Phoenix Contact IB IL 24/230 DOR 4/W-PC, IB IL 24/230 DOR 4/W-PC-PAC Datasheet

IB IL 24/230 DOR 4/W-PC IB IL 24/230 DOR 4/W-PC-PAC
Inline Terminal With Four Relay Changeover Contacts
Data Sheet 6530B
The IB IL 24/230 DOR 4/W-PC and IB IL 24/230 DOR 4/W-PC-PAC only differ in the scope of supply (see "Ordering Data" on page 17). Their function and technical data are identical.
For greater clarity, the Order Designation IB IL 24/230 DOR 4/W-PC is used throughout this document.
This data sheet is only valid in association with the IB IL SYS PRO UM E User Manual or the Inline System Manual for your bus system.
03/2003
Function
The terminal is designed for use within an Inline station. It has four electrically isolated relay changeover contacts. The terminal is suitable for switching inductive and capacitive loads.
6 3 2 6 A 0 0 1
Features
Safe isolation according to EN 50178 – Electrically isolated connection for four actuators – Nominal current at the output: 3 A – Total current of the terminal: 4 x 3 A = 12 A – LED diagnostic and status indicators
The terminal can be used in the SELV area and in the AC area. Observe the appropriate regulations and safety notes when using the terminal in the AC area.
Please use the IB IL 24/230 DOR 4/W terminal for switching voltages less than 12 V or currents less than 100 mA.
6530B 1
6 3 5 0 A 0 0 2
Figure 1 IB IL 24/230 DOR 4/W-PC terminal with
connectors
IB IL 24/230 DOR 4/W-PC (-PAC)
Safety Notes Correct Usage
Safety notes for Inline terminals for installation in voltage ranges outside the SELV (AC area)
Only qualified personnel may work on Inline terminals in the AC area.
Qualified personnel are people who, because of their education, experience, and instruction and their knowledge of relevant standards, regulations, accident prevention, and service conditions, have been authorized by those responsible for the safety of the plant to carry out any required operations and who are able to recognize and avoid any possible dangers. (Definitions for skilled workers according to EN 50110-1:1996.)
The instructions given in the IB IL SYS PRO UM E User Manual or the Inline System Manual for your bus system and in this data sheet must be followed during installation and startup.
The terminal is only to be used within an Inline station as specified in this data sheet and the IB IL SYS PRO UM E User Manual or the Inline System Manual for your bus system. Phoenix Contact accepts no liability if the device is used for anything other than its designated use.
Dangerous voltage
Please note that there are dangerous voltages when switching circuits that do not meet SELV requirements.
Only remove and insert the AC terminals when the power supply is disconnected. When working on terminals and wiring, always switch off the supply voltage and ensure it cannot be switched on again.
Installation Instructions and Notes
Install the system according to the requirements of EN 50178.
Technical modifications reserved.
2 6530B
Please use grounded AC networks
Inline AC terminals must only be operated in grounded AC networks.
Read the user manual
Please observe the installation instructions and installation notes in the IB IL SYS PRO UM E User Manual or the Inline System Manual for your bus system, especially the information about the low voltage area.
Special Features of the IB IL 24/230 DOR 4/W-PC Terminal
Loads up to 230 V can be switched using the IB IL 24/230 DOR 4/W-PC terminal.
Please note that the IB IL 24/230 DOR 4/W-PC terminal interrupts the potential jumpers U and GND (24 V area) as well as L and N (120 V/230 V areas). If required, these supply voltages must be reintroduced/ provided after the relay terminal using an appropriate power terminal.
Switching Loads in the 230 V Area
To switch voltages outside the SELV area, an AC area must be created corresponding to the installation instructions and notes given in the user manual.
, US,
M
IB IL 24/230 DOR 4/W-PC (-PAC)
Operation on an AC network
Operate the terminal from a single phase on an AC network.
Switching Voltages That Are Not Available in the Segment
A relay terminal can be used to switch voltages that are not available in the segment in which the terminal is located (e.g., switching 230 V AC within a 24 V DC segment). In this case, place a distance terminal before and after the IB IL 24/230 DOR 4/W-PC terminal (see "Ordering Data" on page 17). The isolating distances between the individual areas are thus maintained.
See also "Connection Examples" on page 6.
