsschalter jeder USV an. Nachdem alle USVs im Bypass- Modus sind, messen Sie die Ausgangsspannung zwischen L1 jeder USV mit dem Multimeter. Sind beide Spannungsdifferenzen kleiner als 1V, bedeutet dies, dass alle Ve rbindungen korrekt sind. Andernf a lls überprüfen Sie bitte, ob die Kabel ordnungsgemäß angeschlossen sind.
2) Schalten Sie den Ausgangsschutzschalter der einzelnen USVs ein. Vor dem Einschalten der einzelnen USV, ob nacheinander bei jeder USV PARXXX ang e zeigt wird. Falls “PARXXX” bei jeder USV erscheint, überprüfen Sie b itte, ob die parall elen Kabel richti g angeschlo ssen sind.
3) Schalten Sie nacheinander die USVs an. Danach wechseln die USVs synchron in den AC Modus.
3-5-3. Parallel-System im Batteriebetrieb
1) Drehen Sie den Batterieschalter (nur in Long-r un Modellen verfügbar) und den Ausgangsschutzschalter der einzelnen USVs au f an.
HI NWEIS: Es ist nicht erlaubt, einen Akkupack zu teilen und für Long-run Modelle und
Parallel-Systeme zu verwenden. Jede USV sollte an einen separaten Akkupack angeschlossen werden.
Page 47
15
2) USV anschalten. Nach einigen Sekunden wechselt die USV in den Batteriebetr ieb.
3) Drücken Sie die “ON” Taste, um die Stromversorgung für eine weitere USV einzurichten, überprüfen Sie, ob PARXXX an g ezeigt wird. Fall s n i ch t, bit te ü ber p r ü f en Sie, o b d ie Parallel- Kabel ri chtig angeschlossen sind. c) Dann eine andere USV anschalten. Nach einigen Sekunden wechselt die USV in den Batteriebetrieb und ergänzt das Parallel-System.
4) Wenn Sie eine dritte US V haben, wiederholen Sie Schritt 3). Dann ist das P arallel-S ystem komplett.
3-5-4. Einfügen einer neuen Einheit in das Parallel-System
1) Sie kö nnen eine neu e Ei nh eit n icht dem Par allel- System h inzuf üg en, w enn d as System läu ft . Sie
müssen die Last abschal ten und das System herunterfahren.
2) Stellen Sie sicher, dass alle USVs Parallel-Modelle sind und befolgen Sie die Anweisungen zur
Verdrahtung in Abschnitt 2-4.
3) Beziehen Sie sich bei der Installation einer neuen Einhe it auf den vorhergehenden Abschnitt.
3-5-5. Entfernen einer Einheit aus dem Parallel-System
Es gibt zwei Methoden eine Einheit aus dem Parallel-System zu entfer nen: Erste Methode :
1) Drü ck en Sie d i e “OFF” Taste zweim al f ü r mehr al s 0 , 5 Sekunden. Dana ch w ech selt die USV i n den
Bypass-Modus oder den Ausgabemodus ohne Ausgabe.
2) Schalten Sie den Ausgang strennschalter der Einheit aus und dann den Eingangstrennschalter.
3) Nach d em Herun ter fahr en d en Batt eri etr ennschalt er ausschalt en ( fü r Lon g- run Model le) und di e
Parallelkabel und aktuelle K abel entfernen. Entfernen Sie das Gerät nun aus dem Parallel-System.
Zweite Methode:
1) I st der Bypass ab nor mal , k önn en Sie d ie USV ni cht oh ne Un ter br echun g en tf ern en. Sie mü ssen zuerst die Last abschalten und das System herunterfahren.
2) Stellen S ie sicher , dass die Bypass-Einstellung in jeder US V aktiviert ist und fahren dann das System herunter. Alle USVs werden in den Bypass-Modus übertragen. Entfernen Sie alle Wartungs-Bypass-Abdeckungen und stellen Sie die Wartungsschalter von "USV" auf "BPS”. Schalten Sie alle Eingangsschalter und Batterieleistungsschalter auf Paral lel-System.
3) Entfernen Sie die USV, die Sie wollen.
