11000IntroductionIntroduction1-1.1Validity of docume ntation1100Validity of documenta tion1-][BA Einf Gültigkeit Kopfmodul oh ne SB
This documentation is valid for the PSSu XR F-T module. It is valid until
new documentation is published.
Please also refer to the following documents:
PSSuniversal System Description
Einf Einleitung
1.1.1Retaining the documentation
Retaining the documentation1-Einf Aufbewahren
PSSuniversal Installation Manual
This operating manual explains the function and operation, describes
the installation and provides guidelines on how to connect the product .
This documentation is intended for instruction and should be retained
for future reference.
1.1.2Terminology: System environment A and B
Terminology: System environment A and B1-][BA Einf Begriffsdefinition Sys A + B
The PSSu system can be used in two different system environments.
The module's application area is described in the chapter "Intended
Use" of the manual.
The distinction is made between
PSSu in system environment A
PSSu in system environment B
The distinction is based on the application area of the PSSu system.
PSSu in system environment A may be used in the
Decentralised system PSSu I/O with SafetyBUS p
Decentralised system PSSu I/O with ST fieldbuses such as CANopen,
DeviceNet
Not in the automation system PSS 4000
PSSu in system environment B may be used in the
Automation system PSS 4000, e.g. with the
– Decentralised system PSSu I/O with SafetyNET p
– Control system PSSu PLC
– Control system PSSu multi
1.3Definition of symbols1300Definition of symbols1-Einfhrung Zeichen
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation
that poses an immediate threat of serious injury and death and
indicates preventive measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation
that could lead to serious injury and death and indicates preventive measures that can be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor
injury plus material damage, and also provides information on
preventive measures that can be taken.
NOTICE
This describes a situation in which the unit(s) could be damaged
and also provides information on preventive measures that can
be taken. It also highlights areas within the text that are of particular importance.
INFORMATION
This gives advice on applications and provides information on
special features.
22000OverviewOverview2-2.1Module features2100Module features2-Geraetemerkmale_Zusatz BA Einleitung
][Merkmale XR
][Merkmale_LED XR
][Merkmale_E-Module SB p und ST-Bus
][Merkmale_Zusatz ST/FS-Module Sys A + B
The product has the following features:
This module represents the first module in a PSSu remote system.
The module communicates with a base station PSSu XB F-T.
Plug for the module bus connection cable
The cable connection transfers:
–FS data
– ST data
–Module supply
LED indicators on the RJ45 socket for:
– Status of ST bus
– Status of FS bus
Electronic modules that can be used for input/output:
– All failsafe modules
(PSSu E F...)
– All standard modules
(PSSu E S...)
For standard and failsafe applications in system environment A and B
1: LED to display the status of data transfer to the ST module bus
2: LED to display the status of data transfer to the FS module bus
3: RJ-45 interface
4: Labelling strip with:
– Order number
– Serial number
– Hardware version number
– Firmware version number on delivery
31000SafetySafety3-3.1Intended use1100Intended use3-][Gerätebe schreibung FS-Mo dule Sys A + B
][Gertebeschreibung XR
Bestimmung/Gertebeschreibung_Ausschluss
The module may be used for standard and failsafe applications in system environment A and B.
The module may be used as a remote station to extend the PSSuniversal
module bus inside a control cabinet via a cable connection. It can be
operated with a base station of type PSSu XB F-T plus the connection
cable PSSu A RJ45-CAB 1.5M.
Intended use includes making the electrical installation EMC-compliant.
Please refer to the guidelines stated in the "PSSuniversal Installation
Manual". The module is designed for use in an industrial environment. It
is not suitable for use in a domestic environment, as this can lead to interference.
The following is deemed improper use in particular:
Any component, technical or electrical modification to the module
Use of the module outside the areas described in this manual
Use of the module outside the technical details (see chapter entitled
"Technical Details")
INFORMATION
The module is supported by
PSSuniversal Configurator and PSSuniversal Assistant from
Version 1.7.0
PAS4000 from Version 1.2.1
– We recommend that you always use the latest version
The products may only be assembled, installed, programmed, commissioned, operated, maintained and decommissioned by competent persons.
A competent person is someone who, because of their training, experience and current professional activity, has the specialist knowledge required to test, assess and operate the work equipment, devices,
systems, plant and machinery in accordance with the general standards
and guidelines for safety technology.
It is the company's responsibility only to employ personnel who:
Are familiar with the basic regulations concerning health and safety /
accident prevention
Have read and understood the safety guidelines given in this descrip-
tion
Have a good knowledge of the generic and specialist standards ap-
plicable to the specific application.
3.2.2Warranty and liability
Warranty and liability3-Sich Gewhrleistung
3.2.3Disposal
Disposal3-Si ch Entsorgung
All claims to warranty and liability will be rendered invalid if:
The product was used contrary to the purpose for which it is intended
Damage can be attributed to not having followed the guidelines in the
manual
Operating personnel are not suitably qualified
Any type of modification has been made (e.g. exchanging compo-
nents on the PCB boards, soldering work etc.).
In safety-related applications, please comply with the mission time t
M
in the safety-related characteristic data.
