This manual provides the information needed for proper use and maintenance of this air
conditioner. Basic preventative care can help extend the life of this unit. The “Troubleshooting
Tips” section in this manual contains a chart with solutions to the most common problems.
Referring to this section may save time and prevent the need for a service call in the event of
a problem.
!
CAUTION
● Contact an authorized service technician for repair or maintenance of this unit.
● Contact an installer for installation of this unit if necessary.
● The air conditioner is not intended for use by young children without supervision.
Young children should be supervised to ensure that they do not play with the air conditioner.
● Disabled persons may require assistance with set up.
● If the power cord is to be replaced, replacement work should be performed by authorized
personnel only.
● Installation and repair work must be performed in accordance with the national wiring
standards by authorized personnel only.
● Do not operate your air conditioner in a wet room such as a bathroom or laundry room.
● Units with a heating function should be at least 3 1/3 ft (1 meter) away from any combustible/
flammable materials.
NOTE: All the illustrations in this manual are for explanation purposes only. Unit purchased
may be slightly different.
The design and specifications are subject to change without prior notice for product
improvement. Contact customer service for details.
1
Page 4
SAFETY PRECAUTIONS
To prevent injury to the user or other people and property damage, the following instructions
must be followed. Incorrect operation due to ignoring of instructions may cause harm or
damage. The seriousness is classified by the following indications.
!!
!
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property.
Meanings of symbols used in this manual are as shown below.
!
!
!
!
Plug in power plug properly.
Failure to do so may cause
electric shock or fire due to
excess heat generation
Do not modify power cord
length or share the outlet with
other appliances.
Doing so may cause electric
!
shock or fire due to heat
generation.
Always ensure effective
grounding.
Never do this.
Always do this.
!!
Do not operate or stop the unit
by inserting or pulling out the
power plug directly from the wall.
Doing so may cause electric
shock or fire due to heat generation.
.
Do not operate with wet hands
or in damp environment.
Doing so may cause electric shock.
Do not allow water to run into
electric parts.
WARNIN
G
Do not use a damaged power
cord.
Doing so may cause electric shock
or fire. If the power cord is
damaged, it must be replaced by the
manufacturer or an authorized
service center or a similarly qualified
person in order to avoid a hazard.
Do not direct airflow directly at
room occupants.
This could cause health issues.
!!
Always install circuit breaker
and a dedicated power circuit.
Incorrect grounding may cause
!
electric shock.
!
Always unplug the unit if
strange sounds, smell or
smoke comes from the unit.
!
Failure to do so may cause fire
and electric shock.
Do not use firearms near unit.
Doing so may cause fire.
!
!
Ventilate room before operating air conditioner if
there is a gas leakage from another appliance
such as a stove.
Failure to do so may cause explosion,
fire and burns.
Doing so may cause failure of
machine or electric shock.
Do not use the socket if it is
loose or damaged.
Doing so may cause fire and
electric shock.
Do not use the power cord close
to heating appliances.
Doing so may cause fire and
electric shock.
Incorrect installation may cause fire
and electric shock.
Do not open the unit during
operation.
Doing so may cause electric shock.
Do not disassemble, modify,
or drill holes into the air
conditioner.
Doing so may cause failure and
electric shock.
Do not use the power cord near flammable gas
or combustibles, such as gasoline, benzene,
thinner, etc.
Doing so may cause an explosion or fire.
2
Page 5
CAUTION
!
When removing air filter, do not
touch metal parts of the unit.
Doing so may cause an injury.
!
Unit and Circuit breaker/fuse
must be switched OFF when
cleaning.
.
Cleaning unit when power is ON
may cause fire and electric shock
and may cause an injury.
Stop operation and close the
window in severe storms or
hurricanes.
Operation with windows open may
cause moisture to enter the room.
Do not place obstacles around
air-inlets or inside of air-outlet.
Obstacles may cause appliance
failure or accident.
!
Use only a soft cloth to clean
the unit.
Do not clean with water.
Water may enter the unit and
degrade the insulation causing an
electric shock.
Do not put a pet or house plant
where it will be exposed to
direct air flow.
This could injure the pet or plant.
!!!
Hold the plug by the head of the
power plug when taking it out.
Failure to do so may cause electric
shock and damage.
!
Periodically check installation
bracket for damage.
.
Prolonged exposure to outdoor
elements may cause damage to
installation bracket causing unit to
fall.
!
Use caution when unpacking
and installing.
!
Ensure proper ventilation
especially in rooms with a stove
or other appliances.
Failure to do so may result in an
oxygen shortage.
!
Use only as intended.
This unit is NOT intended to
preserve precision devices, food,
pets, plants, and art objects. It may
cause deterioration of quality, etc.
If unit will not be used for a long
period of time, turn OFF main
power switch.
Leaving power on may cause unit
failure or fire.
!
Always insert the filters securely.
Clean filter AT LEAST once
every two weeks.
Operation without secured filters
may cause failure. A dirty filter
can cause the unit to not run
efficiently.
