Powersolve HSD10001 User Manual

Smar
t start
-
up with critical loads
:
HSD10001 DIN Rail
Made in Germany 1000 Watt Power Supply -25...+70°C
340...575Vac 2 & 3 phase, PFC & low inrush current Specification:
Metal housing
92% efficiency typ.
-25°C...+70°C ambient
Natural convection
Galvanic insulated
Continuous short circuit protected
Overload & low voltage protected
Soft start & auto-recovery
Hold up time >12ms
Minimum load = 0A
- motor drives
- capacitive loads
- DC-DC-converters
- Batteries
Single-Output: 12V, 24V, 36V, 48V, 60V, 72V
Powersolve Electronics Ltd., Unit 8A Arnhem Road, Newbury RG14 5RU, United Kingdom Tel 0044 (0)1635 521858 Fax 0044 (0)1635 523771
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
Inrush Current <20Apeak 14,4Aeff (400Vac)
EMI/EMS EN61000-6-2/3, EN55022 class B
PFC: EN61000-3-2
According to cUL60950, IEC(EN)60950-1
Low voltage & overload control message
Remote Shutdown ON/OFF
Power good relay galvanic insulated
Screw terminals AWG21...AWG6
High reliability, shock & vibration resistant
Output Electrolytic Capacitors +125°C
2 phase operation 75% rated load
In accordance with IEC60950-1
www.powersolve.co.uk sales@powersolve.co.uk
p.1/4 05.12A
AC
Input 2PH & 3
PH
340...575Vac , 47...63Hz ,
450…82
0
Vdc (2 phase operation 75% rated load max.)
AC
Input Rating
400...500Vac
(Input Current 3x 3A)
DC Voltage Adjust
10...17V
(12V) 22..30V
(24V) 32...43V
(36V) 43...53V
(48V) 53...72V
(60V)*
68...86V
(72V)*
Voltage Protection
21Vdc
32Vdc
50Vdc
56Vdc
84Vdc
92Vdc
Current 60°C*
50.0A (12Vdc)
40.0A (24Vdc)
28.0A (36Vdc)
21.0A (48Vdc)
17.0A (60Vdc)
14.0A
(72Vdc)
DC Current 40°C*
50.0A (12Vdc)
45.0A (24Vdc)
31.0
A (36Vdc)
23.0A (48Vdc)
18.0A (60Vdc)
15.0A (72Vdc)
Boost 60s/
60°C*
55.0A (12Vdc)
44.0A (24Vdc)
30.8A (36Vdc)
23.1A (48Vdc)
18.7A (60Vdc)
16.3A
(72Vdc)
Ripple
20MHz
50mVpp
50
mVpp
80
mVpp
100 mVpp
100 mVpp
150 mVpp
Load reg
ulation.
*
±0.5%
(12Vdc)
±0.2% (24Vdc)
±0.2% (36Vdc)
±0.2% (48Vdc)
±0.2% (60Vdc)
±0.2%
(72
Vdc)
*400Vac input
*Power Good Relay
& Shutdown
: no
protective electrical separation
>60Vdc
!
Tolerance
( at
Ua adjusted
) ± 0.5%
Transient Time
<1ms
(10-100%
, 100-10%)
Minimum Load
0 A
Efficiency
92% typical
L
oad Protection
1,2
x I
rated
, auto recovery
Short Circuit Protection
Yes
Te
mperature Control
Yes (see
right
graph
)
Hold Up Time
> 12ms (400...500
Vac input)
Inrush Current Lim
i
ter < 20A
peak 14,4Aeff
(400
Vac)
Softstart
50ms typical
C
ooling
Natural convection
Ambient Temperature
-
25°C…+70°C
Storage Temperature
-
40°C…+85°C
EMI EN55022 class B / EN61000
-3-2
EMS EN61000
-6-
2,3 active PFC
Safety
UL60950 , (IEC)EN60950
-1
Safety class 1(A)
VDE0805, VDE0100
Creepage D
istance
> 10,5
mm
Input / Output
Galvanic insulated
3000Vac
Power Good
Relay (galv.
