Phoenix Contact RAD-900-DAIO6, RAD-900-IFS User Manual

Page 1
Radioline - 900 MHz wireless transmission system for ser ial interf aces and I/ O signals
User manual
UM EN RAD-900-IFS(DAIO6)
Page 2
User manual
UM EN RAD-900-IFS(DAIO6), Revision B
This user manual is valid for:
Designation Order No.
RAD-900-IFS 2901540 RAD-900-DAIO6 2702877
I/O extension modules:
RAD-AI4-IFS 2901537 RAD-PT100-4-IFS 2904035 RAD-AO4-IFS 2901538 RAD-DI4-IFS 2901535 RAD-DI8-IFS 2901539 RAD-DOR4-IFS 2901536 RAD-DO8-IFS 2902811 RAD-DAIO6-IFS 2901533
2018-07-23
3827_en_B
PHOENIX CONTACT GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
phoenixcontact.com
Page 3

Table of contents

Table of contents
1 For your safety............................................................................................................................5
1.1 Labeling of warning notes......................................................................................5
1.2 Qualification of users .............................................................................................5
1.3 Safety notes .......................................................................................................... 6
1.4 Installation and operation.......................................................................................6
1.5 Safety regulations for installation in potentially explosive areas............................. 7
1.6 Conformance.........................................................................................................8
2 Short description.........................................................................................................................9
2.1 RAD-900-IFS wireless module ..............................................................................9
2.1.1 Structure .............................................................................................10
2.2 RAD-900-DAIO6.................................................................................................. 11
2.2.1 Structure .............................................................................................12
3 Description of I/O extension modules .......................................................................................15
3.1 RAD-AI4-IFS - analog extension module with four inputs ....................................16
3.1.1 Structure ..............................................................................................16
3.1.2 Basic circuit diagram ............................................................................17
3.1.3 Setting the DIP switches ......................................................................17
3.1.4 Diagnostic LEDs ..................................................................................18
3.1.5 Setting the I/O-MAP address ...............................................................19
3.1.6 Process data in PLC/Modbus RTU mode ............................................19
3.2 RAD-PT100-4-IFS - extension module with four temperature inputs ...................20
3.2.1 Connecting sensors .............................................................................20
3.2.2 Measuring errors using 2-wire connection technology .........................22
3.2.3 Shielding of the sensor cables .............................................................24
3.2.4 Structure ..............................................................................................25
3.2.5 Basic circuit diagram ............................................................................26
3.2.6 Diagnostic LEDs ..................................................................................26
3.2.7 Setting the I/O-MAP address ...............................................................27
3.2.8 Process data in PLC/Modbus RTU mode ............................................27
3.3 RAD-AO4-IFS - analog extension module with four outputs ................................28
3.3.1 Structure ..............................................................................................28
3.3.2 Basic circuit diagram ............................................................................29
3.3.3 Setting the DIP switches ......................................................................29
3.3.4 Diagnostic LEDs ..................................................................................30
3.3.5 Setting the I/O-MAP address ...............................................................31
3.3.6 Process data in PLC/Modbus RTU mode ............................................31
3827_en_B PHOENIX CONTACT 1/138
Page 4
RAD-900-...
3.4 RAD-DI4-IFS - digital extension module with four inputs .....................................32
3.4.1 Structure ..............................................................................................32
3.4.2 Basic circuit diagram ............................................................................33
3.4.3 Diagnostic LEDs ..................................................................................33
3.4.4 Setting the I/O-MAP address ...............................................................34
3.4.5 Process data in PLC/Modbus RTU mode ............................................34
3.5 RAD-DI8-IFS - digital extension module with eight inputs....................................35
3.5.1 Structure ..............................................................................................35
3.5.2 Basic circuit diagram ............................................................................36
3.5.3 Setting the DIP switches ......................................................................36
3.5.4 Functions in pulse counter mode .........................................................37
3.5.5 Diagnostic LEDs ..................................................................................38
3.5.6 Setting the I/O-MAP address ...............................................................39
3.5.7 Process data in PLC/Modbus RTU mode ............................................40
3.6 RAD-DOR4-IFS - digital extension module with four outputs...............................41
3.6.1 Structure ..............................................................................................41
3.6.2 Basic circuit diagram ............................................................................42
3.6.3 Setting the DIP switches ......................................................................42
3.6.4 Diagnostic LEDs ..................................................................................43
3.6.5 Setting the I/O-MAP address ...............................................................44
3.7 RAD-DO8-IFS - digital extension module with eight outputs................................ 45
3.7.1 Structure ..............................................................................................45
3.7.2 Basic circuit diagram ............................................................................46
3.7.3 Setting the DIP switches ......................................................................46
3.7.4 Diagnostic LEDs ..................................................................................47
3.7.5 Setting the I/O-MAP address ...............................................................49
3.7.6 Process data in PLC/Modbus RTU mode ............................................49
3.8 RAD-DAIO6-IFS - analog/digital extension module with six channels .................50
3.8.1 Structure ..............................................................................................51
3.8.2 Basic circuit diagram ............................................................................52
3.8.3 Setting the DIP switches ......................................................................52
3.8.4 Diagnostic LEDs ..................................................................................53
3.8.5 Setting the I/O-MAP address ...............................................................54
3.8.6 Process data in PLC/Modbus RTU mode ............................................55
3.9 RAD-RS485-IFS modules....................................................................................55
4 Installation.................................................................................................................................57
4.1 DIN rail-mounted devices (RAD-900-IFS)............................................................57
4.1.1 Mounting/removal ................................................................................57
4.1.2 Connecting wires ................................................................................59
4.1.3 Connecting the power supply ............................................................... 59
4.1.4 Serial interfaces ...................................................................................60
4.1.5 Connecting the antenna .......................................................................62
2/138
PHOENIX CONTACT 3827_en_B
Page 5
Table of contents
4.2 Wall-mounted devices (RAD-900-DAIO6) ...........................................................63
4.2.1 Mounting ..............................................................................................63
4.2.2 Wire entry .............................................................................................64
4.2.3 Connecting wires .................................................................................64
4.2.4 Connecting power ............................................................................... 65
4.2.5 Connecting the antenna .......................................................................66
5 Configuration and startup..........................................................................................................67
5.1 Default settings of the wireless module................................................................67
5.1.1 Resetting to the default settings ........................................................... 67
5.1.2 Firmware update .................................................................................. 68
5.2 Operating mode of the wireless module ..............................................................68
5.3 Setting the address of the wireless module via the thumbwheel..........................71
5.4 Configuration via CONFSTICK ............................................................................71
5.5 Copying device settings via memory stick ...........................................................73
5.5.1 Saving parameters from the wireless module to the memory stick .......73
5.5.2 Reading the memory stick ....................................................................74
5.6 Configuration via PSI-CONF software .................................................................74
5.6.1 Extended configuration, individual settings .......................................... 75
5.6.2 Data transmission speed of the wireless interface ...............................75
5.6.3 Device settings .....................................................................................77
5.7 Starting up I/O extension modules.......................................................................79
5.7.1 Combinations of extension modules ....................................................79
5.7.2 Setting the address of the extension modules via the thumbwheel ......80
5.7.3 Wireless module in PLC/Modbus RTU dual mode ...............................81
5.8 Starting up the RAD-900-DAIO6..........................................................................82
5.8.1 Setting the address of the RAD-900-DAIO6 via the thumbwheel .........82
5.8.2 RAD-900-DAIO6 in PLC/Modbus RTU dual mode ...............................83
5.9 Startup time of the wireless station ......................................................................84
6 Serial data mode (RAD-900-IFS only).......................................................................................85
6.1 Frame-based data transmission ..........................................................................87
7 PLC/Modbus RTU mode...........................................................................................................89
7.1 Configuration via PSI-CONF software .................................................................90
7.2 Addressing I/O extension modules ...................................................................... 91
7.3 Watchdog ............................................................................................................91
3827_en_B PHOENIX CONTACT 3/138
Page 6
RAD-900-...
8 PLC/Modbus RTU dual mode...................................................................................................93
8.1 Configuration via PSI-CONF software .................................................................94
8.2 Addressing I/O extension modules ...................................................................... 95
8.3 Watchdog ............................................................................................................95
9 Addressing I/O extension modules and RAD-900-DAIO6 with Modbus RTU ...........................97
9.1 Modbus function codes .......................................................................................97
9.2 Modbus protocol.................................................................................................. 97
9.3 Addressing registers............................................................................................ 98
9.4 Module type and error code register....................................................................99
9.4.1 Assigning I/O extension modules to the register ................................100
9.5 Modbus memory map........................................................................................100
9.5.1 RAD-AI4-IFS process data .................................................................101
9.5.2 RAD-PT100-4-IFS process data ........................................................102
9.5.3 RAD-AO4-IFS process data ...............................................................103
9.5.4 RAD-DI4-IFS process data ................................................................104
9.5.5 RAD-DI8-IFS process data ................................................................104
9.5.6 RAD-DOR4-IFS process data ............................................................ 106
9.5.7 RAD-DO8-IFS process data ...............................................................107
9.5.8 RAD-DAIO6-IFS and RAD-900-DAIO6 process data .........................108
9.5.9 Complete overview of the Modbus memory map ...............................109
9.6 Error codes and formats for analog input and output values..............................112
9.7 RSSI signal register ...........................................................................................113
10 Detecting and removing errors................................................................................................115
10.1 Loopback test during serial data transmission...................................................121
11 Diagnostics on the wireless module........................................................................................123
11.1 Diagnostic LEDs ................................................................................................ 123
11.2 LED bar graph ...................................................................................................125
11.3 Diagnostics via PSI-CONF software .................................................................. 128
11.3.1 Recording parameters .......................................................................130
4/138
PHOENIX CONTACT 3827_en_B
Page 7

1 For your safety

Read this user manual carefully and keep it to hand for future reference.

1.1 Labeling of warning notes

For your safety
This symbol indicates hazards that could lead to personal injury. There are three signal words indicating the severity of a potential injury.
DANGER
Indicates a hazard with a high risk level. If this hazardous situation is not avoided, it will result in death or serious injury.
WARNING
Indicates a hazard with a medium risk level. If this hazardous situation is not avoided, it could result in death or serious injury.
CAUTION
Indicates a hazard with a low risk level. If this hazardous situation is not avoided, it could result in minor or moderate injury.
This symbol together with the NOTE signal word alerts the reader to a situation which may cause damage or malfunction to the device, hardware/software, or surrounding property.
Here you will find additional information or detailed sources of information.

1.2 Qualification of users

The use of products described in this user manual is oriented exclusively to: – Qualified electricians or persons instructed by them. The users must be familiar with the
relevant safety concepts of automation technology as well as applicable standards and other regulations.
Qualified application programmers and software engineers. The users must be familiar
with the relevant safety concepts of automation technology as well as applicable standards and other regulations.
3827_en_B PHOENIX CONTACT 5/138
Page 8
RAD-900-...

1.3 Safety notes

Please note that, in combination with antennas, the maximum permissible transmission power may be exceeded. Please set the transmission power via the software.
The use of antennas with a gain greater than 6 dBi may require that the transmit power be reduced from the default setting of 30 dBm. Regulations limit the equivalent isotropically­radiated power (EIRP) to 36 dBm. The EIRP may be calculated as the transmit power (Pt) minus any cable loss (Lc) plus the antenna gain (Ga).
EIRP = Pt - Lc + Ga
For example, in the case of a 12 dBi antenna used with a cable run with a 4 dB loss, the transmit power must be reduced to 28 dBm or less such that the EIRP does not exceed 36 dBm.
The PSI-CONF configuration and diagnostic software can be used to configure the transmit power.
Operation of the wireless system is only permitted if accessories available from Phoenix Contact are used. The use of other accessory components may invalidate the device approval status

1.4 Installation and operation

Follow the installation instructions.
NOTE:
Installation, operation, and maintenance may only be carried out by qualified specialist personnel.
Error-free operation of this device can only be ensured if transport, storage, and assembly are carried out correctly and operation and maintenance are carried out with care.
When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed.
WARNING: Risk of electrical shock
During operation, certain parts of this device may carry hazardous voltages. Disregarding this warning may result in damage to equipment and/or serious personal injury.
NOTE:
Access to circuits within the device is not permitted.
Provide a switch/circuit breaker close to the device that is labeled as the disconnect device for this device.
Provide overcurrent protection (I
During maintenance work, disconnect the device from all effective power sources.
< 6A).
6/138
PHOENIX CONTACT 3827_en_B
Page 9
For your safety
NOTE:
The IP20 degree of protection (IEC 60529/EN 60529) of the RAD-900-IFS is intended for a clean and dry environment. Do not subject the device to mechanical and/or thermal loads that exceed the specified limits.
The RAD-900-DAIO6 provides an IP65 degree of protection.
The radio should not be operated without an antenna or terminating load on the antenna connector.
NOTE:
Prolonged operation without an antenna or terminator may result in damage to the radio.
1.5 Safety regulations for installation in potentially ex­plosive areas
Installation in areas with a danger of dust explosions
WARNING:
The device has not been designed for use in potentially dust-explosive atmospheres.
Installation in Class I, Div. 2 or Zone 2
WARNING:
The device is designed for installation in Class I, Division 2/Zone 2 (UL/cUL) potentially explosive areas. Observe the specified conditions for use in potentially explosive areas.
Install the RAD-900-IFS into a housing (control or distributor box) with at least IP54 protection (EN 60529) and is certified for use in Class I, Div. 2 or Zone 2.
The RAD-900-DAIO6 meets the IP65 degree of protection does not require an additional housing.
When installing and connecting the supply and signal circuits observe the requirements of EN 60079-14. Only devices suitable for operation in Ex zone 2 and the conditions at the application site may be connected to the circuits in zone 2.
In potentially explosive areas, only connect and disconnect cables when the power is disconnected.
Installation/removal of the devices on/from the TBUS DIN rail connector may only be performed when no voltage is applied.
3827_en_B PHOENIX CONTACT 7/138
Page 10
RAD-900-...

1.6 Conformance

FCC
NOTE:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case, the user will be required to correct the interference at his own expense.
Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
This equipment complies with the FCC RF radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with a minimum distance of 20 cm between the radiator and your body.
FCC certificate: SGV-SHR-900
Industry Canada (IC)
Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (EIRP) is not more than that permitted for successful communication.
This device has been designed to operate with the antennas listed in this document and having a maximum gain of 12 dB. Antennas not included in this list or having a gain greater than 12 dB are strictly prohibited for use with this device. The required antenna impedance is 50 .
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (EIRP) is not more than that necessary for successful communication.
IC certificate: IC4720C-SHR900
8/138
PHOENIX CONTACT 3827_en_B
Page 11

2 Short description

Radioline is a wireless system for the transmission of analog and digital I/O signals and serial data. A Radioline network may contain up to 250 stations, and features a self-healing network topology. The Radioline product family consists of a DIN rail-mounted 900MHz transceiver, a variety of I/O extension modules for connection to the transceiver, an outdoor NEMA 4X version with built in I/O, and an RS-485 multiplexer module for expansion of a wireless I/O system.

2.1 RAD-900-IFS wireless module

In addition to an RS-232 and RS-485 two-wire interface, the RAD-900-IFS wireless module supports the option of directly connecting up to 32 I/O extension modules in the station structure via the DIN rail connector.
Addressing of the wireless module and I/O mapping of the extension modules is carried out quickly and easily by means of the thumbwheel on the front. You can use the yellow thumbwheel on the wireless module in order to set the RAD ID, and the white thumbwheel on the extensions modules to set the I/O-MAP address. Programming knowledge is not required. You can easily start up the wireless network without the need for software.
The PSI-CONF configuration and diagnostic software for special functions and diagnostics options in the wireless module is available free of charge.
Short description
Features
Flexible network applications: I/O data, serial data, PLC/Modbus RTU mode – Adjustable data rates for the wireless interface – Easy point-to-point or network structures (star, mesh) – Yellow thumbwheel for the unique addressing of wireless modules in the wireless
network – Integrated RS-232 and RS-485 interface – Can be extended with up to 32 I/O modules per station via DIN rail connector
(hotswappable) – 128-bit AES data encryption and authentication – Unique network addressing via plug-in configuration memory (RAD-CONF) for
secure, parallel operation of multiple networks with different RF bands – Data rates and ranges can be configured using the PSI-CONF software – UL/cUL listed for installation in Class I, Div. 2/Zone 2 environments
3827_en_B PHOENIX CONTACT 9/138
Page 12
RAD-900-...

