Pentair TRACETEK Operating Instructions Manual

TRACETEK
TRACETEK
H58511 08/09
Double flash anytime means low battery
FFS Probe Tester
1. Connect to test plug, Press and Hold RED test button:
Single Flash: Battery OK No Flash: Battery dead/unit damaged
2. Connect to FFS Probe, Press and Hold RED test buttion:
Single Flash: Wiring OK No Flash: Probe wiring/connector damaged
3. With FFS Probe still connected, Release RED test button:
No Flash: Probe OK Single Flash: Probe is in alarm mode-attempt reset
TEST DEVICE FOR TTFFS PROBE
Operating instructiOns
GENERAL INFORMATION
Please read these instructions and keep them in a safe place. These
FFS Probe Tester
1. Connect to test plug, Press and Hold RED test button: Single Flash: Battery OK No Flash: Battery dead/unit damaged
2. Connect to FFS Probe, Press and Hold RED test buttion: Single Flash: Wiring OK No Flash: Probe wiring/connector damaged
3. With FFS Probe still connected, Release RED test button: No Flash: Probe OK Single Flash: Probe is in alarm mode-attempt reset
H58511 08/09
Double flash anytime means low battery
TRACETEK
PRODUCT CHARACTERISTICS
Weight 0.3 kg (0.7 lb) nominal Light source 3 high intensity, high efficiency red LEDs Battery information 2 “AA” Alkaline Long Life Projected battery life 1 year – nominal Recommended battery replacement interval 1 year or whenever low battery signal is detected Duration of low battery signal Minimum 30 days at 20°C (68°F) Maximum ambient temperature 40°C (104°F) Minimum ambient temperature –20°C (–4°F)
instructions must be followed carefully to ensure proper operation. The TT-FFS Probe Tester is a battery powered device that provides the
capability of testing a TT-FFS Probe to determine whether it is functioning properly. Designed for use in ordinary areas, the TT-FFS Probe Tester is a hand held device used to evaluate the operational state of a TT-FFS Probe. It produces flashing signals with bright red LEDs that identify different operational conditions of the TT-FFS Probe.
The TT-FFS Probe Tester also monitors its battery voltage and produces a special DOUBLE Flash signal when the batteries need replacing.
The TT-FFS Probe Tester utilizes the same cable connection hardware as the TT-FFS Probe. When the TT-FFS Probe Tester is properly connected to a TT-FFS Probe, the TT-FFS Probe Tester may produce a SINGLE Flash signal, or a NO Flash signal, to indicate the operational state of the TT-FFS Probe. Follow the specific steps described in these Operating Instructions to determine the operational state of the TT-FFS Probe.
STORAGE
Keep the TT-FFS Probe Tester in a dry place that provides temperature stability in between uses. Avoid impacts that might damage the device.
Operating Instructions
Follow the guidelines discussed in the flow chart sequence on page 2 to evaluate the operational state of any TT-FFS Probe.
Note: A TT-FFS Probe with MC series metal connector can be con-
nected directly to the TT-FFS Probe Tester as shown in Photos 1 and 1A.
TRACETEK
FFS Probe Tester
1. Connect to test plug, Press and Hold RED test button: Single Flash: Battery OK No Flash: Battery dead/unit damaged
2. Connect to FFS Probe, Press and Hold RED test buttion:
Double flash anytime means low battery
Single Flash: Wiring OK No Flash: Probe wiring/connector damaged
3. With FFS Probe still connected, Release RED test button: No Flash: Probe OK Single Flash: Probe is in alarm mode-attempt reset
H58511 08/09
Photo 1
EN-TraceTekTTFFSprobetester-IM-H5849604/16
Photo 1A
Note: A TT-FFS Probe without metal connector (L series) can be
connected with the TT-FFS-ALLIGATOR4CLIP-MC cable end adaptor as shown in Photos 2 and 2A. The 4 colored alligator clip wires should be connected to the corresponding colored wires of the TT-FFS Probe.
TRACETEK
Double flash anytime means low battery
H58511 08/09
No Flash: Probe OK Single Flash: Probe is in alarm mode-attempt reset
3. With FFS Probe still connected, Release RED test button:
Single Flash: Wiring OK No Flash: Probe wiring/connector damaged
2. Connect to FFS Probe, Press and Hold RED test buttion:
Single Flash: Battery OK No Flash: Battery dead/unit damaged
1. Connect to test plug, Press and Hold RED test button:
FFS Probe Tester
Photo 2
Photo 2A
1 / 2THERMAL BUILDING SOLUTIONS
Connect TT-FFS Probe Tester test plug to cable end termination.
