Philips SM40, LBB 1350, LBB 1330, LBB 1350/30 Instructions For Use Manual

Philips Communication & Security Systems
SM40
Sound Distribution System
LBB 1350/30
Instructions for use
IMPORTANT SAFETY INSTRUCTIONS
i
1. Read instructions - All the safety and Instructions for use should be read before the system is operated.
2. Retain instructions - The safety and instructions for use should be retained for future reference.
3 Heed warnings -All warnings on the unit and in the operating instr uctions should be
adhered to.
4. Follow instructions - All operating and instructions for use should be followed.
5. Cleaning - Unplug system units from the mains outlet before cleaning. Do not use
liquid cleaners or aerosol cleaners. Use a damp cloth for cleaning.
6. Attachments - Do not use attachments not recommended by the product manufacture as they may cause hazards.
7. Water and Moisture - Do not use this unit near water for example, near a bath tub, wash bowl, kitchen sink, or laundry tub, in a wet basement, near a swimming pool, in an unprotected outdoor installation, or any area which is classified as a wet location.
8. Accessories - Do not place this unit on an unstable stand, tripod, bracket, or mount. The unit may fall, causing serious injury to a person and serious damage to the unit. Use only with a stand, tripod, bracket, or mount recommended by the manufacturer, or sold with the product. Any mounting of the unit should follow the manufacturer’s instructions, and should use a mounting accessory recommended by the manufacturer.
An appliance and cart combination should be moved with care. Quick stops, excessive force, and uneven surfaces may cause the appliance and cart combination to over tur n.
9. Ventilation - Openings in the enclosure, if any, are provided for ventilation and to ensure reliable operation of the unit and to protect it from overheating. These openings must not be blocked or covered. The unit should not be placed in a built-in installation unless proper ventilation is provided or the manufacturers instructions have been adhered to.
10. Power sources - Units should be operated only from the type of power source indicated on the marking label. If you are not sure of the type of power supply you plan to use, consult your appliance dealer or local power company. For units intended to operate from battery power, or other sources, refer to the instructions for use.
11. Grounding or polarization - This unit may be equipped with a polarized alternating current line plug (a plug having one blade wider than the other). This plug will fit into the power outlet only one way. This is a safety feature. If you are unable to insert the plug fully into the outlet, try reversing the plug. If the plug still does not fit, contact your electrician to replace your obsolete outlet. Do not defeat the safety purpose of the polarized plug. Alternatively, this unit may be equipped with a 3-wire grounding type plug, a plug having a third (grounding) pin. This plug will only fit into a grounding-type power outlet. This is a safety feature. If you are unable to insert the plug into the outlet, contact your electrician to replace your obsolete outlet. Do not defeat the safety purpose of the grounding-type plug.
12. Power-Cord Protection - Power supply cords should be routed so that they are not likely to be walked on or pinched by items placed upon or against them, paying particular attention to cords and plugs, convenience receptacles, and the point where they exit from the appliance.
13. Overloading - Do not overload outlets and extension cords as this can result in a risk of fire or electrical shock.
14. Object and Liquid Entry - Never push objects of any kind into this unit through openings as they may touch dangerous voltage points or short-out parts that could result in a fire or electric shock. Never spill liquid of any kind on the unit.
15. Servicing - Do not attempt to ser vice this unit your self as opening or removing covers may expose you to dangerous voltage or other hazards. Refer all servicing to qualified service per sonnel.
16. Damage Requiring Service - Unplug the unit from the outlet and refer servicing to qualified service per sonnel under the following conditions: a. When the power-supply cord or plug is damaged. b. If liquid has been spilt, or objects have fallen into the unit c. If the unit has been exposed to rain or water. d. If the unit does not operate normally by following the instructions for use. Adjust
only those controls that are covered by the instructions for use, as an improper adjustment of other controls may result in damage and will often require extensive
work by a qualified technician to restore the units to their normal operation. e. If the unit has been dropped or the units has been damaged. f. When the unit exhibits a distinct change in performance - this indicates a need for
service.
17. Replacement Parts - When replacement par ts are required be sure the service technician has used replacement parts specified by the manufacturer or have the same characteristics as the original part. Unauthorized substitutions may result in fire, electric shock or other hazards.
18. Safety Check - Upon completion of any service or repairs to the units, ask the service technician to perform safety checks to determine that the unit is in proper operating condition.
19. Coax Grounding - If an outside cable system is connected to the unit, be sure the cable is grounded, U.S.A. models only - Section 810 of the National Electrical Code, ANSI/NFPA No.70-1981, provides information with respect to proper grounding of the mount and supporting str ucture, grounding of the coax to a discharge unit, size of grounding conductors, location of discharge unit, connection to grounding electrodes, and requirements for the grounding electrode.
20. Lightning - For added protection of the units during a lightning storm, or when it is left unattended and unused for long periods of time, unplug it from the wall outlet and disconnect the cable system. This will prevent damage to the unit due to lightning and power-line sur ges.
FCC and ICES INFORMATION
(U.S.A and Canadian Models only)
WARNINGS - This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules and ICES-003 of Industry Canada. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Intentional or unintentional changes or modifications not expressly approved by the party responsible for compliance shall not be made. Any such changes or modifications could void the user’s authority to operate the equipment.
If necessary, the user should consult the dealer or an experienced radio/television technician for corrective action. The user may find the following booklet prepared by the Federal Communications Commission helpful: “How to identify and Resolve Radio-TV Interference Problems”. This booklet is available from the U.S. Government Pr inting Office, Washington, DC 20402, Stock No. 004-000-00345-4.
