Pentair Raychem RTD-200 Installation Instructions Manual

RTD-200
WARNING:
RTD TempeRaTuRe sensoR foR ambienT sensing insTallaTion insTRucTions
DESCRIPTION
The RTD-200 is a three-wire platinum RTD (resistance­temperature-detector) typically used with electronic control systems that require accurate ambient temperature sensing. The RTD-200 comes with a 1/2” NPT fitting that installs to the appropriate conduit box. This allows mounting of the RTD in a typical ambient location. This also allows for splicing of RTD extension wire back to the controller.
TOOLS REQUIRED
None
ADDITIONAL MATERIALS REQUIRED
None
KIT CONTENTS
Qty Description
1 RTD temperature sensor with 1/2-in NPT fitting
SPECIFICATIONS
Sensor
Housing 316 stainless steel Dimensions 3 in (7.6 mm) length 1/4 in (6 mm)
diameter Accuracy ±0.3°F (0.2°C) Range –100°F to 300°F (–73°C to 149°C) Resistance 100 ohms +/– .25 ohm at 0°C
X=0.00385 ohms/ohm/°C
Extension Wires
Wire size (each of 3) 22 AWG Wire dielectric strength 600 volts Length 6 ft (1.8 m) Outer jacket Fluoropolymer Maximum exposure
temperature Sensor fitting 1/2-in NPT with sealing washer and nut
Approvals Approvals associated with control
300°F (149°C)
device, however not to be used in
Div. 1 areas.
This component is an electrical device. It must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the
Thermal Building & indusTrial heaT Tracing soluTions
installation instructions. Component approvals and performance are based on the use of s pecified parts only. Do not use substitute parts or vinyl electrical tape to make connections.
EN-RaychemRTD200-IM-H5699804/16
1 / 2
1 / 2
INSTALLATION
The RTD-200 can be terminated directly at the controller using the supplied 1/2 in NPT fitting. In this configuration, no additional extension wire is required.
RTD wired directly to controller
(Distance from sensor bulb to controller must be less than 4 ft)
Note: RTD should be placed in a typical ambient location.
1/2 in NPT fitting
4 ft or less
1/2 in Conduit
Electronic
controller
Terminate at
appropriate
terminal block
RTD200 WIRING
RTD wired with splice box
Note: RTD should be placed in
a typical ambient location.
1/2 in NPT fitting
1/2 in Conduit
Electrical Schematic of RTD
Connect the wires as shown.
Field Wiring
White
White (Common return)
Red
Red (Source)
Red
Red (Compensate)
Electronic
controller
Terminate at
appropriate
terminal block
RTD extension wire Splice box (provided by others)
NORTH AMERICA
Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526 Fax: +1.650.474.7711 thermal.info@pentair.com
Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.
© 2003-2016 Pentair. PN P000000095
EuROpE, MIddlE EAsT, AfRICA
Tel: +32.16.213.511 Fax: +32.16.213.603 thermal.info@pentair.com
Thermal Building & indusTrial heaT Tracing soluTions
AsIA pACIfIC
Tel: +86.21.2412.1688 Fax: +86.21.5426.2937 cn.thermal.info@pentair.com
EN-RaychemRTD200-IM-H5699804/16
WWW.PENTAIRTHERMAL.COM
lATIN AMERICA
Tel: +1.713.868.4800 Fax: +1.713.868.2333 thermal.info@pentair.com
2 / 2
Loading...