2.1.1 Structure

Figure 2-1 RAD-900-IFS structure
Table 2-1 RAD-900-IFS structure
Item Designation
1 RSMA antenna connection (socket) 2 Test output RSSI (0...3 V DC) for evaluation of the wireless signal strength 3 Device supply (+24VDC, 0V) 4 12-pos. programming interface (S-PORT) 5 RAD ID address setting via thumbwheel 6 SET button 7 Connection option for TBUS DIN rail connector 8 DIN rail 9 DIN rail release latch 10 Connection terminal block RS-485 interface 11 Connection terminal block RS-232 interface 12 Relay output with PDT contact (floating) 13 D-SUB 9 connector (RS-232 interface) 14 RS-232/485 serial interface status LED (RX/TX) 15 LED bar graph for displaying the wireless signal strength 16 ERR status LED, red (communication error) 17 DAT status LED, green (BUS communication) 18 PWR status LED, green (supply voltage)
10/138
PHOENIX CONTACT 3827_en_B
Page 13
Circuit diagram
Short description
RAD-ID
S-Port
RF
RSSI+
2.1
2.2
1.1
1.2
RSSI-
+24 V
0 V
U
µC
DC
DC
IFS
IFS
RS485
RS232
COM
NO
NC
D(A)
D(B)
RX
TX
GND
4.1
4.2
5.1
5.2
5.3
1
6.1
1
6.2
1
6.3
Figure 2-2 RAD-900-IFS circuit diagram

2.2 RAD-900-DAIO6

The RAD-900-DAIO6 is a NEMA 4X-rated wireless device with one analog input, one analog output, two digital inputs, and two digital outputs directly integrated. It does not have a serial interface.
The RAD-900-DAIO6 may be AC- or DC-powered, and addressing of the wireless module and I/O mapping of the extension modules is carried out quickly and easily by means of the thumbwheel on the front. You can use the yellow thumbwheel on the wireless module in order to set both the RAD ID and I/O-MAP address. Programming knowledge is not required. You can easily start up the wireless network without the need for software. It is interoperable with the RAD-900-IFS.
The PSI-CONF configuration and diagnostic software for special functions and diagnostics options in the wireless module is available free of charge.
3827_en_B PHOENIX CONTACT 11/138
Page 14
RAD-900-...

2.2.1 Structure

1
18 17
19
COM NO NCLV HV COMLV HV COM COM NO NC
DIGITAL IN 2
FUSE
DIGITAL IN 1
DC
COM NO NC
U I COM PWR +I -I + -+ -
230V
POWER
RF LINK
AC
ANALOG OUT
2021 22
DIGITAL OUT 1
DIGITAL OUT 2
ANALOG IN
131415
21112
S-PORT
DIP
ON-OFF
RAD
ID
PWR
DAT
ERR
RSSI
RF
LINK
3
4-3-2-1
4 5 6 8
SET
7 9
D1
1 2
D2
10
16
Figure 2-3 RAD-900-DAIO6 structure
Table 2-2 RAD-900-DAIO6 structure
Item Designation
1 N-type antenna 2 12-pos. programming interface (S-PORT) 3 DIP switches for configuring I/O 4 RAD ID address setting via thumbwheel 5 PWR status LED, green (supply voltage) 6 DAT status LED, green (I/O communication) 7 ERR status LED, red (communication error) 8 SET button 9 LED bar graph for displaying the wireless signal strength 10 Status LEDs of the digital VO 11 Relay output with floating PDT contact 12 Digital input as wide-range input 13 Analog input for 2-, 3-, and 4-wire measuring transducers 14 Analog output (current or voltage) 15 RF link 16 Test output RSSI (0...3 V DC) for evaluation of the wireless signal strength 17 Device supply (+24VDC/120 V AC, 0V/neutral) 18 Fuse 19 Power selection switch 20 Ground lug 21 Internal ground screw 22 Breather
12/138
PHOENIX CONTACT 3827_en_B
Page 15
Short description
Table 2-3 DIP switches of the RAD-DAIO6-IFS
DIP switch
Setting Output signal 1 2 3 4
Analog IN 0 ... 20 mA OFF Analog IN 4 ... 20 mA ON Analog OUT RESET OFF Analog OUT HOLD ON Digital OUT1 RESET OFF Digital OUT1 HOLD ON Digital OUT2 RESET OFF Digital OUT2 HOLD ON
Circuit diagram
RF
RF LINK
RAD-ID
S-Port
COM
NO
NC
COM
NO
NC
1
1
1
RSSI +
RSSI -
+24VDC/120VAC
0V/N
U
PWR
+I
-I
1
µC
1
V
1
I
LOOP
U
I
Figure 2-4 RAD-900-DAIO6 circuit diagram
COM
2
NO
2
NC
2
DI
2L
DI
2H
DI
2
DI
1L
DI
1H
DI
U
1
I
1
1
1
3827_en_B PHOENIX CONTACT 13/138
Page 16
RAD-900-...
14/138
PHOENIX CONTACT 3827_en_B
Page 17
Description of I/O extension modules

3 Description of I/O extension modules

Various I/O extension modules are available for setting up the wireless system quickly and easily. This allows the number and type of I/O signals to be configured for specific applications.
For a detailed description of the available I/O extension modules, refer to the pages in Table 3-1.
Table 3-1 I/O extension modules
Module type Descriptor Order No. See
Analog Four analog inputs RAD-AI4-IFS 2901537 16
Four Pt 100 inputs RAD-PT100-4-IFS 2904035 20 Four analog outputs RAD-AO4-IFS 2901538 28
Digital Four digital inputs RAD-DI4-IFS 2901535 32
Eight digital inputs or two pulse inputs
Four digital relay outputs
Eight digital transistor ­outputs
Analog/digital One analog
input/output, two digital wide-range ­inputs/outputs
RAD-DI8-IFS 2901539 35
RAD-DOR4-IFS 2901536 41
RAD-DO8-IFS 2902811 45
RAD-DAIO6-IFS 2901533 50
page
3827_en_B PHOENIX CONTACT 15/138
Page 18
RAD-900-...

3.1 RAD-AI4-IFS - analog extension module with four inputs

The analog RAD-AI4-IFS I/O extension module can process up to four input signals between 0/4 mA ... 20 mA. All inputs are electrically isolated from one another, from the supply voltage, and from the electronics.
A supply voltage of 12 V DC, minimum, is available at the PWR for passive sensors (see Figure 3-1, item 1).

3.1.1 Structure

2
1
P
w r
P
w
12
11
10
r
P W
R
DAT
ER
R
P
w r
P
w r
P
w
r
1
+
I
1
­I
1
P
w
r
2
+ I
2
­I
2
O N
8
­I
1
­I
2
­I
3
­I
4
RAD-AI4-IFS
IO-MAP
3
4
1
+
I
1
2
+
I
2
O
F F
1
2
3
4
DI
P-1
8
3
+
I
3
4
+
I
4
5
6
7
9
8
connection terminal block
1
Figure 3-1 RAD-AI4-IFS structure
Item Designation
1 Analog input 2 for 2-, 3-, 4-wire measuring transducers 2 Analog input 1 for 2-, 3-, 4-wire measuring transducers 3 DIP switches for configuring the analog inputs (current/voltage input) 4 White thumbwheel for setting the I/O-MAP address 5 Connection option for DIN rail connector 6 DIN rail 7 Metal foot catch for DIN rail fixing 8 Analog input 3 for 2-, 3-, 4-wire measuring transducers 9 Analog input 4 for 2-, 3-, 4-wire measuring transducers 10 ERR status LED, red (communication error) 11 DAT status LED, green (bus communication) 12 PWR status LED, green (supply voltage)
16/138
PHOENIX CONTACT 3827_en_B
Page 19

3.1.2 Basic circuit diagram

Description of I/O extension modules
PWR
2
3.1 +I
2
3.2
PWR IN
2.1
-I
2 Wire
Out
PWR IN
Out
3 Wire
GND
Out
U
4 Wire
S
GND
2
3.3
2.2
PWR
1
2.1
2.1 +I
1
2.2
2.2
-I
1
2.3
2.3
2.2
2.3
IO-MAP
V
LOOP
I
V
LOOP
I
µC
IFS
DCDCIFS
PWR
3
LOOP
LOOP
4.1
+I
3
4.2
I
-I
3
4.3
PWR
4
5.1
+I
4
5.2
I
-I
4
5.3
V
V
Figure 3-2 Basic circuit diagram for the RAD-AI4-IFS

3.1.3 Setting the DIP switches

Using the DIP switches on the front, you can configure the inputs signals (0 mA ... 20 mA or 4 mA ... 20 mA). Any changes in the setting of the DIP switches will be directly applied.
In PLC/Modbus RTU mode, the setting of the input signals is evaluated for error diagnostics. With the setting 4 mA ... 20 mA, it is, for example, possible to detect an open circuit.
-I1+I1PWR1
1WR1
-I2+I2PWR2
22
OFFON 1 2 3 4
DIP-1
PWR
DAT
ERR
-I3+I3PWR3
3WR3
-I4+I4PWR4
44
Figure 3-3 DIP switches of the RAD-AI4-IFS
3827_en_B PHOENIX CONTACT 17/138
Page 20
RAD-900-...
Table 3-2 DIP switches of the RAD-AI4-IFS
DIP switch
Setting Input signal 1 2 3 4
Analog IN1 0 mA ... 20 mA OFF Analog IN1 4 mA ... 20 mA ON Analog IN2 0 mA ... 20 mA OFF Analog IN2 4 mA ... 20 mA ON Analog IN3 0 mA ... 20 mA OFF Analog IN3 4 mA ... 20 mA ON Analog IN4 0 mA ... 20 mA OFF Analog IN4 4 mA ... 20 mA ON

3.1.4 Diagnostic LEDs

The RAD-AI4-IFS I/O extension module uses a total of three LEDs to indicate the operating states.
-I1+I1PWR1
1WR1
-I2+I2PWR2
22
OFFON 1 2 3 4
DIP-1
PWR
DAT
ERR
-I3+I3PWR3
3WR3
-I4+I4PWR4
44
Figure 3-4 Diagnostic LEDs of the RAD-AI4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFF No supply voltage ON Supply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFF No communication Flashing Configuration and addressing mode ON Cyclic data communication
18/138
PHOENIX CONTACT 3827_en_B
Page 21
Description of I/O extension modules
ERR LED
The red ERR LED indicates the error status.
OFF No error Flashing
Slow (1.4 Hz) I/O-MAP address changed Fast (2.8 Hz) No bus communication
ON Critical internal error

3.1.5 Setting the I/O-MAP address

Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline wireless system is addressed using the I/O-MAP address. You can assign a maximum of 01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-3 Setting the I/O-MAP address for the RAD-AI4-IFS
Thumbwheel
Description
setting
01 ... 99 I/O-MAP address 00 Delivery state **, 1* ... 9* Setting not permitted *1 ... *9 Interface System slave address, for use with other Interface System
(IFS) master devices

3.1.6 Process data in PLC/Modbus RTU mode

The process image of the I/O extension module consists of six data words. For additional information, please refer to Section 3.1, “RAD-AI4-IFS - analog extension module with four inputs”.
I/O module Module type IDNumber of
registers
RAD-AI4-IFS 20
hex
06
hex
Address area Function code
30xx0 ... 30xx5 fc 04
3827_en_B PHOENIX CONTACT 19/138
Page 22
RAD-900-...

3.2 RAD-PT100-4-IFS - extension module with four temperature inputs

Use the I/O extension modules in connection with the RAD-900-... wireless module, firmware version 1.40 or later. You can update the firmware free of charge using the PSI-CONF software, Version 2.04 or later.
The firmware and software can be found on the Internet at
The analog RAD-PT100-4-IFS I/O extension module has four Pt 100 inputs for temperatures between -50°C ... +250°C. The Pt 100 inputs T1 ... T4 can be mapped to the analog outputs I1/U1 ... I4/U4 of the RAD-AO4-IFS extension module. All the inputs are electrically isolated from one another, from the supply voltage, and from the remaining electronics.
Pt 100 resistance thermometers can be connected to the RAD-PT100-4-IFS I/O extension module. The thermometers change their resistance depending on the temperature. The Pt 100 input signals are acquired by the RAD-PT100-4-IFS and can be mapped to proportional, analog voltage or current signals of the RAD-AO4-IFS output module.
Example: At the Pt 100 input, a current of 0 mA or a voltage of 0 V is released at the output module at a temperature of -50°C. At the Pt 100 input, a current of 20 mA or a voltage of 10 V is released at the output at a temperature of 250°C.
phoenixcontact.net/products.
Pt 100 input Analog output
-50°C 0 mA or 0 V +250°C 20 mA or 10 V

3.2.1 Connecting sensors

You can connect 2-wire or 3-wire sensors to the extension module. Observe the measuring errors depending on the different measuring methods.
2-wire connection technology
2-wire connection technology is the most cost-effective connection method. The temperature-related voltage is not directly measured at the sensor and therefore falsified by the two cable resistances R measurement to become useless. Please observe the diagrams in Section “Measuring errors using 2-wire connection technology” on page 22.
With 2-wire technology, you need an insertion bridge between terminals x.2 and x.3.
. The measuring errors that occur may lead to the entire
L
20/138
PHOENIX CONTACT 3827_en_B
Page 23
Description of I/O extension modules
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
A
D
1mA
A
D
IFS
I+
+I3
4.1
-U3
4.2
-I3
4.3
+I4
5.1
-U4
5.2
-I4
5.3
RL
I–
RL
ϑ
RTD
Figure 3-5 2-wire connection technology
3-wire connection technology
With 3-wire connection technology, the temperature-related voltage is measured several times. Corresponding calculations additionally reduce the effect of the cable resistance on the measurement result. The results are almost as good as those achieved using the 4-wire technology.
The cable resistances R
at the terminals +I and -I must have the same value. This allows
L
you to subtract the established cable resistance from the measurement result and to get the Pt 100 platinum resistance value.
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
1mA
A
D
1mA
A
D
I+
+I3
4.1
-U3
4.2
-I3
4.3
+I4
5.1
-U4
5.2
-I4
5.3
RL
U–
I–
RL
ϑ
RTD
DC
IFS
DC
IFS
Figure 3-6 3-wire connection technology
3827_en_B PHOENIX CONTACT 21/138
Page 24
RAD-900-...
4-wire connection technology
The RAD-PT100-4-IFS does not support the 4-wire connection technology.
If you want to use a 4-wire sensor, only connect three of the four wires.
The fourth wire should be left unwired. Otherwise there will be a different resistance in
the +I and -I cables owing to the parallel connection of two cable resistances.
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
+I3
4.1
-U3
4.2
A
-I3
D
D
IFS
4.3
(U+) I+
1mA
+I4
5.1
-U4
5.2
A
-I4
5.3
RL
U–
I–
RL
ϑ
RTD
Figure 3-7 4-wire connection technology

3.2.2 Measuring errors using 2-wire connection technology

8
T [K]
6
4
2
0
0 2,5 5 7,5 10 12,5 15 17,5 20
Figure 3-8 Systematic temperature measuring error ΔT depending on the cable
length l
I [m]
22/138
Curves depending on cable cross section A
1 Temperature measuring error for A = 0.25 mm 2 Temperature measuring error for A = 0.5 mm 3 Temperature measuring error for A = 1.0 mm 4 Temperature measuring error for A = 1.5 mm
2
2
2
2
(Measuring error valid for: copper cable χ = 57 m/Ωmm2, TA = 25°C and Pt 100 sensor)
PHOENIX CONTACT 3827_en_B
Page 25
Description of I/O extension modules
10
8
T [K]
6
4
2
0
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
A [mm ]
2
Figure 3-9 Systematic temperature measuring error ΔT depending on the cable cross
section A
2,5
2
T [K]
1,5
1
0,5
0
-50 -30 -10 10 30 50 70 90
T [°C]
Figure 3-10 Systematic temperature measuring error ΔT depending on the cable
temperature T
A
(Measuring error valid for: copper cable χ = 57 m/Ωmm2, TA = 25°C and Pt 100 sensor)
Make sure that the cable resistance and therefore the measuring error is as low as possible.
Use sensor cables that are as short as possible.
Avoid conductor cross sections smaller than 0.5 mm
2
.
The temperature has only a small influence on the cable resistance.
You can calculate the cable resistance as follows:
= R
R
L
R
L
R
L
R
L20
x [1 + 0.00391x (TA - 20°C)]
L20
l
=
x [1 + 0.00391x (TA - 20°C)]
χ x A K
K
Cable resistance in Ω Cable resistance at 20°C in Ω
l Line length in m
2
χ Specific resistance of copper in m/ A Cable cross section in mm
2
Ωmm
0.0039 1/K Temperature coefficient for copper (degree of purity of 99.99%) T
A
Ambient temperature (cable temperature) in °C
Due to there being two cable resistances in the measuring system, the value must be doubled. Using the average temperature coefficient α = 0.385 Ω/K for Pt 100, the absolute measuring error in Kelvin can be determined for platinum sensors according to DIN standards.
3827_en_B PHOENIX CONTACT 23/138
Page 26
RAD-900-...

