Pentair ULTRATEMP ETi 220 Installation And User Manual

ULTRATEMP ETi
HYBRID HEATER
ENGLISH
ENGLISH
ESPAÑOL
FRANÇAIS
IMPORTANT SAFE T Y INSTRUCTIONS
RE AD AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
INSTALLATION AND
USER’S GUIDE
i
CUSTOMER SERVICE / TECHNICAL SUPPORT
If you have questions about ordering Pentair Aquatic Systems, (“Pentair”) replacement parts, and pool products, please use the following contact information:
Customer Service (8 A.M. to 4:30 P.M. — Eastern and Pacific Times) Phone: (800) 831-7133 Fax: (800) 284-4151
Web site
Visit www.pentairpool.com or www.staritepool.com to find information about Pentair products.
TABLE OF CONTENTS
Important Warning and Safety Instructions .......
General Information ..............................................
Heater Introduction Installation Requirements General Installation Information General Features
Positioning the Heater ..........................................
Materials Needed for Installation Roof Run-off Lawn Sprinklers Equipment Pad Recommended Clearances Flue Gas Condensation Management
Preventative Maintenance Condensate Cartridge Service
Installation .............................................................
Anchor Clamp Installation System Layout Internal Automatic Flow Control Valve Water Connections and Plumbing Heat Pump Drainage Connection Isolation and Check Valves Manual Bypass Valve Pressure Relief Valve (PRV) Multi-Heater Installations Solar Installations Water Pressure Switch Adjustment Gas Connections
Gas Line Installation Checking Gas Pressure Through Gas
Control Valve Sediment Traps Gas Pressure Testing
Electrical Connections and Wiring
Wiring Diagram - Input Wiring Diagram - Output
Connecting to an Automation System ................
Remote Operation Relay Remote Controls
Connecting to EasyTouch via Heater Spade
Terminals
Connecting to EasyTouch via RS-485 Connector
Pin Configuration for Heater Control Board
to EasyTouch Connecting EasyTouch to the Heater
Operating the Heater ............................................
Swimming Pool Energy Saving Tips Control Panel Overview Sequence of Operation Pre-Startup
P/N 475922 Rev. A 5/18/18
Technical Support
Sanford, North Carolina (8 A.M. to 4:30 P.M. ET)
Phone: (919) 566-8000 Fax: (919) 566-8920
Moorpark, California (8 A.M. to 4:30 P.M. PT) Phone: (805) 553-5000 (Ext. 5591) Fax: (805) 553-5515
ii 1
1 1 1 1
2
2 2 2 3 3 5 5 5
6
6 6 7 7 7 8 8 8 9 10 10 11 11
12 12 12 13 14 15
16
16 16
17 18
19 19
20
20 20 21 21
Basic Operating Instructions Turning Off Gas to the Heater Safety Controls
Air Flow Switch (AFS) Water Pressure Switch (WPS) High Limit Switch (HLS) and Automatic Gas
Shut-off Switch (AGS) Stack Flue Sensor (SFS) Thermal Fuse (TF) Float Switch (CFS) Ignition Module Operation
Operator Menu Tree Guide and Navigation Using the Operator Menus
Starting and Stopping the Heater Changing the Set Point Efficiency Mode Selection Heater Timer Remote Mode - Relay Remote Mode - RS-485 (Serial Cable) Remote Mode - IntelliFlo
Timers and Delays Control Panel Alarm Messages Service Menu Tree Guide and Navigation Using the Service Menus
Eco-Time Boost Temperature Setting Temperature Scale Set Water Temperature Offset Defrost Cycle Run Time Counters
Locking the Control Panel
Maintenance ........................................................
Water Chemistry
Total Alkalinity Balancing pH Disinfectant Residual
General Maintenance Condensate Drainage Winterizing Spring Start Up Professional Maintenance and Service
Technical Data .....................................................
Electrical Supply - Voltage Requirements Temperature Resistance Chart Pressure Chart Pressure Drop Curves
Troubleshooting ..................................................
Replacement Parts ..............................................
Heater Parts Breakdown Parts List - Refrigeration and Outer Shell Parts List - Gas System Parts List - Electrical Parts List - Plumbing
22 22 22 23 23 23 23 24 24 24 24 25 26 26 26 26 26 26 27 27 27 28 29 29 30 30 30 30 30 31 31
32
32 32 32 32 33 33 34 34 34
35
35 35 36 36
37 43
43 44 45 46 47
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
IMPORTANT WARNING AND SAFETY INSTRUCTIONS
Important Notice:
This guide provides installation and operation instructions for this hybrid heater. Consult Pentair with any questions regarding this equipment.
Attention Installer: This guide contains important information about the installation, operation and safe use of this product. This information should be given to the owner and/or operator of this equipment after installation or left on or near the heater.
Attention User: This manual contains important information that will help you in operating and maintaining this heater. Please retain it for future reference.
READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This is the safety alert symbol. When you see this symbol on your system or in this manual, look for one of the following signal words and be alert to the potential for personal injury.
Warns about hazards that can cause death, serious personal injury, or major property damage if ignored.
Warns about hazards that may cause death, serious personal injury, or major property damage if ignored.
Warns about hazards that may or can cause minor personal injury or property damage if ignored.
NOTE Indicates special instructions not related to hazards.
Carefully read and follow all safety instructions in this manual and on equipment. Keep safety labels in good condition; replace if missing or damaged.
Before installing this product, read and follow all
warning notices and instructions which are included. Failure to follow safety warnings and instructions can result in severe injury, death, or property damage. Call (800) 831-7133 for additional free copies of these instructions.
Codes and Standards
UltraTemp ETi heaters are listed by UL as complying with the latest edition of the “UL Standard for Safety for Heating and Cooling Equipment”, UL 1995, CSA C22.2 No. 236 and ANSI Z21.56
Installation must be in accordance with all local codes and/or the latest edition of the National Fuel Gas Code, ANSI Z223.1 and the latest edition of the National Electrical Code, NFPA 70 (US).
Installation in Canada must be in accordance with the latest CAN/ CGA-B149.1 or .2 and CSA C22.1 Canadian Electric Code, part 1.
