The SGH50 fryer components function in specific order
of operation. Knowing and understanding the sequence
•Opening the RED return valve handle will close
of fryer and components operation will enable you to
diagnose equipment failure more accurately.
Heating System
Power to the machine is turned ON:
•If Fuse F1 on the Relay board is good, the A.C.
•The pump system is equipped with a circuit breaker
indicator will illuminate and the controller will be
supplied with 24 VAC and, if the drain valve handle
is closed, the proximity switch will supply 24 VAC
to the DVI (drain valve interlock) input at the
controller.
•The computer or solid state control is turned ON:
•The return piping system may be provided with
•The side on relay will be energized, closing the
circuit and the S.O. indicator on the Relay Board
will illuminate. If the hi limit is NOT tripped the
ignition module will receive 24VAC at terminal 6 (24
VAC).
Optional Basket Lift:
•The ignition module will have a 24 VAC output from
terminal 3(PV) to the PV terminal on the gas valve
•The basket lift is a self contained unit that requires
and the ignitor will spark. When the pilot has lit and
the module has proven the pilot flame, it will have a
24 VAC output at terminal 1(MV) and put 24 VAC
on pin #2 at connection J/P32 on the relay board.
The heat demand relay on the relay board will
interrupt the 24 VAC supply to the gas valve until
the controller calls for heat.
Note: When the controller is on, the pilot should
always remain lit.
•Controller calls for heat:
•The heat demand relay will energize supplying the
gas valve with 24 VAC and the H.D. indicator on
Probe:
the Relay Board will illuminate. This will also supply
the computer with a heat feedback signal.
The resistance of the probe will change as the temperature changes. The resistance will decrease as the
Hi Limit System:
temperature rises.
If the probe is suspect, check its resistance and the oil
• If the hi limit trips, it interupts the 24 VAC supply to
the ignition module. When the controller calls for
heat, it will not receive a 24 VAC heat feed back.
With approximately 90 seconds of heat feed back
loss, the controller will indicate an ignition failure or
heat failure. After the hi limit is reset (unit cools to
400°F + 20°F) the computer will have to be turned
off and back on for the unit to heat.
temperature at which it was taken. Compare these
values on the probe resistance chart.
If the probe returns an open circuit or 0 Ohms reading, it should be replaced. If the resistance varies more
than 30 Ohms when being checked between 325375°F the probe will give a false temperature reading
on the computer and should be calibrated (up to 10°F)
or replaced. However, it will continue to operate at a
slightly higher or lower temperature.
L22-235 Rev 1 (10/12)4
the proximity switch causing the "pump run" relay
to be energized. The pump motor will begin to
run.Closing the return valve handle will de-energize the relay and the pump motor will stop running.
which will de-energize the system and the heat tape
in the event of over current. The circuit breaker
switch must be in the ON position for the pump
and heat tape to operate.
optional heat tape to prevent solidification of solid
shortening. The heat tape is low wattage and is on
constantly to maintain liquid shortening in the line.
a 120, 208 or 240V supply. With most fryer configurations, the power is supplied from the entrance
box at the back of the fryer but some cofigurations
will require power direct from a wall outlet. When
power is supplied to basket lift assembly, the baskets will lift to the up position. The baskets will
lower with a 24 VDC output from the controller.
Chapter 2: COMPONENT
TROUBLESHOOTING:
This test will cause the burners to run continuously.
Remove test resistor when test is complete.
Leaving the test resistor in the fryer could cause
damage to equipment and/or personal injury.
To test the hi-limit, use a 2kΩ - 5kΩ resistor to simulate
a 230°F - 275°F temperature. This will cause the
burners to run continuously until the hi-limit trips or the
fryer is turned off.
•If the fryer is equipped with a computer or digitalcontroller, plug the resistor in at connector J41 behind
the front panel.
•If the fryer is equipped with a solid state controller
behind the door, plug the resistor in at connector J43
behind the front panel.