When decommissioning, please comply with local regulations regard-
ing the disposal of electronic devices (e.g. Electrical and Electronic
Equipment Act).
The module is a remote station used to extend the PSSu module bus via
a cable connection. The remote station is always the first module in a remote system.
In the remote system, a supply voltage module with the relevant base
module must be used after the remote station:
For supply voltage modules with infeed for the periphery supply,
module supply and C-rail supply, a base module must be used to refresh the supply voltage (PSSu BS-R...).
For supply voltage modules with infeed for the periphery supply and
C-rail supply, a base module must be used to provide the supply volt-
][Funktionsbeschreibung XB/XR
age (PSSu BS-R...).
][Funktionsdiagramm XB/XR
The cable connection disconnects the PSSu module bus on the base
station and continues it on the remote station.
All FS data, all ST data plus the module supply are transferred via the
cable connection. The periphery supply and C-rail supply are not transferred. Up to three PSSu systems can be connected, i.e. you can have
up to two successive cable connections.
The cable connection does not appear in the process image. The cable
connection does not need to be considered in the user program. The
reaction times of the modules on the remote system are not affected by
the cable connection.
The base system is terminated using a special terminating plate (PSSu
A EC XB, supplied with the remote module). The remote system is terminated using the terminating plate supplied with the head module.
55000InstallationInstallation5-5.1General installation guidelines5100General installation guidelines5-][Montage BA Kopfmodul Allgemein
Please also refer to the PSSuniversal Installation Manual.
The description below assumes that the mounting rail is already in-
Montage_EMV ESD
stalled.
CAUTION!
Damage due to electrostatic discharge!
Electrostatic discharge can damage components. Ensure
against discharge before touching the product, e.g. by touching
an earthed, conductive surface or by wearing an earthed armband.
5.3Install a terminating plate5300Install a terminating plate5-][Montage XB/XR Abschlussplatte
You will need two different terminating plates for installation:
PSSu A EC XB
– is supplied with the remote module.
– The base system is terminated using the terminating plate
PSSu A EC XB.
PSSu A EC(-T)
– is supplied with the PSSu head modules.
– The remote system is terminated using the terminating plate
PSSu A EC.
INFORMATION
If the base system is accidentally terminated using the terminating plate PSSu A EC, the I/O modules in the remote system will
not be recognised and will not appear in the process image.
The connection cable PSSu A RJ45-CAB 1.5M is available as an ac-
cessory.
The base station and remote station must be in the same control cab-
inet.
The C-rail supply and the periphery supply are not transferred via the cable connection, so the remote system forms a new supply group.
WARNING!
Risk of electrocution!
Always connect the mounting rail to the protective earth via an
earthing terminal. This will be used to dissipate hazardous voltages in the case of a fault.
If voltages higher than 50 VAC or 120 VDC are connected to the
PSSuniversal, e.g. to switch contacts on relay modules, please
note the following:
– Specific accident prevention regulations apply.
– The C-rail of the supply group should only be connected to
Application rangeStandard/Failsafe
Support in system environment A
from FS firmware version for other head modules1
from ST firmware version for other head modules1
from FS firmware version PSSu H F PN1
from ST firmware version PSSu H S PN1
from ST firmware version PSSu WR S IDN1
Support in system environment B
from head module FS firmware version1.2.0
from head module ST firmware version1.2.0
Electrical data
Internal supply voltage (module supply)
Supply voltage range of module supply4.8 - 5.4 V
Module's current consumption20 mA
Module's power consumption0.10 W
Environmental data
Ambient temperature in accordance withEN 60068-2-14-40 - 70 °C
Storage temperature in accordance with EN 60068-2-1/-2 -40 - 70 °C
Climatic suitabilityEN 60068-2-14, EN 60068-2-1, EN 60068-2-2,
EN 60068-2-30, EN 60068-2-78
Climatic suitability in accordance with EN 60068-2-30,
EN 60068-2-78
Condensationyes
Max. operating height above sea level 5000 m
EMCEN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
Vibration to EN 60068-2-6
Frequency10 - 150 Hz
Max. acceleration1g
Shock stress
EN 60068-2-2715g
EN 60068-2-2910g
Protection type in accordance with EN 60529
Mounting (e.g. cabinet)IP54
HousingIP20
Airgap creepage in accordance with EN 60664-1,
EN 61131-2
Overvoltage categoryII
Pollution degree2
Mechanical data
Housing material
FrontPC
BottomPC
Dimensions
Height125.6 mm
Width50.2 mm
Depth72.6 mm
Weight90 g
In many countries we are
represented by our subsidiaries
and sales partners.
Please refer to our homepage
for further details or contact our
headquarters.
InduraNET p
®
, Pilz
®
, PIT
®
, PMCprotego
®
, PMI
®
, PNOZ
®
, Primo
®
, PSEN
®
, PSS
®
, PVIS
®
, SafetyBUS p
®
, SafetyEYE
®
, SafetyNET p
®
, the spirit of safety
®
are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries. We would point out that product features may vary from the details stated in this document, depending on the status at the time of publication and the scope
of the equipment. We accept no responsibility for the validity, accuracy and entirety of the text and graphics presented in this information. Please contact our Technical Support if you have any questions.
Contact address
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.