Phoenix Contact QUINT-DC-UPS/24DC/40 User Manual

Page 1
1.
Short Description
Uninterruptib
le Power Supply Units for Buffering
Long-Term Power Interruptions
Saves space thanks to the compact, uniform design
• Integrated diode saves money through isolation of loads
• Maximum system availability through optimum battery management and reliable signaling
• Minimum installation time due to ready-to-use plug-in bridges and integrated timeout QUINT-DC-UPS uninterruptible power supply units
with long-life lead-acid batteries provide long buffer times at high currents. Even in the event of a longer supply voltage failure, the units ensure that all connected devices continue to operate without interruption.
The devices have a narrow and uniform design,
which makes them ideal for use on the DIN rail where space is limited. In addition, short wiring paths ensure order and clarity in the control cabinet.
The high level of availability and the particularly long
service life of the battery modules are achieved through professional battery management. An automatic presence check (every minute), automatic quality test (once a week), temperature-determined charging, and electronic overcurrent protection ensure the battery modules are ready to operate at all times. Power is therefore available in the event of an error and the service life of the battery module is maximized.
The actual state must be determined quickly so that
the right decision can be made in an emergency. Optimum signaling is thus required for maximum system availability. Three oating PDT contacts and three LEDs are provided for function monitoring, which indicate all the operating states clearly.
So that relay signaling is more reliable and more
durable than before, an additional positive supply output has been provided. The contact, which is current-limited and resistant to continued short circuits, is located next to the relay connections and enables easy bridging. In the event of wiring errors, the short­circuit protection prevents any welding of the relay contacts. This ensures that the user can rely on an OK signal. Even in the event of connection errors, currents remain below 100 mA, which prevents damage to the relay contacts.
A system is switched off after a specic time that can be set on the device or by an external signal. No additional installation is required for shutdown. In addition, ready-to-use plug-in bridges minimize the installation time.
The connected devices can be divided into buffered and unbuffered loads using the isolated input. This extends the buffer time, which depends on the output current. If only critical devices are protected using fuses, smaller battery modules can be used that save money and space in the control cabinet. In addition, the isolated input protects the connected devices against errors in the internal network.
Uninterruptib
le Power Supply Unit
for Universal Use QUINT-DC-UPS/24DC/40
Headquar
ters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
Phone +49 - 52 35 - 30 0 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com
Local Contact: www.phoenixcontact.com/salesnetwork
Page 2
PHOENIX CONTACT page 2 of
9
Solid
Str
anded
T
orque
[mm2]
A
WG
[Nm] [lb in]
Input
0.5 - 16
0.5 - 10
20 - 6
1.2 - 1.5
10.6 - 13.3
Output
0.5 - 16
0.5 - 10
20 - 6
1.2 - 1.5
10.6 - 13.3
Signal
0.2 - 2.5
0.2 - 2.5 25 - 14
0.5 - 0.6
4.5 - 5.3
Descr
iption
Uninterr
uptib
le power suppl
y unit
3.4 Ah batter
y module
7.2 Ah batter
y module
12 Ah batter
y module
Technical Data Input Data
Nominal input v
oltage
Input v
oltage r
ange
Current consumption (No load/charging/maxim
um) Switching threshold Buff
er time Can be con
gured Input fuse Maxim
um power dissipation (Ready/b
uff
er mode)
Output Data
Can be connected in par
allel (batter
y module)
Output Data in Normal Operation
Nominal output v
oltage
Output v
oltage Output current Current limit Overload fuse
Output Data in Buff
er Mode
Nominal output v
oltage
Output v
oltage Maxim
um Output current Current limit Overload fuse Level of ef
ciency Typical
Remote shutdo
wn
Char
ging
Charge char
acter
istic curve
End-of-charge v
oltage Charge current Batter
y/presence chec
k/time interval
Batter
y/quality test/time interval
Memor
y Medium
Nominal v
oltage Nominal capacity Charge current
Q
UINT
-DC-UPS/24DC/40
DC UPS Module
U u F
T
ype
Or
der No.
