Phoenix Contact QUINT4-PS/1AC/24DC/20, QUINT4-PS/1AC/48DC/5, QUINT4-PS/3AC/24DC/20 Datasheet

1Description

Power supply unit
QUINT4-PS/1AC/24DC/20
© PHOENIX CONTACT
Data sheet
QUINT POWER power supplies with SFB Technology and preventive function monitoring ensure superior system availability.
Powerful
SFB technology: 6 times the nominal current for 15ms Power reserves:
Static boost of up to 125%(P
N
) for a sustained period
Dynamic boost of up to 200%(PN) for 5s
Robust
–Mains buffering 20ms High degree of electrical immunity, thanks to integrated
gas-filled surge arrester (6kV)
Preventive
Comprehensive signaling:
Analog signal, digital signal, relay contact, LED bar graph
Can be ordered pre-configured
Perform configuration online and order 1 or more units
Technical data (short form)
Input voltage range 100 V AC ... 240 V AC
-15% ... +10%
Mains buffering 20 ms (120 V AC)
20 ms (230 VAC)
Nominal output voltage (U
N
) 24 V DC
Setting range of the output voltage (U
Set
)
24 V DC ... 29.5 V DC
Nominal output current (I
N
)
Static Boost (I
Stat.Boost
)
Dynamic Boost (I
Dyn.Boost
)
Selective Fuse Breaking (I
SFB
)
20 A 25 A 30 A (5 s) 120 A (15 ms)
Output power (PN) Output power (P
Stat. Boost
)
Output power (P
Dyn. Boost
)
480 W 600 W 720 W
Efficiency typ. 92.4 % (120 V AC)
typ. 94 % (230 V AC)
Residual ripple < 50 mV
PP
MTBF (IEC 61709, SN 29500) > 673000 h (40 °C)
Ambient temperature (operation) -25 °C ... 70 °C
-40°C (startup type tested) > 60 °C Derating: 2.5 %/K
Dimensions W/H/D 70 mm / 130 mm / 125 mm
Weight 1.3 kg
All technical specifications are nominal values and refer to a room temperature of 25 °C and 70 % relative humidity at 100 m above sea level.
107101_en_01
2018-09-04
QUINT4-PS/1AC/24DC/20

2Table of contents

1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 5
5 Safety and installation notes..................................................................................................16
6 High-voltage test (HIPOT) ..................................................................................................... 17
7 Structure of the power supply ................................................................................................ 19
8 Mounting/removing the power supply.................................................................................... 22
9 Device connection terminal blocks ........................................................................................ 25
10 Output characteristic curves ..................................................................................................27
11 Configuring the power supply ................................................................................................ 30
12 Boost currents ....................................................................................................................... 31
13 SFB technology ..................................................................................................................... 33
14 Signaling................................................................................................................................ 37
15 Operating modes................................................................................................................... 45
16 Derating................................................................................................................................. 47
107101_en_01 PHOENIX CONTACT 2 / 50
QUINT4-PS/1AC/24DC/20

3Ordering data

Description Ty p e Order No. Pcs./Pkt.
Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB(selective fuse breaking) technology, and NFC interface, input: 1­phase,output:24VDC/20 A
One or more of the primary-switched QUINT POWER power supply with SFB Technology (selective fuse breaking) versions configured online can now be ordered using the following web code: phoenixcontact.net/ webcode/#0852
Accessories Ty p e Order No. Pcs./Pkt.
Universal wall adapter for securely mounting the power supply in the event of strong vibrations. The power supply is screwed directly onto the mounting surface. The universal wall adapter is attached at the top/bottom.
2-piece universal wall adapter for securely mounting the power supply in the event of strong vibrations. The profiles that are screwed onto the side of the power supply are screwed directly onto the mounting surface. The universal wall adapter is attached on the left/right.
Assembly adapter for QUINT-PS... power supply on S7­300 rail
Near Field Communication (NFC) programming adapter with USB interface for the wireless configuration of NFC­capable products from PHOENIX CONTACT with software. No separate USB driver is required.
Type 2/3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote signaling for single-phase power supply networks. Nominal voltage 230VAC/DC.
Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote signaling for single-phase power supply networks. Nominal voltage 24VAC/DC.
Type 2/3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote signaling for single-phase power supply networks. Nominal voltage 230VAC/DC.
Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote signaling for single-phase power supply networks. Nominal voltage 24VAC/DC.
Multi-channel electronic device circuit breaker for protecting four loads at 24 V DC in the event of overload and short circuit. With electronic locking of the set nominal currents. For installation on DIN rails.
QUINT4-PS/1AC/24DC/20 2904602 1
UWA 182/52 2938235 1
UWA 130 2901664 1
QUINT-PS-ADAPTERS7/1 2938196 1
TWN4 MIFARE NFC USB ADAPTER
PLT-SEC-T3-230-FM-UT 2907919 5
PLT-SEC-T3-24-FM-UT 2907916 5
PLT-SEC-T3-230-FM-PT 2907928 5
PLT-SEC-T3-24-FM-PT 2907925 5
CBMC E4 24DC/1-4A NO 2906031 1
2909681 1
107101_en_01 PHOENIX CONTACT 3 / 50
QUINT4-PS/1AC/24DC/20
Accessories Ty p e Order No. Pcs./Pkt.
Multi-channel electronic device circuit breaker for protecting four loads at 24 V DC in the event of overload and short circuit. With electronic locking of the set nominal currents. For installation on DIN rails.
Multi-channel electronic circuit breaker with IO-Link interface for protecting four loads at 24VDC in the event of overload and short circuit. With electronic locking of the set nominal currents. For installation on DIN rails.
Multi-channel electronic circuit breaker with IO-Link interface for protecting four loads at 24VDC in the event of overload and short circuit. With electronic locking of the set nominal currents. For installation on DIN rails.
Multi-channel, electronic device circuit breaker with active current limitation for protecting four loads at 24 V DC in the event of overload and short circuit. With nominal current assistant and electronic locking of the set nominal currents. For installation on DIN rails.
Multi-channel, electronic device circuit breaker with active current limitation for protecting eight loads at 24 V DC in the event of overload and short circuit. With nominal current assistant and electronic locking of the set nominal currents. For installation on DIN rails.
The range of accessories is being continuously extended. The current range of accessories can be found in the download area for the product.
CBMC E4 24DC/1-10A NO 2906032 1
CBMC E4 24DC/1-4A+ IOL 2910410 1
CBMC E4 24DC/1-10A IOL 2910411 1
CBM E4 24DC/0.5-10A NO-R 2905743 1
CBM E8 24DC/0.5-10A NO-R 2905744 1
107101_en_01 PHOENIX CONTACT 4 / 50
QUINT4-PS/1AC/24DC/20

4 Technical data

Input data

Unless otherwise stated, all data applies for 25°Cambient temperature, 230VAC input voltage, and nominal output current (I
Input voltage range 100 V AC ... 240 V AC -15% ... +10%
Electric strength, max. 300 V AC 60 s Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 % Frequency (f
) for railway power supply systems 16.7 Hz (acc. to EN 50163)
R
Railway power supply systems can be operated at 16.7 Hz. Use conditions and technical data on request.
Current draw typ. 6.8 A (100 V AC)
The specified values for current consumption apply for operation in the static boost(PNx125%).
).
N
110 V DC ... 250 V DC -18% ... +40%
5.5 A (120 V AC)
2.8 A (230 V AC)
2.7 A (240 V AC) 6 A (110 V DC)
2.5 A (250 V DC)
Discharge current to PE typical
< 3.5 mA
1.7 mA (264 V AC, 60 Hz)
Mains buffering 20 ms (120 V AC)
20 ms (230 VAC) Switch-on time < 1 s Typical response time from SLEEP MODE 300 ms Protective circuit Transient surge protection Varistor, gas-filled surge arrester Switch-on current surge limitation typical after 1 ms 11 A Inrush surge current I2t< 0.4 A
2
s
Input fuse slow-blow, internal 12 A
During the first few microseconds, the current flow into the filter capacitors is excluded.
The SCCR value (short-circuit current rating) of the power supply unit corresponds to the SCCR value of the backup fuse (see input protection table).
The external backup fuse must be approved for the (AC) supply voltage used and the voltage level.
107101_en_01 PHOENIX CONTACT 5 / 50

Input protection , AC ( to be connected externally upstream )

Housing
Output
PE
Input
Signaling
C
A
B
D
B
L
N
(+)
(-)
+
0,4
0,5
0,6
0,7
0,8
0,9
1,0
I [A]
Out
Power Factor
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
= U : 120 V AC/U : 24 V DC
In Out
= U : 230 V AC/U : 24 V DC
In Out
 
Input current I
Input protection
In
Circuit breaker
Neozed fuse
or equivalent
Characteristics A B C D K gG
4 A ----- - 6 A - - - - - -
8 A -  10 A - 13 A  16 A
Electric strength of the insulation
QUINT4-PS/1AC/24DC/20
Power switch
13 x I
(maximum magnetic tripping)
In
A B C D
Type test (IEC/EN 60950-1) 2.5 kV AC 4 kV AC 0.5 kV DC 0.5 kV DC Production test 2 kV AC 2 kV AC 0.5 kV DC 0.5 kV DC Field test (with gas-filled surge arrester) 0.8 kV AC
1.1 kV DC
Field test (gas-filled surge arrester de-contacted) 2 kV AC
2.83 kV DC
0.8 kV AC
1.1 kV DC 2 kV AC
2.83 kV DC
0.5 kV DC 0.5 kV DC
0.5 kV DC 0.5 kV DC
POWER factor
107101_en_01 PHOENIX CONTACT 6 / 50
QUINT4-PS/1AC/24DC/20
0
1
2
3
4
5
6
7
246810
12 14
16 18 20 22 24 26 28 30
I [A]
Out
I [A]
In
= U : 120 V AC/U : 24 V DC
In Out
= U : 230 V AC/U : 24 V DC
In Out
 
Crest factor 120 V AC 230 V AC
typ. 1.55 typ. 1.65
Input current vs. output current

Input connection data

Connection method Screw connection Conductor cross section, solid 0.2 mm² ... 6 mm² Conductor cross section, flexible 0.2 mm² ... 4 mm² Conductor cross section flexible, with ferrule with plastic
sleeve Conductor cross section flexible, with ferrule without
plastic sleeve Conductor cross section AWG 24 ... 10 Stripping length 8 mm Tightening torque 0.5 Nm ... 0.6 Nm
0.25 mm² ... 4 mm²
0.25 mm² ... 4 mm²