3.2.3 Shielding of the sensor cables

Always connect the analog sensors using shielded, twisted pair cables (e.g., LiYCY, TP 2 x 2 x 0.5 mm
2
).
Immediately following entry in the control cabinet, connect the cable shields to the
corresponding shield connection clamps.
Please note that the electrical isolation between the channels may no longer occur when connecting the shields. The isolating distances between the individual channels need to be re-evaluated after connecting the shields. The distances between the individual wires and the common shields are crucial in this respect.
ϑ
RTD
ϑ
RTD
I+
RL
U–
I–
RL
I+
RL
U–
I–
RL
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
A
D
1mA
A
D
IFS
I+
+I3
4.1
-U3
4.2
-I3
4.3
+I4
5.1
-U4
5.2
-I4
5.3
RL
U–
I–
RL
I+
RL
U–
I–
RL
ϑ
RTD
ϑ
RTD
Figure 3-11 Shielding with 3-wire connection technology
2-wire connection technology with twisted pair cables and shielding
24/138
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
+I3
I+
4.1
-U3
4.2
A
-I3
D
D
IFS
4.3
1mA
+I4
5.1
-U4
5.2
A
-I4
5.3
RL
I–
RL
ϑ
RTD
Figure 3-12 2-wire connection technology with twisted pair cables and shielding
PHOENIX CONTACT 3827_en_B
Page 27
Description of I/O extension modules
3-wire connection technology with twisted pair cables and shielding
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
+I3
I+
4.1
-U3
4.2
A
-I3
D
D
4.3
1mA
+I4
5.1
-U4
5.2
A
-I4
5.3
RL
U–
I–
RL
ϑ
RTD
IFS
Figure 3-13 3-wire connection technology with twisted pair cables and shielding

3.2.4 Structure

2
1
+ I
1
+ I
11
10
2
PW
R
D
AT
ER
9
R
­U
­U
8
1
-I
1
2
­I
2
8
+
I
2
RAD-PT100-4-IFS
IO-MAP
+
I
1
­U
1
­I
1
-U
2
­I
2
4
5
6
3
I
3
I
­U
4
3
-
-
U
I
3
4
­I
4
8
7
Figure 3-14 RAD-PT100-4-IFS structure
Item Designation
1 Pt 100 input 2 for 2- and 3-wire sensors 2 Pt 100 input 1 for 2- and 3-wire sensors 3 White thumbwheel for setting the I/O-MAP address 4 Connection option for DIN rail connector 5 DIN rail 6 Metal foot catch for DIN rail fixing 7 Pt 100 input 3 for 2- and 3-wire sensors 8 Pt 100 input 4 for 2- and 3-wire sensors 9 ERR status LED, red (communication error) 10 DAT status LED, green (bus communication) 11 PWR status LED, green (supply voltage)
3827_en_B PHOENIX CONTACT 25/138
Page 28
RAD-900-...

3.2.5 Basic circuit diagram

+I
+I
1
1
2.1
2.2
2.3
-I
1
2-wire
+I
1
2.1
-U
1
2.2
2.3
-I
1
3-wire
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
+I3
4.1
-U3
4.2
A
-I3
D
D
IFS
4.3
1mA
+I4
5.1
-U4
5.2
A
-I4
5.3
Figure 3-15 Basic circuit diagram for the RAD-PT100-4-IFS
With 2-wire technology, you need an insertion bridge between terminals x.2 and x.3. In this case, the measuring accuracy is reduced (see “Measuring errors using 2-wire connection technology” on page 22).

3.2.6 Diagnostic LEDs

The RAD-PT100-4-IFS I/O extension module uses a total of three LEDs to indicate the operating states.
Figure 3-16 Diagnostic LEDs of the RAD-PT100-4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFF No supply voltage ON Supply voltage OK
26/138
PHOENIX CONTACT 3827_en_B
Page 29
Description of I/O extension modules
DAT LED
The green DAT LED indicates the bus communication status.
OFF No communication Flashing Configuration and addressing mode ON Cyclic data communication
ERR LED
The red ERR LED indicates the error status.
OFF No error Flashing
Slow (1.4 Hz) I/O-MAP address changed Fast (2.8 Hz) No bus communication
ON Critical internal error

3.2.7 Setting the I/O-MAP address

Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline wireless system is addressed using the I/O-MAP address. You can assign a maximum of 01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-4 Setting the I/O-MAP address for the RAD-PT100-4-IFS
Thumbwheel
Description
setting
01 ... 99 I/O-MAP address 00 Delivery state **, 1* ... 9* Setting not permitted *1 ... *9 Interface System slave address, for use with other
Interface System (IFS) master devices

3.2.8 Process data in PLC/Modbus RTU mode

The process image of the I/O extension module consists of six data words. For additional information, please refer to Section 3.2, “RAD-PT100-4-IFS - extension module with four temperature inputs”.
I/O module Module type IDNumber of
registers
RAD-PT100-4-IFS 21
hex
06
hex
Address area Function
code
30xx0 ... 30xx5 fc 04
3827_en_B PHOENIX CONTACT 27/138
Page 30
RAD-900-...

3.3 RAD-AO4-IFS - analog extension module with four outputs

Using the analog RAD-AO4-IFS I/O extension module, up to four signals between 0/4 mA ... 20 mA can be output. All the outputs are electrically isolated from one another, from the supply voltage, and from the electronics.
Use either the current or voltage output per analog channel.

3.3.1 Structure

2
1
U
1
U
12
11
10
2
P W
R
DA
T
ER
R
U
1
I
1
1
U
2
I
2
2
1
2
RAD-AO4-IFS
IO-MAP
3
4
I
1
I
2
O
F F
1
ON 2
3
4
D
IP-1
8
8
5
6
7
U
3
U
I
4
3
I
4
3
4
9
8
Figure 3-17 RAD-AO4-IFS structure
Item Designation
1 Analog output 2 (alternatively current or voltage) 2 Analog output 1 (alternatively current or voltage) 3 DIP switches for configuring the outputs (current/voltage output) 4 White thumbwheel for setting the I/O-MAP address 5 Connection option for DIN rail connector 6 DIN rail 7 Metal foot catch for DIN rail fixing 8 Analog output 3 (alternatively current or voltage) 9 Analog output 4 (alternatively current or voltage) 10 ERR status LED, red (communication error) 11 DAT status LED, green (bus communication) 12 PWR status LED, green (supply voltage)
28/138
PHOENIX CONTACT 3827_en_B
Page 31

3.3.2 Basic circuit diagram

Description of I/O extension modules
0/4...20 mA
GND
0...10V DC
GND
U
2
3.1 I
2
3.2
3.2
2
3.3
3.3
U
1
2.1
2.1 I
1
2.2
1
2.3
2.3
IO-MAP
U
I
U
I
µC
IFS
DCDCIFS
U
4
4.1
U
I
4
4.2
I
4
4.3
U
3
5.1
U
I
3
5.2
I
3
5.3
Figure 3-18 Basic circuit diagram for the RAD-AO4-IFS

3.3.3 Setting the DIP switches

You can use the DIP switches on the front to set the behavior of the outputs in the event of an error (e.g., interruption of the wireless connection). Any changes in the setting of the DIP switches will be directly applied.
RESET = Output value is set to 0 – HOLD = Hold last valid output value
1
U1I2I1
11
2U2
222
OFFON 1 2 3 4
DIP-1
PWR
DAT
ERR
3
3
U3I4I3
3
4U4
444
Figure 3-19 DIP switches of the RAD-AO4-IFS
3827_en_B PHOENIX CONTACT 29/138
Page 32
RAD-900-...
Table 3-5 DIP switches of the RAD-AO4-IFS
DIP switch
Input Output signal 1 2 3 4
Analog OUT1 RESET OFF Analog OUT1 HOLD ON Analog OUT2 RESET OFF Analog OUT2 HOLD ON Analog OUT3 RESET OFF Analog OUT3 HOLD ON Analog OUT4 RESET OFF Analog OUT4 HOLD ON

3.3.4 Diagnostic LEDs

The RAD-AO4-IFS I/O extension module uses a total of three LEDs to indicate the operating states.
1
U1I2I1
11
2U2
222
OFFON 1 2 3 4
DIP-1
PWR
DAT
ERR
3
3
U3I4I3
3
4U4
444
Figure 3-20 Diagnostic LEDs of the RAD-AO4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFF No supply voltage ON Supply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFF No communication Flashing Configuration and addressing mode ON Cyclic data communication
30/138
PHOENIX CONTACT 3827_en_B
Page 33
Description of I/O extension modules
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding input module has not been found.
OFF No error Flashing
Slow (1.4 Hz) I/O-MAP address changed Fast (2.8 Hz) Wireless module in I/O data mode
Missing input module – No bus communication
Wireless module in PLC/Modbus RTU mode
No Modbus communication (safe state of outputs,
depending on DIP switch setting)
ON Critical internal error

3.3.5 Setting the I/O-MAP address

Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline wireless system is addressed using the I/O-MAP address. You can assign a maximum of 01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-6 Setting the I/O-MAP address for the RAD-AO4-IFS
Thumbwheel
Description
setting
01 ... 99 I/O-MAP address 00 Delivery state **, 1* ... 9* Setting not permitted *1 ... *9 Interface System slave address, for use with other
Interface System (IFS) master devices

3.3.6 Process data in PLC/Modbus RTU mode

The process image of the I/O extension module consists of six data words. For additional information, please refer to Section 3.3, “RAD-AO4-IFS - analog extension module with four outputs”.
I/O module Module type IDNumber of
registers
RAD-AO4-IFS 30
hex
06
hex
Address area Function code
40xx0 ... 40xx5 fc 03, 16
3827_en_B PHOENIX CONTACT 31/138
Page 34
RAD-900-...

3.4 RAD-DI4-IFS - digital extension module with four inputs

WARNING: Risk of electric shock
Use the same phase for digital inputs and digital outputs. The isolating voltage between the individual channels must not exceed 300 V.
The digital RAD-DI4-IFS I/O extension module can process up to four input signals. The digital inputs process voltages between 0 V ... 50 V AC/DC at the low-voltage input and voltages between 0 V ... 250 V AC/DC at the high-voltage input. All inputs are electrically isolated from one another, from the supply voltage, and from the electronics.

3.4.1 Structure

2
1
D
I
1
L
D
D
I
I
2
1
L
H
D
D
I
I
2
1
H
D
I
12
11
10
9
2
RAD-DI4-IFS
PW
R
D A
T
8
8
E R
R
IO-MAP
DI1
D I2
DI3
DI4
D
I
3L
D
D
I
I
4L
3H
D
D
I
I
4H
3
D
I
4
D
I
1
L
D
I
1
H
D
I
1
D
I
2L
D
I
2H
D
I
2
4
5
6
3
8
7
32/138
Figure 3-21 RAD-DI4-IFS structure
Item Designation
1 Digital input as wide-range input 2 Digital input as wide-range input 3 White thumbwheel for setting the I/O-MAP address 4 Connection option for DIN rail connector 5 DIN rail 6 Metal foot catch for DIN rail fixing 7 Digital input as wide-range input 8 Digital input as wide-range input 9 Status LEDs for digital inputs DI1 ... DI4 10 ERR status LED, red (communication error) 11 DAT status LED, green (bus communication) 12 PWR status LED, green (supply voltage)
PHOENIX CONTACT 3827_en_B
Page 35

3.4.2 Basic circuit diagram

IO-MAP
Description of I/O extension modules
10...50V AC/DC
GND
50...250V AC/DC
GND
DI
2L
2.1
2.1 DI
2H
2.2 DI
2
2.3
2.3
DI
1L
1.1 DI
1H
1.2
1.2 DI
1
1.3
1.3
µC
IFS
DCDCIFS
DI
3L
5.1
DI
3H
5.2
DI
3
5.3
DI
4L
6.1
DI
4H
6.2
DI
4
6.3
Figure 3-22 Basic circuit diagram for the RAD-DI4-IFS

3.4.3 Diagnostic LEDs

The RAD-DI4-IFS I/O extension module uses a total of seven LEDs to indicate the operating states.
DI1L DI1H DI1
1L 1H 1
DI2L DI2H DI2
2L 2
PWR
DAT
ERR
DI1
DI2
DI3
DI4
DI3L DI3H DI3
33H3L
DI4L DI4H DI4
4H4L
Figure 3-23 Diagnostic LEDs of the RAD-DI4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFF No supply voltage ON Supply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFF No communication Flashing Configuration and addressing mode ON Cyclic data communication
3827_en_B PHOENIX CONTACT 33/138
Page 36
RAD-900-...
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding output module has not been found.
OFF No error Flashing
Slow (1.4 Hz) I/O-MAP address changed Fast (2.8 Hz) No bus communication
ON Critical internal error
DI1 ... DI4
The yellow DI1 ... DI4 LEDs indicate the status of the digital inputs.

3.4.4 Setting the I/O-MAP address

Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline wireless system is addressed using the I/O-MAP address. You can assign a maximum of 01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-7 Setting the I/O-MAP address for the RAD-DI4-IFS
Thumbwheel
Description
setting
01 ... 99 I/O-MAP address 00 Delivery state **, 1* ... 9* Setting not permitted *1 ... *9 Interface System slave address, for use with other
Interface System (IFS) master devices

3.4.5 Process data in PLC/Modbus RTU mode

The process image of the I/O extension module consists of two data words. For additional information, please refer to Section 3.4, “RAD-DI4-IFS - digital extension module with four inputs”.
I/O module Module type IDNumber of
registers
RAD-DI4-IFS 01
hex
02
hex
Address area Function code
30xx0 ... 30xx1 fc 04
34/138
PHOENIX CONTACT 3827_en_B
Page 37
Description of I/O extension modules

3.5 RAD-DI8-IFS - digital extension module with eight inputs

Use the I/O extension modules in connection with the RAD-900-... wireless module, firmware version 1.40 or later. You can update the firmware free of charge using the PSI-CONF software, Version 2.04 or later.
The firmware and software can be found on the Internet at
The digital RAD-DI8-IFS I/O extension module can process up to eight digital input signals or two pulse signals. You can use DIP switch 1 to set the operating mode. For more detailed information on setting the DIP switch, please refer to page 36.
The eight digital inputs are arranged in two groups of four inputs each with a common reference potential (GND). The two DC groups are electrically isolated from one another, from the supply voltage, and from the electronics.

