Read this user manual carefully and keep it to hand for future reference.
1.1Labeling of warning notes
For your safety
This symbol indicates hazards that could lead to personal injury.
There are three signal words indicating the severity of a potential injury.
DANGER
Indicates a hazard with a high risk level. If this hazardous situation is not
avoided, it will result in death or serious injury.
WARNING
Indicates a hazard with a medium risk level. If this hazardous situation is not
avoided, it could result in death or serious injury.
CAUTION
Indicates a hazard with a low risk level. If this hazardous situation is not avoided,
it could result in minor or moderate injury.
This symbol together with the NOTE signal word alerts the reader to a situation
which may cause damage or malfunction to the device, hardware/software, or
surrounding property.
Here you will find additional information or detailed sources of information.
1.2Qualification of users
The use of products described in this user manual is oriented exclusively to:
–Qualified electricians or persons instructed by them. The users must be familiar with the
relevant safety concepts of automation technology as well as applicable standards and
other regulations.
–Qualified application programmers and software engineers. The users must be familiar
with the relevant safety concepts of automation technology as well as applicable
standards and other regulations.
3827_en_BPHOENIX CONTACT5/138
Page 8
RAD-900-...
1.3Safety notes
Please note that, in combination with antennas, the maximum permissible transmission
power may be exceeded. Please set the transmission power via the software.
The use of antennas with a gain greater than 6 dBi may require that the transmit power be
reduced from the default setting of 30 dBm. Regulations limit the equivalent isotropicallyradiated power (EIRP) to 36 dBm. The EIRP may be calculated as the transmit power (Pt)
minus any cable loss (Lc) plus the antenna gain (Ga).
EIRP = Pt - Lc + Ga
For example, in the case of a 12 dBi antenna used with a cable run with a 4 dB loss, the
transmit power must be reduced to 28 dBm or less such that the EIRP does not exceed 36
dBm.
The PSI-CONF configuration and diagnostic software can be used to configure the
transmit power.
Operation of the wireless system is only permitted if accessories available from
Phoenix Contact are used. The use of other accessory components may invalidate the
device approval status
1.4Installation and operation
Follow the installation instructions.
NOTE:
Installation, operation, and maintenance may only be carried out by qualified specialist
personnel.
Error-free operation of this device can only be ensured if transport, storage, and assembly
are carried out correctly and operation and maintenance are carried out with care.
When installing and operating the device, the applicable safety directives (including
national safety directives), accident prevention regulations, as well as general technical
regulations, must be observed.
WARNING: Risk of electrical shock
During operation, certain parts of this device may carry hazardous voltages. Disregarding
this warning may result in damage to equipment and/or serious personal injury.
NOTE:
Access to circuits within the device is not permitted.
Provide a switch/circuit breaker close to the device that is labeled as the disconnect device
for this device.
Provide overcurrent protection (I
During maintenance work, disconnect the device from all effective power sources.
< 6A).
6/138
PHOENIX CONTACT3827_en_B
Page 9
For your safety
NOTE:
The IP20 degree of protection (IEC 60529/EN 60529) of the RAD-900-IFS is intended for
a clean and dry environment. Do not subject the device to mechanical and/or thermal
loads that exceed the specified limits.
The RAD-900-DAIO6 provides an IP65 degree of protection.
The radio should not be operated without an antenna or terminating load on the antenna
connector.
NOTE:
Prolonged operation without an antenna or terminator may result in damage to the radio.
1.5Safety regulations for installation in potentially explosive areas
Installation in areas with a danger of dust explosions
WARNING:
The device has not been designed for use in potentially dust-explosive atmospheres.
Installation in Class I, Div. 2 or Zone 2
WARNING:
The device is designed for installation in Class I, Division 2/Zone 2 (UL/cUL) potentially
explosive areas. Observe the specified conditions for use in potentially explosive areas.
Install the RAD-900-IFS into a housing (control or distributor box) with at least IP54
protection (EN 60529) and is certified for use in Class I, Div. 2 or Zone 2.
The RAD-900-DAIO6 meets the IP65 degree of protection does not require an additional
housing.
When installing and connecting the supply and signal circuits observe the requirements of
EN 60079-14. Only devices suitable for operation in Ex zone 2 and the conditions at the
application site may be connected to the circuits in zone 2.
In potentially explosive areas, only connect and disconnect cables when the power is
disconnected.
Installation/removal of the devices on/from the TBUS DIN rail connector may only be
performed when no voltage is applied.
3827_en_BPHOENIX CONTACT7/138
Page 10
RAD-900-...
1.6Conformance
FCC
NOTE:
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference, in which case, the user will be
required to correct the interference at his own expense.
Changes or modifications not expressly approved by the party responsible for compliance
could void the user's authority to operate the equipment.
This equipment complies with the FCC RF radiation exposure limits set forth for an
uncontrolled environment. This equipment should be installed and operated with a
minimum distance of 20 cm between the radiator and your body.
–FCC certificate: SGV-SHR-900
Industry Canada (IC)
Operation is subject to the following two conditions: (1) this device may not cause
interference, and (2) this device must accept any interference, including interference that
may cause undesired operation of the device.
To reduce potential radio interference to other users, the antenna type and its gain should
be so chosen that the equivalent isotropically radiated power (EIRP) is not more than that
permitted for successful communication.
This device has been designed to operate with the antennas listed in this document and
having a maximum gain of 12 dB. Antennas not included in this list or having a gain greater
than 12 dB are strictly prohibited for use with this device. The required antenna impedance
is 50 .
Under Industry Canada regulations, this radio transmitter may only operate using an
antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry
Canada. To reduce potential radio interference to other users, the antenna type and its gain
should be so chosen that the equivalent isotropically radiated power (EIRP) is not more than
that necessary for successful communication.
–IC certificate: IC4720C-SHR900
8/138
PHOENIX CONTACT3827_en_B
Page 11
2Short description
Radioline is a wireless system for the transmission of analog and digital I/O signals and
serial data. A Radioline network may contain up to 250 stations, and features a self-healing
network topology. The Radioline product family consists of a DIN rail-mounted 900MHz
transceiver, a variety of I/O extension modules for connection to the transceiver, an outdoor
NEMA 4X version with built in I/O, and an RS-485 multiplexer module for expansion of a
wireless I/O system.
2.1RAD-900-IFS wireless module
In addition to an RS-232 and RS-485 two-wire interface, the RAD-900-IFS wireless module
supports the option of directly connecting up to 32 I/O extension modules in the station
structure via the DIN rail connector.
Addressing of the wireless module and I/O mapping of the extension modules is carried out
quickly and easily by means of the thumbwheel on the front. You can use the yellow
thumbwheel on the wireless module in order to set the RAD ID, and the white thumbwheel
on the extensions modules to set the I/O-MAP address. Programming knowledge is not
required. You can easily start up the wireless network without the need for software.
The PSI-CONF configuration and diagnostic software for special functions and diagnostics
options in the wireless module is available free of charge.
Short description
Features
–Flexible network applications: I/O data, serial data, PLC/Modbus RTU mode
–Adjustable data rates for the wireless interface
–Easy point-to-point or network structures (star, mesh)
–Yellow thumbwheel for the unique addressing of wireless modules in the wireless
network
–Integrated RS-232 and RS-485 interface
–Can be extended with up to 32 I/O modules per station via DIN rail connector
(hotswappable)
–128-bit AES data encryption and authentication
–Unique network addressing via plug-in configuration memory (RAD-CONF) for
secure, parallel operation of multiple networks with different RF bands
–Data rates and ranges can be configured using the PSI-CONF software
–UL/cUL listed for installation in Class I, Div. 2/Zone 2 environments
3827_en_BPHOENIX CONTACT9/138
Page 12
RAD-900-...
2.1.1Structure
Figure 2-1RAD-900-IFS structure
Table 2-1RAD-900-IFS structure
Item Designation
1RSMA antenna connection (socket)
2Test output RSSI (0...3 V DC) for evaluation of the wireless signal strength
3Device supply (+24VDC, 0V)
412-pos. programming interface (S-PORT)
5RAD ID address setting via thumbwheel
6SET button
7Connection option for TBUS DIN rail connector
8DIN rail
9DIN rail release latch
10Connection terminal block RS-485 interface
11Connection terminal block RS-232 interface
12Relay output with PDT contact (floating)
13D-SUB 9 connector (RS-232 interface)
14RS-232/485 serial interface status LED (RX/TX)
15LED bar graph for displaying the wireless signal strength
16ERR status LED, red (communication error)
17DAT status LED, green (BUS communication)
18PWR status LED, green (supply voltage)
10/138
PHOENIX CONTACT3827_en_B
Page 13
Circuit diagram
Short description
RAD-ID
S-Port
RF
RSSI+
2.1
2.2
1.1
1.2
RSSI-
+24 V
0 V
U
µC
DC
DC
IFS
IFS
RS485
RS232
COM
NO
NC
D(A)
D(B)
RX
TX
GND
4.1
4.2
5.1
5.2
5.3
1
6.1
1
6.2
1
6.3
Figure 2-2RAD-900-IFS circuit diagram
2.2RAD-900-DAIO6
The RAD-900-DAIO6 is a NEMA 4X-rated wireless device with one analog input, one
analog output, two digital inputs, and two digital outputs directly integrated. It does not have
a serial interface.
The RAD-900-DAIO6 may be AC- or DC-powered, and addressing of the wireless module
and I/O mapping of the extension modules is carried out quickly and easily by means of the
thumbwheel on the front. You can use the yellow thumbwheel on the wireless module in
order to set both the RAD ID and I/O-MAP address. Programming knowledge is not
required. You can easily start up the wireless network without the need for software. It is
interoperable with the RAD-900-IFS.
The PSI-CONF configuration and diagnostic software for special functions and diagnostics
options in the wireless module is available free of charge.
3827_en_BPHOENIX CONTACT11/138
Page 14
RAD-900-...
2.2.1Structure
1
18
17
19
COM NO NCLV HV COMLV HV COMCOM NO NC
DIGITAL IN 2
FUSE
DIGITAL IN 1
DC
COM NO NC
U I COM PWR +I -I + -+ -
230V
POWER
RF LINK
AC
ANALOG OUT
202122
DIGITAL OUT 1
DIGITAL OUT 2
ANALOG IN
131415
21112
S-PORT
DIP
ON-OFF
RAD
ID
PWR
DAT
ERR
RSSI
RF
LINK
3
4-3-2-1
4
5
6
8
SET
7
9
D1
1 2
D2
10
16
Figure 2-3RAD-900-DAIO6 structure
Table 2-2RAD-900-DAIO6 structure
Item Designation
1N-type antenna
212-pos. programming interface (S-PORT)
3DIP switches for configuring I/O
4RAD ID address setting via thumbwheel
5PWR status LED, green (supply voltage)
6DAT status LED, green (I/O communication)
7ERR status LED, red (communication error)
8SET button
9LED bar graph for displaying the wireless signal strength
10Status LEDs of the digital VO
11Relay output with floating PDT contact
12Digital input as wide-range input
13Analog input for 2-, 3-, and 4-wire measuring transducers
14Analog output (current or voltage)
15RF link
16Test output RSSI (0...3 V DC) for evaluation of the wireless signal strength
17Device supply (+24VDC/120 V AC, 0V/neutral)
18Fuse
19Power selection switch
20Ground lug
21Internal ground screw
22Breather
12/138
PHOENIX CONTACT3827_en_B
Page 15
Short description
Table 2-3DIP switches of the RAD-DAIO6-IFS
DIP switch
SettingOutput signal1234
Analog IN0 ... 20 mAOFF
Analog IN4 ... 20 mAON
Analog OUTRESETOFF
Analog OUTHOLDON
Digital OUT1RESETOFF
Digital OUT1HOLDON
Digital OUT2RESETOFF
Digital OUT2HOLDON
Circuit diagram
RF
RF LINK
RAD-ID
S-Port
COM
NO
NC
COM
NO
NC
1
1
1
RSSI +
RSSI -
+24VDC/120VAC
0V/N
U
PWR
+I
-I
1
µC
1
V
1
I
LOOP
U
I
Figure 2-4RAD-900-DAIO6 circuit diagram
COM
2
NO
2
NC
2
DI
2L
DI
2H
DI
2
DI
1L
DI
1H
DI
U
1
I
1
1
1
3827_en_BPHOENIX CONTACT13/138
Page 16
RAD-900-...
14/138
PHOENIX CONTACT3827_en_B
Page 17
Description of I/O extension modules
3Description of I/O extension modules
Various I/O extension modules are available for setting up the wireless system quickly and
easily. This allows the number and type of I/O signals to be configured for specific
applications.
For a detailed description of the available I/O extension modules, refer to the pages in Table
3-1.
Table 3-1I/O extension modules
Module typeDescriptorOrder No.See
AnalogFour analog inputsRAD-AI4-IFS290153716
Four Pt 100 inputsRAD-PT100-4-IFS290403520
Four analog outputsRAD-AO4-IFS290153828
DigitalFour digital inputsRAD-DI4-IFS290153532
Eight digital inputs or
two pulse inputs
Four digital relay
outputs
Eight digital transistor outputs
Analog/digitalOne analog
input/output, two digital
wide-range inputs/outputs
RAD-DI8-IFS290153935
RAD-DOR4-IFS290153641
RAD-DO8-IFS290281145
RAD-DAIO6-IFS290153350
page
3827_en_BPHOENIX CONTACT15/138
Page 18
RAD-900-...
3.1RAD-AI4-IFS - analog extension module with four
inputs
The analog RAD-AI4-IFS I/O extension module can process up to four input signals
between 0/4 mA ... 20 mA. All inputs are electrically isolated from one another, from the
supply voltage, and from the electronics.
A supply voltage of 12 V DC, minimum, is available at the PWR
for passive sensors (see Figure 3-1, item 1).
