Polaris Watermatic C316 Owner's Manual

C316 ORP Controller with pH Display, 24 Volt
O WNER’S MANUAL
Table of Contents
I. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
II. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
III. Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
A. Timed Feeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
B. Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . .5
V. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
A. Feeding Systems . . . . . . . . . . . . . . . . . . . . . . . . . .6
B. Controller Installation . . . . . . . . . . . . . . . . . . . . . . .6
C. Flow Cell Installation . . . . . . . . . . . . . . . . . . . . . . .7
D. Sensor Installation . . . . . . . . . . . . . . . . . . . . . . . .11
E. Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
F. Start-up Operations . . . . . . . . . . . . . . . . . . . . . . .11
G. Sanitizer Settings . . . . . . . . . . . . . . . . . . . . . . . . .12
H. pH Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . .13
VI. Panel Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
VII. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
A. Setting Feed and Delay Times . . . . . . . . . . . . . . .15
B. Feed Light Activation . . . . . . . . . . . . . . . . . . . . . .15
C. Out-of-range Indicator . . . . . . . . . . . . . . . . . . . . .16
D. Manual Feed . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
E. Winterizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
VIII. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
A. Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
B. Cleaning the Sensor Tips . . . . . . . . . . . . . . . . . . .17
C. Checking the ORP Sensor . . . . . . . . . . . . . . . . . .18
D. Checking the pH Sensor . . . . . . . . . . . . . . . . . . .18
IX. Erosion Feeder Operating Tips . . . . . . . . . . . . . . . . .19
X. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
XI. Guidelines for Using ORP for Water Maintenance . . .22
XII. Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
POWER
ON
OFF
MAINTAIN PROPER pH
FEED
MANUAL
pH
ADJ.
FEED
C-316 ORP Controller w/pH Display, 24 V
6
.
6
6
.
8
7
.
0
7
.
2
7
.
4
7
.
6
7
.
8
8
.
0
8
.
2
8
.
4
¥
2
0
0
¥
3
0
0
¥
4
0
0
¥
5
0
0
¥
6
0
0
¥
7
0
0
¥
8
0
0
¥
9
0
0
¥
1
0
0
0
¥
1
0
0
D
E
C
R
E
A
S
E
¥
I
N
C
R
E
A
S
E
O
R
P
p
H
2
I. Introduction
For your protection, read all instructions carefully before installing or operating this automatic controller.
The Polaris Watermatic®C316 24-Volt Controller is designed to automatically monitor and maintain the sanitizer level and pH balance in swimming pools, spas and any circulating water sys­tem that requires water chemistry management.This controller is designed for easy installation and simple operation, and is used with tablet erosion feeders.
During the filtration cycle of the pool or spa, the sanitizer level and pH balance are maintained by a constant measurement of the ORP (Oxidation-Reduction-Potential) and pH balance of the water. Levels are displayed on the controller’s ORP and pH light bar arrays (see Figure 1).If the sanitizer level (ORP) falls below a predetermined set point, the controller activates the chemical feeder until the preset level is reached.The pH is maintained in a similar manner.
Figure 1
3
II. Specifications
pH Range: 7.0 - 8.2 ORP Range: 100 mV to 1000 mV Input Power: 24 VAC 50/60 Hz, 40 Volt Amp
(transformer included)
Controller Power: Less than .5 Amp internally fused Output Power: 24 VAC 50/60 Hz, 5 Amp fuse Display: Light Bar Array — Yellow for ORP,
Green for pH
Operating Temperature: 40°-120° F
Sensors: ORP: platinum combination with 10'
cable; pH: glass combination with 10' cable
Selectable Features:
Desired ORP settings
pH calibration
Safety lockouts for low or high (out of range) ORP levels
Visual alert and optional audible aler t for self-correcting and
non-correcting conditions
III. Components
The C316 Controller box contains:
C316 Controller
ORP Sensor (part #3-270)
pH Sensor (part #3-260)
•110 V to 24V Plug-in Transformer (part #9-620)
1/2" Jaco Compression Fittings (part #2-260) Recommended (optional) components include:
Flow Cell Assembly (part #9-700)
4
IV. Pre-installation
Before installing the controller, it is impor tant to do a site assessment and consider where and how you will mount the unit.The controller should be mounted on a wall or other sur­face at least ten feet away from the edge of the water and less than six feet from the GFCI power source.
Once the best site is selected, obtain all necessary mounting screws or anchors (no mounting screws are provided with controller). Seal-tight or strain relief connectors for the electrical access holes in the control box and electrical wire will also be needed.
A. Timed Feeds
The controller was designed with the flexibility to be adjusted to meet individual user applications. Feed times and aler ts can be adjusted through optional dip switch settings.To access and adjust the dip switches, located on the back of the board (see Figure 2), disconnect the controller from the power source and remove the three mounting screws.