3.5.1 Structure

2
1
D
4
14
13
12
11
10
I
1
D
I
3
O 1 2 3 4
PW
R
DAT
8
ERR
C
N T
D
I1
D
I2
D
I3
D
I4
D
I5
D
I6
D
I7
D
I8
D
I
5
D
I
7
D
I
1
1
-4
D
I
2
D
I
3
1-4
D
I
4
1-4
D
1-4
I
2
D I
4
F
F
O
N
D
3
I P
­1
RAD-DI8-IFS
8
IO-MAP
5-8
D
5-8
I
6
D
I
8
5
6
7
9
8
phoenixcontact.net/products.
Figure 3-24 RAD-DI8-IFS structure
Item Designation
1 Digital inputs 3 + 4 2 Digital inputs 1 + 2, DI1: pulse input 1 3 White thumbwheel for setting the I/O-MAP address 4 DIP switch for switching between static mode and pulse counter mode for digital
inputs 5 Connection option for DIN rail connector 6 DIN rail 7 Metal foot catch for DIN rail fixing 8 Digital inputs 5 + 6 9 Digital inputs 7 + 8, DI7: pulse input 2 10 Status LEDs for digital inputs DI1 ... DI8
3827_en_B PHOENIX CONTACT 35/138
Page 38
RAD-900-...
Item Designation
11 CNT status LED, green (pulse counter mode) 12 ERR status LED, red (communication error) 13 DAT status LED, green (bus communication) 14 PWR status LED, green (supply voltage)

3.5.2 Basic circuit diagram

Static:
0...30,5 VDC
GND
Pulse:
0...100 Hz
GND
DI
3
3.1
1-4
3.2
2.1
DI
4
3.3
2.2
DI
1
2.1
2.1
1-4
2.2
DI
2.2
2
2.3
IO-MAP
0
1
CNT CNT
µC
DC
IFS
DC
IFS
DI
5
4.1
5-8
4.2
DI
6
4.3
DI
7
5.1
5-8
5.2
DI
8
5.3
Figure 3-25 Basic circuit diagram for the RAD-DI8-IFS

3.5.3 Setting the DIP switches

You can use the DIP switches on the front to select between static mode or pulse counter mode.
In static mode, the DI1 ... DI8 inputs are activated, 0 V ... 30.5 V DC voltage. – In pulse counter mode, the DI1 and DI7 pulse inputs are activated, 0 Hz ... 100 Hz
pulses.
The pulse counter function is only available in PLC/Modbus RTU mode. Set the operating mode using the PSI-CONF software (from Section 5.6, “Configuration via PSI-CONF software” onwards).
36/138
PHOENIX CONTACT 3827_en_B
Page 39
Description of I/O extension modules
I
Figure 3-26 DIP switches of the RAD-DI8-IFS
Table 3-8 DIP switches of the RAD-DI8-IFS
DIP switch
Input Output signal 1 2 3 4
Digital IN
Static mode OFF n.c. n.c. n.c.
DI1 ... DI8 Counter IN
Pulse counter mode ON n.c. n.c. n.c.
DI1 + DI7 n. c. = not connected, DIP switches 2 ... 4 have no function
Use DIP switch 1 to select between static mode and pulse counter mode.
Disconnect the device from the supply voltage.
Switch the supply voltage back on.
The selected mode is now active.

3.5.4 Functions in pulse counter mode

The counter state can only increase consecutively. When the maximum counter limit of 4,294,967,295 is reached, the counter is automatically set back to 0. In addition, you can manually reset the counter states in three different ways:
Reset counter state via power up
Disconnect the device power supply and then reconnect the voltage.
Reset counter state via the Modbus RTU register
Reset the counter states via Modbus RTU as follows:
DI1: bit 0 = 1 (register 40xx1) – DI7: bit 1 = 1 (register 40xx1)
3827_en_B PHOENIX CONTACT 37/138
Page 40
RAD-900-...
Reset counter state by setting the inputs
Set the corresponding input for at least 0.5 seconds:
Set the DI3 input in order to reset the DI1 counter state. – Set the DI5 input in order to reset the DI7 counter state.

3.5.5 Diagnostic LEDs

The RAD-DI8-IFS I/O extension module uses a total of twelve LEDs to indicate the operating states.
Figure 3-27 Diagnostic LEDs of the RAD-DI8-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFF No supply voltage ON Supply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFF No communication Flashing Configuration and addressing mode ON Cyclic data communication
ERR LED
The red ERR LED indicates the error status.
OFF No error Flashing
Slow (1.4 Hz) I/O-MAP address changed or mode switched using DIP
switch 1, but not yet applied
Fast (2.8 Hz) No bus communication
ON Critical internal error
38/138
PHOENIX CONTACT 3827_en_B
Page 41
Description of I/O extension modules
CNT LED
The green CNT LED indicates that pulse counter mode is activated.
OFF No error Flashing Mode switched using DIP switch 1, but not yet applied ON Pulse counter mode of digital inputs DI1 and DI7
DI1 ... DI8
The yellow DI1 ... DI8 LEDs indicate the status of the digital inputs.
In pulse counter mode: The DI1 and DI7 LEDs flash in time with the recorded pulses. The DI3 and DI5 LEDs light up when the counter state is reset.
DI3 ON (0.5 second) Counter state DI1 reset to 0 DI5 ON (0.5 second) Counter state DI7 reset to 0

3.5.6 Setting the I/O-MAP address

Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline wireless system is addressed using the I/O-MAP address. You can assign a maximum of 01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-9 Setting the I/O-MAP address for the RAD-DI8-IFS
Thumbwheel setting
01 ... 99 I/O-MAP address 00 Delivery state **, 1* ... 9* Setting not permitted *1 ... *9 Interface System slave address, for use with other
Description
Interface System (IFS) master devices
3827_en_B PHOENIX CONTACT 39/138
Page 42
RAD-900-...

3.5.7 Process data in PLC/Modbus RTU mode

The process image of the I/O extension module consists of eight data words. For additional information, please refer to Section 3.5, “RAD-DI8-IFS - digital extension module with eight inputs”.
I/O module Module type IDNumber of
registers
02
hex
Static inputs 06
hex
Pulse inputs
RAD-DI8-IFS
02
hex
Static mode 40
hex
Pulse counter mode
40
hex
Pulse counter mode
02
hex
Reset counter states
Address area Function code
30xx0 ... 30xx1 fc 04
30xx0 ... 30xx5 fc 04
40xx0 ... 40xx1 fc 03, 16
40/138
PHOENIX CONTACT 3827_en_B
Page 43
Description of I/O extension modules

3.6 RAD-DOR4-IFS - digital extension module with four outputs

WARNING: Risk of electric shock
Use the same phase for digital inputs and digital outputs. The isolating voltage between the individual channels must not exceed 300 V.
The digital RAD-DOR4-IFS I/O extension module can process up to four input signals that are switched via relay outputs. The digital outputs are designed as floating relay contacts (PDT). All outputs are electrically isolated from one another, from the supply voltage, and from the electronics.

3.6.1 Structure

2
1
C
O
M
C
1
O
N
M
O
2
1
N
N
O
C
2
1
N
C
2
OF
F
1
O
N
13
12
11
10
2
3
4
D
IP
-1
RAD-DOR4-IFS
P
W
R
D
A T
8
8
ER
R
IO-MAP
D O
1
D
O
2
D
O
3
DO
4
C
O M
C
3
N
O
O
M
3
4
N
N
O
C
3
4
N
C
4
C
O
M
1
N
O
1
N
C
1
C
O
M
2
N
O
2
N
C
2
5
6
3
7
4
9
8
Figure 3-28 RAD-DOR4-IFS structure
Item Designation
1 Relay output 2 with floating PDT contact 2 Relay output 1 with floating PDT contact 3 DIP switches for configuring the output behavior of the relay outputs (hold/reset) 4 White thumbwheel for setting the I/O-MAP address 5 Connection option for DIN rail connector 6 DIN rail 7 Metal foot catch for DIN rail fixing 8 Relay output 3 with floating PDT contact 9 Relay output 4 with floating PDT contact 10 Status LEDs for the relay outputs DO1 ... DO4 11 ERR status LED, red (communication error) 12 DAT status LED, green (bus communication) 13 PWR status LED, green (supply voltage)
3827_en_B PHOENIX CONTACT 41/138
Page 44
RAD-900-...

3.6.2 Basic circuit diagram

IO-MAP
24 V DC/250 V AC
COM
2
2.1 NO
2
2.2 NC
2
2.3
COM
1
1.1
1.1 NO
1
1.2
1.2 NC
1
1.3
µC
IFS
DCDCIFS
COM
COM
3
5.1
NO
3
5.2
NC
3
5.3
4
6.1
NO
4
6.2
NC
4
6.3
Figure 3-29 Basic circuit diagram for the RAD-DOR4-IFS

3.6.3 Setting the DIP switches

You can use the DIP switches on the front to set the behavior of the outputs in the event of an error (e.g., interruption of the wireless connection). Any changes in the setting of the DIP switches will be directly applied.
RESET = Output value is set to 0 – HOLD = Hold last output value
COM1NO1 NC1
1
1 1
COM2NO2 NC2
2
2
OFFON 1 2 3 4
DIP-1
PWR
DAT
ERR
DO1
DO2
DO3
DO4
COM3NO3 NC3
3
3 3
COM4NO4 NC4
4
4 4
42/138
Figure 3-30 DIP switches of the RAD-DOR4-IFS
Table 3-10 DIP switches of the RAD-DOR4-IFS
DIP switch
Setting Output signal 1 2 3 4
Digital OUT1 RESET OFF Digital OUT1 HOLD ON Digital OUT2 RESET OFF
PHOENIX CONTACT 3827_en_B
Page 45
Description of I/O extension modules
Table 3-10 DIP switches of the RAD-DOR4-IFS
DIP switch
Setting Output signal 1 2 3 4
Digital OUT2 HOLD ON Digital OUT3 RESET OFF Digital OUT3 HOLD ON Digital OUT4 RESET OFF Digital OUT4 HOLD ON

3.6.4 Diagnostic LEDs

The RAD-DOR4-IFS I/O extension module uses a total of seven LEDs to indicate the operating states.
COM1NO1 NC1
1
1 1
COM2NO2 NC2
2
2
OFFON 1 2 3 4
DIP-1
PWR
DAT
ERR
DO1
DO2
DO3
DO4
COM3NO3 NC3
3
3 3
COM4NO4 NC4
4
4 4
Figure 3-31 Diagnostic LEDs of the RAD-DOR4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFF No supply voltage ON Supply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFF No communication Flashing Configuration and addressing mode ON Cyclic data communication
3827_en_B PHOENIX CONTACT 43/138
Page 46
RAD-900-...
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding input module has not been found.
OFF No error Flashing
Slow (1.4 Hz) I/O-MAP address changed Fast (2.8 Hz) Wireless module in I/O data mode
Missing input module – No bus communication
Wireless module in PLC/Modbus RTU mode
No Modbus communication (safe state of outputs,
depending on DIP switch setting)
ON Critical internal error
DO1 ... DO4
The yellow LEDs DO1 ... DO4 LEDs indicate the status of the digital outputs.

3.6.5 Setting the I/O-MAP address

Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline wireless system is addressed using the I/O-MAP address. You can assign a maximum of 01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-11 Setting the I/O-MAP address for the RAD-DOR4-IFS
Thumbwheel
Description
setting
01 ... 99 I/O-MAP address 00 Delivery state **, 1* ... 9* Setting not permitted *1 ... *9 Interface System slave address, for use with other
Interface System (IFS) master devices
Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of two data words. For additional information on process data, please refer to Section 3.6, “RAD-DOR4-IFS - digital extension module with four outputs”.
I/O module Module type IDNumber of
Address area Function code
registers
RAD-DOR4-IFS 10
hex
02
hex
40xx0 ... 40xx1 fc 03, 16
44/138
PHOENIX CONTACT 3827_en_B
Page 47
Description of I/O extension modules

3.7 RAD-DO8-IFS - digital extension module with eight outputs

Use the I/O extension modules in connection with the RAD-900-... wireless module, firmware version 1.40 or later. You can update the firmware free of charge using the PSI-CONF software, Version 2.04 or later.
The firmware and software can be found on the Internet at
The digital RAD-DO8-IFS I/O extension module processes up to eight digital output signals that are switched via transistor outputs. The eight outputs are arranged in two groups of four outputs each with a common electrical supply. The two output groups are electrically isolated from one another, from the supply voltage, and from the electronics.
Since the DO1 ... DO4 and DO5 ... DO8 output groups are electrically isolated, the digital outputs must be externally supplied (see Figure 3-33).
The DO1 ... DO4 outputs are supplied via:
Terminal 1.1 (12 V DC ... 30.5 V DC) – Terminals 1.2/1.3 (GND)
The DO5 ... DO8 outputs are supplied via:
Terminal 6.1 (12 V DC ... 30.5 V DC) – Terminals 6.2/6.3 (GND)
phoenixcontact.net/products.

3.7.1 Structure

3
2
1
D
O
3
+
2
4
V
1-4
D
O
1-4
1
D
O
1-4
1-4
3
D
O
1-4
2
D
O
4
O
FF
1
O
N
15
14
13
12
2
3
4
D
IP
-1
RAD-DO8-IFS
P
W
R
D
AT
8
8
ER
R
IO-MAP
D
O1
D O2
D
O3
D O4
D
O
5
D O6
D
O
7
D O
8
D
O
5
D
O
5-8
7
+
2
4
D
V
O
5-8
5-8
6
D O
5
-8 8
5-8
Figure 3-32 RAD-DO8-IFS structure
Item Designation
1 Transistor outputs 3 + 4 2 Transistor outputs 1 + 2 3 Supply voltage for outputs 1 ... 4 4 DIP switches for setting the output behavior of the transistor outputs (hold/reset) 5 White thumbwheel for setting the I/O-MAP address 6 Connection option for DIN rail connector
+
2
4
V
1-4
1-4
1-4
DO
1
1
-4
DO
2
1
­4
D
O
4
4
6
7
8
5
11
10
9
3827_en_B PHOENIX CONTACT 45/138
Page 48
RAD-900-...
Item Designation
7 DIN rail 8 Metal foot catch for DIN rail fixing 9 Transistor outputs 5 + 6 10 Transistor outputs 7 + 8 11 Supply voltage for outputs 5 ... 8 12 Status LEDs of transistor outputs DO1 ... DO8 13 ERR status LED, red (communication error) 14 DAT status LED, green (bus communication) 15 PWR status LED, green (supply voltage)

3.7.2 Basic circuit diagram

DO
5
4.1
5-8
4.2
DO
6
4.3
Do
7
5.1
5-8
5.2
Do
8
5.3
+24V
5-8
6.1
5-8
6.2
5-8
6.3
30,5 V DC
GND
DO
3
3.1
1-4
3.2
DO
4
3.3
DO
2.1
2.2
1
2.1
1-4
2.2
DO
2
2.3
+24V
1-4
1.1
1-4
1.2
1-4
1.3
IO-MAP
0
1
µC
IFS
DCDCIFS
Figure 3-33 Basic circuit diagram for the RAD-DO8-IFS

3.7.3 Setting the DIP switches

You can use the DIP switches on the front to set the behavior of the outputs in the event of an error (e.g., interruption of the wireless connection). Any changes in the setting of the DIP switches will be directly applied.
RESET = Output value is set to 0 – HOLD = Hold last output value
46/138
PHOENIX CONTACT 3827_en_B
Page 49
Description of I/O extension modules
Figure 3-34 DIP switches of the RAD-DO8-IFS
Table 3-12 DIP switches of the RAD-DO8-IFS
DIP switch
Setting Output signal 1 2 3 4
Digital OUT 1 ... 4 RESET OFF n. c. n. c. Digital OUT 1 ... 4 HOLD ON n. c. n. c. Digital OUT 5 ... 8 RESET OFF n. c. n. c. Digital OUT 5 ... 8 HOLD ON n. c. n. c. n. c. = not connected, DIP switches 3 and 4 have no function

3.7.4 Diagnostic LEDs

The RAD-DO8-IFS I/O extension module uses a total of eleven LEDs to indicate the operating states.
Figure 3-35 Diagnostic LEDs of the RAD-DO8-IFS
3827_en_B PHOENIX CONTACT 47/138
Page 50
RAD-900-...
PWR LED
The green PWR LED indicates the supply voltage status.
OFF No supply voltage ON Supply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFF No communication Flashing Configuration and addressing mode ON Cyclic data communication
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding input module has not been found.
OFF No error Flashing Wireless module in I/O data mode
Missing input module – No bus communication
Wireless module in PLC/Modbus RTU mode
No Modbus communication (safe state of outputs, depending on
DIP switch setting)
Short circuit at one output or several outputs
ON Critical internal error
48/138
DO1 ... DO8
The yellow DO1 ... DO8 LEDs indicate the status of the digital outputs.
DO1 ... DO4 Flashing Short circuit at one output or several outputs 1 ... 4 DO5 ... DO8 Flashing Short circuit at one output or several outputs 5 ... 8
PHOENIX CONTACT 3827_en_B
Page 51
Description of I/O extension modules

3.7.5 Setting the I/O-MAP address

Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline wireless system is addressed using the I/O-MAP address. You can assign a maximum of 01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-13 Setting the I/O-MAP address for the RAD-DO8-IFS
Thumbwheel
Description
setting
01 ... 99 I/O-MAP address 00 Delivery state **, 1* ... 9* Setting not permitted *1 ... *9 Interface System slave address, for use with other
Interface System (IFS) master devices

3.7.6 Process data in PLC/Modbus RTU mode

The process image of the I/O extension module consists of four data words. For additional information, please refer to Section 3.7, “RAD-DO8-IFS - digital extension module with eight outputs”.
I/O module Module type IDNumber of
registers
02
hex
Outputs
RAD-DO8-IFS 11
hex
02
hex
Short-circuit detection
Address area Function code
40xx0 ... 40xx1 fc 03.16
30xx0 ... 30xx1 fc 04
3827_en_B PHOENIX CONTACT 49/138
Page 52
RAD-900-...