This heater, when installed, must be electrically grounded and bonded in accordance with local codes, or, in absence of local codes, with the National Electrical Code, ANSI/NFPA70 (US) or in Canada in accordance with the Canadian Electric Code, part 1 as applicable.
Do not permit children to use this product.
Improper installation, adjustment, alteration, service
or m ai ntenance c an cause property damage, personal injury or death. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
RISK OF ELECTRICAL SHOCK OR ELECTROCUTION.
The electrical supply to this product must be installed by a licensed, certified electrician or qualified personnel in accordance with the National Electrical Code and all applicable local codes and ordinances. Improper installation will create an electrical hazard which could result in death or serious injury to pool or spa users, installers, or others due to electrical shock, and may also cause damage to property. Read and follow the specific instructions inside this guide.
For units intended for use in other than single-family
dwellings, a clearly labeled emergency switch shall be provided as part of the installation. The switch shall be readily accessible to the occupants and shall be installed at least 5 feet [1.52 m] away, adjacent to, and within sight of the unit.
Consumer Information and Safety
UltraTemp ETi heaters are designed and manufactured to provide safe and reliable service when installed, operated and maintained according to the information in this manual and the installation codes referred to in later sections. Throughout the manual, safety warnings and cautions are identified by the “ “ symbol. Be sure to read and comply with all of the warnings and cautions.
The U.S. Consumer Product Safety Commission warns
that elevated water temperature can be hazardous.
See below for water temperature guidelines before setting temperature.
The following “Safety Rules for Hot Tubs”
recommended by the U.S. Consumer Product
Safety Commission should be observed when using the spa:
1. Spa or hot tub water temperatures should never exceed 104° F. [40° C.]. A temperature of 100° F. [38° C.] is considered safe for a healthy adult. Special caution is suggested for young children. Prolonged immersion in hot water can induce hyperthermia.
2. Drinking of alcoholic beverages before or during spa or hot tub use can cause drowsiness which could lead to unconsciousness and subsequently result in drowning.
3. Pregnant women beware! Soaking in water above 100° F. [38° C.] can cause fetal damage during the first three months of pregnancy (which may result in the birth of a brain-damaged or deformed child). Pregnant women should stick to the 100° F. [38° C.] maximum rule.
4. Before entering the spa or hot tub, the user should check the water temperature with an accurate thermometer. Spa or hot tub thermostats may err in regulating water temperatures.
5. Persons with a medical history of heart disease, circulatory problems, diabetes or blood pressure problems should obtain their physician’s advice before using spas or hot tubs.
6. Persons taking medication which induce drowsiness, such as tranquilizers, antihistamines or anticoagulants should not use spas or hot tubs.
Should overheating occur or the gas supply fail
to shut off, turn off the manual gas control valve to the heater. Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of control system and gas control which has been underwater.
Risk of fire, carbon monoxide poisoning, or
asphyxiation if exhaust venting system leaks.
Only qualified service technicians should attempt to service the heater, as leakage of exhaust products or flammable gas may result from incorrect servicing.
ii
ENGLISH
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
iii
IMPORTANT WARNING AND SAFETY INSTRUCTIONS
The U.S. Consumer Product Safety Commission warns that carbon monoxide is an “invisible killer”.
Carbon monoxide is a colorless and odorless gas.
1. Carbon monoxide is produced by burning fuel, including natural gas and propane.
2. Proper installation, operation and maintenance of fuel-burning appliances in the home is the most important factor in reducing carbon monoxide poisoning.
3. Be sure that fuel burning appliances such as heaters are installed by professionals according to manufacturer’s instructions and codes.
4. Always follow the manufacturer’s directions for safe operation.
5. Have the heating system inspected and serviced annually by a trained
service technician.
6. Install battery-operated carbon monoxide alarms. The alarms should be certified to the requirements of the most recent UL, IAS, CSA and IAPMO standard for carbon monoxide alarms. Test carbon monoxide alarms regularly and replace dead batteries.
Hyperthermia occurs when the internal temperature of the body reaches a level several degrees above normal body temperature of 98.6° F. [37° C.]. The symptoms of hyperthermia include: drowsiness, lethargy, dizziness, fainting, and an increase in the internal temperature of the body.
The symptoms of hyperthermia include:
1. Unawareness of impending danger.
2. Failure to perceive heat.
3. Failure to recognize the need to leave the spa.
4. Physical inability to exit the spa.
5. Fetal damage in pregnant women.
6. Unconsciousness resulting in danger of drowning.
CARBON MONOXIDE GAS IS DEADLY!
THIS PRODUCT MUST BE INSTALLED AND SERVICED BY A PROFESSIONAL SERVICE TECHNICIAN, QUALIFIED IN POOL HEATER INSTALLATION. Some jurisdictions require that installers be licensed. Check with your local building authority about contractor licensing requirements. Improper installation and/or operation could create carbon monoxide gas and flue gases which could cause serious injury or death. Improper installation and/or operation will void the warranty.
Exhaust from this pool heater contains toxic levels of carbon monoxide, a dangerous, poisonous gas you cannot see or smell. Symptoms of carbon monoxide exposure or poisoning include dizziness, headache, nausea, weakness, sleepiness, muscular twitching, vomiting and inability to think clearly. IF YOU EXPERIENCE ANY OF THE ABOVE SYMPTOMS, IMMEDIATELY TURN OFF THE POOL HEATER, LEAVE THE VICINITY OF THE POOL OR SPA AND GET INTO FRESH AIR IMMEDIATELY. THE POOL HEATER MUST BE THOROUGHLY TESTED BY A GAS PROFESSIONAL BEFORE RESUMING OPERATION.
EXCESSIVE CARBON MONOXIDE EXPOSURE CAN CAUSE BRAIN DAMAGE OR DEATH.
• NEVER use this pool heater indoors.
• NEVER use this pool heater in the home or in partly enclosed areas
(such as garages). Install far from open windows, doors, vents and other openings.
• Pentair strongly recommends that exhaust systems be initially and
periodically tested for proper operation. This testing can be accomplished by using a hand-held carbon monoxide meter and/or by consulting with a gas professional.
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
• Pool heaters must be used in conjunction with carbon monoxide detectors installed near the pool heater. The carbon monoxide detectors must be periodically inspected for proper operation so as to insure continued
safety. Broken or malfunctioning carbon monoxide detectors must be
replaced immediately.