Pcs.
Pkt.
Q
UINT
-DC-UPS/24DC/40
Q
UINT-BA
T/24DC/3,4Ah
Q
UINT-BA
T/24DC/7,2Ah
Q
UINT-BA
T/24DC/12Ah
28 66 24 2 28 66 34 9 28 66 35 2 28 66 36 5
1
24
V DC
22.5 - 30
V DC
0.1 A/2.5 A/42.5 A Ua < 22 V;
dynamic Uin - 1
V/0.1 s
0.5;
1;
2;
3;
10;
15;
20;
30;
contin
uous
Inter
nal, 50 A
20
W/30
W
Yes, to increase the b
uff
er time
24
V DC
U
in
40 A None Inter
nal, 50 A
24
V DC
27.9
V DC
40 A (25 A f
or 3.4 Ah batter
y module) 45 A Electronic 98% Y
es
I/U char
acter
istic curve
T
emper
ature compensated < 2.5 A 60 seconds 180 hours
Exter
nal
24
V DC
3.4 Ah, 7.2 Ah, 12 Ah < 2.5 A
130 mm
(5.118 in.)
66 mm
(2.598 in.)
125 mm (4.921 in.)
1 1
1 2
1 3
t . .. [ m i n ]
J
+ 2 4 V 2 0 0 m A
O u tp u t 0 - 2 0 A D C
2 1
2 2
2 3
3 1
3 2
3 3
A la r m
B a t . M o d e
C h a r g e
I n p u t
D C 2 4 V
2 x 1 2V
+
-
B a t . - S e le c t [ A h ]
B a t t e r y
R e m o te
O n /O f f
R 1
R 2
Uninterruptib
le Power Suppl
y Unit f
or Univer
sal Use – Q
UINT
-DC-UPS/24DC/40
2. Technical Data
7 mm (0.28 in.)
L [mm]
10 mm (0.39 in.)
Page 3
PHOENIX CONTACT page 3 of
9
Uninterruptib
le Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
Green LED Red LED
,
oating PDT
,
30
V A
C/DC
, maxim
um; 1 A, maximum Yellow LED, oating PDT, 30 V AC/DC, maximum; 1 A, maximum Yellow LED, ashing, oating PDT, 30 V AC/DC, maximum; 1 A, maximum
EN 60 204 (Surge Voltage Category III) EN 60950/VDE 0805, UL/C-UL Recognized UL 60 950 UL/C-UL Listed UL 508 Germanischer Lloyd EN 50 178/VDE 0160
1 kV AC type test 1 kV AC routine test On a horizontal 35 mm (1.378 in.) DIN rail EN 60 715 1 kV/1 kV IP20 II > 500,000 h AluNox (AlMg1), closed (66 x 130 x 125 mm [2.598 x 5.118 x 4.921 in.]) (122 x 130 x 69 mm [4.803 x 5.118 x 2.717 in.])
0.9 kg
-25°C to +70°C (-13°F to +158°F)/-40°C to +85°C (-40°F to +185°F) 95%, no condensation 15 - 150 Hz, 2.3g, 90 minutes
30g 2 3K3
Requirements EN 61 000-6-2
QUINT-DC-UPS/24DC/40
4 kV 8 kV
Level 4 8 kV 15 kV
80 -1000 MHz 10 V/m
Level 3 80 - 1000 MHz/1.4 - 2.0 GHz 10 V/m
2 kV asymmetrical
5)
2 kV asymmetrical
5)
1 kV asymmetrical
5)
4 kV (Level 4) 2 kV (Level 3) 1 kV (Level 2)
2 kV asymmetrical
5)
2 kV symmetrical
4)
0.5 kV asymmetrical
5)
0.5 kV symmetrical
4)
1 kV asymmetrical
5)
4 kV (Inst. Class 4) 2 kV (Inst. Class 4)
0.5 kV/(Level 1)
0.5 kV/(Level 1) 1 kV/(Level 2)
asymmetrical
5)
0.15 - 80 MHz 10 V
Level 3
0.15 - 80 MHz 10 V
30% reduction of the input voltage for 0.5 periods
See Input Data: Mains buffering > 20 ms
Class A
6)
Class A
6)
EN 55011 (EN 55022) Class B
7)
EN 55011 (EN 55022) Class B
7)
4)
Symmetrical: Cable to cable.