Ins.)
48Vdc/500mA , 30Vac/500mA
Relative Humidity
95% (25°C) non
-
condensing
Pollution Degree
2 (EN50178)
Climat
ic Class
3k3 (EN60721)
MTBF IEC61709
500000h (IEC61709)
Dimensions (HxWxD)
131.5x200
x124.5mm
Weight
3400g
Connectors (AC & DC)
AWG22...AWG6
(0,5...16mm²)
The
HSD10001
DIN Rail power supply series is designed
for worldwide
electronics
applications
like m
achine building, railway
,
Block Di
a
gram
For further
0-100% 100-0%
derating information
Temperature Control:
If the ambient temperature (ta) 40°C the HSD provides I/Boost continuously and if ta 60°C I derating continuously lowers Vout 2,5%/Kelvin. If ta >70°C (or thermal overload occures) the HSD shuts down. It auto-recovers when the device cools down to approved operation conditions.
is provided continuously. If ta >60°C
rated
see table page 3
(see page 4)
All parameters are specified at +25°C, 15 minutes run in time if not named otherwise.
IEC60664-1, IEC61984
Specification:
military and factory automation. Its regulated DC output with ripple/noise lower than 50mVpp and its high efficiency of 92% makes the HSD robust, economical and reliable. Camtec power supplies are traditionally made with high end low ESR electrolytic output capacitors withstanding +125°C temperature. Our capacitors are rather designed over for longer lifetime and longer hold up times. The power-boost of the HSD starts DC-loads and DC-motors reliable. The built in function diagnostics detects malfunctions. The galvanic insulated DC fail relay and remote on/off provides full control over the power supply unit. The HSD is short circuit and zero load stability protected. It is protected against high transient and provides very good interference resistance. Equal types of the HSD10001 can be operated in parallel or in series connection. We use IP20 stabile aluminum housings with ventilation slots in accordance to the demanding VDE norms. The design meets EN(IEC)60950-1 and low voltage directive EN55022 Class B.
1) Transient Suppressor (VDR) & Filters, Input Fuses
2) Rectifier
3) Electronic Inrush Current Limiter
4) PFC
5) Load Capacitor C
6) Potentiometer (P)
Complex sane filter technology using varistors, supression diodes and X2 capacitors, apply major transient resistance to the input filter. Overload: If <0.9xVout applies to the outputs, the red LED lights and the DC-OK-Relay (Re) drops (control message). The green DC-OK LED is off.
Powersolve Electronics Ltd., Unit 8A Arnhem Road, Newbury RG14 5RU, United Kingdom Tel 0044 (0)1635 521858 Fax 0044 (0)1635 523771
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
www.powersolve.co.uk sales@powersolve.co.uk
p.2/4 05.12A
Remote Shutdown
voltage
shutdown the
LED lights and 0V
or
<500mV are applied to (Rmt/Rm),
the yellow LED
V is distributed
isable the remote voltage to restart
Power Good Control
Series Connection
Redundant Connection
Inrush Current Limitation (Block Diagram)
Power Boost and Temperature Behaviour
Output voltage/current ratio to ambient (U/I to °C)
40°C/Iout
60°C/Iout
Uout 40°
C/Iout
60°C/Iout
Test Time A B C D
Type Test
Factory Test
Field Test
Function Table
and Messages
To increase the output power, equal HSD devices can be used series connected. Observe to safety directives when the output voltage achieves 60Vdc in sum.
Enable a 18…30Vdc 20mA signal to (Rmt/Rm) to HSD, the yellow is distributed to the outputs. If the shutdown is short circuited
the HSD „tickers“, flashes and Uout <5 to the outputs. D the HSD
To increase system availability up to fife HSD can be used in parallel operation mode. Please make sure that wiring length from all units to the load is equal. Full redundant operation modes require external diodes. We suggest to use our RED00202 DIN-Rail N+1 redundant module für professional redundancy.