This heater is equipped with an unconventional gas
control valve that is factory set at a pressure of -.2 inches wc. Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation or service must be performed by a qualified installer, service agency or the gas supplier. If this control is replaced, it must be replaced with an identical control. Do not attempt to adjust the gas flow by adjusting the regulator setting.
Risk of fire or explosion from incorrect fuel use.
Do not try to run a heater set up for natural gas on propane gas or vice versa. Only qualified service technicians should attempt to convert heater from one fuel to the other. Do not attempt to alter the rated input or type of gas by changing the orifice. If it is necessary to convert to a different type of gas, consult your Pentair dealer. Serious malfunction of the burner can occur which may result in loss of life. Any additions, changes, or conversions required in order for the appliance to satisfactorily meet the application needs must be made by a Pentair dealer or other qualified agency using factory specified and approved parts. The heater is available for use with natural gas only. It is not designed to operate with any other fuels. Refer to the nameplate for the type of gas the heater is equipped to use. Use only fuel for which the heater in designed.
Risk of fire or explosion from flammable vapors.
Do not store gasoline, cleaning fluids, varnishes, paints, or other volatile flammable liquids near heater.
Risk of explosion if unit is installed near propane
gas storage. Propane (LP) gas is heavier than air.
Consult local codes and fire protection authorities about specific installation requirements and restrictions. Locate the heater away from propane gas storage and filling equipment as specified by the Standard for the Storage and Handling of Liquefied Petroleum Gases, CAN/CSA B149.2 (latest edition) or ANSI/NFPA 58 (latest edition).
Combustion air contaminated by corrosive chemical
fumes can damage the heater and will void the warranty.
Label all wires prior to disconnection when servicing
controls. Wiri ng errors can cause i mproper and dangerous operation. Wiring errors can also destroy the control board.
• Connect heater to 240 Volt, 60 Hz., Single Phase power only.
• Verify proper operation after servicing.
• Do not allow children to play on or around heater or associated equipment.
• Never allow children to use the pool or spa without adult supervision.
• Read and follow other safety information contained in this manual prior to operating this pool heater.
General Specifications
Installation Location Certified for Use: OUTDOOR USE ONLY. Failure to provide the proper clearances outlined on page 3-4 will lower the performance of the heat pump and void the warranty.
Water Pipe/Heater Connection: Plastic 2” PVC (Unions included)
Flow Rate:
Maximum 120 gpm [456 lpm] - If system flow rate exceeds 120 gpm, a bypass valve is required. Minimum 30 gpm [110 lpm]. Maximum Working Water Pressure 50 psi
For Electrical Supply and Voltage Requirements, refer to the table on page 35.
GENERAL INFORMATION
1
Heater Introduction
Thank you for choosing the UltraTemp ETi™ Hybrid Heater. Proper installation and service of your new heating system, and correct chemical maintenance of the water will ensure years of heater operation. The UltraTemp ETi heater is equipped with Pentair’s advanced heater technology which includes a heat pump and a pool heater, with a multifunction temperature controller to continuously monitor the hybrid heater for proper operation. These heaters are designed with direct spark ignition (DSI) for on demand heat, which eliminates the need for a standing pilot.
The heater is certified as complying with the Standard for Gas Fired Pool Heaters, ANSI Z21.56/CSA 4.7, and with the Standard for Heating and Cooling Equipment, UL 1995/CSA C22.2 No. 236-15. This heater is intended for use in heating fresh water swimming pools or spas.
Installation Requirements
Correct installation is required to assure safe operation. The requirements for Pentair heaters include the following:
Dimensions for critical connections (see Figure 1,
page 2).
Field assembly (if required).
Appropriate site location and clearances (pages 2-4).
Proper electrical wiring (pages 14-16).
Adequate water flow (see page iii).
This manual provides the information needed to meet these requirements. Review all application and installation procedures completely before continuing the installation.
General Specifications,
General Installation Information
1. Installation and service must be performed by a qualified installer or service agency, and must conform to all national, state, and local codes.
2. Heaters get electrical power from an external source and provide a dual electronic thermostat control system for pool/spa combinations or preheat convenience.
3. The heater is designed for the heating of chlorine, bromine or salt system swimming pools and spas. It should NOT be used as a space heating boiler, or general purpose water heater.
4. The heater should be located in an area where leakage of the heater or connections will not result in damage to the area adjacent to the heater or to the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the heater. The pan must not restrict air flow.
5. The heater is designed for outdoor operation in non-freezing conditions only. If installed for seasonal use in freezing climates, the heater must be winterized to avoid freeze damage. See Winterizing, page 34.
General Features
Dual digital thermostats offer precise temperature control to maintain the desired separate water temperatures in pool/spa combinations without overheating or wasting energy.
Long-life corrosion resistant composite plastic cabinet stands up to severe climates and pool chemicals.
100% pure titanium heat pump and direct-fire gas heat exchangers assure corrosion-free performance for extra long life.
Self-diagnostic control panel monitors and troubleshoots heater operations to ensure safe, dependable operation.
Automatic Defrost feature senses refrigerant temperature and prevents the heat pump evaporator coil from freezing, allowing the heater to operate at even lower temperatures.
Compatible with all automated control packages. RS-485 communication compatible with EasyTouch® Control Systems.
Thermostatic expansion valve (TXV) controls refrigerant flow for optimum efficiency and BTU output over a wider operating range.
Elevated base pan for positive drainage of condensation.
2-inch plumbing connections for easy installation.
Separate isolated electrical compartment prevents internal corrosion, extends heater life.
Adjustable timer allows the operator to set the heater to run for a predetermined time. Incremental by 10 minutes to a maximum of 99 hours.
An extensive list of operational conditions, alarms
and water temperatures are logged on the control board. This information is available for the user to track performance and troubleshoot issues.
Four unique operating modes: Heat Pump only,
Gas Heater only, Dual and Hybrid.