SAFETY PRECAUTIONS
This label may appear on the bottom of the unit due to space limitations.
The lightning flash with an arrowhead symbol, with an equilateral triangle, is intended to alert the user to the presence of uninsulated ‘dangerous voltage’ within the products enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons.
The exclamation mark within an equilateral triangle is intended to alert the user to the presence of important oper ating and maintenance (servicing) instructions in the literature accompanying the appliance.
Attention: Installation should be performed by qualified service per sonnel only in accordance with the National Electrical Code or applicable local codes.
Power Disconnect: Units with or without ON-OFF switches have power supplied to the unit whenever the power cord is inserted into the power source; however, the unit is operational only when the ON-OFF switch is in the ON position. The power cord is the main power disconnect for all units.
Warning: To prevent fire or shock hazard, do not expose units not specifically designed for outdoor use to rain or moisture.
CAUTION: TO REDUCE THE RISK OF ELECTRICAL SHOCK, DO NOT OPEN COVERS. NO USER SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.
ALL SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE. INFORMATION FURNISHED BY PHILIPS COMMUNICATION & SECURITY SYSTEMS. (PCSS) IS BELIEVED TO BE ACCURATE AND RELIABLE. HOWEVER, NO RESPONSIBILITY OR LIABILITY IS ASSUMED BY PCSS FOR ITS USE, NOR FOR ANY INFRINGEMENTS OR PATENTS OR OTHER RIGHTS OF THIRD PARTIES WHICH MAY RESULT FROM ITS USE. NO LICENSE IS GRANTED BY IMPLICATION OR OTHERWISE UNDER ANY PATENT OR OTHER RIGHTS OF PCSS
© 1997 by Philips Electronics N.V. All Rights Reserved. Philips® is a registered trademark of Philips Electronics North America Corporation. Marca(s) Registrada(s).
© 1997 All rights strickly reserved. Reproduction by third parties in any form is strickly forbidden, unless prior written authorisation has been given. In the continuing quest for product improvement Philips reserves the right to change the specification of any article or system without prior notice.
SM40 SOUND DISTRIBUTION SYSTEM
ii
This page has been left blank intentionally
TABLE OF CONTENTS
iii
1. GENERAL INTRODUCTION AND OPERATING PRINCIPLES
1.1 Introduction
1.2 Operating Principles
2. SYSTEM UNPACKING AND INSTALLATION
2.1 Unpacking and installation
2.2 Power Supply Modules
3. SM 40 BASIC SYSTEM AND EXTENSION FRAME
3.1 Basic System - BS LBB 1350/30
3.2 Extension Frame - EF LBB 1360/30
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4.1 Central Processor Card - CPC
4.2 Display and Keyboard - DK
4.3 SM40 Programming
4.3.1 User Programming Menu
4.3.2 Error Messages
4.3.3 Status Display
4.3.4 Installer Programming Menu
5. SM40 MODULES
5.1 Interconnection Board - IB
5.2 Termination Board
5.2.1 Termination Board - TB LBB 1377
5.2.2 Matrix Termination Board - MTB LBB 1371
5.2.3 Relay Termination Board - RTB LBB 1379
5.3 Input Card - IPC LBB 1351
5.4 Signal Generator Card - SGC LBB 1354
5.5 Matrix Card - MC LBB 1355
5.6 Control Relay Card - CRC LBB 1356
5.7 Tone Control Card - TCC LBB 1357
5.8 Signal Processing Card - SPC LBB 1358
5.9 Automatic Volume Control Card - AVC LBB 1359/00, /09, /21
5.9.1 Automatic Noise Dependent Volume Control (AVC)
5.9.2 Automatic Noise Dependent Audio Signal Processing (ANDAP)
5.9.3 Procedural Description
5.10 Surveillance Switch Card - SSC LBB 1374 (Appl. Ext. Audio Source Control)
5.11 Digital Message Card - DMC LBB 1378
5.11.1 Recording and Playback
5.12 Call Station - CST LBB 9567
5.12.1 Special Applications
5.13 I/O Port (Communications Link) - I/O LBB 1375/30
6. REMOTE PROGRAMMING PROTOCOL
6.1 Introduction
6.1 Data Protocols
7. TECHNICAL DATA
1. GENERAL INTRODUCTION AND OPERATING PRINCIPLES
1
1.1 Introduction
To meet the demand for a comprehensive public address distribution system, a new concept, built around 19 inch rack mounted Euro card circuit boards, has been developed.
Being controlled by a microprocessor, the system is particularly flexible, specific functions being easily programmed and changed by non technical personnel. In order to meet differing application needs a variety of circuit cards are available and a wide range of system configurations are possible.
The total public address distribution system comprises: Call stations; a 19 inch rack unit, containing a microprocessor controlled SM40 centre; and SQ45 power amplifiers. These in turn feed loudspeakers located in geographical and/or functional zones where people must be reached with background music, announcements alarm signals and evacuation messages
The SM40 Distribution centre is fed by professional microphones mounted on Call Stations. Each Call station contains up to 10 user keys, which can be programmed to route the microphone calls, digitally stored messages, attention tones or alarm signals to one or several power amplifiers.
Because the SM4O centre is designed to handle many different commands simultaneously, a system of priorities has been developed to cope with conflict situations. A person attempting to call a zone already being called by someone with a higher priority will not be switched through, and is warned by a red (busy) LED mounted on the Call station. If the zone is clear to call, or is being called by a station with a lower priority, a green (talk) LED is illuminated and any lower priority calls are overridden.
All wiring in the SM40 system is particularly installer friendly. Two core screened microphone cable is used between call stations and central racks, and standard loudspeaker cable between power amplifiers and loudspeakers.