4) Schalten Sie den Eingan gsschutzschalt er d er v erb lei ben d en USV an un d das Syst em kehr t in den Bypass-Modus zurück.
5) Stellen Sie den Wartungsschalter von "BPS" auf "USV und schließen Sie die Abdeckung. 5) Einschalten der verbleibenden USV und beenden der Parallel-Systemverbindung.
WARNUNG: (Nur für Parallel-System)
Bevor Sie das Parall el-System anscha lten u m de n Inve r ter zu ak tiv i er en v er g e w i ssern Sie sich, dass
alle Wartungsschalter der Einheit auf der gleichen Position stehen.
Wen n d as Parallel-System ei ng eschal t et w i r d u m ü b er d en Inv er t er zu ar b eiten , betätig en Sie n ich t
den Wartungsschalter.
3-6. Abkürzung Bedeutung der LCD-Anzeige
Abkürzung Anzeigeinhalt Bedeutung
Page 48
16
ENA
Aktivieren
DIS
Deaktivieren
ATO
Auto
BAT
Batterie
NCF
Standar dbetrieb (nicht CVCF Modus)
CF
CVCF Modus
S UB
Subtract
ADD
Add
ON
On
OFF
Off
FBD
Unzulässig
OPN
Zulässig
RES
Vorbehaltlich
OP.V
Ausgangsspannung
P AR
Parallel
Page 49
17
3-7. LCD Einstellung
Es können drei Param eter eingestellt werden. Siehe folgendes Diagramm.
Programm-Verfügbarkeitsliste Parameter 1:
Code Beschreibung
Bypass /
Kein
Ausgang
AC ECO CVCF Batterie
Batterie-
test
01
Ausgangsspannung
Y
02
Ausgangsfrequenz
Y
03
Spannungsbereich für Bypass
Y
04
Frequenzbereich für Bypass
Y
05
ECO Modus aktivieren/deaktivieren
Y
06
Spannungsbereich ECO Modus
Y
07
Frequenzbereich ECO Mod us
Y
08
Bypass Modus Einstellung
Y
Y
09
Einstellung max. Batterieentladungszeit
Y Y Y Y Y
Y
10
reserviert
Für zukünftige Optionen reserviert
11
reserviert
Für zukünftige Optionen reserviert
12
Hot-Standby-Funktion akt ivieren /
deaktivieren
Y Y Y Y Y Y
13
Batteriespannungsanpassung
Y Y Y Y Y
Y
14 Ladegerät Spann ungsanpassung Y Y Y Y Y Y
15
Inverter Spannungsanpassung
Y Y Y
16
Ausgangsspannung Kalibrierung
Y Y Y
*Y bedeutet, dass dieses Programm in diesem Mo dus eingesetzt werden kann.
HINWEIS: Alle Parameter-Einstellungen werden nur dann gespeichert, wenn die USV normal mit interner oder externer Batterieverbindung herunterfährt. (Normale USV Abschaltung bedeutet, den Eingangstrennschalter des Bypasses auszuschalten).
01: Ausgangsspannung
Schnittstelle
Einstellung
Parameter 1
Parameter 2
Parameter 3
Parameter 1: Ist für ein alternatives Prog ramm. Es gibt 16 Programme. Siehe Tabelle unten.
Parameter 2 und Parameter 3 geben die Einstelloptionen oder Werte für jedes Progr amm wieder.
Page 50
18
Parameter 3: Ausgangsspannung
S ie können folgende Ausgangsspannungen in Parameter 3 wählen:
208:
Ausgangsspannung 208V Wechselstrom
220: Ausgangsspannung 220V Wechselstrom 230:
Ausgangsspannung 230V Wechselstrom
240: Ausgangsspannung 240V Wechselstrom
02: Ausgangsfrequenz
Schnittstelle
Einstellung
60 Hz, CVCF Mode
50 Hz, Normal Modus
ATO
Parameter 2: Ausgangsfrequenz
Einstellung der Ausgangsfrequenz. Sie können folgende drei
Optionen in Parameter 2 wählen
:
50.0Hz: Einstellung der Ausgangsfrequenz für 50.0Hz.