NEVER drink water drained from
air conditioner.
Cleaners or detergents may change
the color or scratch the surface of
the unit.
Do not place heavy objects on the power cord
and always ensure that the cord is not
compressed.
There is danger of fire or electric shock.
Sharp edges could cause injury.
Meeting Electrical Requirements
!
WARNING
• Electrical ground is required on this appliance.
• DO NOT ground to a gas line.
• If cold water pipe is interrupted by using plastic, nonmetallic gaskets, or other insulating materials. DO NOT use
for grounding.
• Check with a qualified electrician if you are in doubt as to
whether the appliance is properly grounded.
• DO NOT modify power supply cord plug. If it does not fit the
outlet, have a proper outlet installed by a qualified electrician.
• DO NOT have a fuse in the neutral or grounding circuit.
A fuse in the neutral, or grounding circuit could result in an
electrical shock.
• DO NOT use an extension cord with this appliance.
Failure to follow these instructions could result
in electrical shock, serious injury, or death.
Electrical Shock and
Personal Injury Hazard
Water from unit contains
contaminants and could cause
illness.
!
If water enters the unit, turn the unit off at the power
outlet and switch off the circuit breaker. Isolate supply
by taking the power-plug out and contact a qualified
serviced technician.
There is danger of electric shock.
Observe all local governing codes and ordinances.
Do not, under any circumstances, remove the power
supply cord grounding prong.
NOTE: If codes permit, and a separate grounding wire is used,
it is recommended that a qualified electrician determine that the
grounding path is adequate and not interrupted by plastic,
non-metallic gaskets, or other insulating materials.
Receptacle Wiring
Receptacle wiring should be a minimum of 14 gauge. Use copper
wire only. It is your responsibility to provide proper and adequate
receptacle wiring, installed by a qualified electrician.
Electrical Requirements
A time delay fuse or time delay circuit breaker is also required. A
separate circuit, serving only this appliance, MUST be provided.
3
Page 6
IMPORTANT SAFETY INSTRUCTIONS
NOTE
this air conditioner contains a current
detection device designed to reduce
the risk of fire.
Please refer to the section "Operation
of Current Device" (below) for details.
In the event that the power supply cord
is damaged, it MUST be replaced by
an authorized repairman.
Power supply cord
with 3-prong grounding plug
and current detection device
The power supply cord with
DO NOT, under any
circumstances, cut,
remove, or bypass
grounding prong.
WARNING!
DO NOT store or use gasoline or other flammable vapors or liquids in
the vicinity of this or any other appliance.
Avoid fire hazard or electric shock. DO NOT use an extension cord or
an adaptor plug. DO NOT remove any prong from the power cord.
WARNING!
Be sure the electrical service is adequate for the model you have chosen.
This information can be found on the serial plate, which is located on the
side of the cabinet and behind the grille.
Be sure the air conditioner is properly grounded. To minimize shock and fire
hazards, proper grounding is important. The power cord is equipped with a
three-prong grounding plug for protection against shock hazards.
Your air conditioner must be used in a properly grounded wall receptacle. If
the wall receptacle you intend to use is not adequately grounded or
protected by a time delay fuse or circuit breaker, have a qualified electrician
install the proper receptacle.
Ensure the receptacle is accessible after the unit installation.
Do not run air conditioner without side protective cover in place. This could
result in mechanical damage within the air conditioner.
Do not use an extension cord or an adaptor plug.
For Your Safety
Electrical Information
WARNING!
To reduce the risk of fire, electrical shock, or injury to persons when using your air conditioner, follow basic precautions,
including the following:
If the air conditioner is to be installed in a window, you will probably want to clean both sides of the glass first. If the window
is a triple-track type with a screen panel included, remove the screen completely before installation.
Be sure the air conditioner has been securely and correctly installed according to the installation instructions in this manual.
Save this manual for possible future use in removing or installing this unit.
When handling the air conditioner, be careful to avoid cuts from sharp metal fins on front and rear coils.
Prevent Accidents
Operation of Current Device
The power supply cord contains a current device that senses damage to the power
cord. To test your power supply cord do the following:
1. Plug in the air conditioner.
2. The power supply cord will have TWO buttons on the plug head. Press the TEST
button. The RESET button will click as it pops out.
3. Press the RESET button; again you will notice a click as the button engages.
4. The power supply cord is now supplying electricity to the unit.
(On some products this is also indicated by a light on the plug head.)
NOTES:
Do not use this device to turn the unit on or off.
Always make sure the RESET button is pushed in for correct operation.
The power supply must be replaced if it fails to reset when either the TEST button is pushed or it cannot be reset.
If power supply cord is damaged, it cannot be repaired. Please call customer service to assist with replacement.
NOTE: This air conditioner is designed to be operated under conditions as follows:
Plug in &
press RESET
TEST
RESET
NOTE: Some plugs have
buttons on the top.
Cooling operation
If the unit is ope rated beyond the conditions specified above, it may cause a fai lure of the unit.
