Pepperl+Fuchs 6000 SERIES Installation And Operation Manual

PROCESS AUTOMATION
INSTALLATION AND OPERATION MANUAL
6000 SERIES PURGE/PRESSURIZATION SYSTEM
6000 Series Purge/Pressurization System
I/O Manual
The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation of proprietorship".
b
6000 Series Purge/Pressurization System
I/O Manual
Contents
Safety note and symbols used ................................................................................................. 1
Symbols used ....................................................................................................................................1
General instructions regarding ATEX ...................................................................................... 2
Certication information ........................................................................................................... 3
Certication markings .......................................................................................................................3
Warning labels ...................................................................................................................................4
Conditions of Safe use ......................................................................................................................4
Purpose ......................................................................................................................................5
Description ................................................................................................................................. 5
6000 control unit .......................................................................................................................6
Electrical & pneumatic diagrams ............................................................................................. 8
6000 control unit power connections ..............................................................................................8
Electrical installation - power and I.S. wiring ................................................................................ 10
Pneumatic requirements ................................................................................................................. 12
Mounting instructions ............................................................................................................. 13
Manifold assembly, LH & RH mount ..............................................................................................13
EPV-6000 vent .................................................................................................................................. 14
6000 Control unit with housing "WH" ...........................................................................................15
Tightening the cover plate ..............................................................................................................16
6000 series component kit ..................................................................................................... 17
Identication of components .........................................................................................................17
Electrical diagrams ......................................................................................................................... 18
Electrical installation - power and I.S. wiring ................................................................................ 20
Component kit installation .............................................................................................................21
Mounting templates - user interface, EPCU, solenoid .................................................................22
Sequence of events ................................................................................................................. 23
Turning on power to the enclosure ................................................................................................23
Turning off power to the enclosure ...............................................................................................24
Operation of the 6000 series and component kit ................................................................. 25
Operation ..........................................................................................................................................25
Set-up procedures of 6000 series system ....................................................................................29
Operation of the 6000 series system .............................................................................................29
Start-up label located on 6000 series control unit .......................................................................30
The user interface ....................................................................................................................31
Programming menu ................................................................................................................. 32
Purge settings ..................................................................................................................................33
Units ..................................................................................................................................................33
Inputs ................................................................................................................................................34
Outputs .............................................................................................................................................38
Password ..........................................................................................................................................39
Language ..........................................................................................................................................39
Bypass control .................................................................................................................................39
Restore defaults ..............................................................................................................................39
Stats ..................................................................................................................................................40
Statistics ...........................................................................................................................................41
Alarm.................................................................................................................................................43
c
6000 Series Purge/Pressurization System
Fault ..................................................................................................................................................43
Clear statistics ................................................................................................................................44
Clear fault ........................................................................................................................................44
Operation screen .............................................................................................................................44
I/O Manual
System dimensions ................................................................................................................. 45
6000 series control unit ..................................................................................................................45
EPV-6000 vent .................................................................................................................................. 46
6000 series component kit .............................................................................................................47
Temperature hub .............................................................................................................................48
Temperature sensor ........................................................................................................................49
6000 Manifold ...................................................................................................................................50
General specications ............................................................................................................51
Model number designators .....................................................................................................54
Accessories .............................................................................................................................55
Maintenance and repair ..........................................................................................................56
Alarm and fault conditions .....................................................................................................56
Dismantling and decommissioning .......................................................................................57
Establishing connection sizes, lengths & bends ................................................................. 58
Programming worksheet .........................................................................................................59
Notes .........................................................................................................................................66
d
6000 Series Purge/Pressurization System
Warning
Note
Safety note and symbols used
It is strongly urged that you follow all instructions and recommendations in this manual, in addition to all applicable codes, standards, and local requirements. Failure to do so voids all warranties, both implicit and
explicit, and relieves the manufacturer of all liability.
Symbols used
This symbol calls your attention to instructions or requirements that must be followed. Failure to observe the instructions and information that this symbol calls
Attention
attention to may result in the failure of the device and any devices or systems connected to it.
This symbol draws your attention to important information.
Note
I/O Manual
This symbol warns the user of potential danger. Failure to observe this warning may lead to personal injury or death and/or property damage.
This symbol accompanies a list of tools you will need to install the unit.
Grounding points internal and external will be identied with a ground symbol:
This symbol is used for AC power:
This symbol is used for DC power:
Pepperl+Fuchs GmbH Lilienthalstraße 200 68307 Mannheim Germany
1
6000 Series Purge/Pressurization System
Note
Warning
Warning
I/O Manual
General instructions regarding ATEX
1. The guidelines
The guideline 2014/34/EU determines the essential health and safety requirements relating to the design and construction of equipment and protective systems intended for use in potentially explosive atmospheres, given in Annex II of the directive.