60.0Hz: Einstellung der Ausgangsfrequenz für 60.0Hz. ATO:
Wenn ausgewählt, wird die Ausgangsfrequenz entsprechend der neuesten normalen Gebrauchsfrequenz entschieden
. Bei 4 6Hz bis 54Hz, ist die Ausgangsfrequenz
50.0Hz. Bei 56Hz bis 64Hz, ist die Ausgangsfrequenz 60.0Hz. ATO ist die Standardeinstellung.
Parameter 3: Frequenzmodus
Einstellung der Ausgangsfrequenz im CVCF Modus oder nicht CVCF Modus.
Sie können zwei Optionen in Parameter 3
wählen
:
CF: Einstellung der USV in den CVCF Modus. Wenn gewählt,
wird die Ausgangsfrequenz bei 50Hz oder 60Hz entsprechend der Einstellung in Parameter 2 festgesetzt. Die Eingangsfrequenz kann von 46Hz bis 64Hz liegen.
NCF: Einstellung der USV in den No rmalmodus (nicht CVCF
Modu s). Wenn ausgewählt, wird die Ausgangs frequenz mit der
Eingangsfrequenz innerhalb von 46 ~ 54 Hz bei 50 Hz synchronisiert oder gemäß der Einstellung in Parameter 2 innerhalb von 56 ~ 64 Hz bei 60 Hz. Wenn 50 Hz in Parameter 2 ausgewählt ist, wird die USV in den Batteriebetrieb übertragen, falls die Eingangsfrequenz nicht innerhalb von 46 ~ 54 Hz liegt. Wenn 60Hz in Parameter 2 ausgewählt ist, wird
die USV in den Batteriemodus übertragen, falls die E ingangsfrequenz nicht innerhalb 56~ 64 Hz liegt.
*Ist Parameter 2 ATO, zeigt Parameter 3 die aktuelle Frequenz an.
HI NWEIS: Wenn die USV auf CVCF-Modus eingestellt ist, wird die Bypass-Funktion automatisch deaktiviert.
Aber wenn eine einzige USV ohne Parallelfunktion mit Netzstrom eingeschaltet ist bevor die USV startet, gibt es ein paar Sekunden lang Spannungsimpulse (gleich der Eingangss pannung) am Bypass-Ausgang.
Wenn Sie den Impuls zu diesem Modus zu entfernen, um Ihre Last besser zu schützen, bitten Sie I hren Händler um Hilfe.
Für die USV mit Parallelfunktion, wird diese I mpulslage nicht geschehen.
03: Spannungsbereich Bypass
Page 51
19
Schnittstelle
Einstellung
Parameter 2: Stellen Sie die tolerable Höchst- und
Niedrigspannung für den Bypass-Modus ein. Einstellungsbereich
von 110V bis 209V und der Standardwert l iegt bei 110V.
Parameter 3: Stellen Sie die tolerable Höchst- und
Niedrigspannung für den Bypass-Modus ein
. Einstellungsbereich
von 231V bis 276V un d der Standardwert liegt bei 264V.
04: Frequenzbereich Bypass
Schnittstelle
Einstellung
Parameter 2: Stellen Sie die tolerable Niedrigfrequenz für den
Bypass ein. 50 Hz System: Einstellu ngsbereich ist von 46 .0Hz bis 49.0Hz. 60 Hz System: Einstell ungsbereich ist von 56.0Hz bis 59.0Hz. Der Standardwert liegt bei 46.0Hz/56.0Hz.
Parameter 3: Stellen S ie die tolerable Höchstfrequenz für Bypass
ein. 50 Hz: Einstellungsbereich ist von 51.0Hz bis 54. 0 Hz. 60 Hz: Einstellungsbereich ist von 61.0Hz bis 64. 0Hz.
Der Standardwert liegt bei 54.0Hz/64.0Hz.
05: ECO Modus aktivieren/ deaktivieren
Schnittstelle
Einstellung
Parameter 3: Aktivieren oder deaktivieren der ECO F unktion. Sie
können folgende zwei Optionen wählen:
DI S: ECO Funk tion aktivieren ENA: ECO Funktion deaktivieren
Ist die ECO Funktion deaktiviert, kann der Spannungsbereich
und der Frequenzbereich für ECO Modus immer noch festgelegt werden, aber es ist bedeutungslos, wenn die
ECO-Funktion aktiviert ist.