5)
Asymmetrical: Cable to ground.
6)
Class A: Industrial applications
7)
Class B: Industrial and domestic applications
Signaling
Power In OK Alarm
Battery Mode
Battery Charge
Approvals/Standards
Electrical equipment of machines Electrical safety (of IT equipment)
Industrial control equipment Shipbuilding Electronic equipment for use in electrical power installations
General Data
Insulation voltage
Input/output to housing:
Mounting position
Degree of protection Class of protection MTBF According to IEC 1709 (SN 29 500) Housing version Dimensions (W x H x D) default upon delivery Dimensions (W x H x D) rotated 90° Weight Approximately
Climatic Data
Ambient temperature Operation/storage Humidity At +25°C (+77°F) Vibration According to IEC 68-2-6
Shock (in all space directions) According to IEC 68-2-6 Pollution degree According to EN 50 178 Climatic category According to EN 60 721
cc
cc
Conformance With EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility) Noise Immunity According to EN 61000-6-2:
Noise Immunity According to EN 61000-6-2
• EN 61000-4-2
3)
Electrostatic discharge (ESD)
Housing
Contact discharge:
Air discharge:
• EN 61000-4-3
2)
Electromagnetic HF eld
Housing
Frequency:
Field strength:
• EN 61000-4-4
3)
Fast transients (burst):
Input:
Output:
Signal:
• EN 61000-4-5
3)
Input:
Surge current loads (surge):
Output:
Signal:
• EN 61000-4-6
2)
Conducted interference
I/O/S:
Frequency:
U0:
• EN 61000-4-11
3)
Voltage dips
Input:
Noise Emission According to EN 50081-2
• Radio interference emission EN 55011
• Radio interference voltage EN 55011
EN 55011 corresponds to CISPR11/EN 55022 corresponds to CISPR22/EN 61000 corresponds to IEC 1000
2)
Criterion A: Normal operating characteristics within the
specied limits.
3)
Criterion B: Temporary adverse effects on the operating
characteristics that the device corrects automatically.
Page 4
PHOENIX CONTACT page 4 of 9
11
11
DC input, unbuffered 24 V DC input voltage (0.5 mm2 to 16 mm2 solid) (0.5 mm2 to 10 mm2 stranded) (20 - 6 AWG) Internal fuse 50 AT
22
22
DC output, buffered 24 V DC output voltage (0.5 mm2 to 16 mm2 solid) (0.5 mm2 to 10 mm2 stranded) (20 - 6 AWG) The device is idling-proof and short-circuit-proof.
3333 24 V battery module connection 44
44
Floating PDT (11,12,13): Alarm
55
55
Floating PDT (21,22,23): Battery Mode
66
66
Floating PDT (31,32,33): Battery Charge
77
77
24 V supply voltage, maximum current limit 0.2 A
for grouped contacts 11, 21, 31
88
88
Remote shutdown (R1, R2)
99
99
Universal DIN rail adapter UTA 107
00
00
Red LED: Alarm
!!
!!
Yellow LED: Battery Mode/Battery Charge
" Green LED: Power In OK
§§§§ Buffer time setting 0.5 - 30 minutes $$
$$
Battery module/Service setting selection
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
3. Device View, Connections, and Control Elements
4. Safety Notes and Warning Instructions
To ensure that the device can be operated safely and all functions can be used, please read these instructions carefully.
