This data sheet is only valid in
association with the "Configuring and
Installing the INTERBUS Inline
Product Range" User Manual
IB IL SYS PRO UM E.
This bus terminal replaces the
IBS IL 24 BK-T bus terminal, which
was supplied until now (see page 7).
10/2001
Function
The bus terminal connects an Inline station to the
INTERBUS remote bus and provides the supply
voltages for the connected devices.
Features
6 2 9 1 A 0 0 1
6 2 9 1 A 0 0 2
–Remote bus connections using copper
cables
–Can supply an Inline station with all of the
required 24 V voltages for low-level signals
–Electrical isolation of the remote bus
segments
–Automatic configuration of the outgoing
interface as remote bus interface or local bus
interface
–Support of up to 15 connected terminals with
remote bus branch
6291A1
Figure 1IBS IL 24 BK-T/U terminal with
connectors and end plate
Please note that the connectors are
not supplied as standard with the
terminal. To order these connectors,
please refer to the "Ordering Data" on
page 22.
The end plate is supplied with the bus terminal.
Place this plate at the end of the Inline station.
The end plate does not have any electrical
function. It protects the station from ESD pulses
and the user from dangerous voltage.
IBS IL 24 BK-T/U
B A
R D
U LU S
R C
L D
B K - T / U
6 2 9 1 A 0 0 3
U M
Figure 2Diagnostic indicators on the IBS IL 24 BK-T/U terminal
Local Diagnostic Indicators
Des.ColorMeaning
BAGreen Bus active
RCGreen Remote bus cable check
RDYellow Outgoing remote bus switched off
LDYellow Local bus switched off
ULGreen 24 V bus terminal supply/7.5 V communications power/interface supply
USGreen 24 V segment supply
UMGreen 24 V main supply
26291A
IBS IL 24 BK-T/U
1 2
1 . 1
1
1 . 2
2
1 . 3
3
1 . 4
4
2 . 1
1
2 . 2
2
2 . 3
3
2 . 4
4
1 2
1 . 1
1
1 . 2
2
1 . 3
3
1 . 4
4
2 . 1
1
2 . 2
2
2 . 3
3
2 . 4
4
5 5 6 0 0 0 0 5
Figure 3Terminal point assignment
Terminal Point Assignment
Terminal
Point
AssignmentRemark/
Wire Color in the INTERBUS Standard Cable
Connector 1 Incoming Remote Bus
1.1DO1
ReceiveGreen
2.1DO1ReceiveYellow
1.2DI1
SendPink
2.2DI1SendGray
1.3F-GNDReference
Brown
potential
2.3Not used
1.4, 2.4ShieldShield potential is connected with a capacitor to functional
earth ground (FE) of the potential jumper.
Connector 2 Outgoing Remote Bus
1.1DO2
SendGreen
2.1DO2SendYellow
1.2DI2
ReceivePink
2.2DI2ReceiveGray
1.3R-GNDReference
Brown
potential
2.3Not used
1.4, 2.4ShieldShield potential is directly connected to functional earth
See Figure 6 on page 10
external reconfiguration
button
1.2, 2.224 V DCU
BK
24 V bus terminal supply
Supply of the bus terminal power supply unit
1.3, 2.3BK-GNDGNDGND of the bus terminal supply
This potential is reference ground for the bus terminal
electronics.
1.4, 2.4FEFunctional
earth
ground
Grounding of the bus terminal, i.e., of the Inline station
The contacts are directly connected with the potential
jumper and the FE spring on the bottom of the housing.
Functional earth ground is only used to
discharge interference.
Connector 4 Power Connector
1.1, 2.124 V DCU
S
24 V segment supply
The supplied voltage is directly led to the potential jumper.
1.2, 2.224 V DCU
M
24 V main supply
The supplied voltage is directly led to the potential jumper.
1.3, 2.3GNDReference
potential
The reference potential is directly led to the potential
jumper and is, at the same time, ground reference for the
main and segment voltage.
1.4, 2.4FEFunctional
earth
ground
Grounding of the bus terminal, i.e., of the Inline station
The contacts are directly connected with the potential
jumper and the FE spring on the bottom of the housing.
46291A
Functional earth ground is only used to
discharge interference.
IBS IL 24 BK-T/U
Do not mix up the connectors
Do not mix up the connectors, especially the remote bus connectors and connectors for
the voltage supply, as this may damage the terminal.
Observe the current carrying capacity
The maximum total current of the potential jumpers U
and US is 8 A.
M
Ground the bus terminal
Connect the bus terminal to functional earth ground (FE) via one of the FE connections of
connector 3 or connector 4. Connect the corresponding contact with a grounding terminal
block (see also Figure 6 on page 10).
6291A5
IBS IL 24 BK-T/U
Technical Data
General Data
Order DesignationIBS IL 24 BK-T/U
Order No.2742094
Housing dimensions (width x height x depth)48.8 mm x 120 mm x 71.5 mm
(1.921 in. x 4.724 in. x 2.815 in.)
Weight142 g (without connectors)
Permissible temperature (operation)-25°C to +55°C (-13°F to +131°F)
Permissible temperature (storage/transport)-25°C to +85°C (-13°F to +185°F)
Permissible humidity (operation)75% on average, 85% occasionally
In the range from -25°C to +55°C (-13°F to +131°F) appropriate measures against
increased humidity (> 85%) must be taken.