ENGLISH
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
2
POSITIONING THE HEATER
CARBON MONOXIDE GAS IS DEADLY – Exhaust from this pool heater contains carbon monoxide, a dangerous, poisonous gas you
cannot see or smell. Symptoms of carbon monoxide exposure or poisoning include dizziness, headache, nausea, weakness, sleepiness, muscular twitching, vomiting and inability to think clearly. IF YOU EXPERIENCE ANY OF THE ABOVE SYMPTOMS, IMMEDIATELY TURN OFF THE POOL HEATER, LEAVE THE VICINITY OF THE POOL OR SPA AND GET INTO FRESH AIR IMMEDIATELY. THE POOL HEATER MUST BE THOROUGHLY TESTED BY A GAS PROFESSIONAL BEFORE RESUMING OPERATION. EXCESSIVE CARBON MONOXIDE EXPOSURE CAN CAUSE BRAIN DAMAGE OR DEATH.
When pool equipment is located below the pool surface, a leak from any component can cause large scale water loss or flooding.
Pentair Water Pool and Spa, Inc. can not be responsible for such water loss or flooding which may cause damage to property or to the product. Avoid placing the heater in locations where it can cause damage by water or condensate leakage. If this is not possible, provide a suitable drain pan to catch and divert any leakage.
Only a qualified service person should install the UltraTemp ETi™ Hybrid Heater. Before installing this product, refer to the Important Warning and Safety Instructions on page ii.
In the United States, installation must be in accordance with local codes and the most recent edition of the National Fuel Gas Code, ANSI Z223.1/NFPA-54. In Canada, install the heater in accordance with local codes and the most recent edition of the Natural Gas and Propane Installation Code, CAN/CSA B149.1.
Materials Needed for Installation
The following items are needed and are to be supplied by the installer for all heater installations:
1. Plumbing connections (2-inch).
2. Level surface for proper drainage.
3. Suitable electrical supply line. See rating plate on unit for electrical specifications. A junction box is not needed at the heater; connections are made inside of the heater electrical compartment. Conduit may be attached directly to the heater jacket.
4. Electric cutout switch that will interrupt all power to the unit. This switch must be within line of sight of the heater. Check local codes for requirements.
5. Watertight conduit to run the electrical supply line.
6. Suitable gas supply line with sediment trap (see Table 1 on page 11 for sizing requirements).
6.7”
(170mm)
Lawn Sprinklers
Avoid placing lawn sprinkler near the heater ­they can spray water into the heater and void the warranty. Be sure to direct any spraying water away
from the heater. Note the wind direction to be sure water from sprinklers is not blown toward the heater. Sprinkler heads can produce high water pressure and spray at an angle, different from typical rain and humid weather. Also, sprinklers connected to a well water system can cause mineral build up on the evaporator coils and electronics. Salt water can also be an issue if located near the coast.
48.3”
34.4”
(874mm)
(1227mm)
50.7”
(1288mm)
Roof Run-off
Make sure the heater is not located where large amounts of water may run-off from a roof into the unit.
Sharp sloping roofs without gutters will allow massive amounts of rain water, mixed with debris from the roof to be forced through the unit. A gutter or down spout may be needed to protect the heater.
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
4.7”
(119mm)
(1115mm)
12.9”
(328mm)
43.9”
45.7”
(1146mm)
Figure 1
Equipment Pad
For proper drainage of condensation and rain water, place the heater on a flat slightly pitched surface, such as a concrete or fabricated slab (pad).
If possible, place the pad at the same level or slightly higher than the filter system equipment pad.
The equipment pad should also be in an area where leaves or other combustible debris will not collect on or around the heater.
Note:
Be sure that the pad is pitched not more than 1/4 in. per foot in any direction as needed for runoff.
Note: The equipment pad should be no less than 4 in. (100 mm) thick.
Recommended Clearances
All criteria given in the following sections reflect minimum clearances. However, each installation must also be evaluated, taking into account the prevailing local conditions such as proximity and height of walls, and proximity to public access areas.
The UltraTemp ETi™ Hybrid Heater must be placed to provide clearances on all sides for maintenance and inspection. Refer to Figure 2 for a visual representation of the proper clearances.
1. At least 30 inches [610 mm] of clearance is required on both the plumbing and control panel side of the heater. This will provide necessary room for servicing.
2. At least 12 inches [305 mm] of clearance must be available on all the other sides of the heater to allow for proper air flow.
3. If the heater is to be installed under a cover or under a vertical overhang, the unit must have a minimum of five (5) feet [1.5 m] clearance from the top of the heater.
4. Install a minimum of five (5) feet [1.52 m] from the inside wall of the pool or spa unless the heater is separated from the pool or spa by a five (5) foot [1.52 m] high solid fence or other permanent barrier. Canadian installations require a minimum of three (3) meters [9.84 ft] from pool water.
5. Install heater a minimum of 12 in. [305 mm] from the wall of the house.
6. For minimum exhaust vent clearances, see Figure 3 on next page.
Note: In Canada, the heater must be installed with
the top of the vent at least 10 ft. (3 m) below, or to either side of, any opening into a building.
If installing the heater next to or near an air
conditioning unit, heater or another gas pool heater, allow a minimum of 36 in. (91.4 cm) between the unit and the heater.
3
ENGLISH
12"
min.
(305 mm)
SLAB
NO SPRINKLERS
SERVICE ACCESS
30"
min.
(762 mm)
Figure 2: Heater Clearances
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
SERVICE ACCESS
30" min.
(762 mm)
3"
(76 mm)
SLAB
OPEN
AIR FLOW OUT
OVER HANG
5
FT min.
(1.5 m)
12
"
min.
(305 mm)
AIR FLOW IN
4
Recommended Clearances (cont.)
OUTDOOR INSTALLATION VENTING GUIDELINES
3’
(0.9m)
4’
(1.2m)
4’
(1.2m)
From window or door
Vent Termination:
Must be at least 3 ft. (0.9 m) above any forced air inlet located within a 10 ft. (3.5 m) radius.
Must be located 12 in. (30.5 cm) away from the building wall and the following distances away from any building wall openings, included but not limited to vented eaves, doors, windows, gravity air inlet:
4 ft. (1.2 m) below, 4 ft. (1.2 m) horizontally
Building
12"
(30.5cm)
4’
(1.2m)
Force
Air Inlet
SIDE VIEW
From building wall
Exhaust Grill (Vent)
Roof Overhang
Building
4’
(1.2m)
Check local b
for setback requirements.