The guideline 1999/92/EG is addressed to the operator/ user of facilities in explosive areas and governs the safety regulations of persons during installation, handling, and maintenance.
Furthermore, local laws and rules for electrical installations and accident prevention have to be observed.
2. General information for this manual
Preconditions for handling and operating the series 6000 controller safely are basic knowledge of safety regulations and additional training and experience in explosion protection.
4. General information about pressurized enclosures
The pressurized enclosure is one of the most multifunctional applicable types of protection. It is based on a rst ush operation which removes potential, ignitable gas mixtures of the local environment from the enclosure. After the ush, the overpressure will be maintained by adding as much pressurized air as necessary to compensate for the leaks of the enclosure or components. This constant overpressure status protects against the diffusion of potentially explosive atmospheres.
During the ush, the internal pressure will be up to 10-12mbar. In the operation phase, it is reduced to 2-3 mbar. Hot spots at single components inside the enclosure are monitored by temperature sensors (optional) and if required turned off. This assures that no unacceptable surface temperature will occur.
For applications with hazardous dust, the purge process is omitted because purging would raise explosive dust. Instead of pre-purging, the interior of the housing is inspected for dust and cleaned manually if dust is present.
This user manual contains important information and instructions to handle the series 6000 controller in explosive areas safely and to operate it according to guideline 2014/34/EU.
This user manual, in particular the safety instructions, has to be observed by everybody who works with the components.
3. Responsibilities of users and installers
This equipment shall only be used within its intended purpose. Refer to the manual for proper usage.
The user and/or the installer is obligated to let only competent, trained persons work at the 6000 Control Unit who
• are familiar with the regulations about safety and accident prevention and briefed in handling of the component.
• are trained to work on explosion protection equipment.
• know the appropriate instructions and rules for the installation, handling, and maintenance of explosion protected equipment.
For this reason, the pressurized enclosure is especially suited for the use of non-Ex certied equipment in Ex­areas.
The enclosure has to be prepared specially for the use of Ex p:
• all walls have to be additionally armed
• the doors have to be specially constructed
• tested for mechanical stability
• tested for overpressure resistance
When using an inert gas like nitrogen, an asphyxiation hazard can exist.
EN 60079-2 and IEC 60079-2 do not cover both gas and dust hazard atmospheres. The 6000 system provides a solution for both at the same time but would have to be evaluated by the certication bodies for approval.
2
6000 Series Purge/Pressurization System
Certication information
Marking for the 6000 control unit, 6000-__-S2-__-CK-__
Marking for the 6000 Control unit, 6000-__-S2-UN-WH-__ and 6000-__-S2-__-XD-__
I/O Manual
Marking for the 6000 user interface controller, 6000-UIC-01
Marking for the 6000-ISB-___ termination board, DIN mounted
Marking for the 6000 vent, EPV-6000-__-__
Marking for the 6000-TSEN-01
Marking for the 6000-TEMP-01
3
6000 Series Purge/Pressurization System
Warning
Warning
Warning
Warning
I/O Manual
Warning Labels
WARNING - Conduit seal must be installed within 18
inches of the explosion-proof enclosure. To prevent ignition of ammable or combustible atmospheres, disconnect power before servicing.
WARNING - FOR ENCLOSURES IN HAZARDOUS DUST ENVIRONMENTS
This enclosure shall not be opened unless the area is known to be free of ammable materials or unless all devices have been de-energized. Power must not be restored after the enclosure has been opened until combustible dusts have been removed and the enclosure repressurized.
WARNING - FOR ENCLOSURES IN HAZARDOUS GAS ENVIRONMENTS
This enclosure shall not be opened unless the area is known to be free of ammable materials or unless all devices have been de-energized. Power must not be restored after the enclosure has been opened until the enclosure is completely purged of all hazardous gas and the enclosure repressurized.
WARNING - FOR ENCLOSURES IN HAZARDOUS DUST AND GAS ENVIRONMENTS
This enclosure shall not be opened unless the area is known to be free of ammable materials or unless all devices have been de-energized. Power must not be restored after the enclosure has been opened until combustible dusts have been removed and completely purged of all hazardous gas and the enclosure repressurized.
Conditions of Safe Use
1. Conduit seals shall be certied in type of explosion protection ameproof “db”, or explosion-proof Class I/II Div 1 as required for the installation location and suitable for the conditions of use. They shall be correctly installed to the explosion-proof/ameproof enclosure or conduit extensions as required. All NPT threads are to be minimum 5 thread engagement, wrench tight.
