INSTALLER SYSTEM TEST
INSTALLER SYSTEM TESTS
FocusPRO® 5000 Series
To begin, press and hold the s and t buttons until the
1.
display changes.
Presss/t to turn system on/off.
2.
System test System status
number number
10
Done
Press NEXT to advance to next test.
3.
Press DONE to terminate system test.
4.
Proceed to Installer System Tests on page 8.
5.
Next
0
FocusPRO® 6000 Series
To begin, press and hold the s and t buttons until the
1.
display changes.
Presss/t to turn system on/off.
2.
System test System status
number number
10
Done Next
Press NEXT to advance to next test.
3.
Press DONE to terminate system test.
4.
Proceed to Installer System Tests on page 8.
5.
0
Test the system’s heating, emergency heat, cooling, and fan.
Available tests vary by thermostat and system type.
System Test
Number
10 Heating system 0 Heat and fan off
20 Emergency
30 Cooling system 0 Compressor and
40 Fan system 0 Off
caution
Table 2. Installer System Test
Test Type System Status Number
heating system
EQUIPMENT DAMAGE HAZARD.
Compressor protection is bypassed during testing.
To prevent equipment damage, avoid cycling the
compressor quickly.
and Description
1 First stage heat
on (Fan turns on if
Setup Function 1 is
set to 1, 5, 9, or 10
OR setup Function
3 is set to 1)
2 Second stage heat
on
3 Third stage heat
on
0 Heat and fan off
1 Heat and fan on
2 Second stage heat
(Aux. heat) turns on
fan off
1 Compressor and
fan on
2 Second stage
compressor on
1 On
FocusPRO® 5000
and 6000 Series
Thermostats
INSTALLER SETUP AND
SYSTEM TEST POCKET GUIDE
6 7 8
INSTALLER SETUP
FocusPRO® 5000 Series
To begin, press and hold the s and FAN buttons until
1.
the display changes.
Press s or t to change settings.
2.
Function Setting
1
Done
Press NEXT to advance to the next function.
3.
Press DONE to exit and save settings.
4.
Proceed to Installer Setup Functions on page 4.
5.
Next
2 3 4 5
0
FocusPRO
1.
2.
®
6000 Series
To begin, press and hold the s and FAN buttons until
the display changes.
Press s or t to change settings.
Function Setting
1
Done Next
Press NEXT to advance to the next function.
3.
Press DONE to exit and save settings.
4.
Proceed to Installer Setup Functions on page 4.
5.
0
INSTALLER SETUP FUNCTIONS
Available option and default settings vary by thermostat.
Setup functions Setting & Options
1 System type 0 1 heat / 1 cool Conv.
2 Changeover valve
3 Fan control
5 First stage heat
6 Second stage
7 Auxiliary heat
Table 1. Installer Setup
(O/B terminal)
(heating)
cycle rate
heat/Aux heat
cycle rate
cycle rate
(factory default in bold)
1 1 heat / 1 cool heat
pump (no Aux. heat)
2 Heat only (2-wire, 3-wire
zone valves [Series 20],
and normally open zone
valves)
3 Heat only with fan
4 Cool only
5 2 heat / 1 cool heat
pump (with Aux. heat)
6 2 heat / 2 cool Conv.
7 2 heat / 1 cool Conv.
8 1 heat / 2 cool Conv.
9 2 heat / 2 cool heat pump
(no Aux. heat)
10 3 heat / 2 cool heat
pump (with Aux. heat)
0 Controls valve in cooling
1 Controls valve in heating
0 Gas/Oil heat (equipment
controls heating fan)
1 Electric furnace (thermo-
stat controls heating fan)
5 Gas or oil furnaces of
less than 90%
efciency
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
9 Electric furnaces
[Other options: 1–12]
5 Gas or oil furnaces of
less than 90% efciency
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
9 Electric furnaces
[Other options: 1–12]
5 Gas or oil furnaces of
less than 90% efciency
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
9 Electric furnaces
[Other options: 1–12]
Setup functions Setting & Options
8 Emergency heat
9 First stage
10 Second stage
12 Manual/Auto
13 Adaptive Intel-
14 Temperature
15 Compressor
16 Schedule format 0 5/2 (weekdays
26 Auxiliary heat
27 Heat temperature
28 Cool temperature
Functions 13 and 16 only available on the 6000 series;
function 26 only available on the 5000 series
Table 1. Installer Setup
cycle rate
compressor cycle
rate
compressor cycle
rate
changeover
ligent Recovery
display
protection
control
range stops
range stop
(factory default in bold)
9 Electric emergency heat
1 Steam or gravity
3 Hot water systems or fur-
naces of 90%+ efciency
5 Gas or oil furnaces of
less than 90% efciency
[Other options: 1–12]
3 Recommended
[Other options: 1–6]
3 Recommended
[Other options: 1–6]
0 Manual changeover
(Heat/Cool/Off)
1 Auto changeover (Heat/
Cool/Auto/Off)
2 Auto changeover only
(Auto)
1 On
TM
0 Off
0 Fahrenheit
1 Celsius
5 5-minute compressor
off time
[Other options: 0–4
minutes]
and weekends
programmable)
1 5/1/1 (weekdays,
Saturday, and Sunday
programmable)
0 Comfort
1 Economy
90 Max. heat temperature
setting is 90°F (32°C)
[Other options: 40–89°F
(4.5°C to 32°C)]
50 Min. cool temperature
setting is 50°F (10°C)
[Other options: 51–99°F
(10.5°C to 37°C)]
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com
® U.S. Registered Trademark
© 2006 Honeywell International Inc.
US Patent No. 6595430, D509151; other
Patents Pending. All Rights Reserved
69-2026 M.S. 09-06