ROOF OVERHANG
12"
(30.5cm)
Property Line
uilding codes
Figure 3: Vent Clearances
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
5
Flue Gas Condensation Management
The UltraTemp ETi™ Hybrid Heater is a condensing appliance. The flue gases will produce condensate while in operation and must be drained correctly.
The condensate pH level is between 3.1 and 4.2. Pentair recommends neutralizing the condensate to avoid potential damage over time to the drainage system, and to comply with local water authorities where applicable. To neutralize the condensate, use the Condensate Neutralizer Cartridge provided with the heater. The condensate drain must be installed so as to prevent accumulation of condensate. When a condensate pump is not used, the tubing must continuously slope downward toward the drain with no spiraling.
Note: Consult local codes for treated condensate disposal method.
DO NOT allow the exhaust flue gases to vent
through the neutra lizer. All condensate drains MUST have a trap to prevent flue gas leakage. Flue gas leakage can cause personal injury or death from carbon monoxide. Check with local authorities for regulations regarding discharge of condensate to the drain sewer system.
pH levels of 5.0 and below may harm some floor
drains and/or pipes, particularly those that are metal. Ensure that the drain, drainpipe, and anything that will come in contact with the condensate can withstand the acidity. Damage caused by failure to install a neutralizer kit or to adequately treat condensate will not be the manufacturer’s responsibility.
Preventative Maintenance
Annual condensate assembly inspection: Inspect
the internal tubing top for any dirt or particles that could collect and clog the condensate neutralizer cartridge.
Based on operating conditions, algae buildup in the condensate cartridge may occur. Excessive algae buildup can prevent proper condensate drainage
ENGLISH
DO NOT expose the condensate cartridge to
freezing temperatures without draining. This could damage the cartridge. See page 34 for proper Winterizing instructions.
Condensate Cartridge Service
If the control board reads “REPLACE CNC”, check pH of condensate liquid. If the pH is below 5.0, replace the condensate cartridge with a Condensate Neutralizer Kit, (P/N 475954).
If the pH is not known, replace the condensate cartridge when the control board recommends.
To clear this alarm, press the DOWN arrow and MODE button simultaneously. The alarm may take a few moments to clear after the buttons are pressed.
Figure 4: Condensate Neutralizer Cartridge Installed
Mounting
Bracket
in the Heater Base
Internal Tubing
Condensate Neutralizer
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
6
ANCHOR CLAMPS
ANCHOR
CLAMPS
ANCHOR CLAMPS
FILTER
HEATER
TO
POOL
GATE VALVE
FROM
POOL
FROM FILTER
MANUAL
BY-PASS
1/4” x 2-1/4” Stainless
Steel Anchor Bolt
(not included)
INSTALLATION
The installation instructions contained in this manual are designed for use by qualified personnel only, trained especially for installation of this type of heating equipment and related components. Some states require installation and repair by licensed personnel. If this applies in your state, be sure your contractor possesses the appropriate license.
Anchor Clamp Installation
Installation of the anchor clamps is recommended in all installations. Installation of the anchor clamps is required in Florida (see Florida Building Code 301.13).
Anchor clamps hold the heater to the equipment pad in order to withstand high winds caused during extreme weather (i.e. hurricanes).
Note: Anchor clamps are included with the heater. They can be found attached to the wood pallet that the heater is shipped with.
To install the anchor clamps:
1. Be sure the heater is in its permanent location on the equipment pad.
2. Place the clamps at the base of the heater in the eight (8) locations, shown in Figure 5.
Note: Bolts and washers are not included with the heater. The installer must provide 1/4” x 2-1/4” stainless steel anchor bolts and the appropriate size washers to mount the clamp to the concrete equipment pad. Be sure to check local codes.
3. Fit the hook of each clamp into the slots in the base panel of the heater.
4. Mark the position of the hole in each clamp on the equipment pad.
5. Use a masonry drill bit and drill a hole in the cement with a diameter as determined by the concrete anchor, at each of the marks on the concrete equipment pad. The hole should be approximately 2-3/4” (7 cm.) deep.
6. Position the anchor clamps so that the holes in the clamps are over the drilled holes in the equipment pad and the other end of the clamp is secured inside of the heater base.
7. Insert an anchor bolt through each clamp into the anchor and tighten to secure the clamp and heater to the equipment pad. See Figure 6.
Note: Anchor bolts should be tightened to around
four (4) ft/lbs.
CLAMPS
ANCHOR
Figure 5: Anchor Clamp Locations
System Layout
The image below shows the standard plumbing layout with a single UltraTemp ETi™ Hybrid Heater unit. Follow Figure 7 from right to left for the standard plumbing sequence.
Arrangement of pool system components (other than the standard plumbing image below), and the location of the heater (above or below the pool water surface) can affect the operation of the heater’s water pressure switch.
The pressure switch can be adjusted to accommodate this effect if the heater water connections are no more than six (6) feet [1.82 m] below the pool water surface.
See instructions for pressure switch adjustment on pages 10-11. If the heater is installed outside of this range, an external water flow switch may need to be installed in the plumbing upstream of the heater.
Note:
Be advised that when pool equipment is located
below the pool surface a leak can result in large-scale water loss or flooding. Pentair is not responsible for such water loss or flooding or damage.
Figure 7
Heater
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
Base
Concrete Pad
1/4” Stainless
Steel Washer
(not included)
Anchor Clamp
Figure 6
PUMP
Internal Automatic Flow Control Valves
The inlet/outlet header of the UltraTemp ETi™ Hybrid Heater comes equipped with an internal water management system with two automatic flow control valves. The automatic flow control valves maintain the proper flow through the heater at rates up to 120 gpm (454 lpm). If the filter system flow rate is higher than 120 gpm (454 lpm), install a manual bypass valve.
Note:
Be advised that if your circulation pump is over 2
HP or if the total flow exceeds 120 gpm (454 lpm), you will have to add an external bypass valve. Excess water flow will damage the heat exchanger.
Water Connections and Plumbing
Always be sure that flow requirements and pool water turnover rates can be maintained with the
installation of additional equipment and plumbing restrictions.
2 in. Quick Connect fittings have been installed on the water inlet and outlet connections. Filtered cool water is plumbed to the heater.