2. Seals shall be installed within 18 in. (450 mm) of the explosion-proof/ameproof “db” enclosure.
8. The non-metallic membrane touchpad and display is a potential electrostatic discharge hazard. Use only water damp cloth and allow to air dry for cleaning device. Do not use or install in high charge areas. See IEC 60079-32-1 for further information.
9. In hazardous dust environment, regularly remove dust from the control unit enclosure to prevent excessive temperature rise, including the solenoid valve.
10. Only pressure relief vent model EPV-6000-xx-xx covered under the following certicates can be used with devices covered by this certicate: For ATEX applications: Certicate No. DEMKO 15 ATEX 1622X, DEMKO 07 ATEX 0705753X, or SIRA 09ATEX9337X. For IECEx applications: Certicate No. IECEx UL 15.0147X, IECEx UL 08.0003X or IECEx CSA 09.0007X. For cULus and cCSAus applications: UL certication as part of le E184741 or CSA certication as part of 2205652 (LR90178).
11. For all applications, the 6000-TEMP-XX I.S. temperature hub must be mounted in an enclosure that is a minimum IP54. In hazardous dust environment, the 6000-TEMP-xx temperature hub has to be mounted in an enclosure that is certied for the area classication. The pressurized enclosure does not account for this type of enclosure because power to this device is required before safe operation within the pressurized enclosure. Maintain separation of I.S. to non-I.S. wiring as required by local codes.
12. Caution must be used when handling or cleaning products so there is no static charge buildup. Do not wipe off the 6000-TSEN-xx sensor with dry cloth or use in the presence of high charge generating processes such as ionizers or electrostatic equipment. See IEC 60079-32-1 for further information.
13. The 6000 systems may also be provided with previously certied items (operators, gable glands, terminal box, etc.) as specied in the test reports.
14. Enclosure 6000-DPE-xx is only for I.S. termination board 6000-ISB-xx and/or 6000-TEMP-xx.
3. When the purge control unit is mounted to an enclosure, the complete unit shall be evaluated to the current revision of IEC/EN 60079-2 or NFPA 496 as applicable. See certicates and/or Declaration of Conformity for reference to relevant editions of these standards.
4. The purge control unit has an operating temperature class of 135 °C (T4 temperature class). This temperature shall be considered when mounted to an enclosure.
5. The device must be installed in accordance with the manufacturer’s installation drawing number 116-B027.
6. Intrinsically safe cables extending from the explosion­proof/ameproof "db" enclosure must be provided with at least 0.25 mm insulation thickness per conductive core to maintain segregation between intrinsically safe circuits.
7. The cable entries may be used only in places where they are protected against the inuence of mechanical danger.
4
I.S. Termination Board, DIN Mounted: 6000-ISB-xx
1. In hazardous dust environments, the I.S. termination board, DIN mounted: 6000-ISB-xx must be mounted in an enclosure that is certied for the area classication. The pressurized enclosure does not account for this type of enclosure because power to this device is required before safe operation within the pressurized enclosure.
2. Only connect to the 6000 EPCU I.S. termination connection.
3. All wiring to and from this board is for intrinsically safe connections and must be properly routed and managed per international, NEC, local codes, and applicable standards.
4. See the latest revision of installation drawing 116­B027 for other important installation information.
5. The 6000-CBLA-… is not certied to be used in a Zone 21 location. Use approved cable glands for this area classication.
6000 Series Purge/Pressurization System
Note
I/O Manual
Note:
Peripheral devices such as optional SRM module and I.S. solenoid were not evaluated by UL as part of the intrinsically safe certication.
When using third-party certication, ensure that you match the entity parameters for intrinsically safe devices as shown in control drawing 116-B027.
SRM module is a simple apparatus and does not require third-party certication.
EPV-6000 Vent
1. The EPV vent has an operating temperature class of 135 °C (T4 temperature class). This temperature shall be considered when mounted to an enclosure.
2. When the purge control unit is mounted to an enclosure, the complete unit shall be evaluated to IEC/EN 60079­2: 2014 (Ed. 6)
3. Cables used to connect to an EPV- vent must be provided with at least 0.25 mm insulation thickness per conductive core to maintain segregation between intrinsically safe circuits.
4. In hazardous dust environments, regularly remove dust from the EPV vent to prevent excessive temperature rise. See certicate for full information.
5. In hazardous dust environments, the connector end of the vent shall be protected from direct exposure of a UV light source. See certicate for full information.
The 6000 series system features these main parts:
• Electronic processor (EPCU) housed in an explosion-proof enclosure
• I.S. electrical/pneumatic manifold assembly
• I.S. user interface for programming and monitoring the system
• 316L stainless steel (UNS S31603) type4X IP66 enclosure for EPCU and connections
• Pressure relief vent with ow and pressure monitoring at the exhaust.