Allow the oil to cool and check the probe resistance at a
lower temperature. As can be seen from the chart a
greater variation can be tolerated at a lower temperature.
Gas Valve:
The gas valve has a dual 24 VAC operator and will
open when the correct voltage is supplied to the
operator. With 24 VAC applied to the PV (24 VAC)
connection, the pilot valve operator will open, allowing
gas to flow to the pilot.
With 24 VAC applied to the MV (24 VAC)
connection, the main valve operator will open,
allowing gas to flow to the main burners.
Hi Limit:
The hi - limit switch is a normally closed switch until
the temperature at the hi-limit bulb reaches 450°F ±
15°F.
WARNING!
This test should be performed by a qualified
technician only! Monitor the fryer closely. This
test will cause the oil to heat past the normal
operating temperature and can cause damage
to the machine and its operator if care is not
taken.
WARNING!
If the switch does not trip between the prescribed limits
it is defective and should be replaced. Once tripped, the
switch cannot be reset until the oil has cooled to
approximately 400°F + 20°F. If the switch does not
reset after oil has cooled it is defective.
Drain Valve & Return Valve Switches:
These switches are a magnetically operated proximity
switches. When the Drain Valve handle is moved to the
open position, the Actuator will move away from the
switch causing the switch to open. When the Drain Valve
is closed the switch will close.
Opening the RED return valve handle will close the
proximity switch causing the "pump on" relay to be
energized. The pump will begin to pump. Closing
the return valve handle will open the proximity switch
causing the relay to de-energize and the pump will stop
pumping. These switches can also be checked with an
Ohm meter. When the switch is closed, you should have
continuity. The normal gap between the Actuator and the
Sensor switch on the valve handle is 1/8" - 1/4" (3 6mm).
Transformer:
The transformer is a multiple AC input voltage 24 VAC
output voltage and can be checked by reading the input
and output voltages. A quick check for 24 VAC can be
done at the relay board behind the front panel. The AC
5
L22-235 Rev 1 (10/12)
indicator will be illuminated if the F1 fuse is good and the
board is receiving 24 VAC.
Ignition Module:
With a 24 VAC input at pin #6, the ignition module will
have a 24 VAC output from terminal 3(PV) and the ignitor will spark until the module senses pilot flame or for
approximately 90 seconds at which time the module will
lock out, whichever occurs first. When the module has
proven the pilot flame, it will have a 24 VAC output at
terminal 1(MV) and put 24 VAC to pin 2 at connection J/
P32 on the relay board. The relay board will interrupt the
24 VAC to the gas valve until the controller calls for heat.
Note: When the controller is on, the pilot should
always remain lit.
Relay Board:
Note: J connectors are marked on the relay board.
•With 24 VAC supplied to pin #2 at connector J35 and a
good F1 fuse, the relay board will have a 24 VAC output
at pin #2 on connectors J33 and J34 and the A.C. indicator will be illuminated.
Note: If the fryer is equipped with a computer or
solid state digital, at connection J33 there will be a
jumper from pin #2 to pin #10 to supply 24 VAC to
pin # 2 at connection J31 to supply the controller
with 24VAC.
•When the board receives a 24 VDC side on input at pin
#7 on connectors J31 or J33, the S.O. indicator will illuminate, the side on relay (S.O.) will energize and there
will be a 24 VAC output at pin #4 on connector J32.
•When the board receives a 24 VDC heat demand input
at pin #6 on connectors J31 or J33, the H.D. indicator
will illuminate, the heat demand relay (H.D.) will energize
and there will be continuity between pin #1 and pin #2 at
connector J32.
Computer Control:
Note: All controller test points are at connector P/J1 (clos-
est connector to the controller).
•With 24 VAC supplied to pin #1(24VAC supply) and
pin # 5(24VAC input from DVI), the display should read
"OFF".
•With the controller turned on, there will be a 24 VDC
output at pin #9 (side on).