3.1.1Structure
2
1
P
w
r
P
w
12
11
10
r
P
W
R
DAT
ER
R
P
w
r
P
w
r
P
w
r
1
+
I
1
I
1
P
w
r
2
+
I
2
I
2
O
N
8
I
1
I
2
I
3
I
4
RAD-AI4-IFS
IO-MAP
3
4
1
+
I
1
2
+
I
2
O
F
F
1
2
3
4
DI
P-1
8
3
+
I
3
4
+
I
4
5
6
7
9
8
connection terminal block
1
Figure 3-1RAD-AI4-IFS structure
Item Designation
1Analog input 2 for 2-, 3-, 4-wire measuring transducers
2Analog input 1 for 2-, 3-, 4-wire measuring transducers
3DIP switches for configuring the analog inputs (current/voltage input)
4White thumbwheel for setting the I/O-MAP address
5Connection option for DIN rail connector
6DIN rail
7Metal foot catch for DIN rail fixing
8Analog input 3 for 2-, 3-, 4-wire measuring transducers
9Analog input 4 for 2-, 3-, 4-wire measuring transducers
10ERR status LED, red (communication error)
11DAT status LED, green (bus communication)
12PWR status LED, green (supply voltage)
16/138
PHOENIX CONTACT3827_en_B
Page 19
3.1.2Basic circuit diagram
Description of I/O extension modules
PWR
2
3.1
+I
2
3.2
PWR IN
2.1
-I
2 Wire
Out
PWR IN
Out
3 Wire
GND
Out
U
4 Wire
S
GND
2
3.3
2.2
PWR
1
2.1
2.1
+I
1
2.2
2.2
-I
1
2.3
2.3
2.2
2.3
IO-MAP
V
LOOP
I
V
LOOP
I
µC
IFS
DCDCIFS
PWR
3
LOOP
LOOP
4.1
+I
3
4.2
I
-I
3
4.3
PWR
4
5.1
+I
4
5.2
I
-I
4
5.3
V
V
Figure 3-2Basic circuit diagram for the RAD-AI4-IFS
3.1.3Setting the DIP switches
Using the DIP switches on the front, you can configure the inputs signals (0 mA ... 20 mA or
4 mA ... 20 mA). Any changes in the setting of the DIP switches will be directly applied.
In PLC/Modbus RTU mode, the setting of the input signals is evaluated for error diagnostics.
With the setting 4 mA ... 20 mA, it is, for example, possible to detect an open circuit.
-I1+I1PWR1
1WR1
-I2+I2PWR2
22
OFFON1234
DIP-1
PWR
DAT
ERR
-I3+I3PWR3
3WR3
-I4+I4PWR4
44
Figure 3-3DIP switches of the RAD-AI4-IFS
3827_en_BPHOENIX CONTACT17/138
Page 20
RAD-900-...
Table 3-2DIP switches of the RAD-AI4-IFS
DIP switch
SettingInput signal1234
Analog IN10 mA ... 20 mAOFF
Analog IN14 mA ... 20 mAON
Analog IN20 mA ... 20 mAOFF
Analog IN24 mA ... 20 mAON
Analog IN30 mA ... 20 mAOFF
Analog IN34 mA ... 20 mAON
Analog IN40 mA ... 20 mAOFF
Analog IN44 mA ... 20 mAON
3.1.4Diagnostic LEDs
The RAD-AI4-IFS I/O extension module uses a total of three LEDs to indicate the operating
states.
-I1+I1PWR1
1WR1
-I2+I2PWR2
22
OFFON1234
DIP-1
PWR
DAT
ERR
-I3+I3PWR3
3WR3
-I4+I4PWR4
44
Figure 3-4Diagnostic LEDs of the RAD-AI4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFFNo supply voltage
ONSupply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFFNo communication
FlashingConfiguration and addressing mode
ONCyclic data communication
18/138
PHOENIX CONTACT3827_en_B
Page 21
Description of I/O extension modules
ERR LED
The red ERR LED indicates the error status.
OFFNo error
Flashing
Slow (1.4 Hz)I/O-MAP address changed
Fast (2.8 Hz)No bus communication
ONCritical internal error
3.1.5Setting the I/O-MAP address
Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline
wireless system is addressed using the I/O-MAP address. You can assign a maximum of
01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-3Setting the I/O-MAP address for the RAD-AI4-IFS
Thumbwheel
Description
setting
01 ... 99I/O-MAP address
00Delivery state
**, 1* ... 9*Setting not permitted
*1 ... *9Interface System slave address, for use with other Interface System
(IFS) master devices
3.1.6Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of six data words. For additional
information, please refer to Section 3.1, “RAD-AI4-IFS - analog extension module with four
inputs”.
I/O moduleModule type IDNumber of
registers
RAD-AI4-IFS20
hex
06
hex
Address areaFunction code
30xx0 ... 30xx5fc 04
3827_en_BPHOENIX CONTACT19/138
Page 22
RAD-900-...
3.2RAD-PT100-4-IFS - extension module with four
temperature inputs
Use the I/O extension modules in connection with the RAD-900-... wireless module,
firmware version 1.40 or later. You can update the firmware free of charge using the
PSI-CONF software, Version 2.04 or later.
The firmware and software can be found on the Internet at
The analog RAD-PT100-4-IFS I/O extension module has four Pt 100 inputs for
temperatures between -50°C ... +250°C. The Pt 100 inputs T1 ... T4 can be mapped to the
analog outputs I1/U1 ... I4/U4 of the RAD-AO4-IFS extension module. All the inputs are
electrically isolated from one another, from the supply voltage, and from the remaining
electronics.
Pt 100 resistance thermometers can be connected to the RAD-PT100-4-IFS I/O extension
module. The thermometers change their resistance depending on the temperature. The
Pt 100 input signals are acquired by the RAD-PT100-4-IFS and can be mapped to
proportional, analog voltage or current signals of the RAD-AO4-IFS output module.
Example: At the Pt 100 input, a current of 0 mA or a voltage of 0 V is released at the output
module at a temperature of -50°C. At the Pt 100 input, a current of 20 mA or a voltage of 10 V
is released at the output at a temperature of 250°C.
phoenixcontact.net/products.
Pt 100 inputAnalog output
-50°C0 mA or 0 V
+250°C20 mA or 10 V
3.2.1Connecting sensors
You can connect 2-wire or 3-wire sensors to the extension module. Observe the measuring
errors depending on the different measuring methods.
2-wire connection technology
2-wire connection technology is the most cost-effective connection method. The
temperature-related voltage is not directly measured at the sensor and therefore falsified by
the two cable resistances R
measurement to become useless. Please observe the diagrams in Section “Measuring
errors using 2-wire connection technology” on page 22.
With 2-wire technology, you need an insertion bridge between terminals x.2 and x.3.
. The measuring errors that occur may lead to the entire
L
20/138
PHOENIX CONTACT3827_en_B
Page 23
Description of I/O extension modules
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
A
D
1mA
A
D
IFS
I+
+I3
4.1
-U3
4.2
-I3
4.3
+I4
5.1
-U4
5.2
-I4
5.3
RL
I–
RL
ϑ
RTD
Figure 3-52-wire connection technology
3-wire connection technology
With 3-wire connection technology, the temperature-related voltage is measured several
times. Corresponding calculations additionally reduce the effect of the cable resistance on
the measurement result. The results are almost as good as those achieved using the 4-wire
technology.
The cable resistances R
at the terminals +I and -I must have the same value. This allows
L
you to subtract the established cable resistance from the measurement result and to get the
Pt 100 platinum resistance value.
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
1mA
A
D
1mA
A
D
I+
+I3
4.1
-U3
4.2
-I3
4.3
+I4
5.1
-U4
5.2
-I4
5.3
RL
U–
I–
RL
ϑ
RTD
DC
IFS
DC
IFS
Figure 3-63-wire connection technology
3827_en_BPHOENIX CONTACT21/138
Page 24
RAD-900-...
4-wire connection technology
The RAD-PT100-4-IFS does not support the 4-wire connection technology.
•If you want to use a 4-wire sensor, only connect three of the four wires.
•The fourth wire should be left unwired. Otherwise there will be a different resistance in
the +I and -I cables owing to the parallel connection of two cable resistances.
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
+I3
4.1
-U3
4.2
A
-I3
D
D
IFS
4.3
(U+)
I+
1mA
+I4
5.1
-U4
5.2
A
-I4
5.3
RL
U–
I–
RL
ϑ
RTD
Figure 3-74-wire connection technology
3.2.2Measuring errors using 2-wire connection technology
8
T [K]
6
4
2
0
02,557,5 10 12,5 15 17,5 20
Figure 3-8Systematic temperature measuring error ΔT depending on the cable
length l
I [m]
22/138
Curves depending on cable cross section A
1Temperature measuring error for A = 0.25 mm
2Temperature measuring error for A = 0.5 mm
3Temperature measuring error for A = 1.0 mm
4Temperature measuring error for A = 1.5 mm
2
2
2
2
(Measuring error valid for: copper cable χ = 57 m/Ωmm2, TA = 25°C and Pt 100 sensor)
PHOENIX CONTACT3827_en_B
Page 25
Description of I/O extension modules
10
8
T [K]
6
4
2
0
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
A [mm ]
2
Figure 3-9Systematic temperature measuring error ΔT depending on the cable cross
section A
2,5
2
T [K]
1,5
1
0,5
0
-50-30-101030507090
T [°C]
Figure 3-10Systematic temperature measuring error ΔT depending on the cable
temperature T
A
(Measuring error valid for: copper cable χ = 57 m/Ωmm2, TA = 25°C and Pt 100 sensor)
Make sure that the cable resistance and therefore the measuring error is as low as possible.
•Use sensor cables that are as short as possible.
•Avoid conductor cross sections smaller than 0.5 mm
2
.
The temperature has only a small influence on the cable resistance.
You can calculate the cable resistance as follows:
= R
R
L
R
L
R
L
R
L20
x [1 + 0.00391x (TA - 20°C)]
L20
l
=
x [1 + 0.00391x (TA - 20°C)]
χ x AK
K
Cable resistance in Ω
Cable resistance at 20°C in Ω
lLine length in m
2
χSpecific resistance of copper in m/
ACable cross section in mm
2
Ωmm
0.0039 1/KTemperature coefficient for copper (degree of purity of 99.99%)
T
A
Ambient temperature (cable temperature) in °C
Due to there being two cable resistances in the measuring system, the value must be
doubled. Using the average temperature coefficient α = 0.385 Ω/K for Pt 100, the absolute
measuring error in Kelvin can be determined for platinum sensors according to DIN
standards.
3827_en_BPHOENIX CONTACT23/138
Page 26
RAD-900-...
3.2.3Shielding of the sensor cables
Always connect the analog sensors using shielded, twisted pair cables (e.g., LiYCY, TP
2 x 2 x 0.5 mm
2
).
•Immediately following entry in the control cabinet, connect the cable shields to the
corresponding shield connection clamps.
Please note that the electrical isolation between the channels may no longer occur when
connecting the shields. The isolating distances between the individual channels need to
be re-evaluated after connecting the shields. The distances between the individual wires
and the common shields are crucial in this respect.
ϑ
RTD
ϑ
RTD
I+
RL
U–
I–
RL
I+
RL
U–
I–
RL
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
A
D
1mA
A
D
IFS
I+
+I3
4.1
-U3
4.2
-I3
4.3
+I4
5.1
-U4
5.2
-I4
5.3
RL
U–
I–
RL
I+
RL
U–
I–
RL
ϑ
RTD
ϑ
RTD
Figure 3-11Shielding with 3-wire connection technology
2-wire connection technology with twisted pair cables and shielding
24/138
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
+I3
I+
4.1
-U3
4.2
A
-I3
D
D
IFS
4.3
1mA
+I4
5.1
-U4
5.2
A
-I4
5.3
RL
I–
RL
ϑ
RTD
Figure 3-122-wire connection technology with twisted pair cables and shielding
PHOENIX CONTACT3827_en_B
Page 27
Description of I/O extension modules
3-wire connection technology with twisted pair cables and shielding
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
+I3
I+
4.1
-U3
4.2
A
-I3
D
D
4.3
1mA
+I4
5.1
-U4
5.2
A
-I4
5.3
RL
U–
I–
RL
ϑ
RTD
IFS
Figure 3-133-wire connection technology with twisted pair cables and shielding
3.2.4Structure
2
1
+
I
1
+
I
11
10
2
PW
R
D
AT
ER
9
R
U
U
8
1
-I
1
2
I
2
8
+
I
2
RAD-PT100-4-IFS
IO-MAP
+
I
1
U
1
I
1
-U
2
I
2
4
5
6
3
I
3
I
U
4
3
-
-
U
I
3
4
I
4
8
7
Figure 3-14RAD-PT100-4-IFS structure
Item Designation
1Pt 100 input 2 for 2- and 3-wire sensors
2Pt 100 input 1 for 2- and 3-wire sensors
3White thumbwheel for setting the I/O-MAP address
4Connection option for DIN rail connector
5DIN rail
6Metal foot catch for DIN rail fixing
7Pt 100 input 3 for 2- and 3-wire sensors
8Pt 100 input 4 for 2- and 3-wire sensors
9ERR status LED, red (communication error)
10DAT status LED, green (bus communication)
11PWR status LED, green (supply voltage)
3827_en_BPHOENIX CONTACT25/138
Page 28
RAD-900-...
3.2.5Basic circuit diagram
+I
+I
1
1
2.1
2.2
2.3
-I
1
2-wire
+I
1
2.1
-U
1
2.2
2.3
-I
1
3-wire
1mA
+I2
3.1
-U2
3.2
-I2
3.3
1mA
+I1
2.1
-U1
2.2
-I1
2.3
IO-MAP
0
A
1
D
µC
A
D
DC
IFS
DC
1mA
+I3
4.1
-U3
4.2
A
-I3
D
D
IFS
4.3
1mA
+I4
5.1
-U4
5.2
A
-I4
5.3
Figure 3-15Basic circuit diagram for the RAD-PT100-4-IFS
With 2-wire technology, you need an insertion bridge between terminals x.2 and x.3. In
this case, the measuring accuracy is reduced (see “Measuring errors using 2-wire
connection technology” on page 22).
3.2.6Diagnostic LEDs
The RAD-PT100-4-IFS I/O extension module uses a total of three LEDs to indicate the
operating states.
Figure 3-16Diagnostic LEDs of the RAD-PT100-4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFFNo supply voltage
ONSupply voltage OK
26/138
PHOENIX CONTACT3827_en_B
Page 29
Description of I/O extension modules
DAT LED
The green DAT LED indicates the bus communication status.
OFFNo communication
FlashingConfiguration and addressing mode
ONCyclic data communication
ERR LED
The red ERR LED indicates the error status.
OFFNo error
Flashing
Slow (1.4 Hz)I/O-MAP address changed
Fast (2.8 Hz)No bus communication
ONCritical internal error
3.2.7Setting the I/O-MAP address
Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline
wireless system is addressed using the I/O-MAP address. You can assign a maximum of
01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-4Setting the I/O-MAP address for the RAD-PT100-4-IFS
Thumbwheel
Description
setting
01 ... 99I/O-MAP address
00Delivery state
**, 1* ... 9*Setting not permitted
*1 ... *9Interface System slave address, for use with other
Interface System (IFS) master devices
3.2.8Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of six data words. For additional
information, please refer to Section 3.2, “RAD-PT100-4-IFS - extension module with four
temperature inputs”.
I/O moduleModule type IDNumber of
registers
RAD-PT100-4-IFS21
hex
06
hex
Address areaFunction
code
30xx0 ... 30xx5fc 04
3827_en_BPHOENIX CONTACT27/138
Page 30
RAD-900-...
3.3RAD-AO4-IFS - analog extension module with four
outputs
Using the analog RAD-AO4-IFS I/O extension module, up to four signals between
0/4 mA ... 20 mA can be output. All the outputs are electrically isolated from one another,
from the supply voltage, and from the electronics.