The basic (starter) system, LBB 1350, which can be fed by a maximum of 3 call stations, comprises: 1x Input Card; 1x Central Processing Card; the Display and Keyboard (which is mounted on the front panel); 1x Signal Generator Card; 1x Matrix Card; 1x Control Relay Card; 1x power supply; plus 1x Interconnection Board and 3x Termination Boards; tested and mounted in a 19 inch rack frame. The basic system is capable of controlling 8 amplifiers to feed a maximum of 8 loudspeaker zones.
The single 19 inch rack frame, capable of holding 10 circuit cards, has enough room to accommodate the basic system plus 5 extra cards. Adding these cards expands the basic system, enabling it to be fed by additional Call Stations and auxiliary inputs, and to feed more amplifiers.
When a system’s requirements exceed the space offered in a single rack frame, SM40 Extension Frame LBB 1360 is available. This comprises: 1x power supply; 1x Interconnection Board; and 5x Termination Boards; tested and mounted in a 19 inch rack frame. 10 SM40 circuit cards fit into each Extension Frame, and these frames can be linked together to expand the system.
In a maximum configuration, the distribution centre can accept (via a 16 x 64 matrix) up to 16 audio inputs to feed up to 64 individual amplifier inputs, or (via a 32 x 32 matrix) up to 32 audio inputs to feed up to 32 amplifiers. The basic system is expandable to a maximum of:
8 Input Cards,
32 Matrix Cards,
16 Control Relay Cards (128 make and break contacts).
16 Digital Message Cards,
8 Signal Generator Cards
Plus associated:
Tone Control Cards,
Automatic Volume Control Cards,
Signal Processing Cards.
Background music can be supplied by a background music player or from a radio tuner, compact disc player, cassette deck, etc..
1. GENERAL INTRODUCTION AND OPERATING PRINCIPLES
1-1
1
1. GENERAL INTRODUCTION AND OPERATING PRINCIPLES
1-2
1
1. GENERAL INTRODUCTION AND OPERATING PRINCIPLES
1-3
1
The system, being capable of handling several different signals at the same time, is also ideally suited to situations where a number of music sources are fed to the same loudspeaker location simultaneously. Typical applications are hospitals, hotels and nursing homes, where it is required that a choice of music channels are selectable at each individual loudspeaker cabinet.
Various timer facilities allow tones, recorded messages, and music to be both switched in and routed at specific times of the day. Days of the week are also selectable.
An ambient noise dependent volume control function is available for installations where continually changing background noise levels are a problem (e.g. airports, sport stadiums).
As an optional extra, an I/O -PCB is available, which allows the SM40 system to be coupled to a personal computer via a standard RS232 serial interface. Depending on the software applied the computer can be used in the ‘active’ or ‘passive’ mode. In the passive mode you can read or record the static information (system configuration, sources connected) and the ‘dynamic’ information (call logging, auxiliar y routing, failure information). In the ‘active’ mode you can use the computer for up/down loading of the programme, to program the matrix, or even to operate as a Call station or Master Call station.
Because of their integral music/announcement relays, SQ45 amplifiers are ideally matched to the SM40 centre. During an announcement the preset music level can be automatically overridden, while the announcement itself comes through at the normal level.
1. GENERAL INTRODUCTION AND OPERATING PRINCIPLES
1-4
1
1. GENERAL INTRODUCTION AND OPERATING PRINCIPLES
1-5
1
1.2 OPERATION PRINCIPLES
The SM40 Public Address Distribution Centre is easy to use and logical in its operation, it is helpful however to understand, in principle, how the system works.
Herewith a typical series of actions, initiated by the operator, and carried out by the system:
1. User Key on Call Station (CST) is pushed (see Chapter 5.12).
2. Central Processor Card (CPC), which is continuously scanning the system, monitors which User Key
on which CST is being pressed. It then puts into effect a list of orders it was given at its programming stage (see Chapter 4.1).
3. First it looks to see which amplifier input, or inputs, our User Key is routed to (see Chapters 4.3.1, 5.3
and 5.12)
4. Then it makes sure that no other Call Station is currently calling that same input (see Chapter 5.12).
If the requested loudspeaker zone is already being called, the CPC checks which priority rating each User Key has been given, and if the original caller has a lower priority than the Key being pushed, its call will be muted and overridden by the new caller. If the Key being pushed has the same, or a lower priority than the original Key, its call will be ignored, and a ‘BUSY’ LED mounted on the Call station illuminates to advise that the call has not gone through.
5. If all is clear the CPC checks which attention tone and/or pre-recorded message has been programmed
to precede an announcement originating from our User Key, then it switches on the Signal Generator Card; selects a tone; activates message(s) from the Digital Message Card(s) (DMC’s) and feeds it to the designated amplifier inputs (see Chapters 5.4 and 5.11).
6. Meanwhile it sends an electrical signal, via the IPC, back to the CST which energises a flashing green
LED in order to tell the user that the call is going through, but that they will have to wait until the attention signal has finished (see Chapter 5.12).
7. If our key was given an alarm tone it will, dependent on the type of tone, be broadcast either for
1 minute, or until the user key is released.
8. The CPC checks, not only to see where the User Key has been routed to, but whether it has been
given any special orders regarding what it is to do when it gets there. Normally the CPC will mute any music signal being transmitted to a loudspeaker zone, when an announcement is being broadcast in it.
9. In order to allow the announcement and/or signal to come through at full volume, regardless of the
volume settings of amplifiers or individual loudspeakers, the CPC switches in a series of corresponding relays mounted on the Control Relay Card(CRC). These in turn activate the volume control override circuits of the SQ45 amplifiers and/or individual volume controls in loudspeakers, or loudspeaker groups (see Chapter 5.6).