6530B 3
IB IL 24/230 DOR 4/W-PC (-PAC)
General Description
D
1
2
3
4
D O R 4 / W
Local LED Diagnostic and Status Indicators
Des. Color Meaning
D Green Diagnostics
1, 2,
3, 4
Yellow Output status indicator
(relay has picked up)
Terminal Assignment for Each Connector
1 2
1 . 1
1
1 . 2
2
1 . 3
3
1 . 4
4
2 . 1
1
2 . 2
2
2 . 3
3
2 . 4
4
Figure 2 IB IL 24/230 DOR 4/W-PC
with an appropriate connector
Function Identification
Red with lightning bolt
6 5 3 0 A 0 0 3
Terminal
Assignment
Points
1.1, 2.1 Not used
(no contact present)
1.2, 2.2 Relay N/C contact
1.3, 2.3 Relay main contact
1.4, 2.4 Relay N/O contact
In the corresponding connector IB IL SCN-8-AC-REL, the adjacent contacts
1.2/2.2, 1.3/2.3, and 1.4/2.4 are jumpered. It is therefore possible to transmit the power to
supply several relays of IB IL 24/230 DOR 4/W-PC terminals from one connector to the next via a jumper.
Please note that the current at one terminal point must not exceed 8 A.
Housing/Connector Color
Gray housing Gray connector
4 6530B
Internal Circuit Diagram
IB IL 24/230 DOR 4/W-PC (-PAC)
L o c a l b u s
U
L
Figure 3 Internal wiring of the terminal points
O P C
4
4
6 5 3 0 A 0 0 4
Key:
OPC
Protocol chip (bus logic including voltage conditioning)
Other symbols are explained in the IB IL SYS PRO UM E User Manual or in
LED
the Inline System Manual for your bus system.
Terminal point, without metal contact
Relay
FE or PE depending on the area in which the terminal is used
Electrically isolated area I/O area including relay contact isolated from the logic area including the relay coil through "safe isolation" according to EN 50178.
6530B 5
IB IL 24/230 DOR 4/W-PC (-PAC)
Connection Examples
Connecting Actuators
1
2
3
4
1
3
D O R 4 /W
1 2
1
D
2
4
1 2
1
1
2
2
3
3
4
4
3 4
2
1 2
1 2
1
1
1
1
1
2
2
2
2
2
3
3
3
3
3
4
4
4
4
4
N / C c o n t a c t
M a i n c o n t a c t
N / O c o n t a c t
N / O c o n t a c t
M a i n c o n t a c t
N / C c o n t a c t
6 3 2 6 A 0 0 5
Figure 4 Typical connection of actuators
N / C
1 . 2
c o n t a c t M a i n c o n t a c t
1 . 3
1 . 4
N / O
c o n t a c t
5 6 6 3 A 0 0 9
Figure 5 Output relay contacts
6 6530B
IB IL 24/230 DOR 4/W-PC (-PAC)
Switching Voltages That Are Not Available in the Segment
1
D
1
2
3
4
D O R 4 /W
1 2
1 2
1
1
1
2
2
2
3
3
3
4
4
4
1 2
1 2
1
1
2
2
3
3
4
4
1 2
1 2
1 2
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
1 2
1 2
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
32
U M
P W R I N
1 2
1
1
2
2
3
3
4
4
1 2
1
1
2
2
3
3
4
4
6 3 2 6 A 0 0 6
1 2
1
1
2
2
3
3
4
4
Figure 6 Example: Switching 230 V within a
24 V area
Switching Voltages That Are Available in the Segment
The distance terminals are not required to switch a 24 V channel within a 24 V area or to switch a 230 V channel within a 230 V area.
1
1
2
3
1 2
4
1 2
1
1
2
3
4
1
1
2
2
2
3
3
3
4
4
4
D
1
2
3
4
D O R 4 /W
1 2
1 2
1 2
1 2
1
1
1
1
1
1
1
2
2
2
2
2
2
2
3
3
3
3
3
3
3
4
4
4
4
4
4
4
U M
P W R I N
1 2
1 2
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
32
1 2
1 2
1
1
1
2
2
3
3
4
4
1
1
2
2
2
3
3
3
4
4
4
1 24 V area consisting of station head and
I/O terminals
2 IB IL 24/230 DOR 4/W-PC terminal
separated from the 24 V area by distance terminals
3 24 V area consisting of a power terminal and
I/O terminals
See also "Special Features of the IB IL 24/ 230 DOR 4/W-PC Terminal" on page 3.