Output data

Nominal output voltage (U Setting range of the output voltage (U
)24 V DC
N
) ( constant
Set
24 V DC ... 29.5 V DC
capacity ) Nominal output current (IN)20 A Static Boost (I
Stat.Boost
Dynamic Boost (I Selective Fuse Breaking (I
) 25 A
Dyn.Boost
)30 A (5 s)
) 120 A (15 ms)
SFB
Magnetic circuit breaker tripping A1...A16 / B2...B13 / C1...C6 / Z1...Z16 Control deviation Static load change 10% ... 90% < 0.5 % Control deviation Dynamic load change 10% ... 90%, (10
< 4 %
Hz) Control deviation change in input voltage ±10 % < 0.25 % Short-circuit-proof yes No-load proof yes Residual ripple ( with nominal values ) < 50 mV
PP
Connection in parallel Yes, for redundancy and increased capacity Connection in series yes
107101_en_01 PHOENIX CONTACT 7 / 50
QUINT4-PS/1AC/24DC/20
Output data
Feedback resistance 35 V DC Protection against surge voltage on the output 32 V DC Rise time typical < 1 s (U

Output connection data

Connection method Screw connection Conductor cross section, solid 0.2 mm² ... 6 mm² Conductor cross section, flexible 0.2 mm² ... 4 mm² Conductor cross section flexible, with ferrule with plastic
0.25 mm² ... 4 mm²
sleeve Conductor cross section flexible, with ferrule without
0.25 mm² ... 4 mm²
plastic sleeve Conductor cross section AWG 24 ... 10 Stripping length 8 mm Tightening torque 0.5 Nm ... 0.6 Nm

LED signaling

P
> 100% LED lights up yellow, output power > 480W
Out
P
> 75% LED lights up green, output power > 360W
Out
P
> 50% LED lights up green, output power > 240W
Out
U
Out
U
Out
> 0.9xU < 0.9xU
Set
Set
LED lights up green LED flashes green
=10%...90%)
Out

Signal contact (configurable)

Signal output (configurable) Out 1 Digital 0/24VDC , 20 mA Default 24 V DC , 20 mA ( 24VDC for U
>0.9xU
Out
Set
) Signal output (configurable) Out 2 Digital 0/24VDC , 20 mA Analog 4 mA ... 20 mA 5 % (Load 400) Default 24 V DC , 20 mA ( 24VDC for P
Out
<PN ) Relay contact (configurable) 13/14 Function N/O contact Default closed (U
> 0.9 U
out
Set
) Maximum contact load 24 V DC 1 A , 30 V AC/DC 0.5 A Control input (configurable) Rem Function Output power ON/OFF (SLEEP MODE) Default Output power ON (>40kΩ/24 V DC/open bridge between Rem
and SGnd)
Signal ground SGnd Reference potential for Out1, Out2, and Rem
107101_en_01 PHOENIX CONTACT 8 / 50
QUINT4-PS/1AC/24DC/20

Signal connection data

Connection method Push-in connection Conductor cross section, solid 0.2 mm² ... 1 mm² Conductor cross section, flexible 0.2 mm² ... 1.5 mm² Conductor cross section flexible, with ferrule with plastic
sleeve Conductor cross section flexible, with ferrule without
plastic sleeve Conductor cross section AWG 24 ... 16 Stripping length 8 mm

Reliability 230 V AC

MTBF (IEC 61709, SN 29500) > 1112000 h (25 °C)
0.2 mm² ... 0.75 mm²
0.2 mm² ... 1.5 mm²
> 673000 h (40 °C) > 309000 h (60 °C)
Life expectancy (electrolytic capacitors) Output current (I
Out
)
120 V AC 230 V AC
10 A > 375000 h ( 40 °C ) > 436000 h ( 40 °C ) 20 A > 94000 h ( 40 °C ) > 128000 h ( 40 °C ) 20 A > 267000 h ( 25 °C ) > 364000 h ( 25 °C )
The expected service life is based on the capacitors used. If the capacitor specification is observed, the specified data will be ensured until the end of the stated service life. For runtimes beyond this time, error-free operation may be reduced. The specified service life of more than 15 years is simply a comparative value.
Switching frequency Min. Max.
PFC stage 50 kHz 70 kHz Auxiliary converter stage 90 kHz 110 kHz Main converter stage 80 kHz 280 kHz

General data

Degree of protection IP20 Protection class I Inflammability class in acc. with UL 94 (housing / terminal
V0
blocks) Side element version Aluminum Hood version Stainless steel X6Cr17 Dimensions W / H / D (state of delivery) 70 mm / 130 mm / 125 mm Dimensions W / H / D (90° turned) 122 mm / 130 mm / 73 mm Weight 1.3 kg
Power dissipation 120 V AC 230 V AC
Maximum power dissipation in no-load condition < 5 W < 5 W Power dissipation SLEEP MODE < 5 W < 5 W Power loss nominal load max. < 40 W < 32 W
107101_en_01 PHOENIX CONTACT 9 / 50
QUINT4-PS/1AC/24DC/20
70
75
80
85
90
95
I [A]
Out
Eta [%]
24681012141618202224262830
= U : 120 V AC/U : 24 V DC
In Out
= U : 230 V AC/U : 24 V DC
In Out
 
Efficiency 120 V AC 230 V AC
typ. 92.4 % typ. 94 %

Ambient conditions

Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
The ambient temperature (operation) refers to UL 508 surrounding air temperature.
Ambient temperature (start-up type tested) -40 °C Ambient temperature (storage/transport) -40 °C ... 85 °C Max. permissible relative humidity (operation) 95 % (at 25 °C, non-condensing) Installation height 5000 m (> 2000 m, observe derating) Vibration (operation) 5Hz ... 100Hz resonance search 2.3g, 90min., resonance
frequency 2.3g, 90min. (according to DNV GL Class C)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-
2-27) Degree of pollution 2 Climatic class 3K3 (in acc. with EN 60721) Overvoltage category
EN 60950-1 EN 61010-1 EN 62477-1
II ( 5000m)
II(≤5000m)
III(≤2000m)

Standards

Safety transformers for power supply units EN 61558-2-16 (air clearances and creepage distances only) Electrical safety (of information technology equipment) IEC60950-1/VDE0805 (SELV) Electrical safety (of control and regulation devices) IEC 61010-1 SELV IEC60950-1 (SELV)
Network version/undervoltage SEMI F47-0706; EN 61000-4-11 Rail applications EN50121-3-2
EMC requirements, power plant IEC61850-3
HART FSK Physical Layer Test Specification Compliance Output voltage U
107101_en_01 PHOENIX CONTACT 10 / 50
EN 60204-1 (PELV)
EN 50121-4
EN 50121-5
IEC 62236-3-2
IEC 62236-4
IEC 62236-5
EN61000-6-5
Out
compliant