10. When the CPC is certain that all is in order, it proceeds to give the message to the Input Card (IPC),
which in turn initiates the Call Station (CST) microphone.
11. The amplifier built into the CST amplifies the audio signal to line level, after which it runs through
the Input Card (IPC); via the Matrix Cards (MC)s; through Tone Control Cards (TCC)s if fitted; via the Interconnection Board (IB); to the Termination Board (TB); and out to the inputs of the amplifiers; which in turn feed loudspeakers located in geographical or functional zones.
12. When the announcement is completed and the User Key is released, the system returns to its idle
mode, with the CPC continually scanning, until another call is made. This whole operation is carried out in less than
1
/
10
th
of a second, giving the user the speed and power necessary to communicate in a
clear and efficient manner.
2. UNPACKING AND INSTALLATION
2
2. UNPACKING AND INSTALLATION
2-1
2
2.1 Unpacking and Installation
In order to ensure that your SM40 Centre functions properly, please follow these few simple instructions after unpacking your unit.
1. Carefully check the enclosed system components for physical damage caused during shipping. Any
complaints should be made immediately to the shipping company.
2. Mount the Basic System frame in the appropriate position in the 19 inch rack unit (not higher than
shoulder height, so that the display and keyboard can be clearly seen).
3. Extension Frames are available to expand the Basic System into a larger system. These should now be
mounted, and wired according to the appropriate wiring diagrams.
4. Mount the amplifiers and auxiliary equipment in the rack(s). If power amplifiers are mounted beneath
SM40 frames, a heat shield should be installed above them to deflect hot air currents.
5. Taking care to avoid earth (ground) loops, wire the mains power to the units.
SM40 will operate successfully on mains voltages from 187 V to 264 V when tapped for 220 V, and from 90 to 132 V when tapped for 110 V. Be sure to check that your system is wired for the correct mains voltage. Refer to Chapter 2.2 Power Supply Modules.
Warning: Because it is possible to touch the mains voltage terminals when the frame back panels are opened, it is advisable not to turn the power on at this stage.
6. Open the back panel of the Basic system, and check that all of the connectors on the Interconnection
Board and Termination boards are firmly in place. If, in the unlikely event that one of the connectors has become disconnected, refer to the enclosed basic system wiring diagram.
7. Referring to Termination Board illustrations in Chapter 5.2, wire the Call Stations, auxiliary input
sources, amplifiers, etc., to the screwblock connectors.
8. Plug the screwblock connectors into the termination boards, ensuring that they are in the correct
locations.
9. Open the front panel of the rack frame and gently push each of the circuit cards to make sure that
they are all firmly connected to the Interconnection Board.
10. If, after double checking that all of the mains power and signal wiring is correct, and that the system is
adequately earthed, switch on the mains power to the rack.
11. The display on the front panel shows:
For installer programming refer to Chapter 4.3.4.
* * * SYSTEM MUST BE PROGRAMMED * * * * * * GO TO INSTALLER MENU * * *
2. UNPACKING AND INSTALLATION
2-2
2
2.2 Power supply Modules
The SM40 Basic System frame LBB 1350 includes a Power Supply Module type SPM 315, and the SM40 Extension frame includes a Power Supply Module type SPM 215. Both modules, with the placement of jumpers (included on delivery) can be configured for use on either 220 - 230 Volts AC, or 110 - 115 V AC.
To ensure that your SM40 frame operates on the correct voltage, refer to the figure opposite and proceed as follows:
WARNING: BEFORE WORKING ON A SYSTEM, READ THE SECTION ‘IMPORTANT SAFETY INSTRUCTIONS’ FOUND AT THE BEGINNING OF THIS MANUAL. ALWAYS DISCONNECT THE FRAME FROM THE MAINS SUPPLY PRIOR TO WORKING ON THE FRAME ITSELF.
1. SM40 Basic System frame LBB 1350 using Power Supply Module SPM 315
Operation on 110 - 115 V AC
a. Open the front panel of the rack frame, and gently remove the Power Supply Module
from its housing.
b. Once the module is removed, unscrew and remove the 2 retaining screws needed to locate the
module’s printed circuit board. Once removed, carefully slide the top cover plate away from the module itself to reveal the printed circuit board.
c. On the printed circuit board (component side up) locate the jumper circuit (see figure opposite).
Using the jumper link(s) delivered with the module, place the jumper as shown.
Operation on 220 - 230 V AC
d. For operation on 220 - 230 V AC (factory setting) DO NOT PLACE the jumper.
2. SM40 Basic Extension frame LBB 1360 using Power Supply Module SPM 215
Operation on 110 - 115 V AC
a. Open the front panel of the rack frame and gently remove the Power Supply Module
from its housing.
b. Once the module is removed, unscrew and remove the 8 retaining screws found on top of the modules
cover plate, needed to locate the module’s printed circuit board. Once removed, carefully slide the top cover plate away from the module itself to reveal the printed circuit board.
c. On the printed circuit board (component side up) locate the jumper circuit (see figure opposite).
Using the jumper link(s) delivered with the module, place the three jumper(s) as shown.
Operation on 220 - 230 V AC
d. For operation on 220 - 230 V AC (factory setting) only 1 jumper link is placed (see opposite).