Use either the current or voltage output per analog channel.
3.3.1Structure
2
1
U
1
U
12
11
10
2
P
W
R
DA
T
ER
R
U
1
I
1
1
U
2
I
2
2
1
2
RAD-AO4-IFS
IO-MAP
3
4
I
1
I
2
O
F
F
1
ON
2
3
4
D
IP-1
8
8
5
6
7
U
3
U
I
4
3
I
4
3
4
9
8
Figure 3-17RAD-AO4-IFS structure
Item Designation
1Analog output 2 (alternatively current or voltage)
2Analog output 1 (alternatively current or voltage)
3DIP switches for configuring the outputs (current/voltage output)
4White thumbwheel for setting the I/O-MAP address
5Connection option for DIN rail connector
6DIN rail
7Metal foot catch for DIN rail fixing
8Analog output 3 (alternatively current or voltage)
9Analog output 4 (alternatively current or voltage)
10ERR status LED, red (communication error)
11DAT status LED, green (bus communication)
12PWR status LED, green (supply voltage)
28/138
PHOENIX CONTACT3827_en_B
Page 31
3.3.2Basic circuit diagram
Description of I/O extension modules
0/4...20 mA
GND
0...10V DC
GND
U
2
3.1
I
2
3.2
3.2
2
3.3
3.3
U
1
2.1
2.1
I
1
2.2
1
2.3
2.3
IO-MAP
U
I
U
I
µC
IFS
DCDCIFS
U
4
4.1
U
I
4
4.2
I
4
4.3
U
3
5.1
U
I
3
5.2
I
3
5.3
Figure 3-18Basic circuit diagram for the RAD-AO4-IFS
3.3.3Setting the DIP switches
You can use the DIP switches on the front to set the behavior of the outputs in the event of
an error (e.g., interruption of the wireless connection). Any changes in the setting of the DIP
switches will be directly applied.
–RESET = Output value is set to 0
–HOLD = Hold last valid output value
1
U1I2I1
11
2U2
222
OFFON1234
DIP-1
PWR
DAT
ERR
3
3
U3I4I3
3
4U4
444
Figure 3-19DIP switches of the RAD-AO4-IFS
3827_en_BPHOENIX CONTACT29/138
Page 32
RAD-900-...
Table 3-5DIP switches of the RAD-AO4-IFS
DIP switch
InputOutput signal1234
Analog OUT1RESETOFF
Analog OUT1HOLDON
Analog OUT2RESETOFF
Analog OUT2HOLDON
Analog OUT3RESETOFF
Analog OUT3HOLDON
Analog OUT4RESETOFF
Analog OUT4HOLDON
3.3.4Diagnostic LEDs
The RAD-AO4-IFS I/O extension module uses a total of three LEDs to indicate the operating
states.
1
U1I2I1
11
2U2
222
OFFON1234
DIP-1
PWR
DAT
ERR
3
3
U3I4I3
3
4U4
444
Figure 3-20Diagnostic LEDs of the RAD-AO4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFFNo supply voltage
ONSupply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFFNo communication
FlashingConfiguration and addressing mode
ONCyclic data communication
30/138
PHOENIX CONTACT3827_en_B
Page 33
Description of I/O extension modules
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding input module has not
been found.
OFFNo error
Flashing
Slow (1.4 Hz)I/O-MAP address changed
Fast (2.8 Hz)Wireless module in I/O data mode
–Missing input module
–No bus communication
Wireless module in PLC/Modbus RTU mode
–No Modbus communication (safe state of outputs,
depending on DIP switch setting)
ONCritical internal error
3.3.5Setting the I/O-MAP address
Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline
wireless system is addressed using the I/O-MAP address. You can assign a maximum of
01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-6Setting the I/O-MAP address for the RAD-AO4-IFS
Thumbwheel
Description
setting
01 ... 99I/O-MAP address
00Delivery state
**, 1* ... 9*Setting not permitted
*1 ... *9Interface System slave address, for use with other
Interface System (IFS) master devices
3.3.6Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of six data words. For additional
information, please refer to Section 3.3, “RAD-AO4-IFS - analog extension module with four
outputs”.
I/O moduleModule type IDNumber of
registers
RAD-AO4-IFS30
hex
06
hex
Address areaFunction code
40xx0 ... 40xx5fc 03, 16
3827_en_BPHOENIX CONTACT31/138
Page 34
RAD-900-...
3.4RAD-DI4-IFS - digital extension module with four
inputs
WARNING: Risk of electric shock
Use the same phase for digital inputs and digital outputs. The isolating voltage between
the individual channels must not exceed 300 V.
The digital RAD-DI4-IFS I/O extension module can process up to four input signals. The
digital inputs process voltages between 0 V ... 50 V AC/DC at the low-voltage input and
voltages between 0 V ... 250 V AC/DC at the high-voltage input. All inputs are electrically
isolated from one another, from the supply voltage, and from the electronics.
3.4.1Structure
2
1
D
I
1
L
D
D
I
I
2
1
L
H
D
D
I
I
2
1
H
D
I
12
11
10
9
2
RAD-DI4-IFS
PW
R
D
A
T
8
8
E
R
R
IO-MAP
DI1
D
I2
DI3
DI4
D
I
3L
D
D
I
I
4L
3H
D
D
I
I
4H
3
D
I
4
D
I
1
L
D
I
1
H
D
I
1
D
I
2L
D
I
2H
D
I
2
4
5
6
3
8
7
32/138
Figure 3-21RAD-DI4-IFS structure
Item Designation
1Digital input as wide-range input
2Digital input as wide-range input
3White thumbwheel for setting the I/O-MAP address
4Connection option for DIN rail connector
5DIN rail
6Metal foot catch for DIN rail fixing
7Digital input as wide-range input
8Digital input as wide-range input
9Status LEDs for digital inputs DI1 ... DI4
10ERR status LED, red (communication error)
11DAT status LED, green (bus communication)
12PWR status LED, green (supply voltage)
PHOENIX CONTACT3827_en_B
Page 35
3.4.2Basic circuit diagram
IO-MAP
Description of I/O extension modules
10...50V AC/DC
GND
50...250V AC/DC
GND
DI
2L
2.1
2.1
DI
2H
2.2
DI
2
2.3
2.3
DI
1L
1.1
DI
1H
1.2
1.2
DI
1
1.3
1.3
µC
IFS
DCDCIFS
DI
3L
5.1
DI
3H
5.2
DI
3
5.3
DI
4L
6.1
DI
4H
6.2
DI
4
6.3
Figure 3-22Basic circuit diagram for the RAD-DI4-IFS
3.4.3Diagnostic LEDs
The RAD-DI4-IFS I/O extension module uses a total of seven LEDs to indicate the operating
states.
DI1LDI1HDI1
1L 1H 1
DI2LDI2HDI2
2L 2
PWR
DAT
ERR
DI1
DI2
DI3
DI4
DI3LDI3HDI3
33H3L
DI4LDI4HDI4
4H4L
Figure 3-23Diagnostic LEDs of the RAD-DI4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFFNo supply voltage
ONSupply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFFNo communication
FlashingConfiguration and addressing mode
ONCyclic data communication
3827_en_BPHOENIX CONTACT33/138
Page 36
RAD-900-...
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding output module has not
been found.
OFFNo error
Flashing
Slow (1.4 Hz)I/O-MAP address changed
Fast (2.8 Hz)No bus communication
ONCritical internal error
DI1 ... DI4
The yellow DI1 ... DI4 LEDs indicate the status of the digital inputs.
3.4.4Setting the I/O-MAP address
Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline
wireless system is addressed using the I/O-MAP address. You can assign a maximum of
01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-7Setting the I/O-MAP address for the RAD-DI4-IFS
Thumbwheel
Description
setting
01 ... 99I/O-MAP address
00Delivery state
**, 1* ... 9*Setting not permitted
*1 ... *9Interface System slave address, for use with other
Interface System (IFS) master devices
3.4.5Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of two data words. For additional
information, please refer to Section 3.4, “RAD-DI4-IFS - digital extension module with four
inputs”.
I/O moduleModule type IDNumber of
registers
RAD-DI4-IFS01
hex
02
hex
Address areaFunction code
30xx0 ... 30xx1fc 04
34/138
PHOENIX CONTACT3827_en_B
Page 37
Description of I/O extension modules
3.5RAD-DI8-IFS - digital extension module with eight
inputs
Use the I/O extension modules in connection with the RAD-900-... wireless module,
firmware version 1.40 or later. You can update the firmware free of charge using the
PSI-CONF software, Version 2.04 or later.
The firmware and software can be found on the Internet at
The digital RAD-DI8-IFS I/O extension module can process up to eight digital input signals
or two pulse signals. You can use DIP switch 1 to set the operating mode. For more detailed
information on setting the DIP switch, please refer to page 36.
The eight digital inputs are arranged in two groups of four inputs each with a common
reference potential (GND). The two DC groups are electrically isolated from one another,
from the supply voltage, and from the electronics.
3.5.1Structure
2
1
D
4
14
13
12
11
10
I
1
D
I
3
O
1
2
3
4
PW
R
DAT
8
ERR
C
N
T
D
I1
D
I2
D
I3
D
I4
D
I5
D
I6
D
I7
D
I8
D
I
5
D
I
7
D
I
1
1
-4
D
I
2
D
I
3
1-4
D
I
4
1-4
D
1-4
I
2
D
I
4
F
F
O
N
D
3
I
P
1
RAD-DI8-IFS
8
IO-MAP
5-8
D
5-8
I
6
D
I
8
5
6
7
9
8
phoenixcontact.net/products.
Figure 3-24RAD-DI8-IFS structure
Item Designation
1Digital inputs 3 + 4
2Digital inputs 1 + 2, DI1: pulse input 1
3White thumbwheel for setting the I/O-MAP address
4DIP switch for switching between static mode and pulse counter mode for digital
inputs
5Connection option for DIN rail connector
6DIN rail
7Metal foot catch for DIN rail fixing
8Digital inputs 5 + 6
9Digital inputs 7 + 8, DI7: pulse input 2
10Status LEDs for digital inputs DI1 ... DI8
3827_en_BPHOENIX CONTACT35/138
Page 38
RAD-900-...
Item Designation
11CNT status LED, green (pulse counter mode)
12ERR status LED, red (communication error)
13DAT status LED, green (bus communication)
14PWR status LED, green (supply voltage)
3.5.2Basic circuit diagram
Static:
0...30,5 VDC
GND
Pulse:
0...100 Hz
GND
DI
3
3.1
1-4
3.2
2.1
DI
4
3.3
2.2
DI
1
2.1
2.1
1-4
2.2
DI
2.2
2
2.3
IO-MAP
0
1
CNTCNT
µC
DC
IFS
DC
IFS
DI
5
4.1
5-8
4.2
DI
6
4.3
DI
7
5.1
5-8
5.2
DI
8
5.3
Figure 3-25Basic circuit diagram for the RAD-DI8-IFS
3.5.3Setting the DIP switches
You can use the DIP switches on the front to select between static mode or pulse counter
mode.
–In static mode, the DI1 ... DI8 inputs are activated, 0 V ... 30.5 V DC voltage.
–In pulse counter mode, the DI1 and DI7 pulse inputs are activated, 0 Hz ... 100 Hz
pulses.
The pulse counter function is only available in PLC/Modbus RTU mode. Set the operating
mode using the PSI-CONF software (from Section 5.6, “Configuration via PSI-CONF
software” onwards).
36/138
PHOENIX CONTACT3827_en_B
Page 39
Description of I/O extension modules
I
Figure 3-26DIP switches of the RAD-DI8-IFS
Table 3-8DIP switches of the RAD-DI8-IFS
DIP switch
InputOutput signal1234
Digital IN
Static modeOFFn.c.n.c.n.c.
DI1 ... DI8
Counter IN
Pulse counter modeONn.c.n.c.n.c.
DI1 + DI7
n. c. = not connected, DIP switches 2 ... 4 have no function
•Use DIP switch 1 to select between static mode and pulse counter mode.
•Disconnect the device from the supply voltage.
•Switch the supply voltage back on.
•The selected mode is now active.
3.5.4Functions in pulse counter mode
The counter state can only increase consecutively. When the maximum counter limit of
4,294,967,295 is reached, the counter is automatically set back to 0. In addition, you can
manually reset the counter states in three different ways:
Reset counter state via power up
•Disconnect the device power supply and then reconnect the voltage.
Reset counter state via the Modbus RTU register
•Reset the counter states via Modbus RTU as follows:
–DI1: bit 0 = 1 (register 40xx1)
–DI7: bit 1 = 1 (register 40xx1)
3827_en_BPHOENIX CONTACT37/138
Page 40
RAD-900-...
Reset counter state by setting the inputs
•Set the corresponding input for at least 0.5 seconds:
–Set the DI3 input in order to reset the DI1 counter state.
–Set the DI5 input in order to reset the DI7 counter state.
3.5.5Diagnostic LEDs
The RAD-DI8-IFS I/O extension module uses a total of twelve LEDs to indicate the operating
states.
Figure 3-27Diagnostic LEDs of the RAD-DI8-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFFNo supply voltage
ONSupply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFFNo communication
FlashingConfiguration and addressing mode
ONCyclic data communication
ERR LED
The red ERR LED indicates the error status.
OFFNo error
Flashing
Slow (1.4 Hz)I/O-MAP address changed or mode switched using DIP
switch 1, but not yet applied
Fast (2.8 Hz)No bus communication
ONCritical internal error
38/138
PHOENIX CONTACT3827_en_B
Page 41
Description of I/O extension modules
CNT LED
The green CNT LED indicates that pulse counter mode is activated.
OFFNo error
FlashingMode switched using DIP switch 1, but not yet applied
ONPulse counter mode of digital inputs DI1 and DI7
DI1 ... DI8
The yellow DI1 ... DI8 LEDs indicate the status of the digital inputs.
In pulse counter mode: The DI1 and DI7 LEDs flash in time with the recorded pulses. The
DI3 and DI5 LEDs light up when the counter state is reset.
DI3ON (0.5 second)Counter state DI1 reset to 0
DI5ON (0.5 second)Counter state DI7 reset to 0
3.5.6Setting the I/O-MAP address
Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline
wireless system is addressed using the I/O-MAP address. You can assign a maximum of
01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-9Setting the I/O-MAP address for the RAD-DI8-IFS
Thumbwheel
setting
01 ... 99I/O-MAP address
00Delivery state
**, 1* ... 9*Setting not permitted
*1 ... *9Interface System slave address, for use with other
Description
Interface System (IFS) master devices
3827_en_BPHOENIX CONTACT39/138
Page 42
RAD-900-...
3.5.7Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of eight data words. For additional
information, please refer to Section 3.5, “RAD-DI8-IFS - digital extension module with eight
inputs”.