Approvals

UL UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location) CSA CAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01 SIQ BG (type approved)
Shipbuilding DNV GL, PRS, BV, LR, ABS
QUINT4-PS/1AC/24DC/20
107101_en_01 PHOENIX CONTACT 11 / 50
QUINT4-PS/1AC/24DC/20
Electromagnetic compatibility Noise emission according to EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) CE basic standard Minimum normative
requirements
Conducted noise emission EN 55016 EN61000-6-4 (Class A) EN61000-6-3 (Class B) Noise emission EN 55016 EN61000-6-4 (Class A) EN61000-6-3 (Class B) Harmonic currents EN 61000-3-2 EN 61000-3-2 (Class A) EN 61000-3-2 (Class A) Flicker EN 61000-3-3 not required EN 61000-3-3 (Class A)
Higher requirements in
practice (covered)
Noise emission for marine approval Minimum normative
requirements of DNVGL
Higher requirements in
practice of DNVGL
(covered)
DNV GL conducted noise emission Class A
Area power distribution
DNV GL noise radiation Class A
Area power distribution
Area power distribution
Class A
Class B
Bridge and deck area
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply)
CE basic standard Minimum normative
requirements of
Higher requirements in
practice (covered)
EN 61000-6-2 (CE)
(immunity for industrial
environments)
Electrostatic discharge EN 61000-4-2
Housing contact discharge 4 kV (Test Level 2) 8 kV (Test Level 4)
Housing air discharge 8 kV (Test Level 3) 15 kV (Test Level 4)
Comments Criterion B Criterion A
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz ... 1 GHz 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3) 20 V/m (Test Level 3)
Frequency range 1.4 GHz ... 2 GHz 1 GHz ... 6 GHz
Test field strength 3 V/m (Test Level 2) 10 V/m (Test Level 3)
Frequency range 2 GHz ... 2.7 GHz 1 GHz ... 6 GHz
Test field strength 1 V/m (Test Level 1) 10 V/m (Test Level 3)
Comments Criterion A Criterion A
Fast transients (burst) EN 61000-4-4
Input 2 kV (Test Level 3 -
asymmetrical)
Output 2 kV (Test Level 3 -
asymmetrical)
Signal 1 kV (Test Level 3 -
asymmetrical)
4 kV (Test Level 4 -
asymmetrical)
4 kV (Test Level 4 -
asymmetrical)
4 kV (Test Level 4 -
asymmetrical)
Comments Criterion B Criterion A
107101_en_01 PHOENIX CONTACT 12 / 50
QUINT4-PS/1AC/24DC/20
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply)
CE basic standard Minimum normative
requirements of
EN 61000-6-2 (CE)
(immunity for industrial
environments)
Surge voltage load (surge) EN 61000-4-5
Input 1 kV (Test Level 3 -
symmetrical)
2 kV (Test Level 3 -
asymmetrical)
Output 0.5 kV (Test Level 2 -
symmetrical)
0.5 kV (Test Level 1 ­asymmetrical)
Signal 1 kV (Test Level 2 -
asymmetrical)
Comments Criterion B Criterion A
Conducted interference EN61000-4-6
Input/Output/Signal asymmetrical asymmetrical
Frequency range 0.15 MHz ... 80 MHz 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3) 10 V (Test Level 3)
Comments Criterion A Criterion A
Power frequency magnetic field EN 61000-4-8
50 Hz , 60 Hz ( 30 A/m ) 16.7 Hz , 50 Hz , 60 Hz
not required 50 Hz , 60 Hz ( 1 kA/m , 3 s ) not required 0 Hz ( 300 A/m , DC, 60 s )
Comments Criterion A Criterion A Voltage dips EN 61000-4-11 Input voltage ( 230 V AC , 50 Hz )
Voltage dip 70 % , 25 periods
( Test Level 2 )
Comments Criterion C Criterion A: 0.5 / 1 / 25 / 30
Voltage dip 40 % , 10 periods
( Test Level 2 )
Comments Criterion C Criterion A
Voltage dip 0 % , 1 period
( Test Level 2 )
Comments Criterion B Criterion A: 0.5 / 1 period
Higher requirements in
practice (covered)
3 kV (Test Level 4 -
symmetrical)
6 kV (Test Level 4 -
asymmetrical)
1 kV (Test Level 3 -
symmetrical)
2 kV (Test Level 3 -
asymmetrical)
4 kV (Test Level 4 -
asymmetrical)
( 100 A/m 60 s )
70 % , 0.5 / 1 / 25 / 30 periods
( Test Level 2 )
periods
40 % , 5 / 10 / 50 periods
( Test Level 2 )
0 % , 0,5 / 1 / 5 / 50 / 250
periods ( Test Level 2 )
Criterion B: 5 / 50 / 250 periods
107101_en_01 PHOENIX CONTACT 13 / 50
QUINT4-PS/1AC/24DC/20
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) Basic standard Minimum normative
requirements of
EN 61000-6-5
Pulse-shape magnetic field EN 61000-4-9
not required 1000 A/m
Comments none Criterion A Damped oscillating magnetic field EN61000-4-10
not required 100 kHz
not required 1 MHz
Comments none Criterion A Attenuated sinusoidal oscillations (ring wave) EN 61000-4-12
Input not required 2 kV (Test Level 4 -
not required 4 kV (Test Level 4 -
Comments none Criterion A Asymmetrical conducted disturbance variables EN 61000-4-16
Input, Output, Signals 15 Hz ... 150 Hz , 10 V on 1 V
150 Hz ... 1.5 kHz , 1 V
1.5 kHz ... 15 kHz , 1 V on 10 V 15 kHz ... 150 kHz , 10 V
( Test Level 3 )
50 Hz , 60 Hz , 1 0 V (Permanent)
50 Hz , 60 Hz ,
100 V (1 s)
( Test Level 3 )
Comments Criterion A Criterion A
Attenuated oscillating wave EN 61000-4-18
Input, Output 1 MHz , 1 kV
( Test Level 3 - symmetrical ) 10 MHz , 1 kV 1 MHz , 2.5 kV
( Test Level 3 - asymmetrical )
Signals 1 MHz , 1 kV
( Test Level 3 - symmetrical )
1 MHz , 2.5 kV
( Test Level 3 - asymmetrical )
Comments Criterion B Criterion A
Higher requirements in
practice (covered)
110 A/m
110 A/m
symmetrical)
asymmetrical)
15 Hz ... 150 Hz , 30 V on 3 V
150 Hz ... 1.5 kHz , 3 V
1.5 kHz ... 15 kHz , 3 V on 30 V 15 kHz ... 150 kHz , 30 V
( Test Level 4 )
16.7 Hz , 50 Hz , 60 Hz , 30 V (Permanent)
150 Hz , 180 Hz ,
30 V (Permanent)
16.7 Hz , 50 Hz , 60 Hz ,
300 V (1 s)
( Test Level 4 )
100 kHz , 1 MHz , 1 kV
( Test Level 3 - symmetrical )
10 MHz , 1 kV 100 kHz , 1 MHz
, 2.5 kV
( Test Level 3 - asymmetrical )
100 kHz , 1 MHz , 1 kV
( Test Level 3 - symmetrical )
100 kHz , 1 MHz , 2.5 kV
( Test Level 3 - asymmetrical )
107101_en_01 PHOENIX CONTACT 14 / 50
QUINT4-PS/1AC/24DC/20
Key
Criterion A Normal operating behavior within the specified limits. Criterion B Temporary impairment to operational behavior that is corrected by the device itself. Criterion C Temporary adverse effects on the operating behavior, which the device corrects
automatically or which can be restored by actuating the operating elements.
107101_en_01 PHOENIX CONTACT 15 / 50
QUINT4-PS/1AC/24DC/20

5 Safety and installation notes

Only qualified electricians may install, start up, and operate the device. Observe the national safety and accident prevention regulations.
The specified technical characteristics relate to the factory setting of the standard device.
Configured devices may have different technical characteristics. The device behavior may also differ from the documentation.
CAUTION: Before startup, observe the following
Check the device for external damage. If the device is defective, it must not be used.
The power supply must be switched off from outside according to EN 60950-1 (e.g.,via the line protection on the primary side).
Preferably mount the power supply in the normal mounting position.
Ensure that the primary-side and secondary­side wiring of the power supply are the correct size and have sufficient fuse protection.
The power supply is a built-in device. The IP20 degree of protection of the power supply is intended for a clean and dry environment. The power supply is mounted in a control cabinet.
For the connection parameters for wiring the power supply, suchas the required stripping length with and without ferrule, refer to the technical data section.
As a safety measure against shock currents, always wire the protective conductor device terminal block to the control cabinet ground connection.
To avoid accidental contact with live parts, always cover the termination area (e.g.,installation in the control cabinet).
The power supply is maintenance-free. Repairs may only be carried out by the manufacturer. The warranty no longer applies if the housing is opened.
The power supply may only be used for its intended use.
The continuous total output power may not exceed P P
Stat. Boost
at 60°C ambient temperature and
N
at 40°C ambient temperature. Observe all the maximum output powers for all operating conditions.
DANGER: Hazardous voltage
The power supply contains components that have been designed for operation at potentially lethal voltages. The accumulated level of energy can also be high. Never carry out work when mains voltage is present.
CAUTION: Hot surface
Depending on the ambient temperature and load on the power supply, the housing can become hot.
107101_en_01 PHOENIX CONTACT 16 / 50
QUINT4-PS/1AC/24DC/20

6 High-voltage test (HIPOT)

This protection class I power supply is subject to the Low Voltage Directive and is factory tested. During the HIPOT test (high-voltage test), the insulation between the input circuit and output circuit is tested for the prescribed electric strength values, forexample. The test voltage in the high­voltage range is applied at the input and output terminal blocks of the power supply. The operating voltage used in normal operation is a lot lower than the test voltage used.
High-voltage tests up to 0.8kVAC/ 1.1kVDC can be performed as described.
For high-voltage tests > 0.8kVAC/ 1.1kVDC, the gas-filled surge arrester must be disconnected.
The test voltage should rise and fall in ramp form. The relevant rise and fall time of the ramp should be at least two seconds.

6.1 High-voltage dielectric test (dielectric strength test)

In order to protect the user, power supplies (as electric components with a direct connection to potentially hazardous voltages) are subject to more stringent safety requirements. For this reason, permanent safe electrical isolation between the hazardous input voltage and the touch-proof output voltage as safety extra-low voltage (SELV) must always be ensured.
In order to ensure permanent safe isolation of the AC input circuit and DC output circuit, high-voltage testing is performed as part of the safety approval process (type test) and manufacturing (routine test).

6.3 High-voltage dielectric test performed by the customer

Apart from routine and type tests to guarantee electrical safety, the end user does not have to perform another high­voltage test on the power supply as an individual component. According to EN 60204-1 (Safety of machinery
- Electrical equipment of machines) the power supply can be
disconnected during the high-voltage test and only installed once the high-voltage test has been completed.

6.2 High-voltage dielectric test during the manufacturing process

During the manufacturing process for the power supply, a high-voltage test is performed as part of the dielectric test in accordance with the specifications of IEC/UL/EN 60950-1. The high-voltage test is performed with a test voltage of at least 1.5kVAC/2.2kVDC or higher. Routine manufacturing tests are inspected regularly by a certification body.
107101_en_01 PHOENIX CONTACT 17 / 50
QUINT4-PS/1AC/24DC/20
DC OK
NFC
> 100% Boost > 75% > 50%
P
out
DC OK
U
Out
QUINT POWER
Input AC 100-240 V
13 14
Rem SGnd Out 1 Out 2
N/- L/+
Output DC
+
+
Signal
1
2
3
4
HV
/=
M3x8
NFC
QUINT POWER
P
Out
> 75% > 50% DC OK
> 100%
A
B

6.3.1 Performing high-voltage testing

If high-voltage testing of the control cabinet or the power supply as a stand-alone component is planned during final inspection and testing, the following features must be observed.
The power supply wiring must be implemented as
shown in the wiring diagram.
The maximum permissible test voltages must not be
exceeded.
Avoid unnecessary loading or damage to the power supply due to excessive test voltages.
For the relevant applicable test voltages and insulation distances, refer to the corresponding table (see technical data: electric strength of the insulation section).

6.3.2 Disconnecting the gas-filled surge arrester

The built-in gas-filled surge arrester inside the device ensures that the power supply is effectively protected against asymmetrical disturbance variables (e.g.,EN 61000-4-5).
Each surge voltage test represents a very high load for the power supply. Therefore avoid unnecessary loading or damage to the power supply due to excessive test voltages. If necessary, the gas-filled surge arrester inside the device can be disconnected in order to use higher test voltages. Following successful completion of testing, please reconnect the gas-filled surge arrester.
Figure 2 Disconnect gas-filled surge arrester
To disconnect the gas-filled surge arrester, proceed as follows:
1. Remove power from the unit.
2. Unscrew the Phillips head screw completely and keep the gas-filled surge arrester screw in a safe place. The gas-filled surge arrester is now disconnected and is no longer functional.
Figure 1 Potential-related wiring for the high-voltage
test
3. Perform the surge voltage test on the power supply.
4. Following successful high-voltage testing, screw the gas-filled surge arrester screw fully back into the power
Key
No. Designation Color coding Potential
levels
1 DC output circuit Blue Potential 1 2 Signal contacts Blue Potential 1 3 High-voltage
tester
4 AC input circuit Red Potential 2
107101_en_01 PHOENIX CONTACT 18 / 50
-- --
supply.
DANGER: Risk of electric shock or damage to the power supply due to using the wrong gas-filled surge arrester screw
To connect the gas-filled surge arrester, only use the gas-filled surge arrester screw that was originally installed in the power supply.
QUINT4-PS/1AC/24DC/20
NFC
QUINT POWER
Output DC 24V 20A
++
Input AC 100-240 V
> 100% Boost > 75%
> 50%
P
Out
DC OK
U
Out
29.5V
24V
13 14
Rem
SGnd
Out 1 Out 2
N/-
L/+
Signal
7
2
2
3
5
9
6
4
22
1
8
NFC
QUINT POWER
Output DC 24V 20A
++
Input AC 100-240 V
> 100% Boost > 75%
> 50%
P
Out
DC OK
U
Out
29,5V
24V
13 14
Rem SGnd Out 1 Out 2
N/-
L/+
Signal
70
130
65
122
125
130
80
45
131

7 Structure of the power supply

The fanless convection-cooled power supply can be snapped onto all DIN rails according to EN60715.