3. General
a. The SM40 Basic System frame LBB 1350 and the SM40 Extension frame LBB 1360 are supplied with
a 3-core mains cable. The mains cable is terminated with a 2-pole mains plug with earth contacts (or earth pin) for connection to the mains supply, and at the other end with a CEE connector for connection to the mains socket on the rear of the frame. For use in some countries it may be necessary to replace the mains cable with one of a local standard type. The wiring is as follows:
- Live/brown
- Neutral/blue
- Earth/green-yellow
WARNING: THE FRAME MUST BE EARTHED VIA THE MAINS SUPPLY USING THE GREEN/YELLOW WIRE. THE MAINS PLUG MUST BE OF AN EARTHED TYPE.
b. Power Supply Module, replacement fuses, are 4 Amps (adaption is not required for alternative
voltages).
2. UNPACKING AND INSTALLATION
2-3
2
Mains voltage setting
110 - 115 Volts AC
3 jumpers placed
Fuse 4A
Power Supply Module SPM 215
Mains voltage setting
220 - 230 Volts AC
1 jumpers placed
Fuse 4A
Power Supply Module SPM 215
POWER SUPPLY MODULE FOR SM40 EXTENDED MODULE FRAME LBB 1360
JUMPER PLACEMENT
Jumper open
Jumper placed in position
1 jumper placed No jumper placed
Power Supply Module SPM 315 Power Supply Module SPM 315
POWER SUPPLY MODULE FOR SM40 BASIC FRAME LBB 1350
Mains voltage setting
110 - 115 Volts AC
Mains voltage setting
220 - 230 Volts AC
Fuse 4A Fuse 4A
3. SM 40 BASIC SYSTEM AND EXTENSION FRAME
3
3. SM 40 BASIC SYSTEM AND EXTENSION FRAME
3-1
3
3.1 Basic System - BS LBB 1350/30
Self contained, fully operational system, around which all SM40 systems are built. Comprises 5 circuit cards, mounted in a single 19 inch rack frame.
The Basic (starter) System is the heart of the SM40 Public Address Distribution Centre. When supplemented with a variety of Euro-cards and PCB’s, a wide range of system configurations are possible, and many different application needs are successfully met.
Containing (along with its other circuit cards) the Central Processor Card (CPC); and the Display and Keyboard; and because it is mounted in a single rack frame; the Basic System is a self contained, fully working unit in its own right.
Being fed by a maximum of 3 Call Stations LBB 9567 (ordered separately), it is capable of controlling 8 amplifiers to feed a maximum of 8 loudspeaker zones.
Because the Basic System is supplied fully wired, adjusted, tested, and mounted in its own 19 inch rack unit, ready for use, it is an ideal model from which to build a larger system.
By running through the Basic System’s programming sequence it is easy to understand how the SM40 concept works. Any larger system has merely a greater quantity of Call Stations (CST)s, auxiliary inputs, etc. to program, and is dealt with in exactly the same way.
When a system’s requirements exceed the facilities available in the Basic System, further circuit cards (plus the Extension Frames LBB 1360 necessary to accommodate them) are ordered, expanding the system to meet specific application needs.
Units included with Basic System LBB 1350:
1x Single 19 Inch Rack Frame 1x Power Supply +15V/-15V/+5V 1x IB Interconnection Board 2x TB Termination Boards LBB 1377/00 1x MTB Matrix Termination Board LBB 1371/00 1x DK Display & Keyboard
(mounted on front panel)
1x CPC Central Processor Card LBB 1352/30
Distribution System Software 1x CRC Control Relay Card LBB 1356/00 1x IPC Input Card LBB 1351/00 1x SGC Signal Generator Card LBB 1354/00 1x MC Matrix Card LBB 1355/00
Optional Euro-Cards:
TCC Tone Control Card LBB 1357/00 SPC Signal Processing Card LBB 1358/00 AVC Automatic Volume Card LBB 1359/09, /21, /00 DMC Digital Message Card LBB 1378/00 SSC Surveillance Switch Card LBB 1374/00 CRC Control Relay Card LBB 1356/00 IPC Input Card LBB 1351/00 SGC Signal Generator Card LBB 1354/00 MC Matrix Card LBB 1355/00
Optional PCB’s:
CMP Communication PCB LBB 1366/00 I/O I/O - PCB LBB 1375/00 MTB Matrix Termination Board LBB 1371/00 MAP Microphone Amp PCB LBB 1364/00 KSP Key Sensing PCB LBB 1363/30 KCP Key Confirm PCB LBB 1365/00 TB Termination Board LBB 1377/00 RTB Relay Termination Board LBB 1379/00
Optional Units:
CST Call Station (Standard version) LBB 9567/30
- Extension Frame LBB 1360/30
3. SM 40 BASIC SYSTEM AND EXTENSION FRAME
3-2
3
3. SM 40 BASIC SYSTEM AND EXTENSION FRAME
3-3
3
3.2 Extension Frame - EF LBB 1360/30
Single 19 inch rack frame, capable of holding 10 SM40 circuit cards. Complete with power supply, Interconnection and Termination Boards.
A single rack frame, capable of holding, and interconnecting 10 SM40 circuit cards, has enough room to accommodate the Basic (starter) System, described elsewhere, plus 1x Input Card, 3x Matrix Cards, and 1x Control Relay Card.
When the quantity of cards required in an SM40 system exceeds the amount of space offered in this single rack frame, Extension Frame LBB 1360, is available.
Each Extension frame allows expansion of the system by up to 10 circuit cards, so that a system should be specified as 1x Basic System LBB 1350; plus the extra circuit cards required; plus the quantity of extension frames needed to accommodate those cards.
These components, mounted in the 19 inch rack frame, are supplied tested, and wired to accept and power up to 10 SM40 circuit cards.