I/O moduleModule type IDNumber of
registers
02
hex
Static inputs
06
hex
Pulse inputs
RAD-DI8-IFS
02
hex
Static mode
40
hex
Pulse counter
mode
40
hex
Pulse counter
mode
02
hex
Reset counter
states
Address areaFunction code
30xx0 ... 30xx1fc 04
30xx0 ... 30xx5fc 04
40xx0 ... 40xx1fc 03, 16
40/138
PHOENIX CONTACT3827_en_B
Page 43
Description of I/O extension modules
3.6RAD-DOR4-IFS - digital extension module with four
outputs
WARNING: Risk of electric shock
Use the same phase for digital inputs and digital outputs. The isolating voltage between
the individual channels must not exceed 300 V.
The digital RAD-DOR4-IFS I/O extension module can process up to four input signals that
are switched via relay outputs. The digital outputs are designed as floating relay contacts
(PDT). All outputs are electrically isolated from one another, from the supply voltage, and
from the electronics.
3.6.1Structure
2
1
C
O
M
C
1
O
N
M
O
2
1
N
N
O
C
2
1
N
C
2
OF
F
1
O
N
13
12
11
10
2
3
4
D
IP
-1
RAD-DOR4-IFS
P
W
R
D
A
T
8
8
ER
R
IO-MAP
D
O
1
D
O
2
D
O
3
DO
4
C
O
M
C
3
N
O
O
M
3
4
N
N
O
C
3
4
N
C
4
C
O
M
1
N
O
1
N
C
1
C
O
M
2
N
O
2
N
C
2
5
6
3
7
4
9
8
Figure 3-28RAD-DOR4-IFS structure
Item Designation
1Relay output 2 with floating PDT contact
2Relay output 1 with floating PDT contact
3DIP switches for configuring the output behavior of the relay outputs (hold/reset)
4White thumbwheel for setting the I/O-MAP address
5Connection option for DIN rail connector
6DIN rail
7Metal foot catch for DIN rail fixing
8Relay output 3 with floating PDT contact
9Relay output 4 with floating PDT contact
10Status LEDs for the relay outputs DO1 ... DO4
11ERR status LED, red (communication error)
12DAT status LED, green (bus communication)
13PWR status LED, green (supply voltage)
3827_en_BPHOENIX CONTACT41/138
Page 44
RAD-900-...
3.6.2Basic circuit diagram
IO-MAP
24 V DC/250 V AC
COM
2
2.1
NO
2
2.2
NC
2
2.3
COM
1
1.1
1.1
NO
1
1.2
1.2
NC
1
1.3
µC
IFS
DCDCIFS
COM
COM
3
5.1
NO
3
5.2
NC
3
5.3
4
6.1
NO
4
6.2
NC
4
6.3
Figure 3-29Basic circuit diagram for the RAD-DOR4-IFS
3.6.3Setting the DIP switches
You can use the DIP switches on the front to set the behavior of the outputs in the event of
an error (e.g., interruption of the wireless connection). Any changes in the setting of the DIP
switches will be directly applied.
–RESET = Output value is set to 0
–HOLD = Hold last output value
COM1NO1NC1
1
1 1
COM2NO2NC2
2
2
OFFON1234
DIP-1
PWR
DAT
ERR
DO1
DO2
DO3
DO4
COM3NO3NC3
3
3 3
COM4NO4NC4
4
4 4
42/138
Figure 3-30DIP switches of the RAD-DOR4-IFS
Table 3-10DIP switches of the RAD-DOR4-IFS
DIP switch
SettingOutput signal1234
Digital OUT1RESETOFF
Digital OUT1HOLDON
Digital OUT2RESETOFF
PHOENIX CONTACT3827_en_B
Page 45
Description of I/O extension modules
Table 3-10DIP switches of the RAD-DOR4-IFS
DIP switch
SettingOutput signal1234
Digital OUT2HOLDON
Digital OUT3RESETOFF
Digital OUT3HOLDON
Digital OUT4RESETOFF
Digital OUT4HOLDON
3.6.4Diagnostic LEDs
The RAD-DOR4-IFS I/O extension module uses a total of seven LEDs to indicate the
operating states.
COM1NO1NC1
1
1 1
COM2NO2NC2
2
2
OFFON1234
DIP-1
PWR
DAT
ERR
DO1
DO2
DO3
DO4
COM3NO3NC3
3
3 3
COM4NO4NC4
4
4 4
Figure 3-31Diagnostic LEDs of the RAD-DOR4-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFFNo supply voltage
ONSupply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFFNo communication
FlashingConfiguration and addressing mode
ONCyclic data communication
3827_en_BPHOENIX CONTACT43/138
Page 46
RAD-900-...
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding input module has not
been found.
OFFNo error
Flashing
Slow (1.4 Hz)I/O-MAP address changed
Fast (2.8 Hz)Wireless module in I/O data mode
–Missing input module
–No bus communication
Wireless module in PLC/Modbus RTU mode
–No Modbus communication (safe state of outputs,
depending on DIP switch setting)
ONCritical internal error
DO1 ... DO4
The yellow LEDs DO1 ... DO4 LEDs indicate the status of the digital outputs.
3.6.5Setting the I/O-MAP address
Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline
wireless system is addressed using the I/O-MAP address. You can assign a maximum of
01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-11Setting the I/O-MAP address for the RAD-DOR4-IFS
Thumbwheel
Description
setting
01 ... 99I/O-MAP address
00Delivery state
**, 1* ... 9*Setting not permitted
*1 ... *9Interface System slave address, for use with other
Interface System (IFS) master devices
Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of two data words. For additional
information on process data, please refer to Section 3.6, “RAD-DOR4-IFS - digital
extension module with four outputs”.
I/O moduleModule type IDNumber of
Address areaFunction code
registers
RAD-DOR4-IFS 10
hex
02
hex
40xx0 ... 40xx1fc 03, 16
44/138
PHOENIX CONTACT3827_en_B
Page 47
Description of I/O extension modules
3.7RAD-DO8-IFS - digital extension module with eight
outputs
Use the I/O extension modules in connection with the RAD-900-... wireless module,
firmware version 1.40 or later. You can update the firmware free of charge using the
PSI-CONF software, Version 2.04 or later.
The firmware and software can be found on the Internet at
The digital RAD-DO8-IFS I/O extension module processes up to eight digital output signals
that are switched via transistor outputs. The eight outputs are arranged in two groups of four
outputs each with a common electrical supply. The two output groups are electrically
isolated from one another, from the supply voltage, and from the electronics.
Since the DO1 ... DO4 and DO5 ... DO8 output groups are electrically isolated, the digital
outputs must be externally supplied (see Figure 3-33).
•The DO1 ... DO4 outputs are supplied via:
–Terminal 1.1 (12 V DC ... 30.5 V DC)
–Terminals 1.2/1.3 (GND)
•The DO5 ... DO8 outputs are supplied via:
–Terminal 6.1 (12 V DC ... 30.5 V DC)
–Terminals 6.2/6.3 (GND)
phoenixcontact.net/products.
3.7.1Structure
3
2
1
D
O
3
+
2
4
V
1-4
D
O
1-4
1
D
O
1-4
1-4
3
D
O
1-4
2
D
O
4
O
FF
1
O
N
15
14
13
12
2
3
4
D
IP
-1
RAD-DO8-IFS
P
W
R
D
AT
8
8
ER
R
IO-MAP
D
O1
D
O2
D
O3
D
O4
D
O
5
D
O6
D
O
7
D
O
8
D
O
5
D
O
5-8
7
+
2
4
D
V
O
5-8
5-8
6
D
O
5
-8
8
5-8
Figure 3-32RAD-DO8-IFS structure
Item Designation
1Transistor outputs 3 + 4
2Transistor outputs 1 + 2
3Supply voltage for outputs 1 ... 4
4DIP switches for setting the output behavior of the transistor outputs (hold/reset)
5White thumbwheel for setting the I/O-MAP address
6Connection option for DIN rail connector
+
2
4
V
1-4
1-4
1-4
DO
1
1
-4
DO
2
1
4
D
O
4
4
6
7
8
5
11
10
9
3827_en_BPHOENIX CONTACT45/138
Page 48
RAD-900-...
Item Designation
7DIN rail
8Metal foot catch for DIN rail fixing
9Transistor outputs 5 + 6
10Transistor outputs 7 + 8
11Supply voltage for outputs 5 ... 8
12Status LEDs of transistor outputs DO1 ... DO8
13ERR status LED, red (communication error)
14DAT status LED, green (bus communication)
15PWR status LED, green (supply voltage)
3.7.2Basic circuit diagram
DO
5
4.1
5-8
4.2
DO
6
4.3
Do
7
5.1
5-8
5.2
Do
8
5.3
+24V
5-8
6.1
5-8
6.2
5-8
6.3
30,5 V DC
GND
DO
3
3.1
1-4
3.2
DO
4
3.3
DO
2.1
2.2
1
2.1
1-4
2.2
DO
2
2.3
+24V
1-4
1.1
1-4
1.2
1-4
1.3
IO-MAP
0
1
µC
IFS
DCDCIFS
Figure 3-33Basic circuit diagram for the RAD-DO8-IFS
3.7.3Setting the DIP switches
You can use the DIP switches on the front to set the behavior of the outputs in the event of
an error (e.g., interruption of the wireless connection). Any changes in the setting of the DIP
switches will be directly applied.
–RESET = Output value is set to 0
–HOLD = Hold last output value
46/138
PHOENIX CONTACT3827_en_B
Page 49
Description of I/O extension modules
Figure 3-34DIP switches of the RAD-DO8-IFS
Table 3-12DIP switches of the RAD-DO8-IFS
DIP switch
SettingOutput signal1234
Digital OUT 1 ... 4RESETOFFn. c.n. c.
Digital OUT 1 ... 4HOLDONn. c.n. c.
Digital OUT 5 ... 8RESETOFFn. c.n. c.
Digital OUT 5 ... 8HOLDONn. c.n. c.
n. c. = not connected, DIP switches 3 and 4 have no function
3.7.4Diagnostic LEDs
The RAD-DO8-IFS I/O extension module uses a total of eleven LEDs to indicate the
operating states.
Figure 3-35Diagnostic LEDs of the RAD-DO8-IFS
3827_en_BPHOENIX CONTACT47/138
Page 50
RAD-900-...
PWR LED
The green PWR LED indicates the supply voltage status.
OFFNo supply voltage
ONSupply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFFNo communication
FlashingConfiguration and addressing mode
ONCyclic data communication
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding input module has not
been found.
OFFNo error
FlashingWireless module in I/O data mode
–Missing input module
–No bus communication
Wireless module in PLC/Modbus RTU mode
–No Modbus communication (safe state of outputs, depending on
DIP switch setting)
–Short circuit at one output or several outputs
ONCritical internal error
48/138
DO1 ... DO8
The yellow DO1 ... DO8 LEDs indicate the status of the digital outputs.
DO1 ... DO4FlashingShort circuit at one output or several outputs 1 ... 4
DO5 ... DO8FlashingShort circuit at one output or several outputs 5 ... 8
PHOENIX CONTACT3827_en_B
Page 51
Description of I/O extension modules
3.7.5Setting the I/O-MAP address
Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline
wireless system is addressed using the I/O-MAP address. You can assign a maximum of
01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-13Setting the I/O-MAP address for the RAD-DO8-IFS
Thumbwheel
Description
setting
01 ... 99I/O-MAP address
00Delivery state
**, 1* ... 9*Setting not permitted
*1 ... *9Interface System slave address, for use with other
Interface System (IFS) master devices
3.7.6Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of four data words. For additional
information, please refer to Section 3.7, “RAD-DO8-IFS - digital extension module with eight
outputs”.
I/O moduleModule type IDNumber of
registers
02
hex
Outputs
RAD-DO8-IFS11
hex
02
hex
Short-circuit
detection
Address areaFunction code
40xx0 ... 40xx1fc 03.16
30xx0 ... 30xx1fc 04
3827_en_BPHOENIX CONTACT49/138
Page 52
RAD-900-...
3.8RAD-DAIO6-IFS - analog/digital extension module
with six channels
WARNING: Risk of electric shock
Use the same phase for digital inputs and digital outputs. The isolating voltage between
the individual channels must not exceed 300 V.
The analog/digital RAD-DAIO6-IFS I/O extension module has a total of six channels. The
device is able to process two digital input and output signals as well as one analog input
signal and one analog output signal. All inputs and outputs are electrically isolated from one
another, from the supply voltage, and from the electronics.
Two digital inputs
The digital inputs process voltages between 0 V ... 50 V AC/DC at the low-voltage input and
0 V ... 250 V AC/DC at the high-voltage input.
Two digital outputs
The digital outputs are designed as floating relay contacts (PDT). The switching capacity is
2 A at 250 V AC/24 V DC.
Analog input
The analog input is able to process standard signals between 0/4 mA ... 20 mA. A supply
voltage of at least 12 V DC is available at the PWR
passive sensors.
connection terminal block for the use of
1
Analog output
The analog output is designed as active output. You can either select a current signal
0/4 mA ... 20 mA or a voltage signal 0 V ... 10 V.
Use either a current or voltage output at the analog output.
50/138
PHOENIX CONTACT3827_en_B
Page 53
Description of I/O extension modules
3.8.1Structure
3
2
D
I
1
L
D
1
P
w
r
1
+
I
1
I
1
D
I
1L
D
D
I
I
2L
1H
P
D
w
D
I
r
I
2H
1
1
+
D
I
I
1
2
I
1
16
15
14
13
12
OF
F
1
O
N
2
3
4
DIP-
1
P
RAD-DAIO6-IFS
W
R
DA
T
8
8
ER
R
IO-MAP
DI
1
DI2
D
O
1
D
O
2
U
1
C
O
I
M
1
C
1
N
O
O
M
1
1
2
N
N
O
C
2
1
N
C
2
Figure 3-36RAD-DAIO6-IFS structure
Item Designation
1Analog input for 2-, 3-, 4-wire measuring transducers
2Digital input as wide-range input
3Digital input as wide-range input
4DIP switches for configuring the inputs and outputs
5White thumbwheel for setting the I/O-MAP address
6Connection option for DIN rail connector
7DIN rail
8Metal foot catch for DIN rail fixing
9Analog output, alternatively current or voltage
10Relay output with floating PDT contact
11Relay output with floating PDT contact
12Status LEDs of the digital DO1 ... DO2
13Status LEDs of the digital DI1 ... DI2 inputs
14ERR status LED, red (communication error)
15DAT status LED, green (bus communication)
16PWR status LED, green (supply voltage)
I
1
H
D
I
1
D
I
2
L
D
I
2
H
D
I
2
6
7
4
8
5
11
10
9
3827_en_BPHOENIX CONTACT51/138
Page 54
RAD-900-...
