PowerTen 3300 User Manual

0 (0)

3300 Series

DC Power Supplies

Operation Manual

PowerTen

9250 Brown Deer Road San Diego, CA 92121-2294 1-800-978-6680

Tel: (858) 458-0253

Fax: (858) 458-0237

Email: sales@powerten.com www.powerten.com

©2002 by PowerTen. This document contains information proprietary to PowerTen. The information contained herein is not to be duplicated or transferred in any manner without prior written permission from PowerTen.

January 11, 2002

Document No. M520086-01 Rev A

Safety Notice

Before applying power to the system, verify that the unit is configured properly for the user's particular application.

The 3300 series of power supplies is intended for rack mounted application only. Use of the power supplies outside of a rack mount enclosure will expose the user to high voltage and/or high current sources. Extreme caution must be used under these circumstances.

The analog control inputs (connectors J1 and J2) on the rear panel are referenced to the negative output of the power supply. Grounding the positive output of the power supply or biasing the output of the supply above chassis potential will cause these inputs (along with the output of the supply) to have a potentially hazardous offset voltage. Exercise caution under these conditions. Under no circumstances should the output of the supply be biased more than 500 volts from chassis potential.

Installation and service must be performed only by properly trained and qualified personnel who are aware of dealing with attendant hazards. This includes simple tasks such as fuse verification.

Ensure that the AC power line ground is connected properly to the unit input connector or chassis. Similarly, other power ground lines including those to application maintenance equipment must be grounded properly for both personnel and equipment safety.

Always ensure that facility AC input power is de-energized prior to connecting or disconnecting the input/output power cables.

Warning:

Lethal voltages may be present inside the power supply even when the AC input

 

voltage is disconnected. Only properly trained and qualified personnel should

 

remove covers and access the inside of the power supply.

During normal operation, the operator does not have access to hazardous voltages within the chassis. However, depending on the user's application configuration, HIGH VOLTAGES HAZARDOUS TO HUMAN SAFETY may be generated normally on the output terminals. Ensure that the output power lines are labeled properly as to the safety hazards and that any inadvertent contact with hazardous voltages is eliminated.

Due to filtering, the unit has high leakage current to the chassis. Therefore, it is essential to operate this unit with a safety ground.

This unit is designed to be permanently connected to the power source and as such must have a readily accessible disconnect device incorporated in the fixed wiring.

After the unit has been operating for some time, the metal near the rear of the unit may be hot enough to cause injury. Let the unit cool before handling.

These operating instructions form an integral part of the equipment and must be available to the operating personnel at all times. All the safety instructions and advice notes are to be followed.

Neither Power Ten nor any of the subsidiary sales organizations can accept responsibility for personal, material or consequential injury, loss or damage that results from improper use of the equipment and accessories.

M520086-01

ii

PowerTen 3300 User Manual

SERVICE SAFETY NOTICES

WARNING!

HAZARDOUS VOLTAGES IN EXCESS OF 480 V RMS, 700 V PEAK MAY BE PRESENT WHEN COVERS ARE REMOVED. QUALIFIED PERSONNEL MUST USE EXTREME CAUTION WHEN SERVICING THIS EQUIPMENT. CIRCUIT BOARDS, TEST POINTS, AND OUTPUT VOLTAGES MAY BE FLOATING ABOVE CHASSIS GROUND.

WARNING!

TO GUARD AGAINST RISK OF ELECTRICAL SHOCK DURING OPEN COVER CHECKS, DO NO TOUCH ANY PORTION OF THE ELECTRICAL CIRCUITS. EVEN WHEN THE POWER IS OFF, CAPACITORS CAN RETAIN AN ELECTRICAL CHARGE. USE SAFETY GLASSES DURING OPEN COVER CHECKS TO AVOID PERSONAL INJURY BY ANY SUDDEN FAILURE OF A COMPONENT.

WARNING!

SOME CIRCUITS ARE LIVE EVEN WITH THE FRONT PANEL SWITCH TURNED OFF. SERVICE, FUSE VERIFICATION, AND CONNECTION OF WIRING TO THE CHASSIS MUST BE ACCOMPLISHED AT LEAST FIVE MINUTES AFTER POWER HAS BEEN REMOVED VIA EXTERNAL MEANS; ALL CIRCUITS AND/OR TERMINALS TO BE TOUCHED MUST BE SAFETY GROUNDED TO THE CHASSIS.