Distance terminals can also be used to switch a 24 V channel within a 230 V area.
6 3 2 6 A 0 0 7
Figure 7 Switching 24 V within a 24 V area
1 24 V area consisting of station head and
I/O terminals 2 IB IL 24/230 DOR 4/W-PC terminal 3 24 V area consisting of a power terminal and
I/O terminals
6530B 7
IB IL 24/230 DOR 4/W-PC (-PAC)
Interference Suppression Measures on Inductive Loads/Switching Relay
Each electrical load is a mixture of ohmic, capacitive, and inductive elements. Depending on the proportion of the element, switching these loads results in a larger or smaller load on the switch contact.
In practice, loads are generally used with a large inductive element, such as contacts, solenoid valves, motors, etc. Due to the energy stored in the coils, voltage peaks of up to several thousand volts may occur when the system is switched off. These high voltages cause an arc, which may destroy the controlling contact through material evaporation and material transfer.
This pulse, which is similar to a square wave pulse, emits electromagnetic pulses over a wide frequency range with a large amount of power and with spectral elements reaching several MHz.
To prevent such arcs from occurring it is necessary to fit the contacts/loads with protective circuits. The following protective circuits can be used:
Contact protective circuit Load protective circuit Combination of both protective circuits
If sized correctly, these circuit versions do not differ greatly in their effectiveness. In principle, a protective measure should be directly implemented at the source of the interference. In addition, the following points should be observed for a load protective circuit:
When the contact is open, the load is electrically
isolated from the operating voltage.
It is not possible for the load to be activated or to
"stick" due to undesired operating currents, e.g., from RC elements.
Shutdown voltage peaks cannot be coupled in
control lines that run in parallel.
Phoenix Contact provides protective circuit solutions in terminal format or in electronic housing (see the "CLIPLINE" catalog or "TRABTECH" catalog). Additional information is available on request. In addition to this, today the majority of contact manufacturers offer diode, RC or varistor elements that can be snapped on. For solenoid valves, connectors with an integrated protective circuit can be used.
A B
Figure 8 Contact protective circuit (A), load
protective circuit (B)
8 6530B
5 9 7 3 A 0 2 8
Circuit Versions
IB IL 24/230 DOR 4/W-PC (-PAC)
P r o t e c t i n g t h e l o a d
D i o d e
+
L o a d
S e r i e s c o n n e c t i o n d i o d e / z e n e r d i o d e
+
L o a d
S u p p r e s s o r d i o d e
+
( ~ )
( ~ )
L o a d
U
D
U
Z D
U
Z D
A d d i t i o n a l
d e l a y
L o n g
M e d i u m t o s h o r t
M e d i u m t o s h o r t
D e f i n e d
I n d u c t i o n
V o l t a g e
L i m i t a t i o n
Y e s ( U )
D
Y e s ( U )
Z D
Y e s ( U )
Z D
B i p o l a r
E f f e c t i v e
A t t e n u a t i o n
N o
N o
Y e s
A d v a n t a g e s /
D i s a d v a n t a g e s
A d v a n t a g e s :
- E a s y i m p l e m e n t a t i o n
- C o s t - e f f e c t i v e
- P e r m i t t e d
- U n c r i t i c a l s i z i n g
- L o w i n d u c t i o n v o l t a g e
D i s a d v a n t a g e s :
- A t t e n u a t i o n o n l y v i a l o a d r e s i s t o r
- H i g h d e l a y
A d v a n t a g e s :
- U n c r i t i c a l s i z i n g
D i s a d v a n t a g e s :
- A t t e n u a t i o n o n l y a b o v e U
A d v a n t a g e s :
- C o s t - e f f e c t i v e
- U n c r i t i c a l s i z i n g
- L i m i t s p o s i t i v e p e a k s
- S u i t a b l e f o r A C v o l t a g e
D i s a d v a n t a g e s :
- A t t e n u a t i o n o n l y a b o v e U
Z D
Z D
V a r i s t o r
+
( ~ )
( ~ )
L o a d
6530B 9
V D R
A d v a n t a g e s :
- H i g h p o w e r a b s o r p t i o n