The user interface allows programming of up to 4 switch inputs, temperature modules, enclosure power contacts, 2 auxiliary outputs, and various operational functions. Through the user interface menus, conguration of the standard information for setup and operation of a system (purge time, ow rates, pressures, enclosure size, etc.) are easily programmed. Additional features allow inputs for system bypass, enclosure power on/off, temperature overload and activation of rapid exchange ow for cooling or auxiliary relay for separate cooling source, delay power shutdown, and more. The two auxiliary contact outputs can be congured to activate on most of the input switches or any of the congured alarm states for pressure, ows, and temperature.
6. Only EPV-6000-xx-xx vents can be connected to any certied model 6000 control system.
Purpose
The purpose of the Pepperl+Fuchs 6000 series Type X & Ex px, Zone 1 enclosure protection system is to allow the use of general purpose or non-rated electrical or electronic devices located in general purpose enclosures instead of explosion-proof/ameproof, Type 7 or 9 / Ex d enclosures or other means of protection for the rated area. Other purposes include heat, moisture, and dust contamination prevention.
Description
The 6000 series Type X & Ex px purge and pressurization system protects general purpose equipment mounted in a standard enclosure. This allows the enclosure to be located and the equipment operated in a hazardous area. The hazardous area classication can be Class I, Class II, Division 1 / Zone 1, Zone 21. The 6000 series operates by controlling and monitoring compressed instrument air or inert gas through the protected enclosure(s) so as to remove and prevent the accumulation of ammable gas, vapors, or dust.
The power for the solenoid valve on the manifold unit, inputs, the user interface controller (UIC), and EPV-6000 vent are provided by the EPCU through the internal galvanically isolated intrinsic safety barrier. No additional I.S. barrier is required.
The adjustable mounting bracket and the universally mountable vent make the 6000 system easy to install horizontally or vertically onto the enclosure. A component kit is available for custom installations that t specic customer needs.
The 6000 control unit can monitor multiple enclosures and control and accept inputs from two (2) EPV-6000 vents.
The 6000 series provides a complete system for purging and pressurizing enclosures for hazardous location operation.
One (1) operations copy of this manual must be studied and retained by the system operator in addition to one (1) permanent le copy. User’s agents are responsible for transferring this manual to the user/operator prior to start-up.
5
6000 Series Purge/Pressurization System
6000 Control Unit
Main unit
I/O Manual
I.S. wiring terminals
User interface controller
(UIC)
Bracket for mounting to the
enclosure
316L stainless steel
(UNS S31603)
Type 4X (IP66) rating
Removable electronics
Explosion-proof/flameproof
enclosure
3/4" conduit for power
connections
Cable glands for I.S. inputs/outputs
6
6000 Series Purge/Pressurization System
6000 Control Unit
Manifold
I/O Manual
Manifold for purging and
pressurization
Type 4X (IP66)
ttings for
enclosure ow
Needle valve for
pressurization of enclosure
(requires athead
screwdriver for adjustment)
Manifold with
I.S. solenoid
valve
Connection to protective gas
supply
Rotating vent cap
Spark arrestor
Vent
The EPV-6000 vent
is required.
Mounts on vertical or horizontal
surface of the enclosure
Lock nut
Seal washer
I.S. temperature hub
Temperature
monitoring/control
accessories
I.S. temperature sensor
1.5 " NPT knockout (Ø 2", 50.8 mm)
M12 (V1) connector for I.S. connection to control unit
Conduit plug
7
6000 Series Purge/Pressurization System
Warning
Warning
Attention
Warning
Warning
Warning
I/O Manual
Electrical & pneumatic diagrams
Complete 6000 full control unit power connections (-WH-)
General wiring notes
For power connections to the 6000 control unit and relay contacts:
1. All applicable local and national wiring codes MUST be followed when wiring to the unit.
2. Ground wire to be 14 AWG (2.08mm2). Strip length of ground to mate with pigtail under wire nut .437" to .5" (11.1mm to 12.7 mm).
3. If a single wire is used, the maximum wire gauge to the pluggable terminal block is 14 AWG (2.08mm2).
4. If jumpering from one terminal to another at pluggable terminal block, the maximum wire gauge is 16 AWG (1.31mm2) for both wires.
5. Minimum wire gauge to the pluggable terminal
Attention
Warning
Warning
block is 24 AWG (0.20mm2). (Based on connector, not code. Follow all applicable codes.)
6. Strip length of wires terminating into the screw terminals on the pluggable terminal block to be
0.2" to 0.27" (5 mm to 7 mm).