•When the controller calls for heat, there will be a 24 VDC
output at pin #8 (heat demand) and a 24 VAC input at pin
#6 (heat feed back). If the controller does not receive the
24 VAC input at pin #6 in approximately 90 seconds, the
controller will display "HEAT FAIL" or "IGNITION FAILURE". This would indicate a break in the heat demand or
heat feed back circuit.
1. Check the hi-limit switch (is it open or tripped).
2. Check the ignition module (sensing pilot flame,
locked out, 24 VAC at MV terminal).
3. Check the heat demand relay (H.D.) on the relay
board (is heat demand relay energized, continuity
through COM and NO contacts).
•If display reads "PROBE OP" "OPEN", ohm test the
temperature probe. Check the wires and connectors between the probe and controller for continuity.
•If display reads "SYSTEM" "FAILURE", test the temperature probe and the wires and connectors between the
probe and controller for a short.
•If display reads "DRAINING" "TURN OFF", verify that
the drain valve is closed, check the proximity switch on
the drain valve, turn the fryer off, then turn the fryer on.
Digital Solid State Control:
Note: All controller test points are at connector P/J1 (clos-
est connector to the controller).
•With 24 VAC supplied to pin #1(24VAC supply) and
pin # 5(24VAC input from DVI), the display should read
"OFF".
•With the controller turned on, there will be a 24 VDC
output at pin #9 (side on).
•When the controller calls for heat, the display will read
"HEAt", there will be a 24 VDC output at pin #8 (heat
demand) and a 24 VAC input at pin #6 (heat feed back).
If the controller does not receive the 24 VAC input at pin
#6 in approximately 90 seconds, the controller will display "HEAt" "FAIL" . This would indicate a break in the
heat demand or heat feed back circuit.
1. Check the hi-limit switch (is it open or tripped).
2. Check the ignition module (sensing pilot flame,
locked out, 24 VAC at MV terminal).
3. Check the heat demand relay (H.D.) on the relay
board (is heat demand relay energized, continuity
through COM and NO contacts).
•If display reads "Prob", ohm test the temperature probe.
Check the wires and connectors between the probe and
L22-235 Rev 1 (10/12)6
controller for continuity.
•If display reads "Prob" "HI", ohm test the temperature
probe and the wires and connectors between the probe
and controller for a short.
•If display reads "drn" "tUrn" "oFF", verify that the drain
valve is closed, check the proximity switch on the drain
valve.
Primary Solid State Control:
Note: All controller test points are at connector P/J3 (the
12 pin connector at the controller).
•24 VAC is supplied to the controller at pin #1(24VAC
supply) and pin # 5 (24 VAC input from DVI),
•With the controller turned on, there will be a 24 VDC
output at pin #9 (side on) and the green indicator will be
illuminated.
•When the controller calls for heat, there will be a 24 VDC
output at pin #8 (heat demand), the yellow indicator on
the left will be illuminated and there will be a 24 VAC input
at pin #6 (heat feed back).
•When the controller receives the 24 VAC input at pin #6,
the yellow indicator on the right will illuminate. If the controller does not receive the 24 VAC input at pin #6, the
indicator will not illuminate. This would indicate a break in
the heat demand or heat feed back circuit.
1. Check the hi-limit switch (is it open or tripped).
2. Check the ignition module (sensing pilot flame,
locked out, 24 VAC at MV terminal).
3. Check the heat demand relay (H.D.) on the relay
board (is heat demand relay energized, continuity
through COM and NO contacts).
•If the green indicator and the yellow indicator on the left
come on and shut off when the controller is turned on, that
indicates an open or shorted probe or wires in between
the probe and the controller.
•If none of the indicators illuminate when the controller is
turned on, verify that the drain valve is closed and that the
magnetic proximity switch has continuity when the drain
valve is closed. Also verify that there is 24 VAC at pin #1
(24 VAC supply) and pin #5 (24 VAC input from DVI).
controller has been unplugged, the primary controller will
not work. The jumper must be installed on the relay board
(connection J33) to allow the primary controller to function if the backup controller is removed.