3.8.2Basic circuit diagram
PWR IN
3.1
2 Wire
3 Wire
U
4 Wire
S
10...50V AC/DC
GND
50...250V AC/DC
GND
0...10V DC
0/4...20 mA
GND
24 VACDC/250 V
Out
PWR IN
Out
GND
Out
GND
PWR
3.2
1
3.1
+I
1
3.1
3.2
-I
1
3.2
3.3
3.3
DI
2L
2.1
3.2
DI
2H
2.2
3.3
DI
2
2.3
2.1
DI
1L
2.3
1.1
DI
1H
1.2
1.2
DI
1
1.3
1.3
4.1
4.2
4.3
5.1
5.2
IO-MAP
V
LOOP
I
µC
IFS
DCDCIFS
U
1
4.1
U
I
1
4.2
I
1
4.3
COM
1
5.1
NO
1
5.2
NC
1
5.3
COM
2
6.1
NO
2
6.2
NC
2
6.3
Figure 3-37Basic circuit diagram for the RAD-DAIO6-IFS
3.8.3Setting the DIP switches
The DIP switches on the front can be used to configure the input signals ranges. In addition,
you can set the behavior of the outputs in the event of an error (e.g., interruption of the
wireless connection). Any changes in the setting of the DIP switches will be directly applied.
Analog output
–RESET = Output value is set to 0
–HOLD = Hold last output value
Digital outputs
–RESET = Relay drops out
–HOLD = Hold last valid state
Figure 3-38DIP switches of the RAD-DAIO6-IFS
52/138
PHOENIX CONTACT3827_en_B
Page 55
Description of I/O extension modules
Table 3-14DIP switches of the RAD-DAIO6-IFS
DIP switch
SettingOutput signal1234
Analog IN0 ... 20 mAOFF
Analog IN4 ... 20 mAON
Analog OUTRESETOFF
Analog OUTHOLDON
Digital OUT1RESETOFF
Digital OUT1HOLDON
Digital OUT2RESETOFF
Digital OUT2HOLDON
3.8.4Diagnostic LEDs
The RAD-DAIO6-IFS I/O extension module uses a total of seven LEDs to indicate the
operating states.
Figure 3-39Diagnostic-LEDs of the RAD-DAIO6-IFS
PWR LED
The green PWR LED indicates the supply voltage status.
OFFNo supply voltage
ONSupply voltage OK
DAT LED
The green DAT LED indicates the bus communication status.
OFFNo communication
FlashingConfiguration and addressing mode
ONCyclic data communication
3827_en_BPHOENIX CONTACT53/138
Page 56
RAD-900-...
ERR LED
The red ERR LED indicates the error status, e.g., if a corresponding output module has not
been found.
OFFNo error
Flashing
Slow (1.4 Hz)I/O-MAP address changed
Fast (2.8 Hz)Wireless module in I/O data mode
–Missing input module
–No bus communication
Wireless module in PLC/Modbus RTU mode
–No Modbus communication (safe state of outputs,
depending on DIP switch setting)
ONCritical internal error
DI1 / DI2
The yellow DI1 and DI2 LEDs indicate the status of the digital inputs.
DO1/DO2
The yellow DO1 and DO2 LEDs indicate the status of the digital outputs.
3.8.5Setting the I/O-MAP address
Use the thumbwheel to set the I/O-MAP address. The extension module in the Radioline
wireless system is addressed using the I/O-MAP address. You can assign a maximum of
01 ... 99 addresses to the I/O extension modules in the entire wireless network.
Table 3-15Setting the I/O-MAP address for the RAD-DAIO6-IFS
Thumbwheel
setting
01 ... 99I/O-MAP address
00Delivery state
**, 1* ... 9*Setting not permitted
*1 ... *9Interface System slave address, for use with other
Description
Interface System (IFS) master devices
54/138
PHOENIX CONTACT3827_en_B
Page 57
Description of I/O extension modules
3.8.6Process data in PLC/Modbus RTU mode
The process image of the I/O extension module consists of six data words. For additional
information, please refer to Section 3.8, “RAD-DAIO6-IFS - analog/digital extension module
with six channels”.
I/O moduleModule type IDNumber of
registers
03
hex
RAD-DAIO6-IFS 60
hex
(inputs)
03
hex
Address areaFunction
code
30xx0 ... 30xx2fc 04
40xx0 ... 40xx2fc 03, 16
(outputs)
3.9RAD-RS485-IFS modules
For some distributed systems, or networks with very large I/O counts, the master wireless
device can be expanded with RAD-RS485-IFS modules. I/O extension modules in the
wireless network can be mapped to I/O extension modules connected to RAD-RS485-IFS
modules. This is only supported in Wire In/Wire Out mode.
DI1L
DI1H
DI1
+24V
0V
COM1
NC1
NO1
DI2L
DI2H
DI2
RSSI
+
RSSI
-
COM2
NC2
NO2
UL1 +I1 -I1
ANT
S
S
OFF ON
OFF ON
1
1
2
2
3
3
S-PORT
4
4
DIP-1
DIP-1
RAD-2400-IF
RAD-DOR4-IF
RAD-DAIO6-IFS
PWR
PWR
PWR
8 8
1 2
0
2
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DO1
DO1
SET
DO2
DO2
DO3
DO3
RXTX
DO4
DO4
D(A)
D(B)
U1 I1
1
COM3
NC3
NO3
COM1
NC1
RX
GND
NO1
TX
COM4
NC4
NO4
COM2
NC2
1
COM
NC
1
NO2
2
NO
DI1L
DI1H
DI1
+24V
0V
COM1
NC1
NO1
U1U2I1
DI2L
DI2H
DI2
RSSI
+
RSSI
-
COM2
NC2
NO2
UL1 +I1 -I1
ANT
PWR
0
DAT
ERR
RXTX
D(A)
D(B)
RX
TX
1
COM
NO
I2 2
S
S
OFF ON
OFF ON
OFF ON
1
1
1
2
2
2
3
3
3
S-PORT
4
4
4
DIP-1
DIP-1
DIP-1
RAD-2400-IF
RAD-DOR4-IF
RAD-DAIO6-IFS
PWR
PWR
PWR
1 2
8 8
2 2
1
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DO1
DO1
SET
DO2
DO2
DO3
DO3
DO4
DO4
U1 I1
U3U4I3
1
COM3
NC3
NO3
COM1
NC1
GND
I4 4
NO1
COM4
NC4
NO4
COM2
NC2
1
NC
NO2
2
+24V
0V
DI1L
DI1H
DI1
1
DI2L
DI2H
DI2
RAD-AO4-IFS
PWR
7 7
DAT
IO-MAP
ERR
DI1
DI2
DI3
DI4
3
DI3L
DI3H
DI3
DI4L
DI4H
DI4
COM1
NC1
NO1
U1U2I1
1
RSSI
+
RSSI
-
COM2
NC2
NO2
I2 2
ANT
S
RAD-DI4-IF
IO-MAP
S
S
OFF ON
OFF ON
1
1
2
2
3
3
S-PORT
4
4
DIP-1
DIP-1
RAD-AO4-IFS
RAD-2400-IF
RAD-DOR4-IF
PWR
PWR
PWR
8 8
2 2
0
3
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DO1
SET
DO2
DO3
RXTX
DO4
D(A)
D(B)
U3U4I3
3
COM3
NC3
NO3
RX
GND
I4 4
TX
COM4
NC4
NO4
1
COM
1
NC
NO
2
+24V
0V
DI1L
DI1H
DI1
Pwr1
+I1
-I1
RSSI
+
RSSI
-
DI2L
DI2H
DI2
Pwr2
+I2
-I2
ANT
S
S
OFF ON
1
2
3
S-PORT
4
RAD-AI4-IFS
RAD-DI4-IF
DIP-1
RAD-2400-IF
PWR
PWR
PWR
8 8
2 2
0
4
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DI1
SET
DI2
DI3
RXTX
DI4
D(A)
D(B)
Pwr3
+I3
-I3
DI3L
DI3H
DI3
RX
GND
Pwr4
+I4
-I4
TX
DI4L
DI4H
DI4
1
COM
1
NC
NO
2
RS-485
+24V
+24V
0V
COM1
NC1
NO1
U1U2I1
COM2
NC2
NO2
S
OFF ON
1
2
3
S-PORT
4
DIP-1
RAD-DOR4-IF
RAD-RS485-IFS
PWR
PWR
PWR
7 7
0
5
DAT
DAT
DAT
RAD-ID
IO-MAP
ERR
ERR
ERR
DO1
SET
DO2
LINK
DO3
RXTX
DO4
D(A)
D(B)
U3U4I3
COM3
NC3
NO3
COM4
NC4
NO4
COM
1
NC1
NO1
+24V
0V
COM1
NC1
NO1
1
I2 2
OFF ON
1
2
3
4
DIP-1
RAD-AO4-IFS
4 4
IO-MAP
3
I4 4
U1U2I1
COM2
NC2
NO2
S
OFF ON
OFF ON
1
1
2
2
S485-IFS
3
3
S-PORT
4
4
DIP-1
DIP-1
RAD-DOR4-IF
RAD-R
PWR
PWR
PWR
7 7
4 4
0
6
DAT
DAT
DAT
RAD-ID
IO-MAP
ERR
ERR
ERR
DO1
SET
DO2
LINK
DO3
RXTX
DO4
D(A)
D(B)
U3U4I3
COM3
NC3
NO3
COM4
NC4
NO4
COM
1
NC1
NO1
0V
COM1
NC1
NO1
U1U2I1
1
I2 2
RAD-AO4-IFS
IO-MAP
3
I4 4
1
COM2
NC2
NO2
I2 2
S
OFF ON
OFF ON
1
1
2
2
S485-IFS
3
3
S-PORT
4
4
DIP-1
DIP-1
RAD-AO4-IFS
RAD-DOR4-IF
RAD-R
PWR
PWR
PWR
7 7
4 4
0
7
DAT
DAT
DAT
RAD-ID
IO-MAP
IO-MAP
ERR
ERR
ERR
DO1
SET
DO2
LINK
DO3
RXTX
DO4
D(A)
D(B)
U3U4I3
3
COM3
NC3
NO3
I4 4
COM4
NC4
NO4
COM
1
NC1
NO1
RS-485RS-485RS-485
Figure 3-40Typical RAD-RS485-IFS installation
3827_en_BPHOENIX CONTACT55/138
Page 58
RAD-900-...
56/138
PHOENIX CONTACT3827_en_B
Page 59
4Installation
Installation
4.1DIN rail-mounted devices (RAD-900-IFS)
4.1.1Mounting/removal
You can connect up to 32 different I/O extension modules to each wireless module via the
DIN rail connector. Data is transmitted and power is supplied to the I/O extension modules
via the bus foot.
When using the device in a connection station, use the supplied 17.5 mm wide DIN rail
connector. Only use the DIN rail connector in connection with 24 V DC devices.
Mount the wireless module to the left and the I/O extension modules exclusively to the right of the wireless module.
The individual extension modules can be arranged in any order.
Figure 4-1Radioline connection station with up to 32 I/O extension modules
3827_en_BPHOENIX CONTACT57/138
Page 60
RAD-900-...
A
B
C
DE
Figure 4-2Mounting and removal
To mount a connection station with DIN rail connectors, proceed as follows:
1. Connect the DIN rail connectors together for a connection station.
2. Push the connected DIN rail connectors onto the DIN rail.
3. Place the device onto the DIN rail from above (see Figure 4-2, D). Make sure that the
device and DIN rail connector are aligned correctly.
4. Holding the device by the housing cover, carefully push the device towards the
mounting surface so that the device bus connector is fixed securely on the DIN rail
connector.
5. Once the snap-on foot snaps onto the DIN rail, check that it is fixed securely. The device
is only mechanically secured via the DIN rail.
6. Connect the desired number of I/O extension modules to the wireless module via the
DIN rail connector.
58/138
Device replacement is also possible during operation when outside the hazardous area.
Removal
1. Use a suitable screwdriver to release the locking mechanism on the snap-on foot of the
device (see Figure 4-2, E).
2. Hold onto the device by the housing cover and carefully tilt it upwards.
3. Carefully lift the device off the DIN rail connector and the DIN rail.
PHOENIX CONTACT3827_en_B
Page 61
4.1.2Connecting wires
Installation
B
PWR
DAT
8
ERR
8
A
Figure 4-3Connecting wires
For easy installation, it is also possible to pull out the screw terminal block from the device
and to re-insert it after having connected the wires.
2
1. Crimp ferrules to the wires. Permissible cable cross section: 0.2 mm
(24 … 14 AWG).
2. Insert the wire with ferrule into the corresponding connection terminal block.
3. Use a screwdriver to tighten the screw in the opening above the connection terminal
block. Tightening torque: 0.6 Nm
... 2.5 mm2
4.1.3Connecting the power supply
Via screw terminal blocks
Connect a DC voltage source (10.8 V ... 30.5 V DC) to the wireless module. The nominal
voltage is 24 V DC. Supply voltage to the device via the terminals 1.1 (24 V) and 1.2 (0 V).
In the case of a connection station, it is sufficient to supply the first device in the group.
NOTE:
The power supply must be connected to terminals 1.1 and 1.2. Power supply via the DIN
rail connector (TBUS) is not permitted.
3827_en_BPHOENIX CONTACT59/138
Page 62
RAD-900-...
1
.1
1
.2
R
S
S
I+
R
SS
I-
+
2
4
V
R
S
0
S
V
I
+
R
S
S
I
A
N
T
S.PORT
RAD-2400-IFS
PWR
D
A
8
T
8
ER
R
RAD-ID
Reset
RX TX
D
(A
)
D
R
(
X
B
)
C
O
T
M
X
1
N
G
O
N
D
1
N
C
1
Figure 4-4Connecting the power supply
In order to prevent damage to the wireless module, we recommend the installation of a
surge arrester. Wiring between the surge arrester and the wireless module should be as
short as possible. Please also observe the manufacturer’s specifications.
4.1.4Serial interfaces
The RAD-900-IFS wireless module has one RS-232 interface and one RS-485 2-wire
interface. Connect the I/O device to the wireless module via the corresponding serial
interface.
Both serial interfaces are deactivated by default. Activate and configure the RS-232 or
RS-485 interface using the PSI-CONF software (from Section 5.6, “Configuration via PSICONF software” onwards).
You can only use one interface per wireless module. Parallel operation of both interfaces
is not possible.
4.1.4.1Connecting the RS-485 cable
In RS-485 mode, an RS-485 network with several I/O devices can be created. Use a
twisted-pair, common shielded bus
NOTE:
Observe the polarity of the RS-485 cable. Install the bus cable with a termination network
at the two furthest points of the RS-485 network.
Termination resistors are integrated into the RAD-900-IFS and can be switched on using
the DIP switches on the side of the module.
RS-485 pin assignment
In RS-485 mode, you can create a network with several I/O devices. Use a twisted-pair bus
cable to connect the I/O devices. Install this bus cable with a termination network at the two
furthest points.