Are LEDs single
flashing each second?
No
Are LEDs double
flashing at 2 second
intervals?
Yes
Battery voltage is low, replace batteries.
Batteries are completely dead, or TT-FFS Probe Tester is damaged. Replace batteries and repeat this test step. If single flash test still fails, the TT-FFS Probe Tester must be replaced.
Press and hold RED test button.
No
Are LEDs single
flashing each second?
Batteries are OK. Release RED test button, connect TT-FFS Probe Tester to
No
TT-FFS Probe directly, or with alligator4 clip adapter.
Yes
Maintenance and Troubleshooting
Battery Powered Device
The TT-FFS Probe Tester is a powered by two “AA” Alkaline Long Life batteries.
Under normal conditions, when the test plug is connected to the cable end termination, the TT-FFS Probe Tester will not be flashing.
If the batteries reach a low voltage condition, the TT-FFS Probe Tester will DOUBLE Flash at 2 second interval continuously, and maintain the DOUBLE Flash signal for about 1 month before the battery voltage drops to an unusable level. It does not matter if the test plug is connected to the cable end termination, or to a TT-FFS Probe, the DOUBLE Flash signal will still be produced as long as the battery voltage is low.
Note: If the batteries are completely dead, the TT-FFS Probe Tester
will stop its DOUBLE Flash. The TT-FFS Probe Tester will not be able to signal the low battery condition, or properly evaluate the condition of a TT-FFS Probe.
Battery Lifetime
Two “AA” Alkaline Long Life batteries can be expected to provide service for nominally one year. However, under extreme high and low temperature conditions, battery service life may be reduced relative to nominal condi­tions. Battery lifetime also depends on how much flashing is required as part of the TT-FFS Probe evaluation testing.
TT-FFS Probe is in alarm condition. Attempt reset procedure per H58307 TT-FFS Probe care and cleaning instruction. DO NOT RETURN TT-FFS PROBE TO SERVICE.
Yes
No
TT-FFS Probe has internal wire damage or connector damage. DO NOT RETURN TT-FFS PROBE TO SERVICE. IT MUST BE REPLACED.
Press and hold RED test button.
Are LEDs single
flashing each second?
Yes
Release RED test button, TT-FFS Probe is good. Return to service or spares inventory.
Battery Replacement
• The battery replacement for the TT-FFS Probe Tester should be performed in a work shop or other nonhazardous location.
• Place a soft towel on the work surface.
• Position the TT-FFS Probe Tester face down, with the LEDs resting
on the soft towel.
• Loosen the four screws securing the back cover of the TT-FFS Probe Tester, being careful not to put excessive force on the unit, which might result in damage to the LEDs.
• Remove the back cover taking care to not lose any of the four screws. Now the black battery cover is visible in the interior of the TT-FFS Probe Tester.
• Loosen the small screw on the battery cover, then remove the battery cover.
• Remove the old batteries, replace with fresh batteries and verify batteries are installed correctly.
• Reposition the battery cover and tighten the small battery cover screw.
• Replace the back cover of the TT-FFS Probe Tester, and tighten the four screws evenly.
NORTH AMERICA
Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526
EuROpE, MIddlE EAsT, AfRICA
Tel: +32.16.213.511 Fax: +32.16.213.603
thermal.info@pentair.com Fax: +1.650.474.7215 thermal.info@pentair.com
Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.
© 2009-2016 Pentair.
EN-TraceTekTTFFSprobetester-IM-H5849604/16
• Dispose of the old batteries properly. Do not throw away the old batteries in a garbage receptacle; take them to your locally approved collection center for recycling.
WWW.PENTAIRTHERMAL.COM
AsIA pACIfIC
Tel: +86.21.2412.1688 Fax: +86.21.5426.2937 cn.thermal.info@pentair.com
lATIN AMERICA
Tel.: +1.713.868.4800 Fax: +1.713.868.2333 thermal.info@pentair.com
2 / 2THERMAL BUILDING SOLUTIONS