PowerTen 3300 User Manual

January 11, 2002 Document No. M520086-01 Rev A
DC Power Supplies
3300 Series
Operation Manual
PowerTen
9250 Brown Deer Road San Diego, CA 92121-2294 1-800-978-6680 Tel: (858) 458-0253 Fax: (858) 458-0237 Email: sales@powerten.com www.powerten.com
©2002 by PowerTen. This document contains information proprietary to PowerTen. The information contained herein is not to be duplicated or transferred in any manner without prior written permission from PowerTen.
Safety Notice
Before applying power to the system, verify that t he unit is configured properly for the user's particular application.
The 3300 series of power supplies is intended for rack mounted application only. Use of the power supplies outside of a rack mount enclosure will expose the user to hig h voltage and/or high current sources. Extreme caution must be used under these circumstances.
The analog control inputs (connectors J1 and J2) on t he rear panel are referenced to the negative output of the power supply. Grounding t he positive output of the power supply or biasing the output of the supply above chassis potential will cause these inputs (along with the output of the supply) to have a potentially hazardous offset voltage. Exercise caution under these conditions. Under no circumstances should the output of the supply be biased more than 500 volts from chassis potential.
Installation and service must be performed only by properly trained and qualified personnel who are aw are of deal ing with attendant hazards. This incl udes si mple tasks such as fuse verification.
Ensure that the AC power line ground is connected properly to the unit input connector or chassis. Similarly, other power ground l i nes i ncl uding those to application maintenance equipment must
be grounded properly for both personnel and equipment
safety.
Always ensure that facility AC input power is de-energized prior to connecting or disconnect ing the input/output power cables.
Warning: Lethal voltages may be present inside the power supply even when the AC input
voltage is disconnected. Only properly trained and qualified personnel should remove covers and access the inside of the power supply.
During normal operation, the operat or does not have access to hazardous voltages within the chassis. However, depending on the user's application configuration, HIGH VOLTAGES HAZARDOUS TO HUMAN SAFETY may be generated norm ally on the out put terminals. Ensure that the output power lines are labeled properly as to the safety hazards and that any inadvertent contact with hazardous voltages is eliminated.
Due to filtering, t he unit has high leakage current to t he chassis. Therefore, it is essential t o operate this unit with a safety ground.
This unit is designed to be permanently connected to t he power source and as such m ust have a readily accessible disconnect device incorporated in the fixed wiring.
After the unit has been operating for some time, the m et al near the rear of the unit may be hot enough to cause injury. Let the unit cool before handling.
These operating instructions form an integral part of the equipment and must be available to the operating personnel at all times. All t he safety instructions and advice notes are to be followed.
Neither Power Ten nor any of the subsidiary sales organizations can accept r esponsibilit y for personal, material or consequential inj ur y, loss or dam age that results from im pr oper use of the equipment and accessories.
M520086-01 ii
SERVICE SAFETY NOTICES
WARNING!
HAZARDOUS VOLTAGES IN EXCESS OF 480 V RMS, 700 V PEAK MAY BE PRESENT WHEN COVERS ARE REMOVED. QUALIFIED PERSONNEL MUST USE EXTREME CAUTION WHEN SERVICING THIS EQUIPMENT. CIRCUIT BOARDS, TEST POINTS, AND OUTPUT VOLTAGES MAY BE FLOATING ABOVE CHASSIS GROUND.
WARNING!
TO GUARD AGAINST RISK OF ELECTRICAL SHOCK DURING OPEN COVER CHECKS, DO NO TOUCH ANY PORTION OF THE ELECTRICAL CIRCUITS. EVEN WHEN THE POWER IS OFF, CAPACITORS CAN RETAIN AN ELECTRICAL CHARGE. USE SAFETY GLASSES DURING OPEN COVER CHECKS TO AVOID PERSONAL INJURY BY ANY SUDDEN FAILURE OF A COMPONENT.
WARNING!
SOME CIRCUITS ARE LIVE EVEN WITH THE FRONT PANEL SWITCH TURNED OFF. SERVICE, FUSE VERIFICATION, AND CONNECTION OF WIRING TO THE CHASSIS MUST BE ACCOMPLISHED AT LEAST FIVE MINUTES AFTER POWER HAS BEEN REMOVED VIA EXTERNAL MEANS; ALL CIRCUITS AND/OR TERMINALS TO BE TOUCHED MUST BE SAFETY GROUNDED TO THE CHASSIS.