•Connect the single wires of the data cable to the COMBICON plug-in screw terminal
block (Figure 2-1, item 10).
•Make sure the signal assignment is correct.
60/138
PHOENIX CONTACT3827_en_B
Page 63
Installation
COMBICON
+
D(B)
D(A)
RAD-2400-IFS
(4.1)
-
(4.2)
RS-485
D(B)
D(A)
+
-
Figure 4-5RS-485 interface pin assignment
RS-232 pin assignment
In RS-232 mode, point-to-point connections can be established.
The RS-232 interface of the wireless module is a DTE type (Data Terminal Equipment).
This means that terminal point 5.2 (Tx) is always used for transmission and terminal point
5.1 (Rx) is always used for reception.
Only connect the wireless module to devices which meet the requirements of EN 60950.
According to the standard, you can connect a DCE device (Data Communication
Equipment) to the RS-232 interface using a 1:1 cable (Figure 4-6). It is also possible to
connect a DTE device using a crossed cable (Figure 4-7).
If you are not sure whether the device to be connected is of DTE or DCE type, measure the
voltage between TX and GND in the idle state.
–If the voltage measures approximately -5 V, it is a DTE device.
–If the voltage measures approximately 0 V, it is a DCE device.
3827_en_BPHOENIX CONTACT61/138
Page 64
RAD-900-...
D-SUB 9 pin assignment
The RAD-900-IFS provides a D-SUB 9 female connector for attaching RS-232 serial
devices.
Figure 4-8D-SUB 9 straight-through cable pinouts for 3-wire (A) and 5-wire (B)
Figure 4-9D-SUB 9 null cable pinouts for 3-wire (A) and 5-wire (B)
4.1.5Connecting the antenna
The wireless module is provided with an RSMA antenna socket for an external antenna.
Install the antenna outside the control cabinet or building.
Observe the installation instructions of the antenna and the “Installation and operation” on
page 6.
Observe the maximum permissible emitted transmission power of 36 dBm. The
transmission power can be calculated as:
device transmission power + antenna gain - cable attenuation
Reduce the device transmission power, if necessary.
62/138
PHOENIX CONTACT3827_en_B
Page 65
A
+
2
4
V
B
0
V
R
S
S
I+
R
S
S
I-
+
2
4
V
RSSI+
0
V
RS
SI-
A
N
T
S.PORT
RAD-2400-IFS
PW
R
D
AT
8
8
ER
R
RAD-ID
Reset
RX TX
D
(
A
)
D
R
(
X
B
)
C
O
TX G
M
1
N
O
N
D
1
N
C
1
Figure 4-10Connecting the antenna
4.2Wall-mounted devices (RAD-900-DAIO6)
4.2.1Mounting
Installation
The RAD-900-DAIO6 includes mounting feet for installing the device on a vertical surface.
1. Loosen the four screws securing the cover and remove the cover.
2. Attach the mounting feet to the RAD-900-DAIO6 in the desired orientation using the
included screws, flat washers and lockwashers.
4-3-2-1
Figure 4-11Mounting feet
3827_en_BPHOENIX CONTACT63/138
Page 66
RAD-900-...
3. Install the RAD-900-DAIO6 on the desired surface using appropriate hardware (not
supplied).
152
COM NO NCLV HV COMLV HV COMCOM NO NC
DIGITAL IN 2
FUSE
82
DIGITAL IN 1
DC
COM NO NC
230V
POWER
RF LINK
AC
DIGITAL OUT 1
U I COMPWR +I -I+ -+ -
ANALOG IN
ANALOG OUT
DIGITAL OUT 2
S-PORT
DIP
4-3-2-1
ON-OFF
RAD
ID
PWR
DAT
SET
ERR
RSSI
RF
LINK
D1
1 2
D2
204
274
Figure 4-12Mounting dimensions
Mounting considerations:
–Avoid mounting in direct sunlight to minimize the effects of solar loading (heating).
–Installation of a sun shield is recommended over the RAD-900-DAIO6 when it is
mounted in direct sunlight and the ambient temperature can exceed 45°C.
4.2.2Wire entry
The RAD-900-DAIO6 is supplied with two 1/2-in. NPT conduit hubs installed for connection
to rigid or flexible conduit. Alternatively, cable glands may be installed using suitable cables.
Use an approved thread sealant to ensure a water tight seal.
WARNING:
All connections must be sealed. If not, excess moisture accumulation can accumulate
inside the device. Make sure to mount the transmitter with the electrical housing
positioned downward for drainage. To avoid moisture accumulation in the housing, install
wiring with a drip loop, and ensure the bottom of the drip loop is mounted lower than the
conduit connections. The device is fitted with a breather vent to prevent excess moisture
accumulation. Ensure the breather vent is kept free of debris.
64/138
4.2.3Connecting wires
1. Crimp ferrules to the wires. Permissible cable cross section: 0.2 mm² ... 2.5 mm²
(24 … 14 AWG).
2. Insert the wire with ferrule into the corresponding connection terminal block.
3. Use a screwdriver to tighten the screw in the opening above the connection terminal
block. Torque screw to 0.6 Nm.
PHOENIX CONTACT3827_en_B
Page 67
4. Install zip ties to manage wire routing.
Installation
COM NO NCLV HV COMLV HV COMCOM NO NC
DIGITAL IN 2
FUSE
DIGITAL IN 1
DC
COM NO NC
230V
POWER
RF LINK
AC
DIGITAL OUT 1
U I COM PWR +I -I + -+ -
ANALOG IN
ANALOG OUT
DIGITAL OUT 2
S-PORT
DIP
4-3-2-1
ON-OFF
RAD
ID
PWR
DAT
SET
ERR
RSSI
RF
LINK
D1
1 2
D2
Zip ties
Figure 4-13Zip ties
4.2.4Connecting power
DANGER:
Always disconnect power before installing or performing maintenance.
Select the input voltage range via the selector switch
•When the switch is set to DC mode, connect a DC voltage source (10.8 … 30.5 V DC)
to the wireless module. The nominal voltage is 24 V DC.
•When the switch is set to AC mode, connect an AC voltage source (100 … 240 V AC)
to the wireless module. When powered by an AC voltage source, the maximum
temperature is 65°C.
WARNING:
The fuse protects the RAD-900-DAIO6 in case of an overcurrent event or if the selector
switch is in the wrong position.
In order to prevent damage to the wireless module, Phoenix Contact recommends the
installation of a surge arrester. Wiring between the surge arrester and the wireless module
should be as short as possible. Please also observe the manufacturer's specifications.
4.2.4.1Replacing the fuse
The fuse can be replaced using a 5x20 mm slow-blow fuse rated for 800 mA @ 250 V AC.
Use types Littelfuse
®
0215.800MXP, Bel Fuse 5HT 800-R or equivalent.
1. Disconnect supply voltage.
2. To remove the fuse, turn the fuse cover 90° counter-clockwise and remove it to access
the fuse.
3. Install the replacement fuse.
WARNING:
Never operate the device without the cover installed.
4. Replace the cover.
3827_en_BPHOENIX CONTACT65/138
Page 68
RAD-900-...
4.2.5Connecting the antenna
The wireless module has an N-type antenna socket for an external antenna. Although a
0 dB omni-directional antenna is included with the wireless module, it may be replaced with
a coaxial cable and high-gain antenna.
Install the antenna outside the control cabinet or building.
Observe the installation instructions of the antenna and the “Installation and operation” on
page 6.
Observe the maximum permissible emitted transmission power of 36 dBm. The
transmission power can be calculated as:
device transmission power + antenna gain - cable attenuation
Reduce the device transmission power, if necessary.
If the antenna is removed and re-installed or a cable is attached for a remote antenna,
torque the antenna or cable connector between 0.7 and 1.1 Nm.
66/138
PHOENIX CONTACT3827_en_B
Page 69
5Configuration and startup
5.1Default settings of the wireless module
All RAD-900-… wireless modules have the same configuration by default upon delivery or
by resetting to the default settings at a later stage.
Table 5-1Default settings of the wireless module
ParameterSetting
Operating modeI/O data (wire in/wire out)
Wireless interface
Net ID127
RF band1
EncryptionOFF
Network structureStar
Device typeSlave
Data rate of the wireless interface125 kbps
Transmission power1 W (30 dBm)
Configuration and startup
In order to be able to cover the largest possible distances, the preamplifier has been
activated and transmission power set to 30 dBm by default. When operating the devices
directly next to one another, the receiver might become overloaded. In this case, remove
the antennas, increase the distance between the devices and antennas or reduce
transmission power using the PSI-CONF software (from page 74 onwards).
5.1.1Resetting to the default settings
The device can be reset to the default settings either manually or using the PSI-CONF
software.
Resetting manually
1. Disconnect the device from the supply voltage.
2. Hold down the SET button located on the front of the device and switch the supply
voltage on.
3. Press and hold the SET button until the DAT LED flashes.
Resetting via PSI-CONF software
1. Select “Wireless, RAD-900-IFS” on the “Device Selection” page.
2. Select “Local Device”.
3. Select “Set device to factory default configuration”.
3827_en_BPHOENIX CONTACT67/138
Page 70
RAD-900-...
5.1.2Firmware update
Download the latest firmware free of charge at
The firmware can be updated using the PSI-CONF software. The device is reset to the
default settings after a firmware update.
1. Select “Wireless, RAD-900-IFS” on the “Device Selection” page.
2. Select “Update firmware”.
phoenixcontact.net/products.
5.2Operating mode of the wireless module
The Radioline wireless system offers four different options for signal and data transmission:
Operating modeConfiguration
I/O data modeDefault setting, configuration only possible via
thumbwheel
Serial data mode
Configuration via PSI-CONF softwarePLC/Modbus RTU mode
PLC/Modbus RTU dual mode
Only one operating mode can be selected. It is not possible to simultaneously transmit I/O
signals and serial data.
If the wireless system is operated in an environment where other networks are also present
(e.g., additional Radioline networks in the 900 MHz band), then a configuration memory can
be used (see “Configuration via CONFSTICK” on page 71). For configuring extended
settings of the wireless modules, it is also possible to use the PSI-CONF software (from
page 74 onwards).
68/138
PHOENIX CONTACT3827_en_B
Page 71
Configuration and startup
I/O data mode
Figure 5-1I/O data mode
By default, all wireless modules are in the I/O data mode. For simple I/O-to-I/O applications
with extension modules, you can easily set the addresses using the thumbwheel. You can
therefore establish a wireless connection to other wireless modules without any
programming effort (see “Setting the address of the wireless module via the thumbwheel”
on page 71 and “Setting the address of the extension modules via the thumbwheel” on
page 80).
Serial data mode (RAD-900-IFS only)
Figure 5-2Serial data mode
In serial data mode, multiple controllers or serial I/O devices are networked easily and
quickly using wireless technology. In this way, serial RS-232 or RS-485 cables can be
replaced.
Each wireless module must be configured using the PSI-CONF software (from page 74
onwards).
3827_en_BPHOENIX CONTACT69/138
Page 72
RAD-900-...
PLC/Modbus RTU mode
Figure 5-3PLC/Modbus RTU mode
Connect the I/O extension modules to the controller directly via the integrated RS-232 and
RS-485 interface by means of wireless communication. In PLC/Modbus RTU mode, the
master wireless module (RAD ID = 01) operates as a Modbus slave. The master wireless
module has its own Modbus address.
Connect I/O extension modules to each wireless module in the network. The I/O data of the
extension module is stored in the internal Modbus memory map of the master wireless
module. In addition, the diagnostic data from all wireless devices is stored here.
Each wireless module must be configured using the PSI-CONF software (from page 74
onwards).
70/138
PLC/Modbus RTU dual mode
Figure 5-4PLC/Modbus RTU dual mode
Dual mode combines the PLC/Modbus RTU mode and the serial data mode. Serial Modbus
devices can be connected to the RS-232 or RS-485 ports, and connect I/O extension
modules to each wireless module in the network.
PHOENIX CONTACT3827_en_B
Page 73
Configuration and startup
The I/O data of the extension module and the diagnostic data is stored in the internal
Modbus memory map of the wireless module. Each wireless module with I/O extension
modules has its own Modbus address. In addition, the diagnostic data from all wireless
devices can be read from the master wireless module.
Each wireless module must be configured using the PSI-CONF software (from page 74
onwards).
5.3Setting the address of the wireless module via the
thumbwheel
Set the desired station address with the yellow thumbwheel on the wireless module. There
must be one master (RAD ID = 01) and at least one repeater/slave (RAD ID = 02 ... 99) in a
network.
Unique addressing is required in a network. If two wireless modules have the same
address in a network, the network will not function properly.
Setting the address via the thumbwheel has priority over setting the address via the
PSI-CONF software.
After making any change to the module address, press the SET button for one second to
apply the setting.
The following settings can be made using the yellow thumbwheel:
Addressing wireless modules using the PSI-CONF software (address
1 ... 250)
IDs 100 to 250 must be configured using PSI-CONF software
5.4Configuration via CONFSTICK
WARNING: Explosion hazard when used in potentially explosive areas
Do not insert or remove the CONFSTICK in a potentially explosive atmosphere.
By default upon delivery, all wireless modules have the same network ID and the same
RF band. Using a configuration memory (CONFSTICK), you can configure a unique and
secure network without the need for software.
The CONFSTICK is used as a network key. Its network address (network ID) is unique and
cannot be assigned via the PSI-CONF software. Only wireless modules with the same
network ID are allowed to connect with each other.
Each individual network device must be configured. Only one CONFSTICK is needed for all
wireless modules in the network. After configuration, remove the CONFSTICK from the
wireless module.
3827_en_BPHOENIX CONTACT71/138
Page 74
RAD-900-...
In addition, the CONFSTICK contains a preset frequency band (RF band). An RF band is a
group of frequencies compiled of individual frequencies of the entire 900 MHz band.
Different RF bands use different frequencies.
In order to operate several Radioline wireless systems, you should select different
RF bands.
Set different RF bands between 1 ... 8 and network IDs between 1 ... 127 using the PSICONF software (see page 75).
Figure 5-5Configuration via CONFSTICK
ItemDescription
1RAD-CONF-RF CONFSTICK
2Status LEDs
3SET button
1. Carefully insert the CONFSTICK with the 12-pos. IFS connector into the S port of the
wireless module.
2. Press the SET button on the wireless module for one second. Parameter read in is
started. Read in has been completed when the DAT LED lights up once. The new
parameters are activated.
3. Remove the CONFSTICK from the wireless module.
4. Repeat this process for each individual wireless module in the network.
72/138
PHOENIX CONTACT3827_en_B
Page 75
Configuration and startup
5.5Copying device settings via memory stick
To transfer the configuration of a wireless module to another wireless module, save the
configuration to a memory stick (RAD-MEMORY, Order No. 2902828).
