Pfannenberg DTS 3000 User Manual

ELECTRO-TECHNOLOGY FOR INDUSTRY
DTS 3000 Series
Cooling Units
Installation, Operation and Service Manual
Safety for man, machine and the environment®
TABLE OF CONTENTS
SECTION 1: HOW TO USE THIS MANUAL ..........1
SECTION 2: RECEIVING INSPECTION ................2
2.1 Unpacking ...........................................................2
2.2 Included Items ...................................................2
2.3 Review of ID Plate ...............................................2
SECTION 3: HANDLING ......................................3
3.1 Transporting .......................................................3
3.2 Storage ................................................................3
SECTION 4: INSTALLATION ................................3
4.1 Pre-installation testing ......................................3
4.2 Installation onto the electrical panel ................3
4.3 Power connection ...............................................4
4.4 Door contact .......................................................5
SECTION 5: OPERATING CONDITIONS ..............5
5.1 Requirements .....................................................5
5.3 Condensation Consideration .............................6
SECTION 6: UNIT START-UP ...............................7
6.1 General ................................................................7
6.2 Fault indicator / LED Display ..............................7
6.3 Test Mode / Start-up ...........................................8
6.4 Door Contact .......................................................8
6.5 Setting the Operating Parameters ....................8
SECTION 7: MAINTENANCE ...............................9
7.1 General Maintenance .........................................9
7.2 Cleaning ..............................................................9
SECTION 8: TROUBLESHOOTING ................... 10
SECTION 9: DESIGN DATA ............................... 12
SECTION 10: WARRANTY INFORMATION ...... 14
DTS Series Cooling Units
SECTION 1: HOW TO USE THIS MANUAL
This manual contains information on the installation and operation of DTS 3000 Series bolt-on cooling units intended to be door and side mounted on electrical panels.
Conventions used:
Hint: A hint contains additional information on the action or instruction being described
W A R N I N G !
If the information following this is not strictly
followed there is a danger to health or life.
W A R N I N G !
If the information following this is not strictly
followed there is a danger to health or life
due to electrical shock.
The technical data specific to each cooling unit including installation connections and operational data are contained on a separate data sheet.
1
SECTION 2: RECEIVING INSPECTION
2.1 Unpacking
Prior to and during unpacking the cooling unit, visually inspect it to determine if any damage has occurred during shipping. Make sure that it does not contain any loose components. Before discarding any packaging materials: Look for loose parts, dented or scratched panels or fluids.
If any damage is noted it shall be reported immediately to the delivering carrier and a claim should be filed with them. Pfannenberg cannot accept responsibility for freight damage that may occur; we will assist you in any way possible if the need arises to file a claim.
In case of a warranty claim, the following information is required: exact details of the fault (including photographs, if possible), the cooling unit part number and serial number are required.
W A R N I N G !
Burrs caused by production may be present
on the metal edges of the cooling unit. Always
wear protective gloves when carrying out
installation or maintenance work.
2.2 Included Items
The following items should be included: Cooling unit Mounting cutout Manual Technical Data Sheet
DTS 3000 Series accessory pack typically includes:
• Sealing strips
• Threaded mounting studs
• Mounting bolts, nuts and washers
• Condensate hose
• Door contact connector/jumper
2.3 Review of ID Plate
The ID plate is located on the left side of the cooling unit. The technical data specific to the cooling unit is located on the ID plate as shown below.
Frequency
Nominal Voltage
Nominal Current
Power Consumption
Fusing
Cooling Part #
Serial #
Design Pressure
Refrigerant Charge
Cooling Capacity
Heating Capacity
Environmental Conditions
2
DTS Series Cooling Units
SECTION 3: HANDLING
3.1 Transporting
The cooling unit shall only be moved in the fully assembled, upright condition.
If the cooling unit is being shipped with an electrical panel enclosure it shall be packed separately from the electrical enclosure.
W A R N I N G !
If for any reason the cooling unit has been
placed in any position other than fully upright
it shall be placed in a vertical position for a
minimum of 1 hour prior to starting the unit. If
this is not done the compressor may be drained
of oil. Operation of the compressor without
proper oil fill may cause permanent damage to
the cooling unit and void the warranty.
SECTION 4: INSTALLATION
4.1 Pre-installation testing
Before mounting the cooling unit to the electrical panel enclosure it should be tested to verify function.
4.2 Installation onto the electrical panel
Before connecting the cooling unit to the power supply, verify that the following are correct. Voltage must be within ± 10% of the value listed on the ID plate.
Voltage frequency must be within ± 3 Hz of the value listed on the ID plate
Ambient temperature must be below +55ºC (for options see “setting the operating parameters” section)
Place the drilling template supplied with the cooling unit onto the applicable mounting surface of the electrical panel enclosure.
3.2 Storage
The cooling unit shall not be exposed to temperatures exceeding +70ºC. Store the unit fully assembled in the fully upright condition.
W A R N I N G !
Failure to observe these requirements
will void the warranty.
W A R N I N G !
Metal chips from drilling and cutting the openings may damage the electrical panel enclosure. Take precautions required to prevent chips and debris from getting into the enclosure.
W A R N I N G !
Watch out for sharp edges created when drilling
and/or cutting the enclosure.
Drill holes in the electrical panel enclosure to match the unit and cut out air flow openings. Remove the cooling unit cover for handling during installation by removing the cover mounting screws.
Install the two supplied stud bolts (in the accessory pack) into the top two mounting hole locations of the cooling unit.
W A R N I N G !
Please note the information on the “Thread
Reach for Set Screw” label attached to the
cooling unit. If the noted installed thread depth
is exceeded the cooling unit may be damaged.
Install the cooling unit mounting insulation strips (in
3
Loading...