Outdoor temp: 18-43°C/64-109°F (18-52°C/64-125°F for special tropical models)
Indoor temp: 17-32°C/62-90°F
4
Page 7
INSTALLATION INSTRUCTIONS
NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash,
or installation in a metal CASEMENT window. Modification may be necessary when installing in windows made
differently than those shown in these instructions.
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT- Save these instructions.
IMPORTANT- Observe all
governing codes and ordinances.
Note to Installer- Be sure to leave these
instructions with the Consumer.
Note to Consumer- Keep these
instructions for future reference.
Skill level- Installation of this appliance
requires basic mechanical skills.
Preparing for Installation
Installation Tips:
For wood-frame casement windows:
It may be necessary to construct a frame,
using at least 1-inch thick wood, with a
15 1/2-inch wide opening.
For brick or cement building construction:
It may be necessary to put a wood stool strip
under the unit, for mounting purposes.
1. Make sure you have
all the necessary parts.
Completion time- Approximately 1 hour.
We recommend that two people install this product.
Proper installation is the responsibility of the installer.
Product failure due to improper installation is not
covered under the Warranty.
You MUST use all supplied parts and use proper
installation procedures as described in these
instructions when installing this airconditioner.
Installation kit contents:
1. Platform (1)
2. Support brace (1)
3. Adjustment bolt (1)
4. Hex flange nut-1/4” (1)
5. Track seal (1)
6. Side channel seal (1)
7. Foam seal strip/sash seal (1)
8. Safety bracket (1)
9-11. Screw- 2 1/2” (2), or
Screw- 1 3/4” (2), or
Screw- 1” (2)
12. Screw- 3/4” (6)
13. Screw- 3/4” self-threading (7)
14. Window locking bracket (1)
15. Plastic window panel (1)
16. Side channel (2)
17. Screw- 3/8” (6)
18. Panel frame/seal assembly (1)
Tools Required (Not included):
Flat-head screwdriverPhillips-head screwdriver
Carpenter’s levelTape measureFine tooth sawElectric or hand drill
5
Page 8
INSTALLATION INSTRUCTIONS (CONTINUED)
NOTE: Use scale below to measure length of your screws.
The scale will be helpful when separating screws for installation.
Identify Screws
(25mm)
1”
(44mm)
1 3/4”
(63mm)
2 1/2”
By Length
3/8”
(10mm)
2. Choose a proper sized window, as shown to the right.
NOTE : Height measurement must be of a clear opening above mounting
platform. In some cases, due to a variety of stop and track arrangements,
the above dimensions may vary slightly. If necessary, installation can be
made by alternating window jambs. (See Alternate Window Jamb
Applications below).
15 1/2 inches
minimum
width
20 5/16 inches
39 7/16 inches
minimum
height
maximum
height
16 1/4 inches
maximum
width (casement
windows)
3. Choose the proper window location.
Choose a window that allows the cooled air to flow
freely and directly into room (s) you wish to cool.
Remember, it is difficult to move air around corners.
Also, choose a window that is within 6 feet of an electrical
outlet. (See “Meeting Electrical Requirements/Receptable
Wiring Needs” on Page 5).
Do not use an extension cord.
To install in windows having no flanges or wood stops
on the top and side jambs, the channels and panel
frame must fit against a mounting flange (or 1/16-inch
max. thick angle) attached to the window jambs.
Figure A shows this angle installed. Figures B & C
show alternate treatments. On the sash side of the
opening, the leading corner of the inner sash becomes
the flange. You can purchase the angle strip locally.
3
4 or 1
3
4 or 1
or
6
Page 9
INSTALLATION INSTRUCTIONS (CONTINUED)
Installing Unit in a Sliding Window
1. Attach support brace to platform (Fig. 1).
Use adjustment bolt and hex flange nut to
complete assembly. Choose slot and adjustment
bolt hole locations that will create a 45 degree
angle between platform and support brace. Try
assembly in the window to determine if platform
will rest properly, and allow proper slope.
(5/16” lower on outside).
Fig. 1
1/4”
NOTE: If you are planning to use a sliding-protection
board (See Step 5) on the outside of your house, hold
board in place when testing assembly of window.
2. Measure, and lightly mark a line 8 11/16” from
window jamb. (Fig. 2)
NOTE: If any sash stop protrudes more than 1”
from the side window jambs, the 8 11/16”
measurement must be increased accordingly.
Screen and storm window frames may also require
adjustments to the measurement.
3. Center platform assembly. (Fig. 3 and Fig. 4)
Center the platform assembly on the line with inside
platform tab pressed against inside edge of window
track. Using the holes in the platform as a guide,
mark and drill two 9/64” diameter holes. Drill holes
in either track or stool.
CAUTION
!
Property Damage Hazard-Failure to adhere to
the following precaution could result in
damage to window or air conditioner.
Be sure wood stool or window track is securely
attached to the building construction. Use longer
screws in sub-framing if necessary.