3.8 RAD-DAIO6-IFS - analog/digital extension module with six channels

WARNING: Risk of electric shock
Use the same phase for digital inputs and digital outputs. The isolating voltage between the individual channels must not exceed 300 V.
The analog/digital RAD-DAIO6-IFS I/O extension module has a total of six channels. The device is able to process two digital input and output signals as well as one analog input signal and one analog output signal. All inputs and outputs are electrically isolated from one another, from the supply voltage, and from the electronics.
Two digital inputs
The digital inputs process voltages between 0 V ... 50 V AC/DC at the low-voltage input and 0 V ... 250 V AC/DC at the high-voltage input.
Two digital outputs
The digital outputs are designed as floating relay contacts (PDT). The switching capacity is 2 A at 250 V AC/24 V DC.
Analog input
The analog input is able to process standard signals between 0/4 mA ... 20 mA. A supply voltage of at least 12 V DC is available at the PWR passive sensors.
connection terminal block for the use of
1
Analog output
The analog output is designed as active output. You can either select a current signal 0/4 mA ... 20 mA or a voltage signal 0 V ... 10 V.
Use either a current or voltage output at the analog output.
50/138
PHOENIX CONTACT 3827_en_B
Page 53
Description of I/O extension modules

3.8.1 Structure

3
2
D
I
1
L
D
1
P w
r
1
+ I
1
­I
1
D
I
1L
D
D
I
I
2L
1H
P
D
w
D
I
r
I
2H
1
1
+
D
I
I
1
2
­I
1
16
15
14
13
12
OF
F
1
O N
2
3
4
DIP-
1
P
RAD-DAIO6-IFS
W
R
DA
T
8
8
ER
R
IO-MAP
DI
1
DI2
D
O
1
D
O
2
U
1
C
O
I
M
1
C
1
N
O
O
M
1
1
2
N
N
O
C
2
1
N
C
2
Figure 3-36 RAD-DAIO6-IFS structure
Item Designation
1 Analog input for 2-, 3-, 4-wire measuring transducers 2 Digital input as wide-range input 3 Digital input as wide-range input 4 DIP switches for configuring the inputs and outputs 5 White thumbwheel for setting the I/O-MAP address 6 Connection option for DIN rail connector 7 DIN rail 8 Metal foot catch for DIN rail fixing 9 Analog output, alternatively current or voltage 10 Relay output with floating PDT contact 11 Relay output with floating PDT contact 12 Status LEDs of the digital DO1 ... DO2 13 Status LEDs of the digital DI1 ... DI2 inputs 14 ERR status LED, red (communication error) 15 DAT status LED, green (bus communication) 16 PWR status LED, green (supply voltage)
I
1
H
D
I
1
D
I
2 L
D
I
2 H
D I
2
6
7
4
8
5
11
10
9
3827_en_B PHOENIX CONTACT 51/138
Page 54
RAD-900-...

3.8.2 Basic circuit diagram

PWR IN
3.1
2 Wire
3 Wire
U
4 Wire
S
10...50V AC/DC
GND
50...250V AC/DC
GND
0...10V DC
0/4...20 mA
GND
24 V ACDC/250 V
Out
PWR IN
Out
GND
Out
GND
PWR
3.2
1
3.1 +I
1
3.1
3.2
-I
1
3.2
3.3
3.3
DI
2L
2.1
3.2
DI
2H
2.2
3.3
DI
2
2.3
2.1
DI
1L
2.3
1.1 DI
1H
1.2
1.2 DI
1
1.3
1.3
4.1
4.2
4.3
5.1
5.2
IO-MAP
V
LOOP
I
µC
IFS
DCDCIFS
U
1
4.1
U
I
1
4.2
I
1
4.3
COM
1
5.1
NO
1
5.2
NC
1
5.3
COM
2
6.1
NO
2
6.2
NC
2
6.3
Figure 3-37 Basic circuit diagram for the RAD-DAIO6-IFS

3.8.3 Setting the DIP switches

The DIP switches on the front can be used to configure the input signals ranges. In addition, you can set the behavior of the outputs in the event of an error (e.g., interruption of the wireless connection). Any changes in the setting of the DIP switches will be directly applied.
Analog output
RESET = Output value is set to 0 – HOLD = Hold last output value
Digital outputs
RESET = Relay drops out – HOLD = Hold last valid state
Figure 3-38 DIP switches of the RAD-DAIO6-IFS
52/138
PHOENIX CONTACT 3827_en_B
Page 55
Description of I/O extension modules
Table 3-14 DIP switches of the RAD-DAIO6-IFS
DIP switch
Setting Output signal 1 2 3 4
Analog IN 0 ... 20 mA OFF Analog IN 4 ... 20 mA ON Analog OUT RESET OFF Analog OUT HOLD ON Digital OUT1 RESET OFF Digital OUT1 HOLD ON Digital OUT2 RESET OFF Digital OUT2 HOLD ON

3.8.4 Diagnostic LEDs

The RAD-DAIO6-IFS I/O extension module uses a total of seven LEDs to indicate the operating states.
Figure 3-39 Diagnostic-LEDs of the RAD-DAIO6-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFF No supply voltage ON Supply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFF No communication Flashing Configuration and addressing mode ON Cyclic data communication
3827_en_B PHOENIX CONTACT 53/138
Page 56
RAD-900-...
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding output module has not been found.
OFF No error Flashing
Slow (1.4 Hz) I/O-MAP address changed Fast (2.8 Hz) Wireless module in I/O data mode
Missing input module – No bus communication
Wireless module in PLC/Modbus RTU mode
No Modbus communication (safe state of outputs,
depending on DIP switch setting)
ON Critical internal error
DI1 / DI2
The yellow DI1 and DI2 LEDs indicate the status of the digital inputs.
DO1/DO2
The yellow DO1 and DO2 LEDs indicate the status of the digital outputs.

3.8.5 Setting the I/O-MAP address

Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline wireless system is addressed using the I/O-MAP address. You can assign a maximum of 01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-15 Setting the I/O-MAP address for the RAD-DAIO6-IFS
Thumbwheel setting
01 ... 99 I/O-MAP address 00 Delivery state **, 1* ... 9* Setting not permitted *1 ... *9 Interface System slave address, for use with other
Description
Interface System (IFS) master devices
54/138
PHOENIX CONTACT 3827_en_B
Page 57
Description of I/O extension modules

3.8.6 Process data in PLC/Modbus RTU mode

The process image of the I/O extension module consists of six data words. For additional information, please refer to Section 3.8, “RAD-DAIO6-IFS - analog/digital extension module with six channels”.
I/O module Module type IDNumber of
registers
03
hex
RAD-DAIO6-IFS 60
hex
(inputs) 03
hex
Address area Function
code
30xx0 ... 30xx2 fc 04
40xx0 ... 40xx2 fc 03, 16
(outputs)

3.9 RAD-RS485-IFS modules

For some distributed systems, or networks with very large I/O counts, the master wireless device can be expanded with RAD-RS485-IFS modules. I/O extension modules in the wireless network can be mapped to I/O extension modules connected to RAD-RS485-IFS modules. This is only supported in Wire In/Wire Out mode.
DI1L
DI1H
DI1
+24V
0V
COM1
NC1
NO1
DI2L
DI2H
DI2
RSSI
+
RSSI
-
COM2
NC2
NO2
UL1 +I1 -I1
ANT
S
S
OFF ON
OFF ON
1
1
2
2
3
3
S-PORT
4
4
DIP-1
DIP-1
RAD-2400-IF
RAD-DOR4-IF
RAD-DAIO6-IFS
PWR
PWR
PWR
8 8
1 2
0
2
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DO1
DO1
SET
DO2
DO2
DO3
DO3
RXTX
DO4
DO4
D(A)
D(B)
U1 I1
1
COM3
NC3
NO3
COM1
NC1
RX
GND
NO1
TX
COM4
NC4
NO4
COM2
NC2
1
COM
NC
1
NO2
2
NO
DI1L
DI1H
DI1
+24V
0V
COM1
NC1
NO1
U1U2I1
DI2L
DI2H
DI2
RSSI
+
RSSI
-
COM2
NC2
NO2
UL1 +I1 -I1
ANT
PWR
0
DAT
ERR
RXTX
D(A)
D(B)
RX
TX
1
COM
NO
I2 2
S
S
OFF ON
OFF ON
OFF ON
1
1
1
2
2
2
3
3
3
S-PORT
4
4
4
DIP-1
DIP-1
DIP-1
RAD-2400-IF
RAD-DOR4-IF
RAD-DAIO6-IFS
PWR
PWR
PWR
1 2
8 8
2 2
1
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DO1
DO1
SET
DO2
DO2
DO3
DO3
DO4
DO4
U1 I1
U3U4I3
1
COM3
NC3
NO3
COM1
NC1
GND
I4 4
NO1
COM4
NC4
NO4
COM2
NC2
1
NC
NO2
2
+24V
0V
DI1L
DI1H
DI1
1
DI2L
DI2H
DI2
RAD-AO4-IFS
PWR
7 7
DAT
IO-MAP
ERR
DI1
DI2
DI3
DI4
3
DI3L
DI3H
DI3
DI4L
DI4H
DI4
COM1
NC1
NO1
U1U2I1
1
RSSI
+
RSSI
-
COM2
NC2
NO2
I2 2
ANT
S
RAD-DI4-IF
IO-MAP
S
S
OFF ON
OFF ON
1
1
2
2
3
3
S-PORT
4
4
DIP-1
DIP-1
RAD-AO4-IFS
RAD-2400-IF
RAD-DOR4-IF
PWR
PWR
PWR
8 8
2 2
0
3
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DO1
SET
DO2
DO3
RXTX
DO4
D(A)
D(B)
U3U4I3
3
COM3
NC3
NO3
RX
GND
I4 4
TX
COM4
NC4
NO4
1
COM
1
NC
NO
2
+24V
0V
DI1L
DI1H
DI1
Pwr1
+I1
-I1
RSSI
+
RSSI
-
DI2L
DI2H
DI2
Pwr2
+I2
-I2
ANT
S
S
OFF ON
1
2 3
S-PORT
4
RAD-AI4-IFS
RAD-DI4-IF
DIP-1
RAD-2400-IF
PWR
PWR
PWR
8 8
2 2
0
4
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DI1
SET
DI2
DI3
RXTX
DI4
D(A)
D(B)
Pwr3
+I3
-I3
DI3L
DI3H
DI3
RX
GND
Pwr4
+I4
-I4
TX
DI4L
DI4H
DI4
1
COM
1
NC
NO
2
RS-485
+24V
+24V
0V
COM1
NC1
NO1
U1U2I1
COM2
NC2
NO2
S
OFF ON
1
2 3
S-PORT
4
DIP-1
RAD-DOR4-IF
RAD-RS485-IFS
PWR
PWR
PWR
7 7
0
5
DAT
DAT
DAT
RAD-ID
IO-MAP
ERR
ERR
ERR
DO1
SET
DO2
LINK
DO3
RXTX
DO4
D(A)
D(B)
U3U4I3
COM3
NC3
NO3
COM4
NC4
NO4
COM
1
NC1
NO1
+24V
0V
COM1
NC1
NO1
1
I2 2
OFF ON
1
2 3
4
DIP-1
RAD-AO4-IFS
4 4
IO-MAP
3
I4 4
U1U2I1
COM2
NC2
NO2
S
OFF ON
OFF ON
1
1
2
2
S485-IFS
3
3
S-PORT
4
4
DIP-1
DIP-1
RAD-DOR4-IF
RAD-R
PWR
PWR
PWR
7 7
4 4
0
6
DAT
DAT
DAT
RAD-ID
IO-MAP
ERR
ERR
ERR
DO1
SET
DO2
LINK
DO3
RXTX
DO4
D(A)
D(B)
U3U4I3
COM3
NC3
NO3
COM4
NC4
NO4
COM
1
NC1
NO1
0V
COM1
NC1
NO1
U1U2I1
1
I2 2
RAD-AO4-IFS
IO-MAP
3
I4 4
1
COM2
NC2
NO2
I2 2
S
OFF ON
OFF ON
1
1
2
2
S485-IFS
3
3
S-PORT
4
4
DIP-1
DIP-1
RAD-AO4-IFS
RAD-DOR4-IF
RAD-R
PWR
PWR
PWR
7 7
4 4
0
7
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DO1
SET
DO2
LINK
DO3
RXTX
DO4
D(A)
D(B)
U3U4I3
3
COM3
NC3
NO3
I4 4
COM4
NC4
NO4
COM
1
NC1
NO1
RS-485 RS-485 RS-485
Figure 3-40 Typical RAD-RS485-IFS installation
3827_en_B PHOENIX CONTACT 55/138
Page 58
RAD-900-...
56/138
PHOENIX CONTACT 3827_en_B
Page 59

4 Installation

Installation

4.1 DIN rail-mounted devices (RAD-900-IFS)

4.1.1 Mounting/removal

You can connect up to 32 different I/O extension modules to each wireless module via the DIN rail connector. Data is transmitted and power is supplied to the I/O extension modules via the bus foot.
When using the device in a connection station, use the supplied 17.5 mm wide DIN rail connector. Only use the DIN rail connector in connection with 24 V DC devices.
Mount the wireless module to the left and the I/O extension modules exclusively to the right of the wireless module.
The individual extension modules can be arranged in any order.
Figure 4-1 Radioline connection station with up to 32 I/O extension modules
3827_en_B PHOENIX CONTACT 57/138
Page 60
RAD-900-...
A
B
C
DE
Figure 4-2 Mounting and removal
To mount a connection station with DIN rail connectors, proceed as follows:
1. Connect the DIN rail connectors together for a connection station.
2. Push the connected DIN rail connectors onto the DIN rail.
3. Place the device onto the DIN rail from above (see Figure 4-2, D). Make sure that the device and DIN rail connector are aligned correctly.
4. Holding the device by the housing cover, carefully push the device towards the mounting surface so that the device bus connector is fixed securely on the DIN rail connector.
5. Once the snap-on foot snaps onto the DIN rail, check that it is fixed securely. The device is only mechanically secured via the DIN rail.
6. Connect the desired number of I/O extension modules to the wireless module via the DIN rail connector.
58/138
Device replacement is also possible during operation when outside the hazardous area.
Removal
1. Use a suitable screwdriver to release the locking mechanism on the snap-on foot of the device (see Figure 4-2, E).
2. Hold onto the device by the housing cover and carefully tilt it upwards.
3. Carefully lift the device off the DIN rail connector and the DIN rail.
PHOENIX CONTACT 3827_en_B
Page 61

4.1.2 Connecting wires

Installation
B
PWR
DAT
8
ERR
8
A
Figure 4-3 Connecting wires
For easy installation, it is also possible to pull out the screw terminal block from the device and to re-insert it after having connected the wires.
2
1. Crimp ferrules to the wires. Permissible cable cross section: 0.2 mm (24 … 14 AWG).
2. Insert the wire with ferrule into the corresponding connection terminal block.
3. Use a screwdriver to tighten the screw in the opening above the connection terminal block. Tightening torque: 0.6 Nm
... 2.5 mm2

4.1.3 Connecting the power supply

Via screw terminal blocks
Connect a DC voltage source (10.8 V ... 30.5 V DC) to the wireless module. The nominal voltage is 24 V DC. Supply voltage to the device via the terminals 1.1 (24 V) and 1.2 (0 V). In the case of a connection station, it is sufficient to supply the first device in the group.
NOTE:
The power supply must be connected to terminals 1.1 and 1.2. Power supply via the DIN rail connector (TBUS) is not permitted.
3827_en_B PHOENIX CONTACT 59/138
Page 62
RAD-900-...
1
.1
1
.2
R
S
S
I+
R
SS
I-
+
2 4
V R S
0
S
V I +
R S
S
I
­A N
T
S.PORT
RAD-2400-IFS
PWR
D A
8
T
8
ER
R
RAD-ID
Reset
RX TX
D
(A
)
D
R
(
X
B
)
C
O
T
M
X
1
N
G
O
N
D
1
N
C
1
Figure 4-4 Connecting the power supply
In order to prevent damage to the wireless module, we recommend the installation of a surge arrester. Wiring between the surge arrester and the wireless module should be as short as possible. Please also observe the manufacturer’s specifications.