7.1 Function elements

7.2 Device dimensions

Figure 4 Device dimensions (dimensions in mm)
Figure 3 Operating and indication elements
Key
No. Designation
1 DC output voltage connection terminal blocks 2 Accommodation for cable binders 3 Signaling connection terminal blocks 4 Status and diagnostics indicators 5 NFC interface (Near Field Communication) 6 AC input voltage connection terminal blocks 7 Gas-filled surge arrester for surge protection (left
8 Universal DIN rail adapter (rear of housing) 9 Output voltage button (-) / (+)
107101_en_01 PHOENIX CONTACT 19 / 50
side of housing)
Figure 5 Device dimensions (dimensions in mm)

7.3 Keep-out areas

b
130
70
NFC
QUINT POWER
Output DC 24V 20A
++
Input AC 100-240V
> 100% Boost > 75% > 50%
P
Out
DC OK
U
Out
29,5V
24V
13 14
Rem
SGnd
Out 1 Out 2
N/-
L/+
Signal
aa
c
QUINT4-PS/1AC/24DC/20
Nominal output
capacity
Spacing [mm]
a b c
< 50 % 0 40 20 50 % 5 50 50
If adjacent components are active and the nominal output power 50%, there must be lateral spacing of 15 mm.
Figure 6 Device dimensions and minimum keep-out
areas (in mm)
107101_en_01 PHOENIX CONTACT 20 / 50

7.4 Block diagram

NFC
P
Out
OVP
C
+ +
-
-
13 14
Rem SGnd Out 1 Out 2
active
PFC
-
L
N
(+)
(-)
active
PFC
OVP
13 14
Rem SGnd Out 1 Out 2
C
NFC
P
OUT
Figure 7 Block diagram
Key
QUINT4-PS/1AC/24DC/20
Symbol Designation
Surge protection (varistor, gas-filled surge arrester) with filter
Bridge rectifier
Inrush current limitation
Power factor correction (PFC)
Switching transistor and main transmitter (electrically isolating)
Secondary rectification and smoothing
Filter
Auxiliary converter (electrically isolating)
Symbol Designation
Optocoupler (electrically isolating)
Additional regulatory protection against surge voltage
Relay contact and signal contacts
Microcontroller
NFC interface (Near Field Communication)
Output voltage button (-) / (+)
Signal/display LEDs (P
, DC OK)
Out
107101_en_01 PHOENIX CONTACT 21 / 50
8 Mounting/removing the power
B
A
Click
B
A
D
C
M
3
x
8
M3x8
supply

8.1 Mounting the power supply unit

Proceed as follows to mount the power supply:
1. In the normal mounting position the power supply is mounted on the DIN rail from above. Make sure that the universal DIN rail adapter is in the correct position behind the DIN rail (A).
2. Then press the power supply down until the universal DIN rail adapter audibly latches into place (B).
3. Check that the power supply is securely attached to the DIN rail.
QUINT4-PS/1AC/24DC/20
Figure 9 Removing the power supply from the DIN rail

8.3 Retrofitting the universal DIN rail adapter

For installation in horizontal terminal boxes it is possible to mount the power supply at a 90°angle to the DIN rail.
No additional mounting material is required.
Use the Torx screws provided to attach the universal DIN rail adapter to the side of the power supply.
Figure 8 Snapping the power supply onto the DIN rail

8.2 Removing the power supply unit

Proceed as follows to remove the power supply:
1. Take a suitable screwdriver and insert this into the lock hole on the universal DIN rail adapter (A).
2. Release the lock by lifting the screwdriver (B).
3. Carefully swivel the power supply forward (C) so that the lock slides back into the starting position.
4. Then separate the power supply from the DIN rail (D).

8.3.1 Disassembling the universal DIN rail adapter

Proceed as follows to disassemble the universal DIN rail adapter that comes pre-mounted:
1. Remove the screws for the universal DIN rail adapter using a suitable screwdriver (Torx 10).
2. Separate the universal DIN rail adapter from the rear of the power supply.
Figure 10 Disassembling the universal DIN rail adapter
107101_en_01 PHOENIX CONTACT 22 / 50
QUINT4-PS/1AC/24DC/20
M
3
x
8
M
3
x
8
M
3
x
8
M
3
x
8

8.3.2 Mounting the universal DIN rail adapter

To mount the universal DIN rail adapter on the left side of the device, proceed as follows:
1. Position the universal DIN rail adapter on the left side of the housing so that the mounting holes are congruent with the hole pattern for the mounting holes.
2. Insert the Torx screws that were removed earlier into the appropriate hole pattern on the universal DIN rail adapter so that the necessary drill holes on the power supply can be accessed.
3. Screw the universal DIN rail adapter onto the power supply.
The maximum tightening torque of the Torx screw (Torx® T10) is 0.7 Nm.
8.4.1 Mounting the UWA182/52 universal wall adapter
Proceed as follows to disassemble the universal DIN rail adapter that comes pre-mounted:
1. Remove the screws for the universal DIN rail adapter
using a suitable screwdriver (Torx 10).
2. Separate the universal DIN rail adapter from the rear of
the power supply.
3. Position the universal wall adapter in such a way that
the keyholes or oval tapers face up. The mounting surface for the power supply is the raised section of the universal wall adapter.
4. Place the power supply on the universal wall adapter in
the normal mounting position (input voltage connection terminal blocks below).
5. Insert the Torx screws into the appropriate hole pattern
on the universal wall adapter so that the necessary mounting holes on the power supply can be accessed.
6. Screw the universal wall adapter onto the power supply.
Figure 11 Mounting the universal DIN rail adapter

8.4 Retrofitting the universal wall adapter

The UWA 182/52 universal wall adapter (Order No.
2938235) or UWA 130 universal wall adapter (Order No.
2901664) is used to attach the power supply directly to the
Figure 12 Mounting the UWA 182/52 universal wall
adapter
mounting surface. The use of universal wall adapters is recommended under
extreme ambient conditions, e.g.,strong vibrations. Thanks to the tight screw connection between the power supply and
The maximum tightening torque of the Torx screw (Torx® T10) is 0.7 Nm.
the universal wall adapter or the actual mounting surface, an extremely high level of mechanical stability is ensured.
Make sure you use suitable mounting material when attaching to the mounting surface.
The power supply is attached to the UWA182 or UWA130 universal wall adapter by means of the Torx screws of the universal DIN rail adapter.
107101_en_01 PHOENIX CONTACT 23 / 50
QUINT4-PS/1AC/24DC/20
M
3
x
8
M
3
x
8
> 100% Boost > 75% > 50%
Pout
13
14 Rem S
G
nd
O
ut 1 O
ut 2
DC OK
U
O
u
t
Signal
> 100% Boost > 75% > 50%
Pout
1
3
14 Rem S
G
nd
O
ut 1 O
ut 2
DC OK
U
O
u
t
Signal
8.4.2 Mounting the UWA130 2-piece universal wall adapter
Proceed as follows to disassemble the universal DIN rail adapter that comes pre-mounted:
1. Remove the screws for the universal DIN rail adapter
using a suitable screwdriver (Torx 10).
2. Separate the universal DIN rail adapter from the rear of
the power supply.
3. Position the universal wall adapter. The mounting
surface for the power supply is the raised section of the universal wall adapter.
4. Place the power supply on the universal wall adapter in
the normal mounting position (input voltage connection terminal blocks below).
5. Insert the Torx screws into the appropriate hole pattern
on the universal wall adapter so that the necessary mounting holes in the side flanges of the power supply can be accessed.
6. Screw the two-piece universal wall adapter onto the
power supply.

8.5 Fix connection wiring to the power supply

Two receptacles for the bundled attachment of the connection wiring are integrated in the left and right housing panel. Use cable binders to secure the connection wiring (optional PKB 140X3,6 - Order No. 1005460).
Proceed as follows to secure the connection wiring: – Wire the power supply with sufficient connection
reserve (input terminal blocks, output terminal blocks, signal terminal blocks)
Bundle and set up the connection wiring so that the
cooling grilles on the top and bottom of the housing are covered as little as possible.
Thread the cable binders into the necessary
receptacles for the cable binders.
Figure 14 Lay and align connection wiring
Secure the connection wiring with the cable binders.
Make sure that the connection wiring is attached safely and securely without damaging the connection wiring.
Figure 13 Mounting the UWA130 universal wall adapter
Figure 15 Secure connection wiring with cable binder
107101_en_01 PHOENIX CONTACT 24 / 50
QUINT4-PS/1AC/24DC/20
> 100% Boost > 75% > 50%
Pout
1
3
14 Rem SG
nd O
ut 1 O
ut 2
DC OK
U
O
u
t
Signal
L
PEN
L3
L2
L1
+
N
iT
N
L
+
LN
TT
PEN
L
+
L−N
L
L3
L2
L1
+
N
L
N
L3
L2
L1
+
N
L
PE
N
L3
L2
L1
+
N
TN-C
PEN
L
+
LN
PE
N
L
+
LN
TN-S
Shorten the excess length of the cable binder ends. – Then check again that the connection wiring is properly
secured.
Figure 16 Shorten protruding ends of the cable binder
NOTE: Mechanical damage to the connection wiring caused by friction
In extreme ambient conditions, e.g.,strong vibrations, protect the connection wiring against mechanical damage using additional insulation material. The additional insulation material for protecting the connection wiring is limited to the area where the cable binders are attached.

9 Device connection terminal blocks

The AC input and DC output terminal blocks on the front of the power supply feature screw connection technology. The signal level is wired without tools by means of Push-in connection technology.
For the necessary connection parameters for the connection terminal blocks, refer to the technical data section.

