Pfannenberg FLZ 600 Data Sheet

FLZ 600
Control range 40 .. 90% r.H.
Differential gap approx. 5%
Switch point accuracy +/- 4% based on 50% r.H.
Humidification: 24V .. 250V AC / 2(0.2)A - min. 100mA
Dehumidification: 24V .. 250V AC / 5(0.2)A - min. 100mA
DC: 50V, 1A 75V, 0,5A min. 100mA
Working temperature range 0°C..+60°C / +30°F..+140°F
Storage temperature -20°C..+80°C / -5°F..+180°F
Type of contact Change-over switch
Sensor Polyamide band
Type of connection 2-pole clamp, 0,5 .. 2,5mm²
Colour RAL 7035 – grey
Protection category IP 20
Assembly Sn ap fastening for 35mm profile bars in accordance with EN 60715
Монтаж
Montage Assembly Montage Montage Montering Montaggio Montaje
Humidistat FLZ 600 Instructions for use
Application:
- The humidistat is used for the monitoring and regulating of humidity in switch cabinets.
- It is implemented as a changeover contact and is either used to humidify ( ) or dehumidify ( ).
- The adjustment of the switch point is made using a slotted screwdriver.
- The adjustment head is used as protection from twisting in the static form.
- The installation position is optional, it must however be in a casing with an authorised protection class (e.g. switch cabinet).
Safety instructions The humidistats may only be installed by qualified staff.
The protective measures and the protection against contact are to be ensured by the installation.
The information on the name plate (voltage and current) is to be heeded.
The operational reliability of the humidistat is to be ensured by an operating test.