Perlick 66134-3, 66134-4, 66134-1, 66134-2 User Manual

INSTALLATION AND OPERATION INSTRUCTIONS FLOJET BEER PUMP PANELS
MODEL NO.
66134-1 66134-2 66134-3 66134-4
This manual has been prepared to assist you in the operation of Perlick Beer Pump Panel System.
We dedicate considerable time to ensure that our products provide the highest level of customer satisfaction. If service is required, your dealer can provide you with a list of qualified service agents. For your own protection, never return merchandise for credit without our approval.
We thank you for selecting a Perlick product and assure you of our continuing interest in your satisfaction.
8300 West Good Hope Road • Milwaukee, WI 53223 • Phone 414-353-7060 • Fax 414-353-7069
Toll Free 800-558-5592 • E-Mail: Perlick@Perlick.com • www.Perlick.com
Table of Contents
Installing the Panel .............................................. 2
Panel Diagram ..................................................... 3
How to Operate the Beer Panel .......................... 4
Beer Pump Diagram ............................................ 5
Cleaning Diagram ................................................ 6
Cleaning Instructions ........................................... 7
Winterizing a System with Beer Pumps .............. 7
Replacement Parts .............................................. 7
Form No. Z2149A
Rev. 10.11.06
Installation – Beer Pump Panels
■ Use panel as a template to mark where holes should be drilled on cooler wall. Beer pump panels should not be installed with a height of greater than 5 feet from the cooler floor. A height greater than 5 feet will potentially cause flow issues and require system re-balancing. (Note: Make sure panel is level and pumps are in the vertical position).
Drill 9/64 pilot holes in cooler wall. Use fasteners
provided in installation kit to mount the beer pump panel to the cooler wall.
■ Push CO2 supply line over barbed CO2 supply
inlet.
(See diagram on page 3). Position clamp
over joint and tighten. Always use 3/8” I.D. braided tubing for gas supply line. Gas supply line should have drops going to each panel. (Never
connect supply line in a series hook-up
.
Push beer line (from trunk housing) over barbed liquid outlet on flow reversal valve. (See diagram on page 3). Position clamp over joint and tighten.
Push connector hose over liquid inlet on beer
pump flow reversal valve inlet fitting.
(See diagram on page 3). Position clamp over joint and tighten. (NOTE: Connector hose should not exceed 10 feet in length)
. Install washer into hex nut on opposite end of connector hose. Connect to top threaded fitting of Perlick Smart Coupler.
Important Notes
CAUTION: If using CO2 as a pressure supply for pumps, pump exhaust must be vented to a well ventilated area to avoid possible asphyxiation.
Never use a single keg to supply more than one beer pump. Using a single keg to supply more than one pump will create flow problems, pump burn out or premature Smart Coupler shut-off.
Pump panels should never be installed more than 5 (five) feet above the cooler floor. A height in excess of 5 (five) feet causes additional pressure drop between the keg and pump inlet which may cause degassing or premature Smart Coupler shut-off.
Beer pumps must be used in combination with an empty keg sensing device. If an empty keg sensing device is not used premature pump failure will occur.
If using compressed air as pressure source to drive pumps, pump and keg regulators need to be seperated. Air must be clean and dry.
■ Cut a piece of CO2 tubing (red 9/16” vinyl tubing) and push one end onto barbed CO2 outlet to Keg Couplers (See diagram on page3). Position clamp over joint and tighten. Push the other end over the barbed gas inlet on the Perlick Smart Coupler. Position clamp over joint and tighten.
Perlick is committed to continuous improvement. Therefore, we reserve the right to change specifications without prior notice.
Form No. Z2149A Rev. 10.11.06
2
Diagram – Beer Pump Panel Diagram
Perlick is committed to continuous improvement. Therefore, we reserve the right to change specifications without prior notice.
3
Form No. Z2149A
Rev. 10.11.06
How to Operate – Beer Pump Panels
■ Adjust primary CO2 regulator by turning adjusting screw counterclockwise until it turns freely, then turn hand valve counterclockwise on CO2 cylinder to the fully open position. Next, turn regulator adjusting screw clockwise until required system pressure plus an additional 15 psig is reached.
Note: If CO2 is only being used for keg- applied pressure, adjust to approximately 40 psig. Note: If using air to drive beer pumps, adjust the air compressor output regulator pressure to a minimum of 15 psig. greater than the maximum required system pressure required to operate the beer pumps. Maximum setting 100 psig.
■ Adjust secondary CO2 regulator which supplies the keg pressure located on the beer pump panel to the proper pressure setting. Setting depends on beer brand and temperature. Desired goal is to maintain the natural carbonation in the beer. Open the shut­off valves.
■ Ensure the Probe Valve on the Perlick Smart Coupler is in closed position. See figure 1. Ensure the Beer Pump Flow Reversal/Dispense handle is in the dispense position. Adjust the Secondary Air/ CO2 regulator located on the beer pump panel to a minimum operating pressure of 10 psig.