9.1 Input

The power supply is operated on single-phase AC systems or two outer conductors of three-phase systems. The power supply is connected on the primary side via the INPUT L/N/ connection terminal blocks.
The power supply is approved for connection to TN, TT, and IT power grids with a maximum phase-to-phase voltage of 240 V AC.
Figure 17 Network types
107101_en_01 PHOENIX CONTACT 25 / 50
QUINT4-PS/1AC/24DC/20
N/-
L/+
N PE
L
Input AC 100...240 V
L
N PE
+
-
PE
N/-
L/+
-
+
Input DC 110...250 V

9.2 Protection of the primary side

Installation of the device must correspond to EN60950-1 regulations. It must be possible to switch off the device using a suitable disconnecting device outside the power supply. Theline protection on the primary side is suitable for this (see technical data section).
DANGER: Hazardous voltage
An all-pos. fuse must be present for operation on two outer conductors of a three-phase system.
Protection for AC supply

9.3 Output

By default, the power supply is pre-set to a nominal output voltage of 24VDC.
The output voltage is adjusted via the two arrow keys (-) and (+) on the front of the power supply.
When you press the arrow key once briefly, the output voltage is reduced (-) or increased (+) by 3mV. When you press the arrow key for longer, the voltage is adjusted in 100mV increments.

9.4 Protection of the secondary side

The power supply is electronically short-circuit-proof and no-load-proof. In the event of an error, the output voltage is limited
If sufficiently long connecting cables are used, fuse protection does not have to be provided for each individual load.
If each load is protected separately with its own protective device, the selective shutdown in the event of a fault enables the system to remain operational.
Figure 18 Pin assignment for AC supply voltage
Protection for DC supply
Figure 19 Pin assignment for DC supply voltage
DC applications require upstream installation of a fuse that is permitted for the operating voltage.
107101_en_01 PHOENIX CONTACT 26 / 50
QUINT4-PS/1AC/24DC/20
U/I Advanced
Smart HICCUP
FUSE MODE
---
--
-
+
-
M
-
Suitable for the application
Not suitable for the application
Symbol Designation
Characteristics
Your benefits
Reliable power supply
A stable 24 V, even in the
event of a sustained
overload
No over-dimensioned
power supply unit
required
Fast charging
Parallel loads continue
working
Low thermal stress in
the even of faults
Enables configuration
without fuse
Application
Normal load
System extension
Loads with high inrush
current
Energy storage charging
Selective tripping of
fuses
Keeps temperatures
low in the event of
faults
Short circuit, non-fused

10 Output characteristic curves

This section describes the various output characteristic curves together with their areas of application for customization to your specific application. The U/I Advanced characteristic curve is set by default.
107101_en_01 PHOENIX CONTACT 27 / 50
QUINT4-PS/1AC/24DC/20
I [A]
Out
t [s]
I
Dyn. Boost
U [V]
Out
I
N
I
Stat. Boost
U
N
3
5s
U
N
100%
125% 200%
0
0
5s
I [A]
Out
t [s]
2s
I
Dyn. Boost
U [V]
Out
I
N
I
Stat. Boost
U
N
2
5s
U
N
100%
125% 200%
0
0

10.1 U/I Advanced output characteristic curve

The preset U/I Advanced output characteristic curve is optimized for the following applications:
For selective tripping of standard circuit breakers (SFB
technology). The power supply supplies up to 6 times the nominal current for 15ms. Loads connected in parallel continue working.
When supplying loads with high switch-on currents,
such asmotors. The dynamic boost of the power supply supplies up to 200%of the nominal power for 5s. This ensures that sufficient reserve energy is available; overdimensioning of the power supply is not necessary.
For system extension. With the static boost, up to
125%of the nominal output power is available for a sustained period (up to40°C).
For fast energy storage charging (e.g.,of batteries) to
supply a wide range of loads. The power supply operates in the nominal operating range. Energy supply to the load is ensured.

10.2 Smart HICCUP output characteristic curve

The SMART HICCUP output characteristic curve keeps the thermal load of the connecting cables at a low level in the event of a sustained overload. If loads are not protected or are protected in a way that is not permitted, the loads are supplied for 2s. The DC output of the power supply is then switched off for 8s. This procedure is repeated until the cause of the overload has been remedied.
The preset Smart HICCUP output characteristic curve is optimized for the following applications:
If only a low short-circuit current is permitted. – If following an overload or short circuit the output
voltage should be made available again automatically.
Figure 21 Smart HICCUP output characteristic curve
Figure 20 U/I Advanced output characteristic curve
107101_en_01 PHOENIX CONTACT 28 / 50

10.3 FUSE MODE output characteristic curve

t [s]
I
Out
[A]
I
Fuse
t
Fuse
0
In the event of an overload (e.g.,short circuit), the power supply switches off the DC output permanently. The value of the switch-off threshold and the time period for which it may be exceeded can be freely selected. The power supply is restarted via the remote contact. As an option, the power supply can be switched on by switching the supply voltage on the primary side off and on.
Selecting the FUSE MODE output characteristic curve sets the following default values.
Fuse
Fuse
= 100ms
= I
N
–t –I
QUINT4-PS/1AC/24DC/20
Figure 22 FUSE MODE output characteristic curve
107101_en_01 PHOENIX CONTACT 29 / 50
QUINT4-PS/1AC/24DC/20
13 14
Rem SGnd
Out 1 Out 2
Signal
< 15 k
a)
b)
M3x8
NFC
QUINT POWER
>
1
0
0
%
B
o
o
s
t
>
7
5
%
>
5
0
%
Po
u
t
1
3
1
4
Re
m
S
G
n
d
O
u
t 1
O
u
t 2
>
1
0
0
%
B
o
o
s
t
>
7
5
%
>
5
0
%
D
C
O
K
U
O
u
t
1
3
1
4
Re
m
S
G
n
d
O
u
t 1
O
u
t 2
S
ig
n
a
l
NFC
DAT
CONN

11 Configuring the power supply

With the fourth generation of the QUINTPOWER power supply, it is now possible for the first time to adapt the behavior of the power supply. In addition to setting the output voltage and selecting the output characteristic curves, you can configure signal outputs Out1, Out2, and floating signal contact 13/14, forexample. Configuration of the remote input for controlling the power supply or specification of signal options and signal thresholds also extend the range of possible applications.
The power supply is configured via the device's internal NFC (near field communication) interface.
The power supply behaves like a passive NFC tag. An auxiliary power source is required in order to supply the power supply with configuration data.

11.1 Configuration with PC software

In order to configure the power supply via the NFC interface, the following hardware and software requirements must be met:
PC or notebook (as of Windows7, Microsoft.Net
Framework 4.5, USB2.0 interface, 50MB hard disk capacity, QUINT POWER software).
Programming adapter:
TWN4MIFARENFCUSBADAPTER (Order No.
2909681) is plugged into the USB interface.
Programming software: the QUINT POWER software
has been successfully installed.

11.2 Configuring the power supply

To configure the power supply, proceed as follows: – Before you can configure the power supply, it should
either be disconnected from the supply voltage or switched to SLEEP MODE.
To switch the power supply to SLEEP MODE, use one
of the external circuits. The following connection versions are possible between the Rem (remote input) and SGnd (signal ground) connection terminal blocks.
Figure 23 SLEEPMODE connection versions
Hold the USB-PROG-ADAPTER in front of the mounted
power supply so that the NFC antenna symbols are congruent with one another.
Figure 24 Configuration of the power supply
In the programming interface of the QUINT POWER
software, press the [Read] button. The current device and configuration data for the power supply is read and displayed.
If a connection cannot be established between the USB-PROG-ADAPTER and the power supply, more detailed information can be found in the user manual for the QUINT POWER software.
107101_en_01 PHOENIX CONTACT 30 / 50
QUINT4-PS/1AC/24DC/20
T [°C]
A
P [W]
Out
40 60 70
P
Stat. Boost
P
N
100%
125%
P
Dyn. Boost
150%
75%
-25
I [A]
Out
I
Dyn.Boost
t [s]
I
Base Load
t
Dyn.Boost
t
Dyn.Boost
t
Pause
For information regarding the configuration of the power supply, suchas selecting the characteristic curve and output parameters, refer to the user manual for the QUINT POWER software.

11.3 Configuration with NFC-capable mobile terminal device

The QUINT POWER app enables you to conveniently configure the power supply using a mobile terminal device, suchas a smartphone.
In order to configure the power supply via the NFC interface, the following hardware and software requirements must be met:
NFC-capable mobile terminal device with Android
operating system as of Version 4.1.x (Jelly Bean)
QUINT POWER app (Google Play Store)
For information regarding the configuration of the power supply, suchas selecting the characteristic curve and output parameters, please refer to the QUINTPOWERapp.

11.4 Ordering a configured power supply

Customer-specified QUINT POWER power supplies are ordered as a KMAT item (configurable material) and are configured during the production process in the factory. The power supply is therefore supplied ready to connect for your specific application.
You can type in the the web code phoenixcontact.net/webcode/#0852 to configure and order your power supply.

12 Boost currents

The power supply provides the static boost (I
Stat. Boost
sustained load supply or the time-limited dynamic boost (I
Dyn. Boost
).