4.1.4 Serial interfaces

The RAD-900-IFS wireless module has one RS-232 interface and one RS-485 2-wire interface. Connect the I/O device to the wireless module via the corresponding serial interface.
Both serial interfaces are deactivated by default. Activate and configure the RS-232 or RS-485 interface using the PSI-CONF software (from Section 5.6, “Configuration via PSI­CONF software” onwards).
You can only use one interface per wireless module. Parallel operation of both interfaces is not possible.
4.1.4.1 Connecting the RS-485 cable
In RS-485 mode, an RS-485 network with several I/O devices can be created. Use a twisted-pair, common shielded bus
NOTE:
Observe the polarity of the RS-485 cable. Install the bus cable with a termination network at the two furthest points of the RS-485 network.
Termination resistors are integrated into the RAD-900-IFS and can be switched on using the DIP switches on the side of the module.
RS-485 pin assignment
In RS-485 mode, you can create a network with several I/O devices. Use a twisted-pair bus cable to connect the I/O devices. Install this bus cable with a termination network at the two furthest points.
Connect the single wires of the data cable to the COMBICON plug-in screw terminal block (Figure 2-1, item 10).
Make sure the signal assignment is correct.
60/138
PHOENIX CONTACT 3827_en_B
Page 63
Installation
COMBICON
+
D(B) D(A)
RAD-2400-IFS
(4.1)
-
(4.2)
RS-485
D(B) D(A)
+
-
Figure 4-5 RS-485 interface pin assignment
RS-232 pin assignment
In RS-232 mode, point-to-point connections can be established.
The RS-232 interface of the wireless module is a DTE type (Data Terminal Equipment). This means that terminal point 5.2 (Tx) is always used for transmission and terminal point
5.1 (Rx) is always used for reception. Only connect the wireless module to devices which meet the requirements of EN 60950.
According to the standard, you can connect a DCE device (Data Communication Equipment) to the RS-232 interface using a 1:1 cable (Figure 4-6). It is also possible to connect a DTE device using a crossed cable (Figure 4-7).
COMBICON D-SUB-9
RX (5.1) TX (5.2) GND (5.3)
RAD-2400-IFS (DTE)
RS-232
RX (2) TX (3) GND (5)
e.g. PLC (DCE)
Figure 4-6 RS-232 interface pin assignment (DTE - DCE)
COMBICON D-SUB-9
RX (5.1) TX (5.2) GND (5.3)
RAD-2400-IFS (DTE)
RS-232
RX (2) TX (3) GND (5)
e.g. PC (DTE)
Figure 4-7 RS-232 interface pin assignment (DTE - DTE)
If you are not sure whether the device to be connected is of DTE or DCE type, measure the voltage between TX and GND in the idle state.
If the voltage measures approximately -5 V, it is a DTE device. – If the voltage measures approximately 0 V, it is a DCE device.
3827_en_B PHOENIX CONTACT 61/138
Page 64
RAD-900-...
D-SUB 9 pin assignment
The RAD-900-IFS provides a D-SUB 9 female connector for attaching RS-232 serial devices.
Figure 4-8 D-SUB 9 straight-through cable pinouts for 3-wire (A) and 5-wire (B)
Figure 4-9 D-SUB 9 null cable pinouts for 3-wire (A) and 5-wire (B)

4.1.5 Connecting the antenna

The wireless module is provided with an RSMA antenna socket for an external antenna.
Install the antenna outside the control cabinet or building. Observe the installation instructions of the antenna and the “Installation and operation” on
page 6. Observe the maximum permissible emitted transmission power of 36 dBm. The
transmission power can be calculated as:
device transmission power + antenna gain - cable attenuation
Reduce the device transmission power, if necessary.
62/138
PHOENIX CONTACT 3827_en_B
Page 65
A
+
2
4
V
B
0
V
R
S S
I+
R
S
S
I-
+
2 4
V
RSSI+
0
V
RS
SI-
A
N
T
S.PORT
RAD-2400-IFS
PW
R
D
AT
8
8
ER
R
RAD-ID
Reset
RX TX
D
(
A
)
D
R
(
X
B )
C
O
TX G
M
1
N
O
N
D
1
N
C
1
Figure 4-10 Connecting the antenna

4.2 Wall-mounted devices (RAD-900-DAIO6)

4.2.1 Mounting

Installation
The RAD-900-DAIO6 includes mounting feet for installing the device on a vertical surface.
1. Loosen the four screws securing the cover and remove the cover.
2. Attach the mounting feet to the RAD-900-DAIO6 in the desired orientation using the included screws, flat washers and lockwashers.
4-3-2-1
Figure 4-11 Mounting feet
3827_en_B PHOENIX CONTACT 63/138
Page 66
RAD-900-...
3. Install the RAD-900-DAIO6 on the desired surface using appropriate hardware (not supplied).
152
COM NO NCLV HV COMLV HV COM COM NO NC
DIGITAL IN 2
FUSE
82
DIGITAL IN 1
DC
COM NO NC
230V
POWER
RF LINK
AC
DIGITAL OUT 1
U I COM PWR +I -I + -+ -
ANALOG IN
ANALOG OUT
DIGITAL OUT 2
S-PORT
DIP
4-3-2-1
ON-OFF
RAD
ID
PWR
DAT
SET
ERR
RSSI
RF
LINK
D1
1 2
D2
204
274
Figure 4-12 Mounting dimensions
Mounting considerations: – Avoid mounting in direct sunlight to minimize the effects of solar loading (heating). – Installation of a sun shield is recommended over the RAD-900-DAIO6 when it is
mounted in direct sunlight and the ambient temperature can exceed 45°C.

4.2.2 Wire entry

The RAD-900-DAIO6 is supplied with two 1/2-in. NPT conduit hubs installed for connection to rigid or flexible conduit. Alternatively, cable glands may be installed using suitable cables. Use an approved thread sealant to ensure a water tight seal.
WARNING:
All connections must be sealed. If not, excess moisture accumulation can accumulate inside the device. Make sure to mount the transmitter with the electrical housing positioned downward for drainage. To avoid moisture accumulation in the housing, install wiring with a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit connections. The device is fitted with a breather vent to prevent excess moisture accumulation. Ensure the breather vent is kept free of debris.
64/138

4.2.3 Connecting wires

1. Crimp ferrules to the wires. Permissible cable cross section: 0.2 mm² ... 2.5 mm² (24 … 14 AWG).
2. Insert the wire with ferrule into the corresponding connection terminal block.
3. Use a screwdriver to tighten the screw in the opening above the connection terminal block. Torque screw to 0.6 Nm.
PHOENIX CONTACT 3827_en_B
Page 67
4. Install zip ties to manage wire routing.
Installation
COM NO NCLV HV COMLV HV COM COM NO NC
DIGITAL IN 2
FUSE
DIGITAL IN 1
DC
COM NO NC
230V
POWER
RF LINK
AC
DIGITAL OUT 1
U I COM PWR +I -I + -+ -
ANALOG IN
ANALOG OUT
DIGITAL OUT 2
S-PORT
DIP
4-3-2-1
ON-OFF
RAD
ID
PWR
DAT
SET
ERR
RSSI
RF
LINK
D1
1 2
D2
Zip ties
Figure 4-13 Zip ties

4.2.4 Connecting power

DANGER:
Always disconnect power before installing or performing maintenance.
Select the input voltage range via the selector switch
When the switch is set to DC mode, connect a DC voltage source (10.8 … 30.5 V DC)
to the wireless module. The nominal voltage is 24 V DC.
When the switch is set to AC mode, connect an AC voltage source (100 … 240 V AC) to the wireless module. When powered by an AC voltage source, the maximum temperature is 65°C.
WARNING:
The fuse protects the RAD-900-DAIO6 in case of an overcurrent event or if the selector switch is in the wrong position.
In order to prevent damage to the wireless module, Phoenix Contact recommends the installation of a surge arrester. Wiring between the surge arrester and the wireless module should be as short as possible. Please also observe the manufacturer's specifications.
4.2.4.1 Replacing the fuse
The fuse can be replaced using a 5x20 mm slow-blow fuse rated for 800 mA @ 250 V AC. Use types Littelfuse
®
0215.800MXP, Bel Fuse 5HT 800-R or equivalent.
1. Disconnect supply voltage.
2. To remove the fuse, turn the fuse cover 90° counter-clockwise and remove it to access the fuse.
3. Install the replacement fuse.
WARNING:
Never operate the device without the cover installed.
4. Replace the cover.
3827_en_B PHOENIX CONTACT 65/138
Page 68
RAD-900-...

4.2.5 Connecting the antenna

The wireless module has an N-type antenna socket for an external antenna. Although a 0 dB omni-directional antenna is included with the wireless module, it may be replaced with a coaxial cable and high-gain antenna.
Install the antenna outside the control cabinet or building. Observe the installation instructions of the antenna and the “Installation and operation” on
page 6. Observe the maximum permissible emitted transmission power of 36 dBm. The
transmission power can be calculated as:
device transmission power + antenna gain - cable attenuation
Reduce the device transmission power, if necessary.
If the antenna is removed and re-installed or a cable is attached for a remote antenna, torque the antenna or cable connector between 0.7 and 1.1 Nm.
66/138
PHOENIX CONTACT 3827_en_B
Page 69

5 Configuration and startup

5.1 Default settings of the wireless module

All RAD-900-… wireless modules have the same configuration by default upon delivery or by resetting to the default settings at a later stage.
Table 5-1 Default settings of the wireless module
Parameter Setting
Operating mode I/O data (wire in/wire out)
Wireless interface
Net ID 127 RF band 1 Encryption OFF Network structure Star Device type Slave Data rate of the wireless interface 125 kbps Transmission power 1 W (30 dBm)
Configuration and startup
In order to be able to cover the largest possible distances, the preamplifier has been activated and transmission power set to 30 dBm by default. When operating the devices directly next to one another, the receiver might become overloaded. In this case, remove the antennas, increase the distance between the devices and antennas or reduce transmission power using the PSI-CONF software (from page 74 onwards).

5.1.1 Resetting to the default settings

The device can be reset to the default settings either manually or using the PSI-CONF software.
Resetting manually
1. Disconnect the device from the supply voltage.
2. Hold down the SET button located on the front of the device and switch the supply voltage on.
3. Press and hold the SET button until the DAT LED flashes.
Resetting via PSI-CONF software
1. Select “Wireless, RAD-900-IFS” on the “Device Selection” page.
2. Select “Local Device”.
3. Select “Set device to factory default configuration”.
3827_en_B PHOENIX CONTACT 67/138
Page 70
RAD-900-...

5.1.2 Firmware update

Download the latest firmware free of charge at
The firmware can be updated using the PSI-CONF software. The device is reset to the default settings after a firmware update.
1. Select “Wireless, RAD-900-IFS” on the “Device Selection” page.
2. Select “Update firmware”.
phoenixcontact.net/products.

5.2 Operating mode of the wireless module

The Radioline wireless system offers four different options for signal and data transmission:
Operating mode Configuration
I/O data mode Default setting, configuration only possible via
thumbwheel
Serial data mode
Configuration via PSI-CONF softwarePLC/Modbus RTU mode
PLC/Modbus RTU dual mode
Only one operating mode can be selected. It is not possible to simultaneously transmit I/O signals and serial data.
If the wireless system is operated in an environment where other networks are also present (e.g., additional Radioline networks in the 900 MHz band), then a configuration memory can be used (see “Configuration via CONFSTICK” on page 71). For configuring extended settings of the wireless modules, it is also possible to use the PSI-CONF software (from page 74 onwards).
68/138
PHOENIX CONTACT 3827_en_B
Page 71
Configuration and startup
I/O data mode
Figure 5-1 I/O data mode
By default, all wireless modules are in the I/O data mode. For simple I/O-to-I/O applications with extension modules, you can easily set the addresses using the thumbwheel. You can therefore establish a wireless connection to other wireless modules without any programming effort (see “Setting the address of the wireless module via the thumbwheel” on page 71 and “Setting the address of the extension modules via the thumbwheel” on page 80).
Serial data mode (RAD-900-IFS only)
Figure 5-2 Serial data mode
In serial data mode, multiple controllers or serial I/O devices are networked easily and quickly using wireless technology. In this way, serial RS-232 or RS-485 cables can be replaced.
Each wireless module must be configured using the PSI-CONF software (from page 74 onwards).
3827_en_B PHOENIX CONTACT 69/138
Page 72
RAD-900-...
PLC/Modbus RTU mode
Figure 5-3 PLC/Modbus RTU mode
Connect the I/O extension modules to the controller directly via the integrated RS-232 and RS-485 interface by means of wireless communication. In PLC/Modbus RTU mode, the master wireless module (RAD ID = 01) operates as a Modbus slave. The master wireless module has its own Modbus address.
Connect I/O extension modules to each wireless module in the network. The I/O data of the extension module is stored in the internal Modbus memory map of the master wireless module. In addition, the diagnostic data from all wireless devices is stored here.
Each wireless module must be configured using the PSI-CONF software (from page 74 onwards).
70/138
PLC/Modbus RTU dual mode
Figure 5-4 PLC/Modbus RTU dual mode
Dual mode combines the PLC/Modbus RTU mode and the serial data mode. Serial Modbus devices can be connected to the RS-232 or RS-485 ports, and connect I/O extension modules to each wireless module in the network.
PHOENIX CONTACT 3827_en_B
Page 73
Configuration and startup
The I/O data of the extension module and the diagnostic data is stored in the internal Modbus memory map of the wireless module. Each wireless module with I/O extension modules has its own Modbus address. In addition, the diagnostic data from all wireless devices can be read from the master wireless module.
Each wireless module must be configured using the PSI-CONF software (from page 74 onwards).
5.3 Setting the address of the wireless module via the
thumbwheel
Set the desired station address with the yellow thumbwheel on the wireless module. There must be one master (RAD ID = 01) and at least one repeater/slave (RAD ID = 02 ... 99) in a network.
Unique addressing is required in a network. If two wireless modules have the same address in a network, the network will not function properly.
Setting the address via the thumbwheel has priority over setting the address via the PSI-CONF software.
After making any change to the module address, press the SET button for one second to apply the setting.
The following settings can be made using the yellow thumbwheel:
Thumbwheel setting
01 Master address 02 ... 99 Slave address 00 Not permitted
Description
Addressing wireless modules using the PSI-CONF software (address 1 ... 250)
IDs 100 to 250 must be configured using PSI-CONF software