WARNING!

QUALIFIED SERVICE PERSONNEL NEED TO BE AWARE THAT SOME HEAT SINKS ARE NOT AT GROUND, BUT AT HIGH POTENTIAL.

M520086-01

iii

FCC NOTICE

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

M520086-01

iv

About This Manual

This manual has been written expressly for the Power Ten 3300 Series of power supplies.

SAFETY SYMBOLS

CAUTION

Protective Conductor Terminal

Risk of Electrical Shock

 

CAUTION

Alternating Current (AC)

Refer to Accompanying Documents

 

M520086-01

v

TABLE OF CONTENTS

Chapter 1 DESCRIPTION OF EQUIPMENT____________________________________ 1-1

1.1PURPOSE AND CAPABILITIES _______________________________________________ 1-1

1.2TECHNICAL CHARACTERISTICS_____________________________________________ 1-1

Chapter 2 INSTALLATION __________________________________________________ 2-1

2.1INSPECTION _______________________________________________________________ 2-1

2.2INPUT/OUTPUT CONNECTORS ______________________________________________ 2-1

2.3LOCATION AND MOUNTING ________________________________________________ 2-1

2.4CHECKOUT AND PRELIMINARY ADJUSTMENTS ______ Error! Bookmark not defined.

Chapter 3 OPERATING INSTRUCTIONS ______________________________________ 3-4

3.1CONTROLS AND INDICATORS_______________________________________________ 3-4

3.1.1Local Operation ________________________________________________________________ 3-4

3.1.2Remote Current Programming _____________________________________________________ 3-7

3.1.3Remote Voltage Programming _____________________________________________________ 3-7

3.1.4Remote Sensing ________________________________________________________________ 3-8

3.1.5Remote Output On/Off Control_____________________________________________________ 3-8

3.1.6Auto-Parallel Operation __________________________________________________________ 3-9

3.1.7Auto-Series Operation ___________________________________________________________ 3-9

3.1.8Auto-Tracking Operation _________________________________________________________ 3-9

3.1.9Output overvoltage Protection ____________________________________________________ 3-10

Chapter 4 MAINTENANCE AND CALIBRATION _______________________________ 4-1

4-1. INTRODUCTION ___________________________________________________________ 4-1

4-2. PREVENTIVE MAINTENANCE _______________________________________________ 4-1 4-3. CALIBRATION AND ADJUSTMENTS _________________________________________ 4-3

4.1.1Converter Assembly Calibration____________________________________________________ 4-3

4.1.2Display Assembly _______________________________________________________________ 4-6

M520086-01

vi

LIST OF TABLES

TABLE 1-1 3300 SERIES TECHNICAL CHARACTERISTICS ......................................................

1-2

TABLE 1-2 3300 SERIES TECHNICAL CHARACTERISTICS ......................................................

1-4

TABLE 2-1 3300 SERIES INPUT/OUTPUT CONNECTORS ........................................................

2-2

TABLE 3-1 3300 SERIES CONTROLS AND INDICATORS..........................................................

3-5

TABLE 3-2 BARRIER STRIP (TB1) DESIGNATIONS AND FUNCTIONS ....................................

3-6

TABLE 4-1 PREVENTIVE MAINTENANCE SCHEDULE ..............................................................

4-1

TABLE 4-2 INSPECTION AND CORRECTIVE ACTION...............................................................

4-2

LIST OF FIGURES

FIGURE 3-1 3300 SERIES CONTROLS AND INDICATORS .......................................................

3-4

FIGURE 3-2 NORMAL CONNECTION PATTERN......................................................................

3-11

FIGURE 3-3 REMOTE RESISTANCE PROGRAMMING OF OUTPUT CURRENT ...................

3-11

FIGURE 3-4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT CURRENT .........................

3-12

FIGURE 3-5 REMOTE RESISTANCE PROGRAMMING OF OUTPUT VOLTAGE....................

3-12

FIGURE 3-6 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE..........................

3-13

FIGURE 3-7 REMOTE SENSING OPERATION..........................................................................

3-13

FIGURE 3-8 REMOTE ON/OFF CONTROL BY CONTACT CLOSURE.....................................