7. Add extra wire length of 1.25" (31.75 mm) past top of opening in explosion-proof/ameproof box to pluggable terminal block (allows connector to be moved out of the way when changing electronics. Prevents repouring seals).
8. Wires are to be neatly tucked back down past the lid threads before lid is placed on unit. The wires must not loop past the high point of the plastic cover. The wire nut should be tucked in last (If not, it may be difficult to access when changing electronics).
9. If using a single conduit seal, the other conduit on the 6000 control unit will need a cap for the end of the conduit with appropriate hazloc certications (A standard 3/4" conduit cap will not work).
10. Conduit seals with or without the 6000-CC­3/4NPT plug must be within 18" (457.2 mm) of internal explosion-proof/ameproof box, or within
15.25" (387.3 mm) from the end of the conduit supplied with the 6000 unit.
11. When wiring to the terminal plug, it is easier to remove the plug, terminate the wires, then
reconnect the plug.
12. When removing the pluggable terminal block, it is recommended that the electronics module be supported by pressing down on top of the EPCU to counteract the lifting force required to remove the connector.
13. Wire should be copper only, rated 90 °C
Attention
minimum. Minimum of 0.25" (6.3 mm) wire insulation thickness required.
14. The minimum wire strand in a stranded wire should have a diameter of 0.1 mm or greater.
15. The 6000-CC-3/4NPT plug is certied to be used only with the 6000 control unit’s ¾” nipples coming out of the housing. This plug is not certied to be used on any other hazardous location equipment.
16. Ensure that electrical, mechanical, and pneumatic connections and requirements are met to operate this system. Please refer to this manual and applicable standards/codes, including current editio9n of the EN/IEC 60079-
14. Electrical supply to the purge system shall be supplied through a switch or circuit breaker and suitably located and easily reached and must be marked as the disconnect for the equipment.
1 7. Power must be removed from the system when
the Ex d enclosure cover is off, unless the area is known to be non-hazardous.
WARNING – To prevent ignition of the ammable atmospheres, the wiring method must ensure that if any wire is disconnected and extended to the opposite terminal, a 2-inch separation must be maintained.
I.S. wiring notes
For wires going to the explosion-proof/ameproof box on the I.S. side:
1. The wire strip length is to be between 0.2" and
Attention
0.27" (5 mm and 7 mm).
2. The wire's gauge depends on the number of connections. Fewer wires allow for heavier gauge and will still meet the conduit seal ll requirement. See the applicable standards for ll requirement.
3. The terminal blocks are rated for a wire size of 16 AWG (1.31 mm2 ) to 28 AWG (0.08 mm2 ).
8
6000 Series Purge/Pressurization System
Warning
Warning
Warning
Attention
4. If multiple wires need to land to a single terminal (e.g., the RS-485 bus), these wires must be either crimped to a single pin or grouped in an external junction box with one wire going into the terminal.
5. The wires must have a minimum insulation thickness of 0.01" (0.25 mm).
6. Add extra wire length of 1.25" (31.75 mm) past top of opening in explosion-proof/ameproof box to pluggable terminal block. (Allows connector to be moved out of the way when changing electronics. Prevents repouring seals.)
7. Conduit seal on I.S. wiring side must be within 18" (457.2 mm) of the explosion-proof/ameproof box.
8. Wire should be copper only, rated 90 °C minimum.
9. The minimum wire strand in a stranded wire should have a diameter of 0.1 mm or greater.
I/O Manual
For wires going to the I.S. interface board in the main housing or to the DIN-rail-mount I.S. board:
1. The wire strip length is to be between 0.16" and
0.24" (4 mm and 6 mm).
2. The terminal blocks are rated for a wire size of 16 AWG (1.31 mm2) to 26 AWG (0.081 mm2).
3. The only terminals that might have multiple connections are the shield connections. These must be crimped to a single pin before connection to the board.
4. If cables are used (recommended for connections to the vents and UIC), it is recommended that the cables be shielded.
5. The wires must have a minimum insulation thickness of 0.01" (0.25 mm).
6. Wire should be copper only, rated 90 °C
Attention
minimum.