Fig. 3
11
16
Center Platform
assembly on the
line with platform
tab pressed against
window track
Fig. 2
Alternate screw location
(depending o n the stool d epth)
Platform t ab
Window trac k
Window se al
Fig. 4
4. Peel off protective backing from track seal. (Fig. 5)
Next, apply seal to room side of window track.
Center of seal strip should coincide with the line
marked in Step 2. The two screw holes drilled in
Step 3 should be directly above seal strip in the
inner track.
5. Securely attach a siding-protection board to
side of house. (Fig. 6)
NOTE: Siding-protection board should be long enough
to span 2 wall studs.
NOTE: Adjust the platform assembly so that the air
conditioner will be 1-1/8” to 1-1/2” lower than the front
(tilted about 3º to 4º downward to the outside). After
proper installation, condensation should not drain
from the overflow drain hole during normal use.
(You may see condensation in periods of high humidity.
However, if condensation occurs during low or normal
humidity, adjust the slope slightly.)
Fig. 5
Apply track seal to
window side of track
Fig. 6
7
Page 10
INSTALLATION INSTRUCTIONS (CONTINUED)
Installing Unit in a Sliding Window (Continued)
6. Place platform assembly. (Fig. 7)
With platform tab against inside of window track,
place platform assembly and attach it to window
jamb. Use appropriate length screws (Items 9-11
in Preparing For Installation).
7. Adjust platform assembly.
Adjust the platform assembly so that the outside
edge is 5/16 inches lower than inside edge. (Fig. 7)
This ensures proper water drainage from the air
conditioner.
8. Level platform assembly from side-to-side.
Also, make sure window track is level. Use leveling
shims as necessary to ensure unit is level from
side-to-side.
9. Measure height of window opening. (Fig. 8)
Begin measuring height of window opening
from top of platform assembly as shown right.
Subtract 20 5/8 inches. Mark this measurement
on plastic window panel, along the longer side.
approx. 1” to 1¼”
Fig. 7
10. Clamp plastic window panel.
Clamp the plastic window panel between a board
and a work table, and cut along cutting line with a
fine tooth saw. Remove any burrs with a file.
11.Fasten side channels. (Fig. 9)
Fasten the side channels to the sides of the unit
using 3 screws (Item #17, page 10) per channel.
Start with first screw at top of channel. Make sure
hook ends of channels face toward back of unit.
12. Slide plastic window panel into panel frame.
(Fig. 10)Slide in the window panel, with the smooth
side to the room. Slide panel frame assembly into
side channels of the AC cabinet. Make sure plastic
window panel is firmly enclosed on all sides by
the retainer grooves.
13. Cut side channel seal. (Fig. 11)
Cut the side channel seal into 2 equal lengths.
Remove protective backing and apply it to the
rear side of cabinet side channels, starting just
below panel frame assembly. Pinch off excess
length so seal is even with the bottom of the
cabinet side channel.
Fig. 10
Fig. 11
Apply weather
seal to side
channels just
below edge
of panel frame
Fig. 8
Fig. 9
8
Page 11
INSTALLATION INSTRUCTIONS (CONTINUED)
Installing Unit in a Sliding Window (Continued)
14. To Remove Front (Fig. 12)
1. Remove the two front retaining screws
from the front frame.
2. Gently pull the front out and lift up to
release it from the case.
3. Release the coupler plugs.
NOTE: DO NOT push or pull air direction louvers.
15. Place AC in window opening.
The unit should sit on platform assembly so that
window panel frame, and cabinet side channels
are against top and side window jambs. (Fig. 13)
16. Slide inner window sash firmly against side
of cabinet.
Make sure not to peel the seal strips from the window
track and cabinet side channels. If the panel frame
does not fit snugly to the inner window sash, secure
the panel frame to the sash with 3/4” screws, or 3/4”
self-threading screws. Use the partially plugged holes
in the panel frame. Drill 1/8” pilot holes for the screws.
17. Hook the safety bracket. (Fig. 14)
The safety bracket should be hooked over the base
of the unit and fastened to the front of the platform
assembly. Use a 3/4 inch self-threading screw.
NOTE: The bracket prevents movement of the air
conditioner (either in or out) after completing the
installation.
Fig. 12
Front
Retaining
Screw
Fig. 13
Slide inner
window sash
firmly against
cabinet
Fig. 14
18. Stuff the foam seal strip/sash seal.
Stuff the foam seal strip between the vertical sash and
the window glass. (Fig. 15)
19. Lock the inner window sash.
Using the window locking bracket, lock the inner
window sash to the base of the outer window sash.
Use one 3/4” screw, or 3/4” self-threading screw.
(Drill 1/8” pilot hole).
20. To Replace the front.
First, reconnect the coupler plugs. Make the exhaust
control positioned through the front in the proper
location. Then, replace the retaining screws that hold
the panel in place. Do not push or pull the front louvers.