3-14

FIGURE 3-9 REMOTE ON/OFF OPERATION USING AC/DC VOLTAGE SOURCE.................

3-14

FIGURE 3-10 AUTO-PARALLEL OPERATION...........................................................................

3-15

FIGURE 3-11 AUTO-SERIES OPERATION................................................................................

3-16

FIGURE 3-12 AUTO-TRACKING OPERATION ..........................................................................

3-17

M520086-01

vii

Chapter 1

DESCRIPTION OF EQUIPMENT

1.1PURPOSE AND CAPABILITIES

The Power Ten 3300 Series power supplies are general purpose power supplies designed specifically for laboratory test and systems applications requiring variable DC sources with good regulation and low output ripple characteristics. Models of the 3300 Series are constant current/constant voltage supplies with an automatic crossover feature. They provide up to 1000 watts of DC power over a wide range of voltage and current levels.

1.2TECHNICAL CHARACTERISTICS

The physical, electrical and environmental characteristics for the 3300 Series are listed in Tables 1-1 and 1-2.

M520086-01

1-1

Table 1-1

3300 Series Technical Characteristics

PARAMETERS

SPECIFICATIONS

PHYSICAL CHARACTERISTICS:

 

Width

19.00 in.

Depth

18.50 in

Height

1.75 in.

Weight

15 lb. max.

ELECTRICAL CHARACTERISTICS:

 

Input Power (Standard)

95 to 127 VAC, 190 to 253 VAC (Option)

Voltage

Frequency

47 to 63 Hz

Phases

Single, 2-wire plus gnd

Regulation (Line or Load)

0.1% of max. output voltage

Voltage

Current

0.1% of max. output current

Noise and Ripple (RMS)

30 mV max.

Transient Response

A 30% step load will recover to within 2%

 

of original value within 10 ms.

Stability

+0.05% of set point per 8 hr. after warm-up

 

and at a fixed line, load and temperature.

Remote Control/Monitor

On/Off control via contact closure,

 

6-120 VDC or 12-240 VAC.

Power Density

2.5 Watts/cubic in.

Power Factor

.99 min. at full load

Total Harmonic

2.5% max.

 

 

M520086-01

1-2

Table 1-1

3300 Series Technical Characteristics - Continued

PARAMETERS

 

 

SPECIFICATIONS

Remote Programming

 

 

 

Resistive:

 

 

 

Constant Voltage (0-100%)

0

- 5k ohms

Constant Current (0-100%)

0

- 5k ohms

Voltage:

 

 

 

Constant Voltage (0-100%)

0

- 5 VDC

Constant Current (0-100%)

0

- 100 mV

Current:

 

 

 

Constant Voltage (0-100%)

0

- 1 mA

Constant Current (0-100%)

0

- 1 mA

Remote Sensing

Terminals are provided to sense output

 

voltage at point of load. Maximum line drop

ENVIRONMENTAL

3% of rated voltage per line.

 

 

 

CHARACTERISTICS:

 

 

 

Temperature Coefficient

0.02%/° C of max. output voltage rating for

 

voltage set point.

 

0.03%/° C of max. output current rating for

Ambient Temperature

current set point.

 

 

 

Operating

0 to 50° C

Storage

 

°

°

 

-40

to 75 C

Cooling

Internal blowers

 

 

 

 

M520086-01

1-3

Table 1-2

3300 Series Technical Characteristics

MODEL NUMBER

OUTPUT DC

OUTPUT DC

OUTPUT

VOLTS

AMPS

RIPPLE (RMS)

7.575

0-7.5

75

30 mV

7.5125

0-7.5

125

30 mV

1060

0-10

60

30 mV

10100

0-10

100

30 mV

2030

0-20

30

30 mV

2050

0-30

50

30 mV

3020

0-30

20

30 mV

3033

0-30

33

30 mV

4015

0-40

15

30 mV

4025

0-40

25

30 mV

5020

0-50

20

30 mV

6010

0-60

10

30 mV

6016

0-60

16

30 mV

8006

0-80

6

50 mV

8012

0-80

12

50 mV

10010

0-100

10

50 mV

1208

0-120

8

50 mV

1507

0-150

7

50 mV

M520086-01

1-4

Loading...
+ 24 hidden pages