The QUINT-DC-UPS is a built-in device. Installation and startup must only be carried out by qualied
personnel. The relevant country-specic regulations (e.g., VDE, DIN) must also be observed.
Before startup it is particularly important to ensure that:
• All supply lines have sufcient fuse protection and
are the correct size.
• All output cables are the correct size for the maximum
device output current or have separate fuse
protection.
• Sufcient convection is ensured.
• The fuse on the battery module is always removed
when carrying out any work.
Figure 04
+ –
DC 24 V 40 A
Input Output
3 14
DC
OK
+ +
DC
OK
+ +
DC
OK
+ +
+ –
+24V 0,2A
11 21
12 13 2
11 Alarm
Bat.-Mode Bat.-Charge
QUINT-DC-UPS/24DC/40 Order-No.: 28 66 24 2 Input: Operational Voltage: Output:
24VDC/43A
22.5-30VDC 24VDC/40A
APPROVALS
Read installation instructions before connecting
- 25 … + 70 °C
- 13 … + 158
°F
EN 61000-6-2 EN 50081-1
www.interface.phoenixcontact.com
U
INDUSTRIAL CONTROL EQUIPMENT 43KA
LISTED
2
5
F
Alarm
Power In OK
QUINT DC-UPS 40 A
Bat.-Mode
Bat.-Charge
Battery
3 1 4
DC
OK
+ + –
Alarm
Power In
OK
+ –
31 R1 R2
2 23 32 33
21 Bat.­Mode
31 Bat.­Charge
R1 R2 Remote
OFF
ON
10
15
5
3
2
1
0,5
20
30
t
max
[min]
Service
3,4
12
7,2
Bat.-Select
[Ah]
77
77
55
55
44
44
11
11
22
22
33
33
66
66
88
88
99
99
$$
$$
§§
§§
""
""
!!
!!
00
00
Page 5
PHOENIX CONTACT page 5 of 9
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
5. Installation
5.1. Mounting
The uninterruptible power supply unit together with the battery module can be snapped onto all DIN rails according to EN 60715 and should be mounted horizontally (input terminal blocks facing downwards).
Installation Dimensions
No minimum spacing to other modules is required for proper operation of the device.
5.2. Narrow Mounting Position
The device is supplied ex works for a narrow mounting position.
Mounting:
Place the module with the DIN rail guideway on the
top edge of the DIN rail and then snap it downwards. Removal:
Release the snap-on catch using a screwdriver and then detach the module from the bottom edge of the DIN rail.
5.3. Flat Mounting Position
A at mounting position can be achieved by mounting the module onto the DIN rail at a 90° angle. To do this, mount the DIN rail adapter (UTA 107) 7777 as shown in Figure 07. No additional assembly material is required. Mounting screws: Torx T10 (torque 0.8 - 0.9 Nm).