Fig. 15
9
Page 12
INSTALLATION INSTRUCTIONS (CONTINUED)
Installing Unit in a Casement Window
NOTE: Open the window the maximum amount to
allow for clearance of the cabinet. The crank handle
should be removed to allow the platform to be
fastened to the jamb. If the window cannot open far
enough (more than 15 1/2 inches) for the cabinet to
clear the window, remove the window entirely by
drilling out the rivets. Bolts can serve as the rivots
in the future.
To avoid crank handle and window clearance
problems, the unit can be installed in a stationary
sash section. However, the horizontal mullion and
the 2 glass panels must be removed before installation.
1. Attach support brace to platform. (Fig. 1)
Use the adjustment bolt and hex flange nut to
complete the assembly. Choose the slot and
adjustment bolt hole locations that will create a
45 degree angle between the platform and the
support brace. Try the assembly in the window
to determine if the platform will rest properly,
and allow the proper slope (5/16 inch lower on
outside).
NOTE: If you are planning to use a siding-protection
board (See Step 6) on the outside of your house,
hold the board in place when testing the assembly
in the window.
2. Drill a 9/64 inch diameter pilot hole.
Drill the hole in the window jamb an equal distance
from each side of the jamb (Fig. 2), and 3/16 inch up from
the window sill. If the hole coincides with the window
lever slot in the jamb bottom, an additional hole will
have to be drilled through the platform edge and the
window jamb to miss this slot.
3. Peel off the protective backing. (Fig. 3)
Peel off the backing from the track seal, and stick
the seal to the window sill on the outside of the
bottom jamb.
Fig. 1
Fig. 2
Fig. 3
4. Screw the platform assembly to the window
jamb. (Fig. 4)
Screw the platform assembly using the pilot hole
drilled in Step 2. Use a 3/4 inch self-threading screw.
Fig. 4
10
Page 13
INSTALLATION INSTRUCTIONS (CONTINUED)
Installing Unit in a Casement Window (continued)
5. Adjust the platform assembly properly. (Fig. 5)
Adjust the platform assembly so that the rear
of the air conditioner will be 5/16 inches lower
than the front. This ensures proper water drainage
from the air conditioner.
NOTE: Adjust the platform assembly so that the air
conditioner will be 1-1/8” to 1-1/2” lower than the front
(tilted about 3º to 4º downward to the outside). After
proper installation, condensation should not drain
from the overflow drain hole during normal use.
(You may see condensation in periods of high humidity.
However, if condensation occurs during low or normal
humidity, adjust the slope slightly.)
6. Securely attach a sliding-protection board.
Attach the board to the side of the house where
the platform assembly hit the house. The siding-protection
board should be long enough to span 2 wall studs.
7. Measure the height of the window opening. (Fig. 7)
Measure from the top of the platform assembly.
Subtract 20 5/8 inches. Mark this measurement
on the plastic window panel, along the longer side.
(Fig. 6)
approx. 1” to 1¼”
Fig. 5
Fasten
sliding-protection
board to the
house
siding.
Fig. 6
8. Clamp the plastic window panel.
Clamp the plastic window panel between a board
and a work table, and cut along the cutting line with
a fine tooth saw. Remove any burrs with a file.
9. Fasten the side channels to the side of the unit.
Using three screws (Item #17, Pg. 10) per channel
fasten the side channels to the side of the unit. Make
sure hook ends of channels face toward the back of unit.
10. Slide the plastic window panel into panel frame.
(Fig. 8)
Slide the plastic window panel in with the smooth side
to the outside. Slide the panel frame assembly into the
side channels of the air conditioner cabinet. Make sure
the plastic window panel is firmly enclosed on all sides
by the retainer grooves.
11. Cut side channel seal. (Fig. 9)
Cut the channel seal into 2 equal lengths. Remove the
protective backing and apply it to the rear side of the
cabinet side channels, starting just below the panel frame
assembly. Pinch off excess length so the seal is even with
the bottom of the cabinet side channel.
Fig. 7
Fig. 8
Fig. 9
11
Page 14
INSTALLATION INSTRUCTIONS (CONTINUED)
Installing Unit in a Casement Window
(Continued)
12. To remove front: (Fig. 10)
Remove the two front retaining screws from
the front frame.
Gently pull the front out and lift up to release
it from the case.
Release the coupler plugs.
NOTE: DO NOT push or pull air directional
louvers.
13. Place the air conditioner in the window
opening. (Fig. 11)
The air conditioner should sit on the platform
assembly so that the window panel frame, and
the cabinet side channels are against the top and
side window jambs. Side channels should overlap
side window jambs equally.
14. Drill two 9/64 inch diameter pilot holes.
Drill the two pilot holes in the top window jamb in
line with the partially plugged holes in the panel
frame. Secure the panel frame to the window jamb
with two 3/4 inch self-threading screws. If additonal
holding is necessary, two screws may be used on
the sides of the panel frame as well.
15. Drill screw-clearance holes.
Drill two screw-clearance holes in the cabinet side
channels (near bottom) and two 9/64 inch diameter
pilot holes in the side window jambs. Secure the
cabinet side channels to the window jambs with
two 3/4 inch self-threading screws. When doing
this, be careful not to twist the side channel seals
with the screws.
