COAXTRAB Surge Voltage
Protection Adapter CN-UB-280DC
For wireless data, signal and mobile
phone system protection
Installation Instructions 2098A
June 2005
1.Introduction
The Phoenix Contact COAXTRAB CN-UB-280DC
(see Figure 1) is a gas-filled surge protection device
designed to protect wireless radio and module phone
base stations from surge voltages caused by lightning
or other electrical sources that are induced onto antenna cables.
The CN-UB-280DC is available in two configurations;
one with N-type male/female connectors and the other
with N-type female/female connectors.
CN-UB-280DC-SB
PN 28 18 14 8
Male N-type
Connection
2098A003
Female N-type
Connection
Figure 1. CN-UB-280DC Configurations
CN-UB-280DC-BB
PN 28 18 85 0
Female N-type
Connection
Female N-type
Connection
The gas discharge tube can be replaced in the event
that a direct lightning strike causes a failure. See
Figure 3.
COAXTRAB Surge
Voltage Protection
Adapter
Gas Arrester Tube
Access Hole
Gas Arrester Tube
PN 2818203
Threaded Cap
2098A015
Figure 3. CN-UB-280DC Gas Discharge Arrester
The CN-UB-280DC has a separate ground terminal for
installations where nonmetallic enclosures are used or
where a reliable grounding surface is not present.
See Figure 4.
CAUTION
Always keep the ground wire as short as
possible and, when possible, make all
ground connections to a single common
point. Without a single-point ground system,
lightning becomes a critical concern for base
stations. The single-point ground insures
that no ground loops are created.
The CN-UB-280DC features a gas-filled discharge arrester between the inner and outer conductor. See
Figure 2.
N-type
Socket
20 kA
Gas
Discharge
Shield/Housing
Earth Ground
Connection
Arrester
Figure 2. CN-UB-280DC Schematic Diagram
Phoenix Contact Inc. • P.O. Box 4100 • Harrisburg, PA 17111 • Phone: (717) 944-1300 • FAX: (717) 944-1625
N-type
Socket
2098A008
1
COAXTRAB Surge
Voltage Protection
Adapter
M3 Grounding
2098A017
Screw
Figure 4. CN-UB-280DC Ground Connection
Instructions 2098A
Page 2
2.Typical Applications
Figure 5 shows the various ways that you can install
the CN-UB-280DC adapter.
Stand Alone
Straight Bracket
Right-angle Bracket
Figure 5. CN-UB-280DC Applications
3.Mounting Brackets and
Assemblies
Through-hole
2098A002
Phoenix Contact offers two mounting brackets
(straight and right angle) and four mounting bracket
assemblies, which include both the bracket and the
adapter. Figure 6 shows a typical CN-UB-280DC
adapter assembly using a straight mounting bracket.
Coaxial
Cable
N-type Female
Connector
N-type Male
Connection
M4 (5/32-in)
Mounting Screw
Straight
Mounting
Bracket
2098A004-1
14 – 16 AWG
Spade-type
Wire Terminal
14 – 16 AWG
Ground Wire
14 – 16 AWG
Wire Terminal
As Required
Internal tooth
Lock Washer
M3
Phillipshead
Screw
Internal tooth
Lock Washer
19 mm
Hex-head
Nut
Figure 6. Straight Mounting Bracket Assembly
Figure 7 shows a typical adapter assembly using a
right-angled mounting bracket. Refer to the Ordering
Data at the back of these instructions for individual or
assembly part numbers.
Coaxial
Cable
N-type Male
Connector
N-type Female
Connection
Right-angle
Mounting
Bracket
2098A004-2
M4 (5/32-in)
Mounting Screw
14 – 16 AWG
Spade-type
Wire Terminal
14 – 16 AWG
Ground Wire
14 – 16 AWG
Wire Terminal
As Required
(not supplied)
Internal tooth
Lock Washer
M3
Phillipshead
Screw
Internal tooth
Lock Washer
19 mm
Hex-head
Nut
Figure 7. Right-angle Mounting Bracket Assembly
Phoenix Contact Inc. • P.O. Box 4100 • Harrisburg, PA 17111 • Phone: (717) 944-1300 • FAX: (717) 944-1625
Instructions 2098A
2
Page 3
4.Typical Cabinet Installation
Figure 8 shows a typical CN-UB-280DC installation inside a cabinet. To avoid problems, please observe
the following guidelines when installing the CN-UB280DC adapter.
•Install adapter as close as possible to the radio.
•Ensure cabinet is properly grounded to earth.
•Make sure adapter is grounded to cabinet. If
necessary, install separate ground wire.
•Always make ground wire as short as possible.
•When possible, connect ground wire to singlepoint earth ground.
•Avoid loops in grounding wire.
•Avoid making sharp bends in wire.
Antenna
N-type Male
Coneector
CN-UB-280DC
Adapter
16 mm (0.629 in.)
Diameter Hole
N-type Male
Coneector
Antenna Adapter
Cable from
Wireless Radio
To
Antenna
M3 Phillips-head Screw
with Lock washer (Accepts
14 to 16 AWG Ring or Spade
Terminals)
14 to 16 AWG
Ground Wire (see Caution)
1/8 to 1/4-in.
Cap Screw, and
Lock washer
14 to 16 AWG
Wire Terminal
To
Single-point
Earth Ground
CAUTION
Always cut ground wire to size. Do not
let additional length coiled in installation.
