Plantronics DYNZ-600 User Manual

Technical Manual
Models
Electronic Speed Switch
Uncontrolled Document
For Historical Reference Only
DYNZ-60012- 59 to 88 Vdc
F-23371
2002 Invensys. All Rights Reserved
Barber-Colman DYNA Products
P.O. Box 2940 1354 Clifford Avenue Loves Park, IL 61132-2940 USA
Tel: + 1 815 637 3000 Fax: + 1 815 877 0150
www.dynaproducts.com
Table Of Contents
1.0 Introduction 1
2.0 Specifications 1
3.0 Additional Features 2
4.0 Wiring Instructions 3
5.0 Operation and Calibration of DYNZ-60010 3
6.0 Operation and Calibration of DYNZ-60012 and DYNZ-60013 4
7.0 Troubleshooting 5
Uncontrolled Document
For Historical Reference Only
2002 Invensys. All Rights Reserved
F-23371 Electronic Speed Switch Technical Manual Page 1
Note
Colman believes that all information provided
herein is correct and reliable and reserves the right to
update at any time. Barber0Colman does not assume
essly
Caution
Colman Company
recommends that all engines and turbines be equipped
with an independent overspeed shutdown devise.
1.0 INTRODUCTION
The Barber-Colman two setpoint speed switch normally obtains its input signal from a magnetic pickup which is positioned in proximity to the teeth of a gear on a rotating shaft. The pickup generates an AC signal voltage whose frequency is directly proportional to the rate at which the gear teeth pass by the pole piece. The speed switch converts the input signal voltage into a DC signal which is compared to the preset levels (setpoints) and actuate the relays when the input signal frequency exceeds the preset values.
Barber-
any responsibility for its use unless otherwise expr undertaken.
1.1 APPLICATION
l Overspeed Protection Signal l Underspeed Protection Signal l Crank Termination Signal l Generator Field Flashing Signal l Ignition Signal l Sequencing Signal l Tach Signal for Driving Model 40 Tachometer
As a safety measure, Barber-
1.2 RELAY LOGIC TABLE FOR SPEED SWITCHES
Switch
DYNZ-60010 SWl Relay Contacts
DYNZ-60010 OS-SW2 Relay Contacts DYNZ-60012 SW1 Relay Contacts
DYNZ-60012 OS-SW2 Relay Contacts DYNZ-60013 SW1 Relay Contacts
DYNZ-60013 OS-SW2 Relay Contacts
Power to Unit
and Input Signal
Frequency
Uncontrolled Document
below Trip Point De-energized 10 to 12 closed 11 to 12 open
Energized 7 to 9 open 8 to 9 closed
For Historical Reference Only
De-energized 10 to 12 closed 11 to 12 open
De-energized 7 to 9 closed 8 to 9 open
De-energized 10 to 12 closed 11 to 12 open
De-energized 7 to 9 closed 8 to 9 open
Power to Unit and
Input Signal
Frequency above Trip
Point
Energized (non­latching) 10 to 12 open 11 to 12 closed De-energized (latched) 7 to 9 closed 8 to 9 open
Energized (non­latching) 10 to 12 open 11 to 12 closed Energized (non­latching) 7 to 9 open 8 to 9 closed Energized (non­latching) 10 to 12 open 11 to 12 closed Energized (non­latching) 7 to 9 open 8 to 9 closed
2.0 SPECIFICATIONS
2.1 ELECTRICAL
2.1.1 COMMON ELECTRICAL SPECIFICATIONS FOR DYNZ-60010, DYNZ-60012 AND DYNZ-60013 Ambient Operating Temperature: -40 to +185°F (-
40 to +85°C).
Maximum Operating Current: 0.20 amperes. Input Signal Voltage: 0 7 Vrms minimum into 33 k
ohm load. Trip Setpoint: Adjustable 325 to 10,000 Hz. SW1: Factory set at 1100 Hz. SW2: Factory set at 3600 Hz.
Repeatability: ±5 Hz or ±1%, whichever is greater.