NOTE: Inserting screws will prevent the air conditioner
from being pushed into the room.
Fig. 10
Fig. 11
16. To replace the front.
First, reconnect the coupler plugs, make the exhaust
control positioned through the front in the proper location.
Then replace the retaining screws that hold the panel in
place. Do not push or pull the front panel louvers.
12
Page 15
NORMAL SOUNDS
NOT
the Energy Saver function under “Cool,” “Dry”
and “Auto” (only Auto-Cooling and Auto-Fan)
modes
E: The unit will automatic ally initiate
High Pitched Chatter
High efficiency compressors
may have a high pitched chatter
during the cooling cycle.
Sound of Rushing Air
At the front of the unit, the sound of
rushing air being moved by the fan
may be heard.
Gurgle/Hiss
“Gurgling” or “his sing” nois e may
be heard due to refrigerant
passing through ev aporator
during normal operation.
Vibration
Unit may vibrate and make noise
because of poor wall or window
construction or incorrect installation.
This DOES NOT indicate a defective
unit.
Pinging or Switching
Droplets of water hitting condenser
during normal operation may cause
“pinging” or “switching” sounds.
NOTE: All of the pictures in this manual are for explanatory purposes only. The actual shape/look of the
air conditioner purchased may be slightly different, but the operations and functions are similar.
AIR CONDITIONER FEATURES
ELECTRONIC CONTROL OPERATING INSTRUCTIONS
Thoroughly familiarize yourself with the control panel as shown below and all of its functions. Afterwards,
follow the symbol for the functions you desire BEFORE operating the unit. This unit can be controlled by
the unit control or with the remote control.
UNIT CONTROL PANEL
Temp./Timer
Adjustment
DISPLAYS
TEMPERATURE
OR TIME OR ERROR CODES
Remote Signal
Receptor
Turns Unit
On/ Off
Auto
Low
Med High
Fan
Sets Fan
Speed
Close
Exhaust Selector
Exhaust
Open
TO TURN UNIT ON OR OFF:
Press ON/OFF button to turn the
unit on or off.
Auto
Cool
TEMP/TIMER
On
Off
TimerMode
Activates Timer
Dry Fan
Sets Mode
Energy
Saver
Energy Saver
Mode
Sleep
Sleep Mode
Check
Filter
Activates Check
Filter
TO CHANGE TEMPERATURE SETTING:
/
Press
UP/DOWN button to change the
temperature setting.
NOTE:Press or hold eit her UP( ) or DOWN ( ) button
until the desired temperature is seen on the display.
.
This temperature will be automatically maintained
anywhere between 62 F(17 C) and 86 F (30 C). If
you want the display to rea d the actual room
temperature, see “To Operate on Fan Only” section.
OOOO
13
Page 16
AIR CONDITIONER FEATURES (CONTINUED)
TO ADJUST THE FAN SPEED:
Press to select one of four fan speeds: “Auto,”
“Low,” “Med” or “High.” Each time the button is
pressed, the fan speed mode is shifted. On “Dry”
mode the fan speed is set at low automatically.
SLEEP FEATURE:
Press Sleep button to initiate the sleep mode .
In this mode the selected temperature will increase
(cooling) or decrease (units with heating only) by
O
2
F/1OC 30 minutes after the mode is selected. The
temperature will then increase (cooling) or decrease
(units with heating only) by another 2
O
F/1OC after
an additional 30 minutes. This new temperature
will be maintained for 6 hours before it returns to the
originally selected temperature. This ends the Sleep
mode and the unit will continue to operate as
originally programmed. The Sleep mode program
can be cancelled at any time during operation by
pressing the “Sleep” button again.
CHECK FILTER FEATURE:
Press Check Filt er button to initiate this feature.
This feature is a reminder to clean the Air Filter for
more efficient operation. The LED (light) will illumi nate after 250 hours of operation. To reset after
cleaning the filt er, press th e “Check Filter” button
and the light will go off.
ENERGY SAVER FEATURE:
Press Energy Saver button to initiate this
function. This function is available on “Cool,” “Dry,”
and “Auto” (only Auto-Cooling and Auto-Fan)
modes. In this mode, the fan will continue to run for
3 minutes after the compressor
shuts off.The fan
then cycles on for 2 minutes, at 10 minute intervals,
until the room temperature is above the set
temperature, at which time the compressor turns
back on and cooling starts.
FOLLOW ME FEATURE:
Follow
Me
Light
flashing
To activate the Follow Me feature, point the remote
control towards the unit and press the “Follow Me”
button. The remote displays the actual temperature at
its location. The remote control will send this signal to
the air conditioner every 3 minutes until the Follow Me
button is pressed again. If the unit does not receive the
Follow Me signal during any 7 minute interval, the unit
will beep to indicate the Follow Me mode has ended.