M e d i u m
U
V D R
t o s h o r t
Y e s ( U )
V D R
Y e s
- U n c r i t i c a l s i z i n g
- S u i t a b l e f o r A C v o l t a g e
D i s a d v a n t a g e s :
- A t t e n u a t i o n o n l y a b o v e U
V D R
5 6 6 3 A 0 2 9
IB IL 24/230 DOR 4/W-PC (-PAC)
RC Circuit Versions
RC Connected in Series:
P r o t e c i t n g t h e L o a d
R / C c o m b i n a t i o n
+
( ~ )
( ~ )
L o a d
R
C
U
R C
Sizing:
Capacitor: C L
Load
/4 × R
Resistor: R 0.2 × R
RC Parallel Circuit With Series Diode
P r o t e c t i n g t h e l o a d
A d d i t i o n a l
D e l a y
M e d i u m t o s h o r t
Load
Load
A d d i t i o n a l
D e l a y
D e f i n e d
I n d u c t i o n
V o l t a g e
B i p o l a r
E f f e c t i v e
A t t e n u a t i o n
A d v a n t a g e s / D i s a d v a n t a g e s
L i m i t a t i o n
A d v a n t a g e s :
- H F a t t e n u a t i o n v i a p o w e r s t o r e
- S u i t a b l e f o r A / C v o l t a g e
N o
2
D e f i n e d
I n d u c t i o n
V o l t a g e
Y e s
B i p o l a r
E f f e c t i v e
A t t e n u a t i o n
- L e v e l - i n d e p e n d e n t a t t e n u a t i o n
- R e a c t i v e - c u r r e n t c o m p e n s a t i n g
D i s a d v a n t a g e s :
- E x a c t d i m e n s i o n r e q u i r e d
- H i g h i n r u s h c u r r e n t
5 6 6 3 A 0 3 0
A d v a n t a g e s / D i s a d v a n t a g e s
L i m i t a t i o n
R / C c o m m u n i c a t i o n w i t h d i o d e
+
( ~ )
( ~ )
L o a d
C
R
M e d i u m
N o
Y e s
t o s h o r t
U
R C
- H F a t t e n u a t i o n v i a p o w e r s t o r e
- L e v e l - i n d e p e n d a n t a t t e n u a t i o n
- C u r r e n t i n v e r s i o n n o t p o s s i b l e
D i s a d v a n t a g e s :
- E x a c t d i m e n s i o n r e q u i r e d
- O n l y s u i t a b l e f o r D C v o l t a g e
A d v a n t a g e s :
5 6 6 3 A 0 3 1
Sizing:
Capacitor: C L
Load
/4 × R
Resistor: R 0.2 × R
Load
Load
2
10 6530B
Switching AC/DC Loads
Switching Large AC Loads
When switching large AC loads, the relay can be operated up to the corresponding maximum values for switching voltage, current, and power. The arc that occurs during shutdown depends on the current, voltage, and phase angle. This shutdown arc switches off automatically the next time the load current passes through zero.
In applications with an inductive load, an effective protective circuit must be provided, otherwise the life of the system will be reduced considerably.
To prolong the life of the IB IL 24/230 DOR 4/W-PC terminal as mush as possible when using lamp loads or capacitive loads, the current peak must not exceed 6 A when the load is switched on.
IB IL 24/230 DOR 4/W-PC (-PAC)
1 0 0 0
V
1 0 0
U
1 0
1 0 . 1 1 1 0
Figure 9 DC load limiting curve
(REL-SNR-1XU/G 5 GOLD relay)
A
I
5 6 6 3 A 0 1 3
Switching Large DC Loads
In DC operation, a relay can only switch a relatively low current compared with the maximum permissible alternating current. This maximum direct current value is also highly dependent on the voltage and is determined in part by design conditions, such as the contact distance and contact opening speed.
The corresponding current and voltage values are shown in Figure 9.
I Switching current in A U Switching voltage in V
Definition of the load limiting curve: For 1000 cycles, no constant arc should occur with a burning life >10ms.
An unattenuated inductive load further reduces the values given here for switching currents. The energy stored in the inductivity can cause an arc to occur which forwards the current via the open contacts. Using an effective contact protective circuit in relay contacts with the same life enables you to switch currents that are virtually the same as with ohmic loads.
If it is permitted to switch higher DC loads, several relay contacts can be switched in parallel.
Additional technical data is available on request.