+ –
D
C
24 V
20
A
In
pu
t O
u
tput
3 14
DC
OK
+ +
DC
OK
+ +
DC
OK
+ +
+ –
+24V 0,2A
11 21
12 13 2
11 Alarm
Bat.-Mode Bat.-Charge
QUINT-DC-UPS/24DC/20 Order-No.: 28 66 23 9 Input: Operational Voltage: Output:
24VDC/22A
22.5-30VDC 24VDC/20A
APPROVALS
Read installation instructions before connecting
- 25 … + 70
°C
- 13 … + 158
°
F
EN 61000-6-2 EN 50081-1
www.interface.phoenixcontact.com
U
INDUSTRIAL CONTROL EQUIPMENT 43KA
LISTED
–25
F
Alarm
Power In OK
QUINT DC-UPS 20 A
Bat.-Mode
Bat.-Charge
B
attery
3 14
DC
OK
+ + –
Alarm
Power In
OK
+ –
31 R1 R2
2 23 32 33
21 Bat.- Mode
31 Bat.- Charge
R1 R2 Remote
OFF ON
10
15
5
3
2
1
0,5
20
30
t
max
[min]
Service
3,4
12
7,2
Bat.-Select
[Ah]
+ –
D
C
24 V
40
A
In
pu
t O
u
tput
3 14
DC
OK
+ +
DC
OK
+ +
DC
OK
+ +
+ –
+24V 0,2A
11 21
12 13 2
11 Alarm
Bat.-Mode Bat.-Charge
QUINT-DC-UPS/24DC/40 Order-No.: 28 66 24 2 Input: Operational Voltage: Output:
24VDC/43A
22.5-30VDC 24VDC/40A
APPROVALS
Read installation instructions before connecting
- 25 … + 70
°C
- 13 … + 158
°
F
EN 61000-6-2 EN 50081-1
www.interface.phoenixcontact.com
U
INDUSTRIAL CONTROL EQUIPMENT 43KA
LISTED
–25
F
Alarm
Power In OK
QUINT DC-UPS 40 A
Bat.-Mode
Bat.-Charge
B
attery
3 14
DC
OK
+ + –
Alarm
Power In
OK
+ –
31 R1 R2
2 23 32 33
21 Bat.­Mode
31 Bat.­Charge
R1 R2 Remote
OFF ON
10
15
5
3
2
1
0,5
20
30
t
max
[min]
Service
3,4
12
7,2
Bat.-Select
[Ah]
Figure 05
Mounting
Removal
Figure 06
Figure 07
Page 6
PHOENIX CONTACT page 6 of 9
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
QUINT-DC-UPS
Power Supply
+
AC
DC
Unbuffered
Load
+
DC
Buffered
Load
Input Output
Battery
+
+
+
+
QUINT-BAT/24DC
+
+ –
D
C
24 V
40 A
Inp
ut O
utpu
t
3 14
DC
OK
+ +
DC
OK
+ +
DC
OK
+ +
+ –
+24V 0,2A
11 21
12 13 2
11 Alarm
Bat.-Mode Bat.-Charge
QUINT-DC-UPS/24DC/40 Order-No.: 28 66 24 2 Input: Operational Voltage: Output:
24VDC/43A
22.5-30VDC 24VDC/40A
APPROVALS
Read installation instructions before connecting
- 25 … + 70 °C
- 13 … + 158 °F
EN 61000-6-2 EN 50081-1
www.interface.phoenixcontact.com
U
INDUSTRIAL
CONTROL EQUIPMENT 43KA
LISTED
–25
F
Alarm
Power In OK
QUINT DC-UPS 40 A
Bat.-Mode
Bat.-Charge
B
attery
3 1 4
DC
OK
+ + –
Alarm
Power In
OK
+ –
31 R1 R2
2 23 32 33
21 Bat.­Mode
31 Bat.­Charge
R1 R2 Remote
OFF ON
10
15
5
3
2
1
0,5
20
30
t
max
[min]
Service
3,4
12
7,2
Bat.-Select
[Ah]
Figure 09
5.4. Connection
The following cable cross sections can be connected:
For reliable and safe-to-touch
connections: Strip 10 mm (0.39 in.)
from the input and output side connector ends and 7 mm (0.28 in.) from the signal connector ends.
To maintain UL approvals, use copper cables, which
are designed for operating temperatures > +75°C (+167°F). To meet GL requirements, unused terminal compartments should be closed.
5.5. Input (1111, Figure 04, Figure 08)
The QUINT-DC-UPS is connected to the 24 V DC output of the power supply via the "Input +" and "Input -" terminal blocks. The output is isolated from the input by the internal diode. The stored power is only supplied to the output. The device is protected against overcurrent and short circuit by an internal input fuse.
Fuse
Further device protection is not required, as an internal fuse is present.