The actual temperature can be displayed at the unit by
pressing the “Fan” only mode. When in the “Cool”
mode, the unit display indicates the set temperature.
This feature can ONLY be activated
from the remote control. The
remote control serves as a remote
thermostat allowing for precise
temperature control at its location.
TO SELECT THE OPERATING MODE:
To choose operating mode, press the Mode button.
Each time you press the button, a mode is selected in
a sequence that goes from “Auto,” “Cool,” “Dry,” & “Fan.”
The indicator light will illuminate and remain on once
the mode is selected. The unit will automatically
initiate the Energy Saver function under “Cool,”
“Dry,” and “Auto” (only Auto-Cooling and AutoFan) modes.
To operate on “Auto” feature:
When you set the air conditioner in AUTO mode, it will
automatically select cooling, heating (on models with
heating capabilities), or fan only operation depending on
what temperature you have selected and the room
temperature.The air conditioner will control room
temperature automatically around the temperature you set.
In this mode, the fan speed cannot be adjusted.
It starts automatically at a speed according to the
room temperature.
To operate on “Fan” only:
Use this function only when cooling is not desired,
such as for room air circulation or to exhaust stale
air. (Remember to open the vent during this function,
but keep it closed during cooling for maximum cooling
efficiency.) You can choose any fan speed you prefer.
During this function, the display will show the actual
room temperature, not the set temperatur
e as in the
cooling mode. Temperature cannot be adjusted in
“Fan” mode.
To operate on “Dry” mode:
In this mode, the air conditioner will reduce air
humidity. If the space is a closed or sealed area, some
degree of cooling will continue.
TIMER: AUTO START/STOP FEATURE:
When the unit is on or off, first press Timer button.
The TIMER ON indicator light illuminates. It indicates the
Auto Start program is initiated.
When the time of TIMER ON is displayed, if you pres the
Timer button again, the TIMER OFF indicator light
illuminates. It indicates the Auto Stop program is initiated.
Press or hold the UP or DOWN button to change the Auto
time by 0.5 hour increments, up to 10 hours, then by 1
hour increments, up to 24 hours. The control will count
down the time remaining until start.
The selected time will register in 5 seconds and the
system will automatically revert back to display the
previous temperature setting or the room temperature
(depending on whether the unit is powered on or off and
the mode it is in).
Turning the unit ON or OFF at any time or adjusting the
timer setting to 0.0 will cancel the Auto Start/Stop
program.
14
Page 17
AIR CONDITIONER FEATURES (CONTINUED)
DISPLAYS
Shows the set temperature in “°C” or “°F” and the Autotimer settings. While on “Fan” only mode, it shows the
room temperature.
Displays
Error Codes:
AS - Room temperature sensor error - Unplug the unit and
plug it back in. If error repeats, call customer service.
NOTE: If the unit breaks off unexpectedly
due to power being cut, it will restart with the
previous function setting automatically when
the power resumes.
NOTE: If error occurs in “Fan” only mode, unit will
display “LO” (loose connection) or “HI” (short circuit).
HS - Electric heating sensor error - Unplug the unit and
plug it back in. If error repeats, call customer service.
- Evaporator temperature sensor error - Unplug the unit
and plug it back in. If error repeats, call customer service.
(“ ” is displayed as shown in left picture.)
ADDITIONAL THINGS YOU SHOULD KNOW
The Cool circuit has an automatic 3 minute time de layed start if the unit is turned off and on quickly.
After unit is turned off, leave unit off for a minimum of 3 minutes before attempting to turn back on. This prevents
overheating of the compressor and possible circuit breaker tripping. The fan will continue to run during this time.
The control is capable of displaying temperature in degrees Fahrenheit or degrees Celsius.
To convert from one to the other, press and hold the Up and Down Temp/Timer buttons at the
same time, for 3 seconds.
Air D irectional Louvers
Air Direction (4- way)
HOW TO USE:
Use the 4-way directional louvers to direct the air flow
Up or Down and Left or Right throughout the room
as needed.
Move the Center Handles from side to side until the
desired Left/Right direction is obtained.
Exhaust Control
Close
Exhaust
Open
Auto
Low
Med High
Fan
TEMP/TIMER
On
Off
TimerMode
Auto
Dry Fan
Cool
This Exhaust Control allows the air conditioner to
either circulate inside air (Closed) or exhaust air to
the outside (Open).
The Closed position is used when maximum cooling
is desired. It may also be used for air recirculation
without cooling when the air conditioner is set in any
FAN position.
The Open position removes stale air from the room
and exhausts it to the outside. Fresh air is drawn in
through normal passages in the home.
15
Page 18
CARE AND CLEANING
CAUTION
!
Clean air conditioner occasionally to keep it looking and operating like new. Be sure to
unplug the unit before cleaning to prevent shock or fire hazards.
Air Filter Cleaning
The air filter should be cleaned at least every two weeks or as
necessary. Trapped particles in the filter can build up and cause an
accumulation of frost on the cooling coils.
Grasp the filter by the center and pull up and out.