2098A007
Phoenix Contact Inc. • P.O. Box 4100 • Harrisburg, PA 17111 • Phone: (717) 944-1300 • FAX: (717) 944-1625
Figure 8. Typical Cabinet Installation
3
Instructions 2098A
Page 4
5.Dimensions
Figures 9 through 12 provide dimensions for each
mounting bracket and for each of the CN-UB-280DC
mounting bracket assemblies.
6.6 mm (0.260 in.)
4.77 mm (0.187 in.)
16 mm
30 mm
(0.639 in.)
(1.181 in.)
10.325 mm
(0.406 in.)
20.65 mm
(0.813 in.)
72 mm
(2.834 in.)
20 mm
(0.787 in.)
27 mm
(1.062 in.)
Figure 9. Straight Mounting Bracket Dimensions
Male“N”Connector
50 mm
(1.968 in.)
Straight
Mounting
Bracket
35 mm
(1.377 in.)
67 mm
(2.637 in.)
5.2 mm (0.205 in.)
Dia. Hole (3 places)
2 mm
(0.078 in.)
Female“N”Connector
17 mm
(0.669 in.)
27 mm
(1.062 in.)
2098A012
Straight
Mounting
Bracket
23 mm
(0.905 in.)
Female“N”Connector
COAXTRAB
CN-UB-280DC-SB
Figure 10. Adapter and Straight Mounting Bracket Assembly Dimensions
Phoenix Contact Inc. • P.O. Box 4100 • Harrisburg, PA 17111 • Phone: (717) 944-1300 • FAX: (717) 944-1625
1. Using a blade type screwdriver remove the
threaded cap from the adapter housing. See
Figure 13. Then remove and discard the gas
arrester tube from the housing.
COAXTRAB
Surge Voltage
Protection Adapter
Recess
Gas Arrester Tube
Access Hole
Gas Arrester Tube
PN 2818203
Gas Tube
Threaded Cap
2098A005
Figure 13. CN-UB280DC Gas Arrester Replacement
Note
Ω
The threaded cap contains a recess that
positions the gas arrester tube in the center
of the access hole. If the gas arrester tube
is not positioned in this recess while installing
the threaded cap, the arrester will not seat
properly and the threaded cap will not screw
completely into the housing.
If you experience a problem installing the
gas arrester tube, remove the COAXTRAB
adapter from the system. Then position the
adapter as shown in Figure 13 and install
the gas arrester tube.
2. Insert the replacement gas arrester tube in the
recess of the threaded cap. Then carefully
insert the gas arrester tube and cap into the
access hole of the adapter and tighten the cap.
Phoenix Contact Inc. • P.O. Box 4100 • Harrisburg, PA 17111 • Phone: (717) 944-1300 • FAX: (717) 944-1625
Instructions 2098A
6
Page 7
8.Ordering Data
Figure 14 shows identifies the various parts, assemblies and accessories that are available for the COAXTRAB CN-UB-280DC adapter. Table 2 lists the order
1
2098A016
2
numbers for each of these component. To order, refer
to the Phoenix Contact web site listed on the back of
these instructions to locate a distributor near you.
3
4
5
6
CAUTION
Always cut ground wire to size. Do not
let additional length coiled in installation.
91078
Figure 14. CN-UB280DC Surge Voltage Protector Parts and Accessories
Table 2. Parts List for Figure 14 (CN-UB-280DC)
Item
No.
COAXTRAB surge voltage adapter, coaxial N-type connectors,
1
2
3
4
Components
5
6
7
8
9
Assemblies
10
*Recommended spare part
NOTE:
Adapters are also available in F-type connectors. Contact Phoenix ContactTechnical Services at 1-800-322-3225 or
visit our web site at www.phoenixcon.com/trabtech.
female/female
COAXTRAB surge voltage adapter, Coaxial N-type connectors,
male/female
Mounting bracket, straight
Mounting bracket, right angle
Ground wire, 1.5 meter length, 16 AWG with ring lug
Gas arrester tube
COAXTRAB surge voltage adapter assembly, includes straight bracket
COAXTRAB surge voltage protection adapters are available with 7/16-in.connectors upon request.
Description
CN-UB-280DC-BB
CN-UB-280DC-SB
CN-UB/MP
CN-UB/MP-90 DEGREE
C-UFB-PA
CN-UB-G1
CN-UB-280DC-BB-BH ASSY
CN-UB-280DC-SB-BH ASSY
CN-UB-280DC-BB-L ASSY
CN-UB-280DC-SB-L ASSY
Type
Order No.
28 18 85 0
28 18 14 8
28 18 13 5
56 04 83 8
27 62 36 2
28 18 20 3*
56 03 85 9
56 02 35 7
56 05 58 8
56 05 58 7
2098A010
Phoenix Contact Inc. • P.O. Box 4100 • Harrisburg, PA 17111 • Phone: (717) 944-1300 • FAX: (717) 944-1625
7
Instructions 2098A
Page 8
Theinformationgivenherein isbasedon databelievedtobe reliable,but Phoenix
Contact Inc. makes no warranties expressed or implied as to its accuracy and
assumes no liability arising out of itsuse by others.This publication is not to be
takenasalicense tooperateunder,orrecommendationto infringe,anypatent.