Optional Basket Lift:
•The basket lift is a self contained unit that requires a 120,
208 or 240V supply. With most fryer configurations, the
power is supplied from the entrance box at the back of the
fryer but some cofigurations will require power direct from
a wall outlet.
•When supply voltage is applied to the basket lift assembly, it goes through a voltage selector switch to a multi tap
24V, 80VA transformer. The transformer supplies 24 VAC
to the driver board at connection J54.
Note: When power is supplied to basket lift assembly, the
baskets will lift to the up position.
•When a timer is activated, it will send a 24 VDC signal to
pin #1 (24 VDC+) at connector J51 on the driver board.
The driver board will generate a 24 VDC output at J53 to
the basket lift motor, lowering the basket.
Note: For the purpose of testing, jumping pins #1 and #2
at connection J5 on the driver board will simulate a 24
VDC signal from the controller, lowering the basket.
Backup Solid State Control:
The backup solid state control works the same as the primary solid state control, with the exception of the 24 VAC
supply passing through the solid state backup transfer
switch to the computer or solid state digital control.
If the transfer switch is set to backup or if the backup
7
L22-235 Rev 1 (10/12)
Fryer Trouble Shooting
PROBLEMPO SSIBLE CAUSEACTIO N
C o ntro ller will N O T t urn O N
Dis p lay d o es N O T light
Controller indicates "IGNITION
FAILURE" or "HEAT FAIL" and
machine does NOT heat.
Machine is heating slowlyA. Gas vavle not turned fully to the on
Oil is hotter or colder than computer
/c o ntrolle r d is p lays
C o ntro ller will no t tur n on o r d isp lays
"DRAINING" or "TURN OFF"
A. No power to the machine
B. F1 Fuse blown
C. T1 Transformer
A. Hi limit tripped
B. Heat demand relay
C. Relay board
position
B. Gas shut-off (yellow handle) not fully
open
C. Q uick d isconnect not co nnected
properly
D. Low gas pressure
A. Temperature calibration
B. Probe
C. Probe wiring terminals
A. Blue drain valve not fully closed
B. Sensor switch
C . I nco r r e c t s w itc h ga p /a lignme nt
A. Check building circuit breaker, verify
power cord is plugged in
B. Check F1 Fuse. Replace if defective
C. Check voltage in and out of T1
A. O nce the oil temp has gone below
400°F +
auto matically, if no t, r e p lac e Hi- limit
B. Check & replace if defective
C. Check & replace if defective
A. Verify that the gas valve is in the on
position
B. Verify that t he ye llow ha ndle is fully
open (inline with the gas line)
C. Verify that quick disconnect is properly
connected
D. Call a qualified gas technicain
A. Adjust temperature offset up to +
B. Check & replace if defective
C. Clean or repair terminals
A. Check position of handle
B. Switch may be loose or have loose
wires, replace if defective
C. Check gap/alignment, replace if defective
20 °, the Hi- limit sho uld re s e t
10°F
Controller heat d emand lights are lit,
machine does not heat. HD & SO
lights on relay board are lit.