12.1 Static Boost

For system expansion purposes, the sustained static boost (I
Stat. Boost
) supports the load supply with up to 125% of the nominal current of the power supply. The static boost is available at an ambient temperature of up to 40°C.
Figure 25 Performance characteristic in static boost

12.2 Dynamic Boost

Dynamic boost (I
Dyn. Boost
) delivers up to 150% of the power supply nominal current to supply high loads. This temporary power supply to the load lasts a maximum of 5s at an ambient temperature of up to 60°C. The energy supplied adaptively for the load supply and the recovery time (t are calculated based on the specific load situation using algorithms (see recovery time tables).
) for a
Pause
)
Figure 26 Basic curve of the dynamic boost process
107101_en_01 PHOENIX CONTACT 31 / 50
QUINT4-PS/1AC/24DC/20
t [s]
Pause
t [s]
Dyn. Boost
5
12
3
4
5
10
15
20
25
[A]
IBase Load
0
IDyn. Boost
[A]
30
30
30
30
30
30
0,3 0,6
0,9
1,2
1,5
0,2 0,5 0,7 1
1,2
0,4
0,7
3,4
0,8
1,4
7
1,2
2,1
11
1,6
2,8
14
2,1
3,5
17
0,2
0,6
0,4
0,8 1
t [s]
Pause
t [s]
Dyn. Boost
5
12
3
4
5
10
15
20
[A]
IBase Load
0
IDyn. Boost
[A]
30
30
30
30
30
12
3
4
4,9
0,6 1,3 1,9 2,5
3,1
1,9133,7
26
6
38
8
51
10
63
0,4
1,3
0,9
1,7 2,1
t [s]
Pause
t [s]
Dyn. Boost
5
12
3
4
5
10
15
20
25
[A]
IBase Load
0
IDyn. Boost
[A]
30
30
30
30
30
30
0,3 0,6
0,9
1,2
1,5
0,2 0,5 0,7 1
1,2
0,4
0,7
3,4
0,8
1,4
7
1,2
2,1
11
1,6
2,8
14
2,1
3,5
17
0,2
0,6
0,4
0,8 1
Use the following tables to determine the required recovery time (t
Boost
–I – Duration of the boost current (t
) at the maximum dynamic boost current (I
Pause
) based on the following values:
Base Load
Dyn. Boost
Dyn.
)
Ambient temperature (40°C or 60°C)
If a current that is lower than the maximum available dynamic boost current (I
Dyn.Boost
) is required for the same period, the recovery time may (t
Pause
) decrease.
12.2.1 Recovery times at an ambient temperature of 40°C
12.2.3 Example: Determining the recovery time )
(t
Pause
At an output current (I current (I
Dyn.Boost
) of 30A increases for 2s (t
After a recovery time (t
BaseLoad
Pause
) of 10A, the dynamic output
Dyn.Boost
) of 0.6s, the dynamic boost is
available once again.
Figure 29 Example recovery time for ≤40°C
).
Figure 27 Required recovery times at 40°C
12.2.2 Recovery times at an ambient temperature of 60°C
Figure 28 Required recovery times at 60°C
107101_en_01 PHOENIX CONTACT 32 / 50
QUINT4-PS/1AC/24DC/20
6x I
N
I
N
typ. 3 - 5 ms
0
I [A]
t [s]
-
+
-
+
l
Load
Power supply unit

13 SFB technology

SFBTechnology (selective fuse breaking) can be used to quickly and reliably trip miniature circuit breakers and fuses connected on the secondary side. In the event of a short circuit on the secondary side, the power supply supplies up to 6 times the nominal current for 15ms. The faulty current path is switched off selectively.
Loads that are connected in parallel are still supplied with energy. Operation of these system parts is ensured. In order to always enable the reliable tripping of circuit breakers and fuses, certain framework conditions must be observed (see SFB configuration section).
The U/IAdvanced output characteristic curve supports SFBtechnology.

13.1 Tripping circuit breakers

The circuit breaker is tripped by the high SFB current of the power supply, typically within 3 to 5ms. As a result, voltage dips at loads that are connected in parallel are avoided.

13.3 SFB configuration

Observe the following framework conditions for determining the maximum distance between the power supply and load:
The performance class of the power supply – The cross section of the connecting cable – The tripping characteristic of the fuse component
Figure 31 Schematic diagram of the maximum cable
length
Figure 30 SFB pulse trips circuit breakers

13.2 Tripping a fuse

Fuses are tripped by melting the predetermined breaking point inside the fuse capsule. The tripping characteristic of the fuse is described by the melting integral (I²t). A high current is crucial in order to achieve a very short tripping time.
107101_en_01 PHOENIX CONTACT 33 / 50
QUINT4-PS/1AC/24DC/20

13.4 Maximum distance between the power supply and load

The distances given in the table are worst-case values and therefore cover the entire tolerance range for the magnetic tripping of circuit breakers. The possible distances are often greater in practice.
13.4.1 Thermomagnetic device circuit breaker, type: Phoenix Contact CBTM1SFB
Maximum distance l [m] with device circuit
Conductor cross section
breaker
A [mm²] 0.75 1.0 1.5 2.5 4.0 6.0 AWG 18 (17) 16 14 12 10
Phoenix Contact CBTM11ASFBP 27365491<130<200
CBTM12ASFBP 18253763<100<140 CBTM13ASFBP 1318274673<100 CBTM14ASFBP 101421355786 CBTM15ASFBP 8 11 17 29 46 70 CBTM16ASFBP 6 8 12203248 CBTM18ASFBP -- 5 7 122030 CBTM110ASFBP--3481319
The cable lengths determined are based on the following parameters:
Tripping: magnetic DC correction factor (0 Hz): Phoenix Contact = 1,0 Characteristics: C Characteristic C (10 times the rated current) x correction factor Ambient temperature: +20°C Internal resistance R
of the device circuit
i
taken into consideration
breaker: Comments: In addition to the short-circuit current, the power supply unit also supplies
half the nominal current for load paths connected in parallel.
107101_en_01 PHOENIX CONTACT 34 / 50
QUINT4-PS/1AC/24DC/20
13.4.2 Thermomagnetic circuit breaker, type: Siemens 5SY, ABBS200
Maximum distance l [m] with circuit breaker Conductor cross section
A [mm²] 0.75 1.0 1.5 2.5 4.0 6.0 AWG 18 (17) 16 14 12 10
Siemens 5SY A1 78 105 157 263 420 631
ABB S200 B6 10 13 20 33 53 80
A1.6 58 77 116 194 311 467 A2 49 65 98 164 262 394 A3 35 47 71 118 190 285 A4 27 36 54 90 144 217 A6 18 25 37 62 100 150 A8 14 19 28 48 76 115 A10 111523386192 A13 8 11 16 27 44 66 A16 5 7 11183045 B2 28 37 56 93 149 224 B4 16 21 32 53 85 128 B6 10 14 21 36 57 86 B10 5 6 10172741 B13 3 4 6 10 16 24 C1 10 14 21 35 56 84 C1.6 12 17 25 42 68 102 C2 11 15 23 39 62 94 C3 9 1218304872 C4 6 8 12213451 C6 23591523 C8 12 17 25 42 68 102
B8 6 9 13223655 B10 4 5 8 14 23 35 B13 23581320 C1 3 4 6 11 17 26 C1.6 7 1015254162 C2 7 9 14233857 C3 8 1016264264 C4 4 6 9 16 26 39 C6 22471117 Z1 64 85 128 214 343 514 Z1.6 46 62 93 156 250 375 C2 42 57 85 143 229 343 C3 33 44 66 110 176 264 C4 24 33 49 82 132 198 C6 16 21 32 54 87 131 C10 101421365786 C16 4 6 9 16 26 39
The cable lengths determined are based on the following parameters:
Tripping: magnetic DC correction factor (0 Hz): Siemens = 1.4; ABB = 1.5 Characteristics: A, B, C, Z
Characteristic A (3 times the rated current) x correction factor Characteristic B (5 times the rated current) x correction factor Characteristic C (10 times the rated current) x correction factor Characteristic Z (3 times the rated current) x correction factor
Ambient temperature: +20°C Internal resistance R
of the device circuit
i
taken into consideration
breaker: Comments: In addition to the short-circuit current, the power supply unit also supplies
half the nominal current for load paths connected in parallel.
107101_en_01 PHOENIX CONTACT 35 / 50
13.4.3 Fuse, type: Cooper Bussmann GMAxA, GMCxA
QUINT4-PS/1AC/24DC/20
Maximum distance l [m] with fuse
Melting integral I²t [A²s]
Conductor cross section
A [mm²] 0.75 1.0 1.5 2.5 4.0 6.0 AWG 18 (17) 16 14 12 10
Cooper Bussmann GMA1A 0.48 48 64 97 162 259 389
GMA1.25A 0.84 36 49 73 122 196 294 GMA1.5A 1.6 26 35 53 88 142 212 GMA1.6A 2 23 31 47 79 127 190 GMA2A 3.1 19 25 38 63 101 152 GMA2,5A4.9 1520305181122 GMA 3A8.8 111522376090 GMA 3,15A 9.7 10 14 21 36 57 86 GMA 3,5A 13 9 12 18 31 49 74 GMA 4A19 6 8 12213451 GMA 5A 29 4 5 8 14 22 34 GMC1A 1.8 23 31 47 78 125 188 GMC 1,25A 3.4 17 23 34 58 93 140 GMC 1,5A 5.4 13 18 27 46 74 111 GMC1,6A 5.8 13 18 27 45 72 108 GMC 2A8.9 111422375989 GMC 2.5A 13 9 12 18 30 49 73 GMC 3A 19 6 8 12 21 34 51 GMC 3,15A 23 5 7 10 17 28 42 GMC 3,5A 25 4 6 9 16 26 39 GMC 4A 36 3 4 6 11 18 27
The cable lengths determined are based on the following parameters:
Tripping: thermal Characteristics: Cooper Bussmann GMA (fast-blow - fast acting) Cooper Bussmann GMC (medium-blow - medium time delay) Ambient temperature: +20°C Internal resistance R
of the fuse: taken into consideration
i
Comments: In addition to the short-circuit current, the power supply unit also supplies
half the nominal current for load paths connected in parallel.
107101_en_01 PHOENIX CONTACT 36 / 50
QUINT4-PS/1AC/24DC/20
> 100% Boost > 75%
> 50%
P
Out
U
Out
29,5V
24V
13 14
Rem
SGnd
Out 1 Out 2
DC OK
Signal
1
2
3
4
5
6
7
8
9

14 Signaling

A floating signal contact and two digital outputs are available for preventive function monitoring of the power supply. Depending on the configuration of the power supply, either the two digital outputs or one digital and one analog output can be selected. The signal outputs are electrically isolated from the input and output of the power supply.
The current device status of the power supply is signaled using four LED status indicators. The function of each LED status indicator is assigned to a fixed event.
In addition, the power supply can be switched off and on via an external circuit.
The signal outputs are configured on the software side using the QUINT POWER software or the QUINT POWER app. Upon delivery, the power supply is pre-allocated a default configuration for the signal outputs.