2.1.2 ELECTRICAL SPECIFICATIONS FOR DYNZ­60010 Power Input: 8 to 40 Vdc. Voltage Transients: Withstand 200 volts forward and
reverse peaks of 10 milliseconds duration at 5 ohms source input impedance. Withstand 80 volts forward and reverse peaks of 50 milliseconds duration at 50 ohms source input impedance.
Hysteresis:
SW1: Crank dropout, non-latching; nominal 165 Hz SW2: Overspeed, latching; 100% of setpoint. Relay Contact Rating: 10 amperes at 30 Vdc resistive. Overspeed Response Time: With the overspeed set at 4140 Hz and a steady input frequency of 3600 Hz, then switching the input frequency to 5000 Hz must result in the overspeed relay operating in 90 milliseconds or less.
2.1.3 ELECTRICAL SPECIFICATIONS FOR DYNZ­60012 Power Input: 59 to 88 Vdc. Voltage Transients: Withstand 200 volts forward and
reverse peaks of 10 milliseconds duration at 50 ohms source input impedance. Withstand 80 volts forward and reverse peaks of 50 milliseconds duration at 50 ohms source input impedance.
Hysteresis:
SW1: Crank dropout, non-latching; nominal 165 Hz SW2: Overspeed, non-latching; 0% of setpoint. Relay Contact Rating: 0.75 amperes at 88 Vdc resistive. Overspeed Response Time: With the overspeed set at 4140 Hz and a steady input frequency of 3600 Hz, then switching the input frequency to 5000 Hz must result in the overspeed relay operating in 75 milliseconds or less.
2.1.4 ELECTRICAL SPECIFICATIONS FOR DYNZ­60013 Power Input: 8 to 40 Vdc. Voltage Transients: Withstand 200 volts forward and
reverse peaks of 10 milliseconds duration at 50 ohms source input impedance. Withstand 80 volts forward and reverse peaks of 50 milliseconds duration at 50 ohms source input impedance.
Hysteresis:
SW1: Crank dropout, non-latching; nominal 165 Hz SW2: Overspeed, non-latching; 0% of setpoint.
2002 Invensys. All Rights Reserved
F-23371 Electronic Speed Switch Technical Manual Page 2
Relay Contact Rating: 10.0 amperes at 30 Vdc resistive. Overspeed Response Time: With the overspeed set at 4140 Hz and a steady input frequency of 3600 Hz, then switching the input frequency to 5000 Hz must result in the overspeed relay operating in 75 milliseconds or less.
2.2 MECHANICAL / ENVIRONMENTAL Case: Has nickel plated terminals. Humidity and salt
spray resistant. Potted for water protection.
Vibration: 5.0 G’s from 20 to 500 Hz. Shock: 4 foot drop test.
2.3 MOUNTING INSTRUCTIONS
Four mounting holes are provided on the case as shown in Figure 1. Although the unit can withstand the normal vibration levels and temperature excursions encountered, it is a good practice to mount the unit in a location where these effects are minimized. The unit should be attached to the mounting plate with 10-32 screws.
Figure 1. Installation Drawing
3.0 ADDITIONAL FEATURES
3.1 OVERSPEED TRIP TESTING
Overspeed trip testing while the engine is running at its normal speed can be accomplished by temporarily connecting terminal 2 to terminal 3. This lowers the overspeed setpoint of OS-SW2 to 67% of its set/calibrated value.
3.2 TACHOMETER READOUT
Tachometer readout can be obtained by connecting a Synchro-Start Model 40 tachometer to terminals 1, 2 and 4 as shown in Figure 3.
Figure 2
3.3 SW1 & OS-SW2 ADJUSTMENT AND ADJUSTMENT RANGE
l There are two speed trip setpoint adjustments,
SW1 and OS-SW2, located on top of the unit. Turning the 20 turn potentiometer adjustment clockwise increases the RPM setting.