Permissible humidity (storage/transport)75% on average, 85% occasionally
For a short period, slight condensation may appear on the outside of the housing if, for
example, the terminal is brought into a closed room from a vehicle.
Permissible air pressure (operation)80 kPa to 106 kPa
(up to 2000 m [6562 ft.] above sea level)
Permissible air pressure (storage/transport)70 kPa to 106 kPa
(up to 3000 m [9843 ft.] above sea level)
Degree of protectionIP 20 according to IEC 60529
Class of protectionClass 3 according to VDE 0106, IEC 60536
Interfaces (INTERBUS)
Remote Bus
Incoming remote busCopper cable (RS-422), connected with Inline
shield connector; supply electrically isolated;
shielding connected with a capacitor to functional
earth ground
Outgoing remote busCopper cable (RS-422), connected with Inline
shield connector; supply electrically isolated;
shielding directly connected to functional earth
ground
Recommended cable lengthsSee INTERBUS system data
126291A
Interfaces (INTERBUS) (Continued)
Branch/Local Bus
ConnectionThrough data routing
Level5 V CMOS signal level
Number of Inline terminals that can be connected
IBS IL 24 BK-T/U
Limitation through software
Limitation through power supply unit
63, maximum
Maximum logic current consumption of the
connected local bus modules: I
2 A DC
max
Observe the current consumption of the modules
Observe the logic current consumption of each device when configuring an Inline station.
This information is given in every module-specific data sheet. The current consumption
can differ depending on the individual module. The permissible number of devices that
can be connected depends on the specific station structure.
Functions
Reconfiguration (external)If necessary, you can connect an external
reconfiguration button to the bus terminal (see
Figure 6 on page 10).
Pressing this button activates the reconfiguration
request to the controller board.
Interface configuration (internal)When the next device is snapped on, the bus
terminal configures the interface automatically.
If the next device is a terminal with remote bus
branch, the interface is configured as a remote
bus interface.
For every other device (e.g., I/O terminal) the
interface is configured as a local bus interface
with diagnostics.
6291A13
IBS IL 24 BK-T/U
24 V Main Supply/24 V Segment Supply
ConnectionThrough power connector
For terminal point assignment see page 3
Connection methodSpring-clamp terminals
Recommended cable lengths30 m (98.43 ft.), maximum; do not route cable
through outdoor areas
Voltage continuationThrough potential routing
Special demands on the voltage supplyU
terminal supply U
are electrically isolated from the bus
M/US
if they are supplied
BK
separately. This is only possible when using two
separate power supply units.
Behavior if voltage dips and interrupts occurVoltages (main and segment supply) that are
transferred from the bus terminal to the potential
jumpers follow the supply voltages without delay.
Nominal value24 V DC
Tolerance-15%/+20% (according to EN 61131-2)
Ripple±5%
Permissible range19.2 V to 30 V
Current carrying capacity8 A, maximum
Safety measures
Surge voltageYes
Polarity reversalYes
Provide an external fuse for the 24 V area
This 24 V area must be fused externally. The power supply unit must be able to supply 4
times the nominal current of the external fuse, to ensure that the fuse blows safely in the
event of an error.
146291A
IBS IL 24 BK-T/U
24 V Bus Terminal Supply
ConnectionThrough connector
For terminal point assignment see page 3
Connection methodSpring-clamp terminals
Recommended cable lengths30 m (98.43 ft.), maximum; do not route cable
through outdoor areas
Voltage continuationThrough potential routing
Special demands on the voltage supplyThe bus terminal supply U
isolated from U
when it is supplied
M/US
is electrically
BK
separately. This is only possible when using two
separate power supply units.
Nominal value24 V DC
Tolerance-15%/+20% (according to EN 61131-2)
Ripple±5%
Permissible range19.2 V to 30 V
Minimum current consumption at nominal voltage 0.10 A DC
(At no-load operation, i.e., incoming remote bus
connected, no local bus devices are connected,
bus inactive)
Maximum current consumption at nominal voltage 1.25 A DC
Consisting of:
0.75 A DC for communications power
0.5 A DC for analog voltage supply
Safety measuresOnly for the bus terminal supply
Surge voltageYes
Polarity reversalYes
Provide an external fuse for the 24 V area
This 24 V area must be fused externally. The power supply unit must be able to supply 4
times the nominal current of the external fuse, to ensure that the fuse blows safely in the
event of an error.
6291A15
IBS IL 24 BK-T/U
24 V Module Supply
Communications Power (Potential Jumper)
Nominal value7.5 V DC
Tolerance±5%
Ripple±1.5%
Maximum output current2 A DC (observe derating)
Safety measuresElectronic short-circuit protection
Communications Power (Interfaces)
Nominal value2 x 5 V DC
Tolerance±5%
Ripple±1.5%
Maximum output current2 x 0.15 A DC
Safety measuresNone
Communications Power (Internal)
Nominal value1 x 5 V DC
Tolerance±5%
Ripple±1.5%
Maximum output current1 x 0.15 A DC
Safety measuresNone
Analog Supply (Potential Jumper)
Nominal value24 V DC
Tolerance-15%/+20%
Ripple±5%
Maximum output current0.5 A DC (observe derating)
Safety measuresElectronic short-circuit protection
166291A