5.4 Configuration via CONFSTICK

WARNING: Explosion hazard when used in potentially explosive areas
Do not insert or remove the CONFSTICK in a potentially explosive atmosphere.
By default upon delivery, all wireless modules have the same network ID and the same RF band. Using a configuration memory (CONFSTICK), you can configure a unique and secure network without the need for software.
The CONFSTICK is used as a network key. Its network address (network ID) is unique and cannot be assigned via the PSI-CONF software. Only wireless modules with the same network ID are allowed to connect with each other.
Each individual network device must be configured. Only one CONFSTICK is needed for all wireless modules in the network. After configuration, remove the CONFSTICK from the wireless module.
3827_en_B PHOENIX CONTACT 71/138
Page 74
RAD-900-...
In addition, the CONFSTICK contains a preset frequency band (RF band). An RF band is a group of frequencies compiled of individual frequencies of the entire 900 MHz band. Different RF bands use different frequencies.
In order to operate several Radioline wireless systems, you should select different RF bands.
Set different RF bands between 1 ... 8 and network IDs between 1 ... 127 using the PSI­CONF software (see page 75).
Figure 5-5 Configuration via CONFSTICK
Item Description
1 RAD-CONF-RF CONFSTICK 2 Status LEDs 3 SET button
1. Carefully insert the CONFSTICK with the 12-pos. IFS connector into the S port of the wireless module.
2. Press the SET button on the wireless module for one second. Parameter read in is started. Read in has been completed when the DAT LED lights up once. The new parameters are activated.
3. Remove the CONFSTICK from the wireless module.
4. Repeat this process for each individual wireless module in the network.
72/138
PHOENIX CONTACT 3827_en_B
Page 75
Configuration and startup

5.5 Copying device settings via memory stick

To transfer the configuration of a wireless module to another wireless module, save the configuration to a memory stick (RAD-MEMORY, Order No. 2902828).
WARNING: Explosion hazard when used in potentially explosive areas
Do not insert or remove the memory stick in a potentially explosive atmosphere.
Pay attention to the firmware version of the wireless modules before using the memory stick. In order to ensure that a wireless module is capable of reading the memory stick, it must have the same or later firmware version as the wireless module whose configuration file is to be copied. Wireless modules with a lower firmware version are not able to read the memory stick.
Common network parameters
Operating mode – Network ID – RF band – Data rate of the wireless interface – Encryption – Network type
Individual device parameters
Station name – RAD ID – Transmission power – List of permitted connections – Serial interface parameters
5.5.1 Saving parameters from the wireless module to the
memory stick
Copying common network parameters and individual device parameters to the memory stick:
1. Press the SET button located on the wireless module and hold down for at least six seconds.
2. The four RSSI bar graph LEDs start a light sequence from bottom to top.
3. Insert the memory stick in the S port of the wireless module. The copying of parameters is started automatically.
4. Wait until the light sequence stops. The write process has been completed.
5. Remove the memory stick from the wireless module.
3827_en_B PHOENIX CONTACT 73/138
Page 76
RAD-900-...

5.5.2 Reading the memory stick

Reading in common network parameters via the memory stick
1. Insert the memory stick in the S port of the wireless module.
2. Press the SET button located on the wireless module and hold down for at least one second. Parameter read in is started. Read in has been completed when the DAT LED lights up once. The new parameters are activated.
3. Remove the memory stick from the wireless module.
Reading in common network parameters and individual device parameters via the memory stick
This function enables all common network parameters and individual device parameters to be read into the wireless module. A full copy of devices can be created, e.g., as a backup copy.
1. Insert the memory stick in the S port of the wireless module.
2. Press the SET button located on the wireless module and hold down for at least six seconds. Parameter read in is started, the DAT LED flashes.
3. The read in process has been completed once the DAT LED stops flashing. The new parameters are activated.
4. Remove the memory stick from the wireless module.
If an error is detected while saving or checking the data, the DAT and ERR LEDs flash simultaneously.

5.6 Configuration via PSI-CONF software

You can make special settings using the PSI-CONF configuration and diagnostics software. The software is available to download at Windows operating system is required to use the software. Use the RAD-CABLE-USB (Order No. 2903447) USB cable for configuration and diagnostics.
WARNING: Explosion hazard when used in potentially explosive areas
The USB cable must not be used in potentially explosive areas.
For additional information on the USB cable, please refer to the RAD-CABLE-USB package slip. The latest documentation can be downloaded at
phoenixcontact.net/products.
Install the software and the USB driver for the RAD-CABLE-USB cable. Follow the software wizard.
phoenixcontact.net/products. A PC with a
74/138
PHOENIX CONTACT 3827_en_B
Page 77
Configuration and startup

5.6.1 Extended configuration, individual settings

After reading an existing network project or creating a new project, the network settings can be modified under “Individual Settings”. The wireless network can be optimized and adapted to your special requirements. When moving the mouse over the individual network parameters, you obtain a short description under “Help”.
If several wireless systems are operated parallel and in close proximity, you are required to set the RF band and the network ID. These parameters can be set via the PSI-CONF software or by using a CONFSTICK (see “Configuration via CONFSTICK” on page 71).
Figure 5-6 PSI-CONF software: Network Settings

5.6.2 Data transmission speed of the wireless interface

The range is an important parameter in industrial wireless applications, especially in outdoor applications. Even in cases where long ranges do not have to be covered, good receiver sensitivity enables transmission in harsh outdoor conditions, e.g., when there is no direct line of sight.
The receiver sensitivity determines the signal amplitude which can just about be received by the wireless module. The lower the data transmission speed of the wireless interface, the higher the receiver sensitivity and thereby the range.
Adjust the data transmission speed of the wireless interface to the respective application using the PSI-CONF software (default setting = 125 kbps).
3827_en_B PHOENIX CONTACT 75/138
Page 78
RAD-900-...
Table 5-2 Data transmission speed of the wireless interface
Data transmission speed
Typical receiver sensitivity
Typical link budget
Potential distance with line of sight and a system reserve of 12 dB
500 kbps -95 dBm -125 dBm 12 km 250 kbps -102 dBm -132 dBm 25 km 125 kbps -105 dBm -135 dBm 35 km (default setting) 16 kbps -112 dBm -142 dBm 80 km
Figure 5-7 PSI-CONF software: Wizard, Step 3
Figure 5-8 PSI-CONF software: Setting the data transmission speed
76/138
PHOENIX CONTACT 3827_en_B
Page 79
Configuration and startup

5.6.3 Device settings

In order to be able to cover the largest possible distances, the preamplifier has been activated and transmission power set to 30 dBm by default. When operating the devices directly next to one another, the receiver might become overloaded. In this case, remove the antennas, increase the distance between the devices and antennas, or reduce transmission power using the PSI-CONF software.
Assign a device name or set the transmission power under “Device Settings”. All device parameters are listed on the “Overview” tab.
Figure 5-9 PSI-CONF software: Individual Settings, Overview
Depending on the operating mode, configure the serial interface under “Individual Settings” on the “Serial Port” tab.
In I/O data mode (default upon delivery), both interfaces are deactivated. To activate the serial interface, select the “Serial data,” “PLC/Modbus RTU mode,” or “PLC/Modbus RTU dual mode” network application under “Network Settings”.
Only use one interface per wireless module. Parallel operation of both interfaces is not possible.
3827_en_B PHOENIX CONTACT 77/138
Page 80
RAD-900-...
Figure 5-10 PSI-CONF software: Individual Settings, Serial Port
Define the wireless modules to which a connection may be established on the “Allowed Parents” tab under “Individual Settings”. This setting is required, for example, when creating repeater chains. Repeater chains are used to circumvent obstacles or to set up redundant wireless paths by means of several repeaters.
The “Allowed Parents” tab is only available if the “Line/Mesh” network type has been selected.
Figure 5-11 PSI-CONF software: Individual Settings, Allowed Parents
78/138
PHOENIX CONTACT 3827_en_B
Page 81
Configuration and startup

5.7 Starting up I/O extension modules

5.7.1 Combinations of extension modules

Several appropriate output modules at different stations can be assigned to one digital or analog input module. The inputs are transmitted in parallel to the outputs. The channels of the input module are mirrored to the channels of the output module.
It is not possible to separately assign the individual input channels of an extension module to different output modules.
DI1L
DI1H
DI1
+24 V
0 V
DI2L
DI2H
DI2
RSSI
+
RSSI
-
ANT
SPORT
RAD-DI4-IFS
RAD-2400-IFS
PWR
PWR
8 8
0
1
DAT
DAT
IO-MAP
RAD-ID
ERR
ERR
DI1
Reset
DI2
DO1
DO2
RXTX
D(A)
D(B)
DI3L
DI3H
DI3
RX
GND
TX
CO
1
NC
1
DI4L
DI4H
DI4
CO
2
COM1
COM1
NO1
+24 V
0 V
COM2
NO2
RSSI
+
RSSI
-
ANT
OFF ON 1 2 3
SPORT
4
DIP-1
RAD-2400-IFS
PWR
PWR
8 8
0
1
DAT
DAT
RAD-ID
ERR
ERR
DI1
Reset
DI2
DO1
DO2
RXTX
D(A)
D(B)
COM3
RX
GND
NO3
TX
COM4
CO
1
NC
1
NO4
CO
2
NC1 NC2
NC3 NC4
RAD-DOR4-IFS
IO-MAP
NC1
NO1
+24 V
0 V
COM2
NC2
NO2
RSSI
+
RSSI
-
ANT
OFF ON 1 2 3
SPORT
4
DIP-1
RAD-2400-IFS
RAD-DOR4-IFS
PWR
PWR
8 8
0
1
DAT
DAT
IO-MAP
RAD-ID
ERR
ERR
DI1
Reset
DI2
DO1
DO2
RXTX
D(A)
D(B)
COM3
RX
NC3
GND
NO3
TX
COM4
CO
1
NC4
NC
1
NO4
CO
2
COM1
NC1
NO1
+24 V
0 V
COM2
NC2
NO2
RSSI
+
RSSI
-
ANT
OFF ON 1 2 3
SPORT
4
DIP-1
RAD-2400-IFS
RAD-DOR4-IFS
PWR
PWR
8 8
0
1
DAT
DAT
IO-MAP
RAD-ID
ERR
ERR
DI1
Reset
DI2
DO1
DO2
RXTX
D(A)
D(B)
COM3
RX
NC3
GND
NO3
TX
COM4
CO
1
NC4
NC
1
NO4
CO
2
Figure 5-12 Assignment of digital inputs and digital outputs
The combined RAD-DAIO6-IFS extension modules can only be assigned in pairs, because each module is provided with inputs and outputs. That is why only two modules in the network may have the same I/O MAP address.
+24 V
0 V
DI1L
DI1H
DI1
RSSI
+
RSSI
-
DI2L
DI2H
DI2
ANT
UL1 +I1 -I1
OFF ON 1 2 3
SPORT
4
DIP-1
RAD-2400-IFS
RAD-DAIO6-IFS
PWR
PWR
0
1
1 2
DAT
DAT
RAD-ID
IO-MAP
ERR
ERR
DI1
Reset
DI2
DO1
RXTX
DO2
D(A)
D(B)
U1 I1
1
RX
GND
TX
COM1
NC1
NO1
1
CO
NC
1
CO
2
COM2
NC2
NO2
+24 V
0 V
DI1L
DI1H
DI1
RSSI
+
RSSI
-
DI2L
DI2H
DI2
ANT
UL1 +I1 -I1
OFF ON 1 2 3
SPORT
4
DIP-1
RAD-2400-IFS
RAD-DAIO6-IFS
PWR
PWR
0
1
1 2
DAT
DAT
RAD-ID
IO-MAP
ERR
ERR
DI1
Reset
DI2
DO1
RXTX
DO2
D(A)
D(B)
U1 I1
1
RX
GND
TX
COM1
NC1
NO1
CO
1
NC
1
CO
2
COM2
NC2
NO2
Figure 5-13 RAD-DAIO6-IFS assignment: analog/digital inputs and outputs
3827_en_B PHOENIX CONTACT 79/138
Page 82
RAD-900-...
Table 5-3 Assignment of input and output modules
Input module Output module
2901537 RAD-AI4-IFS 2901538 RAD-AO4-IFS 2904035 RAD-PT100-4-IFS 2901538 RAD-AO4-IFS 2901535 RAD-DI4-IFS 2901536 RAD-DOR4-IFS 2901539 RAD-DI8-IFS 2902811 RAD-DO8-IFS 2901533 RAD-DAIO6-IFS 2901533 RAD-DAIO6-IFS

5.7.2 Setting the address of the extension modules via the thumbwheel

For an I/O-to-I/O transmission of signals, assign a corresponding output module to the input module. Set the I/O-MAP address (01 ... 99) using the white thumbwheel on the I/O extension module.
Addressing extension modules
Use the thumbwheel to set the address.
Press the SET button on the front of the wireless module to read the current
configuration.
The following settings can be made using the white thumbwheel:
Thumbwheel setting
01 ... 99 I/O-MAP address 00 Delivery state **, 1* ... 9* Setting not permitted *1 ... *9 Interface System slave address, for use with other Interface System
The following conditions must be met: – Assign a maximum of 1 ... 99 addresses to the extension modules in the entire wireless
network.
Description
(IFS) master devices
80/138
PHOENIX CONTACT 3827_en_B
Page 83
Configuration and startup
Wireless module in I/O data mode
The input module must be provided with the same I/O-MAP address as the assigned
output module at the other wireless station (I/O mapping). Output modules with the
same I/O-MAP address may appear several times in the network at different stations. – The I/O-MAP address of an input module may only appear once in the network. – The channels of the input module are directly assigned to the channels of the output
module:
Input module Output module
Channel 1 Channel 1 Channel 2 Channel 2 ... ...
It is not possible to individually assign the channels of the input and output modules.
Figure 5-14 Input module and output module with the same address
Wireless module in PLC/Modbus RTU mode
Output modules may not have the same I/O-MAP address as input modules. Exception:
Output modules with the same I/O-MAP address may appear several times in the
network at different stations. – The I/O-MAP address of an input module may only appear once in the network. – The input and output data is saved in a Modbus memory map in the master wireless
module. You can read or write the process data via the serial interface of the master
wireless module (RAD ID = 01) using the Modbus RTU command. The process data
tables can be found starting at “Modbus memory map” on page 100.

5.7.3 Wireless module in PLC/Modbus RTU dual mode

Each wireless module may be assigned a Modbus address. The master wireless
module Modbus address may be changed from 01 if an existing Modbus device is
already assigned this address. A Modbus address may only appear once in the
network. – Output modules may not have the same I/O-MAP address as input modules on a single
wireless device (station). Exception: Output modules with the same I/O-MAP address
may appear several times at the same station.
3827_en_B PHOENIX CONTACT 81/138
Page 84
RAD-900-...
The input and output data is saved in a Modbus memory map in the wireless module.
You can read or write the process data via the serial interface of the master wireless
module (RAD ID = 01) using the Modbus RTU command. The process data tables can
be found starting at “Modbus memory map” on page 100.

5.8 Starting up the RAD-900-DAIO6

5.8.1 Setting the address of the RAD-900-DAIO6 via the thumb-
wheel
For an I/O-to-I/O transmission of signals, both the RAD ID and I/O-MAP address are set using the yellow thumbwheel on the RAD-900-DAIO6.
Addressing extension modules
Use the thumbwheel to set the address.
Press the SET button on the front of the wireless module to read the current
configuration.
The following settings can be made using the yellow thumbwheel:
Thumbwheel setting
01 ... 99 RAD ID and I/O-MAP address 01 Delivery state **,
1* ... 9*, *1 … *9
The following conditions must be met: – Assign a maximum of 1 ... 99 addresses to the RAD-900-DAIO6 in the entire wireless
network. If the address is set to 01, the RAD-900-DAIO6 may only be used in point-to-
point mode with another RAD-900-DAIO6.
Wireless module in I/O data mode
The RAD-900-DAIO6 may be used to create a point-to-point or point-to-multipoint connection with RAD-900-IFS devices. In this case, set the I/O-MAP address to between 02 and 99 using the white thumbwheel on the corresponding RAD-DAIO6-IFS extension module(s) to match the yellow thumbwheel setting on the RAD-900-DAIO6.
The I/O-MAP address of an input module may only appear once in the network. – The input channels are directly assigned to the corresponding output channels at the
other wireless station.
Description
Settings not permitted
82/138
PHOENIX CONTACT 3827_en_B
Page 85
Configuration and startup
The RAD-900-DAIO6 may be used to create a point-to-point connection with another
RAD-900-DAIO6. In this case, one RAD-900-DAIO6 must have its address set to 01
and the other must be set to 02.
Figure 5-15 Thumbwheel addressing of the RAD-900-DAIO6 in point-to-point mode
Wireless module in PLC/Modbus RTU mode
Multiple RAD-900-DAIO6 devices may not use the same thumbwheel address in a
single network. – The input and output data is saved in a Modbus memory map in the master wireless
module. You can read or write the process data via the serial interface of the master
wireless module (RAD ID = 01) using the Modbus RTU command. The process data
tables can be found starting at “Modbus memory map” on page 100.