Solid
[mm2]
Stranded
[mm2]
AWG Torque
[Nm]
11
11
Input:
0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5
22
22
Output:
0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5
33
33
Battery:
0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5
4444 ----
-88
88
Signal:
0.2 - 4 0.2 - 2.5 25 - 14 0.5 - 0.6
l
If the internal fuse is blown, this is most probably due to a device fault. In this case, the device should be checked in the factory.
Figure 08
Page 7
PHOENIX CONTACT page 7 of 9
5.6. Output
All devices that must be supplied without interruption in the event of a supply voltage failure ("Buffered Load"), are connected to the "Output +" and "Output -" terminal blocks of the DC output (Fig. 08). It is recommended that all other loads, which do not require buffering ("Unbuffered Load"), are connected to the 24 V DC output of the power supply.
This increases the buffer time, as this time depends on the output current (see Fig. 10). The internal diode ensures that the buffered loads are isolated from the unbuffered loads.
5.7. Battery Module
The battery module is connected to the QUINT-DC-UPS via the "Battery +" and "Battery -" terminal blocks. To interrupt the charge/discharge current of the battery module, the "Battery module selection" selector switch
$ must be set to "Service".
The fuse on the battery module must be removed when installing or replacing the battery module.
The QUINT-DC-UPS is optimized for use with QUINT-BAT/24DC type battery modules. The following battery modules are recommended:
QUINT-BAT/24DC/3,4AH (Order No. 2866349)
QUINT-BAT/24DC/7,2AH (Order No. 2866352)
QUINT-BAT/24DC/12AH (Order No. 2866365)
When using QUINT-BAT/24DC/3,4AH, the maximum output current of 25 A must not be exceeded. Following successful installation, the capacity of the connected battery module must be selected using the "Battery module selection" rotary switch
$.
5.8. Signaling Outputs
The signal outputs are connected via terminal blocks 11/12/13
4, 21/22/23 5 or 31/32/33 6. The contacts
are oating contacts. The plug-in bridge provided can be used to supply +24 V to grouped contacts 11,21,31. This means that N/C contacts 12,22,32 and N/O contacts 13,23,33 can be evaluated as switching outputs with 0 V and +24 V voltage levels.
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
40 A
O
utput
+ –
Bat.-Mo
de
Bat.-Charge
AP
PRO
R b
e
U
IN
C
ONT
EQUI
P
43KA
LISTED
Power In OK
Mo
de
at
.-
C
harge
Battery
Power In
OK
+ –
10
15
5
3
2
1
0,5
20
3
0
t
max
[min]
Service
3,4
12
7,2
Bat.-Select
[Ah]
$$
$$
Figure 11
10
30
20
40 35
25
15
5 0
30 60 90 120
3.4 Ah
7.2 Ah
12 Ah
Current [A]
Time [min.]
Figure 10
Page 8
PHOENIX CONTACT page 8 of 9
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
5.9. Remote Shutdown ("Remote", Fig. 12)
The device has a UPS remote shutdown function for specic shutdown. Remote shutdown must be deactivated for the device to switch to buffer mode in the event of a supply voltage failure.
Remote Shutdown Off
• The "Remote shutdown R1" and "Remote
shutdown R2" terminal points are short circuited
(e.g., with a plug-in bridge) OR
The "Remote shutdown R2" terminal point is
supplied with a 24 V DC voltage
• The QUINT-DC-UPS switches to buffer mode in the
event of a supply voltage failure
Remote Shutdown On
• The "Remote shutdown R1" and "Remote
shutdown R2" terminal points are not connected
• All LEDs are off
• The QUINT-DC-UPS does not switch to buffer mode
in the event of a supply voltage failure, instead the
device is shut down. When the supply voltage is
reapplied, the battery module is charged and the
device remains off until remote shutdown is
deactivated.
• Connected loads are supplied as long as the supply
voltage is present
6. Setting Options on the Device
(Fig. 13)
6.1. Buffer Time Setting
Buffer mode can be exited after a predened time has elapsed or by external shutdown (see 6.9). If the device is to be shut down after a specic time has elapsed, the time can be set via the selector switch § on the front of the device. When the supply voltage is reapplied, the device can switch to buffer mode again.