Low Voltage: If adjusted Vout drops 10% the red LED lights and the DC-OK-Relay (Re) drops (control message). The green DC-OK LED is off. Overload: If <0.9xVout applies to the outputs, the red LED lights and the DC-OK-Relay (Re) drops (control message). The green DC-OK LED is off. Vout o.k. = relay closed Vout fail = relay open
While connecting the HSD to the AC wire network its inrush current is limted to <20Apeak/14,4Aeffective. The start capacitors are loaded after 20ms and the HSD actuates. After passing softstart the power supply is ready for operation after a total of
Ʌ
t=400ms.
Characteristics Vi=400Vac:
Peak Inrush Current = <14,4Aeff. Peak Limiting Duration = 20ms
The HSD10001 operates in accordance to the V/C-characteristic line (see graph I/Boost on page 2). It has a determinate power reserve (boost): With ambient temperatures 40°C the power boost is continuously available while with higher ambient temperatures it is available for a few minutes. When a DC short circuit or an overload occurs to the HSD10001, it is limited to I/Boost (see graph) but it is not shot down. The DC-voltage is lowered until the error is rectified. The V/C-line and the power boost apply operation of critical loads, like DC-DC-converters, capacitive loads, drives and batteries trustworthy.
Uout
10Vdc 50,0A
12Vdc 15Vdc 22Vdc 24Vdc 26Vdc 28Vdc 30Vdc 32Vdc 34Vdc
50,0A 50,0A 45,0A 45,0A 42,0A 38,0A 35,0A 34,0A 32,0A
50,0A 36Vdc 50,0A 40Vdc 50,0A 46Vdc 43,0A 48Vdc 40,0A 53Vdc 37,0A 60Vdc 34,0A 65Vdc 32,0A 72Vdc 31,0A 86Vdc 31,0A
31,0A 27,0A 24,0A 23,0A 21,0A 18,0A 17,0A 15,0A 12,6A
28,0A 25,0A 22,0A 21,0A 20,0A 17,0A 16,0A 14,0A 11,7A
Type test and factory tests are
60s 2500Vac 3000Vac 500Vdc 500Vdc 5s 2000Vac 2000Vac 500Vdc 500Vdc 2s 2000Vac 2000Vac 500Vdc 500Vdc
conducted by the manufacturer.
Do not repeat the test in field.
Field test rules:
a) Use approriate test equipment which apply the voltage with a slow ramp b) Connect L1,L2 and L3 together, as well as all output poles c) Use only AC test-voltages with 50/60Hz. The output voltages is floating and has
no ohmic reference to ground.
d) If testing output voltages are 60Vdc remain to security directives.
Use only isolated screw drivers to adjust output voltages.
