Powercom 1000, 2000, 3000 User Manual

U P S
On Line
1000VA - 3000VA
USER’S MANUAL■
These products have been tested and thereby comply with the condition of a Class C1 (1000VA) and Class C2 (2000VA and 3000VA), which has been established for offering sufficient protection against dangerous interference for installation in a residential area. Installation and use of the equipment should comply with the instructions provided in order to avoid such interference due to the amount of radio frequency energy that is radiated and generated by the equipment. In spite of this, we cannot assure that a certain amount of interference may not occur in some installations.
If, by turning on and off, it can be deduced that your radio or television reception is found to be influenced by harmful interference from the equipment, it is recommended to use one of the following preventive measures:
Place the receiving antenna in a separate location or orientation.
Ensure a greater distance is achieved between the receiver and the
equipment.
Ensure that your equipment is connected to an outlet on a separate circuit
than the receiver.
Contact a technician experienced with radio and TV or a dealer for
further assistance.
Declaration of Conformity Request
Units labeled with a CE mark comply with the following standards and instructions:
Safety: EN 62040-1 EMC: EN 62040-2 EMC Directive: 2014 / 30 / EU LVD Directive: 2014 / 35 / EU
The EC Declaration of Conformity is available upon request for products with CE mark.
i
CONTENT
IMPORTANT SAFETY INSTRUCTIONS ........................................... 1
1. Introduction ......................................................................... 2
2. System Description ............................................................... 2
3. Storage ................................................................................ 2
4. Installation .......................................................................... 3
4.1 Unpacking Package ................................................................. 3
4.2 Hardware Installation .............................................................. 4
4.3 Environment .......................................................................... 4
4.4 Rear panel view ...................................................................... 2
4.5 Connection to batteries ........................................................... 4
4.6 Connection to mains and loads ................................................ 4
5. UPS Monitoring Connection .................................................. 5
5.1 Connect UPS to Computer with USB / RS232 port ...................... 5
5.2 Connect UPS with RS232 port .................................................. 5
5.3 Connect UPS with interface slot (Optional) ................................ 5
5.4 EPO port (Emergency Power Off) (Optional) .............................. 5
6. Operations ........................................................................... 6
6.1 General description ................................................................ 6
6.2 System Configuration .............................................................. 7
6.3 LCD panel overview ................................................................ 8
6.4 LCD control panel ................................................................... 9
6.5 UPS status display ................................................................. 10
6.6 UPS configurations ................................................................ 11
7. Battery Maintenance .......................................................... 12
7.1 Internal Battery replacement (For Rack Mounting Model) ......... 12
7.2 External Battery Pack ............................................................ 12
8. Trouble Shooting ................................................................ 13
8.1 Trouble shooting (Error code) ................................................ 13
9. Technical Specifications ...................................................... 14
ii
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that
should be followed during installation and maintenance of the UPS and batteries. The equipment can be operated by any individuals with no previous experience.
WARNING: It is highly recommended to install the product in a controlled environment;
maximum ambient temperature is 40°C.
CAUTION: Risk of electric shock – Please refer to the details on the cautionary markings at top,
or rear, or bottom of UPS.
CAUTION: Risk of electric shock – Heat-sinks are live. Disconnect unit before servicing. CAUTION (UPS has internal batteries): Risk of electric shock – Hazardous live parts inside this
unit is energized from the battery supply even when the input AC power is disconnected.
CAUTION (No user serviceable parts): Risk of electric shock – do not remove cover, no user
serviceable parts inside. Refer service to qualified service personnel.
CAUTION (Non-isolated battery supply): Risk of electric shock – battery circuit is not isolated
from AC input. Hazardous voltage may exist between battery terminals and ground. Test before touching.
WARNING (Fuses): To reduce risk of fire, replace only with the same type and rating of fuse. CAUTION: Do not disconnect battery connector under load. ATTENTION: Hazardous through electrical shock. Also with disconnection of this unit from the
mains, hazardous voltage still may be accessible through supply from the batteries. The battery supply should therefore be disconnected in the positive and the negative pole when maintenance or service work inside the battery cabinet or UPS is considered.
CAUTION (For any pluggable only): With the installation of this equipment it should be
prevented, that the sum of the leakage current of the UPS and connected consumer does not exceed 3.5 mA.
CAUTION (For permanent connection only): HIGH LEAKAGE CURRENT, Earth connection
essential before connection supply.
CAUTION: Do not dispose of batteries to fire, the battery may explode. CAUTION: Do not open or mutilate the battery, released electrolyte is harmful to human skin,
eyes, etc.
CAUTION: A battery can bring risk of electric shock and high short circuit current.
The following precaution should be observed when working on batteries: A. Remove watches, rings or other metal objects. B. Use only tools with insulated handles. C. Wear rubber gloves and boots. D. Do not lay tools or metal parts on top of batteries. E. Disconnect charging source prior to connecting or disconnecting battery terminals. To reduce risk of electric shock, disconnect the UPS from the mains supply before installing a computer interface signal cable. Reconnect the power cord only after signaling interconnections have been made. Servicing of batteries should be performed or supervised by personnel with knowledge of batteries and the required precautions. Keep unauthorized personnel away from batteries.