6.2. Battery Module Setting
Before startup, the capacity of the battery module used must be set on the device via the selector switch $. When replacing the battery, the selector switch must be set to "Service" (see also 6.7).
40 A Output
+ –
Bat.-Mode Bat.-Charge
Alar
m
Power In OK
Bat.-Mode
Bat.-Charge
Battery
rm
Power In
OK
+ –
10
15
5
3
2
1
0,5
2
0
3
0
t
max
[min]
Service
3,4
12
7,2
Bat.-Select
[Ah]
$$
$$
§§
§§
Figure 13
3 14
DC
OK
+ +
DC
OK
+ +
DC
OK
+ +
0,2A
11 21
12 13 2
11 Alarm
.-Mode
rge
QUI Ord
e
Inp
u
Op
e
Out
p
P
P
Alarm
Bat.-Mode
Bat.-Cha
rge
3 14
DC
OK
+ + –
Alarm
31 R1 R2
2 23 32 33
21 Bat.­Mode
31 Bat.­Charge
R1 R2 Remote
OFF
ON
88
88
Figure 12
Page 9
PHOENIX CONTACT page 9 of 9
7. Method of Operation
In the event of a power failure at the output, the QUINT-DC-UPS supplies all connected devices with a 24 V DC voltage without interruption at a load current up to 40 A. When the 24 V supply voltage is applied, the connected battery module is charged. In the event of a supply voltage failure, the battery module is connected to the output, and the stored power ensures that all connected devices continue to operate without interruption. The professional signaling via function LEDs and oating PDT contacts enables reliable evaluation of all the main operating states.
7.1. Output Voltage
In normal operation, the QUINT-DC-UPS output voltage corresponds to the usual supply voltage. If the supply
voltage drops more than 1 V in the space of 0.1 seconds or falls below the minimum threshold of 22 V, the device switches to buffer mode. If the output voltage drops below 20.4 V in buffer mode, this is indicated by the Alarm indicator. If the output voltage drops to 19.2 V because the battery module is at, the device is shut down completely. When the supply voltage is reapplied, the device automatically switches on again. The device is electronically short-circuit-proof and idling-proof.
7.2. Signaling
Three oating PDT contacts and three indicators are provided for function monitoring.
xx - xx: Contact closed, 1x Alarm, 2x Battery Mode, 3x Battery Charge x1 group contact, x2 N/C contact, x3 N/O contact
7.3. Temperature Response
The charging rate of the connected battery module depends on the temperature.
7.4. Testing the Battery Module
A quality test is carried out on the battery module once a week and its presence is veried every minute. A negative test result is indicated by the Alarm indicator.
Key/Indicators Green "“
Power IN OK
Yellow !
Bat. Mode/Charge
Red 0
Alarm Supply voltage OK, battery module charging
ON Flashing OFF
Supply voltage OK, battery module charged (normal operation)
ON OFF OFF
Buffer mode OFF ON OFF
Battery module at OFF OFF ON
- Battery module quality test negative
- No battery module
- Service
ON OFF ON
- Buffer time elapsed
- Remote shutdown activated
OFF OFF OFF
Key/Output Bat. Charge
6
Bat. Mode
5
Alarm
4
Supply voltage OK, battery module charging
31 - 33 21 - 22
Supply voltage OK, battery module charged (normal operation)
31 - 32 21 - 22
Buffer mode 31 - 32 21 - 23
Battery module at 31 - 32 21 - 22 11 - 13
- Battery module quality test negative
- No battery module
- Service
31 - 32 21 - 22 11 - 13
- Buffer time elapsed
- Remote shutdown activated
21 - 22 11 - 13
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
PHOENIX CONTACT 05/01/05 TNR:101997-00-gb http://www.phoenixcontact.com
Loading...