Uncontrolled Document
For Historical Reference Only
2002 Invensys. All Rights Reserved
F-23371 Electronic Speed Switch Technical Manual Page 3
CAUTION
If the 10 ampere relay contact rating is exceeded, the
rcuit board from the relay contacts
NOTE
Omit/skip step 5.2.3 if you are only checking the
NOTE
If you are only checking calibration point, omit steps
l Barber-Colman sets the units to operate over the
adjustment range of 325 to 10,000 Hz by cutting jumper J2 only. The sensitivity of the adjustment potentiometer is approximately 480 Hz per turn.
n SW1 is factory set at 1100 Hz unless specified in
purchase order.
n OS-SW2 is factory set at 3600 Hz unless specified
in purchase order.
l The unit can be operated at a lower frequency
adjustment range (80 to 2500 Hz instead of 325 to 10,000 Hz) by reconnecting jumper J2 and cutting out jumper J1 (see Figure 2).
4.0 WIRING INSTRUCTIONS
The typical wiring diagram shows the wiring required to properly connect the unit to the DYNA governor. All the wiring for the test, tach and input power terminals should be either 18 or 20 AWG wire. The wiring to the relay contacts should be 16 AWG wire if the current requirement is less than 5 amperes and 14 AWG if the current through the contacts is between 5 and 10 amperes. The current load and wiring to the relay should be checked thoroughly.
foil on the printed ci to the terminals can be damaged.
As shown in Figure 3, a two-conductor shielded cable must be used for mounting the speed sensor (MPU) to the unit. The shield should only be connected as shown. It is good practice to isolate the power wiring from the relay contacts and associated relays from the input signal wiring. The input signal is normally from a magnetic pickup (MPU) mounted on the flywheel housing which senses the ring gear speed.
5.0 OPERATION AND CALIBRATION OF
Uncontrolled Document
DYNZ-60010 SPEED SWITCH
5.1 OPERATING PROCEDURE
Once the system has been wired, the SPEED SWITCH functions in the following manner.
5.1.1 No power applied to unit.
l SW1 and OS-SW2 relays are de-energized;
therefore, contacts are in position as shown on top of unit.
5.1.2 Power is applied to unit when POWER SWITCH is turned on and no input signal to speed switch.
l SW1 relay remains de-energized; therefore, its
contacts remain in same position as those shown on top of unit.
l OS-SW2 relay energizes; therefore, its contacts
change states from those shown on top of unit.
5.1.3 When the engine is cranked and the engine starts, SW1 energizes at its crank-dropout setting which is normally adjusted midway between the cranking RPM and idle RPM of the engine.
For Historical Reference Only
5.1.4 When an overspeed condition occurs, OS-SW2 relay deenergizes and latches up and will remain latched up until the POWER SWITCH is turned off or power is somehow removed from the unit. The engine overspeed setpoint is normally adjusted to trip at 10 to 20% above the engine operating speed.
5.2 CALIBRATION PROCEDURE Equipment Required: Signal generator
Frequency counter Ohmmeter
5.2.1 Determine the desired trip points for your unit when using a magnetic pickup (MPU).
No. of Gear Teeth x
Trip Point in Hz = Engine RPM Trip Point
60
5.2.2 Connect the signal generator and counter to terminals 5 and 6 with terminal 5 being the ground terminal. Set the signal generator frequency 100 Hz below the SW1 or OS-SW2 trip point you are trying to calibrate/set or check. Then adjust the out signal from the signal generator to 1 volt rms or greater.
5.2.3 If you are calibrating unit, turn the desired trip point potentiometer adjustment 10 or 15 turns clockwise.
5.3 CALIBRATION OR CHECKING PROCEDURE FOR SW1 TRIP POINT
5.3.1 With no power applied to unit, connect an
ohmmeter to terminals 10 and 12 (no other wires attached). The ohmmeter should indicate zero resistance (short circuit). This is the normally closed contact on relay SW1.
5.3.2 Apply correct DC power to terminals 1 and 2 of speed switch. The ohmmeter connected to terminals 10 to 12 should still indicate zero resistance, because you should be below the setpoint for SW1 and it should not change states when power is applied to the unit.