CAUTION: When replacing batteries, replace with the same type and number of batteries:
One Sealed lead acid battery, rated 12 V, 9 AH max.
CAUTION: To reduce risk of fire, use only No.26 AWG or larger telecommunication line cable. CAUTION: Do not apply for uses in a computer room as defined in the Standard
for the Protection of Electronic Computer \ Data Processing Equipment, ANSI/NFPA75.
CAUTION: This UPS is not applicable for motors, hair dryers, speakers, and fluorescent lamps. User’s operations:
The only operations that users are permitted to do are:
Turning the UPS unit on and off.
Operating the users interface.
Connecting data interface cables.
Changing the batteries.
All such operations are to be performed exactly as instructed in this manual. The greatest care possible must be taken for any of these operations and any change thereof may prove very
hazardous to the operator. The instructions contained within this safety manual are deemed important and should be closely followed at all times during installation and follow-up maintenance of the UPS and batteries.
1
© All rights reserved. All trademarks are property of their respective owners.
CAUTION
The unit has a dangerous amount of voltage. If the UPS indicator is on, the
unit’s outlets may have a dangerous amount of voltage even when not plugged into the wall outlet because the battery may continue to supply power. Cares should be taken to undertake installation indoors free from electrically-conductive particles which is under temperature and humidity control in order to reduce the risk of electric shock. It is best to disconnect the device using the power supply cord. Ensure that the equipment is placed in a position near the outlet where easily accessible. Except replacing the batteries, all service on this equipment must be carried out by qualified service personnel. Before conducting any maintenance, repair or shipment, first ensure that everything is turned off completely and disconnected.
1. Introduction
The information provided in this manual covers on-line single phase 1KVA to 3VA UPS (Uninterruptible Power System). This manual is about the basic functions, operating procedures, emergency troubleshooting, and also including the information about on how to ship, store, handle and install the equipment. Only detailed requirements of the UPS units are described herein, and installation must be carried out in accordance with this manual. Electrical installations must also carefully follow local legislation and regulations. Only qualified personnel should conduct these installations as failure to acknowledge electrical hazards could prove to be fatal.
2. System Description
Several different kinds of sensitive electrical equipment stay protected by a UPS (Uninterruptible Power System) including computers, workstations, process control systems, telecommunications systems, sales terminals, other critical instrumentation, etc. The purpose of the UPS is to protect these systems from poor utility power quality, complete loss of power, or other associated problems.
Electrical interference abounds in many forms causing problems in AC power, from lightning, power company accidents and radio transmissions to motors, air conditioners, and vending machines, among others. So protection of sensitive electrical equipment is vital to protect against power outages, low or high voltage, slow voltage fluctuations, frequency variations, differential and common-mode noises, transients, etc.
In order to prevent power line problems reaching critical systems causing damage to software, hardware and causing equipment to malfunction, the UPS helps by maintaining constant voltage, isolating critical load output if needed, and provides clean utility AC power.
3. Storage
Please adhere to the following instructions if the UPS is not installed immediately:
Store the equipment as is in its original packing and shipping carton. Do not store in temperatures outside the range of +15°C to +25°C. Ensure that the equipment is fully protected from wet or damp areas and from moist air.
In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6 months for at least 8 hours.
Storage and Transportation
© All rights reserved. All trademarks are property of their respective owners.
Please handle the unit with extreme caution since a high amount of energy is contained with the batteries. Always keep the unit in position as marked on the packaging and never drop the unit.
2
4. Installation
1K
Tower Type UPS
Rack Type UPS
1K or 2K/3K Tower/Rack Type UPS
2K/3K
Power Management Software
(Option)
Users Manual
Rack Tower Stand (4)
(Rack Model Only)
(Rack Model Only)
Rack Mounting Ears (2)
USB Cable
POWER Cord
RS232 Cable
2K/3K
1K
M5X8L(8) Screw
M5X8L(8) Screw
4.1 Unpacking Package
© All rights reserved. All trademarks are property of their respective owners.
3
4.2 Hardware Installation
Rack Tower Stands Installation
Attach four rack tower stands to UPS, using provided M5 screws *8pcs.
The demonstrations of UPS tighten up with rack tower stands.
Rack Mounting Ears Installation
Attach two rack mounting ears to UPS, using provided M5 screws *8pcs.
The demonstrations of UPS tighten up with rack mounting ears.
4.3 Environment
Please follow below instructions about locating the UPS system and battery option or the safety of installation personnel cannot be guaranteed and the unit may malfunction.
Please ensure no flammable substances such as gases or fumes are present. Avoid extreme temperature and humidity. Protect the equipment from moisture. Ensure there are enough space at the behind and side of UPS for well ventilation. Ensure that the front of the UPS remains clear for user operation. Battery lifecycle could be extended with recommended temperature range of 15 °C to 25 °C. It is highly recommended that The External Battery Packs are next to or under the UPS. Only a technician from the manufacturer or an authorized agent may service the unit. Do not open UPS cabinet as the components may contain high voltage and may be fatal. The output receptacles may carry live voltage even when it is not connected to power supply.
4