WARNING!
QUALIFIED SERVICE PERSONNEL NEED TO BE AWAR E T HAT SO M E H EAT SI N KS ARE NO T AT GROUND, BUT AT HIGH POTENTIAL.
M520086-01 iii
FCC NOTICE
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful inter ference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipm ent in a residential area is likely to cause harmful interference in which case the user will be required to correct the interf erence at his own expense.
M520086-01 iv
About This Manual
This manual has been written expressly for the Power Ten 3300 Series of power supplies.
SAFETY SYMBOLS
CAUTION Protective Conductor Terminal Risk of Electrical Shock
CAUTION Alternating Current (AC) Refer to Accompanying Documents
M520086-01 v
TABLE OF CONTENTS
Chapter 1 DESCRIPTION OF EQUIPMENT____________________________________ 1-1
1.1 PURPOSE AND CAPABILITIES _______________________________________________ 1-1
1.2 TECHNICAL CHARACTERISTICS_____________________________________________ 1-1
Chapter 2 INSTALLATION __________________________________________________2-1
2.1 INSPECTION_______________________________________________________________2-1
2.2 INPUT/OUTPUT CONNECTORS ______________________________________________2-1
2.3 LOCATION AND MOUNTING ________________________________________________2-1
2.4 CHECKOUT AND PRELIMINARY ADJUSTMENTS ______ Error! Bookmark not defined.
Chapter 3 OPERATING INSTRUCTIONS ______________________________________3-4
3.1 CONTROLS AND INDICATORS_______________________________________________ 3-4
3.1.1 Local Operation ________________________________________________________________ 3-4
3.1.2 Remote Current Programming _____________________________________________________ 3-7
3.1.3 Remote Voltage Programming _____________________________________________________ 3-7
3.1.4 Remote Sensing ________________________________________________________________ 3-8
3.1.5 Remote Output On/Off Control_____________________________________________________ 3-8
3.1.6 Auto-Parallel Operation __________________________________________________________ 3-9
3.1.7 Auto-Series Operation ___________________________________________________________ 3-9
3.1.8 Auto-Tracking Operation _________________________________________________________ 3-9
3.1.9 Output overvoltage Protection ____________________________________________________ 3-10
Chapter 4 MAINTENANCE AND CALIBRATION _______________________________ 4-1
4-1. INTRODUCTION ___________________________________________________________ 4-1 4-2. PREVENTIVE MAINTENANCE _______________________________________________4-1 4-3. CALIBRATION AND ADJUSTMENTS _________________________________________4-3
4.1.1 Converter Assembly Calibration____________________________________________________ 4-3
4.1.2 Display Assembly_______________________________________________________________ 4-6
M520086-01 vi
LIST OF TABLES
TABLE 1-1 3300 SERIES TECHNICAL CHARACTERISTICS......................................................1-2
TABLE 1-2 3300 SERIES TECHNICAL CHARACTERISTICS......................................................1-4
TABLE 2-1 3300 SERIES INPUT/OUTPUT CONNECTORS........................................................2-2
TABLE 3-1 3300 SERIES CONTROLS AND INDICATORS..........................................................3-5
TABLE 3-2 BARRIER STRIP (TB1) DESIGNATIONS AND FUNCTIONS....................................3-6
TABLE 4-1 PREVENTIVE MAINTENANCE SCHEDULE.............................................................. 4-1
TABLE 4-2 INSPECTION AND CORRECTIVE ACTION...............................................................4-2
LIST OF FIGURES
FIGURE 3-1 3300 SERIES CONTROLS AND INDICATORS ....................................................... 3-4
FIGURE 3-2 NORMAL CONNECTION PATTERN......................................................................3-11
FIGURE 3-3 REMOTE RESISTANCE PROGRAMMING OF OUTPUT CURRENT ...................3-11
FIGURE 3-4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT CURRENT .........................3-12
FIGURE 3-5 REMOTE RESISTANCE PROGRAMMING OF OUTPUT VOLTAGE....................3-12
FIGURE 3-6 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE..........................3-13
FIGURE 3-7 REMOTE SENSING OPERATION..........................................................................3-13
FIGURE 3-8 REMOTE ON/OFF CONTROL BY CONTACT CLOSURE..................................... 3-14
FIGURE 3-9 REMOTE ON/OFF OPERATION USING AC/DC VOLTAGE SOURCE................. 3-14
FIGURE 3-10 AUTO-PARALLEL OPERATION........................................................................... 3-15
FIGURE 3-11 AUTO-SERIES OPERATION................................................................................ 3-16
FIGURE 3-12 AUTO-TRACKING OPERATION.......................................................................... 3-17
M520086-01 vii
Chapter 1

DESCRIPTION OF EQUIPMENT

1.1 PURPOSE AND CAPABILITIES
The Power Ten 3300 Series power supplies are general purpose power supplies designed specifically for laboratory test and system s applicat ions r equiring variable DC sources with good regulation and low output ripple characteristics. Models of the 3300 Ser ies are constant current/constant voltage supplies with an automatic cr ossover feature. They provide up to 1000 watts of DC power over a wide range of voltage and current levels.