Wash the filter using liquid dishwashing detergent and warm water.
Rinse filter thoroughly.
Gently shake excess water from the filter. Be sure the filter is
thoroughly dry before replacing.
As an alternative, vacuum the filter clean.
NOTE: Never use hot water over 104 F (40 C) to clean the air filter.
Never attempt to operate the unit without the air filter.
N
Cabinet Cleaning
Be sure to unplug the air conditioner to prevent shock or fire
hazard. The cabinet and front may be dusted with an oil-free
cloth or with a cloth dampened in a solution of warm water and
mild liquid dishwashing detergent. Rinse thoroughly and wipe dry.
Never use harsh cleaners, wax or polish on the cabinet front.
Be sure to wring excess water from the cloth before wiping the
controls. Excess water in or around the controls may cause
damage to the air conditioner.
Plug in air conditioner after unit has dried completely.
Winter Storage
If air conditioner will be stored during the winter,
remove it carefully from the window according to the
installation instructions. Cover it with plastic or return it
to the original carton. Always store unit in upright position.
16
Page 19
Before calling for service, please review the chart below.
IssuePossible Solutions
AIR
CONDITIONER NOT
COOLING ROOM, OR NOT
BLOWING COLD AIR
TROUBLESHOOTING TIPS
• Be sure unit is not too large or too small for the area of the room.
• Verify that all doors, windows, curtains and any other openings are closed off. Verify nothing is obstructing the
front grille of unit, such as curtains, etc.
• Allow enough time for room to cool, especially if outside temp is very high.
• Check that the filter is not dirty and louvers are open all the way and blowing in the direction desired.
• Check that unit is set to Cool Mode and that temperature is down enough (but not too low).
• If unit is near a heat source, such as a stove, etc., then relocate unit.
• If air coming from unit is cool to the touch, then unit is working properly; please double check the first three
bullet points above.
• If using Follow Me remote feature, move remote away from unit.
• Temperature sensor behind air filter touching cold coil. These two elements should not be touching.
Carefully straighten tube away from coil.
• Unplug unit for at least 5 minutes. Follow Reset instructions on plug.
AIR CONDITIONER COOLING BUT
ROOM IS TOO WARM - ICE
FORMING ON COOLING COIL
BEHIND DECORATIVE FRONT
AIR CONDITIONER
CYCLING ON AND OFF TOO
FREQUENTLY OR NOT ENOUGH
UNIT WILL NOT TURN ON
UNIT BLOWS FUSES OR POPS
CIRCUIT BREAKER
AIR CONDITIONER IS
MAKING NOISES
• Outdoor temperature is below 64ºF (18ºC). To defrost the coil, set to Fan Only mode.
• Air filter may be dirty. Clean filter. Refer to Care and Cleaning section. To defrost, set to Fan Only mode.
• Thermostat is set too cold for night-time cooling. To defrost the coil, set to Fan Only mode. Then, set
temperature to a higher setting.
• Be sure unit is not too large or too small for the area of the room.
• Remove grille and make sure the temperature sensor is not too close to the coils. These two elements should
not be touching. Carefully straighten tube away from coil.
• Make sure nothing is blocking the grille or side vents.
• Make sure there is no dirt or debris inside the unit or on the filter.
• Reset circuit breaker. Make sure there are not too many items (ie lamps, TV’s, etc.) working off the
same breaker.
• Check plug connection.
• If plug is operating on an on/off switch, be sure that the switch is ‘on’.
• Try plugging unit into another outlet.
• Unplug unit for at least 5 minutes. Follow Reset instructions on plug.
• Make sure there are enough available amps on the circuit for the air conditioner.
• Large units which run on a 230v will require a dedicated 20 or 30 amp circuit.
• Check to be sure the unit is free from debris such as leaves, sticks, etc. Verify nothing is obstructing the unit.
• Check the fan blade for cracks or chips.
• Make sure the unit is properly and securely mounted inside the window or wall.
• Clean the air filter.
WATER PUDDLES INSIDE UNIT
OR IS COMING INTO ROOM
WATER DRIPPING OUTSIDE
REMOTE SENSING / FOLLOW ME
DEACTIVATING PREMATURELY
• Adjust the slope of the unit so that it drains downward toward the exterior of the home.
(See Installation Instructions.)
• Make sure that there is no debris blocking the drainage area of the unit.
• Unit is removing a large quantity of moisture from a humid room. This is normal during excessively humid days.
• Remote control not located within range. Place remote control within 20 ft and 180º radius of the front
of the unit.
• Remote control signal obstructed. Remove obstruction.
NOTE: A highly recommended troubleshoot for any issue in general consists of turning off unit and unplugging for 5 minutes.
It is also recommended to try another wall outlet.
17
Page 20
COMFORT...BUILT TO LAST
Distributed by:
Perfect Aire, LLC
5151 Belt Line Rd.
Suite 878
Dallas, TX 75254
877-365-6274
www.perfectaire.us
Specification and performance data is subject to change without notice.
Printed in China
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.