06: Spannungsbereich ECO Modus
Schnittstelle
Einstellung
Parameter 2: Niedrigspannungspunkt im ECO-Modus. Der
Einstellbereich ist von 5% bis 10% der Nennspannung.
Parameter 3: Hochspannungspunkt im ECO Modus. Der
Einstellbereich ist von
5% to 10% der Nennspannung.
07: Frequenzbereich ECO Modus
Schnittstelle
Einstellung
Parameter 2: Stellen Sie Niederspannungspunkt für den ECO
Modus ein.
50 Hz System: Einstellu ngsbereich ist von 46 .0Hz to 48.0Hz. 60 Hz System: Einstell ungsbereich ist von 56.0Hz to 58.0Hz. Der Standardwert liegt bei 48.0Hz/58.0Hz.
Parameter 3: Stelle n Sie den Hochspan nungspunkt für den ECO
Modus ein. 50 Hz: Einstellungsbereich ist von 52.0Hz to 54.0 Hz. 60 Hz: Einstellungsbereich ist von 62.0Hz to 64.0Hz.
Der Standardwert liegt bei 52.0Hz/62.0Hz.
08: Bypass Modus Einstellung
Page 52
20
Schnittstelle
Einstellung
Parameter 2:
OPN: Bypass zulässig. Wenn ausgewählt, läuft die USV über den
Bypass-Modus, je nachdem ob dieser aktiviert oder deaktiviert ist.
FBD: Bypass ist nicht zulässig. Wenn ausgewählt, ist der
Bypass-Modus nicht zulässig.
Parameter 3: ENA: Bypass aktiviert. Wenn ausgewählt, ist der Bypass-Modus
aktiviert.
DI S: Bypass deaktiviert. Wenn ausgewählt , ist der autom atische
Bypass akzeptabel, aber der manuelle Bypass ist nicht zulässig. Manueller Bypass bedeutet, dass der Anwender die USV manuell in den Bypass-Modus umstellen kann. Zum Beispiel durch Drücken
der “OFF” Taste vom AC Modus in den Bypass Mod us wechseln.
09: Einstellung maximale Batterieentladungszeit
Schnittstelle Einstellung
Parameter 3:
000~ 999: Stellen Sie die maximale Entladezeit von 0 min bis
999 min. ein
. Die USV schaltet bei einer festgelegten
Spannungsschwelle ab, um die Batterie vor Tiefentladung zu schützen.
Der Standardwert liegt bei 990 min.
DI S: Deakt ivieren des Batteri eentlad eschutzes und die
Backup-Zeit ist von der Batteriekapazität abhängig.
Der Standardwert ist DIS.
10: R eserviert
Schnittstelle
Einstellung
Reserviert
11: R eserviert
Schnittstelle Einstellung
Reserviert
12: Hot-Standby-Funktion aktivieren / deaktivieren
Schnittstelle
Einstellung
Parameter 2: HS.H
Aktivieren od er deakti vieren der Hot-Standby-Funktion. Sie können f olgende zwei Optionen wählen in Parameter 3:
YES: Hot-Standby-Funktion aktiviert ist. Es bedeutet, dass die
aktuelle USV wird die Hot-Standby-Funktion gehostet und startet nach der AC Wiederherstellung neu, auch ohne Anschluss an die Batterie.
NO: Hot-Standby-Funktion ist deaktiviert. Die USV wird im
normalen Modus ausgeführt und kann nicht ohne Batterie starten.
Page 53
21
13: Batteriespannungsanpassung
Schnittstelle
Einstellung
Parameter 2: Wählen Sie “Add” oder “Sub” um die
Batteriespannung einzustellen.
Parameter 3: Der Spannungsbereich ist von 0V bis 5.7V und der
Standardwert liegt bei 0V.
14: Ladegerät Spannungsanpassung
Schnittstelle Einstellung
Parameter 2: Sie können mit Add oder Sub die Ladespannung
einstellen.