1.2 TECHNICAL CHARACTERISTICS
The physical, electrical and environmental characteristics for the 3300 Series are listed in Tables 1-1 and 1-2.
M520086-01 1-1
Table 1-1
3300 Series Technical Characteristics
PARAMETERS
PHYSICAL CHARACTERISTICS:
Width Depth Height Weight
ELECTRICAL CHARACTERISTICS:
Input Power (Standard) Voltage Frequency Phases
Regulation (Line or Load) Voltage Current
Noise and Ripple (RMS) Transient Response
Stability
Remote Control/Monitor
Power Density Power Factor Total Harmonic
SPECIFICATIONS
19.00 in.
18.50 in
1.75 in. 15 lb. max.
95 to 127 VAC, 190 to 253 VAC (Option) 47 to 63 Hz Single, 2-wire plus gnd
0.1% of max. output voltage
0.1% of max. output current 30 mV max. A 30% step load will recover to within 2%
of original value within 10 ms.
0.05% of set point per 8 hr. after warm-up
+ and at a fixed line, load and temperature.
On/Off cont r ol via contact closur e, 6-120 VDC or 12-240 VAC.
2.5 Wat t s/cubic in. .99 min. at full load
2.5% max.
M520086-01 1-2
3300 Series Technical Characteristics - Continued
PARAMETERS Remote Programming Resistive:
Constant Voltage (0-100%) Constant Current (0-100%)
Voltage: Constant Voltage (0-100%) Constant Current (0-100%)
Current: Constant Voltage (0-100%) Constant Current (0-100%)
Remote Sensing
ENVIRONMENTAL CHARACTERISTICS:
Temperature Coefficient
Ambient Temperature Operating Storage
Cooling
Table 1-1
SPECIFICATIONS
0 - 5k ohms 0 - 5k ohms
0 - 5 VDC 0 - 100 mV
0 - 1 mA 0 - 1 mA
Terminals are provided to sense output voltage at point of load. Maximum line drop 3% of rated voltage per line.
0.02%/°C of max. output voltag e rating for voltage set point.
0.03%/°C of max. output curr ent r ating for current set point.
0 to 50°C
-40° to 75°C Internal blowers
M520086-01 1-3
Table 1-2
3300 Series Technical Characteristics
MODEL NUMBER
7.575
7.5125 1060
10100
2030 2050 3020 3033 4015 4025 5020 6010 6016 8006 8012
10010
1208 1507
OUTPUT DC
VOLTS
0-7.5 0-7.5
0-10 0-10 0-20 0-30 0-30 0-30 0-40 0-40 0-50 0-60 0-60 0-80
0-80 0-100 0-120 0-150
OUTPUT DC
AMPS
75
125
60
100
30 50 20 33 15 25 20 10 16
6 12 10
8
7
OUTPUT
RIPPLE (RMS)
30 mV 30 mV 30 mV 30 mV 30 mV 30 mV 30 mV 30 mV 30 mV 30 mV 30 mV 30 mV 30 mV 50 mV 50 mV 50 mV 50 mV 50 mV
M520086-01 1-4
Loading...
+ 24 hidden pages