Note: All circuit cards controlled by the CPC must be mounted in the basic system and the first 7 extension frames. All other cards (TCC, SPC, AVC, etc.) may then be mounted in as many frames as are necessary.
A maximum of 40 cards can be connected to one I
2
C bus. The basic frame includes two I2C busses.
Units included with Extension Frame LBB 1360:
1x Single 19” rack frame 1x Power Supply Unit +15V/ -15V 1x IB Interconnection Boards 1x TB Termination Boards LBB 1377/00
3. SM 40 BASIC SYSTEM AND EXTENSION FRAME
3-4
3
3. SM 40 BASIC SYSTEM AND EXTENSION FRAME
3-5
3
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4-1
4
4.1 Central Processor Card - CPC
At the heart of the SM40 Public address Distribution System is the Central Processor Card (CPC). Capable of controlling 16 or 32 call stations; 320 user keys; 1024 matrix points; 2 x 128 relays, 16 Digital Message Cards and 8 signal generators; this is a powerful piece of equipment, providing a system of this type with previously unheard of possibilities.
The basic functions of this card are as follows: DETECTION of call station user keys. Using information given it by the Input Card (IPC), the unit is
capable of sensing which user key is being pressed. ROUTING of microphones and attention signal tones (actuated by user keys), alarm tones, digital
messages, background music, etc., via Matrix Card (MC) to amplifiers and loudspeakers located in geographical and/or functional zones.
USER KEY PRIORITY level setting. To cope with conflict situations (e.g. when 2 call stations attempt to call the same zones simultaneously) each user key is given a priority level of 0-9, 9 being highest priority.
ATTENTION SIGNAL TONES, are coupled with the user keys so that when a key is pressed the tone will be broadcast before or instead of an announcement. Dependant on their character these tones may also be used as alarm signals or test tones.
DIGITAL MESSAGE CARD control, allows per card up to 7 messages with varying duration up to a maximum of 65 seconds to be recorded, and played back as desired. The maximum number of cards per centre is 16.
SWITCHING of loudspeaker volume control override circuits, and bypassing of the input attenuators in the SQ45 amplifiers, via the Control Relay Card (CRC). SWITCHING of amplifier outputs for loudspeaker group switching, via ‘unlocked’ Control Relay Cards.
CHECKING of system hardware. The processor acts as a “watchdog”, continuously scanning the SM40 system hardware to check for errors, malfunctions or disconnections. If a problem exists a message is displayed on the lcd screen of the Display & Keyboard; for instance if Call Station 3 is disconnected the message displayed is:
REAL TIME CLOCK is built into the unit, and is displayed, giving date, hours and minutes. A timer facility is coupled to the clock, making it possible to switch on and route tones, recorded messages and music at specific times of the day, or week.
A yellow LED, mounted on the front edge of the (CPC) card advises that the unit is running with the rest of the SM40 system, and 1 green LED indicates that adequate supply voltage is present.
A Display & Keyboard mounted on the rack unit’s front panel, is used to carry out installer and user programming as listed above. When programming is complete, the unit returns to its idle mode and, until a secret password is entered it has no influence on the processor. In this state the day, date, and time are displayed.
The CPC has 2 driver stages providing communication lines for up to 80 cards approximately. All circuit cards controlled by the CPC must be mounted as close as possible to the CPC. All other cards may then be mounted in as many frames as are necessary.
* * * * ERROR * * * * CALL/ALARM STATION 03
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4-2
4
The unit is mounted in the rack unit’s front panel, which may be flipped up, locking automatically in a horizontal position. This is an ideal angle from which to view and operate the unit.
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4-3
4
4.2 Display and Keyboard
A programming tool, containing a keyboard for user key assignment and a display which shows the sequence of programming. Mounted in the front panel of the rack unit.
Users of the SM40 Public Address Distribution System are able to program and make changes to the functions of their system, quickly and easily, with the aid of the Display And Keyboard. This is a simple programming tool comprising a 24 key keyboard and a 2x40 character lcd display which shows the sequence of programming.
SM40 KEY FUNCTIONS
0-9 Numeric keys to select call station number,
user key number, priority level, attention signal tone number and program numbers as listed in the main menu.
Moves the cursor 1 position to the right when routing Call Stations, Attention Tones, pre-recorded messages or Auxiliary sources (background music players, etc.) to amplifier inputs; each amplifier input representing a loudspeaker zone. Also used for programming free-programmable relays. This is called : “MATRIX/RELAY PROGRAMMING”.
Moves the cursor 1 position to the left during matrix/relay programming.
Moves the cursor to the beginning of the following lock of 8 amplifier inputs during matrix programming.
Moves the cursor to the end of the previous block of 8 amplifier inputs during matrix programming.
Switches the output, indicated by the cursor during matrix programming, to the “ON” position. Routing the call station or auxiliary source being programmed to the desired amplifier input.
Switches the output to the “OFF” position, cancelling routing of the call station or auxiliary to the amplifier input indicated by the cursor.
Switches all outputs to the “ON” position, routing the source being programmed to all amplifier inputs.
Switches all outputs to the “OFF” position, cancelling all routing of the source being programmed.
Mute Switches the output, indicated by the cursor,
to the -10 dB mode when it is desired to attenuate the volume of background music during an announcement, rather than muting it. This function is only available on ever y fourth input of the Matrix card.
Break If pressed during auxiliary programming, will
return user to the main menu for the next programming sequence (in this case Call Station programming) without storing any new information. During Call Station programming, ‘BREAK’ returns the user to the previous stage in the program (e.g. after “PROGRAM USER KEY: (1-10)”, it will go back to “PROGRAM CALL STATION: (1-16)” without storing any new information.