Parameter 3: Der Spannungsbereich ist von 0V bis 9.9V und der
Standardwert liegt bei 0V.
HI NWEIS:
*Bevor Sie die Spannungsanpassung durchführen achten Sie darauf, alle Batterien zu trennen, um die genaue Ladespannung zu erhalten. * Wir e mpfehlen dringend, de n Standardwert (0) zu verwenden. Sämtliche Änderungen sollten den entsprechenden
Batterie-Spezifikationen entsprechen .
Page 54
22
15: I nverter Spannungsanpassung
Schnittstelle
Einstellung
Parameter 2: Sie können mit Add oder Sub die Spannung des
Inverters einstellen.
Parameter 3: Der Spannungsbereich ist von 0V bis 6.4V und der
Standardwert liegt bei 0V.
16: Ausgangsspannung Kalibrierung
Schnittstelle Einstellung
Wenn die Ausgangsspannung nicht erkannt werden kann (weniger als 50VAC), wird dieses Menü reserviert, “
” wird im
Parameter 2 und Parameter 3 angezeigt.
Parameter 2: zeigt immer OP.V als Ausgangsspannung.
Parameter 3: zeigt den internen Messwert der
Ausgangsspannung B
, sie können durch Drücken der “Up”
oder “Down” Taste die Messu
ng von einem externen
Spannungsmesser kalibrieren.
Das Kalibrierungsergebnis wird
durch Drücken der “Enter” Taste übernommen. Der Kalibrierungsbereich ist beschränkt auf + /-9V.
Diese Funktion
wird normalerweise für den Parallelbetrieb verwendet.
3-8. Betriebsmodus / Statusbeschreibung
Ist ein Paral le l-System e inger i ch tet, ersch ei n t noch ein e w ei tere An zeig e m it “PAR” in Parame ter 2 und die zugew iesene Numm er in Parameter 3, w ie unten b eschrieben. Der Haupt -USV wird die “001” und den folgenden USVs die “002” oder “003” zugewiesen. Die zugewiesenen Nummern können während des Betriebs dynamisch geändert werden;
Betriebsmodus / Status
AC Modu s Beschreibung Wenn die Eingangsspannung innerhalb des akzeptablen Bereichs ist,
lief ert d ie USV eine n r einen un d stabil en Netzstr om- Ausgang. Die USV lädt die Batterie a uch im AC-Modus.
LCD-Anzeige
Page 55
23
ECO Modus Beschreibung
Die USV leitet die Spannung direkt zum Ausgang, wenn sich die Eingangsspannung im akzeptablen Bereich liegt, um Energie zu sparen.
LCD-Anzeige
CVCF Modus Beschreibung Wenn d ie Eingan g sfr eq uen z innerhalb 46 to 64 Hz ist, k an n d ie USV auf
eine konstante Ausgangsfrequenz von 50Hz oder 60Hz eingestellt werden. In diesem Modus lädt die USV die Batterie auf.
LCD-Anzeige
Batteriebetrieb Beschreibung
Falls sich die Eingangsspannung außerhalb des akzeptablen
Bereichs befindet oder ein Stromausfall eintritt, ertönt der Alarm alle 4 Sekunden
.
LCD-Anzeige
Bypass-Modus Beschreibung
Falls sich die Eingangsspannung außerhalb des akzeptablen Bereichs befindet und der Bypass deak tiv ier t i st , schalt et sich d ie USV
aus und sie wird in den Bypass-Modus wechseln. Das Alarmsignal ertönt
alle zwei Minuten.
LCD-Anzeige
Batterietest Beschreibung Ist die USV im AC- oder CVCF Modus, drücken Si
e für mehr als 0,5
Seku nd en d ie “Test ” Tast e. Es er t ö nt ein Signal t on un d d er Batter ietest begi nn t . Die V erbindung zwischen I/P und Invertersymbol blinkt, um den User daran zu erinnern. Diese Funktion wird verwendet, um den
Batteriestatus überprüfen
.
Page 56
24
LCD-Anzeige
Fehlerstatus Beschreibung Wenn Fehler in der USV auftreten, wird eine Fehlermeldung im
LCD-Panel angezeigt.