7. The minimum wire strand in a stranded wire should have a diameter of 0.1 mm or greater.
9
6000 Series Purge/Pressurization System
Note
Note
IS PWR 1+
IS PWR 1-
IS DATA 1A
IS DATA 1B
IS 1 SHLD
IS PWR 2+
IS PWR 2-
IS DATA 2A
IS DATA 2B
IS 2 SHLD
IS PWR 3+
IS PWR 3-
IS DATA 3A
IS DATA 3B
IS 3 SHLD
INPUT 1-
INPUT 1+
INPUT 2-
INPUT 2+
INPUT 3-
Temp Module
Vent 1
Vent 2
Inputs 1 thru 4
Enclosure
Prewired
Electrical installation - power and I.S. wiring
I/O Manual
Power to
EPCU
GND
GND
GND
Prewired
L1
GND
N
BK
OR
GN
WT
BK/WT
BL/WT
RD/WT
GN/WT
OR/BK
BL
RD
WT/BK
RD/BK
User interface
connection
(pre-wired)
EPCU I.S. connector
I.S. solenoid valve
from manifold
(pre-wired)
Temperature module connection (when Vent 2 is used)
Vent 1 connection
Vent 2 connection or Temperature Module connection
Inputs 1 - 4, 5.0 V DC
Contacts
(2) N.O.
Aux
Output 1
(1) SPDT
Aux
Output 2
(1) SPDT
Connector color code for the user interface, temperature module, and vent:
PWR + BN (brown) PWR - BU (blue) DATA_A WH (white)
DATA_B BK (black)
Requires standard explosion-proof seals to explosion-proof/ameproof enclosure at a
Warning
maximum distance of 18" (457.2 mm).
When removing the terminal block from the EPCU stack, place your hand on top of the plastic to support the stack when lifting the terminal block off the stack.
10
Manifold connection Vent connection
GND
'A' White
+1
-2
'+' Brown
'B' Black
'-' Blue
The EPCU is prewired to the I.S. terminal board.
Note
Both enclosure power contacts are switched at the same time.
6000 Series Purge/Pressurization System
Warning
No wiring is to be in
the area between the
terminals
I/O Manual
I.S. wiring
Non- I.S. wiring
Incoming ground wires
should be terminated into
the supplied wire nut
WARNING: To prevent ignition of the ammable
atmospheres, the wiring method must ensure that if any wire is disconnected and extended to the opposite terminal, a 2" (50.8 mm) separation must be maintained.
EPCU
Maintain a minimum space of 2" (50.8 mm) between the I.S. wiring and the non - I.S. wiring.
Attention
Make sure that the wiring is neatly tucked into the explosion-proof housing. Use wire ties if necessary. As a rule, no wires are to be in the area between the two terminals, as shown above.
11
6000 Series Purge/Pressurization System
Note
I/O Manual
Pneumatic requirements
Protective gas supply
The protective gas supply to the enclosure system must be a clean, instrument quality compressed air or inert gas ltered to a minimum of 40 microns. It must contain no more than trace amounts of ammable gas, vapor, or dust.
The protective gas supply compressor intake must originate in a nonhazardous location. The suction duct passing through a hazardous location and the protective tubing and piping must be fabricated from noncombustible materials suitable for the prevailing hazardous and environmental conditions.
The protective gas supply provided must be able to handle the ow and pressure requirements for purging and pressurization (see page 66, Establishing connection sizes, lengths & bends).
Needle valve
3/8" tubing
Protective
Plug
gas supply
EFC-6-SS
Pneumatic connections
The 6000 series system requires only two pneumatic connections to the protective enclosure, one for the exhaust for the vent mounting and the other for the protective gas supply for purging and pressurization. The vent requires a single 1 1/2" conduit knockout (Ø2"
[50.8mm]) hole in the enclosure. A lock ring with gasket
for sealing are provided. The control unit for the 6000 series provides a compression tting with a lock ring and washer connected to a 3/8" tube. All tubing and ttings are 316L (UNS S31603) stainless steel. A single hole into the enclosure as noted on the mounting template will provide the installation for this tting.
For replacement of this tubing use only 3/8" tubing with wall thickness of 0.035" (0.9 mm).
The 6000 series control unit with the manifold can be top, bottom, right, or left-hand mounted on the enclosure. However, the manifold connections may have to be reversed as shown below.
Needle valve
3/8" tubing
EFC-6-SS
Plug
Protective gas supply
Plug
Solenoid
valve, EEx io
2/2 way
Supply to enclosure
Pressurization adjustment
To adjust, use a at head screw driver inserted into the needle valve of the manifold as shown. Turn clockwise to decrease the ow, counter-clockwise to increase the ow. The maximum number of complete rotations allowed is ve (5).
Diagram shown is without plumbing. See the diagrams on the following page for plumbing
Note
installation.
Unit must be powered to get a pressure reading.
When delivered, the system is in its default mode (fully automatic [FA]). It may be easier to adjust
Note
safe pressure in standard (STD) or semiautomatic (SA) mode so that the system does not automatically begin purging when energized.
