RTD-200
RTD TempeRaTuRe sensoR foR ambienT sensing insTallaTion insTRucTions
DESCRIPTION
The RTD-200 is a three-wire platinum RTD (resistancetemperature-detector) typically used with electronic control
systems that require accurate ambient temperature sensing.
The RTD-200 comes with a 1/2” NPT fitting that installs to the
appropriate conduit box. This allows mounting of the RTD in a
typical ambient location. This also allows for splicing of RTD
extension wire back to the controller.
TOOLS REQUIRED
None
ADDITIONAL MATERIALS REQUIRED
None
KIT CONTENTS
Qty Description
1 RTD temperature sensor with 1/2-in NPT fitting
SPECIFICATIONS
Sensor
Housing 316 stainless steel
Dimensions 3 in (7.6 mm) length 1/4 in (6 mm)
diameter
Accuracy ±0.3°F (0.2°C)
Range –100°F to 300°F (–73°C to 149°C)
Resistance 100 ohms +/– .25 ohm at 0°C
X=0.00385 ohms/ohm/°C
Extension Wires
Wire size (each of 3) 22 AWG
Wire dielectric strength 600 volts
Length 6 ft (1.8 m)
Outer jacket Fluoropolymer
Maximum exposure
temperature
Sensor fitting 1/2-in NPT with sealing washer and nut
Approvals Approvals associated with control
300°F (149°C)
device, however not to be used in
Div. 1 areas.
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all the
Thermal Building &
indusTrial heaT Tracing soluTions
installation instructions. Component approvals and performance
are based on the use of s pecified parts only. Do not use substitute
parts or vinyl electrical tape to make connections.
EN-RaychemRTD200-IM-H5699804/16
1 / 2
1 / 2

INSTALLATION
The RTD-200 can be terminated directly at the controller using
the supplied 1/2 in NPT fitting. In this configuration, no additional
extension wire is required.
RTD wired directly to controller
(Distance from sensor bulb to controller
must be less than 4 ft)
Note: RTD should be placed in
a typical ambient location.
1/2 in NPT
fitting
4 ft or less
1/2 in Conduit
Electronic
controller
Terminate at
appropriate
terminal block
RTD200 WIRING
RTD wired with splice box
Note: RTD should be placed in
a typical ambient location.
1/2 in NPT
fitting
1/2 in Conduit
Electrical Schematic of RTD
Connect the wires as shown.
Field Wiring
White
White (Common return)
Red
Red (Source)
Red
Red (Compensate)
Electronic
controller
Terminate at
appropriate
terminal block
RTD extension wire
Splice box
(provided by others)
NORTH AMERICA
Tel: +1.800.545.6258
Fax: +1.800.527.5703
Tel: +1.650.216.1526
Fax: +1.650.474.7711
thermal.info@pentair.com
Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change
specifications without prior notice.
© 2003-2016 Pentair. PN P000000095
EuROpE, MIddlE EAsT, AfRICA
Tel: +32.16.213.511
Fax: +32.16.213.603
thermal.info@pentair.com
Thermal Building &
indusTrial heaT Tracing soluTions
AsIA pACIfIC
Tel: +86.21.2412.1688
Fax: +86.21.5426.2937
cn.thermal.info@pentair.com
EN-RaychemRTD200-IM-H5699804/16
WWW.PENTAIRTHERMAL.COM
lATIN AMERICA
Tel: +1.713.868.4800
Fax: +1.713.868.2333
thermal.info@pentair.com
2 / 2