LCD-Anzeige
3-9. Fehlercode
Fehlerereignis
Fehlercode
Symbol
Fehlerereignis
Fehlercode
Symbol
Busstartfehler
01
Keines
Batterie SCR Kurzschlu ss
21
Keines
Bus über 02
Keines
Inverter-Relais kurzgeschlossen
24
Keines
Bus unter
03
Keines
Ladegerät kurzgeschlossen
2a
Keines
Bus unausgeglichen
04
Keines
Can Kommunikationsfehler
31
Keines
Inverter Softstart-Fehler
11
Keines
P arallelausgabestrom unausgeglichen
36
Keines
Inverter Überspannung
12
Keines
Übertemperatur
41
Keines
Inverter Niederspannung
13
Keines
CPU Kommunikationsfehler
42
Keines
Inverter Ausgang kurzgeschlossen
14
Überlast
43
Negativer Stromausf all
1A
Keines
Akku Einschalt-Ausfall
6A
Keines
Inverter Überlast
60
Keines
PFC Stromausfall im Batteriebetrieb
6B
Keines
Inverter Wellenform abnormal
63
Keines
Bus-Spannung ändert sich zu schnell
6C
Keines
3-10. Warnanz eige
WARNUNG
Symbol (blinkt)
Alarm
Batterie schwach
Ertönt jede Sekunde
Überlastung
Ertönt zweimal in jeder Sekunde
Batterie ist nicht angeschlossen
Ertönt jede Sekunde
Überspannung
Ertönt jede Sekunde
EPO aktiviert
Ertönt jede Sekunde
Page 57
25
Lüfterfehler/Übertemperatur
Ertönt jede Sekunde
Ladefehler
Ertönt jede Sekunde
I/P Sicherung defekt
Ertönt jede Sekunde
Überlastung 3 Mal in 30 Min.
Ertönt jede Sekunde
3-11 War ncode
Warncode
Warnereignis
Warncode
Warnereignis
01
Batterie nicht ange schlossen
10
L1 IP Sicher ung defekt
07 Überlastung 21
Leitungsposition i m Par a llel-System unterschiedlich
08 Batterie schwach 22
Bypass Position im Par allel-System unterschiedlich
09 Überlastung 33
Im Bypass nach Überlastung 3 Mal in 30 Min. gesperrt
0A Lüfterfehler 3A
Abdeckung des Wartungsschalters ist offen
0B EPO aktiviert 3D Bypass unstabil
0D
Übertemperatur
3E
Bootloader fehlt
0E Ladefehler
Page 58
26
4. Fehlerbehebung
Fal ls die USV nicht einw andfrei funktioniert, können Sie den Fehler mit Hilfe der Tabelle unten beheben.
Symptom
Mögliche Ursache
Abhilfe
Keine Anzeige und Alarm im Displayfeld, obwohl das Netz normal ist.
Die AC-
Eingangsleistung ist
nicht gut verbunden.
Überprüfen Sie, ob das
Eingangskabel fest an das Netz
angeschlossen ist.
Das Symbol
und der Warncode
blinken auf dem LCD-Display
und der Alarm ertönt jede Sekunde.
Die Not-
Aus Funktion (EPO)
ist aktiviert.
Stellen Sie den Kreislauf auf geschlossen, um die
EPO-Funktion zu deaktivieren.
Das Symbol und blinken auf dem LCD-Display und der
Alarm ertönt jede Sekunde.
Ein externer oder interner
Akku ist falsch angeschlossen.
Überprüfen Sie den Anschluss aller Akkus.
Das Symbol und erscheint auf dem LCD-
Display und
der Alarm ertönt zweimal jede
Sekunde.
USV ist überla stet.
Entfernen Sie überschüssige Lasten aus dem USV-Ausgang .
USV ist über lastet . Gerät e di e an der USV angeschlossen
sind, werden direkt ü
ber den Bypass mit elektrischer Leistung versorgt.
Entfernen Sie überschüssige Lasten vom USV Ausgang
Nach wiederholten
Überlastungen wird die USV im Bypass Modus gesperrt.