■ Connect the coupler to a regulated water supply with pressure less than 30 psig. Note: Pump
damage may occur with pressure higher than 30 psig.
■ Open the water supply. Then open probe valve on Perlick Smart coupler to the 45° position. See figure 2. The beer pump will slowly pump up the beer line in the trunk housing to set psig. Note: If pump continues to run for longer than expected, check lines for possible leaks at one or more of the connections.
■ Gradually increase secondary regulator pressure to the designed system pressure to achieve a flow rate of one gallon per minute from the dispensing head. Note: Maximum
beer pump operating pressure is 90 psig.
■ Open dispensing head faucet to purge air trapped within the tubing.
■ Check all gas and liquid line fittings and connections for leaks.
■ Close probe valve on Perlick Smart Coupler. (See figure 1) and disconnect coupler from regulated water source.
■ Clean beer system. After cleaning and rinsing
the system, make sure the beer line is full of cold water (beer dispensing from warm beer lines will be poor quality).
■ Tap fresh keg with Perlick Smart Coupler. Open dispensing head faucet until clear beer flows.
Smart Coupler Probe Valve Lever Positions
Form No. Z2149A Rev. 10.11.06
Figure 1
Closed Position
Perlick is committed to continuous improvement. Therefore, we reserve the right to change specifications without prior notice.
45° or Cleaning Position
Figure 2
Figure 3
Open Position
4
Diagram #2 – Beer Pump
Perlick is committed to continuous improvement. Therefore, we reserve the right to change specifications without prior notice.
5
Form No. Z2149A
Rev. 10.11.06
Diagram #3 – Cleaning Diagram
Form No. Z2149A Rev. 10.11.06
Perlick is committed to continuous improvement. Therefore, we reserve the right to change specifications without prior notice.
6
Cleaning Instructions
General Information
■ The cleaning of beer lines with the new inte­gral flow reversal feature incorporated into the Perlick Beer Pump gives the line cleaner numerous configurations for line cleaning. Although the Perlick Beer Pump can be used as an in-line pump for moving the solution from the coupler to the faucet due to its capability of working with negative lift, the following is the recommended method for cleaning beer lines with the Perlick Beer Pump with integral flow reversal installed.
■ When a beer system with beer pumps will be shut down for an extended period, clean the system thoroughly. After completing the rins­ing step, prepare a mixture of 50% food grade Glycerine and 50% water. Load the lines with this mixture and make sure both ends of the system are closed. Glycerine/water mixture should remain in the lines for the duration of the shutdown period.
Replacement Parts
Cleaning Beer Lines using Smart Couplers
■ Disconnect Smart Coupler from beer connector lines and soak Smart Couplers in cleaning solution.
■ Couple the two beer connectors together using Perlick’s double male adapter part # 186 with beer washers.
Determine which sets of lines will be cleaned
together and rotate the Dispense/Reverse Flow handle to the Reverse Flow position on the line which fluid will be circulated from the faucet, to the tap.
■ Remove the faucet from the line to which the
Beer Line Cleaner pump will be connected. Soak faucets and brush clean before reinstalling.
■ Connect Beer Line Cleaner pump to the shank.
■ Follow standard beer line cleaning procedures.
Perlick recommends that the lines first be flushed with clean warm water (Water temperature not
to exceed 100 degrees). Mix line-cleaning solution per manufacturerís directions. Circulate the solution thoroughly (Time for circulation dependent on length of the system and pump capabilities). Rinse the lines using clean cold water (Ensure all line cleaning solution has been removed from the lines to prevent hazardous results).
■ Disconnect line-cleaning pump and reinstall beer faucets.
■ Reconnect couplers to beer connector lines and
return Beer Pump Dispense/ Reverse Flow valve to the dispense position.
■ Reconnect couplers to keg and open dispensing head faucets until clear beer flows.
Winterizing Systems with Beer Pumps
Perlick is committed to continuous improvement. Therefore, we reserve the right to change specifications without prior notice.
44................... Air valve
40115 ............. Regulator body
40129............. Regulator body
43553A .......... Regulator repair kit
63706............. Flow reversal valve
63707............. Elbow, flow reversal, 2/bag
63708............. Fitting, tee, gas, barbed 1/4” with
check valve
63709 ............. Fitting, elbow, gas, barbed 1/4” with
check valve
43817............. Beer pump, Flo-Jet, w/CO2 elbow
& tee
7
Form No. Z2149A
Rev. 10.11.06
8300 West Good Hope Road • Milwaukee, WI 53223 • Phone 414-353-7060 • Fax 414-353-7069
Toll Free 800-558-5592 • E-Mail: Perlick@Perlick.com • www.Perlick.com
Perlick is committed to continuous improvement. Therefore, we reserve the right to change specifications without prior notice.
Form No. Z2149A
Rev. 10.11.06
Loading...