14.1 Location and function of the signaling elements

Figure 32 Position of signaling elements
Key
No. Signaling elements
1 13/14 floating switch contact (N/O contact) 2 Rem, remote input (switch power supply off and on) 3 SGnd, signal ground (reference potential for signals
Out1, Out2)
4 Out 1 (digital output, function depends on the signal
option set)
5 Out 2 (digital or analog output, function depends on
the signal option set)
6 LED status indicator DC-OK
LED on: U LED flashing: U
7 LED status indicator P
>240W)
8 LED status indicator P
>360W)
9 LED status indicator P
(output power >480W)
>90%xU
Out
Out
Set
<90%xU
Out
Out
Out
Set
>50 % (output power
>75 % (output power
>100 %, boost mode
107101_en_01 PHOENIX CONTACT 37 / 50
QUINT4-PS/1AC/24DC/20
13 14
Rem
SGnd
Out 1 Out 2
Signal
max.
30 V AC 500mA 24 V DC 1A
PLC
Digital Input
DI x
GND
13 14
Rem
SGnd
Out 1 Out 2
Signal
PLC
Digital Input
GND
DI x 0/24 V DC
DI x 0/24 V DC
13 14
Rem
SGnd
Out 1 Out 2
Signal
PLC
Analog Input
GND
AI x 4...20 mA

14.1.1 Floating signal contact

In the default configuration, the floating switch contact opens to indicate that the set output voltage has been undershot by more than 10% (U
<0.9xUN). Signals and
Out
ohmic loads can be switched. For heavily inductive loads (e.g.a relay), a suitable protective circuit (e.g.a freewheeling diode) is necessary.
Figure 33 Signaling

14.1.2 Active signal outputs, digital

Signals are forwarded to the higher-level controller via the "Out 1" and "Out 2" signal outputs.
The 24 V DC signal is applied between the connection terminal blocks "Out1" and "SGnd" or between "OUT2" and "SGnd". It can carry a maximum of 20mA.
By switching from "ActiveHigh" to "ActiveLow", the signal output "Out1" indicates that the set output voltage has been undershot by more than 10% (U
<0.9xUN).
OUT
In the default configuration, the signal output "Out2" indicates that the nominal power has been exceeded. The power supply then switches to boost mode. Thanks to this preventive function monitoring, critical operating states can be recognized at an early stage, prior to a voltage dip occurring.

14.1.3 Active analog signal output

The signal output "Out2" can be used as an analog signal output to continuously monitor the device workload.
The 4...20mA signal is applied between the connection terminal blocks "Out2" and "SGnd". It is proportional to the set signaling parameter.
Figure 35 Signaling
Figure 34 Signaling
107101_en_01 PHOENIX CONTACT 38 / 50
QUINT4-PS/1AC/24DC/20
V
A
P
000h
OVP
AC
OK

14.2 Preventive function monitoring

In contrast to the default signaling set upon delivery, you can customize this to the specific needs of the system. The following signal options can be selected to signal system states.
QUINT POWER default settings upon delivery Out1
digital
0/24VDC
20mA
Key
Output voltage 25...135%
90%
Output current 5...150%
100%
Output power 5...150%
100%
Operating hours 0... h
10years
Early warning of
high temperature
Voltage limitation
active
Input voltage OK 10ms after mains
Warning of
derating
Surge voltage at
output
failure
Default Default 0...32VDC
Out2
digital
0/24VDC
20mA
  ①0...30A
Default ①0...720W
 --
 --
 --
-- --
Relay 13/14
floating
24VDC/≤ 1A
30VAC/≤ 0.5A
Out2
analog
4...20mA
0...30VDC
0...20A
0...480W
Symbol Description
Setting range Default setting of the standard item
Default Configuration set upon delivery Configuration that can be selected
-- Configuration that cannot be selected
The simultaneous control of multiple signal outputs by means of one signal option is possible, as is the use of logic operations to link multiple signal options to one control. The power supply is configured using the QUINT POWER software or the QUINT POWER app.
107101_en_01 PHOENIX CONTACT 39 / 50
QUINT4-PS/1AC/24DC/20

14.3 Description of signaling

14.3.1 Output voltage

Signals whether the output voltage is in the preset range. If the output voltage of the power supply falls below the set threshold value, the signal state changes.
Example of use
Indicates whether the connected load is being supplied. Used to quickly detect a load circuit that is not being supplied (e.g.,in the event of mains failure or short circuit in the supply line).

14.3.2 Output current

If the output current of the power supply exceeds the set threshold value, the signal state changes.
Example of use
In the case of system extensions, loads are added. This increases the utilization of the power supply. Preventive function monitoring detects critical operating states in good time. Action can be taken before system downtime occurs.

14.3.3 Output power

If the output power of the power supply exceeds the set threshold value, the signal state changes.
Example of use
In the case of system extensions, loads are added. This increases the utilization of the power supply. Preventive function monitoring detects critical operating states in good time. Action can be taken before system downtime occurs.

14.3.4 Operating hours

If the preset operating time of the power supply is exceeded, the signal state changes.
is true if a control cabinet fan or cooling system fails. In the event of any form of overtemperature, the power supply provides a warning by means of this signal, well before the supply of the loads is in any danger.
Specifications regarding the available output power (see derating section).

14.3.6 Voltage limitation active

If the circuit inside the device for protecting against surge voltages is activated at the output, the signal state changes.
Example of use
Normative requirements stipulate that an upper voltage limit must be observed at the output in the event of an error. It must therefore be ensured, forexample, that safety-related controllers are not supplied with an output voltage that exceeds 32VDC, even in the event of an error. If foreign bodies (ferrules, screws, etc.) enter the power supply and generate an error, the signal state changes.

14.3.7 Input voltage OK

The power supply signals a mains failure at least 10ms before shutting off.
Example of use
In the event of a mains failure, the power supply continues to supply the load with nominal power for at least 20
ms. Failure of the input voltage is signaled 10ms before the output voltage falls, which means that this information is provided to the higher-level controller at an early stage. System states can therefore be stored promptly without any loss of data as a result of the unexpected failure of the supply voltage.
Example of use
For systems with a very long operating time, suchas wind turbine generators or refineries, maintenance intervals are planned. You can even schedule the maintenance date during configuration based on the ambient temperature and utilization of the power supply.

14.3.5 Early warning of high temperature

Before the power supply protects itself through power derating in the event of an overtemperature, the signal state changes.
Example of use
Outdoor control cabinets can reach a high internal temperature depending on the position of the sun. The same
107101_en_01 PHOENIX CONTACT 40 / 50
QUINT4-PS/1AC/24DC/20
13 14
Rem
SGnd
Out 1 Out 2
Signal
< 15 k
a)
b)
13 14
Rem
SGnd
Out 1 Out 2
Signal
< 40 k
a)
b)
13 14
Rem
SGnd
Out 1 Out 2
Signal
< 1 k
PLC
NPN output
Gnd
PLC
PNP output
Gnd
a)
b)

14.4 Remote input

The power supply is switched on and off using the digital remote input of the power supply. When switched off, power transmission is deactivated on the DC output side of the power supply. The load connected to the DC output terminal blocks is no longer supplied with energy. The operating mode where the DC output side is deactivated is called SLEEPMODE.
To switch the power supply to SLEEPMODE, select one of the external circuit versions below. The external circuit is wired between signal terminal blocks Rem (remote input) and SGnd (signalground).
Figure 36 External wiring versions, enable
SLEEPMODE
To switch the power supply back on, select one of the following external circuits between signal terminal blocks Rem and SGnd. Power transmission inside the device is activated again. As usual, the energy for supplying the loads is available at the DC output terminal blocks.
When using a PLC output, select the following external circuit version to switch the power supply to SLEEP MODE.
Figure 38 External wiring versions with PNP and NPN
output

14.5 LED status indicators

Four LED status indicators are integrated in the front of the power supply, which indicate the current device state.
The green DCOK LED indicates the current status of the output voltage (U long as the value of the output voltage U the value of the output voltage is <0.9xU
). The DCOK LED is permanently on as
Out
is ≥0.9xU
Out
, the green
Set
Set
. If
DCOK LED flashes. Depending on the required output power of the connected
load, the three P
LEDs, which indicate the current output
Out
power, light up. Assuming that the provided output power is >50% of the nominal output power, the >50% LED lights up green. If the demanded power continues to increase until it is above 75%, the >75% LED lights up green in addition to the >50% LED. If the required output power is then greater than the nominal device power, the power supply operates in boost mode. In boost mode, the >100%LED additionally lights up yellow.
Figure 37 External wiring versions, disable
SLEEPMODE
107101_en_01 PHOENIX CONTACT 41 / 50
QUINT4-PS/1AC/24DC/20
LED: DC OK
LED: P >100 %
Out
Signal Out 2: P < P
Out N
Relay: 13/14, DC OK
LED: P > 50 %
Out
Default
Default
P< P
Out N
U < 0.9 x U
Out Set
Signal Out 1: DC OK
LED: P > 75 %
Out
Active High
Active High
Active High
Active Low
Active Low Active Low
P> P
Out N
BOOST
green
yellow
closed closed
open
Normal operation
BOOST
Overload operation
LED flashing
LED off LED on
LED: DC OK
LED: P >100 %
Out
Signal Out 2: P < P
Out N
Relay: 13/14, DC OK
LED: P > 50 %
Out
Default
Default
P< P
Out N
U < 0.9 x U
Out Set
Signal Out 1: DC OK
LED: P > 75 %
Out
Active High
Active High
Active High
Active Low
Active Low
Active Low
P> P
Out N
BOOST
Green
Yellow
Closed
Closed Open
Normal operation
Overload operation
LED flashing
LED off LED on

14.6 U/I Advanced characteristic curve signaling

The following table shows the standard assignment for signaling for the U/I Advanced characteristic curves which is set by default.
Figure 39 Signal image for U/I Advanced

14.7 SMART HICCUP characteristic curve signaling

The following table shows the standard assignment for signaling for the SMART HICCUP characteristic curve.
Figure 40 Signal image for SMART HICCUP
107101_en_01 PHOENIX CONTACT 42 / 50
QUINT4-PS/1AC/24DC/20
LED: DC OK
LED: P >100 %
Out
Signal Out 2: P < P
Out N
Relay: 13/14, DC OK
LED: P > 50 %
Out
Default
Default
P< P
Out N
I > I t > t
Fuse Fuse
Signal Out 1: DC OK
LED: P > 75 %
Out
Active High
Active High
Active High
Active Low
Active Low
FUSE MODEBOOST
Active Low
P> P
Out N
Green
Yellow
Closed
Closed Open
Normal operation
LED flashing
LED off LED on
for

14.8 FUSE MODE characteristic curve signaling

The following table shows the standard assignment for signaling for the FUSE MODE characteristic curve.
Figure 41 Signal image for FUSEMODE
14.9 SLEEPMODE signaling
In SLEEP MODE, all LEDs are off, all signals are low, and the relay switching contact is open.
107101_en_01 PHOENIX CONTACT 43 / 50
QUINT4-PS/1AC/24DC/20
> 100% Boost > 75%
> 50%
POut
U
out
13 14
Rem Sgnd Out 1 Out 2
DC OK
Signal
PLC
Digital Input
GND
DI x 0/24 V DC
6
2
4
5
1
3
> 100% Boost > 75%
> 50%
POut
U
out
13 14
Rem Sgnd Out 1 Out 2
DC OK
Signal
PLC
Digital Input
GND
DI x 0/24 V DC
A1
A2
11
14
12
A1+
A2-
11/13(+)
14

14.10 Special immunity for the signal level

14.10.1 Surge protection for the high-voltage area at the power plant

Surge protection (Phoenix Contact Order No.: 2905223 or comparable protection) must be implemented for power plant applications when using signal connection types t (telecommunications area), h (high voltage area) or f (field) in accordance with IEC/EN61850-3 or signal connection types 3 (process area) and 4 (high voltage area) in accordance with EN61000-6-5.
When using the digital signals, a relay (Phoenix Contact Order No.: 2900299 or a comparable relay) can be implemented.