Angeschlossene Geräte werden direkt vom Netz versorgt.
Entfernen Sie zuerst
überschüssige Lasten vom USV Ausgang
. Dann fahren
Sie die USV herunter und
starten erneut.
Der Feh lercode 43 erschein t au f dem
Display. Das Symbol blinkt auf der LED-Anzeige und
der Alarm
ertönt kontinuierlich
Die USV ist zu lange überlastet un d h at ei nen Fehler. Di e USV fährt automatisch herunter.
Entfernen Sie das
überschüssige Lasten vom USV Ausgang und starten Sie erneut.
Der Fehlercode 14 erscheint auf dem
Display. Das Symbol erscheint auf dem LCD-
Display und
der Alarm ertönt kontinuierlich
Die USV wurde automatisch abgestellt da ein Kurzschluss
am USV Ausgang aufgetreten ist
Überprüfen Sie die Ausgangsverkabelung und ob die angeschlossenen Geräte
einen Kurzschluss haben.
Ein Fehler cod e wie 01, 02, 03, 04, 11, 12, 13, 14,1A, 21 , 2 4, 35, 3 6, 41, 42 oder 43
wird auf dem Display
angezeigt und
der Alarm ertönt
kontinuierlich.
Ein interner USV-Fehler ist
aufgetreten.
Es gibt zwei
mögliche Ergebnisse: 1. Die
Last wird noch geliefert, aber direkt von der
Stromversorgung übe
r den
Bypass.
2. Die Last wird nicht mehr mit
Strom versorgt.
Kontaktieren Sie Ihren Händler .
Die Batterielaufzeit ist kürzer als
angegeben.
Batterien sind nicht vollständig geladen
Laden Sie die Akkus für mindestens 7 Stunden und überprüfen dann Ihre
K
apazität. Falls das Problem immer noch auftritt, kontaktieren Sie Ihren Händler.
Die Batterien sind defekt
Kontaktieren Sie Ihren
Händler, um
die Batterie
auszutauschen.
Die Symbole und blinken auf dem LCD-
Display und der Alarm
ertönt jede Sekunde
Lüfter ist gesperrt oder nicht funktioniert nicht; oder die USV Temperat ur ist zu hoch.
Überp rüfen Si e die Lü ft er un d
kontaktieren Sie Ihren Händler .
Page 59
27
5. Lagerung und I nstandhaltung
5-1. Lagerung
Laden Sie d ie USV fü r 7 Stu nde n. Lagern Sie d ie USV abg edeckt u nd auf r echt in ei nem kü hlen u nd trocken Ort. Laden Sie die Akk us gemäß folgender Tabelle:
Lagertemperatur Ladungshäufigkeit Ladezeit
-25°C - 40°C
Alle 3 Monate
1-2 hours
40°C - 45°C
Alle 2 Monate
1-2 hours
5-2. I nstandhaltung
Das USV-System arbeitet mit gefährlichen Spannungen. Reparaturen sind grundsätzlich nur von
qualifiziertem und geschultem Wartungspersonal durchzuführen.
Selbst nach Trennung vom Stromversorgungsnetz bleiben Bauteile innerhalb der USV an die
Batterien angeschlossen und befinden sich unter gefährlichem Spannungspotential.
Deshalb muss vor Beginn der Wartungsarbeiten die Batterie vom Strom getrennt und überprüft werden, ob Strom oder gefährliche Spannung in den hoch leistungsfähigen Kond e nsatoren, wie den BUS-Kondensat oren, vorhanden ist.
Das Auswechseln der Batterien ist durch Personal mit Sachkenntnis über Batterien und Kenntnis über die geforderten Vorsichtsregeln durchzuführen und zu ü berwachen. Unbefugte Personen sind von den Batterien fernzuhalten.
Stellen Sie vor Wartungs- und Re paraturarbeiten sicher, dass keine Spannung zwischen Batterieanschlüssen und der Erdung vorhanden ist. In diesem P rodukt ist der Batteriestromkreis nicht von der Eingangsspannung isoliert. Zwischen den Batter ieanschlüssen und der Erdung können gefährliche Spannungen auftreten.