Plastic piping (PVC Schedule 40) should be connected to the heater. The unions, provided with the unit, accept 2 in. PVC pipe.
The heater requires proper water flow and pressure for its operation. To properly operate the heater requires a flow rate of at least 30 GPM, but optimal performance is achieved at 50 GPM. The maximum working pressure for the system is 50 PSI.
See Figure 8 for the recommended installation. The filter pump discharges to the filter, the filter discharges to the heater, and the heater discharges directly to the pool or spa.
A manual bypass valve should be installed before the heater when the pump flow exceeds 120 GPM (454 LPM).
Make sure that the outlet plumbing from the heater contains no shut-off valves or other flow restrictions that could prevent flow through the heater (except for pool installations as noted below, or winterizing valves where needed). To switch flow between the pool and spa, use a diverter valve. Do not use any valve that can shut off the flow.
Install the chemical feeder downstream of the heater. Install a chemical resistant one-way check valve between the heater and the chemical feeder to prevent back-siphoning through the heater when the pump is off.
Note: If the heater is plumbed in backwards, it will cycle continuously. Make sure piping from filter is not reversed when installing heater.
Connect the heater directly to 2 in. PVC pipe, using the provided unions. Heat sinks are not required. The low thermal mass of the heater will prevent overheating of the piping connected to the pump even if the heater shuts down unexpectedly.
7
Occasionally a two-speed pump will not develop enough pressure on the low speed to operate the heater. In this case, run the pump at high speed only to operate the heater. If this does not solve the problem, do not try to run the heater. Instead, correct the installation.
Do not operate the heater while an automatic pool cleaner is also operating. If the circulation pump suction is plugged (for example by leaves), there may not be adequate flow to the heater. Do not rely on the pressure switch in this case.
Main Drain
Pool
From Pool
3-Way
Valve
Spa
3-Way
Valve
Chlorinator
Check Valve
Filter
Pump
3-Way
Valve
Figure 8
Heat Pump Drainage Connection
Condensation (water) will be produced while the heat pump is in operation. The heater base is designed to allow the condensation to exit through the bottom drain port when the unit is running.
Before operating the heater for the first time, the drain hose barb must be installed into the threaded drain port located in the base of the heater.
To install the Drain Hose Barb and Drain Hose:
1. Thread the drain hose barb into the threaded drainage port in
the base of the heater. See Figure 9.
2. Connect a 5/8” garden hose to the hose barb.
3.
Ensure the end of the garden hose is positioned so that drainage will flow away from the heater and equipment pad.
Figure 9
DRAIN HOSE BARB
5/8" X 1/2" NPT
HEAT PUMP DRAINAGE PORT
ENGLISH
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
8
Isolation and Check Valves
When any equipment is located below the surface of the pool or spa, valves should be placed in the circulation piping system to isolate the equipment from the pool or spa. Check valves are recommended to prevent back-siphoning. Back-siphoning is most likely to occur when the pump stops, creating a pressure­suction differential. Do NOT sanitize the pool by putting chlorine tablets or sticks into the skimmer(s). When the pump is off, this will cause a high concentration of chlorine to enter the heater, which could cause corrosion damage to the heat exchanger.
Exercise care when installing chemical feeders
so as to not allow back siphoning of chemical into the heater, filters or pump. When chemical feeders are installed in the circulation of the piping system, make sure the feeder outlet line is down stream of the heater, and is equipped with a positive seal noncorrosive Check Valve, (P/N R172288), between the feeder and heater.
Manual By-Pass Valve
Where the water flow rate exceeds the maximum 120 GPM, a manual bypass should be installed. After installing the valve, adjust the valve to bring the flow rate within the acceptable range. Then remove the valve handle or lock it in place to avoid tampering.
Lower Gas Engine
Manifold Plug
Figure 10
Pressure Relief Valve (PRV)
Ex p los i o n ha zar d ! A n y he ate r ins t all e d
with restri ctive devices in th e piping system downstream from the heater, (including check valves, isolation valves, flow nozzles, or therapeutic pool valving), must have a relief valve installed as described in this section.
Canadian code, and some U.S. local codes, may require installation of a Pressure Relief Valve (PRV). Purchase and install a Hybrid Pressure Relief Valve Kit (P/N 475943) complying with the ANSI/ASME Boiler and Pressure Vessel Code, having a capacity equal to the Btu/hr rating of the heater.
Note: The relief pressure of the valve MUST NOT EXCEED 50 PSI. The relief valve must be installed vertically.
To install the pressure relief valve: Note: Be sure to use threaded seal tape (PTFE) or
equivalent, on all threaded metal pipe connections.
1. Remove the heater service panel.
2. Remove the lower gas engine manifold 3/4” brass
plug. See Figure 10.
3. Thread the Schedule 40 brass pipe and 45-degree elbow [1], included in the PRV kit, into the lower gas engine manifold. The elbow should be oriented so that the elbow’s female thread is horizontal. See Figure 11.
4. Thread the second Schedule 40 brass pipe and 90-degree elbow [2] into the 45-degree elbow [1]. Ensure that the open end of the 90-degree elbow is oriented vertically. See Figure 11.
5. Install the Pentair pressure relief valve (P/N
072138), included in the PRV kit, or an equivalent 50 PSI 3/4” ASME-Type IV relief valve [3] into the 90-degree elbow [1]. See Figure 11.
Note: Ensure the relief valve is oriented so the
outlet is facing straight into the heater and will not direct towards the service panel.
6. Inspect the valve annually to ensure proper operation. Replace if improper operation is determined.
!
"
Pressure Relief
Valve (Installed)
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
Figure 11
Extend 12" (305 mm)
past end heater
inlet for hydraulic
balancing
Extend 12" (305 mm) past end heater inlet for hydraulic balancing
From Pool Pump
Flow Meter
Minimum
2" PVC Pipe
2" PVC Pipe
Flow Meter
To Pool
OPTIONAL
2" Check Valve Bypass
Check Valves are optional on heater inlets but will help system balancing
36"
(914 mm)
12"
Extend 12"
(305 mm) past
end heater
inlet for hydraulic
balancing
Extend 12" (305 mm) past end heater inlet for hydraulic balancing
From Pool Pump
Flow Meter
Minimum
3" PVC Pipe
2" PVC Pipe
Flow Meter
To Pool
3" Ball Valve Bypass
Check Valves are optional on heater inlets but will help for system balancing
36"
(914 mm)
2" PVC Pipe2" PVC Pipe
2" PVC Pipe
3" PVC Pipe3" PVC Pipe
120 GPM (456 lpm)
Minimum
(305 mm)
Multi-Heater Installations
All plumbing on multiple heater installations must be done in parallel (see Figure 12 and 13 below). An equal flow of water to each heater is important for optimum operation.