5.3.3 Adjust the signal generator frequency to the desired SW1 set/trip point as specified or calculated in step 5.2.1.
5.3.4 Slowly adjust SW1 setpoint potentiometer counterclock-wise until the ohmmeter indicates an open circuit. This is now the set/trip point for SW1.
5.3.5 Slowly increase the signal generator frequency until the ohmmeter connected to terminals 10 to 12 indicates an open circuit. Note the frequency and verify that it is correct for your SW1 set/trip point
2002 Invensys. All Rights Reserved
F-23371 Electronic Speed Switch Technical Manual Page 4
NOTE
If you are only checking calibration point, omit steps
NOTE
ps
NOTE
Omit/skip step 6.2.3 if you are only checking the
requirements. If set/trip point of SW1 is correct it is properly calibrated. If set/trip point is incorrect, go to step 5.3.2, 5.3.3 and 5.3.4 and calibrate unit.
5.4 CALIBRATION OR CHECKING PROCEDURE FOR OS-SW2 TRIP POINT
5.4.1 With no power applied to unit, connect an
ohmmeter to terminals 7 and 9 (no other wires attached). The ohmmeter should indicate zero resistance (short circuit). This is the normally closed contact on relay OS-SW2.
5.4.2 Apply correct DC power to terminals 1 and 2 of speed switch.
The ohmmeter connected to terminals 7 to 9 should now indicate infinite resistance (open circuit). Originally the signal generator frequency was set below the units set/trip point (see step 5.2.2); therefore, it must change states when power is applied.
5.4.3 Adjust the signal generator frequency to the desired OS-SW2 set/trip point as specified or calculated in step 5.2.1.
5.4.4 Slowly turn the OS-SW2 potentiometer adjustment counterclockwise until the ohmmeter indicates an open circuit. This gives you the correct setpoint for OS-SW2. Remember OS-SW2 latches.
5.4.5 Slowly increase the signal generator frequency until the ohmmeter connected to terminals 7 to 9 indicates an open circuit. Note the frequency and verify that it is correct for your OS-SW2 set/trip point requirements. If set/trip point of OS-SW2 is correct it is properly calibrated. If set/trip point is incorrect, go to step 5.4.2, 5.4.3 and 5.4.4 and calibrate unit.
Uncontrolled Document
6.0 OPERATION AND CALIBRATION OF DYNZ-60012 AND DYNZ-60013 SPEED SWITCH
6.1 OPERATING PROCEDURE
Once the system has been wired, the SPEED SWITCH functions in the following manner.
6.1.1 No power applied to unit.
l SW1 and OS-SW2 relays are de-energized;
therefore, contacts are in position as shown on top of unit.
6.1.2 Power is applied to unit when POWER SWITCH is turned on and no input signal to speed switch.
l SW1 relay remains de-energized; therefore, its
contacts remain in same position as those shown on top of unit.
For Historical Reference Only
l OS-SW2 relay remains de-energized; therefore, its
contacts remain in the same position as shown on top of unit.
6.1.3 When the engine is cranked and the engine starts, SW1 energizes (non-latching) at its crank­dropout trip point setting which is normally set to trip midway between the cranking RPM and idle RPM of the engine.
6.1.4 When an overspeed condition occurs, OS-SW2 relay energizes and it will remain energized until the frequency falls below the trip point at which time the relay will de-energize (relay is non-latching with no hysteresis). The engine over-speed setpoint is normally adjusted to trip at 10 to 20% above the engine operating speed.
6.2 CALIBRATION PROCEDURE Equipment Required: Signal generator
Frequency counter Ohmmeter
6.2.1 Determine the desired trip points for your unit when using a magnetic pickup (MPU).
No. of Gear Teeth x
Trip Point in Hz = Engine RPM Trip Point
60
6.2.2 Connect the signal generator and counter to terminals 5 and 6 with terminal 5 being the ground terminal. Set the signal generator frequency 100 Hz below the SW1 or OS-SW2 trip point you are trying to calibrate/set or check. Then adjust the out signal from the signal generator to 1 volt rms or greater.