Batterien können Stromschlag verursachen und weisen hohen Kurzschluss S trom auf. Entfernen S ie Ihre Uh ren, Ringe u nd andere metallischen Objekte und verwenden Sie n ur Werkzeuge mit isolierten Griffen.
Beim Austauschen der Batterien dieselbe Anzahl und denselben Batterietyp verwenden.
Versuch en Sie NICHT, Batterien dur ch Verbrennen zu vernichten. Dies könnte eine Explosion der Batterie verursachen. Die Batterien müssen entsprechend den lokalen Bestimmunge n entsorg t werden.
Batterien nicht öffnen oder zerstören. Elektrolyt kann Haut und Augen reizen. Es kann giftig sein.
Ersetzen Sie die defekte Sicherung durch eine neue mit der gleichen Amperezahl, um eine Brandgefahr zu vermeiden.
Das USV-System nicht demontieren.
Page 60
28
6. Spezifikationen
MODELL
VFI 6000 CG PF1
VFI 10000 CG PF1
KAPAZI TÄT*
6000 VA / 6000 W
10000 VA / 10000 W
I NPUT
Spannungsber eich
Niedrige Überleitung
110~ 300Vac @ (0~ 60% ) Last
140~ 300V @ (60~ 80%) Last
176~ 300Vac @ (80~ 100%) Last
Niedriges Leitungs-Comeback
Niederspannungsleistung + 10V
Hohes Leitungs-Comeback
Hochspannungsleistung - 10V
Frequenzbereich
46Hz ~ 54 Hz @ 50Hz
System
56Hz ~ 64 Hz @ 60Hz System
Phase
Einphasig mit Erdung
Leistungsfaktor
0.99 at 100% Load
AUSGANG
Ausgangsspannun g
208/220/230/240VAC
Wechselspannungsregulation
± 1%
Frequenzbereich (Synchronisierter Bereich)
46Hz ~ 54 Hz @ 50Hz System
56Hz ~ 64 Hz @ 60Hz System
Frequenzbereich (Batteriebetrieb)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Überladung
AC Modus
100% ~110% : 10min; 110%~ 130%: 1min; > 130%: 1sec
Batteriebetrieb
100% ~110% : 30sec; 110%~130% : 10sec; >130%: 1sec
Stromverhältnis
3:1 max
Harmonische Verzerrung 1 % @ 100% lineare Last; 4 % @ 100% nicht-lineare Last
Transfer Time
Wechselstrom B atterie
0 ms
Inverter Bypass
0 ms
Inverter EC O
<10 ms
EFFIZ I ENZ
AC Modus
> 94%
Batteriebetrieb
> 93%
BATTERI E
Typ
12 V / 9 Ah
12 V / 9 Ah
Nummern
16
20
Ladezeit 9 Stunden Ladezeit bis 90% Kapazität
Ladestrom
1 A ± 10% (max.)
Ladespannung
(Batterie-Nummer*13.65 V) ± 1%
PHYSIKALI SCH
Abmessungen, DXWXH(mm)
369 x 190 x 688
442 x 190 x 688
Nettogewicht (kgs)
57
67
UMGEBUNGSBEDI NGUNGEN
Betriebstemperatur
0 ~ 40°C (die Batterie fällt aus bei > 25°C)
Luftfeuchtigkeit bei Betrieb
<95 % und nicht kondensierend
Aufstellwinkel **
<1000m
akustische Geräusche Level
Kleiner als 55dB @ 1 Meter
Kleiner als 58dB @ 1 Meter
MANAGEMENT
Smart RS-232 oder USB
Unterstützt Windows® 2 000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMP
Powermanagement vom SNMP-Manager und Webbrowser
* De-Nen nleistung bis 60% der Kapazität im CVCF Modus und auf 90%, wenn die Ausgangsspannung auf 208 V eingestellt ist. **
Wenn die USV installiert ist oder an einem Ort höher als 1000m verwendet wird, muss die Ausgangsleistun g ein Prozent pro 100 m
herabgesetzt werden. ** *
Produktspezifikationen können jederzeit ohne vorherige Ankündigung geändert werden.