Supply to enclosure
MAXIMUM of ve (5) turns
Counterclockwise
rotation
increases ow
6000 control unit
housing
Plug
Solenoid valve, EEx io 2/2 way
Flathead screwdriver
Clockwise
rotation
decreases ow
Needle valve
in manifold
12
6000 Series Purge/Pressurization System
Mounting Instructions
Manifold assembly – left-hand or right-hand mount
Left-hand mount*
*Reverse ttings for right-hand mount
Protective gas
supply inlet
Protective gas to
enclosure
I/O Manual
3/8" SS tube
(included)
3/8" ferrule tting
(included)
1/4 - 20
at head screws
(4 included)
3/8" SS tube
(included)
3/8" ferrule tting
(included)
Wiring entry
EFC-6-SS (included)
EFC-6-SS nut
(included)
13
6000 Series Purge/Pressurization System
Note
Warning
EPV-6000 vent
Tools:
1 1/2" NPT knockout (Ø 2" [50.8mm] hole ) for vent
Vent mounted on the outside of the enclosure
Pressurized enclosure
I/O Manual
Locking nut w/grounding screw
(included)
Seal gasket (included)
Ø 2" (50.8 mm)
6000 control unit
I.S. wire tag
(included)
Vent mounted on the inside of the enclosure
Pressurized enclosure
6000 control unit
Vent cap
(included)
EPV-6000
Vent cable (included)
Ø 2" (50.8 mm)
Seal gasket (included)
Locking nut w/o ground
(included)
Vent cap (included)
I.S. wire tag
(included)
Vent is not gravity sensitive and can be installed
in any orientation.
14
Hex screws 0.05"(1.3 mm) (3)
*Bulkhead tting for reference
pressure
EPV-6000
*Reference tube
Cord grip CG-8
(optional)
Vent cable (included)
*Reference tubing and hardware included with EPV-6000-SS models
Cable to the vent is I.S. wiring and must be properly isolated from other wiring.
6000 Series Purge/Pressurization System
6000 Control unit with housing "WH"
Tools:
Appropriate sized drill bits or knockout holes 1 1/16" open end box wrench Bolts: 1/4-20 (provided),
hole clearance = 0.27" (6.86 mm) diameter EFC-6-SS (provided):
hole clearance = 0.61" (15.54 mm) diameter
I/O Manual
Seal washer (3 included)
Lock washer (3 included)
1/4-20 pan head bolts
(3 included)
Grounding lug
(included)
Mounting bracket
(included)
6000 control unit
1/4-20 pan head
w/lock washer screws
(4 included)
Ø 0.61" (15.54 mm) hole
Ø 0.27" ( 6.86 mm)
hole (3x)
1/4-20 nuts (3 included)
Locking nut
w/grounding screw
(included)
Seal gasket
(included)
Vent cap
(included)
EPV-6000
Vent cable
(included)
Enclosure
EFC-6-SS nut (included)
EFC-6-SS (included)
1. Drill holes using template. Check the scale if printing an electronic version.
2. Assemble tubing and tting to control unit. Install on the "Out" port of the correct side.
3. Bolt mounting plate to the enclosure. Type 4X washers must be mounted inside the enclosure. Tighten to 60 – 80 in-lb (16.38 – 18.08 Nm).
3/8" stainless steel tube, 2.5" (65 mm) long (included)
3/8" ferrule tting (included)
4. Put 2 of the mounting screws in the back of the control unit to align with the key holes in the mounting plate.
5. Hang the control unit onto the plate. Slide the unit towards the enclosure so that the EFC-6-SS tting is in the proper location.
6. Tighten the 2 bolts. Put the other two mounting bolts in place and tighten.
7. Place the EFC-6-SS bolt in position and tighten.
15
6000 Series Purge/Pressurization System
(2.5")
Warning
Tightening unit cover plate
The screws on the unit cover plate must be tightened in the order shown on the diagram to the right. The cover plate to the main housing has positive stops so that the gasket is not over tightened. Torque screws at 12 in-lb (1.36 Nm).
When rotating the UIC, torque down the 4 screws at 4 in-lb (0.46 Nm) using a crisscross pattern.
Note
I/O Manual
45
1 2
63
Left-hand mounting template
ø15.5 mm
(.60")
ø 7. 0 mm
(.25")
ø 7. 0 mm
(.25")
ø 7. 0 mm
(.25")
19.0 mm (.75")
60.0 mm
2.35"
Right-hand mounting template
ø 15.5 mm
(.60")
ø 7. 0 mm
(.25")
189.5 mm
(7.45")
(7.45")
114.5 mm
(4.50")
57.0 mm
(2.25")
189.5 mm
(4.50")
114.5 mm
(2.25")
57.0 mm
2.35"
60.0 mm (2.5")
ø 7. 0 mm
(.25")
ø 7. 0 mm
(.25")
19.0 mm (.75")
16
6000 Series Purge/Pressurization System
Attention
Attention
6000 Series component kit
Identication of components
I/O Manual
Optional pneumatic manifold
User interface (Included)
Cannot be mounted in a
hazardous dust environment.
with solenoid (Included)
EPV-6000 vent: required for 6000 control unit / component kit
Atmospheric reference kit (6000-ACC-514482)
for mounting vent inside the enclosure
EPV-6000
The EPV-6000 vent is required.