Enter Enters numerical inputs into the memory and
moves to the next program stage, or at the end of a program sequence; to the main menu ready for the next program.
A While the system is in its run mode, pressing
button A, displays the system status. The top line of the display indicates where Call Stations, Signal Generator Cards, Digital Message Cards and auxiliary sources are connected to the matrix. The bottom line indicates which user key is currently being pushed, and which SGC is producing a signal or which DMC is relaying a message.
B In the Installer programming Menu, button B,
is used to set the I/O RS232 serial interface communication parameters with an external computer. The parameters are as follows: Baud rate, stop bits and parity. See Chapter 5.13 on the I/O PCB.
C With the system in programming mode,
button C is used to couple or uncouple the Keysets (KST)s, as described in the Input Card, see Chapter 5.3.
0
1
0
1
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4-4
4
4.3 SM40 Programming
During the remainder of this chapter, specific contexts (status) and user actions are shown in the left column, and possible display results are shown in the right column. Characters between quotes (‘Key’) denote keyboard inputs, and ocurrances of XX and YY in any displays shown in the right column denote information which is dependant on the system configuration, or entered by the user.
When the SM40 system is powered up, either one of the following two displays is shown:
4.3.1 User Programming Menu
The User Programming Menu allows the user to program the following options:
Call Station Programming
- Call Station No.
- Alarm Station No.
- User Key No.
- Key priority level
- Signal No.
- Digitally Stored Messages
- Unlocked CRC Relay activation
- Routing to Amplifiers
Auxiliary Programming
(for signals from a music source):
- Routing signals to 1 or more outputs
Real-time clock / timer
settings
- Set real-time clock
- Program timers
Status / Action
When memory was cleared the display shows:
When the system was installed previously, the display shows:
Status / Action
To enter the User Programming Menu, enter the password: ‘9’, ‘6’, ‘Enter’.
Wait until the welcome message clears.
Press ‘Break’ to return the system to its ‘Normal Run Mode’. Otherwise, to proceed with the first programming option, press the key marked ‘1’, as shown in the display.
Result / Remarks
Display after entering the password. Indicated here are the software version number and release date.
The display now shows the first programming option. Note: To scroll through the programming options, use the ‘Enter’ key.
* USER MENU * scroll with 'ENTER' PRESS '1' TO PROGRAM CALL STATIONS
>> WELCOME TO SM40 PROGRAMMING MODE << >> VERSION X.X DATE XX-XX-XX <<
Result / Remarks
* * * SM40 ROUTING SYSTEM * * * DAY XX-XX TIME XX:XX
* * * SYSTEM MUST BE PROGRAMMED * * * * * * GO TO INSTALLER MENU * * *
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4-5
4
User Programming Menu: Call Station Programming
Status / Action
Press the ‘1’ key when the display shows the ‘User Menu’.
Enter Call Station number and press ‘Enter’. When a non-existent Call Station number is
entered (numbers 1-16 in 16x64 mode or 1­32 in 32x32 mode) the display shows:
Otherwise, when a non-existent Call Station number was entered (numbers 17-32 in 16x64 mode) the display shows:
Otherwise, when an existing Call Station number was entered the display shows:
Enter User Key and press ‘Enter’. Pressing ‘Break’ will return display to
“PROGRAM STATION:”. When the Key Number is entered, and the
Call Station number exists the display shows:
Otherwise, when the Key Number is entered and the Call Station number is between 17 and 32 in 16x64 mode the display shows:
If the current priority level is desired press ‘Enter’ to save this level, otherwise enter the desired level by pressing one of ‘0’ to ‘9’ followed by ‘Enter’.
Pressing ‘Break’ will return display to “PROGRAM USER-KEY:”.
If there is a signal generator present within the system, the display will show:
Result / Remarks
The current priority level will blink. If the memory has been cleared previously, the priority level will be set at default level zero.
The current signal number programmed for key XX will be displayed. Pressing ‘Enter’ will save this value, any other signal number, followed by ‘Enter’ changes the signal number. Entering ‘00’ means “no signal”. The list of available signals should be consulted to avoid selection of a non-existent signal.
CST:XX KEY:XX PRIORITY:X SIGNAL NR:X_X PRESS 'ENTER' OR CHANGE AND PRESS ENTER
AST:XX KEY:XX PRIORITY:X_ (0-9;0=lowest) PRESS 'ENTER' OR CHANGE AND PRESS ENTER
CST:XX KEY:XX PRIORITY:X_ (0-9;0=lowest) PRESS 'ENTER' OR CHANGE AND PRESS ENTER
PROGRAM STATION:XX PROGRAM USER-KEY:
_
PROGRAM STATION:X_X CALL/ALARM STATION XX NOT PRESENT
PROGRAM STATION:X_X CALL/ALARM STATION XX NOT PRESENT
PROGRAM STATION:
_
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4-6
4
User Programming Menu: Call Station Programming (32x32 mode)
Status / Action
When a Modified Surveillance Switch Card (MSC) installed in the system, used for activating messages from an external message source, the display shows:
Press ‘Break’ to return to “PROGRAM USER-KEY:”.
Otherwise, press ‘Enter’. If there are one or more Digital Message Cards in the system, the display shows:
To exit recorded message programming, enter a ‘0’ for either selection.
Status / Action
The display shows the following:
Result / Remarks
The Modified Surveillance Switch Card (MSG) can activate up to 8 messages from an external message source. Entering ‘0’ means “no message” (default after memory cleared: zero).
The upper line on the display shows the Digital Message Card selection. The lower line shows the message numbers.
