Recirculating Coolers —
Model 3370 Liquid-to-Air Cooler
Key Specifications
Working Temperature Range: Ambient +5 to 70°C
Maximum Fluid Temperature: 70°C
Cooling Capacity: 4000 W based on 11°C ǻT
Reservoir Capacity: 1.1 gallons/4.2 liters
Overall Dimensions 20.5 x 15 x 22.3"
(L x W x H): 52 x 38.1 x 56.6 cm
1
(water)
Features:
• An economical cooling solution for applications where
cooling fluid temperature is higher than ambient and
temperature control is not required
• Quiet liquid-to-air cooling
• Positive displacement or turbine pump
• Built-in low liquid level indicator
Liquid-to-air cooling uses ambient air to cool your
application. Heated process fluid is pumped through the
3370’s fan-cooled heat exchanger and returned
to the process.
C 155859 US
Temperature Range Ambient to 70°C
Cooling Capacity @
20°C (W)
Power Requirements (V/Hz) 120/60 240/50 120/60 240/50
Pump 1/3 HP Positive Displacement 1/3 HP Turbine Pump
Maximum Pressure psi (bar) 100 (6.9) 100 (6.9) 62 (4.3) 50 (3.4)
Maximum Flow gpm (l/min) 2.4 (9.1) 2 (7.6) 5.4 (20.5) 4.5 (17.1)
Part Number 120 VAC/60 Hz 3370P9A11B 3370TBA11B
Part Number 240 VAC/50 Hz 3370P9A12E 3370TBA12E
500 based on 2°C ǻT
1000 based on 4°C ǻT1
2000 based on 8°C ǻT1
3000 based on 10°C ǻT1
4000 based on 11°C ǻT
Front-mounted gauge lets you check process pressure at a glance.
1
1
ǻT = Process water temperature — ambient air temperature
See pages 124 and 125 for considerations when choosing a chiller.
Electrical plugs for the part numbers listed are standard U.S. and European types. See page 128 for additional plug types and part numbers.
www.polyscience.com |www.polyscience.com |
107