5.8.2 RAD-900-DAIO6 in PLC/Modbus RTU dual mode

Each wireless module is assigned a Modbus address. The Modbus address of each
module is that of the RAD-ID (yellow thumbwheel) set on the module. The master
wireless module Modbus address may be changed from 01, if an existing Modbus
device is already assigned this address. A Modbus address may only appear once in
the network. – Each RAD-900-DAIO6 device must use a unique thumbwheel address within a single
network. – The input and output data is saved in a Modbus memory map in the wireless module.
You can read or write the process data via the serial interface of the master wireless
module (RAD ID = 01) using the Modbus RTU command. The process data tables can
be found starting at “Modbus memory map” on page 100.
3827_en_B PHOENIX CONTACT 83/138
Page 86
RAD-900-...

5.9 Startup time of the wireless station

Once a wireless station has been started (power “ON”), the wireless module will take 15 seconds to be ready for operation. Each linked I/O extension module increases the startup time by 3 seconds.
Startup time of a wireless station = 15 seconds + (number of I/O modules x 3 seconds)
Accordingly, a complete wireless station with 32 I/O extension modules requires a startup time of 111 seconds. Only after this period of time has elapsed is the wireless station ready for operation.
84/138
PHOENIX CONTACT 3827_en_B
Page 87

6 Serial data mode (RAD-900-IFS only)

In serial data mode, multiple controllers or serial I/O devices are networked quickly and easily using wireless technology. In this way, serial RS-232 or RS-485 cables can be replaced.
Figure 6-1 Serial data mode
Configure the serial interface of the RAD-900-IFS wireless module using the PSI-CONF software. In order to connect the wireless module to the PC, you need the RAD-CABLE-USB cable (Order No. 2903447).
Serial data mode (RAD-900-IFS only)
WARNING: Explosion hazard when used in potentially explosive areas
The USB cable must not be used in potentially explosive areas.
When operating the network in serial data mode, it may not be possible to diagnose all devices. In this case, stop the serial application in order to allow for complete diagnostics.
Use PSI-CONF software to assign different serial settings to the devices under “Individual Settings”.
3827_en_B PHOENIX CONTACT 85/138
Page 88
RAD-900-...
Start the PSI-CONF software.
Follow the software wizard.
Once you have run through all steps of the wizard, save the project and transmit it to the
wireless modules.
Figure 6-2 PSI-CONF software: Wizard, Step 3
86/138
Figure 6-3 PSI-CONF software: Wizard, Step 4
PHOENIX CONTACT 3827_en_B
Page 89
Serial data mode (RAD-900-IFS only)

6.1 Frame-based data transmission

T
The T
parameter (minimum pause between two frames)
IdleMin
parameter refers to the minimum pause that must elapse between two frames
IdleMin
on the output side (wireless module is transmitting data via serial interface).
Frame 1
Frame 2
Frame 3
IdleIdleIdle
T
idleMin
Figure 6-4 Frame-based data transmission: T
T
FrameEnd
T
FrameEnd
parameter
is the time which is kept by the transmitting wireless module between two frames.
T
idleMin
IdleMin
T
idleMin
parameter
If the data received by the wireless module is followed by a certain period of time where no further data is received, the wireless module assumes that the frame has arrived in its entirety. The frame is then transmitted. This period of time is referred to as T
T
FrameEnd
(T
FrameEnd < TIdleMin
must be shorter than the minimum interval between two frames
). T
FrameEnd
must, however, also be greater than the maximum interval
FrameEnd
.
that is permitted between two characters in a frame. Otherwise the frame might be fragmented.
Frame 1
OK
Frame 2
NOT OK
IdleIdleIdle
T
FrameEnd
Figure 6-5 Frame-based data transmission: T
3827_en_B PHOENIX CONTACT 87/138
FrameEnd
T
FrameEnd
parameter
Page 90
RAD-900-...
Setting telegram pauses, based on the example of Modbus/RTU
A frame is also referred to as a telegram. The length of the transmission pause between the telegrams depends on the set data rate. The beginning and end of a telegram is recognized by means of a time condition. A pause of 3.5 characters means that the telegram is complete and the next character is to be interpreted as the slave address. A telegram must therefore be sent as a continuous data flow. If there is an interruption of more than 1.5 characters within a telegram, the data will be discarded by the receiver.
If the master is not able to transmit the successive characters quickly enough and the communication is aborted, you must increase the minimum pause time (T
FrameEnd
) between the individual characters of a telegram. Frames with a length of 1480 characters can be transmitted by the Radioline wireless system.
In order to adapt data transmission to other protocols, it is possible to adapt the
T
FrameEnd
and T
parameters. Set the interface parameters under “Individual
IdleMin
Settings”.
88/138
Figure 6-6 PSI-CONF software: Individual Settings
PHOENIX CONTACT 3827_en_B
Page 91

7 PLC/Modbus RTU mode

The PLC/Modbus RTU mode is available for firmware version 1.30 or later. If necessary, start an update using the PSI-CONF software (version 2.03 or later).
Activate the PLC/Modbus RTU mode using the PSI-CONF software (from Section 5.6, “Configuration via PSI-CONF software” onwards).
In PLC/Modbus RTU mode, you can read the I/O values of the extension modules con­nected to the wireless slave modules via the Modbus RTU protocol (I/O to serial). The wire­less module provides an RS-232 or RS-485 interface for this purpose. In PLC/Modbus RTU mode, the master wireless module works as a Modbus slave and has its own Modbus slave address.
You can connect I/O extension modules to each wireless device in the network. A wireless network can have a maximum of 99 extension modules. Use the white thumbwheel to set the I/O-MAP addresses.
PLC/Modbus RTU mode
Figure 7-1 PLC/Modbus RTU mode
3827_en_B PHOENIX CONTACT 89/138
Page 92
RAD-900-...

7.1 Configuration via PSI-CONF software

1. Start the PSI-CONF software (see Section 5.6, “Configuration via PSI-CONF soft-
ware”).
2. Create a new network project.
3. Follow the software wizard.
Figure 7-2 PSI-CONF software: Wizard, Step 3
4. Select “PLC/Modbus RTU mode” and assign a Modbus address.
5. Follow the software wizard.
The Modbus address is a unique address in the Modbus network. It is only assigned to the master wireless module (RAD ID = 01). Assign an address between 1 ... 247.
In order to enable the master wireless module to communicate with a controller via the RS-232 or RS-485 interface, you must set the interface parameters. Please note that the controller settings must match the settings of the wireless module.
Table 7-1 Configuration via PSI-CONF software
Parameter Possible values Default setting
Interface type RS-232, RS-485 RS-232 Data rate 300 ... 115,200 bps 19,200 bps Parity None, even, odd None Number of stop bits 1; 2 1 Number of data bits 8 8 Modbus address 1 ... 247 1
The Modbus connection between the controller and the wireless module can be monitored via a watchdog. For additional information on the watchdog, refer to page 91.
90/138
PHOENIX CONTACT 3827_en_B
Page 93
PLC/Modbus RTU mode

7.2 Addressing I/O extension modules

In PLC/Modbus RTU mode, a wireless network can have a maximum of 99 I/O extension modules.
Use the white thumbwheel on the I/O extension module to set the I/O-MAP address. You can find information on addressing extension modules from “Setting the address of the ex­tension modules via the thumbwheel” on page 80 onwards.

7.3 Watchdog

The Modbus telegram watchdog monitors the connection between the master wireless module and the controller. It is triggered each time a Modbus telegram is received correctly. Activate the watchdog using the PSI-CONF software.
Select the “Network Settings” item under “Individual Settings”. Set a watchdog time be-
tween 200 ms ... 65,000 ms.
.
Figure 7-3 PSI-CONF software: Individual Settings, Network Settings
If the watchdog is triggered, an action will be performed on the I/O output modules. You can set this behavior in the event of an error using the DIP switches on the front.
OFF = RESET: Output value is set to 0 – ON = HOLD: Hold last output value
For more detailed information regarding switch setting for the different extension modules, please refer to Section 3, “Description of I/O extension modules”.
If the watchdog is activated and Modbus communication interrupted, the red ERR LED will flash on all wireless modules in the network. Depending on the DIP switch settings, the out­put modules issue the corresponding hold or reset value.
3827_en_B PHOENIX CONTACT 91/138
Page 94
RAD-900-...
92/138
PHOENIX CONTACT 3827_en_B
Page 95

8 PLC/Modbus RTU dual mode

PLC/Modbus RTU dual mode is available for firmware version 1.80 or later. You can update the firmware free of charge using the PSI-CONF software, Version 2.33 or later.
The firmware and software can be found on the Internet at
Activate the PLC/Modbus RTU dual mode using the PSI-CONF software (from Section 5.6, “Configuration via PSI-CONF software” onwards).
In PLC/Modbus RTU dual mode, you can read the I/O values of the extension modules connected to the wireless slave modules via the Modbus RTU protocol (I/O to serial). In addition, serial Modbus devices can be connected over the wireless network. The master wireless module provides an RS-232 or RS-485 interface to a Modbus RTU master.
In PLC/Modbus RTU dual mode, all the wireless modules work as Modbus slaves and have unique Modbus slave addresses. The Modbus ID of each wireless module is set using the yellow thumbwheel.
You can connect I/O extension modules to each wireless device in the network. A wireless station can have a maximum of 32 extension modules. Use the white thumbwheel to set the I/O-MAP addresses.
PLC/Modbus RTU dual mode
phoenixcontact.net/products.
Figure 8-1 PLC/Modbus RTU dual mode
3827_en_B PHOENIX CONTACT 93/138
Page 96
RAD-900-...

8.1 Configuration via PSI-CONF software

1. Start the PSI-CONF software (see Section 5.6, “Configuration via PSI-CONF
software”).
2. Create a new network project.
3. Follow the software wizard.
Figure 8-2 PSI-CONF software: Wizard, Step 3
4. Select “PLC/Modbus RTU dual mode” and assign a Modbus address.
5. Follow the software wizard.
The Modbus address is a unique address in the Modbus network. Assign an address between 1 ... 247.
In order to enable the master wireless module to communicate with a controller via the RS-232 or RS-485 interface, you must set the interface parameters. Please note that the controller settings must match the settings of the wireless module.
Table 8-1 Configuration via PSI-CONF software
Parameter Possible values Default setting
Interface type RS-232, RS-485 RS-232 Data rate 300 ... 115,200 bps 19,200 bps Parity None, even, odd None Number of stop bits 1; 2 1 Number of data bits 8 8 Modbus address 1 ... 247 1
The Modbus connection between the controller and the wireless module can be monitored via a watchdog. For additional information on the watchdog, refer to page 95.
94/138
PHOENIX CONTACT 3827_en_B
Page 97
PLC/Modbus RTU dual mode

8.2 Addressing I/O extension modules

In PLC/Modbus RTU dual mode, a wireless station can have a maximum of 32I/O extension modules.
Use the white thumbwheel on the I/O extension module to set the I/O-MAP address. You can find information on addressing extension modules from “Setting the address of the extension modules via the thumbwheel” on page 80 onwards.

8.3 Watchdog

The Modbus telegram watchdog monitors the connection between the master wireless module and the controller. It is triggered each time a Modbus telegram is received correctly. You can activate the watchdog using the PSI-CONF software.
Select the “Network Settings” item under “Individual Settings”. Set a watchdog time
between 200 ms ... 65,000 ms.
.
Figure 8-3 PSI-CONF software: Individual Settings, Network Settings
If the watchdog is triggered, an action will be performed on the I/O output modules. You can set this behavior in the event of an error using the DIP switches on the front.
OFF = RESET: Output value is set to 0 – ON = HOLD: Hold last output value
For more detailed information regarding switch setting for the different extension modules, please refer to Section 3, “Description of I/O extension modules”.
If the watchdog is activated and Modbus communication interrupted, the red ERR LED will flash on all wireless modules in the network. Depending on the DIP switch settings, the output modules issue the corresponding hold or reset value.
3827_en_B PHOENIX CONTACT 95/138
Page 98
RAD-900-...
96/138
PHOENIX CONTACT 3827_en_B
Page 99

Addressing I/O extension modules and RAD-900-DAIO6 with Modbus RTU

9 Addressing I/O extension modules and RAD-900-DAIO6
with Modbus RTU

9.1 Modbus function codes

In the Modbus protocol, the function codes define which data is to be read or written. With a single request, the registers 1 ... 123 can be read or written.
Table 9-1 Supported Modbus function codes
Code number Function code Description
fc 03 Read Holding Register Read process output data
(address area 40010 ... 40999)
fc 04 Read Input Register Read process input data
(address area 30010 ... 30999)
fc 16 Write Multiple Registers Write multiple output registers word by word
Other function codes exist in the Modbus protocol, but they are not supported.

9.2 Modbus protocol

The data is transmitted using the Modbus/RTU (Remote Terminal Unit) protocol. Commu­nication takes place according to the master/slave method. The Modbus master initiates communication with a request to the slave. If the slave detects that its address has been ac­cessed by the master, the slave always sends a response.
Only the master is able to initiate communication. The slaves are not able to initiate commu­nication and do not communicate with each other.
The connected extension modules write the analog or digital input and output values to an internal register. The Modbus master (e.g., a PLC) can read the individual registers using the Modbus address of the slaves. The data to be transmitted is always included in a de­fined frame. The frame is referred to as telegram.
The Modbus protocol defines the format of the telegrams. If an error occurs when the tele­gram is received on the slave side, or if the slave is unable to carry out the master request, an error telegram is sent back to the master.
3827_en_B PHOENIX CONTACT 97/138
Page 100
RAD-900-...
Request from master
The function code in the request informs the addressed slave which action is to be carried out. The address and data bytes contain all additional information that the slave requires in order to carry out the action.
Example: The master uses function code 03 to request the slave to read the process output data and send its content to the master. The data and address bytes need to include the fol­lowing information: from which register reading should start and how many registers should be read. Using the CRC check value, the slave is able to detect whether the complete tele­gram has been received.
Response from slave
If the response from a slave is valid, the function code will match the request from the mas­ter. The address and data field contains the data recorded by the slave (e.g., register val­ues).
The function code is modified in the event of an error. The address and data field then con­tains a code that describes the error. By using the CRC check value, the master is able to determine whether the telegram content is valid or not.
The Modbus/RTU telegrams are separated by telegram pauses known as end-of-frame times. The end-of-frame time must be at least 3.5 x as long as the time required for one transmitted character. The end-of-frame time cannot be changed.
Table 9-2 Modbus protocol: structure of telegrams (frames)
Frame Description Size
Slave address Slave address, valid area 1 ... 247 8 bits Function code Definition whether the parameter is to be read or writ-
ten Address Register address 16 bits Data E.g., from the master: Which parameters are
requested?
E.g., from the slave: Content of the requested
parameters
CRC (Cyclic Redundancy Check)
Test value for the cyclic redundancy check in order
to detect errors in data transmission
8 bits
N x 16 bits
16 bits

9.3 Addressing registers

Function code 04
You must enter 0000 (hex0000) as the start address in order to read register 30001. The address area 3xxxx is already defined by the function code field.
Function codes 03 and 16
In order to read/write registers 40032 ... 40039, you must enter 0031 (hex001F) as the start address. The address area 4xxxx is already defined by the function code field.
98/138
PHOENIX CONTACT 3827_en_B
Loading...