PowerWalker VFD 600 APFC User Manual

Standby (Offline) UPS
PowerWalker VFD 600 APFC PowerWalker VFD 800 APFC
PowerWalker VFD 600 APFC/FR
PowerWalker VFD 800 APFC/FR
Uninterruptible Power Supply System
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
CAUTION!!
Please read the following information carefully and save this manual for further reference. Disregard of these safety notes may endanger life or health, as well as the function of the equipment and the safety of your data. Risk of Electric Shock Heatsinks are live. Disconnect unit before
servicing.
Risk of Electric Shock. This unit receives power from more than one
source. Disconnection of AC sources and the DC source is required to de-energize this unit before servicing.
Risk of Electric Shock. Hazardous live parts inside this unit are
energized from the battery supply even when the input AC power is disconnected.
Risk of Electric Shock. Do not remove cover. No user serviceable parts
inside. Refer servicing to qualified service personnel.
To reduce the risk of fire, replace only with same type of fuse. Refer
servicing to qualified service personnel only.
The sum of the leakage current of the UPS and the connected
equipment should not exceed 3.5mA.
Do not dispose of batteries in a fire as they may explode.  Do not open or mutilate the battery or batteries. Released electrolytes
are harmful to the skin and eyes. It may be toxic.
A battery can present a risk of electric shock and of having a high short
circuit current. The following precaution should be observed when working on batteries:
1) Remove watches, rings or other metal objects from the handles.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting
batteries terminal.
To replace the batteries by qualified service personnel. Use the same
number and type of sealed lead-acid batteries.
This pluggable type A equipment with battery already installed by the
supplier is operator installable and may be operated by laymen.
The mains socket outlet that supplies the UPS shall be installed near
the UPS and shall be easily accessible.
Sealed, lead-acid, 6 cells battery.  φ on the rating label stands for phase symbol.  The maximum ambient temperature rating is 40°C.
WARNING!!
Refer servicing to qualified service personnel only.  To reduce the risk of fire or electric shock, install in a temperature and
humidity controlled indoor area free of conductive contaminants.
Risk of Electric Shock. Battery circuit is not isolated from AC input,
hazardous voltage may exist between battery terminals and ground. Test before touching.
System Description
Top --
1. Power On/Off Switch
2. Green LED : AC Mode/Battery mode
3. Red LED: Fault LED
4. All receptacles are surge protected
5. Surge protection receptacles
6. Battery power supplied receptacles
Side --
7. AC Input
8. Breaker
9. Modem/Phone Line Surge Protection
VFD 600 APFC VFD 800 APFC
Installation & Operation
Installing the PowerWalker VFD 600/800 APFC UPS is as easy as the following steps shown. Be aware that the Power Switch must be kept in the “ON” position and all equipment must be plugged into the Battery Power Supplied Receptacles, otherwise, the UPS will be disabled and your equipment will not be protected during a power failure.
1. Inspection
Remove the UPS from its packaging and inspect it for damage that may have occurred during shipping. If any damage is discovered, repack the unit and return it to the place of purchase.
2. Placement
Install the UPS unit in any protected environment that provides adequate airflow around the unit, and is free from excessive dust, corrosive fumes and conductive contaminants. DO NOT operate your UPS in an environment where the ambient temperature or humidity is high.
3. Charging
This unit is shipped from the factory with its internal battery fully charged. However, some energy may be lost during shipping, so the battery should be recharged before using it. Plug the unit into an appropriate power supply, then switch on UPS and allow the UPS to charge fully by leaving it plugged in for at least 8-10 hours with no load (no electrical devices such as computers, monitors, etc.) connected.
4. Computer Connection
Connect one computer-related device into one of the battery supplied receptacles on the top of UPS. PowerWalker VFD 600/800 APFC UPS provides six receptacles, all with surge protection, four of them including battery backup.
5. Peripheral Equipment Connection
Plug your peripheral equipment (printer, scanners, speakers) into the full-time surge protection outlets. These receptacles do not provide any power during a power failure.
Note: DO NOT plug a laser printer, copier, space heater, vacuum or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage the unit.
6. Modem/Phoneline Connection
Plug incoming internet line into the “In” socket at the side panel of the UPS. Use one more internet line cable and plug one end of the internet line cable to the “Out” socket at the side panel of the UPS. Plug the other end of the modem input socket as shown.
7. Circuit Breaker
When short circuit happens, the circuit breaker will pop-up and then the UPS will shutdown automatically. After waiting for 2 minutes, please press the circuit breaker button again and the mains (AC power) will comeback.
8. Turn On/Off
Press power switch 2 seconds to turn on the UPS. Press power switch again to turn off the UPS.
9. DC Start Function
DC Start Function enables UPS to be started up when AC utility power is not available and battery is fully charged. Just simply press the power switch to turn on the UPS.
10. Battery Replacement CAUTION: Battery replacement should be performed by qualified service personnel. Please follow the charts below to replace the batteries.
Step 1: Please prize up the battery cover gently.
Chart 1
Step 2: Please remove the battery cover gently.
Chart 2
Step3: After removing battery cover, gently extract the battery by disconnecting the two wires connecting to the UPS. Be sure to replace the same type of batteries and dispose of old batteries properly at an appropriate recycling facility.
Chart 3
POWER RATING
600VA/300W
800VA/420W
INPUT
Pure Sine Wave
Range of Input Voltage
170Vac~270Vac
Nominal Voltage
220Vac
Nominal Frequency
50H/60HZ
OUTPUT
Line Mode
Same as input
Battery Mode
Step wave
Line Mode Voltage
Same as input voltage
Battery Mode Voltage
220Vac10%
Line Mode Frequency
Same as input frequency
Battery Mode Frequency
50Hz/60Hz 1Hz
Transfer time
2-8ms typical ,12ms Max
BATTERY
Battery type
600VA
800VA
12V/5Ah*1
12V/7Ah*1
Backup time
100W SPS LOAD
17mins
20mins
Recharge time
10 hours max. (Recharge to 90% Capacity)
DISPLAY
Condition
Green Led/ Red Led
Line mode normal
Lighting/ Off
Battery normal
Lighting per 5s/ Off
Battery low
Lighting per 1s/ Lighting
Fault
Off/ Lighting
Over load(battery mode)
Lighting per 1s/ Lighting
AUDIBLE ALARM
Condition
Buzzer
Battery normal
Buzzing Per 5s
Specification
Battery low
Buzzing Per 1s
Fault
Continuous sounding
Over load
Buzzing Per 0.5s
PROTECTION
TVSS / Over load / Short Circuit Protection/Over
charge
PHYSICAL
600VA
800VA
Dimension (DxWxH)
320*125*86(mm)
335*170*92.5(mm)
Net Weight
3.1KG
4.1KG
Outlets
Schuko type/French type
6 outlets (2 for surge only, 4 for battery backup)
ENVIRONMENT
Operation Temperature/ Operation Humidity
0-40/0%-85%
Green LED is blinking every 5s,but audible alarm is heard intermittently
UPS is not connected properly to the mains
Connect the UPS according to the installation guide
UPS is function but audible alarm is heard continuously
Over load of the UPS
Verify that the load matches the UPS capacity specified in the spec.
Trouble Shooting
If the UPS failed to operate properly, please review the following points firstly.
System Possible Cause Remedy