14.10.2 Surge protection for signals in railway applications

Surge protection (Phoenix Contact Order No.: 2905223 or comparable protection) must be implemented for railway applications when using signals in accordance with EN62236-4 and EN50121-4.
When using the digital signals, a relay (Phoenix Contact Order No.: 2900299 or a comparable relay) can be implemented.

14.10.3 Surge protection for devices in use in safety-related systems

Surge protection (Phoenix Contact Order No.: 2905223 or comparable protection) must be implemented for railway applications when using signals in accordance with EN61000-6-7 for devices provided to perform functions in safety-related systems (functional safety) in industrial settings.
When using the digital signals, a relay (Phoenix Contact Order No.: 2900299 or a comparable relay) can be implemented.
Figure 42 Schematic diagram, signal wiring with TRABTECH surge protection
Figure 43 Schematic diagram, signal wiring with relay module
107101_en_01 PHOENIX CONTACT 44 / 50
QUINT4-PS/1AC/24DC/20
+
-
+
-
-48 V
+
-
+
-
-24 V
+24 V
+
-
+
-
+48 V
+
I
N
+
I
N
+
+
Σ = I
N

15 Operating modes

15.1 Series operation

To double the output voltage, connect two power supplies in series. Only use power supplies with the same performance class and configuration for series operation. If two 24 V DC power supplies are connected in series, an output voltage of 48VDC is available to supply the loads.
Figure 44 Schematic diagrams in series operation

15.2 Parallel operation

You can connect several power supplies in parallel in order to increase the power or to supply the loads redundantly.
Figure 45 Schematic diagram in parallel operation
Observe the following points when carrying out parallel connection:
1. Use power supplies of the same type and performance class
2. Setting the same output voltages
3. Using the same cable cross sections for wiring
4. Using the same cable lengths for the DC convergence point
5. Operating power supplies in the same temperature environment
6. When three or more power supplies are connected in parallel, each output must be protected (e.g.,with circuit breakers, fuses or decoupling modules)
We recommend the configuration "parallel operation" for a parallel connection. For more detailed information on the operating mode for parallel operation, refer to the user manual for the QUINT POWER software or the QUINT POWER app.
107101_en_01 PHOENIX CONTACT 45 / 50
QUINT4-PS/1AC/24DC/20
+
I
N
+
I
N
+
+−−
Σ = I
N
+
I
N
+
I
N
+
Σ = I
N
+–
I
N
+–
I
N
+
+–
IΣ =2xI
N

15.2.1 Redundancy operation

Redundant circuits are suitable for supplying systems and system parts which place particularly high demands on operational reliability.
If energy is to be supplied to the load with 1+1 redundancy, two power supplies of the same type and performance class must be used. In the event of an error, it must be ensured that one of the power supplies is able to provide the total required power for the load. This means that in redundancy mode, two 20A power supplies supply a load with a nominal current of 20 A, forexample. During normal operation of the power supplies, each power supply therefore supplies 10A.
Always use cables with the same cross sections and lengths when wiring the power supplies on the DC output side.
Redundancy modules can be used to 100%decouple two power supplies from one another and to ensure the supply. A distinction is made here between passive and active redundancy modules. Optimum decoupling with simultaneous monitoring and minimal power dissipation can be achieved with the QUINTORING or QUINTS-ORING active redundancy module.
redundancy operation, the power supplies are operated with maximum half the nominal power. The keepout areas are therefore reduced.
Using the signaling settings, you can monitor whether both power supplies are being operated with half the nominal load. In the case of system extension, an overload is prevented if one of the power supplies fails.

15.2.2 Increased power

When n power supplies are connected in parallel, the output current is increased to n x I
. Parallel connection for
N
increased power is used when extending existing systems. If the individual power supply does not cover the current consumption of the most powerful load, parallel connection of power supplies is recommended.
When three or more power supplies are connected in parallel, each output must be protected separately, e.g.,by a circuit breaker, fuse or decoupling module such as QUINTORING, QUINT S-ORING or QUINTDIODE.
Figure 46 Schematic diagram, redundant operation with
QUINTORING
Figure 48 Schematic diagram of increased performance
Figure 47 Schematic diagram, redundant operation with
QUINT S-ORING
Certain specifications apply in redundancy operation with regard to the configuration of the keepout areas. In
107101_en_01 PHOENIX CONTACT 46 / 50
QUINT4-PS/1AC/24DC/20
T [°C]
A
P [W]
Out
40 60 70
P
Stat. Boost
P
N
100%
125%
P
Dyn. Boost
150%
75%
-25
H [m]
[%]
0
25
50
75
100
125
150
175
P
Out
  
= P 125 % 40 °C
Stat.
= P
Dyn.
150 % 60 °C
= P
N
100 % 60 °C
0 1000 2000 3000 4000 5000

16 Derating

The QUINTPOWER power supply runs in nominal operation without any limitations. For operation outside the nominal range, the following points should be observed depending on the type of use.

16.1 Ambient temperature

When operating the power supply at an ambient temperature of >60°C, a power derating of 2.5%/K should be observed. Up to an ambient temperature of40°C, the power supply can take power from the static boost for a sustained period. In the 40°Cto60°C temperature range, the power supply can output more than the nominal power for a sustained period.

16.3 Installation height

The power supply can be operated at an installation height of up to 2000m without any limitations. Different data applies for installation locations above 2000m due to the differing air pressure and the reduced convection cooling associated with this (see technical data section). The data provided is based on the results of pressure chamber testing performed by an accredited test laboratory.
Figure 50 Output power depending on the installation
height
Figure 49 Output power depending on the ambient
temperature

16.2 Input voltage

Derating 1 %/V
U
In
< 100 V AC < 110 V DC < 115 V AC < 110 V DC
107101_en_01 PHOENIX CONTACT 47 / 50
T
A
≤60°C I
≤40°C I
I
Out
Stat. Boost
N
U
Out
24 V DC
QUINT4-PS/1AC/24DC/20
T [°C]
[%]
0
25
50
75
100
125
150
175
-25 0 10203040506070
  
= P 125 %
Stat.
= P
Dyn.
150 %
= P
N
100 %
P
Out
Z
X
Y
NFC
QUINT POWER
> 100%
Boost
> 75% > 50%
Pout
13 14
Rem
SGnd
Out 1 Out 2
> 50% DC OK
U
O u
t
Signal
Z
X
Y
NFC
Q
UIN
T PO
W
ER
> 100% Boost
> 75%
> 50%
Pout
13
14
Rem
SGnd
Out 1
Out 2
> 100% Boost
> 75%
> 50%
DC OK
U
Out
13
14
Rem
SGnd
Out 1
Out 2
Signal
T [°C]
[%]
0
25
50
75
100
125
150
175
-25 0 10203040506070
  
= P 125 %
Stat.
= P
Dyn.
150 %
= P
N
100 %
P
Out

16.4 Position-dependent derating

The fanless convection-cooled power supply can be snapped onto all DIN rails according to EN60715.
The power supply should be mounted horizontally for heat dissipation reasons (AC connection terminal blocks facing downward). Please observe the derating for any mounting other than the normal mounting position. Reduce the output power based on the prevailing ambient temperature.
The recommended output power for different mounting positions and ambient temperatures can be found in the characteristic curves below.
Exceeding these values will reduce the service life of the power supply.

16.4.1 Normal mounting position

16.4.2 Rotated mounting position 90° Z-axis

107101_en_01 PHOENIX CONTACT 48 / 50

16.4.3 Rotated mounting position 180° Z-axis

T [°C]
[%]
0
25
50
75
100
125
150
175
-25 0 10203040506070
  
= P 125 %
Stat.
= P
Dyn.
150 %
= P
N
100 %
P
Out
Z
X
Y
N
F
C
QUINT POWER
> 100% Boost
> 75%
> 50%
Pout
13
14
Rem
SGnd
Out 1
Out 2
> 100% Boost
> 75%
> 50%
DC OK
U
O
ut
13
14
Rem
SGnd
Out 1
Out 2
Signal
Z
X
Y
M
3x8
NFC
Q
U
IN
T PO
W
ER
> 100% Boost
> 75%
> 50%
Pout
13
14
Rem
SGnd
Out 1
Out 2
> 100% Boost
> 75%
> 50%
DC OK
U
Out
13
14
Rem
SGnd
Out 1
Out 2
Signal
T [°C]
[%]
0
25
50
75
100
125
150
175
-25 0 10203040506070
  
= P 125 %
Stat.
= P
Dyn.
150 %
= P
N
100 %
P
Out

16.4.4 Rotated mounting position 270° Z-axis

QUINT4-PS/1AC/24DC/20
107101_en_01 PHOENIX CONTACT 49 / 50

16.4.5 Rotated mounting position 90° X-axis

Z
X
Y
T [°C]
[%]
0
25
50
75
100
125
150
175
-25 0 10203040506070
  
= P 125 %
Stat.
= P
Dyn.
150 %
= P
N
100 %
P
Out
Z
X
Y
T [°C]
[%]
0
25
50
75
100
125
150
175
-25 0 10203040506070
  
= P 125 %
Stat.
= P
Dyn.
150 %
= P
N
100 %
P
Out
M3x8
NFC
Q
U
IN
T PO
W
ER
> 100% Boost
> 75%
> 50%
Pout
13
14
Rem
SGnd
Out 1
Out 2
> 100% Boost
> 75%
> 50%
DC OK
U
O
ut
13
14
Rem
SGnd
Out 1
Out 2
Signal

16.4.6 Rotated mounting position 270° X-axis

QUINT4-PS/1AC/24DC/20
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
107101_en_01 50 / 50
Loading...