PRODUCTS VISUAL SIGNALING DEVICES
Accessories
EXTERNAL FLASH MONITORING
This device monitors the correct functioning of a flashing light by opto-electronic means. The flash from the light is
fed via an optical fibre to a phototransistor, which converts the optical impulse to an electrical impulse. The electronic circuit evaluates the pulse and its regular repetition. As soon as the operating voltage is applied, the evaluation relay closes the changeover contact. If the operating voltage fails, the relay opens immediately.
This method of operation represents the fail-safe normally-closed circuit function and guarantees an alarm even if
the operating voltage fails. On the other hand, the changeover contact serves to continue an alarm, e.g. in an failure
message line, or the direct blocking of further machine processes.
PRODUCT
ARTICLE NO. 29130800000
DATA
Operating range
Nominal current consumption 0.001 A 0.05 A
Fibre optic cable 1 m
Switching capacity of the
evaluation circuit
Suitable for ... any flashing light with a 1 Hz flash rate
Operating temperature –20 … +50 °C
Protection system
according to EN 60529
Material acrylonitrile butadiene styrene (ABS)
Colour similar to RAL 7035
Cable entry 2x M20
Weight 330 g 230 g
55
198–242 V 11–15 V 16–34 V 38–52 V
AC 50 | 60 Hz DC
120
EXTERNAL FLASH MONITORING
max. 230 V AC: 2 A
IP 55
80
55
operating voltage
evaluation circuit
connector
M20
fibre optic cable 1 m
Ø 4.1
108