6530B 11
IB IL 24/230 DOR 4/W-PC (-PAC)
Programming Data/Configuration Data
INTERBUS
ID code BD Length code 41 Process data channel 4 bits Input address area 0 bits Output address area 4 bits Parameter channel (PCP) 0 bits Register length (bus) 4 bits
Other Bus Systems
For the configuration data of other bus systems, please refer to the appropriate electronic device data sheet (GSD, EDS).
hex
hex
(189
dec
)
Process Data
Assignment of Terminal Points to OUT Process Data
(Byte.bit) view
AssignmentSlot 4321
Status indicator
Bit 0.3 0.2 0.1 0.0
N/C contact 1.2 1.2 1.2 1.2 Main contact 1.3 1.3 1.3 1.3 N/O contact 1.4 1.4 1.4 1.4 LED 4321
If the bits are set to 1, the corresponding N/O contact is closed.
The LEDs light up, if the corresponding N/O contact is closed.
For the assignment of the illustrated (byte.bit) view for your INTERBUS control or computer system, please refer to data sheet DB GB IBS SYS ADDRESS, Part No.9000999.
12 6530B
IB IL 24/230 DOR 4/W-PC (-PAC)
Technical Data
General Data
Order Designation (Order No.) IB IL 24/230 DOR 4/W-PC-PAC (28 62 18 1)
IB IL 24/230 DOR 4/W-PC (28 60 41 3)
Housing dimensions (width x height x depth) 48.8 mm x 120 mm x 71.5 mm
(1.921in. x 4.724 in. x 2.815 in.) Weight 138 g (without connectors) Operating mode Process data mode with 4 bits Type of actuator connection To an electrically isolated relay changeover contact Permissible temperature (operation) -25°C to +55°C (-13°F to +131°F) Permissible temperature (storage/transport) -25°C to +85°C (-13°F to +185°F) Permissible humidity (operation) 75% on average, 85% occasionally
In the range from -25°Cto+55°C (-13°F to +131°F) appropriate measures against increased humidity (> 85%) must be taken.
Permissible humidity (storage/transport) 75% on average, 85% occasionally
For a short period, slight condensation may appear on the outside of the housing if, for example, the terminal is brought into a closed room from a vehicle.
Permissible air pressure (operation) 80 kPa to 106 kPa
(up to 2000 m [6562 ft.] above sea level) Permissible air pressure (storage/transport) 70 kPa to 106 kPa
(up to 3000 m [9843 ft.] above sea level) Degree of protection IP 20 according to IEC 60529
Mechanical Requirements (Deviation From the Inline Specifications)
Vibration test
2g load, 2 hours for each space direction sinusoidal vibrations according to IEC 60068-2-6; EN 60068-2-6
Shock test according to IEC 60068-2-27; EN 60068-2-27
2g load for 11 ms, half sinusoidal wave,
three shocks in each space direction and orientation
Interface
Local bus Through data routing
Power Consumption
Communications power 7.5 V Current consumption from the local bus off/on 22 mA/187 mA Power consumption from the local bus 0.17 W/1.4 W
Supply of the Module Electronics and I/O Through Bus Terminal/Power Terminal
Connection method Through potential routing
6530B 13
IB IL 24/230 DOR 4/W-PC (-PAC)
Relay output
Number 4 Contact material AgSnO2, hard gold-plated Contact resistance 50 m at 100 mA/6 V Limiting continuous current
3 A
(at maximum ambient temperature) Maximum switching voltage 253 V AC, 250 V DC Maximum switching power (AC/DC) 750 VA (see derating) Minimum load 5 V; 10 mA Switching current at 30 V DC 3 A Switching current at 250 V DC 0.15 A Maximum inrush current peak for lamp loads and
6 A for T = 200 µs
capacitive loads
See also the Table entitled "Maximum Switching Current for Ohmic Load Depending on the Switching Voltage" on page 15.
