Pentax HE260A, HE260B Installation Information

HE260A,B
69-1106EF-3
Bypass Flow-Through Humidifier
INSTALLATION INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
APPLICATION
INSTALLATION
WARNING
Hazardous V oltage. Can cause Personal Injury or Equipment Damage.
Do not cut or drill into any air conditioning or electrical accessory.
CAUTION
Freezing Water and High Water or Static Pressure Hazard. Can cause water damage or permanent equipment damage.
• The humidifier must be located where the ambient temperature is
TEMPLATE
IMPORTANT
above 32°F (0°C) and below 160°F (71°C).
• Be sure supply plenum static pressure is no greater than 0.3 in. w.c. and water pressure is no greater than 125 psi.
To assure optimal product performance, be sure the template is level before marking.
2. Tape the template in position and trace around the template.
3. Remove the template and carefully cut the rectangular opening.
4. Disassemble the humidifier; remove the cover and take out the
humidifier pad assembly. See Fig. 2. NOTE: Sidewalls are interchangeable for either left or right
5. Position the humidifier housing in the opening (be sure it is level), so the locking tabs are in place on the lower sheet metal edge of the opening.
6. Secure the humidifier housing to the opening at the top and bottom using sheet metal screws.
bypass installation. To change direction, remove the screws holding each sidewall, switch sidewall locations and reinstall the screws.
COVER
SIDEWALL
WATER FEED NOZZLE
HUMIDIFIER PAD ASSEMBLY
FRAME
HUMIDIFIER HOUSING
WATER FEED TUBE
TEMPLATE
1. Determine the best location for the humidifier and draw a level line on
the plenum. See Fig. 1.
IMPORTANT
Mount the humidifier at least 3 in. (76 mm) above the furnace jacket to allow adequate space for the solenoid valve and drain line. Check that there is adequate space above the humidifier to remove and install the humidifier cover. Do not install on a furnace jacket.
HORIZONTAL
HIGHBOY
DOWN
FLO
LOWBOY
M12248B
BYPASS SIDEWALL
Fig. 2. Humidifier components.
7. Locate the other plenum and cut an opening for a 6 in. (152 mm) collar.
8. Install the 6 in. (152 mm) collar.
NOTE: Be sure to install a duct damper for summer shutoff on
systems with air conditioning.
9. Install a 6 in. (152 mm) diameter duct from the collar to the humidifier. NOTE: Some installations require a 90° elbow attachment to the
collar.
10. Seal the duct connections with duct tape.
M12304
Fig. 1. Typical humidifier installation locations.
® U.S. Registered Trademark Copyright © 1998 Honeywell Inc. • All Rights Reserved
NOTE: To avoid sagging and stress on the humidifier, add support
when ducting is longer than 4 ft (120 cm).
TEMPLATE
11. Reinstall the humidifier pad assembly in the humidifier housing.
NOTE: Be sure the water feed tube nozzle is not pinched or kinked.
12. Hinge the cover in place and secure with the thumbscrew located at the bottom of the cover.
PLUMBING SADDLE VALVE
Hot or cold water, either hard or softened, can be used in the humidifier.
1. Use the self-piercing saddle valve (included) to tap into the water supply line at an appropriate location.
WIRING
CAUTION
Hazardous V oltage. Can cause personal injury or equipment damage.
• Disconnect power supply before installing or servicing.
• On multispeed blower applications, do not wire the high voltage side of the transformer to the same power source that services the furnace blower or the transformer may burn out prematurely.
All wiring must comply with applicable local codes, ordinances and regulations.
1. Mount the transformer in a convenient location.
IMPORTANT
Install transformer on the outside of a grounded metal junction box using only a 7/8 in. (22 mm) knockout hole. Place mounting tabs into the knockout hole and firmly tighten the locking screw. Field wiring connections and grounding means for the tr ansformer and enclosure shall be in accordance with the National Electrical Code (NEC) and the Canadian Electrical Code (CEC).
2. Connect the wires to the 120V side of the transformer.
For humidity control wiring connections:
1. Wire the humidifier solenoid valve, current sensing relay or sail switch,
humidity control and transformer. Refer to humidity control installation instructions for mounting and wiring information.
CAUTION
Chemical Hazard. Can cause personal injury or equipment damage.
Do not use any line connected to an air conditioner.
IMPORTANT
• The saddle valve is not designed to regulate water flow. The valve is either open or closed.
• To prevent debris from clogging the solenoid in-line filter, be sure to install the saddle valve handle pointing toward the ceiling.
NOTE: Lightly clean the copper tubing ends with fine sandpaper
before making any connections.
2. Use 1/4 in. O.D. copper tubing and connect the saddle valve to the inlet side of the solenoid valve.
a. Place the brass compression nut over the copper tubing.
NOTE: Do not over tighten the compression nut. Moderate tightness
prevents leaking.
b. Slide the brass ferrule ov er the tubing. c. Insert the tubing into the solenoid valve fitting and support the
valve while tightening the compression nut.
NOTE: Slope the drain downward for correct drainage.
3. Connect a 1/2 in. drain tube to the humidifier drain fitting and run to a suitable drain.
IMPORTANT
• The humidifier must be energized during blower motor cycles for proper operation.
• Current sensing relay or sail switch is not needed with the Automatic Humidity Control.
NOTE: Select models of fan centers include humidifier taps so the current
sensing relay or sail switch are not needed.
CHECKOUT
1. Open the saddle valve.
NOTE: The furnace blower must be on for the humidifier to operate.
2. Set the thermostat setpoint to 10°F (6°C) above the room temperature.
3. Set the Convertible Humidity Control to a high humidity setting, or
place the H1008A Automatic Humidity Control in the test position.
4. Observe the water running out of the drain line to be sure the humidifier is working properly.
5. Check for leaks.
6. Reset the thermostat and Convertible Humidity Control to a
comfortable setting, or the Automatic Humidity Control to the desired frost factor setting.
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN 55408-0524
69-1106EF—3 G.H. 6-98 www.honeywell.com
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7