WARNING: Explosion hazard when used in potentially explosive areas
Do not insert or remove the memory stick in a potentially explosive atmosphere.
Pay attention to the firmware version of the wireless modules before using the memory
stick. In order to ensure that a wireless module is capable of reading the memory stick, it
must have the same or later firmware version as the wireless module whose configuration
file is to be copied. Wireless modules with a lower firmware version are not able to read
the memory stick.
Common network parameters
–Operating mode
–Network ID
–RF band
–Data rate of the wireless interface
–Encryption
–Network type
Individual device parameters
–Station name
–RAD ID
–Transmission power
–List of permitted connections
–Serial interface parameters
5.5.1Saving parameters from the wireless module to the
memory stick
Copying common network parameters and individual device parameters to the memory
stick:
1. Press the SET button located on the wireless module and hold down for at least six
seconds.
2. The four RSSI bar graph LEDs start a light sequence from bottom to top.
3. Insert the memory stick in the S port of the wireless module. The copying of parameters
is started automatically.
4. Wait until the light sequence stops. The write process has been completed.
5. Remove the memory stick from the wireless module.
3827_en_BPHOENIX CONTACT73/138
Page 76
RAD-900-...
5.5.2Reading the memory stick
Reading in common network parameters via the memory stick
1. Insert the memory stick in the S port of the wireless module.
2. Press the SET button located on the wireless module and hold down for at least one
second. Parameter read in is started. Read in has been completed when the DAT LED
lights up once. The new parameters are activated.
3. Remove the memory stick from the wireless module.
Reading in common network parameters and individual device parameters via the
memory stick
This function enables all common network parameters and individual device parameters to
be read into the wireless module. A full copy of devices can be created, e.g., as a backup
copy.
1. Insert the memory stick in the S port of the wireless module.
2. Press the SET button located on the wireless module and hold down for at least six
seconds. Parameter read in is started, the DAT LED flashes.
3. The read in process has been completed once the DAT LED stops flashing. The new
parameters are activated.
4. Remove the memory stick from the wireless module.
If an error is detected while saving or checking the data, the DAT and ERR LEDs flash
simultaneously.
5.6Configuration via PSI-CONF software
You can make special settings using the PSI-CONF configuration and diagnostics software.
The software is available to download at
Windows operating system is required to use the software. Use the RAD-CABLE-USB
(Order No. 2903447) USB cable for configuration and diagnostics.
WARNING: Explosion hazard when used in potentially explosive areas
The USB cable must not be used in potentially explosive areas.
For additional information on the USB cable, please refer to the RAD-CABLE-USB
package slip. The latest documentation can be downloaded at
phoenixcontact.net/products.
Install the software and the USB driver for the RAD-CABLE-USB cable. Follow the software
wizard.
phoenixcontact.net/products. A PC with a
74/138
PHOENIX CONTACT3827_en_B
Page 77
Configuration and startup
5.6.1Extended configuration, individual settings
After reading an existing network project or creating a new project, the network settings can
be modified under “Individual Settings”. The wireless network can be optimized and
adapted to your special requirements. When moving the mouse over the individual network
parameters, you obtain a short description under “Help”.
If several wireless systems are operated parallel and in close proximity, you are required
to set the RF band and the network ID. These parameters can be set via the PSI-CONF
software or by using a CONFSTICK (see “Configuration via CONFSTICK” on page 71).
Figure 5-6PSI-CONF software: Network Settings
5.6.2Data transmission speed of the wireless interface
The range is an important parameter in industrial wireless applications, especially in
outdoor applications. Even in cases where long ranges do not have to be covered, good
receiver sensitivity enables transmission in harsh outdoor conditions, e.g., when there is no
direct line of sight.
The receiver sensitivity determines the signal amplitude which can just about be received
by the wireless module. The lower the data transmission speed of the wireless interface, the
higher the receiver sensitivity and thereby the range.
Adjust the data transmission speed of the wireless interface to the respective application
using the PSI-CONF software (default setting = 125 kbps).
3827_en_BPHOENIX CONTACT75/138
Page 78
RAD-900-...
Table 5-2Data transmission speed of the wireless interface
Data
transmission
speed
Typical receiver
sensitivity
Typical link
budget
Potential distance with line
of sight and a system
reserve of 12 dB
500 kbps-95 dBm-125 dBm12 km
250 kbps-102 dBm-132 dBm25 km
125 kbps-105 dBm-135 dBm35 km (default setting)
16 kbps-112 dBm-142 dBm80 km
Figure 5-7PSI-CONF software: Wizard, Step 3
Figure 5-8PSI-CONF software: Setting the data transmission speed
76/138
PHOENIX CONTACT3827_en_B
Page 79
Configuration and startup
5.6.3Device settings
In order to be able to cover the largest possible distances, the preamplifier has been
activated and transmission power set to 30 dBm by default. When operating the devices
directly next to one another, the receiver might become overloaded. In this case, remove
the antennas, increase the distance between the devices and antennas, or reduce
transmission power using the PSI-CONF software.
Assign a device name or set the transmission power under “Device Settings”. All device
parameters are listed on the “Overview” tab.
Depending on the operating mode, configure the serial interface under “Individual Settings”
on the “Serial Port” tab.
In I/O data mode (default upon delivery), both interfaces are deactivated. To activate the
serial interface, select the “Serial data,” “PLC/Modbus RTU mode,” or “PLC/Modbus RTU
dual mode” network application under “Network Settings”.
Only use one interface per wireless module. Parallel operation of both interfaces is not
possible.
3827_en_BPHOENIX CONTACT77/138
Page 80
RAD-900-...
Figure 5-10PSI-CONF software: Individual Settings, Serial Port
Define the wireless modules to which a connection may be established on the “Allowed
Parents” tab under “Individual Settings”. This setting is required, for example, when creating
repeater chains. Repeater chains are used to circumvent obstacles or to set up redundant
wireless paths by means of several repeaters.
The “Allowed Parents” tab is only available if the “Line/Mesh” network type has been
selected.
Several appropriate output modules at different stations can be assigned to one digital or
analog input module. The inputs are transmitted in parallel to the outputs. The channels of
the input module are mirrored to the channels of the output module.
It is not possible to separately assign the individual input channels of an extension module
to different output modules.
DI1L
DI1H
DI1
+24 V
0 V
DI2L
DI2H
DI2
RSSI
+
RSSI
-
ANT
SPORT
RAD-DI4-IFS
RAD-2400-IFS
PWR
PWR
8 8
0
1
DAT
DAT
IO-MAP
RAD-ID
ERR
ERR
DI1
Reset
DI2
DO1
DO2
RXTX
D(A)
D(B)
DI3L
DI3H
DI3
RX
GND
TX
CO
1
NC
1
DI4L
DI4H
DI4
CO
2
COM1
COM1
NO1
+24 V
0 V
COM2
NO2
RSSI
+
RSSI
-
ANT
OFF ON
1
2
3
SPORT
4
DIP-1
RAD-2400-IFS
PWR
PWR
8 8
0
1
DAT
DAT
RAD-ID
ERR
ERR
DI1
Reset
DI2
DO1
DO2
RXTX
D(A)
D(B)
COM3
RX
GND
NO3
TX
COM4
CO
1
NC
1
NO4
CO
2
NC1
NC2
NC3
NC4
RAD-DOR4-IFS
IO-MAP
NC1
NO1
+24 V
0 V
COM2
NC2
NO2
RSSI
+
RSSI
-
ANT
OFF ON
1
2
3
SPORT
4
DIP-1
RAD-2400-IFS
RAD-DOR4-IFS
PWR
PWR
8 8
0
1
DAT
DAT
IO-MAP
RAD-ID
ERR
ERR
DI1
Reset
DI2
DO1
DO2
RXTX
D(A)
D(B)
COM3
RX
NC3
GND
NO3
TX
COM4
CO
1
NC4
NC
1
NO4
CO
2
COM1
NC1
NO1
+24 V
0 V
COM2
NC2
NO2
RSSI
+
RSSI
-
ANT
OFF ON
1
2
3
SPORT
4
DIP-1
RAD-2400-IFS
RAD-DOR4-IFS
PWR
PWR
8 8
0
1
DAT
DAT
IO-MAP
RAD-ID
ERR
ERR
DI1
Reset
DI2
DO1
DO2
RXTX
D(A)
D(B)
COM3
RX
NC3
GND
NO3
TX
COM4
CO
1
NC4
NC
1
NO4
CO
2
Figure 5-12Assignment of digital inputs and digital outputs
The combined RAD-DAIO6-IFS extension modules can only be assigned in pairs, because
each module is provided with inputs and outputs. That is why only two modules in the
network may have the same I/O MAP address.
+24 V
0 V
DI1L
DI1H
DI1
RSSI
+
RSSI
-
DI2L
DI2H
DI2
ANT
UL1 +I1 -I1
OFF ON
1
2
3
SPORT
4
DIP-1
RAD-2400-IFS
RAD-DAIO6-IFS
PWR
PWR
0
1
1 2
DAT
DAT
RAD-ID
IO-MAP
ERR
ERR
DI1
Reset
DI2
DO1
RXTX
DO2
D(A)
D(B)
U1 I1
1
RX
GND
TX
COM1
NC1
NO1
1
CO
NC
1
CO
2
COM2
NC2
NO2
+24 V
0 V
DI1L
DI1H
DI1
RSSI
+
RSSI
-
DI2L
DI2H
DI2
ANT
UL1 +I1 -I1
OFF ON
1
2
3
SPORT
4
DIP-1
RAD-2400-IFS
RAD-DAIO6-IFS
PWR
PWR
0
1
1 2
DAT
DAT
RAD-ID
IO-MAP
ERR
ERR
DI1
Reset
DI2
DO1
RXTX
DO2
D(A)
D(B)
U1 I1
1
RX
GND
TX
COM1
NC1
NO1
CO
1
NC
1
CO
2
COM2
NC2
NO2
Figure 5-13RAD-DAIO6-IFS assignment: analog/digital inputs and outputs
5.7.2Setting the address of the extension modules via the
thumbwheel
For an I/O-to-I/O transmission of signals, assign a corresponding output module to the input
module. Set the I/O-MAP address (01 ... 99) using the white thumbwheel on the I/O
extension module.
Addressing extension modules
•Use the thumbwheel to set the address.
•Press the SET button on the front of the wireless module to read the current
configuration.
The following settings can be made using the white thumbwheel:
Thumbwheel
setting
01 ... 99I/O-MAP address
00Delivery state
**, 1* ... 9*Setting not permitted
*1 ... *9Interface System slave address, for use with other Interface System
The following conditions must be met:
–Assign a maximum of 1 ... 99 addresses to the extension modules in the entire wireless
network.
Description
(IFS) master devices
80/138
PHOENIX CONTACT3827_en_B
Page 83
Configuration and startup
Wireless module in I/O data mode
–The input module must be provided with the same I/O-MAP address as the assigned
output module at the other wireless station (I/O mapping). Output modules with the
same I/O-MAP address may appear several times in the network at different stations.
–The I/O-MAP address of an input module may only appear once in the network.
–The channels of the input module are directly assigned to the channels of the output
module:
Input moduleOutput module
Channel 1Channel 1
Channel 2Channel 2
......
It is not possible to individually assign the channels of the input and output modules.
Figure 5-14Input module and output module with the same address
Wireless module in PLC/Modbus RTU mode
–Output modules may not have the same I/O-MAP address as input modules. Exception:
Output modules with the same I/O-MAP address may appear several times in the
network at different stations.
–The I/O-MAP address of an input module may only appear once in the network.
–The input and output data is saved in a Modbus memory map in the master wireless
module. You can read or write the process data via the serial interface of the master
wireless module (RAD ID = 01) using the Modbus RTU command. The process data
tables can be found starting at “Modbus memory map” on page 100.
5.7.3Wireless module in PLC/Modbus RTU dual mode
–Each wireless module may be assigned a Modbus address. The master wireless
module Modbus address may be changed from 01 if an existing Modbus device is
already assigned this address. A Modbus address may only appear once in the
network.
–Output modules may not have the same I/O-MAP address as input modules on a single
wireless device (station). Exception: Output modules with the same I/O-MAP address
may appear several times at the same station.
3827_en_BPHOENIX CONTACT81/138
Page 84
RAD-900-...
–The input and output data is saved in a Modbus memory map in the wireless module.
You can read or write the process data via the serial interface of the master wireless
module (RAD ID = 01) using the Modbus RTU command. The process data tables can
be found starting at “Modbus memory map” on page 100.
5.8Starting up the RAD-900-DAIO6
5.8.1Setting the address of the RAD-900-DAIO6 via the thumb-
wheel
For an I/O-to-I/O transmission of signals, both the RAD ID and I/O-MAP address are set
using the yellow thumbwheel on the RAD-900-DAIO6.
Addressing extension modules
•Use the thumbwheel to set the address.
•Press the SET button on the front of the wireless module to read the current
configuration.
The following settings can be made using the yellow thumbwheel:
Thumbwheel
setting
01 ... 99RAD ID and I/O-MAP address
01Delivery state
**,
1* ... 9*,
*1 … *9
The following conditions must be met:
–Assign a maximum of 1 ... 99 addresses to the RAD-900-DAIO6 in the entire wireless
network. If the address is set to 01, the RAD-900-DAIO6 may only be used in point-to-
point mode with another RAD-900-DAIO6.
Wireless module in I/O data mode
The RAD-900-DAIO6 may be used to create a point-to-point or point-to-multipoint
connection with RAD-900-IFS devices. In this case, set the I/O-MAP address to between 02
and 99 using the white thumbwheel on the corresponding RAD-DAIO6-IFS extension
module(s) to match the yellow thumbwheel setting on the RAD-900-DAIO6.
–The I/O-MAP address of an input module may only appear once in the network.
–The input channels are directly assigned to the corresponding output channels at the
other wireless station.
Description
Settings not permitted
82/138
PHOENIX CONTACT3827_en_B
Page 85
Configuration and startup
–The RAD-900-DAIO6 may be used to create a point-to-point connection with another
RAD-900-DAIO6. In this case, one RAD-900-DAIO6 must have its address set to 01
and the other must be set to 02.
Figure 5-15Thumbwheel addressing of the RAD-900-DAIO6 in point-to-point mode
Wireless module in PLC/Modbus RTU mode
–Multiple RAD-900-DAIO6 devices may not use the same thumbwheel address in a
single network.
–The input and output data is saved in a Modbus memory map in the master wireless
module. You can read or write the process data via the serial interface of the master
wireless module (RAD ID = 01) using the Modbus RTU command. The process data
tables can be found starting at “Modbus memory map” on page 100.
5.8.2RAD-900-DAIO6 in PLC/Modbus RTU dual mode
–Each wireless module is assigned a Modbus address. The Modbus address of each
module is that of the RAD-ID (yellow thumbwheel) set on the module. The master
wireless module Modbus address may be changed from 01, if an existing Modbus
device is already assigned this address. A Modbus address may only appear once in
the network.