Note: It may be necessary to adjust the water pressure switch if a unit is installed below the water level. Refer to page 10-11 for details on when and how to adjust the pressure switch.
Each heater in a multiple unit installation allows a maximum flow rate of 100 gpm (380 lpm) and requires a minimum of 30 gpm (110 lpm).
9
(305 mm)
Figure 12 Dual Heater Layout
60 GPM (220 lpm)
Minimum
ENGLISH
12"
Figure 13 Multiple Heater
Layout
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
10
FILTE
S
SPA
OOL
A
RETURN
OOL
N
CHECK
VALVE
FROM SOLAR
TO SOLAR
PUMP
POOL DRAIN
SPA DRAIN
CHECK
VALVE
SPA MAKE-UP
Solar Installations
The UltraTemp ETi™ Hybrid Heater can be used in combination with other heating schemes such as solar. All heat sources must be plumbed in series to work correctly and efficiently.
A recommended plumbing layout for a heater-solar combination heating system for a pool / spa combination is shown below (Figure 14). Your system may not contain all of these components, but the basic plumbing will apply by eliminating the component in the illustration that is not a part of your system.
Note: Water temperatures produced by supplemental heating sources, such as solar, are not regulated or controlled by the heater and may exceed the maximum temperature allowed.
P
RETUR
P
SP
Figure 14
Heater-Solar Layout
Turn star wheel clockwise to raise pressure set point
Turn star wheel counterclockwise to lower pressure set point
A reference scale is on the back of pressure switch
Water Pressure
Figure 15
Switch
Star Wheel
Water Pressure Switch Adjustment
The water pressure switch should be adjusted to turn
the heater off when the pump is off. Setting the switch to close at too low of a flow can damage the appliance. Adjust the switch to turn the heater off, not on.
The pressure switch is preset at the factory for activation at 6 psi [41.4 kPa]. This factory setting works for most basic installations. Only adjust the water pressure switch if the heater does not operate when the proper flow is applied to unit or if the heater does not shut off when the filter pump is off. Occasionally, unusual plumbing configurations or necessary restrictions in the plumbing may cause pressure sensing problems. In these rare situations, the plumbing system configuration may require adjustment of the water pressure switch.
Adjustment of the pressure switch may be necessary if any part of the filter system piping is 3 feet [0.91 m] or more above the top of the heater.
In general, if the heater is installed more than 6 feet [1.83 m] below the pool surface, an external water flow switch must be added to the plumbing system.
On some installations, the piping from the heater to the pool is very short. The back pressure could be too low to trigger the pressure switch. If this happens, install a directional fitting or elbow where the return line enters the pool. This will increase back pressure for the heater to operate properly. Be sure to check that the system flow is above the minimum requirement of 30 gpm (110 lpm) after the directional fitting installation.
Be sure the pool filter is clean before making any pressure switch adjustment: A dirty filter will restrict the water flow and the pressure switch cannot be adjusted properly.
To adjust the pressure switch:
The following adjustment is for installations where the heater is
1. Be sure that all valves in the system are set to allow
2. Set the heater temperature above the actual temperature
3. Once the heater is running, turn off the filter pump. The
4. If the heater continues to operate when the filter pump is
5. Remove the heater’s left front panel and remove
6. Slowly rotate the adjustment wheel on the water pressure
below pool water level.
water flow through the heater. Start the filter pump.
to call for heat. Turn the heater ON.
heater should turn off immediately.
off, then the water pressure switch needs to be adjusted.
remaining right front panel. The water pressure switch is located in the water plumbing in the lower corner of the heater.
switch in a counterclockwise direction until the “LOW WATER FLOW” Alarm shows on the LCD, the red SERVICE light turns ON, and the heater stops. See Figure 15.
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
Water Pressure Switch Adjustment (cont.)
7. Check the setting of the water pressure switch by starting and stopping the filter pump and checking the control panel and operation of the heater between each flow change.
8. If the water pressure switch cannot be adjusted to accommodate the conditions listed above, an external flow switch must be added to the plumbing system to ensure that the heater will not operate without the proper flow through the heat exchanger.
The following adjustment is for installations where the heater is above pool water level.
1. Be sure that all valves in the system are set to allow water flow through the heater. Start the filter pump.
2. Set the heater temperature above the actual temperature to call for heat. Turn the heater ON.
3. If the LCD shows a “LOW WATER FLOW” Alarm and red SERVICE light is present then the water pressure switch needs to be adjusted.
4. Remove the UltraTemp ETi™ Hybrid Heater’s left front panel and remove remaining right front panel. The water pressure switch is located in the water plumbing in the lower corner of the heater.
5. Slowly rotate the adjustment wheel on the water pressure switch in a counterclockwise direction until the “LOW WATER FLOW” Alarm and red SERVICE light vanish, time delay countdown will start.
6. Once the heater is running, turn off the filter pump. The heater should turn off immediately.
7. If the heater continues to operate when the filter pump is off, turn the adjustment wheel on the water pressure switch in a clockwise direction until the “LOW WATER FLOW” Alarm shows on the LCD, the red SERVICE light turns ON, and the heater stops.
8. Check the setting of the water pressure switch by starting and stopping the filter pump and checking the control panel and operation of the heater between each flow change.
9. If the water pressure switch cannot be adjusted to accommodate the conditions listed above, an external flow switch must be added to the plumbing system to ensure that the heater will not operate without the proper flow through the heat exchanger.
11
Gas Connections
The use of Flexible Gas Connectors (FLEX) is NOT
recommended unless they are properly sized according to the supplier recommendations for the heater rating. In all cases, the connectors must be bonded to the electrical service grounding point or, when provided, the lighting protection grounding point according to the latest edition of the National Fuel Gas Code.