The timed feed and delay option allows the use of erosion feed­ers on spas and small bodies of water without spiking. An auto­matic shut down feature that can be adjusted for small pool/spa applications. Additionally, the timed feed allows the injection of sanitizer before the ORP/pH sensors.
Pool Spa
For Remote Monitoring
Flow Jumper
Transformer
OFF ON
1 2 3 4 5 6
Dip Switches
Figure 2
5
B. Switch Settings
1. Dip switches #1 and #2 control the feed times. Feed times
vary depending on whether the controller is in the pool or spa mode.
Note: Once the settings have been modified, move the Pool/Spa Switch on the front of the controller to the appro­priate mode to activate the changes. Refer to Figure 4.
2. Dip switch #3 controls the delay time between feeds.
OFF 30 sec.
ON 7 min.
3. Dip switch #4 must be in the OFF position.
4. Dip switch #5 controls the low ORP shutoff.
The controller is set to shut down when the ORP level drops below 100 mV.This prevents overfeeding if there is an ORP sensor failure.
Moving switch #5 to the OFF position will override this function.This override might be required in extremely small bodies of water where sudden organic loads dissipate the sanitizer in a very short time.
5. Dip switch #6 has no assigned function.
Pool Position
Dip Switch Feed
12 Time
OFF ON 1 min.
ON ON 5 min.
OFF OFF 10 min.
Spa Position
Dip Switch Feed
12 Time
OFF OFF 1 sec.
ON OFF 5 sec.
OFF ON 10 sec.
6
V. Installation
The feeder should be installed before the controller.
A. Feeding System
Install the feeding system as shown in Figure 3 or in accor­dance with the installation instructions that were provided with the feeder.
B. Controller Installation
The voltage on the feeder solenoid valve must match the output voltage of the controller. The C316 Controller must be matched with a 24V solenoid valve.
1. Turn off the power to the filter pump at the breaker box.
2. Remove the Caution Plate at the bottom of the controller by
removing the two screws.
3. To avoid damage, remove the controller module from the
controller box by removing the BNC connector(s) and the faceplate screws.
4. Drill or cut out the electrical access holes that are best
suited for your installation (using a hammer can damage the controller). Install seal-tight or strain relief connectors in the access holes and replace the module.
5. Mount the controller on a wall or surface within eight feet of
the feeder.
316 Controller
110V to 24V Plug-in Transformer
To Pool
Heater
pH Sensor
Filter
Pump
From Pool
Flow
Flow
Switch
Flow Cell
Check Valve
24V Solenoid Valve
Figure 3
7
6. A plug-in 110v to 24v transformer (part #22-3190) is
provided with the controller. Locate the nearest 110V standard outlet. Using a minimum of 20 to 22 gauge PVC jacketed wire, connect the controller to the transformer that will plug into the 110V outlet.Thread the wire through the controller seal-tight or strain relief connecter and hook it to the line side of the terminal strip and transformer.
6. Connect the controller output using a minimum of 20 to 22
gauge wire through the compression fitting to the solenoid.
7. Replace the Caution Plate at the bottom of the controller.
8. We recommend that the sensor be installed in the Flow Cell
Assembly (part #9-700), available from Polaris. If you do not use the flow cell assembly, you can install the
sensor using the compression fitting that comes with the controller.The fitting should be installed in a vertical position on the pressure side of the pool circulation system. It should be located after the filter and before the heater, and it can be installed using a tee, saddle tee or a 1/2” NPT tap.
C. Flow Cell Assembly Installation (Optional)
If using the flow cell assembly, locate the assembly within eight feet of the controller and mount it using the brackets provided. The flow cell must be plumbed so the pressure difference between the inlet and outlet is sufficient to ensure flow through the flow cell. It is also desirable to have filtered water pass over the sensors to minimize cleaning.
Flow Switch/ Flow Indicator
Sample Port
Inlet
Ball Valve
Outlet
Compression Fittings with Sensors
Flow Cell Assembly
8
There are three suggested methods to install the flow cell.
1. Plumb the inlet to the flow cell after the filter and plumb the
outlet of the flow cell after the heater using the saddle clamps provided. See the Pressure Differential Installation diagram. Fittings for 1/4" NPT taps are included.
2. Plumb from after the filter to before the pump. This ensures
excellent flow but the flow will need to be adjusted so the sensors are not subjected to a suction environment. See the Pressure Suction Installation diagram. Open the sample port (see Flow Cell Assembly drawing) to verify that the water is flowing freely.
To Pool
From Pool Flow
Flow Cell
pH Sensor
ORP Sensor
Filter
Heater
Pump
Controller
Flow Switch
pH
Controller
To Pool
Flow
Flow Switch
ORP
Flow Cell
From Pool Flow
Filter
Pump
Pressure Differential Installation
Pressure Suction Method
Loading...
+ 18 hidden pages