Indicators DC-ok
LED green Normal operation On Off Off Closed Power boost On Off Off Closed Overload (0.9xVout) Off On Off Open Shutdown with open contact On Off Off Closed Shutdown with 10..30Vdc Off Off On Open Shutdown with <500mVdc Off Pulse Pulse Open Temperature shutdown Off Off Off Open Input voltage low or fail Off Off Off Open
Overload LED red
Shutdown LED yellow
DC-ok Relay
Powersolve Electronics Ltd., Unit 8A Arnhem Road, Newbury RG14 5RU, United Kingdom Tel 0044 (0)1635 521858 Fax 0044 (0)1635 523771
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
www.powersolve.co.uk sales@powersolve.co.uk
p.3/4 05.12A
Terminal Connects:
DC +
Optional Coating (option C)
:
Order Codes
:
Rail
Options to be added to the order
-
code:
Mechanics
&
Installation
of the
HSD10001
:
Safety Instructions:
Connectors
35mm DIN
-
Rail (EN60725)
Input L1
L2 L3
We offer the HSD-Series with optional coating. It is to be used in e.g. dusty, dirty, high humidity, or in awaiting quick temperature changes. Short circuit and corrosion at print board lines and at solder points can be prevented. The coat itself is a transparent acrylic resin. It is procured with a robotics varnishing machine. Peters SL 1306 N-FLZ (transparent) IEC60216-1 2001, IPC-CC-830B, UL listed as permanent coating FileNo.: E80315 , UL94V-0
GND
Output DC + DC ­ DC -
Control & monitoring connections: A= parallel/series mode switcher B= DC-OK Relay C= Remote On/Off (shutdown)
Screw terminal order codes: DC-fail-relay& Shutdown, one plug for each required (each package = 10 pcs ) Art.No.: 3520037 (2 pins)
HSD10001.12T 10..17Vdc DIN­HSD10001.24T 22..30Vdc DIN-Rail HSD10001.36T 32..43Vdc DIN-Rail
Stable metal/aluminium housing IP20. To allow adequate convection, a free air space of 50mm (top/bottom) and 5mm (sidewalls) is required for the HSD10001; for active devices 15mm space from the HSD-sidewalls. For free air convection it is necessary to install the HSD horizontal (Figure1). You can use the DIN-Rail installation (equiped standard) with our patented 35mm DIN-Rail bracket according to EN60275. It is easy to mount/dismount while snaping it onto the 35mm DIN-Rail without any tools necessary.It is a wallmount fastener available as option, too. Use the wall mount option for baseplate-cooling. Consult our support for further information.
HSD10001.48T 43..53Vdc DIN-Rail HSD10001.60T 53..72Vdc DIN-Rail HSD10001.72T 68..86Vdc DIN-Rail
C=coating exs: HSD10001.24TC DIN-Rail+Coating
Backplate-kit (wall-mount):
220.1002.001CA (including Screws)
Fig.1
Wiring Solid Flexible AC-Input & DC-Outputs Rated Current 76A (+40°C) 76A (+40°C) Signal Outputs (A,B)
(IEC60664-1 , IEC61984)
0,5...16mm²
22...6 AWG
0,2...2,5mm²
25...14 AWG
0,5...14mm²
22...7AWG
0,2...2,5mm²
25...14 AWG
ready to hand.The HSD must be installed by specialist staff only.
Installation:
1.) The HSD is designed for systems fulfilling the safety norms of dangerous voltages/energy and fire prevention
2.) Installation is restricted to specialists only, make sure that the AC wire system is free of voltage
3.) Opening the HSD, making any modifications to it, dismounting any screws from it, operating the HSD out of specification and/or using it in appropriate area will unevitably result in loosing manufactureres guarantee; we decline taking any responsibility for risk of demages caused to someones health or to any installed system.
4.) Attention: The HSD has an internal input fuse. It is necessary to wire an automatic circuit braker to the line. We suggest to use a 10A-type with B-characteristic. It is verboten to operate the HSD without protective earth wired. It essential to install a line switch before the HSD.
Please read all warnings and advices carefully before installing or operating the HSD. Retain this operation manual always
Warnings
Disregard these warnings can cause fire, electic shock, serious accident and death.
:
1. Never operate the HSD without Protective Earth Conductor
2. Before connecting the HSD to the AC wire system make all wires free of voltage and assure accidently switch on
3. Allow neat and professionel cabeling
4. Never open nor try to repair the HSD by yourself. Inside are dangerous voltages that can cause electric shock hazard.
5. Avoid metal pieces or other conductive material to fall into the HSD
6. Do not operate the HSD under damp or wet conditions
7.
It is verboten to operate the HSD under Ex conditions or in Ex-Area
Powersolve Electronics Ltd., Unit 8A Arnhem Road, Newbury RG14 5RU, United Kingdom Tel 0044 (0)1635 521858 Fax 0044 (0)1635 523771
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
www.powersolve.co.uk sales@powersolve.co.uk
p.4/4 05.12A