Gas Line Installation
When sizing gas lines, calculate three (3) additional feet of straight pipe for every elbow used. When installing the gas line, avoid getting dirt, grease or other foreign material in the pipe as this may cause damage to the gas valve, which may result in heater failure.
The gas meter should be checked to make sure that it will supply enough gas to the heater and any other appliances that may be used on the same meter. The gas line from the meter will usually be of a larger size than the gas valve supplied with the heater. Therefore a reduction of the connecting gas pipe will be necessary. Make this reduction as close to the heater as possible.
The heater requires a gas supply of no less than 4 in. (10.2 cm) wc, and no more than 10.5 in. (27 cm) wc for natural gas (no more than 14 in. [36cm] for propane gas). Gas supply pressures outside of this range may result in improper burner operation. A minimum flowing or dynamic inlet pressure (while the heater is running) of 4 in (10.2 cm) wc is required to maintain input rating with no more than a 2 in. pressure drop between static and dynamic. The gas supply must be installed in accordance with the National Fuel Gas Code, ANSI Z223.1, or standard CSA B149.1, Natural Gas and Propane Installation Codes, as applicable and all applicable local codes. Install a manual shut-off valve and a sediment trap and union located outside the heater panels, see Figure 17 on the next page. Do not use a restrictive gas cock. The following minimum gas pipe sizes are recommended for natural gas supply piping, see Table 1 below. Check for compliance with local codes.
The heater and any other gas appliances must be disconnected from the gas supply piping system during any pressure testing on that system, (greater than ½ PSI). The heater and its gas connection must be leak tested before placing the heater in operation. Do not use flame to test the gas line. Use soapy water or another nonflammable method.
Note: A manual main shut-off valve for the heater must be installed externally.
Do NOT install the gas line union inside the heater cabinet.
This will void the warranty.
ENGLISH
Model # BTUs
220 110,000 50’ 80’ 125’ 250’ 450’ 600’ - - - - - -
3/4” 1” 1-1/4” 1-1/2” 2” 2-1/2”
NG PRO NG PRO NG PRO NG PRO NG PRO NG PRO
Table 1: Gas Pipe Sizing
MAXIMUM EQUIVALENT PIPE LENGTH (FT.)
Natural Gas at 1000 B.T.U. per Cubic Ft.
Propane Gas at 2500 B.T.U. per Cubic Ft.
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
12
Manual Shut-off Valve
Sediment Trap
Union
At least 9-in (23 cm)
At least 3-in (8 cm)
1-in (3 cm) Diameter or larger
(See Recommended Pipe Sizes Chart)
18–24-in of 3/4-in Gas line from Valve
Bell Reducer
Checking Gas Pressure Through Gas Control Valve
Risk of explosion if a unit burning propane gas is
installed in a pit or other low spot. Propane is heavier than air. Do not install the heater using propane in pits or other locations where gas might collect. Consult your local building code officials to determine installation requirements and specific installation restrictions of the heater relative to propane storage tanks and filling equipment. Installation must meet the requirements for the Standard for the Storage and Handling of Liquefied Petroleum Gases, CAN/CSA B149.2 (latest edition) or ANSI/NFPA 58 (latest edition). Consult local codes and fire protection authorities about specific installation restrictions.
The UltraTemp ETi™ Hybrid Heater is 100% factory tested, however Pentair recommends installations be tested to ensure proper combustion and optimal performance. During the initial startup, run the heater continuously for at least 10 minutes and then insert a probe connected to a combustion analyzer capable of reading CO and either CO2 or O2 into the exhaust vent. Wait for the reading to stabilize and confirm values are consistent with ranges in Table 2. If combustion values are outside of these ranges, contact technical support.
Measured Gas High Low
CO 150 -
CO
2
O
2
Air-Free CO 199 -
9.2 7.8
7.2 4.8
Table 2
This appliance is equipped with an unconventional gas control valve that is factory set with a manifold pressure of –.2” (–0.5cm) wc. Installation or service must be performed by a qualified installer, service agency, or the gas supplier. If this control valve is replaced, it must be replaced with an identical control.
The combination gas valve incorporates dual shut-off valves and a negative-pressure regulator. For proper operation, the regulated pressure at the outlet manifold of the valve must be –0.2” (–0.5cm) wc below the reference pressure at the blower mixer inlet, and the gas valve ‘VENT’ tap must be connected to the end cap air orifice as shown in Figure 16.
Do not attempt to adjust the gas input by adjusting the regulator setting. The correct gas regulator setting is required to maintain proper combustion and must NOT be altered.
To Gas
To Air Flow Switch
To Gas Valve Vent
To Air Flow Switch
Valve Vent
To Low Side of Differential Pressure Gauge
Vent
Pressure Tap
To High Side of Differential Pressure Gauge
Pressure Tap Inlet
Figure 16
Sediment Traps
Install a sediment trap and union located outside the heater panels in accordance with National code requirements. Do not use a restrictive gas cock. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet which can be removed for cleaning, as shown in Figure 17, or an other device recognized as an effective sediment trap. All gas piping should be tested after installation in accordance with local codes.
Figure 17
Gas Pressure Testing
The heater and its manual shut-off valve must be
disconnected from the gas supply during any pressure testing of that system at test pressures in excess of 1/2 psi (3.45 Kpa). Dissipate test pressure in the gas supply line before reconnecting the heater and its manual shut off valve to gas supply line. Failure to follow this procedure may damage the gas valve. Over pressurized gas valves are not covered by warranty. The heater and its gas connections shall be leak tested before placing the appliance in operation.
Before operating the heater, the heater and its gas connections must be leak tested. Do NOT use an open flame to test for leaks. Test all gas connections for leaks with soapy water or another non-flammable method.
The heater and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The heater must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply at test pressures equal to or less than 1/2 psig (3.5 kPa).
Note: Do not use threaded seal tape on gas line pipe thread. A pipe compound rated for use with natural and
propane gases is recommended. Apply sparingly only on male pipe ends, leaving the two end threads bare.
ULTRATEMP ETI™ Hybrid Heater Installation and User’s Guide
Loading...
+ 36 hidden pages