Nominal power consumption of the coil (at 20°C [68°F]) 330 mW from the 7.5 V supply Resistance of the coil (at 20°C [68°F]) 119 ±12 Maximum switching frequency (without load) 1200 cycles/minute Maximum switching frequency (with nominal load) 6 cycles/minute Response delay 5 ms, typical Bouncing time 5 ms, typical Release time 6 ms, typical Mechanical life 2 x 10 Electrical life 10
7
cycles
5
cycles
(at 20 cycles/minute)
Common potentials All contacts electrically isolated
14 6530B
IB IL 24/230 DOR 4/W-PC (-PAC)
Maximum Switching Current for Ohmic Load Depending on the Switching Voltage (With Direct Voltage)
Switching Voltage (V DC) Switching Current (A)
53.0 10 3.0 20 3.0 30 3.0 40 1.0 50 0.4 60 0.3 70 0.26 80 0.23 90 0.215
100 0.2 150 0.18 200 0.165 250 0.155
Load Current (I
in A) as a Function of the Switching Voltage (U
L
switch
in V)
3
A
2 . 5
I
L
2
1 . 5
1
0 . 5
0
1 0 2 0
3 0
4 0 5 0 6 0
7 0 8 0
9 0
1 0 0
1 5 0
U
s w i t c h
2 0 0
5 6 6 3 A 0 0 4
V
2 5 0
6530B 15
IB IL 24/230 DOR 4/W-PC (-PAC)
Maximum Switching Current Depending on the Temperature (With Alternating Voltage)
With a switching current of 3 A, the switching voltage with alternating current must not exceed 253 V AC. Observe the derating.
Load Current (I
3
A
2 . 5
2
I
L
1 . 5
1
0 . 5
0
in A) as a Function of the Ambient Temperature (TA in °C)
L
1 0 2 0
3 0
4 5 ° C
4 0 5 0
T
A
Power Dissipation Formula to Calculate the Power Dissipation in the Terminal
P
= P
EL
PEL = 0.17 W + 4 x ((0.31 W) + I
BUS
+ (P
REL
) + P
L
For N/C contacts, the term P
2
x 0.04 Ω)
L
is omitted from the formula.
REL
5 5
6 3 2 6 A 0 0 8
Where P P P P I
EL BUS REL L
L
Total power dissipation in the terminal Power dissipation through bus operation Power dissipation of the relay coil Power dissipation through the load current via the contacts Load current of the output
Power Dissipation of the Housing Depending on the Ambient Temperature
P
= 2.7 W -25°C (-13°F) < TA +25°C (+77°F)
HOU
P
= 2.7 W - ((TA - 25°C [77°F]) x 0.02 W/°C) +25°C (+77°F) < TA +55°C (+131°F)
HOU
Where P T
HOU A
Permissible power dissipation of the housing Ambient temperature
16 6530B
IB IL 24/230 DOR 4/W-PC (-PAC)
Safety Measures
None
Error Messages to the Higher-Level Control or Computer System
None
Air and Creepance Distances (According to EN 50178, VDE 0109, VDE 0110) Isolating Distance Clearance Creepance
Distance
Relay contact/bus logic 5.5 mm
(0.217 in.)
Contact/contact 3.1 mm
(0.122 in.)
Contact/PE 3.1 mm
(0.122 in.)
5.5 mm (0.217 in.)
3.1 mm (0.122 in.)
3.1 mm (0.122 in.)
Ordering Data
Test Voltage
4 kV, 50 Hz, 1 min.
1 kV, 50 Hz, 1 min.
1 kV, 50 Hz, 1 min.
Description Order Designation Order No.
Terminal with four relay changeover contacts;
IB IL 24/230 DOR 4/W-PC-PAC 28 62 18 1
including connectors and labeling fields Terminal with four relay changeover contacts IB IL 24/230 DOR 4/W-PC 28 60 41 3
Four connectors are required for the complete fitting of the IB IL 24/230 DOR 4/W-PC-PAC terminal.
Connector with seven terminals, spring-cage connection
IB IL SCN-8-AC-REL 27 40 29 0 (gray, w/o color print); pack of 10
Distance terminals
IB IL DOR LV-SET 27 42 64 1 (isolation of various voltage areas); pack of 1 set (2 pcs.)
Connector for IB IL DOR LV-SET;
IB IL DOR LV-PLSET 27 42 66 7 pack of 1 set (2 pcs.)
"Configuring and Installing the INTERBUS Inline Product
IB IL SYS PRO UM E 27 43 04 8 Range" User Manual
Make sure you always use the latest documentation. This is available on the Internet at www.phoenixcontact.com
.
6530B 17
IB IL 24/230 DOR 4/W-PC (-PAC)
Phoenix Contact GmbH & Co. KG Flachsmarktstr. 8 32825 Blomberg Germany
+49 - 52 35 - 30 0 +49 - 52 35 - 34 12 00
www.phoenixcontact.com
Worldwide Locations:
www.phoenixcontact.com/salesnetwork
18 6530B
TNR 90 11 32 6
Technical modifications reserved.
© Phoenix Contact 03/2003
Loading...