The reference kit comes with the EPV-6000-SS vent but must be ordered when mounting the EPV-6000-AA vent inside the enclosure.
Control unit and explosion-proof/
ameproof enclosure (Included)
6000 series component kit accessories
6000-DPE-01-xxx (Not Included)
Dust-proof enclosure to house the
6000-ISB-01 and 6000-TEMP-01 devices
6000-ISB-01 (Not Included)
DIN-mounted I.S. termination board.
See data sheet for specications
6000-CBLA-ISB-xxxt (Not Included)
Cable assembly for connection from the
6000 EPCU to the 6000-ISB-01. See
data sheet for specic lengths.
17
6000 Series Purge/Pressurization System
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Attention
Warning
Warning
I/O Manual
Electrical diagrams
General wiring notes for component kit design
For power connections to the control unit and relay contacts:
1. All applicable local and national wiring codes MUST be followed when wiring to the unit.
2. Protective earth wire to be 14 AWG (2.08 mm2). Strip length of earth to mate with pigtail under wire nut .437" to .5" (11.1mm to 12.7 mm).
3. If a single wire is used, the maximum wire gauge to the pluggable terminal block is 14 AWG (2.08mm2).
4. If jumpering from one terminal to another at pluggable terminal block, the maximum wire gauge is 16 AWG (1.31 mm2) for both wires.
5. Minimum wire gauge to the pluggable terminal
Attention
block is 24 AWG (0.20 mm2). (Based on connector, not code. Follow all applicable codes.)
6. Strip length of wires terminating into the screw terminals on the pluggable terminal block to be
0.2" to 0.27" (5 mm to 7 mm).
12. When removing the pluggable terminal block, it is recommended that the electronics module be supported by pressing down on top of the EPCU to counteract the lifting force required to remove the connector.
13. Wire should be copper only, rated 90 °C minimum.
14. The minimum wire strand in a stranded wire should have a diameter of 0.1 mm or greater.
15. The 6000-CC-3/4NPT plug is certied to be used only with the 6000 control unit’s ¾” nipples coming out of the housing. This plug is not certied to be used on any other hazardous location equipment.
16. Ensure that electrical, mechanical, and pneumatic connections and requirements are met to operate this system. Please refer to this manual and applicable standards/codes, including current editio9n of the EN/IEC 60079-
14. Electrical supply to the purge system shall be supplied through a switch or circuit breaker and suitably located and easily reached and must be marked as the disconnect for the equipment.
7. Add extra wire length of 1.25" (31.75 mm) past top of opening in explosion-proof/ameproof box to pluggable terminal block. (Allows connector to be moved out of the way when changing electronics. Prevents repouring seals.)
8. Wires are to be neatly tucked back down past the lid threads before lid is placed on unit. The wires must not loop past the high point of the plastic cover. The wire nut should be tucked in last (if not, it may be difficult to access when changing electronics).
9. If using a single conduit seal, the other conduit on the 6000 control unit will need a cap for the end of the conduit with appropriate hazloc certications. (A standard 3/4" conduit cap will not work.)
10. Conduit seals or the 6000-CC-3/4NPT plug must be within 18" (457.2 mm) of internal explosion­proof/ameproof box, or within 15.25" (387.3 mm) from the end of the conduit supplied with the 6000 unit.
11. When wiring to the terminal plug, it is easier to remove the plug, terminate the wires, then reconnect the plug.
1 7. Power must be removed from the system when
the Ex d enclosure cover is off, unless the area is known to be non-hazardous.
I.S. wiring notes
For wires going to the explosion-proof/ameproof box on the I.S. side:
1. The wire strip length is to be between 0.2" and
Attention
0.27" (5 mm and 7 mm).
2. The wire's gauge depends on the number of
Attention
connections. Fewer wires allow for heavier gauge and will still meet the conduit seal ll requirement. See the applicable standards for ll requirement.
3. The terminal blocks are rated for a wire size of 16 AWG (1.31 mm2 ) to 28 AWG (0.08 mm2 ).
4. If multiple wires need to land to a single terminal (e.g., the RS-485 bus) these wires must be either crimped to a single pin or grouped in an external junction box with one wire going in to the terminal.
5. The wires must have a minimum insulation thickness of 0.01" (0.25 mm).
18
Loading...
+ 50 hidden pages