–Each RAD-900-DAIO6 device must use a unique thumbwheel address within a single
network.
–The input and output data is saved in a Modbus memory map in the wireless module.
You can read or write the process data via the serial interface of the master wireless
module (RAD ID = 01) using the Modbus RTU command. The process data tables can
be found starting at “Modbus memory map” on page 100.
3827_en_BPHOENIX CONTACT83/138
Page 86
RAD-900-...
5.9Startup time of the wireless station
Once a wireless station has been started (power “ON”), the wireless module will take
15 seconds to be ready for operation. Each linked I/O extension module increases the
startup time by 3 seconds.
Startup time of a wireless station = 15 seconds + (number of I/O modules x 3 seconds)
Accordingly, a complete wireless station with 32 I/O extension modules requires a startup
time of 111 seconds. Only after this period of time has elapsed is the wireless station ready
for operation.
84/138
PHOENIX CONTACT3827_en_B
Page 87
6Serial data mode (RAD-900-IFS only)
In serial data mode, multiple controllers or serial I/O devices are networked quickly and
easily using wireless technology. In this way, serial RS-232 or RS-485 cables can be
replaced.
Figure 6-1Serial data mode
Configure the serial interface of the RAD-900-IFS wireless module using the PSI-CONF
software. In order to connect the wireless module to the PC, you need the
RAD-CABLE-USB cable (Order No. 2903447).
Serial data mode (RAD-900-IFS only)
WARNING: Explosion hazard when used in potentially explosive areas
The USB cable must not be used in potentially explosive areas.
When operating the network in serial data mode, it may not be possible to diagnose all
devices. In this case, stop the serial application in order to allow for complete diagnostics.
Use PSI-CONF software to assign different serial settings to the devices under “Individual
Settings”.
3827_en_BPHOENIX CONTACT85/138
Page 88
RAD-900-...
•Start the PSI-CONF software.
•Follow the software wizard.
•Once you have run through all steps of the wizard, save the project and transmit it to the
wireless modules.
Figure 6-2PSI-CONF software: Wizard, Step 3
86/138
Figure 6-3PSI-CONF software: Wizard, Step 4
PHOENIX CONTACT3827_en_B
Page 89
Serial data mode (RAD-900-IFS only)
6.1Frame-based data transmission
T
The T
parameter (minimum pause between two frames)
IdleMin
parameter refers to the minimum pause that must elapse between two frames
IdleMin
on the output side (wireless module is transmitting data via serial interface).
Frame 1
Frame 2
Frame 3
IdleIdleIdle
T
idleMin
Figure 6-4Frame-based data transmission: T
T
FrameEnd
T
FrameEnd
parameter
is the time which is kept by the transmitting wireless module between two frames.
T
idleMin
IdleMin
T
idleMin
parameter
If the data received by the wireless module is followed by a certain period of time where no
further data is received, the wireless module assumes that the frame has arrived in its
entirety. The frame is then transmitted. This period of time is referred to as T
T
FrameEnd
(T
FrameEnd < TIdleMin
must be shorter than the minimum interval between two frames
). T
FrameEnd
must, however, also be greater than the maximum interval
FrameEnd
.
that is permitted between two characters in a frame. Otherwise the frame might be
fragmented.
Frame 1
OK
Frame 2
NOT OK
IdleIdleIdle
T
FrameEnd
Figure 6-5Frame-based data transmission: T
3827_en_BPHOENIX CONTACT87/138
FrameEnd
T
FrameEnd
parameter
Page 90
RAD-900-...
Setting telegram pauses, based on the example of Modbus/RTU
A frame is also referred to as a telegram. The length of the transmission pause between the
telegrams depends on the set data rate. The beginning and end of a telegram is recognized
by means of a time condition. A pause of 3.5 characters means that the telegram is
complete and the next character is to be interpreted as the slave address. A telegram must
therefore be sent as a continuous data flow. If there is an interruption of more than 1.5
characters within a telegram, the data will be discarded by the receiver.
If the master is not able to transmit the successive characters quickly enough and the
communication is aborted, you must increase the minimum pause time (T
FrameEnd
) between
the individual characters of a telegram. Frames with a length of 1480 characters can be
transmitted by the Radioline wireless system.
•In order to adapt data transmission to other protocols, it is possible to adapt the
T
FrameEnd
and T
parameters. Set the interface parameters under “Individual
IdleMin
Settings”.
88/138
Figure 6-6PSI-CONF software: Individual Settings
PHOENIX CONTACT3827_en_B
Page 91
7PLC/Modbus RTU mode
The PLC/Modbus RTU mode is available for firmware version 1.30 or later. If necessary,
start an update using the PSI-CONF software (version 2.03 or later).
Activate the PLC/Modbus RTU mode using the PSI-CONF software (from Section 5.6,
“Configuration via PSI-CONF software” onwards).
In PLC/Modbus RTU mode, you can read the I/O values of the extension modules connected to the wireless slave modules via the Modbus RTU protocol (I/O to serial). The wireless module provides an RS-232 or RS-485 interface for this purpose. In PLC/Modbus RTU
mode, the master wireless module works as a Modbus slave and has its own Modbus slave
address.
You can connect I/O extension modules to each wireless device in the network. A wireless
network can have a maximum of 99 extension modules. Use the white thumbwheel to set
the I/O-MAP addresses.
PLC/Modbus RTU mode
Figure 7-1PLC/Modbus RTU mode
3827_en_BPHOENIX CONTACT89/138
Page 92
RAD-900-...
7.1Configuration via PSI-CONF software
1. Start the PSI-CONF software (see Section 5.6, “Configuration via PSI-CONF soft-
ware”).
2. Create a new network project.
3. Follow the software wizard.
Figure 7-2PSI-CONF software: Wizard, Step 3
4. Select “PLC/Modbus RTU mode” and assign a Modbus address.
5. Follow the software wizard.
The Modbus address is a unique address in the Modbus network. It is only assigned to
the master wireless module (RAD ID = 01). Assign an address between 1 ... 247.
In order to enable the master wireless module to communicate with a controller via the
RS-232 or RS-485 interface, you must set the interface parameters. Please note that the
controller settings must match the settings of the wireless module.
Table 7-1Configuration via PSI-CONF software
ParameterPossible valuesDefault setting
Interface typeRS-232, RS-485RS-232
Data rate300 ... 115,200 bps19,200 bps
ParityNone, even, oddNone
Number of stop bits1; 21
Number of data bits88
Modbus address1 ... 2471
The Modbus connection between the controller and the wireless module can be monitored
via a watchdog. For additional information on the watchdog, refer to page 91.
90/138
PHOENIX CONTACT3827_en_B
Page 93
PLC/Modbus RTU mode
7.2Addressing I/O extension modules
In PLC/Modbus RTU mode, a wireless network can have a maximum of 99 I/O extension
modules.
Use the white thumbwheel on the I/O extension module to set the I/O-MAP address. You
can find information on addressing extension modules from “Setting the address of the extension modules via the thumbwheel” on page 80 onwards.
7.3Watchdog
The Modbus telegram watchdog monitors the connection between the master wireless
module and the controller. It is triggered each time a Modbus telegram is received correctly.
Activate the watchdog using the PSI-CONF software.
•Select the “Network Settings” item under “Individual Settings”. Set a watchdog time be-
If the watchdog is triggered, an action will be performed on the I/O output modules. You can
set this behavior in the event of an error using the DIP switches on the front.
–OFF = RESET: Output value is set to 0
–ON = HOLD: Hold last output value
For more detailed information regarding switch setting for the different extension modules,
please refer to Section 3, “Description of I/O extension modules”.
If the watchdog is activated and Modbus communication interrupted, the red ERR LED will
flash on all wireless modules in the network. Depending on the DIP switch settings, the output modules issue the corresponding hold or reset value.
3827_en_BPHOENIX CONTACT91/138
Page 94
RAD-900-...
92/138
PHOENIX CONTACT3827_en_B
Page 95
8PLC/Modbus RTU dual mode
PLC/Modbus RTU dual mode is available for firmware version 1.80 or later. You can
update the firmware free of charge using the PSI-CONF software, Version 2.33 or later.
The firmware and software can be found on the Internet at
Activate the PLC/Modbus RTU dual mode using the PSI-CONF software (from Section 5.6,
“Configuration via PSI-CONF software” onwards).
In PLC/Modbus RTU dual mode, you can read the I/O values of the extension modules
connected to the wireless slave modules via the Modbus RTU protocol (I/O to serial). In
addition, serial Modbus devices can be connected over the wireless network. The master
wireless module provides an RS-232 or RS-485 interface to a Modbus RTU master.
In PLC/Modbus RTU dual mode, all the wireless modules work as Modbus slaves and have
unique Modbus slave addresses. The Modbus ID of each wireless module is set using the
yellow thumbwheel.
You can connect I/O extension modules to each wireless device in the network. A wireless
station can have a maximum of 32 extension modules. Use the white thumbwheel to set the
I/O-MAP addresses.
PLC/Modbus RTU dual mode
phoenixcontact.net/products.
Figure 8-1PLC/Modbus RTU dual mode
3827_en_BPHOENIX CONTACT93/138
Page 96
RAD-900-...
8.1Configuration via PSI-CONF software
1. Start the PSI-CONF software (see Section 5.6, “Configuration via PSI-CONF
software”).
2. Create a new network project.
3. Follow the software wizard.
Figure 8-2PSI-CONF software: Wizard, Step 3
4. Select “PLC/Modbus RTU dual mode” and assign a Modbus address.
5. Follow the software wizard.
The Modbus address is a unique address in the Modbus network. Assign an address
between 1 ... 247.
In order to enable the master wireless module to communicate with a controller via the
RS-232 or RS-485 interface, you must set the interface parameters. Please note that the
controller settings must match the settings of the wireless module.
Table 8-1Configuration via PSI-CONF software
ParameterPossible valuesDefault setting
Interface typeRS-232, RS-485RS-232
Data rate300 ... 115,200 bps19,200 bps
ParityNone, even, oddNone
Number of stop bits1; 21
Number of data bits88
Modbus address1 ... 2471
The Modbus connection between the controller and the wireless module can be monitored
via a watchdog. For additional information on the watchdog, refer to page 95.
94/138
PHOENIX CONTACT3827_en_B
Page 97
PLC/Modbus RTU dual mode
8.2Addressing I/O extension modules
In PLC/Modbus RTU dual mode, a wireless station can have a maximum of 32I/O extension
modules.
Use the white thumbwheel on the I/O extension module to set the I/O-MAP address. You
can find information on addressing extension modules from “Setting the address of the
extension modules via the thumbwheel” on page 80 onwards.
8.3Watchdog
The Modbus telegram watchdog monitors the connection between the master wireless
module and the controller. It is triggered each time a Modbus telegram is received correctly.
You can activate the watchdog using the PSI-CONF software.
•Select the “Network Settings” item under “Individual Settings”. Set a watchdog time
If the watchdog is triggered, an action will be performed on the I/O output modules. You can
set this behavior in the event of an error using the DIP switches on the front.
–OFF = RESET: Output value is set to 0
–ON = HOLD: Hold last output value
For more detailed information regarding switch setting for the different extension modules,
please refer to Section 3, “Description of I/O extension modules”.
If the watchdog is activated and Modbus communication interrupted, the red ERR LED will
flash on all wireless modules in the network. Depending on the DIP switch settings, the
output modules issue the corresponding hold or reset value.
3827_en_BPHOENIX CONTACT95/138
Page 98
RAD-900-...
96/138
PHOENIX CONTACT3827_en_B
Page 99
Addressing I/O extension modules and RAD-900-DAIO6 with Modbus RTU
9Addressing I/O extension modules and RAD-900-DAIO6
with Modbus RTU
9.1Modbus function codes
In the Modbus protocol, the function codes define which data is to be read or written. With
a single request, the registers 1 ... 123 can be read or written.
Table 9-1Supported Modbus function codes
Code numberFunction codeDescription
fc 03Read Holding RegisterRead process output data
(address area 40010 ... 40999)
fc 04Read Input RegisterRead process input data
(address area 30010 ... 30999)
fc 16Write Multiple Registers Write multiple output registers word by word
Other function codes exist in the Modbus protocol, but they are not supported.
9.2Modbus protocol
The data is transmitted using the Modbus/RTU (Remote Terminal Unit) protocol. Communication takes place according to the master/slave method. The Modbus master initiates
communication with a request to the slave. If the slave detects that its address has been accessed by the master, the slave always sends a response.
Only the master is able to initiate communication. The slaves are not able to initiate communication and do not communicate with each other.
The connected extension modules write the analog or digital input and output values to an
internal register. The Modbus master (e.g., a PLC) can read the individual registers using
the Modbus address of the slaves. The data to be transmitted is always included in a defined frame. The frame is referred to as telegram.
The Modbus protocol defines the format of the telegrams. If an error occurs when the telegram is received on the slave side, or if the slave is unable to carry out the master request,
an error telegram is sent back to the master.
3827_en_BPHOENIX CONTACT97/138
Page 100
RAD-900-...
Request from master
The function code in the request informs the addressed slave which action is to be carried
out. The address and data bytes contain all additional information that the slave requires in
order to carry out the action.
Example: The master uses function code 03 to request the slave to read the process output
data and send its content to the master. The data and address bytes need to include the following information: from which register reading should start and how many registers should
be read. Using the CRC check value, the slave is able to detect whether the complete telegram has been received.
Response from slave
If the response from a slave is valid, the function code will match the request from the master. The address and data field contains the data recorded by the slave (e.g., register values).
The function code is modified in the event of an error. The address and data field then contains a code that describes the error. By using the CRC check value, the master is able to
determine whether the telegram content is valid or not.
The Modbus/RTU telegrams are separated by telegram pauses known as end-of-frame
times. The end-of-frame time must be at least 3.5 x as long as the time required for one
transmitted character. The end-of-frame time cannot be changed.
Table 9-2Modbus protocol: structure of telegrams (frames)
FrameDescriptionSize
Slave addressSlave address, valid area 1 ... 2478 bits
Function codeDefinition whether the parameter is to be read or writ-
ten
AddressRegister address16 bits
Data–E.g., from the master: Which parameters are
requested?
–E.g., from the slave: Content of the requested
parameters
CRC (Cyclic
Redundancy Check)
Test value for the cyclic redundancy check in order
to detect errors in data transmission
8 bits
N x 16 bits
16 bits
9.3Addressing registers
Function code 04
You must enter 0000 (hex0000) as the start address in order to read register 30001. The
address area 3xxxx is already defined by the function code field.
Function codes 03 and 16
In order to read/write registers 40032 ... 40039, you must enter 0031 (hex001F) as the start
address. The address area 4xxxx is already defined by the function code field.
98/138
PHOENIX CONTACT3827_en_B
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.