When activating a call which includes a programmed digital message, all message cards needed for that call are reserved and can not be used for another call before the message cycle has ended. This is not the case when the new call has a higher priority level.
Up to 7 individual messages can be randomly programmed under one Call Station user key. If the selected Digital Message Card is not present, this will be displayed on the lower display line.
Note: Entering a seventh message will also exit message programming. The selected message will be played sequentially in the same order as programmed.
CST:XX KEY:XX DMC:X_X XX XX XX XX XX XX RECORDED MESSAGES: X X X X X X X
CST:XX KEY:XX PRIORITY:X_ SIGNAL NR:XX MESSAGE:X
Result / Remarks
The above display shows a graphical representation of the routing for key XX of call station XX. The number of symbol blocks displayed depends on the number of matrix cards connected to that particular Call Station, or on the presence of Control Relay Cards L1 to L4.
The number shown at the lower right of the display indicates the actual Amplifier Zone at the current cursor position.
CST:XX KEY:XX ROUTED TO AMPLIFIERS 0_0001111 00000*** -------- 11111111 01
Keys
, , , Move cursor to specific zone
,,Mute’ (De-)activate routing
Switch all zones ON Switch all zones OFF
Symbols
0
Zone switched off.
1
Zone switched on (an auxiliary source routed to that zone will be muted during the call).
*
Zone switched on (an auxiliary source routed to that zone will be attenuated during the call). Only possible for auxiliaries connected to every fourth input.
-
No Matrix Card / Locked Relay Card present.
0
1
0
1
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4-7
4
Status / Action
Press ‘Enter’ to save the new settings. Otherwise press ‘Break’ to return to
“PROGRAM USER-KEY:”.
When the routing is entered, the display shows:
When ‘Enter’ is pressed and Unlocked CRC U-4, U-5, U-6, U-7 and U-8 are present in the system, the display shows:
When the keys of Call Station XX are programmed, pressing ‘Break’ will return display to “PROGRAM STATION:”.
When all Call Stations present are programmed, pressing ‘Break’ again will return the display to the main menu.
CST:XX KEY:XX ACTIVATES RELAYS (L5-L8): 1_1100000 00000000 -------- 00000000 01
Result / Remarks
When an audio output of SM40 is activated by a call, the corresponding relay of the Locked Relay Card, with address 1-4 is also automatically activated. If a system has no more than 8 audio outputs, CRC cards 2, 3 and 4 can be considered as being freely programmable. However they are still shown on the display as routing. They can be used to activate zone relays or volume override relays.
In the 32x32 matrix mode, the relays of Locked Relay Cards L5-L8 are free and can be considered as free programmable and can be programmed accordingly.
[L-5] [L-6] [L-7] [L-8]
This is the current programming of the relays on Locked Relay Cards 5-8. This causes the programmed relays to activate when the corresponding Call Station key is active. In addition the relays on Unlocked CRC U-4, U-5, U-6, U-7 and U-8 can be activated via a user-key.
[U-4] [U-5] [U-6] [U-7]
[U-8]
The above screen shows the current programming of the relays CRC U-4, U-5, U-6, U-7 and U-8. This causes the programmed relays to activate when the corresponding Call Station key is active. Programming is identical to matrix programming.
CST:XX KEY:XX ACTIVATES RELAYS (U4-U8): 0_0000000 33
CST:XX KEY:XX ACTIVATES RELAYS (U4-U8): 0_0011111 00000000 -------- 00000000 01
CST:XX KEY:XX ACTIVATES RELAYS (L5-L8): 1_1100000 00000000 -------- 00000000 01
4. OPERATING AND PROGRAMMING THE SM40 SYSTEM
4-8
4
User Programming Menu: Call Station Programming (16x64 mode)
Status / Action
The display shows the following:
Press ‘Enter’ to save the new settings. Otherwise, press ‘Break’ to return to
“PROGRAM USER-KEY:”. When ‘Enter’ is pressed and Unlocked CRC
U-4, U-5, U-6, U-7 and U-8 are present in the system, the display shows:
When the keys of Call Station XX are programmed, pressing ‘Break’ will return display to “PROGRAM STATION:”.
When all Call Stations present are programmed, pressing ‘Break’ again will return the display to the main menu.
Result / Remarks
The above display shows a graphical representation of the routing for key XX of call station XX. The number of symbol blocks displayed depends on the number of matrix cards connected to that particular Call Station, or on the presence of Control Relay Cards L1 to L8.
The number shown at the lower right of the display indicates the actual Amplifier Zone at the current cursor position.
Note: A guide to the symbols shown on the display, and to the keys used to edit the routing, refer to the table on page 4-6.
When an audio output of SM40 is activated by a call, the corresponding relay of the Locked Relay Card, with address L-1 to L-8 is also automatically activated. If a system has no more than 8 audio outputs, CRC cards L-2 to L-8 can be considered as being free programmable. However they are still shown on the display as routing. They can be used to activate zone relays or volume control override relays.
[U-4] [U-5] [U-6] [U-7]
[U-8]
The above screen shows the current programming of the relays CRC U-4, U-5, U-6, U-7 and U-8. This causes the programmed relays to activate when the corresponding Call Station key is active. Programming is identical to matrix programming.
CST:XX KEY:XX ACTIVATES RELAYS (U4-U8): 1_1100000 33
CST:XX KEY:XX ACTIVATES RELAYS (U4-U8): 1_1100000 00000000 00000000 11000001 01
CST:XX KEY:XX ROUTED TO AMPLIFIERS: 0_0001111 00000*** -------- 11111111 01
Loading...
+ 110 hidden pages