Computer displays "PROBE
FAILURE"
A. K1 relay (relay board)
B. Gas valve
C. Ignition module
A. Shorted probe
B. Open probe
C. Probe wiring terminals
L22-235 Rev 1 (10/12)8
A. Check & replace if defective
B. Check & replace if defective
C. Check & replace if defective
A. Check probe & replace if defective
B. Check probe & replace if defective
C. Clean or repair terminals
Filter Trouble Shooting
PROBLEMPOSSIBLE CAUSEACTION
Re d r e t ur n hand le is p ulled out , b ut no
pump sound can be heard
Drain valve is closed, computer has
been reset, but computer still displays
"DRAIN IN G"
Oil is returning to the vat slowly or not
at all
Air b ubbles are in the oil being returned
to the vat
A. Red return handle not completly
open
B. Filter circuit breaker may be tripped
or in the off position
C . Filte r motor therma l o ve r lo ad ma y
be tripped
D. Sensor switch may be loose or
defective
E. Powe r cord unplugged or loose
A. Blue drain valve not fully closed
B. Sensor switch
C. Incorrect switch gap/alignment
A. D irty filter pape r
B. Strainer cap dirty
C. Filter pan not pushed in completely
D. O-rings not sealing on pick up tube
A. Strainer cap not tight
B. Stainer cap not in pick up tube
C. Filter pan not pushed in completely
D. O-rings not sealing on pick up tube
A. Pull on red return handle to make sure
valve is c o mpletly ope n
B. Reset the circuit breaker or press it to
the on position
C. Push the red reset button on the end of
the motor
D. Check that the switch is tight and that it
has the correct gap. Replace if defective
E. Check the power cord at the fryer
entrance box and at the pump box and
make sure that the power cords are plugged
in and /or pushed in all the way
A. Check position of handle
B. Switch may be loose or have loose
wires, replace if defective
C. Check gap/alignment, replace if defective
A. Change filter paper
B. Remove strainer cap and clean it
C. P ush filter pan in
D. Check & replace if defective
A. Tighten strainer cap
B. I nsta ll s tra iner c ap
C. P ush filter pan in
D. Check & replace if defective
Drain valve is open, the oil is draining
slowly or not at all
A. D ra in valve is not fully o p en
B. Drain line is plugged with debris
9
A. Apply a little more pressure to the drain
valve handle to check that the drain valve is
fully o p e n
B. Use the clean out rod to clear the drain
valve opening. If this does not clear the
blockage, close the drain valve, and call for
service
L22-235 Rev 1 (10/12)
Fuse:
A
If fuse is blown, A.C. will not be lit.
F1 -
Relay Board Component Explanation
Trouble Shooting Lights:
When lit, F1 Fuse and T1 Transformer are good.
.C. S.O. H.D. -
When lit, A1 Computer is on and K10 Contactor should be energized.
When lit, A1 Computer is on and calling for heat, K11 Contactor should be energized
Relays:
Heat Demand Relay, will be energized when A1 Computer calls for heat and when H.D. is lit.
K1 -
Side On Relay, will be energized when A1 Computer is on and A.C. is lit.
K3 -
Connectors:
J31 J32 J33 J34 J35 -
Connects to A1 Computer
To Side On and Heat Demand Contactors and Heat Feed Back.
To 24VAC jumper harness.
To Drain Switch and optional Basketlifts
Input voltage from transformer
Relay Board:
Note:
J connectors are marked on the
relay board.
•With 24 VAC supplied to pin #2 at
connector J35 and a good F1 fuse, the
relay board will have a 24 VAC output
at pin #2 on connectors J33 and J34
and the A.C. indicator will be
illuminated.
Note: If the fryer is equipped with a
computer or solid state digital, at
connection J33 there will be a
jumper from pin #2 to pin #10 to
supply 24 VAC to pin # 2 at
connection J31 to supply the
controller with 24VAC.
•When the board receives a 24 VDC
side on input at pin #7 on connectors
J31 or J33, the S.O. indicator will
illuminate, the side on relay (S.O.) will
energize and there will be a 24 VAC
output at pin #4 on connector J32.
•When the board receives a 24 VDC
heat demand input at pin #6 on
connectors J31 or J33, the H.D.
indicator will illuminate, the heat
demand relay (H.D.) will energize and
there should continuity between pin #1
and pin #2 at connector J32.
6
J32
1
7
J34
1
12
J35
1
A.C.
F1 FUSE
PITCO# 60127301A
DATE: MMDDYY
H.D.
K1
HEAT
DEMON
J33
10
J31
5
S.O.
K3
SIDE
1
1
L22-235 Rev 1 (10/12)10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.