6.2.3 If you are calibrating unit, turn the desired trip point potentiometer adjustment 4 or 5 turns clockwise.
6.3 CALIBRATION OR CHECKING PROCEDURE FOR SW1 TRIP POINT
6.3.1 With no power applied to unit, connect an
ohmmeter to terminals 10 and 12 (no other wires attached). The ohmmeter should indicate zero resistance (short circuit). This is the normally closed contact on relay SW1.
6.3.2 Apply correct DC power to terminals 1 and 2 of speed switch. The ohmmeter connected to terminals 10 to 12 should still indicate zero resistance, because you should be below the trip point for SW1 and it should not change states when power is applied to the unit.
If you are only checking calibration point, omit ste
2002 Invensys. All Rights Reserved
F-23371 Electronic Speed Switch Technical Manual Page 5
CAUTION
As a safety measure, the engine should be
equipped with an independent overspeed
ice in the event of failure which
-
NOTE
-
Colman believes that all information
provided herein is correct and reliable but
-
lity for
NOTE
If you are only checking calibration point, omit steps
6.3.3 Adjust the signal generator frequency to the desired SW1 set/trip point as specified or calculated in step 6.2.1.
6.3.4 Slowly turn the SW1 setpoint potentiometer adjustment counterclockwise until the ohmmeter indicates an open circuit. This gives you the correct setpoint for SW1.
6.3.5 Slowly increase the signal generator frequency until the ohmmeter connected to terminals 10 to 12 indicates an open circuit. Note the frequency and verify that it is correct for your SW1 set/trip point requirements. If set/trip point of SW1 is correct it is properly calibrated. If set/trip point is incorrect, go to step 6.2.3, 6.3.3 and 6.3.4 and calibrate unit.
6.4 CALIBRATION OR CHECKING PROCEDURE FOR OS-SW2 TRIP POINT
6.4.1 With no power applied to unit, connect an
ohmmeter to terminals 7 and 9 (no other wires attached). The ohmmeter should indicate zero resistance (short circuit). This is the normally closed contact on relay OS-SW2.
6.4.2 Apply correct DC power to terminals 1 and 2 of speed switch. The ohmmeter should indicate zero resistance (short circuit) with the signal generator frequency set below the OS-SW2 set/trip point; therefore, it must not change states when power is applied.
6.4.3 Adjust the signal generator frequency to the desired OSSW2 set/trip point as specified or calculated in step 6.2.1.
6.4.4 Slowly turn the OS-SW2 potentiometer counterclockwise until the ohmmeter indicates an open circuit. This gives you the correct setpoint for OS-SW2.
6.4.5 Slowly increase the signal generator frequency until the ohmmeter connected to terminals 7 to 9 indicates zero resistance. Note the frequency and verify that it is correct for your OS-SW2 set/trip point requirements. If set/trip point of OS-SW2 is correct, it is properly calibrated. If set/trip point is incorrect, go to step 6.2.3, 6.4.3 and 6.4.4 and calibrate unit.
Uncontrolled Document
For Historical Reference Only
7.0 TROUBLESHOOTING PROCEDURE
The unit is potted and, therefore, non-repairable, but the following checkpoints can be used to determine if there is an internal fault.
7.1 UNIT DOES NOT FUNCTION
7.1.1 Check battery voltage on terminals 1 and 2.
DYNZ-60010-000-0-40 — 8 to 40 Vdc DYNZ-60012-000-0-74 — 58 to 88 Vdc DYNZ-60013-000-0-40 — 8 to 40 Vdc
7.1.2 Check input signal from MPU on terminals 5 and 6 with an AC voltmeter — must be greater than 0.7 volts rms.
7.1.3 Check wiring to speed switch.
7.2 TRIPPING AT WRONG RPM
7.2.1 Check for proper trip point settings.
7.2.2 See calibration section.
7.3 RELAY DOES NOT FUNCTION
7.3.1 Check wiring to relays.
7.3.2 Check relay contacts for proper operation.
shutdown dev may render the governor inoperative.
Barber­reserves the right to update at any time. Barber
Colman does not assume any responsibi its use unless otherwise expressly undertaken.
2002 Invensys. All Rights Reserved
Loading...